impact of corrosion inhibitors on lead release and biofilm ... · impact of corrosion inhibitors on...
TRANSCRIPT
Impact of Corrosion Inhibitors on Lead Release and Biofilm
Development in Simulated Partial Lead Service Lines
by
Aki Kogo
A thesis submitted in conformity with the requirements
for the degree of Master of Applied Science
Civil Engineering
University of Toronto
© Copyright by Aki Kogo 2016
ii
Impact of Corrosion Inhibitors on Lead Release and Biofilm
Development in Simulated Partial Lead Service Lines
Aki Kogo
Master of Applied Science, 2016
Graduate Department of Civil Engineering
University of Toronto
ABSTRACT
Partial lead service line replacements intended to decrease lead in drinking water but found to
potentially increase lead release by galvanic corrosion. This study investigated the effects of
corrosion inhibitors on lead release in simulate partial lead service lines. The performance of
orthophosphate, zinc orthophosphate, and sodium silicate were compared under different water
quality conditions (CSMR, conductivity, chlorination). Both orthophosphate and zinc
orthophosphate immediately decreased lead release in all conditions, while sodium silicate
seemed to slowly decrease lead release over time.
Biofilm is a potential reservoir of lead in distribution systems, and the detachment of biofilm
containing lead particles can cause health risk in drinking water. The effect of corrosion control
on biofilm development was also examined under stagnant and flow-through conditions.
Chlorination significantly decreased biofilm and was effective both under stagnant and flow-
through conditions. The densities of ATP and lead in biofilm were typically consistent.
iii
ACKOWLEDGEMENTS
This project was funded by Canadian Water Network (CWN), and I gratefully thank CWN for
the financial support.
I would like to thank my supervisor Prof. Robert C. Andrews, Sarah Jane Payne, and Jim Wang
for walking through this project with me as a team. Your guidance, support, and encouragement
were indispensable to accomplish this project. Also, I appreciate Dave Scott and all the staff at
the R. C. Harris Water Treatment Plant for providing source water for this project. I would like
to thank everyone in Drinking Water Research Group. It was a great time for me to work with
you all. Finally, I thank my family and friends for your continued support and encouragement.
iv
TABLE OF CONTENTS ABSTRACT .................................................................................................................................... ii
ACKOWLEDGEMENTS .............................................................................................................. iii
TABLE OF CONTENTS ............................................................................................................... iv
LIST OF TABLES ........................................................................................................................ vii
LIST OF FIGURES ....................................................................................................................... ix
NOMENTCLATURE .................................................................................................................... xi
1 Introduction .................................................................................................................................1
1.1 Background ..........................................................................................................................1
1.2 Objective ..............................................................................................................................3
1.3 Description of Chapters .......................................................................................................3
2 Literature Review ........................................................................................................................4
2.1 Lead Release From Lead Service Lines ...............................................................................4
2.1.1 Galvanic Corrosion ..................................................................................................4
2.1.2 Precipitation and Dissolution of Pipe Scales ...........................................................5
2.2 Water Chemistry Affecting Lead Release ...........................................................................6
2.2.1 CSMR ......................................................................................................................6
2.2.2 Alkalinity and pH .....................................................................................................8
2.2.3 Corrosion Inhibitors .................................................................................................9
2.2.4 Disinfectant: Chlorine in Comparison to Chloramine ...........................................11
2.3 Bacterial Regrowth and Biofilm Formation in Distribution Systems ................................12
3 Materials and Methods ..............................................................................................................13
3.1 Experimental Setup ............................................................................................................13
3.1.1 Pipe Loops for Partial Lead Service Line Replacement Study ..............................13
3.1.2 Pipe Loops for Biofilm Study ................................................................................14
3.1.3 Lead Release During Stagnation Periods ...............................................................15
3.1.4 Mass Balance .........................................................................................................17
3.1.5 Experimental Timeline...........................................................................................17
3.1.6 pH Control in the Reservoirs .................................................................................18
3.1.7 Preparation of A Free Chlorine Working Solution ................................................19
3.2 Analytical Methods ............................................................................................................19
3.2.1 Total and Dissolved Metals (Lead and Copper) ....................................................19
v
3.2.2 Galvanic Current ....................................................................................................20
3.2.3 Alkalinity ...............................................................................................................20
3.2.4 pH ...........................................................................................................................21
3.2.5 Turbidity ................................................................................................................21
3.2.6 Total Organic Carbon ............................................................................................21
3.2.7 Chloride, Sulfate, Phosphate, Nitrate, and Nitrite .................................................22
3.2.8 Silica ......................................................................................................................23
3.2.9 Free Chlorine .........................................................................................................23
3.2.10 ATP ........................................................................................................................23
3.3 Statistical Analysis .............................................................................................................24
4 Comparison of Three Corrosion Inhibitors in Simulated Partial Lead service Line
Replacements ............................................................................................................................25
4.1 Abstract ..............................................................................................................................25
4.2 Introduction ........................................................................................................................25
4.3 Materials and Methods .......................................................................................................29
4.3.1 Partial Lead Service Line Experimental Setup ......................................................29
4.3.2 Experimental Plan ..................................................................................................32
4.3.3 Experimental Design ..............................................................................................34
4.3.4 Sample Analysis.....................................................................................................34
4.3.5 Statistical Analysis .................................................................................................35
4.4 Results and Discussion ......................................................................................................36
4.4.1 Effects of corrosion inhibitors for different stagnation periods .............................36
4.4.2 Effects of CMSR and conductivity ........................................................................40
4.4.3 Effects of Galvanic corrosion ................................................................................42
4.4.4 Comparison of dissolved and particulate lead release ...........................................46
4.4.5 Copper release during acclimation and treatment ..................................................47
4.5 Conclusions ........................................................................................................................51
5 Impact of Corrosion Control on Biofilm Development in Simulated Partial Lead Service
Line Replacements ....................................................................................................................52
5.1 Abstract ..............................................................................................................................52
5.2 Introduction ........................................................................................................................52
5.3 Materials and Methods .......................................................................................................54
vi
5.3.1 Partial lead service line setup .................................................................................54
5.3.2 Experimental plan ..................................................................................................56
5.3.3 Sample Analysis.....................................................................................................56
5.3.4 Estimation of lead released through galvanic current ............................................58
5.3.5 Statistical Analysis .................................................................................................58
5.4 Results and Discussion ......................................................................................................58
5.4.1 Effects of corrosion inhibitors on biofilm growth under stagnant and flow-
through conditions .................................................................................................58
5.4.2 Estimation of capacity of biofilm for storing lead .................................................67
5.5 Conclusion .........................................................................................................................69
6 References .................................................................................................................................70
7 Appendices ................................................................................................................................81
7.1 Sample Quality Assurance/Quality Control Charts ...........................................................81
7.2 Raw Data ............................................................................................................................85
7.3 Preliminary Results ..........................................................................................................115
7.3.1 Tank Acidification ...............................................................................................115
7.3.2 Chlorine Demand Test .........................................................................................119
vii
LIST OF TABLES
Table 3-1: Pipe Loop Test Section Composition .......................................................................... 14
Table 3-2: Typical Daily Flow Pattern used in Experiments from Friday Evening to Tuesday
evening .......................................................................................................................................... 15
Table 3-3: Timeline for Experiments ............................................................................................ 18
Table 3-4: Reagents for Alkalinity Analysis ................................................................................ 21
Table 3-5: Reagents for TOC and DOC Analysis ........................................................................ 22
Table 3-6: Instrumental Conditions for TOC and DOC Analysis ................................................ 22
Table 4-1: Experimental conditions for both acclimation and treatment phases (OP, ZOP, sodium
silicate) .......................................................................................................................................... 31
Table 4-2: Characteristics of raw Lake Ontario water used for the experiments ......................... 32
Table 4-3: Recirculation event and sample collection for a weekly cycle ................................... 33
Table 4-4: Event in a weekly cycle ............................................................................................... 33
Table 4-5: Comparison of dissolved and total lead release (± standard deviation) ...................... 39
Table 5-1: Experimental conditions for both acclimation and corrosion inhibitor trials (OP, ZOP,
and sodium silicate) ...................................................................................................................... 55
Table 5-2: Raw water quality ........................................................................................................ 56
Table 5-3: Log reduction in ATP in stagnant and flow-through biofilm by chlorination ............ 60
Table 5-4: Particulate lead fraction in biofilm and bulk water (at the end of a weekly cycle) ..... 66
Table 5-5: Estimation of lead storing capacity of biofilm and removal from theoretical weekly
mass release .................................................................................................................................. 68
Table 7-1: Total and dissolved lead release for 30-min stagnation periods (part 1) ..................... 85
viii
Table 7-2: Total and dissolved lead release for 6-h stagnation periods (part 1) ........................... 88
Table 7-3: Total and dissolved lead release for 65-h stagnation periods (part 1) ......................... 91
Table 7-4: Lead concentrations in samples of pre-acidification bulk water (90 L) and acidified
bottom 20 L of reservoir water (part 1) ........................................................................................ 93
Table 7-5: Weekly mass release calculated based on samples collected (part 1) ......................... 96
Table 7-6: Total and dissolved copper release for 30-min stagnation periods (part 1) ................ 98
Table 7-7: Total and dissolved copper release for 6-h stagnation periods (part 1) ..................... 101
Table 7-8: Total and dissolved copper release for 65-h stagnation periods (part 1) ................... 104
Table 7-9: Copper concentrations in samples of pre-acidification bulk water (90 L) and acidified
bottom 20 L of reservoir water (part 1) ...................................................................................... 106
Table 7-10: Total and dissolved lead accumulation in biofilm under stagnant and flow-through
conditions .................................................................................................................................... 109
Table 7-11: Total and dissolved copper accumulation in biofilm under stagnant and flow-through
conditions .................................................................................................................................... 110
Table 7-12: ATP accumulation under stagnant (Stag) and flow-through (Flow) conditions ..... 111
Table 7-13: Average galvanic current (± standard deviation) .................................................... 112
Table 7-14: Water quality parameters of reservoir water (part 1) .............................................. 113
ix
LIST OF FIGURES
Figure 3-1: Typical pipe loop system ........................................................................................... 14
Figure 3-2: Weekly Cycle and Sampling Times ........................................................................... 16
Figure 4-1: Comparison of average dissolved (blue) and particulate (black) lead release for each
corrosion inhibitors (a. 30 min, b. 6 h, c. 65 h). ............................................................................ 38
Figure 4-2: Galvanic current in Cu-Pb systems during three treatment phases. ........................... 41
Figure 4-3: Predicted vs. observed total lead release for 6-h stagnation period under conditions of
a) low CSMR, b) high CSMR-low conductivity, c) high CSMR-high conductivity, and d) high
CSMR-high conductivity-chlorine................................................................................................ 44
Figure 4-4: Average weekly lead release. ..................................................................................... 45
Figure 4-5: Comparison of average dissolved (blue) and particulate (black) copper release for
each corrosion inhibitors (a. 30 min, b. 6 h, c. 65 h). ................................................................... 50
Figure 5-1: ATP accumulation under a) stagnant and b) flow-through conditions. n=4, 2, 2, and 8
for low CSMR, high CSMR-low conductivity, high CSMR-high conductivity, and high CSMR-
high conductivity-chlorine phases. ............................................................................................... 61
Figure 5-2: Total lead and ATP accumulation under a) stagnant and b) flow-through conditions
(linear regression). ........................................................................................................................ 62
Figure 5-3: Lead accumulating in biofilm under a) stagnant and b) flow-through conditions with
and without chlorination. n=2 and 8 for high CSMR-high conductivity and high CSMR-high
conductivity-chlorine phases. ....................................................................................................... 63
Figure 5-4: Copper accumulating in biofilm under a) stagnant and b) flow-through conditions
with and without chlorination. ...................................................................................................... 64
Figure 5-5: Copper accumulating in biofilm under a) stagnant and b) flow-through conditions
with and without chlorination. n=2 and 8 for high CSMR-high conductivity and high CSMR-
high conductivity-chlorine phases. ............................................................................................... 65
x
Figure 7-1: QC chart – lead (Check standards = 100 µg/L) ......................................................... 82
Figure 7-2: QC chart – copper (Check standards = 100 µg/L) ..................................................... 82
Figure 7-3: QC chart – TOC (Check standards = 2.5 mg/L) ........................................................ 83
Figure 7-4: QC chart – phosphate (Check standards = 2.0 mg/L) ................................................ 83
Figure 7-5 : QC chart – chloride (Check standards = 25 mg/L) ................................................... 84
Figure 7-6: QC chart – sulfate (Check standards = 30 mg/L)....................................................... 84
Figure 7-7: Daily galvanic current .............................................................................................. 112
Figure 7-8: Treatments to Determine Lead Recovery from Reservoirs ..................................... 116
Figure 7-9: Lead Concentrations During 50-h Acidification ...................................................... 118
Figure 7-10: Free chlorine concentrations in 1 L of waters from the six reservoirs (second
time)Control of the free chlorine and monochloramine residual in the reservoirs .................... 120
xi
NOMENTCLATURE
≈ approximate
< Less than
> Greater than
≤ Less than or euqual to
- To
± Plas/minus
α Confidence level
μg/L Microgram(s) per liter
μL Microlitrer(s)
μm Micrometer(s)
Ω Ohm(s)
% Percent
ATP Adenosine triphosphate
APHA American Public Health Association
AWWA American Water Works Association
BLL Blood lead level
cm Centimeter(s)
Cl- Chloride ion
CSMR Chloride to sulfate mass ratio
Cl2 Chlorine
CFU/cm2 Colony forming unit per centimeter squared
CFU/L Colony forming unit per liter
CI Confidence interval
Cu Copper
° C Degrees Celsius
d Diameter
DBP Disinfection by-product
DIC Dissolved inorganic carbon
e Electron
EPA Environmental protection agancy
xii
N Equivalent concentration (eq/L)
EPS Exopolysaccharide
g Gram(s)
g/L Gram(s) per liter
HPC Heterotrophic plate count(s)
h Hour(s)
h/day Hour(s) per day
ICP-OES Inductively coupled plasma optical emission spectrometry
Fe Iron
Pb Lead
Pb(IV) Lead (4+), Pb4+
PbO2 Lead dioxide
LSL Lead service line
Pb(II) Lead(2+), Pb2+
LPM Liter per minute
L Liter(s)
L/day Liter(s) per day
L/min Liter(s) per minute
pH -log (hydrogen ion concentration)
Mn Manganese
MPI Metabolic potential index
mg/L Milligram(s) per liter
mL Milliliter(s)
mm Millimeter(s)
mS/cm Millisiemens per centimeter
min Minute(s)
M Molar concentration (mol/liter)
NH2Cl Monochloramine
ng/cm2 Nanogram per centimeter squared
nm Nanometer(s)
NTU Nephelometric turbidity unit(s)
N/m2 Newton per meter squared
xiii
ON Ontario
OP Orthophosphate
ORP Oxidation reduction potential
PLSLR Partial lead service line replacement
Pa Pascal
R2 Pearson’s correlation coefficient
P Phosphorus
PVC polyvinyl chloride
QA/QC Quality assurance quality control
RLU Relative light units
SO4- Sulfate ion
TDC Total direct count
TOC Total organic carbon
U.S. United States
USA United States of America
v/v Volume per volume
ZOP Zinc orthophosphate
1
1 Introduction
1.1 Background
The events of increased lead leaching to drinking water occurred in Flint, Michigan in 2014-
2016 (Kennedy et al., 2016) and Washington, DC in 2001-2004 (Edwards and Dudi, 2004) raised
public concern to lead contamination in drinking water. Those cases happened when the utilities
changed the chemical characteristics of water by changing the water source from Lake Huron to
Flint River, which was more corrosive (Kennedy et al., 2016), or switched the disinfectant from
chlorine to chloramine to manage the formation of disinfectant by-products (Edwards and Dudi,
2004).
The complexity and difficulty for lead control in drinking water is also attributed to distribution
systems. Drinking water is a source of human exposure to lead along with air, house dust, and
food (Health Canada, 2013). It was estimated that lead in drinking water accounts for
approximately 20% of lead entering a human body (U.S. EPA, 2002). Following the inhibition of
lead pipe installation in drinking water distribution systems in 1986 in the U.S. (U.S. EPA, 2015)
and in 1975 for lead pipes and 1986 for solder in Canada (Health Canada, 2007), the strategy of
PLSLR was employed to decrease lead in drinking water by removing lead pipes in distribution
systems. However, it was found PLSLR may not significantly decrease BLLs of children when
compared to full LSLs (Brown et al., 2011) and can increase lead release due to galvanic
corrosion between lead and copper (Cartier et al., 2013; Wang et al., 2013) in addition to
temporary but serious lead release by physical disturbance at replacement (Zietz et al., 2001).
Galvanic corrosion can increase lead release while protecting the copper side by cathodic
protection and can elevate lead concentrations in water for weeks (Wang et al., 2013; Edwards
and Triantafyllidou, 2007) to months (Triantafyllidou and Edwards, 2011).
CSMR have effects on lead release by changing the composition of lead products. Higher CSMR
can be resulted from the source water and the use of chloride-based coagulants during treatment
processes and tends to increase lead release. The critical CSMR that can increase lead corrosion
was estimated to be 0.5-0.77 (Gregory, 1985; Dodrill and Edwards, 1995; Nguyen et al., 2011b).
In addition, it was considered higher conductivity affects galvanic corrosion. Willison and Boyer
2
(2012) observed the water with higher concentrations of chloride and sulfate had higher lead
leaching than lower concentrations with the consistent CSMR.
It is also necessary to search for alternatives to conventional corrosion inhibitors in cases of
waters in which phosphate being ineffective or unfeasible cost. Phosphate is a common corrosion
inhibitor for lead control, and McNeill and Edwards (2002) reported 56% of utilities used
phosphate-based inhibitors for lead control in 2001. However, the price of phosphate rock is
volatile and increased by 800% in 2007-2008 (McGill, 2012). ZOP, in comparison to OP, was
reported to increase particulate lead release (McNeill and Edwards, 2004). It is concerned the use
of phosphate-based inhibitors can increase microbial activity in drinking water (McNeill and
Edwards, 2002). Biofilm can be a sink for particles released from pipe materials, but the capacity
of biofilm storing lead is not well-documented. Ginege et al. (2011) reported the ability of
biofilm to remove iron and manganese both under unchlorinated and chlorinated condition.
Detachment of biofilm can cause release of trapped iron and manganese (Ginege et al., 2011),
which can be applicable to lead as well. Deshommes and Prévost (2012) reported ingestion of
lead particles in tap water can contribute to the exposure of children to lead. Sodium silicate can
be a potential alternative to phosphate-based inhibitors (Dart and Foley, 1970) and has been used
for iron control in drinking water (Robinson et al., 1992). Past studies showed sodium silicate
effectively decreased lead release (Schock et al., 2005; Lintereur et al., 2010; Sastri et al., 2006).
It was reported that the effect of sodium silicate may take time to appear because of slow
formation of silicate film (Thompson et al., 1997; Schock et al., 2005).
The events of lead leaching in drinking water reminded that the situation regarding drinking
water is complicated. This study provided a realistic simulation of PLSLRs to investigate
corrosion inhibitors under various water qualities.
3
1.2 Objective
This thesis investigated the following objectives:
1. Compare the performance of three corrosion inhibitors (orthophosphate, zinc
orthophosphate, and sodium silicate) to mitigate lead release in PLSLR under two levels
of CSMR and conductivity in the absence and presence of free chlorine.
2. Examine the impact of free chlorine on biofilm and bulk water microbiology in the
presence of three corrosion inhibitors in partial LSLs.
1.3 Description of Chapters
Chapter 2 provides a literature review of past studies regarding lead control strategies and
factors affecting lead release.
Chapter 3 contains the materials and methods used to conduct the experiments for this
study.
Chapter 4 examines the effects of corrosion inhibitors on lead release in simulated partial
lead service line replacement under different water quality conditions.
Chapter 5 evaluates the effects of corrosion inhibitors on biofilm development under non-
chlorinated and chlorinated conditions.
Chapter 6 provides the list of references used in this study.
Chapter 7 provides the appendices, including the results of preliminary study, the QA/QC
chart, and the raw data.
4
2 Literature Review
2.1 Lead Release From Lead Service Lines
Lead in drinking water can be attributed from two main mechanisms: galvanic corrosion and
dissolution of leaded pipe scales.
2.1.1 Galvanic Corrosion
Galvanic corrosion occurs when dissimilar metals with different electrochemical potentials
become connected and are in contact with an electrolyte. In a galvanic coupling, the metal with
higher electrochemical potential corrodes. In a system with partial lead service line replacement
(PLSLR) in which a lead pipe is galvanically connected to a copper pipe, lead acts as an anode
and copper as a cathode. Water flowing through the pipes acts as the electrolyte and provides a
pathway for ions to migrate. The following half reactions and the net reaction occur when lead
enters solution (Wang et al., 2012; Sastri et al., 2006).
Pb (s) = Pb2+ + 2e− 2-1
O2(aq) + 4H+ + 4e− = 2H2O 2-2
2Pb (s) + O2(aq) + 4H+ = 2Pb2+ + 2H2O 2-3
Occurrence of galvanic corrosion can be observed by measuring current between lead and copper
pipes. Galvanic currents have been shown to have a positive linear correlation with lead with R2
values of 0.93 and 0.77 reported by Nguyen et al. (2010) and Hu et al. (2012), respectively.
Galvanically connected systems have shown an increase in lead concentration by a factor of 5.5
(Cartier et al., 2013). Wang et al. (2013) also observed an eight-fold increase in total lead
concentration after a 6 hour stagnation following installation of an external wire connecting a
lead pipe to a copper pipe. Following removal of the external wire, lead concentration
immediately decreased to the same level as that without galvanic corrosion (Wang et al., 2013).
Galvanic corrosion has also been observed in lead bearing brass to copper connections. In a
study conducted by Cartier et al. (2012b), lead concentration increased by a factor of 2.4 in a
faucet composed of red brass which was connected to a copper nipple.
5
Even though PLSLR without galvanic corrosion can increase lead release in distribution systems,
galvanic corrosion can exacerbate lead release in the systems. Elevated lead concentrations were
presumably attributed from mechanical disturbance due to PLSLR or pipe repair in
approximately 50% of households examined in Lower Saxony, Germany (Zietz et al., 2001).
Lead release due to mechanical disturbance increases lead concentrations for a short period of
time. High lead concentrations were observed in waters for the first 15 min following non-
galvanic connection of pipes, and the concentration declined below 10 µg/L afterward (Boyd et
al., 2004). However, PLSLR with galvanic connection can further increase lead concentrations
and have a prolonged impact, as galvanic current has been reported to persist over 6 weeks
(Wang et al., 2013), 11 weeks (Edwards and Triantafyllidou, 2007), and several months
(Triantafyllidou and Edwards, 2011).
The extent of galvanic corrosion also varies depending on other factors, including stagnation
period and flow rate. Wang et al. (2012) reported that, when compared to systems without
galvanic corrosion, 6-h and 65-h stagnations increased total lead leaching due to galvanic
corrosion by 4-6 and 15-30 times, respectively. Similarly, lead release from galvanic systems of
lead solder and copper pipe rigs increased in waters regardless of disinfectant type (free chlorine
and chloramines) by increasing stagnation time from 30 min to 24 h (Woszczyski et al., 2013).
Lytle and Schock (2000) observed exponential increases in lead concentrations over a 90 h
stagnation period, with 50-70% of lead leaching during the first ten hours. The impact of flow
rate was investigated in Cartier et al. (2013), and particulate lead release significantly (p < 0.05)
increased by a factor of 12 on an average regardless of treatment when the flow rate was raised;
particulate lead release from pure lead pipes, for example, increased from 21±16 to 284±314
µg/L as flow rate was increased from 5 to 15 LPM. In contrast, dissolved lead concentration
showed a limited impact of flow rate change (Cartier et al., 2013).
2.1.2 Precipitation and Dissolution of Pipe Scales
Precipitation and dissolution of leaded pipe scales are major factors affecting lead concentrations
in drinking water, and are controlled by water chemistry and presence of corrosion inhibitors.
Studies have shown that leaded pipe scales are composed of various compounds, including Pb(II)
carbonates, Pb(II) oxides, and Pb(IV) oxides (Schock et al., 2008). A Pb(II) carbonate
6
hydrocerussite (Pb3(CO3)2(OH)2) is a widely observed component of leaded pipe scales (Kim
and Herrera, 2010; Hozalski et al., 2005; Noel et al., 2014). Released lead can precipitate onto
the surface of pipes, forming passivating scales (Lintereur et al., 2010). Under conditions of high
redox potential, PbO2 precipitates along with dominant or coexisting Pb (II) mineral forms
hydrocerussite and cerussite (Lytle and Schock, 2005).
Lead release from scale dissolution was strongly affected by pH and dissolved inorganic carbon
(DIC), and the steady-state concentrations of hydrocerussite decreased with increasing pH from
6 to 10 when the water had 0 mg/L DIC (Noel et al., 2014). Similarly, decreasing pH from 10 to
8.5 resulted in increased lead due to the dissolution of hydrocerussite and lead oxides (Xie and
Giammer, 2011). Increasing DIC from 0 to 10 mg/L decreased hydrocerussite dissolution,
however increasing DIC to 50 mg/L did not reduce the dissolution further (Noel et al., 2014).
Conversely, increasing DIC can enhance dissolution of corrosion products by reducing Pb(IV) to
Pb(II) and by forming soluble Pb(II) (Xie et al., 2010). Also, physical conditions of water
including flow rates and stagnation periods, can increase the rates of lead scale dissolution. It
was demonstrated that, when compared to stagnant water, flowing water had considerably
accelerated dissolved lead release rates, even though higher lead release would occur during
stagnation periods due to longer contact time between water and pipe during stagnation than
flowing periods (Xie and Giammer, 2011).
2.2 Water Chemistry Affecting Lead Release
Various water parameters can have strong impacts on lead release from distribution systems.
2.2.1 CSMR
Chloride-to-sulfate mass ratio (CSMR) shows the relative mass of chloride to sulfate, and CSMR
can be calculated using the equation shown below (Edwards and Triantafyllidou, 2007).
