iecee-ctl eql 60502-4_ed3_201404
DESCRIPTION
IECEE-CTL EQL 60502-4_Ed3_2014TRANSCRIPT
IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT
COMMITTEE OF TESTING LABORATORIES
60502-4: 3.0Edition
April 2014
1/4
TESTING AND MEASURING EQUIPMENT/ALLOWED SUBCONTRACTING Power cables with extruded insulation and their accessories for rated voltages
from 1kV (Um=1,2kV) up to 30kV (Um=36kV) Part 4: Test requirements on accessories for cables for rated voltages
from 6kV (Um=7,2kV) up to 30kV (Um=36kV) IEC 60502-4 3.0 Edition (2010-12)
R=Required by Lab S=May be subcontracted
Clause Measurement/testing Testing / measuring equipment / material needed Subcontracting
Table 5,6,7,8,9,11,12
IEC 61442 cl.4
AC voltage test High voltage power supply (AC); suitable time meter. R
Table 5,6,7,8,9,11,12
IEC 61442 cl.5
DC voltage test DC voltage power supply; suitable time meter. R
Table 5,6,7,8,9,11,12
IEC 61442 cl.7
Partial discharge test
- at θt
- at ambient temperature
High voltage power supply(AC); Measuring circuit; Discharge calibrator; Double pulse generator;
Current heating system; thermocouple;
R
IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT
COMMITTEE OF TESTING LABORATORIES
60502-4: 3.0Edition
April 2014
2/4
Clause Measurement/testing Testing / measuring equipment / material needed Subcontracting
Table 5,6,7,8,9,11,12
IEC 61442 cl.6
Impulse voltage test
- at θt
- at ambient temperature
Current heating system; thermocouple;
Impulse voltage generator;
R
Table
5,6,8,9,11,12
IEC 61442 cl.9.2 and 9.3
Heating cycles voltage test
- in air
- under water
Current heating system; thermocouple;
Water tank; High voltage power supply (AC);
R
Table 5
IEC 61442 cl.9.4
Immersion test for outdoor termination Water tank;
Current heating system; thermocouple;
R
Table 5,6,8,9
IEC 61442 cl.10 and cl.11
Thermal short-circuit test
- screen
- conductor
Current heating system; thermocouple;
Short -circuit generator and control system.
S
Table 5,6,8,9
IEC 61442 cl.12
Dynamic short-circuit test Short-circuit generator and control system S
Table 5
IEC 61442 cl.13
Humidity test Single or three-phase a.c. voltage source.
Humidity test chamber equipped with spray nozzle or other form of
humidifier capable of discharging atomized water at a rate of (0.4±0.1)l/h/m3 volume;
R
IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT
COMMITTEE OF TESTING LABORATORIES
60502-4: 3.0Edition
April 2014
3/4
Clause Measurement/testing Testing / measuring equipment / material needed Subcontracting
spay water with the conductivity of (70±10)mS/m
Table 6
IEC 61442 cl.13
Salt fog test Single or three-phase a.c. voltage source.
Humidity test chamber equipped with spray nozzle or other form of
humidifier capable of discharging atomized water at a rate of (0.4±0.1)l/h/m3 volume;
spay water with the conductivity of (1600±200)mS/m
S
Table 8,9 Disconnect / connect Manual way R
Table 8
IEC 61442 cl.19
Operating eye test suitable tool to apply the tensile force to operating eye;
Suitable tool to apply the rotational torque to operating eye with clockwise direction and anti-clockwise direction.
R
Table 8
IEC 61442 cl.15
Screen resistance measurement Silver painter or wraparound electrode;
Oven; Timer;
Testing apparatus for measuring resistivity which power dissipation in test circuit shall not exceed 100mW.
R
Table 8
IEC 61442 cl.16
Screen leakage current 50mm×50mm metal foil; Resistance of 2000Ω;Millimeter; A.C.
power supply.
R
Table 8
IEC 61442 cl.17
Screen fault current initiation test Erosion resistance metal faulting rod of approximately 10mm in diameter; Copper wire of approximately 0.2mm in diameter;
Circuit a.c. voltage generator and control system which can initiate
S
IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT
COMMITTEE OF TESTING LABORATORIES
60502-4: 3.0Edition
April 2014
4/4
Clause Measurement/testing Testing / measuring equipment / material needed Subcontracting
the fault current and control voltage switched on and off;
Table 8
IEC 61442 cl.18
Operation force Conditional chamber (-20±2) ℃; Timer; Measurement force
equipment.
R
Table 8
IEC 61442 cl.20
Capacitive test point performance Differential bridge or other capacitance measurement device. R
Table 5,6,7,8,9,11,12
Examination By naked eyes. R