Installation / ᅝ㺱ᮍ⊩ Built-in display flush monuting i3 / 3 2 iF / F 2 Fault History ᶹⳟᬙ䱰ሹ⅋ Automatically-scrolling display 䳏⌕㞾ᕾ⪄ᣛ⼎㛑 Fault history check : Pressing the ESC button more than 5sec, it displays the latest fault cause and the fault current or fault phase. Continuing to press DN button, you can see the current of L1(R),L2(S),L3(T),(GR) in turn. press the DN button again to check the previous fault continually. In the latest fault display, the 100% LED of bargraph lights on and two LEDs of 95%,100% lights on for the second fault display, three LEDs of 90%,95%,100% lights on for the oldest fault display. When you press the ESC button in this mode, it returns to the normal current display mode. The oldest fault record is over written when the number of fault to record exceeds three. TFD TFD TFD - - - "NQ TFD - - - "NQ TFD - - - "NQ TFD Once the SET button is pressed during a product operation, the auto-scrolling is de-activated so that the display does NOT change. Another SET press will turn the current on display to the next phase one. (e.g. If you press the SET button with L1 current displayed, the display will show L2 current.) To re-activate the auto-scrolling, press the ESC button.In manually-scrolling display, you can access each setting in a circular manner as pressing UP or DN. 3 2 ≦䗮咲 Models with ‘2’ at the end do NOT include communication terminal. 72 56.3 74.5 53.3 91.3 70 22.5 22.5 3- 12 83.8 102.4 108 126.7 108 45.3 126.7 82 95 82 4.5 95 65 3- 12 82 4.5 95 4.5 W H T 72 64 56.3 21.4 21.4 70 21.4 21.4 6-M4 70 W H T 56.3 74.5 53.3 91.3 70 22.5 22.5 3- 12 83.8 108 108 45.3 82 95 82 4.5 95 3- 12 82 4.5 95 4.5 56.3 21.4 21.4 70 21.4 21.4 6-M4 70 13.4 28 Dimensions / ᔶሎᇌ Description Description of terminal ッᄤ䜡㕂೪ Setting 䀁㕂 Press UP or DN to find a menu item. Refer to the User's guide for detailed menu description. ᣝ83'1ᣝ䟩՚ᶹᡒ㽕䀁㕂ⱘ㦰DŽ㦰䂟গ㗗䀁㕂䷚ᑣঞ乃⼎䁾ᯢ ᣝϔ6(7ᣝ䟩ˈ㑐䳏ⱐ䗕䭟䀁㕂㰳 ℸᰖˈ㽕䀁㕂ⱘᄫ᭛ᄫ䭟䭗⟡DŽ䗭㸼ᯢҹ䘆㸠䀁㕂DŽ In the menu mode, pressing SET makes blinking. A parameter and allows modifying paramete. Press “UP” or “DN” key to set the parameter while blinking. ᣝ83'1ᣝ䟩՚ᶹᡒ㽕䀁㕂ⱘᄫ᭛ᄫ 乃⼎㽕䀁㕂ⱘ᭛ᄫᄫᕠˈᣝ6(7ᣝ䟩ᄬ㑐䳏Ϟ 䭗⟡ⱘ᭛ᄫᄫϡݡ䭗⟡ˈ㸼⼎Ꮖᄬ䀁㕂 ᣝ(6&ᣝ䟩䖨ಲ䳏⌕乃⼎ᓣDŽ ᅠ៤䀁㕂ᕠˈՓϡᣝ(6&ᣝ䟩ˈ㍧䘢⾦ᕠˈг㞾䖨ಲ䳏⌕乃⼎ᓣ Press “SET” again then blinking is stopped and it will be stored the parameter in the non-volatile menorywhile blinking. To return normal display mode, either press “ESC” or wait for 50secs of the time elapsed from set menu D C C B B Trip Cause Indication ॳᣛ⼎ 乃⼎䳏⌕ᕾ⪄ⱘᚙ⊕ϟˈ䭋ᣝ(6&ᣝ䥉⾦ҹϞˈህ乃⼎䖥ᬙ䱰ॳঞ䳏⌕䳏Ⳍˈ䗭ᰖݡᣝ'1ᣝ䥉 ↣ᣝ'1ᣝ䥉ህҹ5Ⳍˈ6Ⳍˈ7Ⳍ䳏⌕ⱘ䷚ᑣ乃⼎ˈབᵰ㽕⺎䁡䘢এᬙ䱰ሹ⅋ˈݡᣝ'1ᣝ䥉ˈህ乃⼎ᬙ䱰㿞ᙃ ᇡᮐ乃⼎ᬙ䱰ᙃˈ乃⼎䖥ᆍᰖˈህ҂䍋Bargraphⱘˈ㢹乃⼎Пⱘᬙ䱰ᆍˈህ҂䍋 ן/('➜ˈݡ乃⼎ҹⱘᬙ䱰ᆍᰖˈህ҂䍋ˈϝ('➜ ᶹⳟᬙ䱰ሹ⅋ПЁˈᣝ(6&ᣝ䥉ˈህ䔝⚎䳏⌕ᕾ⪄ˈ䗭ᰖ83'1ᣝ䥉ˈ㢹乃⼎ᬙ䱰䳏⌕ ህᎺ䙞/// /('➜Ё҂䍋Ⳍ䮰ⱘ/('➜ བᵰ乃⼎Ҫᬙ䱰ᙃᰖˈህ乃⼎ᬙ䱰䷙Ⳃᙃ ᬙ䱰ሹ⅋ᄬϝˈן㢹䍙䘢ϝˈןЙⱘᬙ䱰ᆍህ㞾߾䰸 (PL) Phase Loss Tripped by current phase-loss on L1 phase /Ⳍ䳏⌕᧡༅ᓩ䍋ⱘ䏇䭬 (Sc) stall at starting Ё䥪ᅮ Tripped by 45A current on L1 phase that detects a locked or stalled rotor during start state ЁᣝϔVHW䥉ˈህ乃⼎ᕾ⪄ˈҷ᳓㞾ᕾ⪄ˈᕾ⪄ᓣ↣ᣝVHW䥉ˈᣝབϞ䷚ᑣᕾ⪄ˈ ᠔ҹᖙ㽕ᰖ䥪ᅮᶤϔןⳌⱘ䳏⌕䳏⌕ˈ䘆㸠䲚Ёㅵ⧚ˈ㢹ᣝϔ(6&䥉ˈህಲᕾ⪄ᓣˈ ᕾ⪄ᣛ⼎ᓣᣝ83'1䥉ˈህ䔝⚎ן䀁ᅮᓣ ⢔ϟ/ⳌԡϞ⁶␀$ⱘ䥪ᅮ䳏⌕㗠䏇䭬 (JA) stall at running 䘟㸠Ё䥪ᅮ Tripped by 35A current on L2 phase that detects a locked rotor during run state 䘟㸠⢔ϟ/ⳌԡϞ⁶␀$ⱘ䥪ᅮ䳏⌕㗠䏇䭬 Tripped by over-current, the maximum phase was L1 and 3.5A detected 㹿䘢䳏⌕䏇䭬ˈⳌԡ⚎/Ϻ⁶ᶹߎњ$ (oc) Over Current 䘢䳏⌕ Fault History Initial State ⅋ⱘ⢔˄⛵䏇䭬⢔˅ None Fault ࢩ⛵Auto Reset is not possible because the number of times of activation limit is exceeded within 30 minutes 䍙䘢Ꮖ䀁㕂ⱘߚ䧬ଳ㗠⛵⊩ݡactivation limit Tripped by self-test completion 7HVWᅠ៤㗠䏇䭬 Test Complete 7HVWᅠ៤ (uc) Under Current Ԣ⬉⌕ Tripped by 1.5A under-current during run state 䘟㸠⢔ϟ/Ⳍԡ⁶␀$ⱘԢ䳏⌕㗠䏇䭬 (Ub) Unbalance ϡᑇ㸵 Tripped by current phase imbalance on L3 phase. /Ⳍ䳏⌕ϡᑇ㸵㗠䏇䭬 (RP) Reverse Phase 䗚Ⳍ Tripped because the current phases of a 3-phase motor are phase reversal during start state Ё⁶ᶹ䳏⌕ডⳌ㗠䏇䭬 For the trunk cable use a single, shielded, twisted pair cable and at least 3rd conductor. Keep the Modbus cable away from the power cables (at least 30 cm - 11.8in).Create crossovers of the Modbus cable and the power cables at right angles, if nessary. Place at line terminator at 120 each end of the bus to avoid malfuntions on the communication bus. Line terminator cabling is as follows ⚎њ䅋ষˈ䂟Փ⫼ሣ㬑䲭㌲㎮ Shielded Twisted Conductors Modbus䳏㑰㟛䳏㎮াᇥ㽕㟇ᇥ㽕ᣕFP㣅য় ᖙ㽕ᰖˈՓModbus䳏㑰㟛䳏㎮ⳌѦൖⳈ 䳏䏃㌖ッ˄Line Terminator˅ⱘ㎮ᮍ⊩བϟ Authorized technical engineers only for installation, maintanance or repair. ᠔䳏ⱘᅝ㺱㎁䅋ᖙ䷜⬅⥆ᕫ䁡䄝ⱘ䳏⇷ᡔᎹ᪡ᅠ៤ Check periodically whether our product works properly by pressing and holding the test button. ⚎њ䄝ℷᐌˈ䂟ᅮᰖ⺎䁡⫶ક18 months warranty from the date of shipment. 