𝐶𝑆𝑀𝑅 =
[𝐶𝑙−]
[𝑆𝑂42−]
2-4
7
CSMR of water can be affected by the compositions of specific coagulants used in drinking
water treatment. Application of chloride-based and sulfate-based coagulants during treatment
results in high and low CSMRs, respectively. Studies have shown that waters with high CSMR
can enhance galvanic corrosion. Conductivity tends to increase in high CSMR, which facilitates
galvanic current and consequently galvanic corrosion (Gregory, 1985; Willison and Boyer,
2012). The critical values of CSMR that can enhance lead corrosion to unacceptably high levels
are estimated to be 0.5 (Gregory, 1985), 0.58 (Dodrill and Edwards, 1995), and 0.77 (Nguyen et
al., 2011b). Edwards and Triantafyllidou (2007) treated water with polyalminum chloride and
alum to compare high and low CSMR conditions, and the authors reported that the higher CSMR
(1.42-4.5) waters had 1.5 to 3 times higher lead leaching from solder than the low CSMR (0.5)
waters. Also, significant (95% CI) pH drops were observed in both higher and lower CSMR
galvanic samples, declining from 7.6-7.8 to as low as 3.4 and 4.4 near the solder surface,
respectively (Edwards and Triantafyllidou, 2007). Nguyen et al. (2011c) found increasing CSMR
from 0.1 to 1.0 resulted in an increase in galvanic corrosion from 50:50 lead-tin solders, but
increasing CSMR higher than 1.0 did not have an additional impact in some of the waters which
they investigated. Wang et al. (2013) did not observe an increase in total lead release when
increasing CSMR from 0.7 to 7 and presumed this may be because a high initial CSMR of 0.7
had already enhanced lead corrosion for this system.
Even though CSMR can be used to predict lead corrosion in water, high chloride and sulfate
concentrations can result in enhanced lead release. Willison and Boyer (2012) examined higher
concentrations of chloride and sulfate while the CSMR value was kept constant (0.5). It was
demonstrated that water with higher concentrations of chloride (50 mg/L) and sulfate (100 mg/L)
had significantly (95% CI) higher lead release than waters with lower concentrations (5 mg Cl-/L
and 100 mg SO42-/L) (Willison and Boyer, 2012). Since anions, such as chloride and sulfate, can
be drawn toward the anode surface due to galvanic corrosion, concentrations of anions and
locally high CSMR in the microenvironment around the anode can influence lead corrosion
(Nguyen et al., 2010). In addition, a pH drop from 8.3 to 6.4 was observed within 5 cm of
galvanic junction after 1 h stagnation under both high (16.2) and low (0.2) CSMR conditions,
indicating galvanic corrosion created a corrosive microenvironment at the junction (Hu et al.,
2012).
8
2.2.2 Alkalinity and pH
Alkalinity is used to represent the capacity of a solution to neutralize an acid and has indirect
impacts on lead corrosion. In addition, pH is also an important factor that is often interrelated
with alkalinity. Alkalinity and high pH are considered to be beneficial when considering
corrosion control of lead. When compared to 15 mg/L as CaCO3, water with 45 mg/L as CaCO3
or higher alkalinity resulted in decreased lead release at pH 7.2 (McNeill and Edwards, 2004).
Similarly, assessment of waters without corrosion inhibitors by Dodrill and Edwards (1995)
reported that higher 90th percentile lead concentrations were observed in waters with alkalinity <
30 mg/L as CaCO3 and for pH ranges of < 7.40, 7.40-7.80, and 7.80-8.40, ranging from
approximately 0.024-0.034 mg/L, when compared to most waters with the higher alkalinity (> 30
mg/L). Lead release tended to decrease for alkalinities in the ranges of 30-74, 74-174, and > 174
mg/L as CaCO3, except when water had 30-74 mg/L alkalinity as CaCO3 and pH < 7.40 (Dodrill
and Edwards, 1995). Edwards et al. (1999) showed that increasing alkalinity resulted in
decreases in 90th percentile lead concentrations. The same study estimated an optimum alkalinity
range to be 20-40 mg/L as CaCO3 at pH > 8.5 for lead corrosion control (Edwards et al., 1999).
In contrast, addition of 100 to 150 mg/L alkalinity as CaCO3 resulted in three to five time higher
lead concentrations at pH 7, when compared to controls with 20 mg/L alkalinity as CaCO3; lead
concentrations of approximately 230, 210, and 350 µg/L in the samples with 100, 125, 150 mg/L
alkalinity while approximately 70 µg/L in control (Tam and Elefsinotis, 2009). However, the
effects of alkalinity on lead concentrations became insignificant at pH > 8 (Tam and Elefsinotis,
2009). Also, an increase in pH (7.7-8.4) and alkalinity (80-240 mg/L) resulted in a decrease in
lead concentrations in a 1-year pilot study (Tang et al., 2006). Similarly, raising pH to 8.4 was
effective in a new faucet (30% reduction) with and without connection to copper piping (Cartier
et al. 2012b). Nguyen et al. (2011c) adjusted CSMR in 100 % distribution water (alkalinity 125
mg/L as CaCO3) and a 75:25 desalinated: distribution water blend (61 mg/L as CaCO3) to be 1.1
to examine the effect of alkalinity. The blended water increased lead release from approximately
60 µg/L to 560 µg/L, when compared to the 100% distribution water (Nguyen et al., 2011c).
Low pH prevents formation of passivated scales on the lead anode and thus increases lead
leaching via continuous galvanic corrosion. Although alkalinity can buffer pH and decrease
corrosion, increased conductivity due to alkalinity may outweigh the benefit. Nguyen et al.
9
(2011c) showed that galvanic lead corrosion was promoted when alkalinity was < 10 mg/L
CaCO3, while galvanic corrosion was mitigated by scale formation on the lead anode when
alkalinity was > 10 mg/L as CaCO3.
2.2.3 Corrosion Inhibitors
Corrosion inhibitors may be added to treated water to reduce lead release from distribution pipes.
2.2.3.1 Orthophosphate and Zinc Orthophosphate
Phosphate-based inhibitors are commonly applied to control lead corrosion in drinking water
distribution systems. Use of orthophosphate is becoming increasingly common, growing from
5% (of utilities employing phosphate inhibitors using orthophosphate in 1994) to approximately
20% in 2001 (McNeill and Edwards, 2002). Zinc orthophosphate is another common corrosion
inhibitor, being applied at approximately 30% of the utilities using phosphate inhibitors in 2001
(McNeill and Edwards, 2002). Tam and Elefsinotis (2009) reported that the addition of
orthophosphate (0.8 mg P/L) decreased lead release by 70% for a pH of 7.5 and was also
effective at the higher pH (8.0). Similarly, Cartier et al. (2013) showed the addition of
orthophosphate reduced 64% of lead release (from 72±14 to 26±9 µg/L) for pure lead pipes
within 8 days of application. The effectiveness of orthophosphate has been reported in other
studies as well (Cardew 2009; Cartier et al., 2012b; Edwards and McNeill, 2002).
Orthophosphate tends to be more effective on the soluble lead portion. Addition of
orthophosphate suppressed dissolved lead concentrations to be 21±15 µg/L following a galvanic
connection with copper pipe (Cartier et al., 2012b). Water treated with zinc orthophosphate (0.37
and 1.0 mg/L) resulted in significantly (95% CI) lower lead concentrations following 4 months
and 8 months, when compared to a control (Churchill et al., 2000). When comparing
orthophosphate and zinc orthophosphate, both inhibitors significantly reduced (95% CI) lead
release from brass and solder galvanically connected to copper regardless of CSMR (Edwards
and Triantafyllidou, 2007). In their study, orthophosphate showed better performance than zinc
orthophosphate.
In contrast, other studies have reported that the addition of phosphate can increase lead corrosion
from pipes under certain conditions. Nguyen et al. (2011a) showed lead release increased by as
10
much as six times for 50:50 Pb: Sn solder when 1 mg/L phosphate was added in waters with
sulfate concentration < 10 mg/L or when < 30% of the current was carried by sulfate ions. Case
studies showed that the addition of 1 mg P/L of orthophosphate doubled lead release when
chloride and alkalinity were 17 mg Cl/L and 20 mg/L, respectively, as CaCO3, while
orthophosphate decreased lead release for waters with a chloride concentration of 8 mg/L Cl and
alkalinity of 20 mg/L as CaCO3 (Nguyen et al., 2011a). McNeill and Edwards (2004) also
showed zinc orthophosphate addition resulted in increases (95% CI) in particulate lead release in
waters with pH 7.2 and with 45 mg/L alkalinity, while both orthophosphate and zinc
orthophosphate significantly reduced soluble lead in all types of waters tested.
2.2.3.2 Sodium Silicate
Sodium silicate (Na2SiO3) has been used to control pipe corrosion since the late 1920’s
(Thompson et al., 1997), but its effectiveness and mechanism for corrosion control have not been
well-studied (Lintereur et al., 2010). Examination of the effectiveness of sodium silicate may be
difficult to distinguish from the effect of pH increase following the application of sodium
silicate. According to Schock et al. (2005), addition of 25-30 mg/L sodium silicate decreased
lead concentrations by 55 % with increase in pH from 6.3 to 7.1, and increasing the dose to 45-
55 mg/L further decreased lead concentrations below 15 µg/L with final pH 7.5. The overall
reduction was 97% for 90th percentile lead concentration (Schock et al., 2005). Lintereur et al.
(2010) also reported that addition of 10, 20, 40 mg/L silicate (initial 1-5 weeks) was generally
effective to mitigate total lead concentrations below the lead action level (15 µg/L), even though
10 mg/L silicate dose was less effective than 20 and 40 mg/L. Similarly, addition of sodium
silicate (40 mg/L), phosphate (40 mg/L), and sodium silicate+phosphate (20+20 mg/L) were
effective and reduced lead release after 112 days from 2750 µg/L in control to below detection
limit (< 1 µg/L), 28 µg/L, and < DL, respectively (Sastri et al., 2006). MacQuarrie et al. (1997)
reported sodium silicate showed some effectiveness in reducing lead release from brass faucets,
while sodium silicate had no impact on lead release from lead/tin solder coils and worsened lead
release from lead soldered copper plumbing coils. Thompson et al. (1997) pointed that silicate
may need longer time to reduce lead release effectively. Scheetz et al. (1997) also suggested
increased corrosion of copper and lead pipes may occur as a result of incomplete silica film
11
formation by filling in the voids on other corrosion products and forming a thin layer over the
existing films.
2.2.4 Disinfectant: Chlorine in Comparison to Chloramine
In order to meet regulatory limits for disinfection by-products some utilities have switched from
chlorine to chloramine (Renner, 2010). Even though chloramines are widely used secondary
disinfectants because of the lower reactivity, chlorine is less or equally corrosive to water with
no disinfectant (Cantor 2003). Studies have been conducted to examine the effects of switching
disinfectant from free chlorine to chloramine on lead release. Water disinfected with free
chlorine (target residual concentration 1 mg/L) had approximately one order of magnitude lower
lead concentrations than that with chloramine (target residual concentration 5 mg/L) after 24 h
stagnation (Woszczynski et al., 2013). In a study conducted by Hu et al. (2012), chloraminated
water almost always resulted in increased lead release after both 30 min and 24 hour periods: 49
µg/L and 382 µg/L (5 mg/L chloramine), and 14 µg/L and 73 µg/L in (2 mg/L chloramine),
versus 2 µg/L and 12 µg/L (free chlorine), respectively. This study also showed that increasing a
target chloramine dose from 2 to 5 mg/L resulted in a significant increase in lead release
(α=0.05) (Hu et al., 2012).
Disinfectants also influence lead release by changing the oxidation reduction potential (ORP) of
water. Boyd et al. (2008) reported that free chlorine can raise ORP while chloramine can lower
ORP; elevated ORP may be beneficial in controlling lead release. Free chlorine can oxidize
Pb(II) solids to PbO2 and possibly other Pb(IV) solids, which have lower solubility than Pb(II)
solids (Boyd et al., 2008). However, in a study conducted by Xie and Giammar (2011), free
chlorine was consumed during oxidation of lead, and an increase in dissolved lead was observed
following a free chlorine decline to nearly zero. Switzer et al. (2006) demonstrated that a 0.5-µm
thick lead film (112 µg) almost completely dissolved in chloraminated water (107 µg loss), while
the film remained nearly constant (approximately 0.5 µg loss) with a PbO2 passive layer being
formed. Edwards and Dudi (2004) also suggested that free chlorine can reduce lead
concentration by precipitating lead solid and that chloramine did not have the same effect. Field
samples from Washington DC showed that switching from chloramine to free chlorine decreased
lead after one-hour stagnation and one-minute flushing by a factor of 7.6 to below the lead action
12
limit of 15 µg/L, and when switched back to chloramine, lead concentration increased by a factor
of 13.6 to approximately 120 µg/L (Edwards and Dudi, 2004). Vasquez et al. (2006) reported
that the low and high ORPs generated by chloramine and free chlorine resulted in different
dominant lead solids in chloraminated and chlorinated systems, which were hydrocerussite and
PbO2, respectively. Since hydrocerussite has a higher solubility than PbO2, the difference in
dominant species may have contributed to increased lead release in chloraminated water
(Vasquez et al., 2006).
2.3 Bacterial Regrowth and Biofilm Formation in Distribution
Systems
Application of phosphate-based inhibitors has been effective in reducing lead corrosion from
pipes, however the addition of phosphate can enhance regrowth of bacteria in distribution
systems. Almost 70 % of utilities using phosphate inhibitors surveyed in 2001 identified bacterial
regrowth as a potential drawback (McNeill and Edwards, 2002). When compared to water
leaving a treatment facility (pH 7.4), water in a public works building had a lower pH (7.1),
which was presumably attributed to biological activity, and this location had a greater number of
heterotrophic bacteria (> 500 CFU/L) in the first litter of the samples, while other location had
less than 200 CFU/L in the first litter of water (Gagnon and Doubrough, 2011). Chu et al. (2005)
examined changes in bacterial growth due to addition of phosphate. Heterotrophic plate counts
(HPCs) in biofilm reached a stable level (2.47×105 CFU/cm2) after 6 weeks and significantly
increased to 1.04×106 CFU/cm2 following an addition of 0.01 mg P/L phosphate, but increasing
phosphate dose to 0.05 did not further increase HPCs (Chu et al., 2005). However, in a study by
Batté et al. (2003b), addition of phosphate did not enhance bacterial regrowth. Phosphate
addition can contribute to bacterial regrowth since phosphorus is a nutrient for bacterial growth.
Fang et al. (2009) reported addition of 30 and 300 µg/L of phosphorus decreased
exopolysaccharide (EPS) production by 81% and 77%. However, after 15 and 30 days, addition
of 30 and 300 µg/L of phosphorus increased the biofilm cell metabolic potential by seven and
eight fold to 70.89 and 67.96 MPI (metabolic potential index), respectively (Fang et al., 2009). In
contrast, silicate is not a major nutrient for bacteria and is not considered to contribute to
bacterial regrowth in drinking water distribution systems. The impact of sodium silicate on
13
biofilm formation has not been well reported in the literature. A study conducted by Rompré at
al. (2000) showed that silicate addition did not change biofilm densities while phosphate
inhibitors increased biofilm densities.
Disinfectant type can also impact bacteria in distribution system biofilms. Batté et al. (2003b)
showed that chlorine and chloramine were both effective in reducing biofilm bacteria.
Chlorination treatments (0.75 and 1 mg Cl2/L) decreased total direct count (TDC) cells by more
than 2 log after 7 days from 7.6×106 and 3.0×107 cells/cm2, while monochloramine treatments
(0.6 and 1.9 mg NH2Cl/L) progressively decreased TDC cells by a factor of three and five over a
month from 2.7×107 and 3.0×107 cells/cm2, respectively (Batté et al., 2003b). In contrast,
Murphy et al. (2008) showed that chlorine was more effective than chloramine when disinfectant
dosages were increased. In their study, chlorine achieved a 2.64-log reduction in suspended
Escherichia coli from 8.9×102 CFU/100 mL and reduced the bacteria to below detection limits
(2.65-log reduction following 0.2 mg/L residual for four to five weeks and subsequent 1.0 mg/L
for three weeks, respectively) (Murphy et al., 2008). Chloramine decreased E. coli from 1.6×103
CFU/100 mL to a similar level as the chlorinated water in the same period (1.0 mg/L), but was
not capable of reducing E. coli below the detection limit (Murphy et al., 2008).
3 Materials and Methods
3.1 Experimental Setup
3.1.1 Pipe Loops for Partial Lead Service Line Replacement Study
Three corrosion inhibitors (orthophosphate, zinc orthophosphate, and sodium silicate) were
compared for their effectiveness on decreasing lead release from PRLSLs. To compare the three
corrosion inhibitors with controls (Table 3-1), five recirculation pipe loops were built based on a
design by Wang et al. (2012).
Five aged lead service lines (internal diameter 12.8 ± 0.3 mm; length 0.5 m) were harvested from
a city of Ontario after 63 years of service. Copper pipes (internal diameter 12.7 mm; length 0.5
m) were used as the lead service line replacement material. PVC pipe (internal diameter 13.5
mm, length 0.5 m) was used as the LSLR material for a galvanic connection free control. A
14
plastic spacer separated the lead service line and copper pipe or PVC pipe. An external copper
wire attached at 7 cm on either side of the plastic spacer was used to create and external and
measurable galvanic current (Figure 3-1).
Table 3-1: Pipe Loop Test Section Composition
Figure 3-1: Typical pipe loop system
3.1.2 Pipe Loops for Biofilm Study
Biofilm growth was investigated to examine the effect of water treatment on microbial
population in distribution systems. In addition to the five pipe loops for PLSLR study as
previously described, a sixth recirculation pipe loop was constructed with PVC pipes (internal
diameter 13.5 mm, length 0.5 m) in order to generate a lead-free biofilm as a control. A 50-L
reservoir containing Lake Ontario raw water was used as this pipe loop was used to observe
ID Test Section Corrosion Inhibitor Purpose
1 PVC-PVC No Biofilm Control
2 Pb-PVC No Galvanic Corrosion Control
3 Pb-Cu No Corrosion Inhibitor Control
4 Pb-Cu Orthophosphate Corrosion Inhibitor
5 Pb-Cu Zinc Orthophosphate Corrosion Inhibitor
6 Pb-Cu Sodium Silicate Corrosion Inhibitor
Flow Floating basket
holding biofilm
coupons
Tubing inserted with
biofilm coupons
Floating lid
Recirculation
Reservoir
(90 or 50 L)
Plastic Coupling Sampling
Port
Copper Wire
Pump
Timer
Test Section
Cu or PVC (0.5 m) Pb or PVC (0.5 m)
15
biofilm growth under the same flow and stagnation pattern as the five PLSLR pipe loops (Figure
3-1). The 50-L reservoir was selected due to space constraints.
3.1.3 Lead Release During Stagnation Periods
The recirculating pipe loops were connected to 90-L reservoirs (Cole-Parmer Canada Inc.,
Montreal, QC) holding raw Lake Ontario water, which allows for one complete daily flush of the
system with fresh water, given 120 min of flow per day. Water pumps (Iwaki Co., Ltd., Tokyo,
Japan or Pan World Co., Ltd., Ibaraki, Japan) provided recirculation flow in all pipe loops.
Timers were programmed to simulate a flow rate of 5 L/min for a total 120 min of flow (600
L/day for typical household). The daily flow pattern is shown in Table 3-2.
Table 3-2: Typical Daily Flow Pattern used in Experiments from Friday Evening to Tuesday
evening
Lead release during three stagnation times was examined: 65 h representing a long weekend
(Wang et al., 2012), 6 h (U.S. EPA sampling protocol), and 30 min preceded by a 5-min flush
(based on Ontario Ministry of Environment). The mass of lead released during a stagnation
period was determined by taking both pre-stagnation and post-stagnation samples once a week
for the 65-h stagnation from Tuesday evening (≈ 4 PM) to Friday morning (≈ 9 AM) and twice a
week for 6-h and 30-min stagnations (Figure 3-2). At the end of a weekly cycle, the recirculation
Time Event Duration
8:20 AM-8:25 AM Flow 5 min
8:25 AM-8:35 AM Stagnation 10 min
8:35 AM-9:00 AM Flow 25 min
9:00 AM-3:00 PM Stagnation 6 h (U.S. EPA Sampling)
3:00 PM -3:05 PM Flow 5 min (Ontario MOE Sampling)
3:05 PM -3:35 PM Stagnation 30 min (Ontario MOE Sampling)
3:35 PM -3:55 PM Flow 20 min
3:55 PM-5:55 PM Stagnation 2 h
5:55 PM-6:15 PM Flow 20 min
6:15 PM-9:15 PM Stagnation 3 h
9:15 PM-9:55 PM Flow 40 min
9:55 PM-11:55 PM Stagnation 2 h
11:55 PM-12:00 AM Flow 5 min
12:00 AM-8:00 AM Stagnation 8 h 20 min
16
pump was stopped in order to prepare for acidification of reservoirs and the weekly water change.
Reservoirs were acidified to pH < 2 by the addition of nitric acid (67.0-70.0%, OmniTrace®
nitric acid, EMD Millipore, Billerica, MA) to the bottom 20 L of water for 2 h to ensure that
released particulate lead was captured as it was considered to be an important contributor to the
overall mass balance. All pre-stagnation and both pre and post-acidification samples (0.25 L)
were collected from the reservoirs, and all post-stagnation samples (0.5 L) were collected from
the sampling port (Figure 3-1). Reservoirs were cleaned with tap water and filled with newly
obtained Lake Ontario water for the next cycle.
Mon Recirculation 6-h stagnation Recirculation
Tue Recirculation 65-h stagnation
Wed 65-h stagnation
Thu 65-h stagnation
Fri 65-h stag 6-h stagnation Acidification Water Change Recir.
Sat&Sun Recirculation
Figure 3-2: Weekly Cycle and Sampling Times
The red arrows show sampling times during a weekly cycle.
Pre-stagnation
Post 6-h
stagnation
Post 30-min
stagnation
Pre 65-h
stagnation
Post 6-h
stagnation
Post 30-min
stagnation
30-min stagnation
Pre-acid.
Post 65-h stagnation
Post-acid.
30-min stagnation
17
3.1.4 Mass Balance
Two approaches were used to estimate lead release on a weekly basis: i) theoretical lead release
according to Faraday’s Law based on galvanic current measurement and ii) measurement of
average lead concentrations in the reservoirs.
Estimation of Lead Release from PLSLR Through Galvanic Current
Faraday’s law was used to estimate lead release through galvanic corrosion as given in Equation
3-1 (Dudi, 2004):
Maximum Lead Leaching (g) =I(
coulombs
)×t(s)×207.2g Pb
mole Pb
1.6×10-19(coulomb
e)×6.023×1023(
Pbmole Pb
)×2(e
Pb)
3-1
where, I = current
t = time that current was applied
The procedure for current measurement is described in Section 3.2.2.
Estimation of Lead Release from PLSLR Through Reservoir Assessment
To determine total lead release after seven days including all particulate lead at the bottom of
reservoirs, water in each of the five reservoirs was acidified for 2 h prior to collection of post-
acidification samples. To determine the total mass of lead released during the week, the mass of
lead from the reservoir was added to the mass of lead in the pre and post-stagnation samples.
3.1.5 Experimental Timeline
This study was composed of three phases: a) acclimation, b) CSMR comparison, c) conductivity
comparison and d) chlorine treatment (Table 3-3). During the acclimation period, no galvanic
connection was present between the lead and copper pipes, and water was recirculated through
the systems at a CSMR of 0.2 with no corrosion inhibitors. Acclimation was conducted for 4
weeks until lead levels were stabilized. Once lead release was stabilized, a galvanic connection
between the lead and copper pipes was made using an external copper wire. During the three
“treatment” phases following acclimation, three corrosion inhibitors were added to reservoir
18
water: OP (1 mg P/L), ZOP (1 mg P/L), and sodium silicate (10 mg/L). The CSMR was adjusted
to 0.2 by addition of sodium sulfate in all pipe loop systems for 12 weeks (August to November,
2015), and increased to 1, which was the original CSMR of the raw water, for 6 weeks
(November to December 2015) to compare the performance of the three corrosion inhibitors
under two CSMR conditions. Then, the conductivity was increased while the CSMR was
maintained to be 1 by equally increasing the concentrations of chloride and sulfate (+50 mg/L for
each) to examine the effects of conductivity on lead corrosion and the effectiveness of inhibitors.
The last phase examined the effect of chlorine on the performance of the corrosion inhibitors.
Chlorine was added to achieve a residual concentration range of 1.25-1.5 mg/L as Cl2. Chlorine
was monitored and adjusted on a daily basis for 13 weeks. Microbial growth in both biofilm and
bulk water was monitored as ATP counts from August 2015 May 2016 to compare the condition
without disinfectant and with chlorine.
Table 3-3: Timeline for Experiments
Phase Experimental period Galvanic
current CSMR
Conductivity
(mS/cm) Chlorine
Acclimation July 2015 No 0.2 NM No
Low CSMR August 2015-November
2015 Yes 0.2 550 No
High CSMR-low
conductivity
November 2015-
Decemver 2015 Yes 1 330 No
High CSMR-high
conductivity
December 2015-
February 2016 Yes 1 570 No
High CSMR-high
conductivity-chlorine
February 2016-
May 2016 Yes 1 600 Yes
3.1.6 pH Control in the Reservoirs
The pH of waters in the reservoirs was controlled within the range of 8.0±0.2 by adding 99%
pure CO2 gas (Zhou, 2013) or NaOH (Cartier et al., 2013). CO2 and NaOH were selected in
order to limit changes in water quality through the introduction of ions, such as Cl-. The amount
of NaOH needed to adjust pH was determined by titration. Floating lids made of StyrofoamTM
and wrapped with food wrap were placed on the surface of the water to reduce contact of
19
samples with air and prevent CO2 absorption to maintain target pH. Throughout the experiment,
pH was monitored on a daily basis.
3.1.7 Preparation of A Free Chlorine Working Solution
Free chlorine working solution was prepared by making a 1:50 dilution of a concentrated stock
solution of sodium hypochlorite (approximately 10 to 15%wt) (Sigma-Aldrich Co., Oakville,
Ontario) to approximately 2000 mg/L as Cl2. The concentration of a working solution was
validated by the DPD colorimetric method described in Section 3.2.9. This concentration was
used to calculate the volume of the working solution needed to adjust the free chlorine residual
of 1.25-1.5 mg/L in the reservoirs.
3.2 Analytical Methods
3.2.1 Total and Dissolved Metals (Lead and Copper)
3.2.1.1 Water Samples Collected From Pipe Loop Systems
Samples (0.5 L) from the pipe loop systems were collected from the sampling port (Figure 3-1).
Samples for dissolved lead analysis were prepared by filtering 10 mL samples through 0.45-μm
syringe filters and preserved by adding 0.25% (v/v) nitric acid to pH < 2 according to Standard
Method 3030 B (APHA et al., 2005). The rest of samples were acidified to pH < 2 by addition of
nitric acid for at least 24 h to dissolve particulate lead and filtered through 0.45-μm syringe
filters to collect 10 mL of total lead samples. All samples were stored at 4º C until time of
analysis. Reagents used to prepare samples for analysis are listed.
In order to assess the total mass of lead released on a weekly basis, water in the reservoirs was
acidified to pH < 2 by adding nitric acid after the reservoir water was drained to 20 L from the
top. The acidified water was allowed to sit for 2 h. 0.25 L of samples were collected before and
after acidification for assessment of weekly mass release and prepared as previously described.
