Proprietary and Confidential. Not for distribution. Improving Energy Security Thru Energy Efficiency, using the LOad Based Optimization System (LOBOS) AEE So Cal Annual Conference 09.22.11

Upload: others

Post on 05-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Proprietary and Confidential. Not for distribution.

Improving Energy Security Thru Energy Efficiency, using the

LOad Based Optimization System (LOBOS)

AEE So Cal Annual Conference – 09.22.11

Page 2: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

• We offer this presentation in the memory of

Gary Gates, a Navy man that fought

tirelessly to save energy while improving

working conditions for Navy personnel. He

is sorely missed by all who knew him.

ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

2

Page 3: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

• Why LOBOS?

• Project Description

• How LOBOS Works

• LOBOS EE

• Case Studies

• LOBOS DR

• Summary

• Q & A

ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

3

Agenda

Page 4: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

GE Ecomagination Challenge

• The Ecomagination Challenge is a worldwide

competition sponsored by General Electric to identify

viable strategies to reduce energy waste and

consumption, as well as viable methods to effectively

produce renewable energy and improve grid/system

performance on a global basis.

• Out of 3,800 entries received and evaluated by GE,

Enerliance is the only firm with two entries in the

top 100.

4 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 5: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

“Poor controls can waste more energy than

great equipment can save.”

Prius with

“Efficient” HVAC

Control Strategies

16 MPG

Prius with “Load

Based” HVAC

Control 99 MPG

11.9 MPG on

the Prius

Why LOBOS?

5 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 6: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Project Description

• The Building 56 Chiller plant at the Pt. Loma Naval

Base serves 24/7 loads including data centers, office

areas and computerized training labs and other

classified areas that we could tell you about, but then

we’d have to kill you.

• The project consisted of adding one new 450 ton VFD

centrifugal chiller to the two existing 350 ton VFD

centrifugal chillers, adding VFD’s to the primary and

condenser water pumps, removing a multitude of

tertiary pumps from the buildings and installing the

Load Based Optimization System (LOBOS) to optimize

the system.

6 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 7: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

History

• The Navy had installed a well marketed optimization system from another firm on a previous project, but after two years of operation, it was not meeting expectations.

• When this project was brought up, there was a huge pushback from many in the Navy, due to concerns about not meeting expectations.

• They reviewed real operational data from several Load Based Optimization System projects and decided to utilize this system for their project.

7 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 8: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

History

• Prior to the Load Based Optimization System (LOBOS)

installation, the plant was run 24/7 with fixed CHWS

temperatures and differential pressure setpoints, as

there was no feedback from the Data Center and

Trainer loads to allow the system to be run more

effectively.

• The timing of the cooling load needs at night and on

weekends is based on the use of the data centers and

trainers, and is totally unpredictable.

• Since it was impossible to predict or know the

schedules of use and the cooling needs of these critical

loads, the system had to be run 24/7.

8 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 9: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Results

• After one year of operation, the M&V process has shown that the results have exceeded savings expectations by over 50%.

• There has been a net reduction of energy used in the chiller plant of over 70%, based on a separate utility meter.

• Additional scope incorporated into the project have added approximately 1,000 MWH of savings that were not expected.

9 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 10: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Plant load 325 tons, Total Plant = 0.28 kW/ton (note the OSA humidity at 105% - previously existing sensor, and why we do

not use RH in any of our code…)

10 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 11: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Many existing loads still have 3-way valves, so secondary flow and pump energy is still

higher than it needs to be. Low CHW temperature differential from 3-ways also drives primary

pump energy higher than it needs to be, so we could eventually get down to 0.22 to 0.25

kW/ton for the entire plant under similar conditions.

11 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 12: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Multiple CT control loops to optimize the chiller plant

while protecting the chillers

12 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 13: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Obvious Savings Directly Attributed to LOBOS

13 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Savings during “Limited Reset Operation” during

commissioning were running 45% until Nov. when we

were directed to shut LOBOS off. Savings for

“Equipment only” changes ran about 12% for the

month that LOBOS was shut off. When restarted,

savings went back to 45% -50%. When full LOBOS

resets were allowed in June, savings climbed to 73%-

75% per month.

Page 14: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

14 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Savings during “Limited Reset Operation” during

commissioning were running 45% until Nov. when we

were directed to shut LOBOS off. When restarted,

savings went back to 45% -50%. When full LOBOS

resets were allowed in June, savings climbed to 73%-

75% per month.

Page 15: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Nozzle Spray pattern – very little

coverage of fill – design flow rate

15 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 16: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Approximate 14” to 16” wide dry area at the

bottom of the fill with the CT fan in bypass

(100% speed) and design CDW flow

16 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 17: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Bottom of the fill with the fan in bypass – 100%

speed, design flow rate

17 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 18: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Bottom of fill with the CT fan off, design flow

rate

18 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 19: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

One cell open to flow – Design flow –

1100 GPM

19 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 20: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Solids Buildup with new fill.