緩립열劉搾넏補Е蔬밤使涉3:늦朶리밤댩쯔뒏졺홶쳆뤼툤뼼눌0 Adjust the settings according to the electric characteristics of a motor, an inappropriate setting may cause permanent damage on the motor. 굶넫鬚끽켒礫灸펱捷잣礫補ⓕ얷쾤켒礫墮홟碗끀滴錮0 With a device using SCRs to control electricity such as an inverter set 'LFd YE' or contact customer service center for more information. 搾혷킲톱豌UET棧봐툆욟0 俚헥Hidden menu켒礫㈜LFd YE㈜豌쿎옰塔립열콒쯔 External filter should be installed to reduce harmonics in an environment where the AC power contains excessive harmonic than IEC standard. No installation in the site may result in accuracy problem, abnormal operation and mal-function. 헥搾홵욈楕KGE칆礫굶ベ뙄댩擧ベⓕV딪嚼ボ귱톱 耽V딪귱톱墮표껪뒏졺ⓕ얘본憊呪숵뒏뒌쾤샴꾕0 EOCR-3DM2 / FDM2 / i3DM / iFDM / i3M420 / iFM420 HAZARD OF ELECTRIC SHOCK, EXPLOSION,OR ARC FLASH Disconnect all power before servicing equipment. Failure to follow these instructions will result in death or serious injury. 繰ⅰ낃껧豌甥썩 헥[눌켒딪в붕ⓕ쿎箚謠楕『0 얷횢쌰홖겊쾫戚ⓕ 불엘썢墮旒쒃팼r뙄골풏떵簾뒆쒂B겝0 DANGER / D-TIME O-TIME U-TIME UC Set AL Set OC Set Sc Set Lc Set Motor starting time Motor Start SC-TIME SC Trip LC Trip UC Trip OC Trip At start-up The trip is deactivated until the over-current run time is longer than O-time. 꾃葯럤횘補ⓕ矩幣☜켒礫 O-Time 捷럮 불ボ샴꾕 Changing an item in the Special Menu makes the device operate differently from the standard characteristic. Consult with technical service on the change. 矩눌重娩搾콪윭취뙄뚸ⓕ뒏졺샴꾕累쒗o"애榛ボ옥ⓕ표⊫헥눌重붕쿎섀蘇쒗塔립열슲쀋홶쳆룵쾋0 Hidden Menu Press ESC and SET together over 5s to enter the Hidden Menu as follows / 옥捷贇GUE잣UGV7멢굶ベⓕ릖Hidden Menu旁汥鉉朽槕艼儱薌錧 Description Setting Range Toggle display of FW version(EOCR, PDM), Reference Code 懲鄪儱煮每踄涑*GQET尤RFO+崎鴀惚改鍜 FW version, Reference Code q踄涑荒鴀惚改鍜 yE, no 釖慔紅鞠悤敵板 Reset to Factory Setting Item 1L1 3L2 5L3 2T1 4T2 6T3 Avoid ZCT secondary grounding ZCT secondary shielding recommended Keep the PDM Display unit communication cable away from the main power and control power line cable. 