Total and dissolved lead concentrations in the samples were determined using inductively
coupled plasma optical emission spectrometry (ICP-OES) with an Optima 7300 DV ICP-OES
20
spectrometer (PerkinElmer, Waltham, MA) based on the U.S. EPA Method 6010B (APHA et al.,
2005). Samples prepared for total lead was simultaneously analyzed for total copper.
3.2.1.2 Biofilm Samples
To analyze dissolved and total lead in biofilm, coupons were collected from the six reservoirs.
Biofilm was removed from both sides of a collected coupon by a clean disposable lead-free
scraper into a clean 15-mL polypropylene tube. All biofilm on each coupon was obtained by
rinsing any remaining biofilm off with Milli-Q water. The volume of the solution with biofilm in
a tube was adjusted to 30 mL, and all samples were mixed thoroughly. For dissolved lead
analysis, half of each sample was filtered using a 0.45-µm syringe filer, and first 5 mL of filtrate
was discarded. To capture the total lead content, including the particulate portion, the remaining
sample was prepared by nitric acid digestion at 105º C for 2 h (Standard Method 3030 E, APHA
et al., 2005). A set of blank control samples was prepared using the same protocol to 30 mL of
Milli-Q water. Dissolved and total lead samples were added with 0.25% (v/v) nitric acid to pH
< 2 according to Standard Method 3030 B (APHA et al., 2005) for preservation and stored at 4º
C until time of analysis using ICP-AES.
3.2.2 Galvanic Current
Galvanic current flowing from the lead to the copper pipes was measured by a multi-meter
(Model#22-811, RadioShack, Fort Worth, TX) with 100-Ω resistance based on the method used
by Nguyen et al. (2011b). The external copper wire connecting the two pipes was removed and
replaced with the multi-meter for 30 sec for the readings.
3.2.3 Alkalinity
Alkalinity of samples was determined by an end-point colorimetric titration procedure based on
Standard Method 2320B (APHA et al., 2005). Each water sample was collected in a 125-mL
amber vial. All vials were capped with Teflon® septum screw caps and were allowed to come to
room temperature (22º C) prior to the analysis. 100 mL of each sample water was obtained in a
250-mL beaker with a stir bar, and the beaker was placed on a magnet stir plate. Five drops of
bromocresol green indicator were added to the solution. Each sample was titrated with 0.02-N
21
sulfuric acid using a burette until the color changed from blue to yellow. The reagents used are
listed in Table 3-4. Alkalinity was calculated using Equation 3-2:
𝐴𝑙𝑘𝑎𝑙𝑖𝑛𝑖𝑡𝑦 (𝑚𝑔 𝐿 𝑎𝑠 𝐶𝑎𝐶𝑂3⁄ ) =
𝐴 × 𝑁 × 50,000
𝑉 3-2
where A = volume of sulfuric acid titrated (mL), N = normality of sulfuric acid (0.02 N), and V
= volume of a sample (100 mL). The procedure was repeated twice to ensure accuracy.
Table 3-4: Reagents for Alkalinity Analysis
Reagent Supplier and Purity
Milli-Q® water Prepared in the laboratory
Sulfuric acid, H2SO4 RICCA Chemical Company, 0.02 N
Bromocresol green VWR International
3.2.4 pH
A laboratory pH meter (Model 8015, VWR Scientific Inc., Mississauga, ON) was used to
determine pH of the samples. Standard buffer solutions of pH 4, 7, and 10 (Canadawide
Scientific, Ottawa, ON) were used for calibration prior to each measurement. All samples and
standard solutions were brought to room temperature prior to analysis. Samples were gently
stirred, and pH readings were taken when readings of the pH meter stabilized and displayed
“Ready”. Milli-Q® water was used to rinse the electrode of the pH meter between samples.
3.2.5 Turbidity
A 2100 N Turbidimeter (HACH Co., Loveland, CO) was used to measure turbidity in
Nephelometric Turbidity Units (NTU). Samples were collected in 40-mL clear glass vials which
were rinsed twice with Milli-Q® water and once with sample prior to measurement.
3.2.6 Total Organic Carbon
TOC samples were collected from containers of raw water immediately after water collection
and each reservoir at the end of weekly cycles. Reagents and instrumental condition used for this
analysis are listed in Table 3-5 and Table 3-6. Each sample was collected in a 40-mL amber glass
vial and capped with a Teflon® lined screw cap (VWR International, Mississauga, ON). A series
22
of calibration standards (0.625, 1.25, 2.5, 5, 10 mg/L TOC) were prepared by dilution of 1-g/L
TOC stock solution, which was prepared by dissolving dry potassium hydrogen phthalate (KHP)
(Sigma-Aldrich Corporation, Oakville, ON) in Milli-Q® water. Milli-Q® water was used as a
blank, and standards were run every 10 samples. TOC were analyzed using a Model 1010 Wet
Oxidation TOC Analyzer with Model 1051 Vial Multi-Sampler (O.I. Analytical, College Station,
TX) based on a wet oxidation method as described in Standard Method 5310 D (APHA et al.,
2005). When preservation was needed, the samples were acidified to pH < 2 by adding 3 drops
of concentrated sulfuric acid and refrigerated at 4º C. TOC concentrations in the samples were
determined from a calibration curve obtained from those calibration standards. The method
detection limit for TOC was 0.07 mg/L, which is the product of the standard deviation of eight
lowest concentrations and the Student’s t-value (3.0).
Table 3-5: Reagents for TOC and DOC Analysis
Reagent Supplier and Purity
Sodium persulfate [Na2S2O8] (100 g/L) Aldrich, 98+%
Potassium hydrogen phthalate [C8H5KO4] Aldrich, 98+%
Sulfuric acid, concentrated [H2SO4] VWR International, 98+%
Table 3-6: Instrumental Conditions for TOC and DOC Analysis
Parameter Condition
Sample Volume 15 mL
Oxidant Volume and Type 1000 μL of 100 g/L sodium persulfate
Acid Volume and Type 200 μL of 5% phosphoric acid
Reaction Time 150 sec
Detection Time 120 sec
Purge Gas Nitrogen
3.2.7 Chloride, Sulfate, Phosphate, Nitrate, and Nitrite
The raw water and reservoir water samples were filtered through a 0.45-µm syringe filer in 1.5-
mL polypropylene vials for measurement of anions. The concentrations of chloride, sulfate,
phosphate, nitrate and nitrite ions were determined by ion chromatography (IC) with a Dionex
ICS-5000 system (Thermo scientific, Sunnyvale, CA) based on the U.S. EPA Method 300.0
(Pfaff, 1993).
23
3.2.8 Silica
For sodium silicate treatment, the concentrations of silica (SiO2) in raw water and the reservoir
water of the sodium silicate system were determined using a DR 2700 Portable
Spectrophotometer (HACH Co., Loveland, CO) according to HACH Silicamolybdate Method
(8185) for a silica range of 1-100 mg/L. Unmodified sample water was used as a blank for the
measurement.
3.2.9 Free Chlorine
Free chlorine were measured according to DPD colorimetric method described in Standard
Method 4500-Cl- (APHA et al., 2005) with a DR 2700 Portable Spectrophotometer (HACH Co.,
Loveland, CO). Unmodified sample water was used as a blank for the measurement. For free
chlorine measurement, each 10-mL sample water was prepared with a DPD free chlorine powder
pillows (HACH Co., Loveland, CO) in a square glass vial. The vial was capped with a glass cap
and shaken rapidly. All samples were allowed to sit for 20 sec for reaction and then analyzed for
absorbance with the spectrophotometer at the wavelength of 530 nm.
3.2.10 ATP
Adenosine triphosphate (ATP) in bulk water samples and biofilm were determined by using
Quench-GoneTM Aqueous test kits and Deposit and Surface Analysis test kits (LuminUltra
Technologies Ltd., Fredericton, NB), respectively. A pre-calibrated luminometer (LuminUltra
Technologies Ltd., Fredericton, NB) was used to determine ATP in the sample in Relative Light
Units (RLU). For bulk water analysis, water samples with a known volume were filtered through
a Quench-Gone syringe filter. Each filter was reattached, and the ATP was extracted with 1-mL
UltraLyse 7 into a 9-mLUltraLuse (Dilution) tube. One hundred-µL of each ATP extract was
transferred to a new 12×55 mm Assay Tube, 100 μL of Luminase was added. Tubes were gently
swirled five times and immediately measured with a luminometer. For biofilm analysis, biofilm
was collected in a 5 mL UltraLyse 7 (Extraction) Tube. Each tube was capped, mixed
thoroughly, and allowed to stand for 5 min. One mL of each ATP solution was transferred into a
new 9 mL UltraLute (Dilution) Tube and mixed by inverting the capped tube three times. One
24
hundred µL of the ATP solution and 100 μL of Luminase were transferred to a new 12×55 mm
Assay Tube. Tubes were swirled five times and immediately measured with a luminometer.
3.3 Statistical Analysis
Confidence intervals were used for comparison of treatments. All statistical analyses were
conducted at the 95% confidence level (Berthouex and Brown, 2002).
25
4 Comparison of Three Corrosion Inhibitors in Simulated
Partial Lead service Line Replacements
4.1 Abstract
The effects of CSMR (0.2 and 1), conductivity (≈330 mS/cm or ≈560 mS/cm) and chlorine
residual (1.4 mg/L) were examined with respect to their effect on lead and copper release at three
different stagnation times (30 min, 6 h, 65 h). Recirculating pipe loops connected to individual
90-L reservoirs were used to simulate a partial lead service line replacement (PLSLR). Three Cu-
Pb pipe loops each received one of three corrosion inhibitors: zinc orthophosphate (1 mg/L as P),
orthophosphate (1 mg/L as P) or sodium silicate (10 mg/L). In addition, one Cu-Pb pipe loop
served as an “inhibitor-free control”; another pipe loop with a PVC-Pb coupling acted as a
“galvanic current-free control”. In this study, changes in water quality (CSMR and conductivity)
were not observed to provide a significant impact on lead or copper release. Although galvanic
corrosion was shown to be a significant driving factor, the mitigating effect of surface
passivation through scale formation coincided with a decrease in released lead. Estimates for
lead released through galvanic currents but stored as corrosion scale ranged from 89.1-91.4%
(corrosion inhibitor-free control), 96.7-98.0% (orthophosphate), 96.1-99.3% (zinc
orthophosphate), and 89.0-96.1% (sodium silicate). Generally, both orthophosphate and zinc
orthophosphate provided better corrosion control for both lead (30 min, 6 h, 65 h) and copper (30
min, 6 h), when compared to either the inhibitor-free control or the sodium silicate treated
system. However, following a 65-h stagnation, evidence of copper deposition in both the
corrosion inhibitor-free control and sodium silicate systems was observed. This work highlights
the importance of understanding the complex interplay of corrosion inhibitors on particulate and
dissolved species when considering both lead and copper.
4.2 Introduction
Installation of lead service lines was banned by the Safe Drinking Water Act in the United States
in 1986 (U.S. EPA, 2015); in Canada in 1975 (for lead pipes) and in 1986 (for solder) (Health
Canada, 2007). In an effort to decrease sources of lead in drinking water, many utilities created
26
lead service line replacement programs, where lead service lines were removed and replaced
with copper. However, the ownership of the service line is shared between the utility and the
homeowner. In cases where the homeowners opted not to replace their portion, it resulted in a
partial lead service line replacement (PLSLR). Lead release from PLSLR has been observed
(even after 14 months) to persist or worsen, even when compared to a 100% lead service line (St.
Clair et al., 2016). Studies by others have identified mechanisms that contribute to these
increases including physical disturbance of scales (Del Toral et al., 2013) and galvanic corrosion
(Triantafyllidou and Edwards, 2010; Triantafyllidou and Edwards, 2011; Wang et al., 2012).
Changes in water quality have also been associated with increases in lead release (Edwards and
Dudi, 2004; Edwards and Triantafyllidou, 2007; Nguyen et al., 2011c; Xie and Giammar, 2011;
Hu et al., 2012;
Chloride-to-sulfate mass ratio (CSMR) has been reported to have an effect on lead release and
may be calculated using the equation shown below (Edwards and Triantafyllidou, 2007).
CSMR=Cl
- (𝑚𝑔 𝐿⁄ )
SO42- (𝑚𝑔 𝐿⁄ )
4-1
CSMR of water can be affected by the compositions of specific coagulants used during drinking
water treatment whereby the application of chloride and sulfate-based coagulants may result in
high and low CSMRs, respectively (Nguyen et al., 2011c). Others have shown that waters with
high CSMR values (1.42-7.1, 0.77, 16.2) can enhance galvanic corrosion (Edwards and
Triantafyllidou, 2007; Nguyen et al., 2011c; Hu et al., 2012). Conductivity tends to increase with
high CSMR, which facilitates galvanic current and subsequently galvanic corrosion (Gregory,
1985; Willison and Boyer, 2012). CSMR values >0.5 can enhance lead corrosion to unacceptably
high levels (Gregory, 1985), 0.58 (Dodrill and Edwards, 1995), and 0.77 (Nguyen et al., 2011b).
Edwards and Triantafyllidou (2007) treated water with polyalminum chloride and alum to
compare high and low CSMR conditions, and reported that the higher CSMR (1.42-4.5) waters
to have 1.5 to 3 times higher lead leaching from solder when compared to low CSMR (≤0.5)
waters. Wang et al. (2013) did not observe an increase in total lead release when increasing
CSMR from 0.7 to 7 and suggested this may be because the initial CSMR had already enhanced
lead corrosion for this system.
27
Chlorine is widely applied as a secondary disinfectant, which may also influence lead release by
changing the oxidation reduction potential (ORP) of water. Free chlorine can oxidize Pb(II)
solids to PbO2 and possibly other Pb(IV) solids, which have lower solubility than Pb(II) solids
(Boyd et al., 2008). However, in a study conducted by Xie and Giammar (2011), free chlorine
was consumed during oxidation of lead, and an increase in dissolved lead was observed
following a free chlorine decline to nearly zero. In addition, Triantafyllidou et al. (2015) reported
the depletion of chlorine for a long stagnation time (74 h) increased lead release by a factor of 3
when compared to a short stagnation (11 h). Edwards and Dudi (2004) suggested that free
chlorine may reduce lead concentration by precipitating lead solid and that chloramine did not
have the same effect.
Phosphate-based inhibitors are commonly applied in drinking water distribution systems to
prevent lead corrosion, and their use has increased from 38% in 1994 to 56% in 2001 (McNeill
and Edwards, 2002). Orthophosphate (OP) is becoming increasingly common, growing from
less than 5% of utilities employing phosphate-based inhibitors in 1994 to approximately 20% in
2001; zinc orthophosphate (ZOP) has been applied at approximately 30% of utilities using
phosphate-based inhibitors (McNeill and Edwards, 2002). Phosphate reacts to form a relatively
insoluble scale which may decrease lead release (Edwards and McNeill, 2002). Zinc ions in a
ZOP corrosion inhibitor can react with carbonate to form a protective layer at the cathode (Volk
et al., 2000), although evidence suggests the advantages of ZOP over sodium OP are
inconclusive and dependant on particular water quality conditions (McNeill and Edwards, 2004).
Tam and Elefsinotis (2009) reported that the addition of sodium OP (0.8 mg P/L) decreased lead
release by 70% for a pH of 7.5 and was also effective at a pH of 8.0. Similarly, Cartier et al.
(2013) showed the addition of OP (phosphoric acid) reduced 64% of lead release (from 72±14 to
26±9 µg/L) for pure lead pipes within 8 days of application. The effectiveness of OP has also
been reported by others (Cardew, 2009; Cartier et al., 2012b; Edwards and McNeill, 2002).
When comparing OP and ZOP, both inhibitors significantly reduced lead release from brass and
solder galvanically connected to copper regardless of CSMR (Edwards and Triantafyllidou,
2007). In their study, OP was shown to have better performance than ZOP in mitigating lead
corrosion for galvanic solder, while ZOP was more effective in preventing corrosion for galvanic
brass. However, there are also three notable considerations regarding the use of phosphate-based
28
corrosion inhibitors: i) association of phosphate-based treatments with particulate lead release
(Cartier et al., 2012b; Wang et al., 2012; Camara et al., 2013; Woszczynski et al., 2015),
especially given the potential for lead particle ingestion (Triantafyllidou et al., 2007); ii)
phosphate could act as a nutrient for bacteria, enhancing microbial growth (McNeill and
Edwards, 2002); and iii) price volatility of the raw material, e.g. an 800% increase in rock
phosphate cost in 2007-2008 (McGill, 2012).
Sodium silicates (Na2SiO3) represent a potential alternative to phosphate-based inhibitors and
have been used in drinking water since the 1920’s (Thompson et al., 1997), but their
effectiveness and mechanism for corrosion control have not been well-documented (Lintereur et
al., 2010). Examination of the effectiveness of sodium silicate may be difficult to distinguish
from the effect of a simultaneous increase in pH following their application. According to
Schock et al. (2005), addition of 25-30 mg/L sodium silicate decreased total lead concentrations
by 55% with a coinciding increase in pH from 6.3 to 7.1; increasing the dose to 45-55 mg/L
further decreased lead concentrations to 15 µg/L with a final pH of 7.5. Lintereur et al. (2010)
also reported that addition of silicate at 3, 6, 12 mg/L above initial doses of 10, 20, 40 mg/L (for
1-4 weeks) was generally effective to mitigate total lead concentrations below the U.S. EPA lead
action level of 15 µg/L (U.S. EPA, 2016), even though a silicate dose of 3 mg/L was less
effective than either 6 and 12 mg/L. Similarly, addition of sodium silicate (40 mg/L), phosphate
(40 mg/L), and a combination of sodium silicate and phosphate (20+20 mg/L) were observed to
be equally effective and reduced lead release from soldered copper coupons after 112 days from
2750 µg/L to < 1 µg/L, 2.8 µg/L, and < 1 µg/L, respectively (Sastri et al., 2006). MacQuarrie et
al. (1997) reported sodium silicate to show some effectiveness in reducing lead release from
brass faucets, while it had no impact on lead release from lead/tin solder coils and increased lead
release from lead soldered copper plumbing coils. Thompson et al. (1997) suggested that silicate
may need a longer time to reduce lead release effectively. Scheetz et al. (1997) reported
increased corrosion of copper and lead pipes may occur as a result of incomplete silica film
formation by filling in the voids on other corrosion products and forming a thin layer over the
existing films. Zhou et al. (2015) reported that the use of monochloramine (compared to
chlorine) was not favorable to lead corrosion control in PLSLR systems treated with sodium
silicates. Additionally, Woszczynski et al. (2015) observed that in comparison to ZOP, SS
29
treated copper pipe rigs with lead tin solder released fewer lead particles than the zinc
orthophosphate system, suggesting an additional benefit to sodium silicate addition.
The primary objective of this study was to compare the performance of three corrosion inhibitors
(OP, ZOP, and sodium silicate) to mitigate lead release in PLSLR. The effect of changes in water
chemistry (CSMR, conductivity, addition of chlorine) on lead release were observed The effect
of corrosion inhibitors on biofilm is also an important consideration, and these results will be
explored in a future study.
4.3 Materials and Methods
4.3.1 Partial Lead Service Line Experimental Setup
Partial lead service line replacement was simulated using aged lead pipes which were harvested
following 63 years of service from a city located in Ontario, Canada. The treated water in this
city can be generally characterized as having moderate alkalinity (≈ 83 mg CaCO3/L), typical of
the Great Lakes, with a chlorine residual. Lead pipes (inner diameter 1.28±0.3 cm) used in this
study were cut into 0.5 m sections and coupled with 0.5 m sections of new copper pipes (inner
diameter 1.27 cm). Insulating plastic spacers (approximately 0.4 mm) were placed between the
copper and lead pipes. The insulating spacer would not be expected to create a significant drop in
current based on observations made in Clark et al. (2013). The two pipe materials were
connected via an external copper wire placed 7 cm from the junction to create an external and
measurable galvanic current. An external wire was used to measure galvanic current. In practice,
lead and copper connections in PLSLR can be made through a number of mechanisms including
direct contact of lead and copper, through a coupling with a third dissimilar metal (e.g. brass),
through a dielectric fitting with an external grounding strap, or through crevice corrosion inside a
connector sleeve (Wang et al., 2012; Clark et al., 2013). However, it should be noted that
connection method of lead and copper has been shown to have a significant effect on lead release.
In Wang et al. (2013), PLSLR connected with a plastic fitting and an external copper wire
provided varied results comparable to a plastic fitting with no external connection between lead
and copper and a brass dielectric fitting; however both were lower than the brass coupling. In
effect, the lead release observed in this study would be anticipated to be lower than if a brass
30
connection were used. Both acclimation and subsequent corrosion inhibitor trials (Table 4-1)
were conducted under alternating stagnant and flow-through conditions using a recirculation
system (Figure 3-1). Untreated Lake Ontario water was selected as the source water as it could
be easily augmented with corrosion inhibitors and disinfectant allowing for greater control over
finished water quality. It should be noted that, with the exception of turbidity, the treatment
processes do not greatly alter the chemical characteristics. The recirculating pipe loops were
connected to 90-L reservoirs holding Lake Ontario water (Table 4-2), which allowed for one
complete daily flush of the system with fresh water, given 120 minutes of flow per day. Typical
Canadian household usage formed the basis of flow rate calculations, and considered an average
household of 2.5 people (Environment and Climate Change Canada, 2011) using 251 L/day
(Statistics Canada, 2011), or approximately 627 L/day, which was rounded to 600 L/day.
Stagnation periods of 6 hours and 30 minutes were used to reflect typical sampling stagnation
periods from various jurisdictions in North America. The long stagnation period (65 h) was
added to reflect a typical long stagnation period (occupants away for a weekend). Recent work
has shown a median flow rate of 1.4 gpm or 5.3 L/min (interquartile range 1.25 gpm [4.7L/min] -
1.88 gpm [7.1L/min]) to be typical of household kitchen faucet use (Welter, 2016).
Recirculating pumps provided flow in all pipe loops. Programmed timers simulated a flow rate
of 5 L/min for a total 120 minutes of flow (600 L/day for typical household).
31
Table 4-1: Experimental conditions for both acclimation and treatment phases (OP, ZOP, sodium silicate)
Phase Experimental
period (weeks)
Galvanic
current CSMR
Conductivity
(mS/cm) Chlorine
Number of samples collected
30 min 6 h 65 h weekly
Acclimation 4 No 0.2 NM No 8 8 4 4
Low CSMR 12 Yes 0.2 550 No 13 13 11 11
High CSMR-low
conductivity 6 Yes 1 330 No 6 6 6 6
High CSMR-high
conductivity 8 Yes 1 570 No 8 8 8 8
High CSMR-high
conductivity-chlorine 9 Yes 1 600 Yes 9 9 9 9
NM represents not measured.
32
Table 4-2: Characteristics of raw Lake Ontario water used for the experiments
Parameter (unit) Average (± standard deviation)
pH 7.9±0.1
Turbidity (NTU) 0.607±0.580
Alkalinity (mg/L as CaCO3) 91.4 ±1.0
TOC (mg/L) 2.3±0.3
Chloride (mg/L) 29.0±3.0
Sulfate (mg/L) 25.6±1.3
Phosphate (mg/L as P) <MDL (0.04 mg/L)
Silicate (mg/L as SiO2) 1.5 ±0.3
4.3.2 Experimental Plan
Timelines and conditions for the acclimation and experimental trials are shown in Table 4-1; the
weekly and daily recirculation and sampling schedules are shown in Table 4-3 and Table 4-4.
Fresh raw water was placed in the recirculation reservoirs on Day 0. Pre-stagnation (0.25 L) and
post-stagnation (0.5 L) samples were subsequently collected following 65-h, 6-h, and 30-min
stagnation periods with a 5-min flush in between on Day 3 and 7. At the end of a weekly cycle,
the reservoirs were drained to a volume of 20 L and acidified to pH<2 by the addition of nitric
acid (67%) for 2 h to ensure that released particulate lead was captured as it was considered to be
an important contributor to the overall mass balance.
pH of the recirculation reservoirs was maintained in a (control) range of 7.8-8.2 using sodium
hydroxide. Sodium silicate addition provided an initial increase to 8.4-8.6 but decrease to
approximately 7.9 (Day 3). The pH of the sodium silicate system was maintained in the control
range from Day 3-7. Lowering pH to the control range (8.0±0.2) on Day 0 would have obscured
the observations of the dual benefit of adding sodium silicate (raising pH and scale formation) to
control lead release by raising pH.
33
Table 4-3: Recirculation event and sample collection for a weekly cycle
Day Recirculation event Sample
Day 0 (Day 7) Reservoir water change/flow (Day 0)
65-h stagnation/flow/reservoir acidification (Day 7)
65 h, 6 h, 30 min,
acidification (Day 7)
Day 1 Flow
Day 2 Flow
Day 3 Flow 6 h, 30 min
Day 4 Flow/65-h stagnation
Day 5 65-h stagnation
Day 6 65-h stagnation
Table 4-4: Event in a weekly cycle
Cycle repeated 4 times a week
Event Duration
Flow 40 min
Stagnation 2 h
Flow 5 min
Stagnation 8 h 20 min
Flow 5 min
Stagnation 10 min
Flow 25 min
Stagnation 6 h
6-h stagnation samples collected, 5 min flush
Stagnation 30 min
30-min stagnation samples collected
Flow 20 min
Stagnation 2 h
Flow 20 min
Stagnation 3 h
1 event per weekly cycle
Stagnation 65 h
65-h stagnation samples collected, 5 min flush
Stagnation 6 h
6-h stagnation samples collected, 5 min flush
Stagnation 30 min
30-min stagnation samples collected
Flow 10 min
2-h acidification of reservoir waters (bottom 20 L)
Acidification samples collected
Water change
34
4.3.3 Experimental Design
This study consisted of an initial acclimation followed by four treatment phases: i) low CSMR,
ii) high CSMR with low conductivity, and iii) high CSMR with high conductivity, and iv) high
CSMR, high conductivity and chlorine (Table 4-1). During acclimation, no galvanic connection
was present between the lead and copper pipes, and no corrosion inhibitors were added. CSMR
was adjusted to 0.2 by addition of 100-mg/L sodium sulfate (Sigma-Aldrich Co., Oakville, ON,
Canada). Acclimation was conducted for 4 weeks until lead levels stabilized within ±15% of the
average lead concentration, consistent with the approach described by Wang et al. (2012).
Stability was defined when a three-week moving average of the dissolved lead release of a
system after 6-h stagnation (following a recirculation period of 3 days) fell within ±15% of the
overall average of the dissolved lead release of the system. The stabilization periods and the use
of control pipe loops (galvanic connection free control and the corrosion inhibitor free control)
were used to establish baselines to observe change.
