igs-nt gecon datasheet 2009-07 cplegecn

Upload: sdiaman

Post on 03-Apr-2018

233 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Igs-nt Gecon Datasheet 2009-07 Cplegecn

    1/6

    IG/IS-NT GeCon

    GENERATOR CONTROLLER FOR MARINE AND

    LAND-BASED APPLICATIONS

    DescriptionIG/IS-NT GeCon provides comprehensive

    generator protection and control for

    single or multiple gen-sets based on

    field proven InteliGenNT and InteliSysNT

    platforms. Special configurations

    optimized for use in marine and

    land-based installations allow customers

    to select a tailored solution for their

    application with the option of modified

    options for critical applications.

    A built-in synchronizer and digital

    isochronous load sharer allow a

    total integrated solution for gen-sets

    in standby, island parallel or mains

    parallel. Native cooperation of up to

    32 gen-sets is a standard feature.

    A powerful graphic display with

    user-friendly controls allows any

    user whatever their ability to find the

    information they need. Arrangement

    with redundant controllers is

    available for critical applications.

    The hot standby controller takes over

    generator protection and control in

    case of failure of the main controller.

    BenefitsExcellent configurability enables users

    to customise to the needs of their

    application

    Choice of communication options

    ensures easy remote supervising and

    servicing

    Optional redundant hot standby

    controller guarantees uninterrupted

    generator control in case of failure of

    the primary controller

    Built-in PLC functions remove the need

    for an external PLC controller

    Perfect price/performance ratio

    Gen-set performance log for easy

    problem tracing

    ComAp products meet the highest standards, with

    every stage of production undertaken in accordance

    with the ISO certification obt ained in 1998.

    ComAp is a member of AMPS

    (The Association of Manufacturers

    of Power generating Systems).

    CREATIVE ENGINEERING

  • 7/28/2019 Igs-nt Gecon Datasheet 2009-07 Cplegecn

    2/6

    PCMODE

    M

    IS-BIN16/8

    IS-AIN8- IN

    IGS-PTM

    IGL-RA15

    M

    - A1

    I-AOUT8

    IN16/I -

    1p

    h

    3p

    h

    3p

    h

    Genera

    torC

    .B.C

    ontro

    l

    12BINARY

    OUTPUTS

    (OPEN

    COLLECTOR)

    3ANALOG

    INPUTS

    GENERATO

    RIG-NT-Marin

    e

    EAR

    TH

    FAULT

    CU

    RRE

    NT

    AV

    RiO

    UT

    INTER-

    CONTROLLER

    &MONITORIN

    G

    CAN2

    RS232(1)

    INTERFACE

    RS485(1)

    INTERFACE

    12BINARYIN

    PUTS

    EXTENSION

    MODULES

    CAN1

    POWERSUP

    PLY

    8TO36VDC

    + -

    CU

    R

    REN

    T

    VO

    LTAG

    E

    MEASU

    R

    EMEN

    T

    12

    BUS

    IG-IB

    I-LB

    IG-IB

    GENERATOR

    DIESEL/GASENGIN

    E

    ENGINE

    CONTROLLERNGI

    ECU

    MODBUS

    TO

    OTH

    ER

    GEN

    ER

    ATO

    R

    CO

    NTR

    OLLE

    RS

    SHIPORBUIL

    DING

    MANAGEMENT

    LOAD

    IG-MTUT

    A

    IG-MTU

    h

    U

    A

    Aonlyfor

    Marine

    AVRi

    General featuresPanel mounted device

    Dimensions 180 120 mm

    (front panel)

    Sealed to IP65 (front panel)