挨黠\EV听媞有沸彽策 怭艢稅甮\EV 4媞有麃豌錇鷭 RFO悤肥底鷭兌夯蕚虫溲崎忥貞溲蠨估μ Only available when the PDM is connected. PDM嚯彽估陔�鍼簕 栜裟悤敵板 Select Max D-Time valueD-Time 200, 250, 300, 350, 400, 450, 500, 600 棞栜裟悤敵板 Select Max CT ratioCT 800, 3000 Ld, t, S, r 膢意阢席軍講莠 on-site manual calibration 30, 50, 80, 120 ot 栜裟悤敵板 Select Max ot, utot, ut 30, 50, 80, 120 ut 栜裟悤敵板 Select Max ot, utot, ut 軍講勦溒板 User-Calibration User- defined / 麃灱韦拱板 PT100煸講咭惎錧 PT Temperature compensation 0.1 °C 4-20噠軥->4mA 韦拱咭惎錧 4-20mA Current loop input --> Calibration for 4mA 0.01mA 4-20噠軥->20mA 韦拱咭惎錧 4-20mA Current loop input --> Calibration for 20mA 0.1mA User- defined / 麃灱韦拱板 4-20mA 韦紅軍講莠 4 - 20mA Output Calibration manu A D C B L1 L2 L3 Volt / x10 Amp / % / °C sec / kW / kWh 65 70 75 80 85 90 95 100% SET ESC UP DN VJ18232 PDM yE, no 遻黺羜檯㫲壴 External WatchDog 2 sec ~ 10sec (Enhanced Version Only) Fault duration by detecting the breakdown of the power protection circuit Temperature compensation 0.1 °C Tripped when PDM communication status is lost 湮RFO底噆囑聿珆だ栀 PDM Loss RFO底聿珆 Tripped when Modbus network communication status is lost 湮Oqfdwu欈撑底噆囑珆だ栀 Network Loss 欈撑底聿珆 Humidity compensation 1 % i3 / 3 2 iF / F 2 Diagnosis / 儱珆 Major Internal Fault 拯鍦巏鬗柜 Operated by diagnosing EEPROM memory error If the fault persists after the power cycle, replace the product. 珆GGRTQO封嬋廊墚燝餽席佯 鎄昮娀佯溲餽戒蕛鳿郝羛理郎盖妍昑鴀惚 EEPROM error GGRTQO墚燝 Tripped by detecting the breakdown of the power protection circuit.In this case, please replace the product 湮趹胵衫溲幸撑臌沴だ栀 盖妍昑鴀惚 (Only Enhanced Version) 溲幸撑臌沴 Power LED is flashing fastly Rqygt NGF栭蟾後 FND display is flashing fastly HPF栭蟾後 Operated by diagnosing system faults internally If the fault persists after power cycle, replace the product. 珆拯鍦巏鬗柜だ席佯 鎄昮娀佯溲餽戒蕛鳿郝羛理郎 盖妍昑鴀惚 Notice. Blade terminal width: less than 2.3mm. Cable: less than 2.0 SQMM. Control Power Communication Control Power NO output AL NO output AL NO/NC output OL NO/NC output OL NO/NC output OL 3DM2 / FDM2 i3DM / iFDM Control Power 4~20mA output Communication i3M420 / iFM420 A1 A2 07 08 95 96 97 98 V- D1 D0 S AL OL OL COMM A1 A2 07 08 95 96 97 98 AL OL OL A1 A2 95 96 97 98 V- D1 D0 S OL OL COMM 4~20mA RCPGN ( FKP TCKN V[RG OQWPVKPI JQNG UK\G RCPGN ( FKP TCKN V[RG OQWPVKPI JQNG UK\G OQWPVKPI JQNG UK\G 悤敵溲幸撑栀陔 煸講叠洭莠 趔講叠洭莠 RD12-03-001_ R2 2019.08 3090-3XX02-02 3090-3XX02-02