A galvanic connection was then installed between the lead and copper pipes using an external
copper wire. Three corrosion inhibitors were added during the “treatment” phases: sodium OP 1
mg P/L (Sigma-Aldrich Co.), ZOP 1 mg P/L (Carus Co., LaSalle, IL), and sodium silicate 10
mg/L (National Silicates, Toronto, ON, Canada). To compare their performance under two
CSMR conditions, initially the CSMR was adjusted to 0.2 to represent a “low” value by adding
sodium sulfate for 12 weeks after which it was raised to 1 (the original CSMR of the raw water)
for 6 weeks to represent a “high” value. In addition, conductivity was increased (to a similar
level as the low CSMR phase) for 8 weeks by applying equal amounts of sodium sulfate and
chloride in the high CSMR phase while maintaining a CSMR of 1. Finally, chlorine (24-h free
chlorine residual range of 1.25-1.50 mg/L as Cl2) was added to the systems for 12 weeks. Water
quality data observed during acclimation and the three treatment phases is shown in Table 7-14.
4.3.4 Sample Analysis
Concentrations of chloride, sulfate, and phosphate were measured using ion chromatography (IC)
with a Dionex ICS-5000 system (Thermo scientific, Sunnyvale, CA) according to the U.S. EPA
Method 300. Concentrations of silica and free chlorine were determined using the HACH
35
silicomolybdate Method (8185) for high range (1-100 mg/L) and the DPD colorimetric method
described in Standard Method 4500-Cl-, respectively, with a DR 2700 Portable
Spectrophotometer (HACH Co., Loveland, CO). Total organic carbon (TOC) was analyzed using
a Model 1010 Wet Oxidation TOC Analyzer with a Model 1051 Vial Multi-Sampler (O.I.
Analytical, College Station, TX) based on a wet oxidation method as described in Standard
Method 5310D (APHA et al., 2005). Alkalinity was determined by an end-point colorimetric
titration procedure based on Standard Method 2320B (APHA et al., 2005). Galvanic current
flowing from the lead to the copper pipes was measured using a multi-meter (Model #22-811,
RadioShack, Fort Worth, TX) with 100-Ω resistance based on the method used by Nguyen et al.
(2011b). The external copper wire connecting the two pipes was removed and replaced with the
multi-meter for 30 seconds when taking readings. Conductivity was monitored using a sensION+
MM150 portable Multi-parameter meter (HACH Co., Loveland, CO).
For lead and copper analysis, pre (0.25L) and post (0.5L) stagnation samples were collected from
the recirculation pipe loops (Figure 3-1). Samples for dissolved lead analysis were prepared by
filtering 10 mL of samples through 0.45-μm syringe filters. Millex, PVDF (Millipore, Darmstadt,
Germany) syringe filters used in this experiment were not specifically examined for lead
sorption; however, Cartier et al. (2011) reported the same type of syringe not to sorb significant
quantities of lead. Samples for total lead analysis were prepared by acidification to pH<2 by
adding nitric acid for 24 h and filtering through a 0.45-μm filter according to manufacturer’s
instructions for inductively coupled plasma optical emission spectrometry (ICP-OES). The
method detection limits were 6 µg/L for lead and 5.7 µg/L for copper. All samples were
preserved by adding 0.25 % (v/v) nitric acid according to Standard Method 3030B (APHA et al.,
2005) and stored at 4 ºC until analysis, typically within 2 weeks. Total and dissolved samples
were analyzed for lead and copper using an Optima 7300DV ICP-OES spectrometer
(PerkinElmer, Waltham, MA) in accordance with the U.S. EPA Method 6010B (APHA et al.,
2005).
4.3.5 Statistical Analysis
All statistical analyses were conducted by comparing the 95% confidence intervals (Berthouex
and Brown, 2002).
36
4.4 Results and Discussion
4.4.1 Effects of corrosion inhibitors for different stagnation periods
The Cu-Pb pipe loops treated with OP (1 mg P/L) and ZOP (1 mg P/L) significantly (α=0.05)
decreased both total and dissolved lead release for all stagnation periods. Figure 4-1 shows the
results for three stagnation periods and four experimental conditions, and Table 4-5 presents the
samples which had significant decrease or increase during experimental trials when compared to
the baseline release during acclimation. OP and ZOP decreased total and dissolved lead release
for all stagnation periods and all treatment conditions compared to the acclimation baseline
release. It should be noted that after the addition of chlorine, in the OP system, the total lead
release was significantly lower compared to the acclimation phase. Both total and dissolved lead
significantly increased for the 65 h stagnation periods compared to the high CSMR, high
conductivity (without chlorine) phase. This increase in lead release was not observed in the ZOP
treated systems for any of the stagnation periods. There was no significant difference (α=0.05)
observed when comparing the effectiveness of OP and ZOP for all four conditions following the
30-min stagnation. However, ZOP showed better performance overall and had significantly
(α=0.05) lower total and dissolved lead release for the 6-h stagnation for high CSMR with high
conductivity, as well as the 65-h stagnation for CSMR with high and low conductivity. For
example, at the 65 stagnation, high CSMR, high conductivity condition, the total lead release in
the OP system was 22 µg/L and 6 µg/L in ZOP system. This result was consistent with a study
by Edwards and Triantafyllidou (2007), which showed ZOP was more effective than OP in
preventing lead release from galvanic brass and copper systems. Generally, the application of
sodium silicate treatment did not significantly (α=0.05) decrease total or dissolved lead release
when compared to the acclimation baseline (with a few exceptions) or the OP and ZOP
treatments. Although high CSMR and high conductivity should theoretically have created
conditions more conducive to corrosion, the total lead release in the sodium silicate system
decreased, possibly as a result of the slow formation of a sodium silicate based passivation layer
as suggested by Thompson et al., 1997; Pinto et al., 1997, and Schock et al., 2005. Sodium
silicates (25-30 mg/L) had previously been demonstrated to decrease lead release in a full scale
37
study by 55% (Schock et al., 2005), however only after six months of treatment. Similarly, in this
study sodium silicate treatment decreased lead following six months of treatment.
Longer stagnation periods (6 h and 65 h) resulted in significantly higher total and dissolved lead
concentrations in both the control and sodium silicate systems (Figure 4-1). Generally, for the
OP and ZOP systems, the average dissolved lead release increased slightly but remained <15
µg/L with the exception of the average total lead release for OP with high CMSR high
conductivity. When lead release (during different stagnation periods) was compared for the two
control systems and sodium silicate system, approximately half of lead release for 65-h
stagnation occurred in 6 h, indicating that the rate of release decreased with time. Lytle and
Schock (2000) observed lead concentrations to increase exponentially over a 90-h stagnation,
with 50-70% lead release in the first 10 h. Woszczynski et al. (2015) also showed lead release to
be higher in 24-h stagnation samples when compared to the 30-min stagnation samples for
treatment using zinc orthophosphate or sodium silicate, with or without pH control.
38
Figure 4-1: Comparison of average dissolved (blue) and particulate (black) lead release for each
corrosion inhibitors (a. 30 min, b. 6 h, c. 65 h). Vertical bars represent the 95% CI. The numbers
above the columns show the particulate lead fractions in the total lead release.
48 23 44 29
5814
15 13 22 37 1130 27 36 53
1049
77 82 8917 21 9 23
47
0
20
40
60
80
100
120
140
160
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:
Sodium
silicate
Lea
d r
elea
se (
µg/L
)
1715
19 27
53
9
57 14 36 9
37 28 21 47
12
3363 59 56
13 10 4
946
0
20
40
60
80
100
120
140
160
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:
Sodium
silicate
Lea
d r
elea
se (
µg/L
)
26
1612
23
42 14
87 12
17
17
38 2231
25
11
2156 52 46
1713
10
1335
0
20
40
60
80
100
120
140
160
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:
Sodium
silicate
Lea
d r
elea
se (
µg/L
)
Acclimation (No corrosion inhibitor) Low CSMR
High CSMR-low conductivity High CSMR-high conductivity
High CSMR-high conductivity-chlorine USEPA lead action limit (15 µg/L)
a)
b)
c)
39
Table 4-5: Comparison of dissolved and total lead release (± standard deviation)
Stagnation Experimental
condition
Dissolved lead release (µg/L) Total lead release (µg/L)
PVC-Pb:
No
corrosion
inhibitor
Cu-Pb:
No
corrosion
inhibitor
Cu-Pb:
OP
Cu-Pb:
ZOP
Cu-Pb:
Sodium
silicate
PVC-Pb:
No
corrosion
inhibitor
Cu-Pb:
No
corrosion
inhibitor
Cu-Pb:
OP
Cu-Pb:
ZOP
Cu-Pb:
Sodium
silicate
30 min
Acclimation 4±2 12±3 13±3 14±4 15±4 8±2 14±3 15±3 15±4 18±4
Low CSMR 6±5 18±4 4±5 4±5 14±7 8±5 21±5 6±5 8±7 18±6
High CSMR-low
conductivity 3±2 14±2 2±2 0±1 17±1 5±3 16±2 3±3 2±2 19±2
High CSMR-high
conductivity 5±1 15±2 3±1 1±1 11±2 8±2 19±3 4±2 3±3 14±2
High CSMR-high
conductivity-
chlorine
6±4 11±4 2±1 1±1 10±4 20±14 19±5 4±2 5±3 23±10
6 h
Acclimation 16±4 31±4 38±5 38±7 42±9 19±4 34±2 42±5 43±6 49±9
Low CSMR 23±5 54±10 7±6 10±10 45±10 27±6 57±10 11±6 14±9 50±11
High CSMR-low
conductivity 17±4 47±4 6±3 2±2 53±4 21±6 51±6 8±6 5±5 55±3
High CSMR-high
conductivity 18±3 40±4 8±2 2±2 33±5 20±2 47±3 10±3 4±3 37±5
High CSMR-high
conductivity-
chlorine
15±4 27±10 5±3 3±2 23±5 45±35 46±16 11±4 8±3 46±10
65 h
Acclimation 46±13 82±11 102±17 123±15 85±21 62±20 95±11 123±17 138±23 103±27
Low CSMR 32±8 101±24 9±5 12±10 83±21 38±9 110±26 15±6 15±11 96±25
High CSMR-low
conductivity 28±6 96±14 11±4 2±1 98±21 32±4 103±16 14±4 5±4 109±23
High CSMR-high
conductivity 32±7 90±5 15±5 3±3 54±10 42±9 102±16 22±5 6±3 63±13
High CSMR-high
conductivity-
chlorine
44±6 51±2 29±1 5±2 42±12 76±25 62±17 39±9 9±3 65±18
Lead release from each system during experimental trials was compared to the lead release during acclimation (compared vertically). The
values shaded in blue present significant decrease, and the cells shaded in orange present significant increase (α=0.05).
40
4.4.2 Effects of CMSR and conductivity
The anticipated effects of CSMR on lead release or the performance of the corrosion inhibitors
were not observed to be significant (α=0.05) for any of the conditions examined. Triantafyllidou
and Edwards (2010) reported higher galvanic current in galvanically connected lead and copper
pipes for waters with high CSMRs, which resulted in increased lead release by a factor of 2 to 5.
As such, it was anticipated that by increasing the CSMR from 0.2 to 1 there would be a
subsequent increase in lead release, however lead release did not significantly increase for any of
the five systems and the three stagnation periods prior to chlorine addition. However, Wang et al.
(2013) observed in their study that an increase in CSMR from 0.7 to 7 did not result in an
increase in lead release, and the authors cited the combined effect of high bicarbonate an the
presence of orthophosphate as possible mitigating factors.
Two levels of conductivity were investigated for the high CSMR conditions. Conductivity during
low CSMR was approximately 550 mS/cm and was approximately 330 mS/cm at high CSMR.
However, these two conditions may not be directly compared due to differences in conductivity.
To eliminate conductivity as a confounding factor, it was increased to a similar level as for the
low CSMR condition (≈570 mS/cm). Galvanic current slightly decreased at the high CSMR-low
conductivity (Figure 4-2); however, the change was not significant. Galvanic current increased in
all systems for the high CSMR-high conductivity with significant increases for the ZOP and
sodium silicate systems; however neither showed an increase in lead release. Effects of corrosion
inhibitors appeared to outweigh the impacts of both CSMR and conductivity. Willison and Boyer
(2012) compared waters with the same CSMR with different chloride and sulfate concentrations
and suggested that galvanic current increased as a result of higher conductivity which potentially
caused higher lead release. Nguyen et al. (2011a) examined the effects of conductivity using
sodium bicarbonate and sodium perchlorate and reported that increasing conductivity
exacerbated total lead release and increased current density. In the present study, increasing
conductivity resulted in increased galvanic current only for the ZOP and sodium silicate systems
which did not translate into subsequent increases in lead release. For example, the average
galvanic current during the flow period (Figure 4-2) significantly increased from 9.4 to 12.6 µA
in the ZOP system and from 10.4 to 20.2 µA in the sodium silicate system. The total and
dissolved lead release remained the same for the ZOP system and decreased in the sodium
41
silicate system (Figure 4-1), indicating that the corrosion inhibitors prevented lead corrosion by
forming a protective layer and precipitating lead. The average galvanic current during the 65-h
stagnation increased significantly only for the sodium silicate system (from 3.4 to 6.0 mS/cm).
Contrary to the increase in galvanic current, lead release from this system for high CSMR-high
conductivity was significantly lower than that for high CSMR-low conductivity conditions. This
is likely an artefact of the suspected slow formation of a sodium silicate based passivation layer
(Thompson et al., 1997; Pinto et al., 1997; Schock et al., 2005).
Figure 4-2: Galvanic current in Cu-Pb systems during three treatment phases. Vertical bars
represent the 95% CI.
0.0
5.0
10.0
15.0
20.0
25.0
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:
Sodium
silicate
Gal
van
ic c
urr
ent
( µ
A)
Flow, low CSMR
Flow, high CSMR- low
conductivity
Flow, high CSMR-high
conductivity
Flow, high CSMR-high
conductivity-chlorine
65-h stagnation, low CSMR
65-h stagnation, high CSMR-low
conductivity
65-h stagnation, high CSMR-high
conductivity
65-h stagnation, high CSMR-high
conductivity-chlorine
42
4.4.3 Effects of Galvanic corrosion
The PVC-Pb pipe loop served as a “control” for lead release and did not have a galvanic
connection or receive a corrosion inhibitor. This pipe loop showed relatively small but
significant increase in dissolved lead concentrations, from 16 (acclimation) to 23 µg/L (low
CSMR), for the 6-h stagnation (Figure 4-1b). The Cu-Pb system with no corrosion inhibitor
provided a “control” when considering corrosion inhibitors with galvanic corrosion and showed
that the connection between Cu-Pb pipes significantly (α=0.05) increased lead release for both 6-
h stagnation samples and 30-min stagnation samples collected after 3 days of the flow period (2
h/day, Figure 4-1). Once the galvanic connection was made for the low CSMR, dissolved and
total lead release from the Cu-Pb system with no corrosion inhibitor significantly increased in
both the 6-h stagnation and 30-min stagnation samples (Table 4-5).
The observed total lead release from the Cu-Pb system with no corrosion inhibitor during the low
CSMR condition was approximately 11% of the theoretical lead leaching as estimated from the
observed galvanic currents (Figure 4-2) using Faraday’s Law, assuming 100% of galvanic
current is associated with lead release (Dudi, 2004).
Maximum Lead Leaching (g) =I(
coulombs
)×t(s)×207.2g Pb
mole Pb
1.6×10-19(coulomb
e)×6.023×1023(
Pbmole Pb
)×2(e
Pb)
4-2
Predicted vs. observed total lead release is shown in Figure 4-3; 89.1-91.4% of lead theoretically
released due to galvanic corrosion was stored as corrosion scale in the Cu-Pb system with no
corrosion inhibitor. In the OP and ZOP systems, 96.7% and 96.1% of theoretically released lead
was assumed to be stored as a corrosion scale after being released during low CSMR, these
increased to 98.0% and 98.8% for high CSMR-low conductivity, and 98.0% and 99.3% for high
CSMR-high conductivity, and 97.6% and 98.5% for the chlorine treatment, respectively. The
sodium silicate system showed 90.9%, 89.0%, 96.1% and 92.8% of theoretically released lead
was stored for low CSMR, high CMSR-low conductivity and high CSMR-high conductivity, and
chlorine conditions, respectively. Nguyen et al. (2010) reported that only 25% of theoretical lead
release was observed from a pure lead wire connected to a Cu pipe via an external Cu wire.
Similarly, an estimated 91-96% of released lead was presumed to be stored as a corrosion scale
43
in a flow-through PLSLR simulated system (Cartier et al., 2012a). Results were also consistent
with the observations by Zhou et al. (2015) where 67-98% of the theoretically released lead
based on galvanic current in sodium silicate treated PLSLR systems was stored in corrosion scale
under various water quality conditions.
The impact of galvanic corrosion was also observed in the average weekly lead release (Figure
4-4). When a galvanic connection was completed during low CSMR conditions, lead release
increased in the Cu-Pb system with no corrosion inhibitor, while lead release decreased in other
systems. Average weekly lead release continuously decreased with time during acclimation and
for the three treatment scenarios as scale formation occurred.
44
Figure 4-3: Predicted vs. observed total lead release for 6-h stagnation period under conditions
of a) low CSMR, b) high CSMR-low conductivity, c) high CSMR-high conductivity, and d) high
CSMR-high conductivity-chlorine.
0
10
20
30
40
50
60
0 100 200 300 400 500 600 700
Ob
serv
ed t
ota
l le
ad
rele
ase
(µg)
Predicted total lead release (µg)
0
10
20
30
40
50
60
0 100 200 300 400 500 600 700
Ob
serv
ed t
ota
l le
ad
rele
ase
(µg)
Predicted total lead release (µg)
0
10
20
30
40
50
60
0 100 200 300 400 500 600 700
Ob
serv
ed t
ota
l le
ad
rele
ase
(µg)
Predicted total lead release (µg)
0
10
20
30
40
50
60
0 200 400 600
Ob
serv
ed t
ota
l le
ad
rele
ase
(µg)
Predicted total lead release (µg)
Cu-Pb: No corrosion
inhibitor
Cu-Pb: OP
Cu-Pb: ZOP
Cu-Pb: Sodium silicate
Linear (1:1)
c)
b)
a)
d)
45
Figure 4-4: Average weekly lead release. Vertical bars represent the 95% CI.
0
1000
2000
3000
4000
5000
6000
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:
Sodium
Silicate
Aver
age
wee
kly
lea
d r
elea
se (
µg)
Acclimation (No corrosion inhibitor) Low CSMR
High CSMR-low conductivity High CSMR-high conductivity
High CSMR-high conductivity-chlorine
46
4.4.4 Comparison of dissolved and particulate lead release
Addition of corrosion inhibitors and chlorine impacted dissolved and total lead release
differently. When compared to the controls and the sodium silicate, the OP and ZOP systems had
higher proportions of particulate lead. Even though the increases were not statistically significant
(α=0.05) due to large variations, the percentages of particulate lead release for the 6-h stagnation
increased from 9% during acclimation to a high of 47% in the high CSMR, high conductivity,
chlorine phase for the OP system, and from 12% in the acclimation phase to a high of 56% in the
high CSMR low conductivity phase as well as the high CSMR, high conductivity, chlorine phase
for the ZOP system (Figure 4-1). In contrast, Cu-Pb with no corrosion inhibitor and the sodium
silicate system had relatively stable particulate results for acclimation, with particulates
comprising 9% in the acclimation phase and a high of 36% in the high CSMR, high conductivity,
chlorine phase. For the sodium silicate system, the particulate fraction was 13% in the
acclimation phase and 46% in the high CSMR, high conductivity, chlorine phase. The results
from this study indicate that the phosphate-based inhibitors decreased dissolved lead release. Xie
and Giammar (2011) reported that 49% of the total lead release from lead pipes receiving
phosphate treatment was particulate while <10% was particulate lead in pipes without phosphate
treatment (with high DIC, free chlorine, or monochloramine). Woszczynski et al. (2015) also
reported that systems treated with phosphate had a higher average percentage of particulate lead
(49%) when compared to sodium silicate, with and without pH control (28% and 36%). McNeill
and Edwards (2004) reported ZOP achieved better performance for preventing soluble lead
release than OP for most conditions but that use of ZOP tended to increase particulate lead
release. Cartier et al. (2012b) also observed an association between orthophosphate and
particulate lead when observing brass fixtures, as orthophosphate reacts with dissolved but not
particulate lead. Similarly, Edwards and Dudi (2004) observed that phosphate addition decrease
soluble lead over a wide range of pHs (7.5, 8.25, and 9). Additionally, Edwards and Dudi (2004)
observed that at higher pH (where chlorine is a less powerful oxidant), insoluble solids took
longer to form, suggesting that chlorine plays a role in stable scale formation.
Clark et al. (2014) suggested that lead release may be a function of flow rate, where lead levels
can be 4 times higher when collected at medium flow rates (3-10 L/min) when compared to low
flow first draw samples (1 L/min). The durability of the scale also plays a factor in how much
47
lead is released; for example, Clark et al. (2014) observed that for corrosion controlled samples,
with non-durable scale, lead release was erratic and dominated by particulate lead (100%
particulate) at a high flow rate (4-14 L/min). The apparent discrepancy between observations for
sodium silicate treated systems were in medium to high flow systems (this study [5L/min], and
Woszczynski et al., 2015) where dissolved lead dominated. For stagnant, low flow studies with
dump and fill protocols (Zhou et al., 2015) particulate species dominated, suggesting that sodium
silicate scale formation and subsequent lead release are also affected by flow regime.
Past studies have also shown less soluble Pb(IV) oxide forms in chlorinated water, limiting the
release of dissolved lead (Lytle et al., 2009; Lytle and Schock, 2005).
4.4.5 Copper release during acclimation and treatment
In this study, copper release for 30-min, 6-h, and 65-h stagnations was simultaneously monitored
with lead release during the acclimation and the three treatment phases. Copper release (Figure
4-5) was calculated by subtracting the pre-stagnation from post-stagnation concentrations. The
copper present in the pre-stagnation samples was a result of copper release from previous flow
cycles (background copper). Negative releases suggest that a lower copper concentration existed
after stagnation, indicating deposition has occurred. Dissolved copper release for both 30-min
and 6-h stagnations during acclimation were similar for the four systems containing copper pipe:
29-34 µg/L for 30-min stagnation (Figure 4-5a), 168-217 µg/L for 6-h stagnation (Figure 4-5b).
Following galvanic connection, copper release decreased in all Cu-Pb systems, including the
control which did not receive inhibitor, suggesting that cathodic protection played at least a
partial role in decreasing the release. In terms of corrosion inhibitor performance similar trends
were observed as for lead, where both OP and ZOP systems released significantly (α=0.05) less
copper than either the control or the sodium silicate for both 30-min and 6-h stagnation times.
For the 65-h stagnation, copper deposition was observed in both the corrosion inhibitor free
control and the sodium silicate treated system; whereas a net release was observed in both the OP
and ZOP systems suggesting that for phosphate treated systems copper is not preferentially
precipitated. Results from the PVC-Pb system showed a negligible contribution to copper
48
release from legacy deposits on the harvested lead pipe. Clark et al. (2015) demonstrated that
copper deposition can be a significant corrosion mechanism in galvanically coupled lead and
copper pipes. The extent of copper deposition was also demonstrated to be correlated to the
theoretical copper solubility in the test water and the magnitude of lead release (Clark et al.,
2015). Although this study was not specifically designed to examine the contribution of copper
deposition corrosion, it is plausible that copper deposition may have occurred and could
therefore have played a contributing role; however, scale analysis would be necessary to verify.
When particulate copper fractions in pre and post-stagnation samples were compared, the relative
amounts of copper tended to decrease following stagnation. However, since release and
deposition of copper probably occurred at the same time, all mechanisms including dissolution,
deposition of particles, precipitation, and galvanic corrosion, would be confounding factors. For
the Cu-Pb system with no corrosion inhibitor, the OP and sodium silicate systems, particulate
fractions in pre and post 6-h stagnation samples showed similar decrease for the experimental
conditions. In contrast, the ZOP system showed a higher particulate fraction in both pre and post
6-h stagnation samples for the same set of conditions.
Copper release showed complementary results to the effect of corrosion inhibitors for galvanic
corrosion. Decreases in copper release for 65-h stagnation in the Cu-Pb system with no corrosion
inhibitor and the sodium silicate system showed galvanic corrosion occurred and that copper ions
were consumed as well as decreases in copper concentrations by long stagnations. Addition of
OP and ZOP effectively reduced copper release in the present study. Dartmann et al. (2010)
reported a phosphate protective layer was formed on copper pipe surface after 26 weeks of
operation and that phosphate could prevent oxidation of metallic copper to ions by blocking
active sites on the pipe surface. Edwards et al. (2002) observed that although phosphate-based
corrosion inhibitors promote the formation of cupric phosphate scales, these scales can ultimately
prove less effective for controlling copper release over the long term.
Increasing CSMR resulted in an increased copper release for 30-min and 6-h stagnations but
decreased copper release in 65-h stagnation. CSMR may have an effect on copper corrosion but
other factors such as length of stagnation and presence or absence of corrosion inhibitors are
likely more significant. Wang et al. (2013) reported plastic-coupled non-galvanic systems of
49
copper tubing and lead pipe to have highest increases in copper release when stagnation was
increased from 6 h to 65 h. It was suggested that released copper accumulated in the solution as
the effect of cathodic protection decreased as a result of galvanic current decrease. Lytle and
Schock (2000) showed copper release from copper tubing to non-softened water reached a
maximum in approximately 8 h of stagnation then gradually decreased following 72-92 h of
stagnation.
Similar to observations made for lead release, copper release also increased with increased
stagnation time. The addition of chlorine consistently and significantly increased copper release
when compared to the high chlorine, high CSMR (without chlorine treatment) for the 65 h
stagnation period. Cantor et al. (2003), reported chlorinated to have higher copper concentrations
than untreated water. The presence of chlorine may have a stronger effect on copper release than
corrosion inhibitors and galvanic corrosion, which would decrease copper release.
50
Figure 4-5: Comparison of average dissolved (blue) and particulate (black) copper release for
each corrosion inhibitors (a. 30 min, b. 6 h, c. 65 h). Vertical bars represent the 95% CI.
-100
-50
0
50
100
150
200
250
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:
Sodium
silicate
Co
pp
er r
elea
se (
µg/L
)
-100
-50
0
50
100
150
200
250
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:
Sodium
silicate
Co
pp
er r
elea
se (
µg/L
)
-100
-50
0
50
100
150
200
250
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:
Sodium
silicate
Co
pp
er r
elea
se (
µg/L
)
Acclimation (No corrosion inhibitor) Low CSMR
High CSMR-low conductivity High CSMR-high conductivity
High CSMR-high conductivity-chlorine
b)
c)
a)
51
4.5 Conclusions
In this study, both ZOP and OP were observed to effectively decrease lead release following
application. Their performance was unaffected by changes in CSMR (0.2 and 1) or conductivity
(approximately 330 mS/cm and 550-570 mS/cm). In comparison, addition of sodium silicate did
not effectively decrease lead release. It should be noted however that sodium silicate did
significantly decrease lead after six months, corroborating evidence from other studies that
suggest that a longer surface passivation period is required. ZOP and OP provided significantly
greater decreases in both total and dissolved lead release when compared to sodium silicates.