It is obvious where water is flowing and where water is not flowing.

There is more surface area with solids build up than there is clean

area where water is flowing.

20 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 21: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Scaling/Solids

• It can be seen from these pictures that scale is already forming on the fill which has been installed for approximately 6 months.

• We rectified the issue by installing nozzles that were two sizes smaller, and getting up inside the towers and directing the spray nozzles to wet the entire fill at low flow rates.

• Works even better at high flow rates.

• Allows much better use of the CT system, as well as reducing CDW pump energy waste and improving chiller energy performance.

21 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 22: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Future Savings Projects at Pt. Loma

• New fan coil units are being selected at

350 feet per minute face velocity to

double CHW system temperature

differential, improving overall system

efficiency markedly.

• LOBOS being applied to new FCU’s.

22 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 23: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS and VSE Design Strategy

Results for a Large Convention Center

• 4 Variable Speed Drive and one constant speed electric centrifugal chillers

• Total Plant Capacity = 4,600 tons

• Plant converted to Variable Primary Flow/Variable Secondary Flow, with Variable Flow Condenser water pumping as well. This is called “Variable Speed Everything” (VSE).

• LOad Based Optimization System (LOBOS) software added to control the chiller plant.

23 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 24: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS and VSE Design Strategy

Results for a Large Convention Center

(cont’d)

• We removed an Absorption plant, installed and Electric Plant with LOBOS and saved electricity…

– Approximate annual electrical savings when compared to the base case natural gas fired plant is 2,890,000 kWh per year.

– Also saved 117,000 therms of natural gas per year….

24 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 25: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS and VSE Design Strategy

Results for a Large Convention Center

(cont’d)

• Loads vary considerably from AHU to AHU, and room to room so Load-Based Optimization is required. Load Based Optimization looks at each AHU and determines what the chiller plant needs to be delivering, in terms of water temperatures and water differential pressures.

– Cut chiller plant energy consumption by approximately 50%.

• This note from the serving utility to the Building Superintendent says it better than anyone else could:

“Ron.....our billing department is questioning the low usage of two of the sub meters. Is the usage correct?”

Gotta love it!

25 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 26: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Total Plant Operation @ 0.24 kW per ton

(1200 ton chiller serving 377 ton load)

-Report below was generated from the EMS-

26 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Load-Based Optimization reset strategies

look at the AHU loads, and raise the CHW

temperature as high as possible and lower

the CHW differential pressure as low as

possible so that the worst case AHU load is

met, and overall system energy is reduced.

Page 27: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Total Plant Operation @ 0.47 kW per ton (600 ton chiller serving 331 ton load) Less heat transfer surface area and greater pumping system losses drive energy use up – the 1200 ton chiller is more efficient.

27 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

We stopped the 1200 ton chiller and started the

600 ton chiller to serve the same load. This was

done to show that you want to run the most heat

transfer surface area possible when you have

VFD equipped chillers – don’t try to match the

chillers to the load, as you would with constant

speed chillers. (Assumes LOBOS controls, and

VSE Design of the plant systems)

Page 28: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS

• Minimize Financial Risk, Maximize Owner

Savings

• LOBOS Energy Efficiency (EE) and LOBOS

Demand Response (DR) patent protected logic

are pre-programmed, pre-tested and pre-

commissioned software and hardware solutions

that maximize owner savings while minimizing

the financial risks and loss of time associated

with installing advanced control system routines.

28 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 29: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS: How It Works

• Energy Efficiency and Demand Response

control logic is contained in the LOBOS system.

• LOBOS integrates into the existing DDC

Systems via the OPC server, LonTalk or

BACnet software or hardware driver.

• The operating data from the HVAC system is

gathered by LOBOS; the control setpoints are

calculated and sent back out to the local DDC

panels for an optimized PID loop control.

29 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 30: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Simple & Sustainable

• Energy Efficiency

– Most Energy Management Systems (EMS)

leave a substantial amount of savings on

the table

– In many cases, complex or non-

adjustable optimization programs are

disabled or overridden so Facility

Engineers can keep tenants comfortable.

30 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 31: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Control Strategy

• Make it consistent / repeatable from

building-to-building.

• Make it user-friendly so the Operator can

make adjustments within certain parameters.

• Make it self tuning to account for

system/climate variations.

• Improve tenant experience, reduce energy

costs and consumption.

31 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 32: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Pick the Right Optimization Strategy!

• Central Plant Optimization routines must look at the site loads – without knowing AHU load information, you cannot maximize energy savings, or respond to load changes properly.