Upload: others

Post on 25-Oct-2021

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: iFM420 i3M420 iFDM i3DM FDM2 EOCR-3DM2 Installation / EL

Installation /

Built-in display flush monuting i3 / 3 2 iF / F 2

Fault History

Automatically-scrolling display

Fault history check : Pressing the ESC button more than 5sec, it displays the latest fault cause and the fault current or fault phase.

Continuing to press DN button, you can see the current of L1(R),L2(S),L3(T),(GR) in turn.

press the DN button again to check the previous fault continually.

In the latest fault display, the 100% LED of bargraph lights on and two LEDs of 95%,100% lights on for the second fault display,

three LEDs of 90%,95%,100% lights on for the oldest fault display. When you press the ESC button in this mode,

it returns to the normal current display mode. The oldest fault record is over written when the number of fault to record exceeds three.

Once the SET button is pressed during a product operation,

the auto-scrolling is de-activated so that the display does NOT change.

Another SET press will turn the current on display to the next phase one.

(e.g. If you press the SET button with L1 current displayed, the display will show L2 current.)

To re-activate the auto-scrolling, press the ESC button.In manually-scrolling display,

you can access each setting in a circular manner as pressing UP or DN.

3 2

Models with ‘2’ at the end do NOT include communication terminal.

72

56.3 74.5

53.3

91.3

70

22.5 22.5 3- 12

83.8102.4

108126.7

10845.3

126.7

82

95

82

4.5

95

65

3- 12

82

4.5

95

4.5

W

H

T

72

64 56.3

21.4

21.4

70

21.4 21.46-M4

70

W

H

T

56.3 74.5

53.3

91.3

70

22.5 22.5 3- 12

83.8

108

10845.3 82

95

82

4.5

95

3- 12

82

4.5

95

4.5

56.3

21.4

21.4

70

21.4 21.46-M4

70

13.4

28

Dimensions /

Description

Description of terminal

Setting

Press UP or DN to find a menu item.

Refer to the User's guide for detailed menu description.

In the menu mode, pressing SET makes blinking.

A parameter and allows modifying paramete.

Press “UP” or “DN” key to set the parameter while blinking.

Press “SET” again then blinking is stopped and it will be stored the parameter

in the non-volatile menorywhile blinking.

To return normal display mode,

either press “ESC” or wait for 50secs of the time elapsed from set menuD

C

C

B

B

Trip Cause Indication

Bargraph

(PL)Phase Loss

Tripped by current phase-loss on L1 phase

(Sc)stall at starting

Tripped by 45A current on L1 phase that detects a locked or

stalled rotor during start state

(JA)stall at running

Tripped by 35A current on L2 phase that detects a locked rotor

during run state

Tripped by over-current,

the maximum phase was L1 and 3.5A detected

(oc)Over Current

Fault History Initial State None Fault

Auto Reset is not possible because the number of times of

activation limit is exceeded within 30 minutesactivation limit

Tripped by self-test completionTest Complete

(uc)Under Current

Tripped by 1.5A under-current during run state

(Ub)Unbalance

Tripped by current phase imbalance on L3 phase.

(RP)Reverse Phase

Tripped because the current phases of a 3-phase motor are

phase reversal during start state

For the trunk cable use a single, shielded, twisted pair cable and at least 3rd conductor.Keep the Modbus cable away from the power cables(at least 30 cm - 11.8in).Create crossovers of the Modbus cable and the power cables at right angles, if nessary.Place at line terminator at 120 each end of the bus to avoid malfuntions on the communication bus. Line terminator cabling is as follows

Shielded Twisted ConductorsModbus

ModbusLine Terminator

Authorized technical engineers only for installation, maintanance or repair.

Check periodically whether our product works properly by pressing and holding the test button.

18 months warranty from the date of shipment.

Adjust the settings according to the electric characteristics of a motor, an inappropriate setting may cause permanent damage on the motor.

With a device using SCRs to control electricity such as an inverter set 'LFd YE' or contact customer service center for more information.

Hidden menu LFd YE

External filter should be installed to reduce harmonics in an environment where the AC power contains excessive harmonic than IEC standard.No installation in the site may result in accuracy problem, abnormal operation and mal-function.