Chlorine initially increased particulate lead release, but its presence decreased dissolved lead
release in most systems.
Similar observations were made for copper control, where both OP and ZOP provided significant
decreases following 30-min and 6-h stagnation times. Following 65-h stagnation, there was
evidence that copper deposition had occurred in both the corrosion inhibitor free control and
sodium silicate treated systems which have important implications for lead release. Mechanisms
of differences between inhibitor performances could be revealed by an autopsy analysis of pipe
scales and should be considered in future studies. Utilities operating systems where lead and
copper couplings occur (PLSLR) should consider the impact of the corrosion control strategy on
copper control. This research highlights the complex interplay of corrosion inhibitor, metal
fractions (particulate or dissolved), stagnation time and copper deposition on the management of
lead and copper release from PLSLR.
52
5 Impact of Corrosion Control on Biofilm Development in
Simulated Partial Lead Service Line Replacements
5.1 Abstract
The interaction of water quality, flow conditions, and the presence of lead and biofilm was
examined. Recirculating pipe loops connected to individual 90-L reservoirs were used to
simulate a partial lead service line replacement (PLSLR). PVC coupons were placed in the
reservoirs in stagnant or active flow positions. Various water quality conditions CSMR (0.2 and
1), conductivity (≈330 mS/cm or ≈560 mS/cm) and chlorine residual (1.4 mg/L) were examined
in conjunction with three corrosion inhibitors orthophosphate (1 mg/L as P), zinc orthophosphate
(1 mg/L as P) or sodium silicate (10 mg/L). In addition, one Cu-Pb pipe loop served as an
“inhibitor-free control,” whereas another with a PVC-Pb coupling acted as a “galvanic current-
free control.” Phosphate-based corrosion inhibitors were not observed to act as a source of
nutrient for biofilm growth. However, a strong correlation was observed between the presence of
lead and biofilm density, with densities ranging from 0.06 µg/cm2 to 0.81 µg/cm2 prior to
chlorination (high CSMR, high conductivity) and 0.04 µg/cm2 to 0.21 µg/cm2 in the presence of
chlorine (high CSMR, high conductivity). This work highlights the potential for biofilm to act as
a potential reservoir for lead and underscores the value of including biofilm evaluation when
selecting corrosion inhibitors.
5.2 Introduction
Application of phosphate-based inhibitors has been effective in reducing lead corrosion from
pipes and is applied by approximately 56% of U.S. based utilities (McNeill and Edwards, 2002).
However, phosphate addition can contribute to bacterial regrowth since phosphorus serves as a
nutrient for bacteria. Bacterial regrowth was identified as a potential drawback in 70% of U.S.
based utilities using phosphate inhibitors surveyed in 2001 (McNeill and Edwards, 2002).
There have been conflicting reports of the role of phosphate. Several studies have shown that the
addition of phosphate enhances bacteria growth in drinking water (Chu et al., 2005; Fang et al.,
53
2009; Payne et al., 2016; Lehtola et al., 2002); whereas in other cases phosphate was not
observed to enhance bacteria growth (Batté et al., 2003b). Chu et al. (2005) reported
heterotrophic plate counts (HPCs) in biofilm to reach a stable level (2.47×105 CFU/cm2) after 6
weeks and significantly increase to 1.04×106 CFU/cm2 following the addition of 0.01 mg P/L
phosphate, but the increasing phosphate dose to 0.05 did not result in a further increase. Fang et
al. (2009) reported addition of 30 and 300 µg/L of phosphorus to decrease exopolysaccharide
(EPS) production by 81% and 77%, respectively. However, after 15 and 30 days, addition of 30
and 300 µg/L of phosphorus increased the biofilm cell metabolic potential by seven and eight
fold to 70.89 and 67.96 MPI (metabolic potential index). Payne et al. (2016) observed that 3 mg-
PO4/L resulted in significantly higher biofilm on PVC coupons compared to a control in lead and
copper impacted environments. The same authors reported phosphate addition to increase
biofilm community diversity, which has been demonstrated to have important implications for
disinfection effectiveness by Simões et al. (2010).
The role of surface area on biofilm growth has been implied in several studies (Camper et al.,
2003; Ollos et al., 2003; Payne, 2013). Recent studies have demonstrated that zinc
orthophosphate treated lead systems are dominated by particles, compared to dissolved species
(Cartier et al., 2012b; Camara et al., 2013; Woszczynski et al., 2013). It is hypothesized that
increased particles, could act to increase available surface area for biofilm growth, thus
increasing biofilm density. In contrast, silicate is not a major nutrient for bacteria and as such
does not contribute to bacterial regrowth in drinking water distribution systems.
This study explored the complex interrelationship of lead particles, biofilm growth, the absence
and presence of chlorine, and corrosion inhibitor type (orthophosphate, zinc orthophosphate and
sodium silicate).
54
5.3 Materials and Methods
5.3.1 Partial lead service line setup
Partial lead service line replacement was simulated using aged lead pipes which were harvested
following 63 years of service from a city located in Ontario, Canada. Lead pipes (internal
diameter 1.28±0.3 cm) used in this study were cut into 0.5 m sections and were coupled with 0.5
m sections of new copper pipes (internal diameter 1.27 cm). Insulating plastic spacers were
placed between the copper and lead pipes. The two pipe materials were connected via an external
copper wire placed 7 cm from the junction to create an external and measurable galvanic current.
Periods of the acclimation and subsequent corrosion inhibitor trials (Table 5-1) were conducted
under alternating stagnant and flow-through conditions using a recirculation system (Figure 3-1).
To facilitate biofilm collection, polycarbonate coupons (approximate surface area 45 cm2; length
15 cm) subjected to stagnant conditions were inserted in each reservoir. Coupons subjected to
flow-through conditions were connected to the effluent of pipe loops.
Recirculating pipe loops were connected to 90-L reservoirs holding Lake Ontario water (Table
5-2), which allowed for one complete daily flush of the system with fresh water, given 120 min
of flow per day. Recirculating pumps provided flow in all pipe loops. Timers were programmed
to simulate a flow rate of 5 L/min for a total 120 min of flow (600 L/day for typical household)
with alternating stagnation periods ranging from 10 min to 8 h 20 min. To serve a control for
biofilm analysis, a similar system with a 50-L reservoir and PVC pipe sections was used.
55
Table 5-1: Experimental conditions for both acclimation and corrosion inhibitor trials (OP, ZOP, and sodium silicate)
Phase Experimental
period (weeks)
Galvanic
current CSMR
Conductivity
(mS/cm)
Chlorine residual
(mg/L)
Number of biofilm samples collected
ATP Pb and Cu
Acclimation 4 No 0.2 NM 0 0 0
Low CSMR 12 Yes 0.2 550 0 4 0
High CSMR-low
conductivity 6 Yes 1 330 0 2 0
High CSMR-high
conductivity 8 Yes 1 570 0 2 2
High CSMR-high
conductivity-
chlorine
13 Yes 1 600 1.4 8 8
56
Table 5-2: Raw water quality
Parameter (unit) Average (± standard deviation)
pH 7.9±0.1
Turbidity (NTU) 0.607±0.580
Alkalinity (mg/L as CaCO3) 91.4 ±1.0
TOC (mg/L) 2.3±0.3
Nitrate (mg/L) 1.56±0.24 mg/L
Nitrite (mg/L) <MDL (0.57 mg/L)
Phosphate (mg/L as P) <MDL (0.04 mg/L)
Silicate (mg/L as SiO2) 1.5 ±0.3
ATP (ng/100 mL) 0.06±0.02
5.3.2 Experimental plan
Following 4 weeks of acclimation (Table 5-1), a galvanic connection was installed between the
lead and copper pipes using an external copper wire and maintained during four “treatment”
phases of low CSMR, high CSMR-low conductivity, high CSMR-high conductivity, and high
CSMR-high conductivity-chlorine. Three corrosion inhibitors were added during the treatment
phases: sodium orthophosphate (OP) 1 mg P/L (Sigma-Aldrich Co.), zinc orthophosphate (ZOP)
1 mg P/L (Carus Co., LaSalle, IL), and sodium silicate 10 mg/L (National Silicates, Toronto,
ON, Canada).
A 42-day biofilm development period was used, consistent with previous studies (Gagnon et al.,
2004, 2005; Rand et al., 2007; Payne et al., 2016). One set of polycarbonate coupons under
stagnant and flow-through conditions was collected from each reservoirs and used for ATP
analysis. During phases with high CSMR-high conductivity and high CSMR-high conductivity-
chlorine conditions, each coupon was cut in half; one piece was used for ATP analysis and the
other for analysis of lead accumulating in biofilm.
5.3.3 Sample Analysis
5.3.3.1 Analysis of water quality parameters
A laboratory pH meter (Model 8015, VWR Scientific Inc., Mississauga, ON) was used to
determine pH. Concentrations of chloride, sulfate, and phosphate were measured using ion
chromatography (IC) with a Dionex ICS-5000 system (Thermo Scientific, Sunnyvale, CA)
57
according to the U.S. EPA Method 300.0 (Pfaff, 1993). Silica and free chlorine were determined
using a HACH silicomolybdate Method (8185) and the DPD colorimetric method described in
Standard Method 4500-Cl- (APHA et al., 2005), respectively, with a DR 2700 Portable
Spectrophotometer (HACH Co., Loveland, CO). Total organic carbon (TOC) was analyzed using
a Model 1010 Wet Oxidation TOC Analyzer with a Model 1051 Vial Multi-Sampler (O.I.
Analytical, College Station, TX) based on a wet oxidation method as described in Standard
Method 5310 D (APHA et al., 2005). Alkalinity was measured using an end-point colorimetric
titration procedure based on Standard Method 2320 B (APHA et al., 2005). Galvanic current
flowing from the lead to the copper pipes was measured by a multi-meter (Model #22-811,
RadioShack, Fort Worth, TX) with 100-Ω resistance based on the method used by Nguyen et al.
(2011b). The external copper wire connecting the two pipes was removed and replaced with the
multi-meter for 30 sec to obtain readings. Conductivity was monitored using a sensION+
MM150 portable Multi-parameter meter (HACH Co., Loveland, CO).
5.3.3.2 Analysis of ATP
Adenosine triphosphate (ATP) in biofilm and raw water samples were determined by using
Quench-GoneTM Aqueous test kits and Deposit and Surface Analysis test kits (LuminUltra
Technologies Ltd., Fredericton, NB), respectively, with a pre-calibrated luminometer
(LuminUltra Technologies Ltd., Fredericton, NB). Half of each coupons was used for ATP
analysis for biofilm, leaving the left for lead and copper analyses.
5.3.3.3 Analysis of dissolved and total lead in biofilm
To analyze dissolved and total lead in biofilm, half of the coupons were collected from the six
reservoirs. Biofilm was removed from both sides of a collected coupon by a clean disposable
lead-free scraper into a clean 15-mL polypropylene tube. All biofilm on each coupon was
obtained by rinsing any remaining biofilm with Milli-Q water. The volume of the solution was
adjusted to 30 mL, and all samples were mixed thoroughly. For dissolved lead analysis, half of
each sample was filtered using a 0.45-µm syringe filer, discarding the first 5 mL of filtrate. To
capture the total lead, including the particulate portion, the remaining sample and coupons were
prepared using nitric acid digestion at 105º C for 2 h (Standard Method 3030 E, APHA et al.,
2005). For both dissolved and total lead samples, 0.25% (v/v) nitric acid was added to pH <2
according to Standard Method 3030 B (APHA et al., 2005) for preservation and stored at 4º C
58
until analysis using ICP-AES. Method detection limit for lead and copper were 6.0 and 5.7 µg/L,
respectively.
5.3.4 Estimation of lead released through galvanic current
The theoretical amount of lead released through galvanic currents was estimated using Faraday’s
law (Dudi, 2004).
5.3.5 Statistical Analysis
Confidence intervals were used for comparison of treatments. All statistical analyses were
conducted at the 95% confidence level (Berthouex and Brown, 2002).
5.4 Results and Discussion
5.4.1 Effects of corrosion inhibitors on biofilm growth under stagnant and
flow-through conditions
Biofilm on polycarbonate coupons under stagnant and flow-through conditions (Figure 3-1) was
measured to determine the impact of corrosion inhibitors and flow conditions on microbial
growth (Figure 5-1). In general, prior to chlorination, biofilm growth under stagnant conditions
tended to have higher ATP densities when compared to flow-through conditions, with the OP
system having the highest ATP during the high CSMR high conductivity trial. Under flow
conditions, prior to chlorination, ZOP had significantly higher ATP counts for the low CSMR
and high CSMR high conductivity trials.
Chlorination significantly decreased ATP densities in all systems. A 0.9 to 2.2 and 1.0 to 2.0-log
reduction was observed under stagnant condition and flow-through condition, respectively (Table
5-3). Notably, the biofilm was more resistant to disinfection when considering flow through
conditions. Biofilm cohesiveness has been reported to increase after exposure to shear stress (0.2
Pa-10 Pa), Mathieu et al. (2014), consistent with observations by others that biofilm volumetric
Maximum Lead Leaching (g) =I(
coulombs
)×t(s)×207.2g Pb
mole Pb
1.6×10-19(coulomb
e)×6.023×1023(
Pbmole Pb
)×2(e
Pb)
5-1
59
density increases under higher flow velocities (Garny et al., 2008). Lehtola et al. (2006) also
observed an increase in biofilm with increasing flow rate for both copper and plastic pipes. Ollos
et al. (2003) compared two levels of shear stress (0.4 and 2.0 N/m2) and suggested lower shear
stress (or flow) may limit biofilm accumulation by reducing mass transfer of biodegradable
organic matter.
The presence of particles may also play a role in biofilm accumulation by creating more
available surface area for growth. A correlation between lead trapped in the biofilm for the high
CSMR-high conductivity and the high CSMR-high conductivity-chlorine were compared (Figure
5-2); positive correlations were observed for all systems where lead was available.
Lead accumulating in biofilm was measured to determine the effect of corrosion inhibitors. For
all systems containing lead pipes, approximately 96-99% and 96-99% of lead accumulating in
biofilm under stagnant and flow-through conditions, respectively, was in the form of particulate
for non-chlorinated-high CSMR-high conductivity condition (Table 5-4). In the presence of
chlorine, the amount of lead accumulation decreased with the inactivation and detachment of
biofilm. Approximately 85-98% and 92-98% of lead stored in biofilm under stagnant and flow-
through conditions was of particulate form in the chlorinated water.
Typically, trends of ATP and lead accumulation were consistent, suggesting that the density of
biofilm impacted lead storage capacity (Figure 5-1; Figure 5-3). Higher amounts of lead
accumulating in stagnant biofilm were observed for the systems with higher ATP densities under
non-chlorinated conditions, such as the corrosion inhibitor-free Cu-Pb, OP, and sodium silicate
systems. When considering non-chlorinated flow-through conditions, the highest lead
accumulation was observed in the ZOP system, consistent with the highest ATP density. Under
chlorinated condition, the average ATP and lead accumulation were less correlated. The biofilm
under flow-through condition in the ZOP system stored a larger amount of lead both in non-
chlorinated and chlorinated conditions, when compared to other systems. While the average ATP
densities were similar for all systems, the amounts of lead remained high only in the ZOP system
for chlorinated flow-through trial. The ZOP system released more lead particles due to the
apparent effect of ZOP (Payne 2013; Woszczynski et al, 2013) and entrapped them in biofilm
during flow. In contrast, the phosphate-enriched OP system had low accumulation even though it
had the second highest ATP density. Systems with greater ATP densities tended to have better
60
correlations with lead accumulation. Past studies have reported systems with ductile iron to have
greater HPCs than systems with plastic pipes when considering a range of chlorine
concentrations (Camper et al., 2003) and carbon levels (Ollos et al., 2003). The same researchers
hypothesized that surface area played a role. Accumulation of lead particles in biofilm increased
surface area, and it is plausible that the presence of lead particles in biofilm conversely affected
microbial growth. Similarly, total copper was also observed to accumulate in biofilm (Figure 5-4;
Figure 5-5) with positive correlations between ATP and copper accumulation.
The ability of phosphate to serve as a nutrient was also examined. Comparison to a phosphate-
free sodium silicate system did not reveal any clear trends (Figure 5-1). Rompré et al. (2000)
reported that the mass of biofilm was not significantly different in phosphate systems when
compared to sodium silicate treated systems and concluded that the surface was a key factor
influencing biofilm development. In this study, phosphate does not act as a nutrient. Batté et al.
(2003a) observed that P addition did not enhance biofilm growth in a carbon limited
environment, and the authors deduced that the added P was stored in the extracellular matrix of
the biofilm.
Table 5-3: Log reduction in ATP in stagnant and flow-through biofilm by chlorination
System Log reduction
Stagnant Flow-through
PVC-PVC: No corrosion inhibitor 0.9 1.0
PVC-Pb: No corrosion inhibitor 1.3 1.2
Cu-Pb: No corrosion inhibitor 2.0 1.3
Cu-Pb: OP 2.2 1.5
Cu-Pb: ZOP 1.3 2.0
Cu-Pb: Sodium silicate 2.0 1.3
61
Figure 5-1: ATP accumulation under a) stagnant and b) flow-through conditions. n=4, 2, 2, and
8 for low CSMR, high CSMR-low conductivity, high CSMR-high conductivity, and high
CSMR-high conductivity-chlorine phases. Vertical bars represent 95% CI.
0.0
1.0
2.0
3.0
Low CSMR High CSMR-low
conductivity
High CSMR-high
conductivity
High CSMR-high
conductivity-chlorine
Lo
g1
0 (
AT
P n
g/c
m2)
0.0
1.0
2.0
3.0
Low CSMR High CSMR-low
conductivity
High CSMR-high
conductivity
High CSMR-high
conductivity-chlorine
Lo
g1
0 (
AT
P n
g/c
m2)
PVC-PVC: No corrosion inhibitor PVC-Pb: No corrosion inhibitor
Cu-Pb: No corrosion inhibitor Cu-Pb: OP
Cu-Pb: ZOP Cu-Pb: Sodium silicate
a)
b)
62
Figure 5-2: Total lead and ATP accumulation under a) stagnant and b) flow-through conditions
(linear regression). n=10.
R² = 0.1582
R² = 0.9523R² = 0.9756
R² = 0.9379
R² = 0.8101
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.00 0.20 0.40 0.60 0.80 1.00
AT
P (
ng/c
m2)
Total lead in biofilm (µg/cm2)
R² = 0.9056R² = 0.8579
R² = 0.503
R² = 0.8309R² = 0.5663
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.00 0.20 0.40 0.60 0.80 1.00
AT
P (
ng/c
m2)
Total lead in biofilm (µg/cm2)
PVC-PVC: No corrosion inhibitor PVC-Pb: No corrosion inhibitor
Cu-Pb: No corrosion inhibitor Cu-Pb: OP
Cu-Pb: ZOP Cu-Pb: Sodium silicate
b)
a)
63
Figure 5-3: Lead accumulating in biofilm under a) stagnant and b) flow-through conditions with
and without chlorination. n=2 and 8 for high CSMR-high conductivity and high CSMR-high
conductivity-chlorine phases. Vertical bars represent 95% CI.
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
High CSMR-high conductivity High CSMR-high conductivity-chlorine
To
tal
lead
in b
iofi
lm (
µg/c
m2)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
High CSMR-high conductivity High CSMR-high conductivity-chlorine
To
tal
lead
in b
iofi
lm (
µg/c
m2)
PVC-PVC: No corrosion inhibitor PVC-Pb: No corrosion inhibitor
Cu-Pb: No corrosion inhibitor Cu-Pb: OP
Cu-Pb: ZOP Cu-Pb: Sodium silicate
b)
a)
64
Figure 5-4: Copper accumulating in biofilm under a) stagnant and b) flow-through conditions
with and without chlorination. n=10.
R² = 0.4804
R² = 0.9869R² = 0.991
R² = 0.8571
R² = 0.9771
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.00 0.20 0.40 0.60 0.80 1.00
AT
P (
ng/c
m2)
Total copper in biofilm (µg/cm2)
R² = 0.8774 R² = 0.7547
R² = 0.8494 R² = 0.8891
R² = 0.5671
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.00 0.20 0.40 0.60 0.80 1.00
AT
P (
ng/c
m2)
Total copper in biofim (µg/cm2)
PVC-PVC: No corrosion inhibitor PVC-Pb: No corrosion inhibitor
Cu-Pb: No corrosion inhibitor Cu-Pb: OP
Cu-Pb: ZOP Cu-Pb: Sodium silicate
b)
a)
65
Figure 5-5: Copper accumulating in biofilm under a) stagnant and b) flow-through conditions
with and without chlorination. n=2 and 8 for high CSMR-high conductivity and high CSMR-
high conductivity-chlorine phases. Vertical bars represent 95% CI.
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
High CSMR-high conductivity High CSMR-high conductivity-chlorine
To
tal
cop
per
in b
iofi
lm (
µg/c
m2)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
High CSMR-high conductivity High CSMR-high conductivity-chlorine
To
tal
cop
per
in b
iofi
lm (
µg/c
m2)
PVC-PVC: No corrosion inhibitor PVC-Pb: No corrosion inhibitor
Cu-Pb: No corrosion inhibitor Cu-Pb: OP
Cu-Pb: ZOP Cu-Pb: Sodium silicate
66
Table 5-4: Particulate lead fraction in biofilm and bulk water (at the end of a weekly cycle)
Particulate fraction in total lead (%)
Acclimation Low CSMR High CSMR-
low
conductivity
High CSMR-
high
conductivity
High CSMR-
high
conductivity-
chlorine
Weekly lead
release in bulk
water
PVC-PVC: No corrosion inhibitor - - - - -
PVC-Pb: No corrosion inhibitor 12 20 35 19 24
Cu-Pb: No corrosion inhibitor 10 19 22 17 21
Cu-Pb: OP 11 47 69 41 48
Cu-Pb: ZOP 9 74 85 80 81
Cu-Pb: Sodium silicate 17 34 28 17 26
Stagnant
biofilm
PVC-PVC: No corrosion inhibitor - - - - 75
PVC-Pb: No corrosion inhibitor - - - 96 95
Cu-Pb: No corrosion inhibitor - - - 98 96
Cu-Pb: OP - - - 99 98
Cu-Pb: ZOP - - - 98 85
Cu-Pb: Sodium silicate - - - 99 96
Flow-through
biofilm
PVC-PVC: No corrosion inhibitor - - - 84 73
PVC-Pb: No corrosion inhibitor - - - 98 92
Cu-Pb: No corrosion inhibitor - - - 98 98
Cu-Pb: OP - - - 96 92
Cu-Pb: ZOP - - - 99 96
Cu-Pb: Sodium silicate - - - 99 96
The dash (-) refers to the results which samples were not collected or no lead was detected in the samples.
67
5.4.2 Estimation of capacity of biofilm for storing lead
During the initial weeks of chlorination, total lead release increased in the bulk water. This may
be partially attributed to release of biofilm containing lead particles. The capacity of biofilm for
storing lead was estimated based on observed ATP and lead densities for the flow-through
system, and an approximate wetted surface area of the pipe section. It was assumed that ATP and
lead densities in biofilm were similar throughout the system.
At the end of the high CSMR-high conductivity trial, 0.3-1.7% of the theoretical cumulative
mass release of lead was accumulated in the biofilm: 0.3, 0.1, 1.7, and 0.3% was observed for the
inhibitor free control, OP, ZOP, and sodium silicate (Table 5-5). Biofilm densities were
significantly lower for chlorinated water (Figure 5-1; Table 5-5). The biomass was estimated to
contain only 0.0-0.3% of theoretically released lead.
The capacity of biofilm to sorb lead is an important consideration as biofilm can be mobilized
during disinfection, physical disturbances. In order to quantify the impact biofilm associated
lead, estimates were made for a theoretical pipe (1 m long, 1cm diameter) under flow conditions
using lead-biofilm densities observed in this study (Table 5-5). Based on a 1m pipe (1 cm
diameter), the lead capacity prior to chlorination (high CSMR-high conductivity ranged from
20.1 to 254.5 µg. Following chlorination, the lead capacity ranged from 12.4 to 66.2 µg. Lehtola
et al. (2006) observed that copper concentrations increased in bulk water following periods of
flow, attributing it to detached biofilm. Similarly, Ginige et al. (2011) reported that biofilm
inactivation can release trapped Fe and Mn in biofilm, resulting in increased Mn concentrations.
Thus, the capacity of biofilm to act as a reservoir for lead is important, as detached biofilm could
potentially release a significant quantity of lead.
68
Table 5-5: Estimation of lead storing capacity of biofilm and removal from theoretical weekly mass release
High CSMR-high conductivity High CSMR-high conductivity-chlorine
Density
(µg/cm2)
Removal from
weekly mass
release (%)
Capacity
(µg)
Density
(µg/cm2)
Removal from
weekly mass
release (%)
Capacity
(µg)
PVC-PVC: No corrosion inhibitor 0.00 NA NA 0.00 NA NA
PVC-Pb: No corrosion inhibitor 0.14 NA 42.9 0.04 NA 14.0
Cu-Pb: No corrosion inhibitor 0.18 0.3 57.0 0.05 0.1 14.9
Cu-Pb: OP 0.06 0.1 20.1 0.04 0.0 12.4
Cu-Pb: ZOP 0.81 1.7 254.5 0.21 0.3 66.2
Cu-Pb: Sodium silicate 0.22 0.3 68.1 0.06 0.0 17.9
The capacities for storing lead were estimated for wetted internal surface area of a 1-m long pipe with 1-cm internal diameter
(approximate surface area of 314 cm2).
The weekly mass release of the systems was estimated based on daily galvanic current.
69
5.5 Conclusion
This study examined the impacts of various water quality and flow conditions, corrosion
inhibitors and chlorine disinfectant on biofilm growth and lead accumulation in biofilm. In this
study, the phosphate-based corrosion inhibitors (ZOP, OP) were not observed to act as a nutrient,
as in this water type microbial growth was likely limited by carbon. There was, however, a
strong correlation between the presence of lead and ATP, suggesting that lead particles may
provide surface area for biofilm growth. The results also suggest that biofilm could represent a
significant reservoir for lead storage and subsequent release. This work highlights the potential
for biofilm to act as a potential reservoir for lead, which could be released under changing water
quality conditions, and underscores the value of including biofilm assessment when selecting
corrosion inhibitors.
70
6 References
American Public Health Association (APHA), American Water Works Association (AWWA),
and Water Environment Federation (WEF). (2005) Standard methods for the examination
of water and wastewater, twenty first ed. (Washington, DC, USA).
Berthouex, P.M. and Brown, L.C. (2002) Statistics for Environmental Engineers. 2nd Edition.
CRC Press, Boca Raton, Florida
Batté, M., Koudjonou, B., Laurent, P., Mathieu, L., Coallier, J., and Prévost, M. (2003a) Biofilm
responses to ageing and to a high phosphate load in a bench-scale drinking water system.
Water Research 37, 1351-1361.
Batté, M., Mathieu, L., Laurent, P., and Prévost, M. (2003b) Influence of phosphate and
disinfection on the composition of biofilms produced from drinking water, as measured
by fluorescence in situ hybridization. Canadian Journal of Microbiology 49, 741-753.
Boyd, G.R., Dewis, K.M., Korshin, G.V., Reiber, S.H., Schock, M.R., and Sandvig, A.M. (2008)
Effects of changing disinfectants on lead and copper release. Journal American Water
Works Association 100 (11), 75-87.
Boyd, G.R., Shetty, P., Sandvig, A.M., and Pierson G.L. (2004) Pb in tap water following
simulated partial lead pipe replacements. Journal of environmental Engineering 130,
1188-1197.
Brown, M.J., Raymond, J., Homa, D., Kennedy, C., and Sinks, T. (2011) Association between
children’s blood lead levels, lead service lines, and water disinfection, Washington, DC,
1998-2006. Environmental Research 111, 67-74.
Camara, E., Montreuil, K.R., Knowles, A.K., and Gagnon, G.A. (2013) Role of the water main in
lead service line replacement: a utility case study. Journal American Water Works
Association 105 (8), E423-E431.
71
Camper, A.K., Brastrup, K., Sandvig A., Clement, J., Spencer C., and Capuzzi A.J. (2003) Effect
of distribution system materials on bacterial regrowth. Journal American Water Works
Association 95 (7), 107-121.
Cantor, A.F., Park, J.K., and Vaiyavatjamai, P. (2003) Effect of chlorine on corrosion in drinking
water systems. Journal American Water Works Association 95 (5), 112-123.
Cardew, P.T. (2009) Measuring the benefit of orthophosphate treatment on lead in drinking
water. Journal of Water and Health 7 (1), 123-131.
Cartier, C., Laroche, L., Deshommes, E., Nour, S., Richard, G., Edwards, M., and Prévost, M.
(2011) Investigating dissolved lead at the tap using various sampling protocols. Journal
American Water Works Association 103 (3), 55-67.
Cartier, C., Arnold, R.B., Triantafyllidou, S., Prévost, M., and Edwards, M. (2012a) Effect of
flow rate and lead/copper pipe sequence on lead release from service lines. Water
Research 46 (13), 4142-4152.
Cartier, C., Nour, S., Richer, B., Deshommes, E., and Prévost, M. (2012b) Impact of water
treatment on the contribution of faucets to dissolved and particulate lead release at the
tap. Water Research 46, 5205-5216.
Cartier, C., Doré, E., Laroche, L., Nour, S., Edwards, M., and Prévost, M. (2013) Impact of
treatment on Pb release from full and partially replaced harvested lead service lines
(LSLs). Water Research 47 (2), 661-671.
Chu, C., Lu, C., and Lee, C. (2005) Effects of inorganic nutrients on the regrowth of
heterotrophic bacteria in drinking water distribution systems. Journal of Environmental
Management 74, 255-263.
Churchill, D.M., Mavinic, D.S., Neden, D.G., and MacQuarrie, D.M. (2000) The effect of zinc
orthophosphate and pH-alkalinity adjustment on metal levels leached into drinking water.
Canadian Journal of Civil Engineering 27, 33-43.
72
Clark, B., Cartier, C., St. Clair, J., Triantafyllidou, S., Prévost, M., Edwards, M. 2013. Effect of
connection type on galvanic corrosion between lead and copper pipes. Journal American
Water Works Association 105(10), E576-E586.
Clark, B., Masters, S., and Edwards, M. (2014) Profile sampling to characterize particulate lead
risks in potable water. Environmental Science & Technology 48, 6836-6843.
Clark, B., St. Clair, J., and Edwards, M. (2015) Copper deposition corrosion elevated lead release
to potable water. Journal American Water Works Association 107 (11), E627-E637.
Dart, J.F. and Foley, P.D. (1970) Preventing iron deposition with sodium silicate. Journal
American Water Works Association 62 (10), 663-668.
Dartmann, J., Sadlowsky, B., Dorsch, T., and Johannsen, K. (2010) Copper corrosion in drinking
water systems – effect of pH and phosphate-dosage. Materials and Corrosion 61 (3), 189-
198.
Del Toral, M.A., Porter, A., and Schock, M.R. (2013) Detection and evaluation of elevated lead
release from service lines: a field study. Environmental Science & Technology 47(16),
9300-9307.
Deshommes, E. and Prévost, M. (2012) Pb particles from tap water: bioaccessibility and
contribution to child exposure. Environmental Science & Technology 46, 6269-6277.
Dodrill, D.M. and Edwards, M. (1995) Corrosion control on the basis of utility experience.
Journal American Water Works Association 87, 74-85.
Dudi, A. (2004) Reconsidering lead corrosion in drinking water: product testing, direct
chloramine attack and galvanic corrosion (MSc. thesis). Virginia Polytechnic Institute:
Blacksburg, VA, USA.
Edwards, M., Jacobs, S., and Dodrill, D. (1999) Desktop guidance for mitigating Pb and Cu
corrosion by-products. Journal: American Water Works Association 91 (5), 66-77.
73
Edwards, M. and Dudi, A. (2004). Role of chlorine and chloramine in corrosion of lead-bearing
plumbing materials. Journal American Water Works Association 96 (10), 69-81.
Edwards, M., Hidmi, L., and Gladwell, D. (2002) Phosphate inhibition of soluble copper
corrosion by-product release. Corrosion Science 44 (5), 1057-1071.
Edwards, M. and McNeill, L.S. (2002) Effect of phosphate inhibitors on lead release from pipes.
Journal American Water Works Association 94 (1), 79-90.
Edwards, M.A. and Triantafyllidou, S. (2007) Chloride-to-sulfate mass ratio and lead leaching to
water. Journal American Water Works Association 99 (7), 96- 109.
Environment and Climate Change Canada (2011) Residential water use in Canada.
https://www.ec.gc.ca/indicateurs-indicators/default.asp?lang=en&n=7E808512-1
(accessed June 2016)
Fang, W., Hu, J.Y., and Ong, S.L. (2009) Influence of phosphorus on biofilm formation in model
drinking water distribution systems. Journal of Applied Microbiology 106, 1328-1335.
Gagnon, G.A. and Doubrough J.D. (2011) Lead release from premise plumbing: a profile of
sample collection and pilot studies from a small system. Canadian Journal of Civil
Engineering 38, 741-750.
Gagnon, G.A., O’Leary, K.C., Volk, C.J., Chauret, C., Stover, L., and Andrews, R.C. (2004)
Comparative analysis of chlorine dioxide, free chlorine and chloramines on bacterial
water quality in model distribution systems. Journal of Environmental Engineering 130
(11), 1269-1279.
Gagnon, G.A., Rand, J.L., O’Leary, K.C., Rygel, A.C., Chauret, C., and Andrews, R.C. (2005)
Disinfectant efficacy of chlorite and chlorine dioxide in drinking water biofilms. Water
Research 39 (9), 1809-1817.
Garny, K., Horn, H., and Neu, T.R. (2008) Interaction between biofilm development, structure
and detachment in rotating annular reactors. Bioprocess and Biosystems Engineering 31,
619-629.
74
Ginige, M.P., Wylie, J., and Plumb, J. (2011) Influence of biofilms on iron and manganese
deposition in drinking water distribution systems. Biofouling 27 (2), 151-163.
Gregory, R. (1985) Galvanic corrosion of lead in copper pipework: phase I, measurement of
galvanic corrosion potential in selected waters. Water Research Centre Engineering.
Swindon, England.
Hu, J., Gan, F., Triantafyllidou, S., Nguyen, C.K., and Edwards, M.A. (2012) Copper-induced
metal release from lead pipe into drinking water. Corrosion 68 (11), 1037-1048.
Health Canada (2007) Water talk: minimizing exposure to lead from drinking water distribution
systems. http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/lead-plomb-eng.php (accessed
March 2016).
Health Canada (2013) Final Human Health State of the Science Report of Lead. http://www.hc-
sc.gc.ca/ewh-semt/pubs/contaminants/dhhssrl-rpecscepsh/index-eng.php (accessed July
2016).
Hozalski, R.M., Esbri-Amador, E., and Chen, C.F. (2005) Comparison of stannous chloride and
phosphate for lead corrosion control. Journal: American Water Works Association 97 (3),
89-103.
Hu, J., Gan, F., Triantafyllidou, S., Nguyen, C.K., and Edwards, M.A. (2012) Copper-induced
metal release from lead pipe into drinking water. Corrosion 68 (11), 1037-1048.
Kennedy, C., Yard, E., Dignam, T., Buchanan, S., Condon, S., Brown M.J., Raymond J., Rogers,
H.S., Sarisky, J., de Castro R., Arias, I., and Breysse, P. (2016) Blood Lead Levels
Among Children Aged <6 Years — Flint, Michigan, 2013–2016. Morbidity and
Mortality Weekly Report. ePub: 24 June 2016. DOI:
http://dx.doi.org/10.15585/mmwr.mm6525e1 (accessed July, 2016).
Kim, E.J. and Herrera, J.E. (2010) Characteristics of lead corrosion scales formed during
drinking water distribution and their potential influence on the release of lead and other
contaminants. Environmental Science & Technology 44, 6054-6061.
75
Lehtola, M.J., Miettinen, I.T., and Martikainen, P.J. (2002) Biofilm formation in drinking water
affected by low concentrations of phosphorus. Canadian Journal of Microbiology 48,
4994-499.
Lehtola, M.J., Laxander, M., Miettinen, I.T., Hirvonen, A., Vartiainen, T., and Martikainen, P.J.
(2006) The effects of changing water flow velocity on the formation of biofilms and
water quality in pilot distribution system consisting of copper or polyethylene pipes.
Water Research 40, 2151-2160.
Lintereur, P.A., Duranceau, S.J., Taylor, J.S., and Stone, E.D. (2010) Sodium silicate impacts on
lead release in a blended potable water distribution system. Desalination and Water
Treatment 16, 427-438.
Lytle, D.A. and Schock, M.R. (2000) Impact of stagnation time on metal dissolution from
plumbing materials in drinking water. Journal of Water Supply: Research and
Technology-AQUA 49 (5), 243-257.
Lytle, D.A. and Schock, M.R. (2005) Formation of Pb(IV) oxides in chlorinated water. Journal
American Water Works Association 97 (11), 102-114.
Lytle, D.A., Schock, M.R., and Scheckel, K. (2009) The inhibition of Pb(IV) oxide formation in
chlorinated water by orthophosphate. Environmental Science & Technology 43, 6624-
6631.
MacQuarrie, D.M., Mavinic, D.S., and Neden, D.G. (1997) Greater Vancouver Water District
drinking water corrosion inhibitor testing. Canadian Journal of Civil Engineering 24, 34-
52.
Mathieu, L., Bertrand, I., Abe, Y., Angel, E., Block, J.C., Skali-Lami, S., and Francius, G. (2014)
Drinking water biofilm cohesiveness changes under chlorination or hydrodynamic stress.
Water Research 55, 175-184.
McGill, S.M. (2012) ‘Peak’ phosphorous? The implications of phosphate scarcity for sustainable
investors. Journal of Sustainable Finance and Investment 2 (3-4), 222-239.
76
McNeill, L.S. and Edwards, M. (2002) Phosphate inhibitor use at US utilities. Journal American
Water Works Association 94 (7), 57-63.
McNeill, L.S. and Edwards, M. (2004) Importance of Pb and Cu particulate species for corrosion
control. Journal of Environmental Engineering 130, 136-144.
Murphy, H.M., Payne, S.J., Gagnon, G.A. (2008) Sequential UV- and chlorine-based
disinfection to mitigate Escherichia coli in drinking water biofilms. Water Research 42,
2083-2092.
Nguyen, C.K., Stone, K.R., Dudi, A., and Edwards, M.A. (2010) Corrosive Microenvironments
at lead solder surfaces arising from galvanic corrosion with copper pipe. Environmental
Science & Technology 44 (18), 7076-7081.
Nguyen, C.K., Clark, B.N., Stone, K.R., and Edwards, M.A. (2011a) Acceleration of galvanic
lead solder corrosion due to phosphate. Corrosion Science 53, 1515-1521.
Nguyen, C.K., Clark, B.N., Stone, K.R., and Edwards, M.A. (2011b) Role of chloride, sulfate,
and alkalinity on galvanic lead corrosion. Corrosion 67 (6), E1-9.
Nguyen, C.K., Stone, K.R., and Edwards, M.A. (2011c) Chloride-to-sulfate mass ratio: practical
studies in galvanic corrosion of lead solder. Journal American Water Works Association
103 (1), 81-92.
Noel, J.D., Wang, Y., and Giammar, D.E. (2014) Effect of water chemistry on the dissolution
rate of the lead corrosion product hydrocerussite. Water Research 54, 237-246.
Ollos, P.J., Huck, P.M., and Slawson, R.M. (2003) Factors affecting biofilm accumulation in
model distribution systems. Journal American Water Works Association 95 (1), 87-97.
Payne, S.J.O. (2013) Interactions of corrosion control and biofilm on lead and copper in premise
plumbing (Ph. D. dissertation). Dalhousie University, Halifax, Nova Scotia, Canada.
Payne, S., Piorkowski, G.S., Truelstrup Hansen, L., and Gagnon, G.A. (2016) Impact of zinc
orthophosphate on simulated drinking water biofilms influenced by lead and copper.
Journal of Environmental Engineering 142 (2), 04015067.
77
Pfaff, J.D. (1993) Method 300.0 Determination of inorganic anions by ion chromatography. U.S.
Environmental Protection Agency, Cincinnati, Ohio, USA.
Pinto, J.A., McAnally, A.S., and Flora, J.R. (1997) Evaluation of lead and copper corrosion
control techniques. Journal of Environmental Science and Health A 32 (1), 31-53.
Rand, J.L., Hoffman, R., Alam, M.Z.B., Chauret, C., Cantwell, R., Andrews, R.C., and Gagnon,
G. A. (2007) A field study evaluation for mitigating biofouling with chlorine dioxide or
chlorine integrated with UV disinfection. Water Research 41(9), 1939-1948.
Renner, R. (2010) Reaction to the solution: lead exposure following partial service line
replacement. Environmental. Health Perspectives A202-A208.
Robinson B.R., Minear, R.A., and Holden J.M. (1992) Effects of Several Ions on iron treatment
by sodium silicate and hypochlorite. Journal American Water Works Association 79 (7),
116-125.
Rompré, A., Prévost, M., Coallier, J., Brisebois, P., and Lavoie, J. (2000) Impacts of
implementing a corrosion control strategy on biofilm growth. Water Science and
Technology 41 (4-5), 287-294.
Sastri, V.S., Subramanian, K.S., Elboujdaini, M., and Perumareddi, R. (2006) Inhibition of
release of lead into water owning to galvanic corrosion of lead solders. Corrosion
Engineering, Science and Technology 41 (3), 249-254.
Scheetz, B.E., Thompson, J.L., and Delaney, P.J. (1997) XPS characterization of films formed
on distribution systems using additives to control Pb/Cu levels in drinking water. Proc.
AWWA Water Quality Technology Conference, Denver, CO.
Schock, M.R., Lytle, D.A., Sandvig, A.N., Clement, J., and Harmon, S.M. (2005) Replacing
polyphosphate with silicate to solve lead, copper, and source water iron problems. Journal
American Water Works Association 97 (11), 84-93.
Schock, M.R., Hyland, R.N., and Welch, M.M. (2008) Occurrence of contaminant accumulation
in lead pipe scales from domestic drinking-water distribution systems. Environmental
Science & Technology 42, 4285-4291.
78
Simões, L.C., Simões, M., and Vieira, M.J. (2010) Influence of the diversity of bacterial isolates
from drinking water on resistance of biofilms to disinfection. Applied and Environmental
Microbiology 76 (19), 6673-6679.
Statistics Canada (2011). Household size by province and territory (2011 Census).
http://www.statcan.gc.ca/tables-tableaux/sum-som/l01/cst01/famil53a-eng.htm (accessed
June 2016).
St. Clair, J., Cartier, C., Triantafyllidou, S., Clark, B., and Edwards, M. (2016) Long-term
behavior of simulated partial lead service line replacements. Environmental Engineering
Science 33 (1), 53-64.
Switzer, J.A., Rajasekharan, V.V., Boonsalee, S., Kulp, E.A., and Bohannan, E.W. (2006)
Evidence that Monochloramine disinfectant could lead to elevated Pb levels in drinking
water. Environmental Science & Technology 40, 3384-3387.
Tam, Y.S. and Elefsiniotis, P. (2009) Corrosion control in water supply systems: effect of pH,
alkalinity, and orthophosphate on lead and copper leaching from brass plumbing. Journal
of Environmental Science and Health Part A. 44, 1251-1260.
Tang, Z., Hong, S., Xiao, W., and Taylor, J. (2006) Impacts of blending ground, surface, and
saline waters on lead release in drinking water distribution systems. Water Research 40,
943-950.
Thompson, J.L., Scheetz, B.E., Schock, M.R., Lytle, D.A., and Delaney, P.J. (1997) Sodium
silicate corrosion inhibitors: issues of effectiveness and mechanism, Proc. AWWA Water
Quality Technology Conference, Denver, CO.
Triantafyllidou, S., Schock, M., DeSantis, M., and White, C., (2015) Low contribution of PbO2-
coated lead service lines to water lead contamination at the tap. Environmental Science &
Technology 49 (6), 3746-3754.
Triantafyllidou, S., Parks, J., and Edwards, M. (2007). Lead particles in potable water. Journal
American Water Works Association 99 (6), 107-117.
79
Triantafyllidou, S. and Edwards, M. (2010) Contribution of galvanic corrosion to lead in water
after partial lead service line replacement. Water Research Foundation. Denver, CO.
Triantafyllidou, S. and Edwards, M. (2011) Galvanic corrosion after simulated small-scale partial
lead service line replacements. Journal American Water Works Association 103(9), 85-
99.
U.S. EPA (2002) Lead in drinking water regulation: public education guidance. Available at
https://www.epa.gov/dwreginfo/drinking-water-lead-and-copper-rule-historical-
documents (accessed March 2016).
U.S. EPA (2015) Section 1417 of the safe drinking water act: prohibition on use of lead pipes,
solder, and flux. Available at https://www.epa.gov/dwstandardsregulations/section-1417-
safe-drinking-water-act-prohibition-use-lead-pipes-solder-and (accessed March, 2016).
U.S. EPA (2016) Lead and copper rule. Available at https://www.epa.gov/dwreginfo/lead-and-
copper-rule (accessed April, 2016).
Vasquez, F.A., Heaviside, R., Tang, Z., and Taylor, J.S. (2006) Effect of free chlorine and
chloramines on lead release in a distribution system. Journal: American Water Works
Association 98 (2), 144-154.
Volk, C., Dundore, E., Schiermann, J., and Lechevallier, M. (2000) Practical evaluation of iron
corrosion control in a drinking water distribution system. Water Research 34 (6), 1967-
1974.
Wang, Y., Jing, H., Mehta, V., Walter, G.J., and Giamar, D.E. (2012) Impact of galvanic
corrosion on lead release from aged lead service lines. Water Research 46, 5049-5060.
Wang, Y., Mehta, V., Welter, G.J., and Giammar D.E. (2013) Effect of connection methods on
lead release from galvanic corrosion. Journal American Water Works Association. E337-
E351.
Welter, G. (2016) Typical kitchen faucet-use flow rates: implications for lead concentration
sampling. Journal American Water Works Association. 108(7): E374-E380.
80
Willison, H. and Boyer, T.H. (2012) Secondary effects of anion exchange on chloride, sulfate,
and lead release: systems approach to corrosion control. Water Research 46 (7), 2385-
2394.
Woszczynski, M., Bergese, J., and Gagnon, G. (2013) Comparison of chlorine and chloramines
on lead release from copper pipe rigs. Journal of Environmental Engineering 139, 1099-
1107.
Woszczynski, M., Bergese, J., Payne, S.J., and Gagnon G.A. (2015) Comparison of sodium
silicate and phosphate for controlling lead release from copper pipe rigs. Canadian
Journal of Civil Engineering. 42, 953-959.
Xie, Y. and Giammar, D.E. (2011) Effects of flow and water chemistry on lead release rates from
pipe scales. Water Research 45, 6525-6534.
Xie, Y., Wang, Y., Singhal, V., and Giammar, D.E. (2010) Effects of pH and carbonate
concentration on dissolution rates of the lead corrosion product PbO2. Environmental
Science & Technology 44, 1093-1099.
Zhou, E. (2013) Impact of galvanic corrosion on lead release after partial lead service line
replacement (MASc thesis). University of Toronto, Toronto, Ontario, Canada.
Zhou, E., Payne, S.J.O., Hofmann, R., and Andrews, R.C. (2015) Factors affecting lead release
in sodium silicate-treated partial lead service line replacements. Journal of Environmental
Science and Health, Part A 50, 922-930.
Zietz B., Dassel de Vergara, J., Kevekordes, S., and Dunkelberg, H. (2001) Lead contamination
in tap water of households with children in Lower Saxony, Germany. The Science of the
Total Environment 275, 19-26.
81
7 Appendices
7.1 Sample Quality Assurance/Quality Control Charts
For analysis of samples, a QA/QC chart was prepared by analyzing 8 standards spiked with the
same concentration as check standards and calculating the mean and standard deviations of the
standards. Check standards were run after every 10 samples, and the concentrations of check
standards were compared to the means and standard deviations according to Standard Method
1020 (APHA et al., 2005). The calibration is considered to be unacceptable if check standards
meet any of the following conditions.
- 2 consecutive measurements fall outside the control limits of the mean ± 3 standard
deviation
- 3 out of 4 consecutive measurements were outside the warning limits of the mean ± 2
standard deviation
- 5 out of 6 consecutive measurements were outside of the mean ± 1 standard deviation
- 5 out of 6 consecutive measurements exhibited an increasing or decreasing trend
- 7 consecutive measurements were greater or less than the mean
If the calibration is considered unacceptable, a new calibration curve was prepared, and samples
were reanalyzed.
The example QA/QC charts are shown for the following analyses: lead (Figure 7-1), copper
(Figure 7-2), TOC (Figure 7-3), phosphate (Figure 7-4), chloride (Figure 7-5), and sulfate
(Figure 7-6).
82
Figure 7-1: QC chart – lead (Check standards = 100 µg/L)
Figure 7-2: QC chart – copper (Check standards = 100 µg/L)
60.0
70.0
80.0
90.0
100.0
110.0
120.0
1 6 11 16 21 26 31
Lea
d C
on
cen
tra
tio
n (
µg
/L)
Check Standards
Checks
Average
+/-2 SD (warning linits)
+/- 3 SD (control limits)
60.0
70.0
80.0
90.0
100.0
110.0
120.0
1 6 11 16 21 26 31
Co
pp
er C
on
cen
tra
tio
n (
µg
/L)
Check Standards
Checks
Average
+/-2 SD (warning linits)
+/- 3 SD (control limits)
4/19 4/20 4/28 5/5
4/19 4/20 4/28 5/5
83
Figure 7-3: QC chart – TOC (Check standards = 2.5 mg/L)
Figure 7-4: QC chart – phosphate (Check standards = 2.0 mg/L)
1.6
1.8
2.0
2.2
2.4
2.6
2.8
3.0
1 6 11 16 21 26
TO
C (
mg
/L)
Check Standards
Check STD
Average
+/- 2 SD (warning limits)
+/- 3 SD (control limits)
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
1 6 11 16 21
Ph
osp
ha
te (
mg
/L)
Checks
Average
Warning Limits
Control Limits
84
Figure 7-5 : QC chart – chloride (Check standards = 25 mg/L)
Figure 7-6: QC chart – sulfate (Check standards = 30 mg/L)
16.0
18.0
20.0
22.0
24.0
26.0
28.0
30.0
1 6 11 16 21
Ch
lori
de
(mg
/L)
Check Std
Average
Warning Limits
Control Limits
20.0
22.0
24.0
26.0
28.0
30.0
32.0
34.0
1 6 11 16 21
Su
lfa
te (
mg
/L)
Checks
Average
Warning Limits
Control Limits
85
7.2 Raw Data Table 7-1: Total and dissolved lead release for 30-min stagnation periods (part 1)
Experimental
condition Week
Lead release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
Acclimation
1 5 5 11 13 12 17 9 10 10 14
1 (Tue) 3 9 11 14 14 17 16 16 12 19
3 3 8 10 12 9 10 9 10 11 15
3 (Tue) 6 11 11 15 12 14 15 17 16 17
4 6 6 20 21 17 18 18 19 23 24
4 (Tue) 5 10 11 11 17 17 16 19 16 21
6 0 5 13 13 11 12 12 14 14 16
6 (Tue) 5 6 11 14 13 15 16 19 14 15
Low CMSR
1 8 9 15 15 7 8 16 26 10 10
1 (Tue) 5 7 13 14 7 11 8 16 15 17
3 10 15 22 26 18 19 6 9 11 23
3 (Tue) 4 6 14 26 1 4 1 8 9 18
4 7 7 19 23 1 8 1 6 7 12
5 3 4 21 24 3 3 4 5 15 15
6 4 4 24 25 2 2 2 7 16 18
7 2 4 16 17 2 2 2 3 10 13
8 0 1 16 17 0 0 0 0 7 8
9 6 9 11 19 0 1 0 4 11 18
10 5 6 20 28 1 3 1 4 21 25
11 4 6 19 20 6 7 7 11 19 20
12 19 21 22 21 7 8 6 6 30 31
86
Table 7-1: total and dissolved lead release for 30-min stagnation periods (part 2)
Experimental
condition Week
Lead release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
low
conductivity
1 2 8 13 16 3 4 0 3 17 16
2 5 5 11 12 0 0 0 0 18 20
3 1 1 16 18 0 0 0 0 17 19
4 2 6 16 17 3 2 0 3 18 19
5 2 4 16 18 4 5 0 1 16 17
6 6 8 12 14 4 8 2 4 16 21
High CSMR-
high
conductivity
1 3 4 17 17 1 6 0 4 15 17
2 5 7 16 16 3 4 3 8 9 14
3 7 11 12 20 5 8 0 1 10 11
4 7 9 14 16 3 3 1 3 10 12
5 6 7 13 20 2 2 0 1 9 15
6 5 8 14 17 1 5 -2 1 9 12
7 5 8 17 20 3 3 0 7 11 17
8 6 7 15 24 5 5 0 3 11 13
Table 7-1: total and dissolved lead release for 30-min stagnation periods (part 3)
87
Experimental
condition Week
Lead release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
high
conductivity-
Chlorine
1 4 24 17 25 1 1 2 3 7 14
2 3 52 11 15 3 3 1 7 13 18
3 0 34 4 25 0 8 0 9 5 17
4 10 12 10 20 2 5 2 3 14 32
5 7 13 18 20 4 5 1 9 14 40
6 6 15 8 24 1 4 0 3 16 32
7 7 9 10 13 2 3 0 5 11 21
8 14 14 12 13 3 3 0 6 6 23
9 5 9 12 13 3 4 0 0 7 10
10 10 10 6 11 3 7 0 4 9 11
11 4 7 4 7 2 3 0 6 6 6
12 5 15 5 12 3 6 0 8 9 14
13 3 4 4 6 0 1 0 2 6 14
88
Table 7-2: Total and dissolved lead release for 6-h stagnation periods (part 1)
Experimental
condition Week
Lead release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
Acclimation
1 14 15 35 34 42 44 30 35 38 43
1 (Tue) 11 22 29 35 36 44 34 36 39 49
3 16 19 32 33 33 39 31 43 39 43
3 (Tue) 11 14 31 32 33 40 33 48 34 42
4 25 28 37 37 48 51 51 52 62 66
4 (Tue) 16 20 25 36 42 45 46 49 46 59
6 16 17 26 32 36 37 36 39 43 47
6 (Tue) 16 16 30 30 36 36 38 40 36 41
Low CMSR
1 22 29 42 47 20 23 33 37 33 34
1 (Tue) 18 21 36 38 13 19 25 21 31 36
3 29 33 63 68 11 20 10 17 40 53
3 (Tue) 19 24 49 55 6 12 8 15 38 43
4 26 29 61 63 9 11 14 20 36 38
5 30 32 59 62 6 8 10 14 49 50
6 29 33 64 68 7 8 10 12 43 50
7 24 25 52 52 3 5 6 8 39 43
8 16 17 55 57 0 0 2 2 51 57
9 18 25 61 62 0 7 0 7 56 57
10 27 28 69 70 8 8 7 8 66 70
11 19 20 45 46 8 12 0 17 52 54
12 23 38 45 50 0 12 0 11 51 64
89
Table 7-2: total and dissolved lead release for 6-h stagnation periods (part 2)
Experimental
condition Week
Lead release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
low
conductivity
1 15 31 43 58 7 17 3 14 52 59
2 20 20 40 40 0 0 0 0 55 55
3 14 15 49 51 3 4 0 5 57 58
4 15 18 50 52 9 10 4 4 53 54
5 18 20 48 50 8 10 2 3 55 55
6 23 24 51 52 7 8 2 5 46 51
High CSMR-
high
conductivity
1 14 20 46 50 7 11 0 7 42 46
2 17 23 41 45 8 9 5 7 39 39
3 16 19 46 49 12 12 3 5 34 36
4 15 18 38 45 6 12 0 3 31 37
5 19 22 36 41 10 10 0 0 35 39
6 14 22 40 48 7 11 1 2 31 35
7 11 20 41 48 9 10 2 5 29 34
8 11 16 34 48 4 4 1 1 25 27
Table 7-2: total and dissolved lead release for 6-h stagnation periods (part 3)
90
Experimental
condition Week
Lead release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
high
conductivity-
Chlorine
1 15 120 47 51 3 8 6 6 32 35
2 13 85 37 59 8 15 2 11 27 41
3 13 45 25 64 0 19 0 15 21 49
4 19 29 29 65 5 16 1 12 23 49
5 22 32 25 50 6 11 4 7 24 58
6 19 28 24 47 9 11 6 6 25 63
7 21 23 23 32 9 11 4 8 22 38
8 23 24 12 20 3 5 3 7 16 49
9 17 21 22 27 5 8 2 4 20 32
10 15 32 16 21 5 8 3 6 16 28
11 10 13 14 18 6 9 5 6 12 28
12 13 26 10 26 3 7 1 9 12 24
13 11 23 21 21 4 6 3 3 13 17
91
Table 7-3: Total and dissolved lead release for 65-h stagnation periods (part 1)
Experimental
condition
Week
Lead release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
Acclimation
1 62 86 83 97 112 143 133 137 78 102
3 43 65 81 90 117 129 128 155 90 105
4 30 36 96 110 102 118 132 155 111 135
6 48 60 68 85 79 102 101 106 63 70
Low CMSR
1 37 49 103 106 19 20 37 37 62 71
3 38 48 135 155 9 26 14 29 61 79
4 46 47 92 97 9 10 13 13 59 62
5 29 35 91 96 8 10 13 14 68 72
6 29 31 96 103 7 9 5 6 70 73
7 38 42 124 133 10 13 10 11 111 123
8 18 20 139 147 0 7 0 4 122 130
9 32 43 98 124 5 18 7 7 91 124
10 33 34 99 102 10 13 12 14 93 106
11 26 36 71 76 10 19 17 27 92 112
12 21 32 65 76 12 14 7 8 86 99
High CSMR-
low
conductivity
1 36 39 76 75 9 10 1 0 99 103
2 32 35 101 107 5 11 0 7 136 152
3 27 28 107 115 8 10 0 0 96 104
4 23 29 86 96 14 15 2 7 92 112
5 24 29 106 117 13 20 6 8 78 90
6 25 29 98 107 17 18 5 10 86 91
Table 7-3: Total and dissolved lead release for 65-h stagnation periods (part 2)
92
Experimental
condition
Week
Lead release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
high
conductivity
1 21 31 111 134 18 26 6 4 66 78
2 32 38 91 105 13 21 6 6 58 70
3 40 55 82 95 15 24 0 6 59 75
4 36 46 90 99 18 27 3 11 62 67
5 37 50 96 115 12 27 0 6 51 61
6 34 45 79 84 20 22 1 4 53 60
7 36 42 84 97 11 14 1 1 37 40
8 25 31 86 88 16 17 5 5 48 50
High CSMR-
high
conductivity-
Chlorine
1 34 138 79 91 25 28 9 10 47 59
2 48 137 73 102 24 38 8 16 50 63
3 54 74 57 73 36 51 8 17 59 79
4 58 93 54 75 39 54 8 8 49 74
5 36 49 42 45 35 46 5 7 44 128
6 38 42 56 61 44 54 0 10 33 60
7 41 52 26 27 26 34 4 5 31 49
8 53 58 38 45 22 30 3 6 30 32
9 38 42 34 38 12 17 0 6 37 41
10 39 43 44 51 15 17 3 5 32 34
11 22 25 29 31 10 11 5 4 30 35
12 29 32 24 26 14 18 3 3 24 29
13 23 28 31 31 14 19 4 6 41 42
93
Table 7-4: Lead concentrations in samples of pre-acidification bulk water (90 L) and acidified bottom 20 L of reservoir water (part 1)
Experimental
condition Week
Lead concentration (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Acclimation
1 38 38 40 46 48 59 47 49 55 42 42 45 39 41 51
3 29 33 45 38 39 54 32 33 45 33 37 45 29 34 51
4 21 23 42 34 37 57 28 30 46 31 33 44 26 33 55
6 32 38 NM 44 47 NM 35 41 NM 38 43 NM 36 40 NM
Low CMSR
1 23 25 31 40 41 53 13 14 20 7 27 32 26 31 54
3 22 22 31 43 47 64 1 8 43 2 9 24 17 24 69
4 16 21 34 49 54 70 7 9 19 4 12 21 21 28 43
5 25 25 31 52 58 73 5 7 18 3 11 18 24 29 39
6 18 25 42 45 51 78 7 9 27 5 10 23 23 29 47
7 13 14 37 27 31 86 4 4 20 5 5 15 12 17 56
8 24 26 35 26 28 86 0 0 16 0 0 14 9 16 49
9 15 20 44 39 50 71 4 7 10 3 11 15 27 41 53
10 24 25 35 54 56 68 4 4 11 2 7 17 39 39 55
11 21 22 29 43 45 71 4 6 5 0 0 12 26 33 52
12 22 22 30 43 47 62 5 6 11 4 8 18 27 31 43
High CSMR-
low
conductivity
1 7 10 15 22 32 41 0 0 2 0 0 0 11 17 29
2 6 7 25 20 22 42 0 0 5 0 0 8 13 16 38
3 6 25 29 26 41 52 0 0 9 0 0 19 18 34 42
4 23 25 35 42 48 59 5 9 12 5 9 23 32 37 51
5 20 24 28 44 46 60 6 7 10 2 8 19 33 35 41
6 25 26 31 47 48 57 6 9 12 2 6 19 34 35 47
94
Table 7-4: Lead concentrations in samples of pre-acidification bulk water (90 L) and acidified bottom 20 L of reservoir water (part 2)
Experimental
condition Week
Lead concentration (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
High CSMR-
high
conductivity
1 24 26 31 46 54 60 7 12 14 2 7 18 36 36 46
2 17 19 44 26 29 88 2 3 16 2 5 17 20 22 70
3 16 18 39 35 36 55 2 4 6 1 2 14 27 26 46
4 18 21 36 31 33 53 4 7 7 3 3 14 26 26 51
5 20 20 33 36 39 57 2 3 11 0 5 12 27 31 41
6 19 20 32 42 45 61 4 4 11 0 1 19 27 29 40
7 21 22 28 39 42 56 8 8 14 4 7 22 28 28 48
8 18 20 30 33 34 45 6 6 10 0 4 21 22 24 32
High CSMR-
high
conductivity-
Chlorine
1 21 24 37 37 48 76 7 10 24 9 20 55 35 36 63
2 17 23 36 37 46 77 3 8 26 4 11 32 29 36 68
3 20 27 52 45 52 88 10 15 34 5 12 27 34 45 83
4 22 25 50 43 47 73 5 11 23 3 16 30 40 42 114
5 26 27 38 32 40 58 6 8 13 0 12 29 38 41 170
6 22 29 39 35 41 59 3 9 18 1 7 26 33 39 123
7 22 25 35 29 36 49 8 9 15 3 8 21 30 32 62
8 20 21 35 32 33 48 9 9 15 3 7 19 31 33 60
9 21 21 32 25 27 35 6 7 14 2 8 16 21 25 42
10 15 16 25 22 22 39 1 4 9 1 4 11 23 23 32
11 16 18 34 18 19 31 2 4 11 0 3 9 13 15 22
12 17 21 29 20 25 36 6 10 13 2 10 10 17 19 37
13 18 22 29 23 24 32 5 8 10 2 7 11 21 22 27
NM represents not measured. In acclimation Week 4, reservoir water was not changed until the end of Week 5 because water was not collected for the following
week.
95
Dissolved (90L) and Total (90L) samples were collected before the weekly reservoir acidification and represent the lead concentrations in the bulk water. Total (20L)
samples were collected after the reservoir acidification of the bottom 20 L of reservoir water and represent total lead concentrations in the reservoir including the bulk
water and particulates at the bottom of the reservoir.
96
Table 7-5: Weekly mass release calculated based on samples collected (part 1)
Experimental condition Week Lead mass release (µg)
PVC-Pb: No
corrosion inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP
Cu-Pb: Sodium
silicate
Acclimation
1 3499 4621 4623 3974 4045
3 3266 3914 3388 3691 3551
4 NM NM NM NM NM
6 3492 4550 3911 4009 3983
Low CMSR
1 2449 4075 1468 2560 3363
3 2236 4797 1455 1162 3184
4 2222 5301 1009 1259 2914
5 2422 5619 887 1180 2920
6 2618 5257 1154 1171 3090
7 1749 4022 684 696 2459
8 2520 3895 316 287 2276
9 2305 5086 685 1091 4046
10 2443 5412 521 832 3966
11 2179 4680 527 286 3493
12 2141 4608 618 945 3130
High CSMR-low
conductivity
1 1062 3129 270 174 1921
2 1052 2483 115 164 2058
3 2345 4002 190 381 3305
4 2459 4672 903 1130 3783
5 2275 4522 754 946 3377
6 2497 4789 932 817 3637
97
Table 7-5: Weekly mass release calculated based on samples collected (part 2)
Experimental condition Week Lead mass release (µg)
PVC-Pb: No
corrosion inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP
Cu-Pb: Sodium
silicate
High CSMR-high
conductivity
1 2507 5264 1191 901 3661
2 2279 4063 555 719 3161
3 2101 3715 439 466 2862
4 2231 3484 650 523 2933
5 2093 3961 483 588 3060
6 2099 4443 501 485 2876
7 2128 4189 859 920 2993
8 2042 3377 629 723 2375
High CSMR-high
conductivity-Chlorine
1 2642 4979 1195 2483 3847
2 2508 4844 1152 1464 3968
3 3028 5452 1765 1388 4879
4 2843 4804 1231 1711 5288
5 2728 3991 866 1401 6380
6 2860 4100 1042 999 5288
7 2477 3520 930 991 3555
8 2194 3290 948 900 3516
9 2164 2595 753 851 2660
10 1690 2375 496 538 2262
11 1959 2031 532 434 1513
12 2071 2591 952 919 2097
13 2130 2363 786 737 2087
98
Table 7-6: Total and dissolved copper release for 30-min stagnation periods (part 1)
Experimental
condition Week
Copper release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
Acclimation
1 0 0 36 36 34 30 35 27 41 39
1 (Tue) 0 0 30 38 32 35 37 28 37 39
3 0 0 30 31 28 27 29 27 33 33
3 (Tue) -2 0 24 33 25 29 24 29 27 29
4 0 1 36 34 34 33 33 32 36 37
4 (Tue) 0 0 34 37 28 28 31 29 32 36
6 0 0 24 39 23 37 24 37 30 46
6 (Tue) 0 0 34 29 29 27 31 25 35 31
Low CMSR
1 0 0 26 17 6 6 9 6 22 20
1 (Tue) 0 0 18 19 -2 1 1 1 18 18
3 0 0 14 18 -7 -10 4 5 13 19
3 (Tue) 0 -1 9 9 0 -2 1 0 11 10
4 0 -1 18 18 6 4 4 3 19 18
5 2 0 24 25 6 5 5 5 27 29
6 0 1 21 21 4 3 3 3 22 22
7 0 0 21 20 11 10 6 4 16 18
8 0 0 20 16 4 3 2 2 14 12
9 0 0 16 25 5 11 1 5 26 36
10 6 0 40 23 29 10 17 5 40 23
11 0 1 21 8 3 -3 4 -6 21 9
12 0 0 22 24 9 10 2 3 26 27
Table 7-6: Total and dissolved copper release for 30-min stagnation periods (part 2)
99
Experimental
condition Week
Copper release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
low
conductivity
1 -1 3 23 28 9 18 3 13 22 27
2 0 0 23 23 12 12 3 3 26 26
3 0 0 25 26 9 10 2 2 26 31
4 1 1 27 26 11 11 4 5 30 31
5 0 1 27 28 9 10 4 4 29 29
6 0 1 22 23 9 10 2 2 24 25
High CSMR-
high
conductivity
1 0 1 24 26 7 8 2 2 24 26
2 1 2 22 25 10 11 2 2 23 26
3 0 2 27 27 12 12 4 3 27 26
4 1 1 24 26 12 12 2 3 24 25
5 1 1 28 30 10 11 2 2 24 25
6 1 0 27 26 11 11 2 1 21 24
7 -1 -1 24 26 9 7 2 0 22 19
8 -1 1 29 38 9 13 3 2 21 21
Table 7-6: Total and dissolved copper release for 30-min stagnation periods (part 3)
Experimental Week Copper release (µg/L)
100
condition PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
high
conductivity-
Chlorine
1 -1 0 62 65 21 24 14 14 38 47
2 1 1 34 36 15 19 8 7 30 35
3 3 2 37 52 12 21 7 7 28 39
4 1 1 32 41 12 14 7 5 21 26
5 2 2 43 53 14 14 4 6 37 50
6 2 1 41 50 15 12 4 4 32 36
7 0 0 32 41 10 11 3 3 36 39
8 0 0 44 45 11 13 2 4 30 34
9 0 1 31 32 9 11 3 2 28 31
10 1 1 29 36 9 12 1 3 32 39
11 1 1 23 26 8 9 1 2 22 23
12 3 1 24 45 12 14 2 3 5 34
13 0 1 30 32 8 9 2 -1 24 31
101
Table 7-7: Total and dissolved copper release for 6-h stagnation periods (part 1)
Experimental
condition Week
Copper release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
Acclimation
1 0 0 207 205 240 231 167 158 212 224
1 (Tue) 0 0 194 227 232 250 170 175 219 226
3 0 0 220 221 217 234 163 197 214 218
3 (Tue) -2 -1 167 185 195 217 143 163 181 191
4 0 1 201 201 231 233 175 184 234 238
4 (Tue) 1 0 156 172 195 218 169 168 186 199
6 0 0 203 225 225 254 177 192 206 231
6 (Tue) 0 0 163 169 200 213 184 170 182 193
Low CMSR
1 0 0 181 177 14 22 38 36 126 131
1 (Tue) 0 0 104 103 3 1 6 12 85 93
3 0 0 55 58 10 15 11 12 48 57
3 (Tue) 0 -1 31 32 4 2 2 0 17 13
4 0 -1 80 79 11 11 13 14 70 73
5 2 1 125 126 10 9 16 15 101 105
6 0 1 133 140 4 3 9 8 69 74
7 0 0 108 109 47 51 19 20 62 66
8 0 0 94 92 1 2 2 1 14 15
9 0 0 215 216 86 91 41 45 142 151
10 6 1 186 166 91 74 43 30 131 111
11 1 1 104 106 4 5 0 4 59 60
12 0 1 181 199 61 69 13 15 93 101
Table 7-7: Total and dissolved copper release for 6-h stagnation periods (part 2)
102
Experimental
condition Week
Copper release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
low
conductivity
1 1 2 170 177 65 72 21 23 100 104
2 0 0 167 167 69 70 17 17 100 102
3 1 2 133 136 39 40 13 13 95 104
4 2 2 190 194 74 76 20 20 117 123
5 -1 -1 191 194 72 79 20 22 125 129
6 0 0 174 182 53 57 12 13 80 86
High CSMR-
high
conductivity
1 -1 0 133 141 32 34 6 7 78 78
2 1 2 104 119 40 45 5 6 86 98
3 1 1 161 168 65 69 12 12 105 108
4 0 0 168 177 60 64 8 9 96 102
5 2 2 138 142 47 50 7 7 85 90
6 0 0 198 202 62 65 11 11 90 96
7 -1 -2 165 172 43 41 7 6 91 92
8 5 7 165 189 56 63 15 12 70 75
Table 7-7: Total and dissolved copper release for 6-h stagnation periods (part 3)
Experimental Week Copper release (µg/L)
103
condition PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
high
conductivity-
Chlorine
1 1 3 209 231 99 108 45 46 155 160
2 2 2 139 160 87 98 40 42 112 125
3 2 3 141 171 65 81 37 39 85 104
4 3 2 113 137 48 56 27 28 53 78
5 2 2 89 121 52 62 20 23 78 92
6 2 2 103 125 40 41 16 16 76 81
7 1 0 94 109 37 40 15 16 80 97
8 1 1 71 77 44 49 10 11 71 80
9 1 1 85 87 28 29 8 9 79 83
10 2 2 83 98 29 35 6 8 78 88
11 1 1 68 78 26 26 6 6 64 70
12 1 3 69 102 23 34 4 6 72 99
13 0 0 89 95 26 28 5 4 68 72
104
Table 7-8: Total and dissolved copper release for 65-h stagnation periods (part 1)
Experimental
condition
Week Copper release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
Acclimation 1 0 0 19 27 24 30 12 15 -1 -2
3 3 1 5 4 19 19 12 14 5 6
4 0 0 15 11 8 6 7 5 -1 -2
6 -2 1 173 183 33 39 1 -1 276 267
Low CMSR 1 -2 0 -4 -4 26 26 32 27 32 39
3 -0 -2 5 4 43 43 30 27 1 -0
4 -0 -4 7 -1 27 20 23 16 0 -5
5 -1 7 -4 2 27 34 20 26 -3 2
6 3 5 -9 -4 15 24 8 16 -7 2
7 0 0 -1 -2 12 11 10 5 -4 -10
8 0 0 -7 -8 7 8 12 11 0 -1
9 0 0 -9 -9 6 11 10 17 -6 -6
10 -0 -0 -13 -16 9 7 20 17 -11 -11
11 0 0 -12 -18 13 -4 18 10 -5 -13
12 -1 -0 -20 -20 1 1 8 9 -13 -13
High CSMR-
low
conductivity
1 0 2 5 5 4 7 12 12 -7 -8
2 0 0 -8 -7 8 8 18 20 -2 -2
3 -0 -1 -10 -14 5 4 12 9 -10 -15
4 1 2 -13 -14 5 6 10 12 -9 -9
5 0 0 -15 -15 6 7 9 11 -14 -13
6 0 1 -11 -12 8 8 11 11 -4 -6
Table 7-8: Total and dissolved copper release for 65-h stagnation periods (part 2)
105
Experimental
condition
Week Copper release (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissolved Total Dissolved Total Dissolved Total Dissolved Total Dissolved Total
High CSMR-
high
conductivity
1 2 2 -12 -11 6 6 5 5 -11 -12
2 -1 -0 -4 -9 6 6 8 10 -10 -13
3 -1 -2 -8 -10 12 8 5 3 -16 -18
4 0 1 -8 -7 8 8 4 5 -14 -15
5 0 1 -12 -8 2 4 7 8 -15 -13
6 1 1 -13 -12 7 8 3 3 -14 -16
7 1 1 -14 -11 2 2 4 3 1 1
8 2 5 1 -0 8 12 10 12 -14 -12
High CSMR-
high
conductivity-
Chlorine
1 5 9 160 177 250 266 106 120 34 47
2 8 11 382 440 274 314 122 139 145 176
3 7 9 236 260 284 323 76 85 156 170
4 9 10 226 251 218 232 51 57 107 129
5 7 7 122 137 126 154 34 39 76 113
6 5 1 161 147 173 179 64 65 82
7 3 4 75 86 117 128 20 20 71 81
8 4 5 96 102 133 146 40 45 78 84
9 4 4 104 121 103 112 46 51 206 223
10 3 4 116 110 105 108 39 39 86 92
11 3 3 80 79 60 61 20 20 169 168
12 2 3 92 94 104 109 23 26 244 268
13 2 2 86 98 99 104 18 19 145 150
106
Table 7-9: Copper concentrations in samples of pre-acidification bulk water (90 L) and acidified bottom 20 L of reservoir water (part 1)
Experimental
condition Week
Copper concentration (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Acclimation
1 0 0 0 43 49 55 42 50 53 38 43 46 40 45 56
3 2 3 4 47 53 61 47 54 59 42 50 53 46 53 70
4 0 0 NM 36 43 NM 33 39 NM 29 36 NM 33 39 NM
6 6 5 6 60 64 70 55 58 63 54 57 60 58 61 75
Low CMSR
1 6 5 8 42 46 50 20 26 32 13 22 27 32 35 50
3 0 4 5 19 23 37 6 12 24 5 10 18 17 25 43
4 3 7 9 31 40 52 11 18 27 7 15 21 23 33 42
5 9 1 2 48 46 57 17 11 22 13 8 14 35 31 41
6 0 0 0 36 34 46 13 8 20 10 5 8 25 21 29
7 0 0 0 23 27 53 5 8 26 1 7 13 14 23 39
8 0 0 2 31 34 60 7 10 27 1 3 12 14 17 30
9 0 3 9 30 43 56 0 18 30 0 12 19 18 36 47
10 3 4 4 51 55 63 17 19 30 8 12 16 38 41 52
11 0 2 3 37 43 59 9 26 28 0 9 14 23 33 43
12 2 2 2 42 46 57 15 17 25 6 7 12 29 32 39
High CSMR-
low
conductivity
1 11 10 10 43 44 57 28 28 35 15 16 18 34 37 42
2 11 11 3 46 49 51 26 27 28 15 16 11 36 39 39
3 2 2 4 40 46 57 14 16 22 5 9 12 27 33 42
4 4 5 5 45 49 58 19 19 24 10 11 14 34 37 47
5 4 4 5 46 50 54 19 20 25 9 10 12 32 35 39
6 4 4 5 41 44 51 17 19 24 8 9 11 29 33 39
107
Table 7-9: Copper concentrations in samples of pre-acidification bulk water (90 L) and acidified bottom 20 L of reservoir water (part 2)
Experimental
condition Week
Copper concentration (µg/L)
PVC-Pb: No corrosion
inhibitor
Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium silicate
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
Dissol
ved
(90L)
Total
(90L)
Total
(20L)
High CSMR-
high
conductivity
1 3 3 4 41 46 54 16 19 23 7 8 11 30 34 39
2 4 5 6 36 42 69 17 19 31 7 9 12 27 32 51
3 3 3 4 40 42 57 17 19 25 6 7 10 29 32 46
4 2 4 3 43 46 60 19 20 27 7 7 11 32 35 52
5 3 5 6 41 46 58 18 20 30 6 8 10 27 32 40
6 6 6 7 48 52 63 20 23 30 8 10 12 34 37 45
7 6 5 6 46 50 59 20 22 29 8 9 11 35 40 50
8 4 4 4 43 50 56 19 22 27 8 10 13 30 32 39
High CSMR-
high
conductivity-
Chlorine
1 2 2 4 163 186 208 61 72 89 24 35 54 101 115 130
2 3 4 5 164 183 209 54 64 78 18 28 41 102 117 128
3 2 1 2 175 187 213 44 57 69 12 19 25 94 106 117
4 3 5 5 161 169 178 42 47 55 9 14 21 81 91 101
5 4 5 4 142 154 160 38 47 47 8 12 16 82 90 101
6 4 4 5 144 151 159 39 40 46 9 10 12 80 81 93
7 3 4 5 125 137 142 35 38 43 5 9 12 82 89 95
8 5 7 8 125 132 144 35 41 45 7 10 13 74 81 87
9 2 3 3 97 101 109 28 29 34 3 4 5 55 58 65
10 1 2 2 100 101 110 29 33 38 2 5 5 73 76 74
11 2 3 3 83 86 92 24 26 28 3 5 5 49 51 53
12 5 5 6 93 95 102 29 30 33 6 7 8 69 71 76
13 3 2 3 103 106 110 26 29 31 3 4 5 70 71 79
NM represents not measured. In acclimation Week 4, reservoir water was not changed until the end of Week 5 because water was not collected for the following
week.