• AHU Optimization routines are required to minimize energy use and promote occupant comfort! Don’t ignore 40% to 50% of the energy consumption of the cooling system!

• The System Must be Operator Friendly – If the person that designed it cannot explain it in an understandable manner to the people that operate the facility, it is too complex.

32 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 33: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Status at a Glance Efficiency Speedometer

The LOBOS Efficiency

Speedometer is

dynamic in nature.

The levels of

efficiency change

with the loads.

33 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 34: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

AHU Set-up Screen

This page presents

an overview of the

information for each

particular AHU.

There is general

information for the

central plant and a

summary of the

WCAH values

being utilized to

drive LOBOS. On

this page, the user

can opt in/out the

particular AHU to

be monitored by

LOBOS.

34 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 35: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

AHU Supply Temperature Tuning

35 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

The Supply Air

Temperature

Setpoint tuning

page allows for

setting up the

supply fan speed

setpoint, which

should be set as

the value that the

operators would

like to see the fan

speed run at.

Page 36: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

AHU Supply Duct Static Tuning

36 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

The Supply

Static Pressure

Setpoint tuning

page gives

adjustability for

how aggressive

the setpoint will

change to

widening return

air temperature

deviation and

space

temperature

deviation.

Page 37: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Air Handler Overview

37 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Provides an

overview of

values used

in establishing

Worst Case

AHU Size/

Criticality/

Distance.

All floors are

not loaded

alike – the

Plant

Optimization

system must

consider all

loads!

Page 38: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Central Plant Optimization

38 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

To make the

CHWS

temperature

and CHW DP

adjustments

faster or

slower, the

slide bars can

be used to

double the

gain, or cut the

gain in half, or

any amount

between them.

Page 39: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Condenser water return temperature

Condenser water supply temperature

Chiller kW per ton of cooling

Chilled water return temperature

Temp Scale kW/ton Scale

Chilled water supply temperature

Effects of Changing CDW Temp Setpoint on

VFD Chiller System Efficiency

39 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 40: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Case Study – 75% savings at the Navy

Point Loma Project

• This project installed one new variable speed chiller,

instituted a “variable everything” chilled water pumping

system and implemented the LOBOS software into the

existing EMS.

• Overall annual efficiency is running around 0.52 kWh

per ton and at around 200 tons the plant runs at around

0.36 kW/ton.

• The plant operation should be reduced by over 1,500

hours per year, due to “Thermal Flywheel” logic in the

control scheme that shuts down chillers and uses the

cold water that is in the pipes to meet small loads.

40 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 41: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Building 56 at Naval Base Point Loma

– kWH monthly savings.

41 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

At the current

savings rates,

the chiller plant

/ LOBOS

upgrade

savings will

exceed

projected

savings by

more than 55

percent.

Page 42: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Monthly Average kWh Consumption

for Pre and Post TES System Upgrade [From Utility Meter]

42 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

18350 Von Karmen Chiller Plant Monthly Energy Consumption

(average, excluding 2003 due to low occupancy)

100,000

200,000

300,000

400,000

500,000

1 2 3 4 5 6 7 8 9 10 11 12

kW

h/m

o.

Post Modification Pre-Modification

Page 43: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Average Monthly Energy Savings

From TES Upgrade Project

43 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

18350 Von Karmen Chiller Plant Monthly % savings (average,

excluding 2003 due to low occupancy)

0%

10%

20%

30%

40%

50%

60%

1 2 3 4 5 6 7 8 9 10 11 12

Chiller Plant Monthly % savings

Page 44: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Case Study 600 B Street San Diego

Optimized Plant vs. Normal Operation/Equipment

44 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 45: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Case Study Inland Center Mall

• LOBOS control strategies can optimize CHW supply

temperature and CDW supply temperature, as well

as AHU variables.

• Total chiller plant energy efficiency on the following

sample project is averaging less than 0.50 kW/ton,

even on 100°F days.

• Total Plant includes all chillers, chilled water pumps,

condenser water pumps and cooling towers.

45 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 46: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

E-mail from Dave Manley – 86% HVAC

System Energy Reduction

Gentlemen,

• If we reduce usage anymore…we can turn everything off and go home! Overall usage down an amazing 55.89% from last year. HVAC usage down 86.59% from last year, triple checked figures. Duncanization didn’t effect Tower water usage like it did last month. Total monthly breakdown usage shows HVAC = 22%, INTERIOR = 50%, EXTERIOR = 28%. Only increase was in #2 COM. AREA due to increase in RMU’s and contractors using common area power during TI’s.

• David Manley | Operations Manager

• Inland Center Mall

• 500 Inland Center

• San Bernardino, CA, 92408

46 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 47: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Chiller Plant Snapshot: Inland Center

Mall

Chiller @ 0.32

kW/ton

Total chiller

plant @ 0.45

kW/ton,

including

pumps,

chillers and

CTF’s

100°F OSA.

47 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 48: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Complete Day Performance:

Tons & kW/ton

48 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 49: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Complete Day Performance:

Tons and kW/ton

49 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 50: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Case Study

10-Story Office Building; 80% Energy Efficiency Improvement

50 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 51: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Total Plant Efficiency @ 0.38 kW/Ton

At 33% load on

the chiller, the

total HVAC

system,

including fans

and central

plant

equipment is

using 0.51kW

per ton.

51 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 52: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Total Plant Efficiency @ 0.33 kW/Ton

At 55% load on

the chiller, the

total HVAC

system,

including fans

and central

plant

equipment is

using .52kW

per ton.

52 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 53: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

2040 Main Street 750 Ton VFD Chiller System

53 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 54: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Energy Efficiency Summary

54 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

• Properly designed and applied TES systems can reduce site and source energy consumption and enable wind power to become a viable part of the energy infrastructure.

• Energy Efficiency, Demand Response and Demand Reduction Technologies are not mutually exclusive!

• You can start with the most efficient design possible, which reduces demand, then add demand response software and Thermal Energy Storage (TES) if/when appropriate.

• With TES, airside Demand Response controls can be added to further reduce site demand, over and above the central plant peak demand savings.

• It is possible to reduce energy consumption at the site and source, while simultaneously reducing peak electrical demands and T&D congestion and improving occupant comfort.

• It is not cheap, but the benefits and GHG emission reductions are substantial.

Page 55: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Demand Response

(LOBOS DR)

55 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 56: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS DR • Typical DR Control systems require substantial manual

intervention and often do not get utilized because of the

manpower costs associated with enabling them.

• The LOBOS DR 10 Stage is a fully automatic DR control

system that can be applied to an individual building or across an

entire portfolio.

• The system is as close to set it and forget it as you can get.

• Depending upon the facility size and the demand reduction

potential at the site, the SCE Technical Installation Incentive

may cover the entire cost of the DR system, thus eliminating

any owner out of pocket expense.

• On a Portfolio-level project, incentives from the larger facilities

can be applied to offset the costs for the smaller facilities.

56 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 57: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS DR Web Home Page

LOBOS allows

customers to

login from the

web.

57 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 58: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

AHU Selection Dashboard

58 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 59: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Portfolio Bid Allocation Dashboard

59 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

The Portfolio

Demand

Response Module

is intended to be a

master control for

the individual site

DR programs. It

will allocate

individual kW

reduction values to

the various sites if

they are enabled

for DR control.

Page 60: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Demand Response

Central Plant

Configuration

Dashboard

60 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 61: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Demand Response

Typical Air

Handler

Configuration

Dashboard

61 61 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 62: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Demand Response

Our Air

Handler

Summary

Page allows

you to view

what stage

each

individual AHU

is curtailing

too.

62 62 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 63: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Demand Response

Dashboard

allows you to

schedule your

individual

building on a

rotating block

curtailment

based on the

value you

input and the

time you

schedule the

event.

63 63 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 64: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Automated Demand Response

LOBOS ADR

Configuration

& Set-up

Dashboard

64 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 65: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Demand Response

Lighting

Equipment -up to

20 different zones

can be

incorporated

Select the stage

# from the

individual drop

down menu to

begin turning off

the lighting group

when the stage

selected is

activated (set to

zero to Disable

DR Control)

65 65 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 66: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

LOBOS Demand Response

Miscellaneous

Equipment - up to

20 different zones

can be

incorporated

Select the stage

# from the

individual drop

down menu to

begin turning off

the lighting group

when the stage

selected is

activated (set to

zero to disable

DR).

66 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 67: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Demand Response and Automatic AHU Coasting

Cycle Showing Fan Speed Reduction after 5:00 PM

Based on Floor Loading

67 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 68: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Summary

• LOBOS Design and Control strategies save energy while improving tenant comfort and temperature control.

• By packaging the LOBOS system and using it in conjunction with the existing EMS network infrastructure, costs can be dramatically reduced.

• User flexibility is enhanced by allowing the operators to tune their facilities without having to enter the EMS programming code.

• LOBOS helps reduce cooling system related energy consumption by

30% to 50% or more. • LOBOS has been integral to the success of many energy savings

projects. • LOBOS enables you to easily tune your system, which is the key to its

long-term success.

68 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 69: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

Q&A

69 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Page 70: Improving Energy Security Thru Energy Efficiency, using ... · competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well

70 ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for

distribution.

Presented by:

Scot M. Duncan, P.E.

[email protected]

949 370 8582

enerliance.com

roi-engineering.com