EOCR-3DM2 / FDM2 / i3DM / iFDM / i3M420 / iFM420

HAZARD OF ELECTRIC SHOCK,EXPLOSION,OR ARC FLASHDisconnect all power before servicing equipment.

Failure to follow these instructions will result in death or serious injury.

DANGER

D-TIME O-TIMEU-TIME

UC Set

AL Set

OC Set

Sc Set

Lc Set

Motor starting time

Motor Start

SC-TIME

SC TripLC Trip

UC Trip

OC TripAt start-up

The trip is deactivated until the over-current run time is longer than O-time.

O-Time

Changing an item in the Special Menu makes the device operate differently from the standard characteristic. Consult with technical service on the change.

Hidden MenuPress ESC and SET together over 5s to enter the Hidden Menu as follows /

Hidden Menu,

Description Setting Range

Toggle display of FW version(EOCR, PDM), Reference CodeFW version, Reference Code

yE, noReset to Factory Setting

Item

1L1 3L2

5L3

2T1 4T2

6T3

Avoid ZCT secondary groundingZCT secondary shielding recommendedKeep the PDM Display unit communication cable away from the main power and control power line cable.

Only available when the PDM is connected.PDM

Select Max D-Time valueD-Time200, 250, 300, 350, 400, 450, 500, 600

Select Max CT ratioCT 800, 3000

Ld, t, S, ron-site manual calibration

30, 50, 80, 120ot Select Max ot, utot, ut

30, 50, 80, 120ut Select Max ot, utot, ut

User Calibration User- defined

PT100PT Temperature compensation 0.1 °C

4-20 ->4mA 4-20mA Current loop input --> Calibration for 4mA

0.01mA

4-20 ->20mA 4-20mA Current loop input --> Calibration for 20mA

0.1mA

User- defined 4-20mA 4 - 20mA Output Calibration manu

A

D

C

B

L1

L2

L3 Volt / x10

Amp / % / °C

sec / kW / kWh

65 70 75 80 85 90 95 100%

SET

ESCUP

DN

VJ18232

PDM

yE, noExternal WatchDog

2 sec ~ 10sec(Enhanced Version Only)

Fault duration by detecting the breakdown of the power protection circuit

Temperature compensation 0.1 °C

Tripped when PDM communication status is lostPDM Loss

Tripped when Modbus network communication status is lostNetwork Loss

Humidity compensation 1 %

i3 / 3 2

iF / F 2

Diagnosis

Major Internal Fault

Operated by diagnosing EEPROM memory error

If the fault persists after the power cycle, replace the product.EEPROM error

Tripped by detecting the breakdown of the power

protection circuit.In this case, please replace the product(Only

Enhanced Version)

Power LED is flashing fastly

FND display is flashing fastly

Operated by diagnosing system

faults internally If the fault persists after

power cycle, replace the product.

Notice.Blade terminal width: less than 2.3 mm.Cable: less than 2.0 SQMM.

Control PowerCommunication

Control Power

NO output AL

NO output AL

NO/NC output OL

NO/NC output OL

NO/NC output OL

3DM2 / FDM2

i3DM / iFDM

Control Power 4~20mA output

Communication

i3M420 / iFM420

A1 A2 07 08 95 96 97 98 V- D1 D0 S

AL OL OL COMM

A1 A2 07 08 95 96 97 98

AL OL OL

A1 A2 95 96 97 98 V- D1 D0 S

OL OL COMM4~20mA

RD12-03-001_ R2 2019.08 3090-3XX02-02

3090-3XX02-02

Page 2: iFM420 i3M420 iFDM i3DM FDM2 EOCR-3DM2 Installation / EL

000 ‐999(000 for no password setting)

3ph, 1ph

Non, 2t, 5tct:10~3000

On, oFF

On, oFF

On, oFF

no, dE, In, th(none, definite, inverse, thermal inverse)

dE: 0.5 ‐ 80In/th: 0.5 - 32

0 ‐ 200

0.2 ‐ 30

oFF, 0.5 ‐ (oc -1)

