I INTOOLS HANDBOOK INDEX MODULE The following activities are part of the index module. 1. Populate the following tables with respect to project. a. Type of instruments and their profiles. b. P&ID No. c. Instrument status (i.e. scope of supply) d. Type of I/O (i.e. AI, AO, DI, DO, Fieldbus, etc.) e. Equipment No. f. Instrument Certification g. Loop types (DCS, PLC, etc.) h. Instrument Location (i.e. Field, LCP, DCS, etc.) 2. Creation of new loop. This is done through “new loop” module tool bar clicking. Add tag in the loop no. one by one. Note : Do not create a tag no. and then attach it with the existing loop no. 3. Duplication of Loop. This is done through “Dup. Loop” icon on module tool bar. On clicking this button, first enter the loop no. from which the new duplicate loop can be created. Then enter the duplicate loop no. and then select the loop components from the pop-up Window. 4. Batch Loop Creation. Go to “Edit” menu and select “Typical loop Manager”. Then add the different components of the loop and save with a name. After this, again go to “Edit” menu and select “batch creation” and select the typical loop and enter new loop nos. and then click “create” button. 5. Deletion of loop. Go to “Edit” menu, select “Loop” then select “delete loop” and then enter the loop no.

Upload: seenubala

Post on 07-Oct-2014

102 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: In Tools Handbook

I

INTOOLS HANDBOOK

INDEX MODULE

The following activities are part of the index module.

1. Populate the following tables with respect to project. a. Type of instruments and their profiles.

b. P&ID No.

c. Instrument status (i.e. scope of supply)

d. Type of I/O (i.e. AI, AO, DI, DO, Fieldbus, etc.)

e. Equipment No.

f. Instrument Certification

g. Loop types (DCS, PLC, etc.)

h. Instrument Location (i.e. Field, LCP, DCS, etc.)

2. Creation of new loop. This is done through “new loop” module tool bar clicking. Add tag in the loop no. one

by one.

Note : Do not create a tag no. and then attach it with the existing loop no.

3. Duplication of Loop. This is done through “Dup. Loop” icon on module tool bar. On clicking this button, first

enter the loop no. from which the new duplicate loop can be created. Then enter the

duplicate loop no. and then select the loop components from the pop-up Window.

4. Batch Loop Creation.

Go to “Edit” menu and select “Typical loop Manager”. Then add the different

components of the loop and save with a name. After this, again go to “Edit” menu and

select “batch creation” and select the typical loop and enter new loop nos. and then

click “create” button.

5. Deletion of loop. Go to “Edit” menu, select “Loop” then select “delete loop” and then enter the loop no.

Page 2: In Tools Handbook

INDEX MODULE

Go to Inst. Table

Select Process Parameter i.e. General, Flow, