imola – june, 19 2013 - 01 hvac & water application note
TRANSCRIPT
Imola – June, 19 2013 - 01
HVAC & WATERApplication note
HVAC & WATER
HVAC
Heating, Ventilation and Air-Conditioning (HVAC) is all about efficiency:
•Room temperatures need to be maintained at optimum levels to achieve the best occupant confort.
•It is essential to consider how hit targets in reducing costs and carbon dioxide (CO2) levels.
HVAC & WATER
WATER - PUMP
An operating pump will normally consume more power than the hydraulic circuit requires and it is usually positioned in unconfortable site:
•It is essential to consider how achieve targets in reducing power consumption, costs and CO2 levels.
•Maintenance time and costs need to be reduced in order to avoid long plant standstill.
HVAC & WATER - Why VFD flow control?
HVAC & WATER systems are designed to operate under the most extreme conditions
and, HVAC typically, in the “worst case” situations that the system will encounter
Most of the time they have excess capacity
HVAC & WATER - Why VFD flow control?
Problems of traditional flow control
•Low system efficiency•Difficult in regulation •Electromechanical stress•Noise due to mechanical resonance•High starting current•Big supply cable section or cable number•Maintenance cost and time
HVAC & WATER - Why VFD flow control?
Reducing the capacity of the systems when full capacity is not required provides significant energy
savings without sacrificing system performance
VFD Flow control
HVAC & WATER
Return Fan
Supply Fan
Primary cold/ChilledWater Pumps
CondensorWater Pump
Cooling Tower Fans Secondary Hot/ChilledWater Pumps
HVAC & WATER - Characteristic
0 100 200 300 400 500 600
Flow
0
5
10
15
20
25
30
35
40
45
50
Pre
ssur
e
Pump Curve
System Curve
OperatingPoint
HVAC & WATER - Traditional throttling flow control
0 100 200 300 400 500 600
Flow
0
5
10
15
20
25
30
35
40
45
50
Pre
ssur
e Power
Flowx
Pressure
New Power
required
WASTED Power
Powerto load
P
Pressuredrop
HVAC & WATER - VFD flow control
Cooling
Coil
Primary
Chilled WaterPump
SecondaryChill Water
Pump
DifferentialPressureSensor
Secondary
Chilled Water
Pump Drive
ChillerAir
Duct
Cooling
Coil
AirDuct
Cooling
Coil
AirDuct
Cooling
Coil
AirDuct
VFD avoids the pressure dropby controlling the speedof the pump
HVAC & WATER - VFD flow control
0 100 200 300 400 500 600
Flow
0
5
10
15
20
25
30
35
40
45
50
Pre
ssur
e
P
«VFD c.» Power
required
«Throttlecontrol» Power
required
HVAC & WATER - VFD flow control
Proportional Integral Derivative function (PID)
The sum of these three actions is used to adjust the process via a control element such as the position of a control valve or the power supply of a heating element.
PID controllers attempts to correct the error between a measured process variable and a desired set-point by calculation and then outputting a corrective action that can adjust the process accordingly.
HVAC & WATER - VFD flow control
Controller
DetectorFeedback value
Controlled Variable
Actuating Signal
Motorfreq.
Comparator
Σ SystemSet point
0-10VDC or 4-20mA signal
The target value or Set-point has to be set by user. This could be the desired pressure, flow, temperature, vacuum, etc.
E.g.: this reference is the measure of how much fluid is required to be sent to the wastewater pipeline.
Feedback value
Set point
Motor & PumpVSD
Transducer
Pump outlet
HVAC & WATER - VFD flow control
The standard «ready-to-install» IP54 SINUS PENTA solution is particularly suited to HVAC & WATER
applications:
High degree of protection against dust and water spraysAbility to mount without additional enclosures and ventilationPID functions for automatic controlBuilt-in EMC filterOnboard communications allows control and monitoring
HVAC & WATER - VFD flow control
The standard «ready-to-install» IP54 SINUS PENTA solution is particularly suited to HVAC &
WATER applications:
Extensive I/O with internal comparator functionsFire Mode function for extended operation in critical periodsSpeed Search function to start on a rotating loadReal Time Clock (RTC) function to adjust confort to demands that change over the weekMultipump functionRobustness and reliability
HVAC - SINUS PENTA advantages
AIR HANDLER
Reduce energy costs and CO2 emissionsVariable torque load characteristics use less energy as speed is reduced
Reduce supply demandDrives reduce motor starting current up to 10 times
Reduce noise in buildingsAirflow noise decreases by eliminating starts/stops and optimising flow rates
Reduce shock and vibrationDrive avoids running at speed near system resonant frequency and provides controlled acceleration
Increased life of motor beltsDrives provide low torque starts reducing stress on belts, pulleys and keys
HVAC - SINUS PENTA advantages
WATER CONDENSER CHILLER
Reduce energy consumptionProvide improved efficiency and reduce energy requirements
Reduce CO2 emissionsDue to the energy savings
Provide continuous operationRestart a spinning motor after momentary power loss
HVAC - SINUS PENTA advantages
COOLING TOWER FAN
Energy savings and reduce energy costsMotor use less energy as speed is reduced
Reduce CO2 emissionsDue to the reduce energy consumption
Reduce maintenance requirements and reduce operating costsRobust constructions and energy efficient
WATER - SINUS PENTA advantages
PUMPReduce energy costs and CO2 emissionsVariable torque load characteristics use less energy as speed is reduced
Reduce demand chargesDrives reduce motor starting current up to 10 times
Control of pressure of flow using PIDThe drive can optimize the pressure flow, and its linearity variations, with a single pressure transducer
Wide power range for different pump sizesNetwork communicationsSupport all major protocols
Prevention of water hammer, pipe stress, valve, pump seals and cavitationExtends the life of the entire system
WATER - MULTIPUMP application overview
• Controls a multi-pump pumping system (up to 5 pumps)
• One pump is the speed-controlled master and the other pumps are variable speed or fixed speed slaves
• Multi-Master mode
• Connection using I/O or Modbus
• Automatic balancing of operating hours of all pump sets
• Elimination of water hammer
WATER - MULTIPUMP: Fixed Speed Slaves (FSS)
The Master pump operates to ensure the system fine-tuning. The slave pumps are started up/stopped based on the criteria below:
1.Percentage of the working power required for the master pump (allowing optimum performance of the plant).
2.Maximum allowable adjusting error.
3.Maximum difference among the working time of each available pump.
The power ratio of the connected pumps must meet one of the following requirements:1.All pumps must have the same power ratings.2.The connected pumps can have different power ratings, provided that each pump with the greatest power rating is matched with lower-rated pumps that, if combined, have power ratings equal to or higher than the former pump.3.The power rating of the master pump must be higher than/equal to the power rating of the lower-rated pump.
WATER - MULTIPUMP: Fixed Speed Slaves (FSS)
Soft-Starter ASAB
Soft-Starter ASAB
Soft-Starter ASAB
Soft-Starter ASAB
Basic diagram for a fixed-speed plant including 4 slave devices and 1 MP Penta drive controlling the system in analog mode.
PENTA MULTIPUMP SOFTWARE
WATER - MULTIPUMP: Fixed Speed Slaves (FSS)
WATER - MULTIPUMP: Fixed Speed Slaves (FSS)
WATER - MULTIPUMP: Fixed Speed Slaves (FSS)
WATER - MULTIPUMP: Variable Speed Slaves (VSS)
The slave pumps and the master pump are started/stopped based on the following criteria:
1.Percentage of the working power required for the master pump (allowing optimum performance of the plant).
2.Maximum allowable adjusting error.
3.Maximum difference among the working time of each available pump.
All the connected pumps must have the same power ratings.
WATER - MULTIPUMP: Variable Speed Slaves (VSS)
PENTA MULTIPUMP SOFTWARE
Modbus MASTER
MODBUS RTU
Modbus SLAVE
MULTIMASTER
FUNCTION
PENTA DRIVEPENTA DRIVE
The diagram above shows a configuration for a variable-speed multipump system, serial communications and Multimaster function.
PENTA DRIVE
WATER - MULTIPUMP: Variable Speed Slaves (VSS)
HVAC & WATER: Variable Air Volume (VAV) Supply Fan
SupplyFan
HeatingCoil
CoolingCoil
ReliefAir Damper
OutsideAir Damper
ReturnAir Damper
PressureSensor
Supply Fan Drive
ReturnFan
ConditionedSpace
HVAC & WATER: Supply Fan - Temperature
ConditionedSpace
Supply Fan Drive
SupplyFan
T
T
HVAC & WATER: Supply Fan - Smoke Extraction
SupplyFan
ReliefAir Damper
OutsideAir Damper
ReturnAir Damper
SmokeSensor
Supply Fan Drive
ReturnFan
ConditionedSpace
Close thisdampe r
Reversethis fan
HVAC & WATER: Stairwell Pressurization
Fan Drive
Fan
Tp
Fire mode function
HVAC & WATER: Parking Garage Ventilation Fan
COSensor
Vent. Fan Drive
Vent.Fan
SmokeSensor
HVAC & WATER: Fume Hood Fan
Fume HoodFan Drive
Fan
HVAC & WATER: Cooling Tower Fan
TemperatureSensor
Cooling TowerFan Drive
CoolingTower Cells Chiller
CondenserWater Pump
HVAC & WATER: Condenser Water Pump
Flow Sensor
CoolingTower
Chiller
CondenserWaterPumpDrive
Strainer
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER: Examples
HVAC & WATER
Thank you