    Event-based history with configurable

    list of stored values up to 500 records

    deep

    Integrated standard PLC programmable

    functions

    Inputs and outputs3 U generator 400 V ph-ph

    3 U bus 400 V ph-ph

    3 I generator CT 5 A

    1 I earth/I bus CT 5 A

    12 binary inputs

    12 binary outputs

    3 analog inputs

    1 RS232/485

    InteliGenNT GeCon

    InteliGenNT GeCon, InteliSysNT GeConGenerator monitoring

    and controlIndependent engine controller

    (e.g. ID-DCU) is required

    Generator measurement: U, I, Hz, kW,

    kVAr, kVA, PF, kWh, kVAhr

    Bus/Mains measurement: U, I, Hz, kW,

    kVAr, kVA, PF

    Manual, Semi-auto and Automatic

    operational modes

    Automatic VAr sharing and Load

    sharing in all modes

    Automatic synchronizing and Voltage

    control in Auto and Semi-auto modes

    Power management: kW, kVA or %

    load based in Auto mode

    Baseload, Import/Export, Peak

    shaving for land based applications

    All binary/analog inputs are

    configurable for various protection

    types

    Generator protections3 phase generator over/under

    frequency

    Generator overcurrent and IDMT

    overcurrent

    Additional 160 user configurable

    generator and bus/mains protections

    Communication

    and PC toolsRS232/RS485 interface with Modbus

    support

    Analog/GSM/ISDN/CDMA modem

    support

    Ethernet/Internet interface via IG-IB

    module

    InteliMonitor free PC SCADA

    software for supervision of single or

    multiple controllers, configurable site

    structure, easy site overview, common

    history log, direct/modem/Internet

    connection

  • 7/28/2019 Igs-nt Gecon Datasheet 2009-07 Cplegecn

    3/6

    GenConfig free configuration tool;

    allows full configuration of an NT

    controller and its peripherals

    WinScope PC oscilloscope with up

    to 32 traces, any signal available in

    controller can be visualized

    Extension modulesand remote displays

    up to 4 I-AOUT8 8 analogue

    configurable outputs

    IGL-RA15 remote annunciator

    up to 4 IGS-PTM input/output

    module

    up to 10 IS-AIN8 analogue input

    module

    up to 4 IS-BIN16/8 binary

    input/output module

    up to 2 InteliVision controller

    colour display unit

    IG-Display LT GC additional remote

    display

    Upgrade kitsIGS-NT-GECON-LSM+PMS dongle:

    Enables Multiple isolated parallel or

    multiple parallel with mains

    Power management operation

    (with CAN bus)

    Digital Load Sharing

    Digital VAr Sharing

    IGS-NT-GECON-PCM dongle:

    Enables single parallel with mains

    InteliGenNT GeCon, InteliSysNT GeCon

    General featuresBasic unit + detachable display

    Dimensions 284 180 mm

    (front panel)

    Sealed to IP65 (front panel)

    Event-based history with configurable

    list of stored values up to 1000 records

    deep

    Integrated extended PLC programmable

    functions

    Inputs and outputs3 U generator 400 V/170 ph-ph

    3 U bus 400 V/170 ph-ph

    3 I generator CT 5/1 A

    1 I earth/I bus CT 5/1 A

    16 binary inputs

    16 binary outputs

    4 analog inputs

    1 analog output

    2 RS232/485

    1 USB

    InteliSysNT GeCon

    PC

    PC

    IS-DISPLAY#1

    MODEM

    IS-BIN16/8

    IS-AIN8-A

    IGS-PTM

    IGL-RA15

    LOAD

    -RA1

    I-AOUT8

    IN16/

    I-AO

    IS-

    16BINARY

    OUTPUTS

    (OPEN

    COLLECTOR)

    4ANALOGINPUT

    S

    BUSGENE

    RATOR

    IS-NT-BB-M

    arine

    EAR

    TH

    FAU

    LT

    CU

    RREN

    T

    AVR

    iO

    UT

    INTER-

    CONTROLLER

    &MONITORIN

    G

    CAN2

    RS232(1)

    INTERFACE

    IS-DISPLAY

    RS232/RS485

    (2)

    INTERFACE

    USB16BIN

    ARYINPUTS

    EXTENSION

    MODULES

    CAN1

    POWERSUP

    PLY

    8TO36VDC

    + -

    CU

    RR

    EN

    T

    VO

    LTAG

    E

    CU

    R

    REN

    T

    VO

    LTAG

    E

    MEA

    SU

    R

    EMEN

    T

    16

    ANALOG

    OUTPUT

    020mA

    1

    GENERATORDIESE

    L/GAS

    ENGINE

    ENGINE

    CONTROLLER

    1p

    h

    3p

    h

    3p

    h

    Genera

    torC

    .B.C

    ontro

    l

    SH

    IPM

    ON

    ITO

    RIN

    G

    SYS

    TEM

    TO

    OTH

    ER

    GEN

    ER

    ATO

    R

    CO

    NTR

    OLLER

    S

    E INE

    ECU

    IG-MTUU

    I-LB

    SHIPOR

    BUILDING

    MANAGEMENT

    MODBUS

    IG-IB

    I-LB

    IG-IB

    I -DILAY#2

    NINT

    IS

    AVRi

    A

    IG-MTUU

    A

    A

    onlyforMarine

  • 7/28/2019 Igs-nt Gecon Datasheet 2009-07 Cplegecn

    4/6

    Engine is controlled by independent

    controller. Two GeCon controllers are

    used to control and protect the generator.

    First GeCon is in PROT configuration, the

    second is in MINT (Master) configuration.

    Generator can be operated

    in three basic modes:

    MANUAL

    Both PROT and MINT controllers

    protect the generator

    Synchronization and load control of

    the generator are done manually

    Start and Stop are manual

    SEMI-AUTO

    Both PROT and MINT controllers

    protect the generator

    Synchronization and digital load-sharing via CAN bus are done by

    MINT controller

    Start and Stop are manual

    AUTO

    Both PROT and MINT controllers

    protect the generator

    Synchronization and digital load-

    sharing via CAN bus are done by

    MINT controller

    MINT controller automatically start

    and stop the genset in dependence

    on bus load, requirements to start

    heavy consumers, transfer the

    load between Auxiliary and Shaft

    generators etc.

    Engine is controlled by independent

    controller. Two GeCon controllers are

    used to control and protect the generator.

    Both GeCon controllers are in MINT

    (Master) configuration. One controller

    provides complete control and protection

    of the generator. The second controller is

    used as Hot standby, always ready to

    take over the control of the generator in

    case of failure of the master controller.

    Generator can operate in

    three basic modes:

    MANUAL

    SEMI-AUTO

    AUTO

    The same way as in the

    installation described above.

    Both Master and Redundancy

    controllers are connected to CAN bus.

    The Redundant controller checks and

    evaluates CAN bus messages from the

    Master controller. It immediately takes

    over control of the generator in case of

    detection of failure of the Master

    controller. A short period between

    failure of the Master controller and

    take over of control by Redundancy

    controller, less than 300 ms,

    guarantees minimal disturbance of

    generator voltage and current.

    START/ST

    OP

    OVERCURR

    ENT

    TOOTHER

    GENERAT

    ORS

    CAN2AUTO

    MANUAL

    SEMI-AUT

    O

    SPEEDUP

    /DOWN

    READYTO

    LOAD

    ENGINECONTROL

    3UG

    3I

    G

    3UB

    BUS

  • 7/28/2019 Igs-nt Gecon Datasheet 2009-07 Cplegecn

    5/6

    AUXGENERAT

    OR1

    AUXGENERA

    TOR2

    ENGINE

    CONTROLLER

    ENGINE

    CONTROLLER

    AUXGENERAT

    OR

    CONTROLLER

    AUXGENERA

    TOR

    CONTROLLER

    SHAFTGENE

    RATOR

    CONTROLLER

    SHAFTGENE

    RATOR

    PROTECTION

    SHAFT

    GENERATOR

    ESSENTIAL

    CONSUMERS

    HEAVY

    CONSUMER

    BLOCKING

    NONESSENTIA

    L

    CONSUMERS

    AUXGEN

    ERATOR

    PROTECTION

    AUXGENERAT

    OR

    PROTECTION

    GENERATOR1

    GENERATOR2

    SHAFTGENER

    ATOR

    Two auxiliary generators and one

    shaft generator deliver electricity

    for systems of the ship. Generators

    are controlled by GeCon controllers

    in MINT (Master) configurations.

    PMS can work in three basic

    operational modes:

    MANUAL complete manual control

    SEMI-AUTO synchronizing and

    load-sharing is automatic; genset start/

    stop and load transfer between aux and

    shaft generators in manual

    AUTO complete automatic control

    PMS continuously evaluates load reserve

    on the bus and blocks start of the bow

    thruster if the load reserve is insufficient.

    PMS automatically trips the

    non-essential consumers, if the

    power system is overloaded.

    PMS can control up to 10 independent

    circuits of non-essential consumers.

    Freely programmable built-in PLC

    functions are used to accomplish

    load transfer between shaft

    and auxiliary generators.

    Power Management System of the ship

  • 7/28/2019 Igs-nt Gecon Datasheet 2009-07 Cplegecn

    6/6

    Northern Corona is a supply vessel

    owned by Trico Shipping AS operating in

    Norway and was recently upgraded with

    a new generator synchronizing and load

    sharing system supplied by Industrimarin.

    They have also specified and installed

    the GeCon controller system for

    several customers vessels for

    on board generator applications

    as they provide a higher level of

    flexibility, as Bjarte explains We

    are continually amazed at the level of

    flexibility this controller offers us.

    Bjarte Steen

    Director

    www.industrimarin.com

    Product reportNorway, Northern Corona

    Features and specification are subject to change without prior notice 2009-07/CPLEGECN

    ComAp, spol. s r. o.

    Czech Republic

    Phone: + 420 246 012 111

    Fax: + 420 266 316 647

    E-mail: [email protected]

    Internet: www.comap.cz

    MANUFACTURER: LOCAL DISTRIBUTOR / PARTNER:

    www.comap.cz

    For more information about our products and solutions visit our web-page