108
Dissolved (90L) and Total (90L) samples were collected before the weekly reservoir acidification and represent the copper concentrations in the bulk water. Total
(20L) samples were collected after the reservoir acidification of the bottom 20 L of reservoir water and represent total copper concentrations in the reservoir including
the bulk water and particulates at the bottom of the reservoir.
109
Table 7-10: Total and dissolved lead accumulation in biofilm under stagnant and flow-through conditions
Condition Phase/Week
Lead accumulation in biofilm (µg/cm2)
PVC-PVC: No
corrosion
inhibitor
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP Cu-Pb: ZOP Cu-Pb: Sodium
silicate
Dissolv
ed Total
Dissolv
ed Total
Dissolv
ed Total
Dissolv
ed Total
Dissolv
ed Total
Dissolv
ed Total
Stagnant
High CSMR-high
conductivity
10 0.000 0.002 0.003 0.074 0.002 0.536 0.000 0.571 0.002 0.125 0.005 0.365
13 0.003 0.000 0.004 0.111 0.014 0.523 0.013 0.628 0.004 0.116 0.002 0.286
High CSMR-high
conductivity-
Chlorine
1 0.000 0.000 0.000 0.034 0.005 0.176 0.005 0.625 0.000 0.029 0.000 0.050
2 0.000 0.007 0.000 0.056 0.004 0.041 0.006 0.085 0.002 0.016 0.001 0.055
3 0.001 0.005 0.006 0.067 0.004 0.035 0.002 0.065 0.002 0.020 0.005 0.042
5 0.000 0.000 0.005 0.036 0.000 0.020 0.000 0.020 0.000 0.014 0.000 0.040
9 0.000 0.001 0.000 0.091 0.000 0.035 0.000 0.021 0.000 0.014 0.000 0.061
10 0.003 0.010 0.000 0.074 0.005 0.051 0.005 0.036 0.006 0.027 0.002 0.085
12 0.003 0.007 0.010 0.095 0.003 0.071 0.005 0.034 0.007 0.024 0.007 0.148
13 0.004 0.013 0.004 0.097 0.001 0.082 0.001 0.039 0.009 0.024 0.008 0.127
Flow-
through
High CSMR-high
conductivity
10 0.000 0.006 0.002 0.160 0.000 0.200 0.001 0.072 0.005 0.864 0.003 0.314
13 0.001 0.003 0.005 0.113 0.008 0.163 0.004 0.056 0.014 0.756 0.001 0.120
High CSMR-high
conductivity-
Chlorine
1 0.000 0.005 0.002 0.108 0.000 0.085 0.000 0.079 0.013 0.875 0.000 0.034
2 0.000 0.005 0.007 0.053 0.000 0.028 0.016 0.053 0.000 0.138 0.000 0.039
3 0.001 0.007 0.003 0.047 0.003 0.063 0.003 0.049 0.010 0.074 0.006 0.042
5 0.000 0.000 0.001 0.023 0.000 0.020 0.000 0.024 0.000 0.040 0.001 0.066
9 0.001 0.000 0.000 0.026 0.000 0.020 0.000 0.009 0.004 0.225 0.000 0.056
10 0.000 0.005 0.006 0.048 0.000 0.067 0.002 0.028 0.023 0.107 0.001 0.065
12 0.006 0.003 0.007 0.028 0.001 0.047 0.002 0.028 0.008 0.182 0.001 0.064
13 0.000 0.004 0.003 0.021 0.005 0.049 0.001 0.043 0.012 0.044 0.008 0.090
110
Table 7-11: Total and dissolved copper accumulation in biofilm under stagnant and flow-through conditions
Condition Phase/Week
Copper accumulation in biofilm (µg/cm2)
PVC-PVC: No
corrosion
inhibitor
PVC-Pb: No
corrosion
inhibitor
Cu-Pb: No
corrosion
inhibitor
Cu-Pb: OP
Cu-Pb: ZOP
Cu-Pb: Sodium
silicate
Dissolv
ed Total
Dissolv
ed Total
Dissolv
ed Total
Dissolv
ed Total
Dissolv
ed Total
Dissolv
ed Total
Stagnant
High CSMR-high
conductivity
10 0.004 0.006 0.002 0.028 0.007 0.533 0.007 0.800 0.004 0.084 0.010 0.339
13 0.006 0.031 0.006 0.014 0.046 0.620 0.053 0.834 0.009 0.061 0.021 0.316
High CSMR-high
conductivity-
Chlorine
1 0.007 0.016 0.007 0.016 0.046 0.371 0.032 0.777 0.007 0.023 0.016 0.093
2 0.007 0.005 0.007 0.004 0.007 0.056 0.007 0.071 0.013 0.018 0.012 0.033
3 0.001 0.007 0.001 0.006 0.004 0.029 0.002 0.027 0.001 0.011 0.002 0.025
5 0.002 0.005 0.001 0.005 0.003 0.023 0.003 0.012 0.003 0.010 0.003 0.031
9 0.000 0.003 0.000 0.004 0.002 0.024 0.001 0.014 0.001 0.007 0.004 0.029
10 0.004 0.008 0.004 0.010 0.004 0.031 0.005 0.014 0.004 0.013 0.005 0.032
12 0.004 0.009 0.006 0.010 0.006 0.037 0.006 0.015 0.006 0.012 0.005 0.067
13 0.006 0.011 0.006 0.012 0.006 0.040 0.006 0.017 0.007 0.013 0.007 0.043
Flow-
through
High CSMR-high
conductivity
10 0.000 0.013 0.002 0.031 0.005 0.181 0.006 0.181 0.013 0.477 0.007 0.281
13 0.006 0.037 0.006 0.037 0.016 0.257 0.013 0.110 0.027 0.359 0.010 0.435
High CSMR-high
conductivity-
Chlorine
1 0.007 0.017 0.008 0.019 0.018 0.162 0.015 0.142 0.022 0.387 0.016 0.070
2 0.013 0.008 0.018 0.007 0.007 0.032 0.018 0.062 0.009 0.066 0.012 0.037
3 0.001 0.005 0.002 0.008 0.004 0.047 0.009 0.065 0.004 0.032 0.005 0.035
5 0.002 0.008 0.002 0.005 0.003 0.032 0.005 0.028 0.004 0.018 0.006 0.032
9 0.001 0.005 0.002 0.005 0.003 0.032 0.002 0.014 0.004 0.044 0.005 0.045
10 0.005 0.008 0.004 0.008 0.008 0.058 0.005 0.015 0.008 0.041 0.008 0.039
12 0.006 0.009 0.005 0.012 0.007 0.050 0.006 0.020 0.006 0.044 0.009 0.041
13 0.005 0.008 0.005 0.010 0.007 0.049 0.007 0.027 0.005 0.016 0.012 0.060
111
Table 7-12: ATP accumulation under stagnant (Stag) and flow-through (Flow) conditions
Experimental phases/
Week
ATP (µg/cm2)
PVC-PVC: No
corrosion inhibitor
PVC-Pb: No
corrosion inhibitor
Cu-Pb: No
corrosion inhibitor Cu-Pb: OP Cu-Pb: ZOP
Cu-Pb: Sodium
silicate
Stag Flow Stag Flow Stag Flow Stag Flow Stag Flow Stag Flow
Low CSMR
0 3.66 2.48 11.90 6.45 7.09 2.43 12.15 5.93 5.43 2.05 9.05 2.37
2 2.75 1.59 20.93 5.59 47.26 3.68 15.58 4.92 8.93 5.24 26.12 3.81
4 4.43 3.29 41.83 5.69 22.47 5.00 64.08 16.16 47.52 36.57 15.82 7.78
6 5.45 4.71 72.02 7.45 40.02 12.58 40.83 21.43 33.32 44.26 9.02 9.05
8 9.69 9.98 204.94 19.98 82.76 14.04 121.74 40.78 38.20 96.68 14.40 29.46
10 6.06 4.86 73.77 7.86 53.53 5.59 60.80 25.58 24.54 63.62 21.69 18.08
12 7.62 6.63 46.26 13.41 53.42 6.05 69.18 18.29 27.28 67.10 30.73 13.86
High CSMR-low
conductivity
2 14.73 8.52 45.85 19.97 84.64 8.28 151.77 30.72 34.66 78.86 52.94 26.58
4 2.51 11.84 44.50 26.02 46.46 16.82 232.35 30.79 20.72 68.12 59.27 35.35
High CSMR-high
conductivity
4 9.92 16.57 17.79 35.36 153.51 34.45 376.05 86.31 12.00 136.11 86.62 82.21
8 5.34 16.54 25.13 14.46 150.41 24.11 246.39 34.61 28.98 186.69 157.48 14.95
High CSMR-high
conductivity-Cl2
1 0.02 5.53 0.03 2.71 13.86 3.05 127.27 9.83 0.83 13.34 1.23 7.14
2 0.01 0.02 0.02 0.54 0.01 1.34 1.00 0.31 0.03 1.31 0.03 2.97
3 0.06 0.87 0.01 0.04 0.03 2.86 0.01 1.53 0.16 0.12 0.06 1.86
5 0.01 0.45 0.07 0.01 0.02 0.16 0.11 1.22 0.01 0.01 0.01 0.61
9 0.00 0.31 0.00 0.28 0.00 0.01 0.00 0.40 0.00 0.20 0.00 0.03
10 0.00 0.32 0.00 0.31 0.00 0.00 0.00 0.03 0.00 0.39 0.01 0.01
12 0.00 0.12 0.00 0.09 0.00 0.02 0.00 0.06 0.01 0.14 0.00 0.03
13 0.00 0.10 0.01 0.09 0.00 0.00 0.00 0.10 0.00 0.06 0.00 0.01
112
Table 7-13: Average galvanic current (± standard deviation)
Condition Experimental phase Cu-Pb: No corrosion
inhibitor Cu-Pb: OP Cu-Pb: ZOP
Cu-Pb: Sodium
silicate
Flow
Low CSMR 10.3±2.2 9.5±3.3 9.2±4.1 11.6±2.3
High CSMR- low conductivity 9.4±2.5 8.8±2.4 9.4±2.8 10.4±3.2
High CSMR-high conductivity 10.4±2.9 10.5±2.4 12.6±2.6 20.2±3.5
High CSMR-high conductivity-chlorine 9.6±2.1 9.6±2.4 11.9±3.1 14.7±5.8
65-h stagnation
Low CSMR 5.4±3.0 3.9±1.2 2.6±0.6 4.0±1.5
High CSMR- low conductivity 5.1±3.0 4.3±0.9 2.3±0.5 3.4±0.8
High CSMR-high conductivity 4.4±3.1 4.9±2.3 2.4±0.5 6.0±1.6
High CSMR-high conductivity-chlorine 9.9±2.3 8.5±2.0 7.8±1.9 13.9±5.8
Figure 7-7: Daily galvanic current
0
5
10
15
20
25
30
35
8/20 9/3 9/17 10/1 10/15 10/29 11/12 11/26 12/10 12/24 1/7 1/21 2/4 2/18 3/3 3/17 3/31 4/14 4/28 5/12 5/26
Gal
van
ic c
urr
ent
(µA
)
Cu-Pb: No corrosion inhibitor Cu-Pb: OP Cu-Pb: ZOP Cu-Pb:Silicate
Low CSMR High CSMR-
low
conductivity
High CSMR-
high
conductivity
High CSMR- high
conductivity- chlorine
113
Table 7-14: Water quality parameters of reservoir water (part 1)
Experimental
condition Systems pH
Conduc
tivity
(mS/cm
)
Chloride
(mg/L)
Sulfate
(mg/L) CSMR
Corrosion
Inhibitor
Added (mg/L)
Residual
chlorine
(mg/L)
TOC
(mg/L)
Acclimation
PVC-Pb: No corrosion inhibitor 7.9±0.0 NM 27.2±1.0 127.9±2.1 0.2±0.0 NA NA 2.7±0.1
Cu-Pb: No corrosion inhibitor 7.9±0.1 NM 27.0±0.8 127.9±1.8 0.2±0.0 NA NA 2.5±0.1
Cu-Pb: OP 7.9±0.1 NM 27.2±1.0 127.4±2.2 0.2±0.0 NA NA 2.7±0.1
Cu-Pb: ZOP 7.9±0.0 NM 27.3±1.1 127.6±2.7 0.2±0.0 NA NA 2.6±0.1
Cu-Pb: Sodium Silicate 8.0±0.2 NM 27.3±1.1 128.8±2.7 0.2±0.0 NA NA 2.7±0.1
Low CSMR
PVC-PVC: No corrosion inhibitor 7.9±0.1 533±2 27.3±1.8 133.8±3.2 0.2±0.0 NA NA 8.1±1.7
PVC-Pb: No corrosion inhibitor 7.9±0.1 545±5 26.8±1.9 135.6±4.7 0.2±0.0 NA NA 3.7±0.7
Cu-Pb: No corrosion inhibitor 7.9±0.1 546±3 27.0±1.7 137.2±3.9 0.2±0.0 NA NA 4.0±1.0
Cu-Pb: OP 7.9±0.1 552±6 27.1±1.7 136.5±3.4 0.2±0.0 1.0±0.1 NA 5.7±1.9
Cu-Pb: ZOP 7.9±0.0 558±5 27.5±1.9 137.3±2.9 0.2±0.0 0.9±0.1 NA 5.2±1.5
Cu-Pb: Sodium Silicate 8.0±0.2 543±2 27.2±1.9 134.6±2.8 0.2±0.0 10.1±1.0 NA 5.6±1.8
High CSMR
with low
electrical
conductivity
PVC-PVC: No corrosion inhibitor 7.9±0.1 323±7 30.5±0.9 26.3±0.6 1.2±0.1 NA NA 4.4±0.7
PVC-Pb: No corrosion inhibitor 7.9±0.1 327±8 30.2±1.0 26.0±0.5 1.2±0.0 NA NA 2.5±0.2
Cu-Pb: No corrosion inhibitor 7.9±0.1 327±8 30.2±1.0 26.0±0.6 1.2±0.0 NA NA 2.3±0.3
Cu-Pb: OP 7.9±0.1 336±10 30.2±0.9 26.9±0.7 1.1±0.0 0.9±0.1 NA 2.5±0.4
Cu-Pb: ZOP 7.9±0.1 337±10 30.7±0.9 26.9±0.7 1.1±0.0 0.9±0.0 NA 2.4±0.3
Cu-Pb: Sodium Silicate 8.0±0.3 329±7 30.3±0.9 26.1±0.6 1.2±0.0 9.8±0.5 NA 2.5±0.3
High CSMR
with high
electrical
conductivity
PVC-PVC: No corrosion inhibitor 7.9±0.1 571±22 88.0±4.0 82.1±1.8 1.1±0.1 NA NA 3.3±0.3
PVC-Pb: No corrosion inhibitor 7.9±0.1 567±21 86.1±5.4 80.0±1.8 1.1±0.0 NA NA 2.5±0.4
Cu-Pb: No corrosion inhibitor 7.9±0.1 570±20 86.8±5.2 80.8±1.7 1.1±0.0 NA NA 2.2±0.1
Cu-Pb: OP 7.9±0.1 573±20 85.8±4.9 81.4±2.1 1.1±0.1 1.0±0.1 NA 2.4±0.1
Cu-Pb: ZOP 7.9±0.1 573±22 86.1±4.7 81.7±1.5 1.1±0.1 1.0±0.1 NA 2.3±0.1
Cu-Pb: Sodium Silicate 8.0±0.3 567±22 86.4±5.0 80.0±1.3 1.1±0.0 9.9±0.9 NA 2.5±0.1
114
Table 7-14: Water quality parameters of reservoir water (part 2)
Experimental
condition Systems pH
Conducti
vity
(mS/cm)
Chloride
(mg/L)
Sulfate
(mg/L) CSMR
Corrosion
Inhibitor
Added (mg/L)
Residual
chlorine
(mg/L)
TOC
(mg/L)
High CSMR
with high
electrical
conductivity
PVC-PVC: No corrosion inhibitor 8.0±0.0 603±20 88.8±0.9 78.7±1.8 1.1±0.0 NA 1.4±0.2 3.3±0.6
PVC-Pb: No corrosion inhibitor 7.9±0.1 599±19 87.1±1.1 77.7±1.3 1.1±0.0 NA 1.4±0.2 2.7±0.4
Cu-Pb: No corrosion inhibitor 7.9±0.1 597±19 87.1±1.1 77.8±1.0 1.1±0.0 NA 1.4±0.2 2.5±0.7
Cu-Pb: OP 7.9±0.1 601±20 87.1±1.1 77.8±1.0 1.1±0.0 1.0±0.1 1.4±0.3 2.8±0.7
Cu-Pb: ZOP 7.9±0.1 603±19 86.4±1.0 75.9±0.8 1.1±0.1 1.1±0.1 1.4±0.2 3.0±0.8
Cu-Pb: Sodium Silicate 8.1±0.2 603±19 86.4±1.0 75.9±0.8 1.1±0.1 10.2±0.8 1.4±0.2 2.7±0.8
115
7.3 Preliminary Results
7.3.1 Tank Acidification
7.3.1.1 Materials and Methods
The objectives of this preliminary experiment were: i) to determine the time required to dissolve
all particulate lead in the reservoirs when acidified to pH < 2, ii) to examine the effect of
mechanical mixing during acidification, and iii) to compare two methods for sample preparation:
acid preservation and acid digestion.
Determination of Time to Completely Acidify Reservoir
Three reservoirs (Reservoirs 1, 2, and 3) (Figure 7-8), each holding 90 L of water, were acidified
to pH < 2 by adding concentrated nitric acid (67%). The amount of acid required to acidify each
tanks to pH < 2 was determined by titration prior to the experiment. To compare the
effectiveness of mixing, Reservoir 3 (Figure 7-8) was acidified to pH < 2 in the same way and
also received mechanical mixing at 320 rpm with a 22-inchTeflon® anchor-style paddle assembly
(Cole-Parmer Canada Inc., Montreal, QC).
Reservoirs 4 and 5 (Figure 7-8) were used to compare the effect of decreasing the volume of
water and determine the feasibility of acidifying a smaller volume. Water was drained to 20 L by
pumping water out of the reservoirs to waste.
A 10-mL sample was collected from all five reservoirs by inserting a volumetric pipette 6-cm
below the water surface at time = 0, 4, 20, 24, 26, and 30 hours post acidification.
Comparison of Two Sample Preparation Methods
10 mL of samples were collected from all reservoirs at time = 0, 24, and 30 hours following
acidification. Samples were digested with 0.5 mL of nitric acid at 105º C for 2 h, following the
Standard Method 3030 E (APHA, 2004). The two methods (preservation at pH < 2 and nitric
acid digestion) were then compared for lead recovery.
Measurement of Residual Lead in Reservoir after the First Acidification
116
Following reservoir acidification, a follow-up experiment was conducted to evaluate the
potential contribution of lead adsorption to the reservoir walls. Following the experiments, water
was pumped to waste. Reservoir 2 was washed thoroughly to evaluate the effectiveness of
cleaning. Three of the five reservoirs (# 1, 2, and 3) were then refilled with 90 L of Lake Ontario
water and acidified to pH < 2. This second acidification lasted for 24 h; samples were collected
at t = 0, 4, 24 h. Samples were collected 6-cm below the surface using a disposable plastic pipette
tip.
All samples obtained in the two experiments were analyzed for total lead using ICP-MS as
described in Section 3.2.1.
Figure 7-8: Treatments to Determine Lead Recovery from Reservoirs
7.3.1.2 Results
Experiments were conducted to determine the time required to dissolve all particulate lead in the
reservoirs when acidified to pH < 2. Three approaches were examined: 1) acidification of 90 L of
water, 2) acidification of 90 L of water with mechanical mixing by a 22-inch anchor-style paddle
assembly (320 rpm), and 3) acidifying only 20 L of the water. There was no significant
difference between these three approaches. The total lead concentrations in the samples ranged
from 136 to 350 µg/L. The average total lead concentrations in the samples ranged from 143 to
248 µg/L, and approximately 96% of data remained within ± 10% of the averages after 20 hours
of acidification (Figure 7-9). The result suggested that all lead in the reservoirs was dissolved
90 L 90 L
Reservoir 1 Reservoir 2 Reservoir 3
Reservoir 5 Reservoir 4
90 L
20 L 20 L
117
within 20 hours and that the reservoirs contained only limited amounts of particulate lead. The
difference in total lead presumably originated from difference in the harvested lead pipes. In
order to assess the contribution of particles to total lead, the preservation method (pH < 2) and
the nitric acid digestion method (105º C for 2 h) were compared and did not produce statistically
significant difference (95% CI), which implied a limited contribution of particulate lead. During
reservoir acidification, pH ranged from 1.63-1.96 throughout the 50-hour experiment, and
turbidity of the waters did not show a trend.
Following acidification experiment, three reservoirs were refilled with water and acidified to pH
< 2 to assess the amount of lead adsorbed to reservoir walls. One reservoir was left stagnant, a
second reservoir was cleaned with raw water and brushed with a plastic brush prior to
acidification, and the third reservoir received mechanical mixing during acidification. After 4
hours of the second acidification, the total lead concentration was within ± 10% of the average of
each reservoir and ranged from 0.18 to 2.78 µg/L. The third reservoir, which employed a
mechanical mixer whereas had the highest average total lead concentration (2.78 µg/L), and the
reservoir that received cleaning before the second acidification had the lowest average total lead
concentration (0.20 µg/L). The lead released from the reservoir walls was < 4% of the average
total lead concentrations of the first acidification samples.
118
Figure 7-9: Lead Concentrations During 50-h Acidification
0
50
100
150
200
250
300
350
400
0 10 20 30 40 50
Pb C
once
ntr
atio
ns
(µg/L
)
Time (h)
Reservoir 1 (90 L, No mixing)
Reservoir 2 (90 L, No mixing)
Reservoir 3 (90 L, Mixing)
Reservoir 4 (20 L, No mixing)
Reservoir 5 (20 L, No mixing)
119
7.3.2 Chlorine Demand Test
7.3.2.1 Materials and Methods
Free chlorine demand test
Chlorine demand test was conducted using 1 L of waters from the six reservoirs to
determine whether the addition of corrosion inhibitors and other water matrix factors have any
effects on chlorine demand. Free chlorine residuals and pH of the waters from the six reservoirs
in 1-L beakers were monitored daily for 6 days with daily adjustment of chlorine concentrations.
The beakers used for this experiment were not processed for chlorine demand free, for the
reservoirs will not be prepared for chlorine demand free at the beginning of every weekly cycle.
The initial dose was 1.5 mg/L as Cl2, and the free chlorine concentrations in the waters were
raised to 1.5 mg/L by daily adjustment. Parallel to this experiment, a reservoir with 90 L of water
was used to determine if there is stratification of chlorine concentrations among the locations of a
reservoir (near surface, middle, and bottom). A pump was used to collect 1 L of water from the
middle and bottom of the reservoir, and 10 mL of each sample was used to determine total and
free chlorine concentrations. The same experiments using 1 L of waters and a reservoir with 90-
L water were repeated with an initial dose of 2.0 mg/L as Cl2, and the free chlorine concentration
was raised to 1.5 mg/L by daily adjustment. Samples were collected from the near surface
location of a reservoir because no stratification was observed in the first experiment.
7.3.2.2 Results
The free chlorine concentrations were monitored for 4 days. The initial dose of free
chlorine was 2.0 mg/L, and the concentrations were raised to 1.5 mg/L by daily adjustment from
Day 2. There was a large decrease in the free chlorine concentration of Cu-Pb: ZOP system on
the first day, but the results were similar to each other on other days (Figure 2).
120
Figure 7-10: Free chlorine concentrations in 1 L of waters from the six reservoirs (second time)
0.00
0.25
0.50
0.75
1.00
1.25
1.50
1.75
2.00
0 1 2 3 4 5
Fre
e c
hlo
rin
e (
mg/
L as
Cl2
)
Time (day)
Reservoir (90 L)
Cu-PVC: No corrosionInhibitorCu-Pb: No corrosioninhibitorCu-Pb: OP
Cu-Pb: ZOP
Cu-Pb: Silicate
PVC-PVC: Nocorrosion inhibotor
121
Control of the free chlorine and monochloramine residual in the reservoirs
The concentrations of free chlorine were measured daily to control the free chlorine and
monochloramine residual in the reservoirs to be 1.0 mg/L and 3.0 mg/L as Cl2.
The initial dose of free chlorine was 2.0 mg/L at the beginning of a weekly cycle, and the
concentration of free chlorine was raised to 1.5 mg/L by daily adjustment based on the free
chlorine residual concentration. The amount of a chlorine working solution needed to have the
free chorine residual in the reservoirs to be 1 mg/L as Cl2 was calculated as below. The amount
of a monochloramine working solution needed was calculated in a similar way.
Example:
𝑇ℎ𝑒 𝑎𝑚𝑜𝑢𝑛𝑡 𝑜𝑓 𝑎 𝑐ℎ𝑙𝑜𝑟𝑖𝑛𝑒 𝑤𝑜𝑟𝑘𝑖𝑛𝑔 𝑠𝑜𝑙𝑢𝑡𝑖𝑜𝑛 𝑛𝑒𝑒𝑑𝑒𝑑
=1.5 𝑚𝑔 𝐿⁄ − 𝑓𝑟𝑒𝑒 𝑐ℎ𝑙𝑜𝑟𝑖𝑛𝑒 𝑟𝑒𝑠𝑖𝑑𝑢𝑎𝑙 𝑐𝑜𝑛𝑐.
2000 𝑚𝑔 𝐿⁄ (𝑐𝑜𝑛𝑐. 𝑜𝑓 𝑎 𝑤𝑜𝑟𝑘𝑖𝑛𝑔 𝑠𝑜𝑙𝑢𝑡𝑖𝑜𝑛)× 90 𝐿 (𝑣𝑜𝑙𝑢𝑚𝑒 𝑜𝑓 𝑤𝑎𝑡𝑒𝑟)
Example: Assume the free chlorine working solution and the residual concentration to be
2000mg/L and 1.0 mg/L, respectively.
Example:
𝑇ℎ𝑒 𝑎𝑚𝑜𝑢𝑛𝑡 𝑜𝑓 𝑎 𝑐ℎ𝑙𝑜𝑟𝑖𝑛𝑒 𝑤𝑜𝑟𝑘𝑖𝑛𝑔 𝑠𝑜𝑙𝑢𝑡𝑖𝑜𝑛 𝑛𝑒𝑒𝑑𝑒𝑑 =1.5 𝑚𝑔 𝐿⁄ − 1.0 𝑚𝑔 𝐿⁄
2000 𝑚𝑔 𝐿⁄× 90 𝐿
= 0.0225 𝐿 = 22.5 𝑚𝐿
After the addition of free chlorine and monochloramine, the water in the reservoirs was mixed
thoroughly using an anchor paddle. The concentrations of free chlorine and monochloramine
were measured 2 h after the adjustment.