0.5 ‐ 30

Time-current characteristic

System fundamental frequency50,60

Reversed phase detection

Phase loss

Alert threshold (% of oc)

Over current threshold

Starting delay time

Over current duration

Unbalance threshold

Stall threshold (multiples of oc)

Jam threshold (multiples of oc)

Jam fault duration

Under current threshold

Under current duration

Alert output type

4-20 Output range threshold4-20

0.5 ‐ 5

oFF, 10 ‐ 50

1 ‐ 10

0.2 ‐ 10

no, A, F, H, to, uc, IH

no, A, F, H, to, uc, tE,hU,Pt,42,IHConnected PDM

50 ‐ 100 (ALo F H Selected)

0.5 - 80

H-r ( Manual reset only )E-r ( Electric, Manual, Comm reset ) A-r ( Auto, Electric, Manual, Comm reset )

0.5 ‐ 20n

oFF,1 - 5

0 ‐ 99999

0 ‐ 99999

0 ‐ 9990

1 ‐ 247

Reset type(manual,Electric,auto)

Auto reset timer

MODE Description Range MODE Description Range

1 - 999

1.2, 2.4, 4.8, 9.6, 19.2, 38.4, auto

Baud rate(bps)

Communication Loss operating time

Output test

End of output test

Unbalance duration

Restart limitation

Total running hour

Running hour

Communication (Modbus slave address)

C

B

D

E

Default Default

000

3ph

dE

non

60

oFF

oFF

oFF

5

5

5

5

on

2

50

5

4

4

5

no

50

10

E-r

5

oFF

trh

rh

oFF

oFF

1

192

Eun

Press RESET to reset it from a trip after the test is complete.

3sec 10sec

Password

Phase loss duration

Set/Reset Fail safe modeFail Safe

Test is Not applicable under normal operation

Wiring /

2020 - 1000

51 - 30

Harmonics Menu

L1 Phase - Current Total Harmonic Distortion

L1 Phase - Fundamental Frequency Current

L2 Phase - Fundamental Frequency Current

L3 Phase - Fundamental Frequency Current

Alarm Level for maximum Current THD of Three phases

L2 Phase - Current Total Harmonic Distortion

L3 Phase - Current Total Harmonic Distortion

yE, no

yE, no

no

no

Enable disconnection detection of sPDMsPDM

Select Enable Low Frequency Detection

G

G

1st~ 8th : 5% 9th~ 16th : 10%

Select 3 phase or single phase

External CT ratio,select cuS for separate configuration of primary, secondary and multiple passes

Timeout alarm threshold of running hour

3DM2 / FDM2

L1 L2 L3

MCCB

KM1

M3~

CT

+ / ~

+ / ~

Start

Stop

KM1

KM1

07

07

08

08

95

95

96

96

98

98

A1

A1

A2

A2

97

97

Control Power Fail safe OFF

i3DM / iFDM

L1 L2 L3

MCCB

KM1

M3~

CT

+ / ~

+ / ~

Start

Stop

KM1

KM1

07

07

08

08

95

95

96

96

98

98

A1

A1

A2

A2

97

97

D0

D0

SSD1

D1

V-

V-

Control Power

RS485

Fail safe OFF

L1 L2 L3

MCCB

KM1

M3~

CT

i3M420 / iFM420

95

95

96

96

98

98

A1

A1

A2

A2

97

97 ++ --

+ / ~

+ / ~

Start

Stop

KM1

KM1

D0

D0

SSD1

D1

V-

V-

Control Power

RS485

Fail safe OFF

Alarm duration for maximum Current THD of Three phases

Configuration Menu

D

G

E

C

B

1) Applicable for 3DM2 / FDM2 / i3DM / iFDM

2) Applicable for i3M420 / iFM420

3) Applicable for i3DM / iFDM / i3M420 / iFM420

4) Applicable for FDM2 / iFDM / iFM420

Harmonics Menu G

non, no1, Eun(even), oddCommunication Paritypr:no1 -> stop bit = 2 pr:non, pr:Eun, pr:odd -> stop bit = 1

2~8times of oc setting if Sc x OC doesn’t exceed 250A

1.5~8times of oc setting if JA x OC doesn’t exceed 250A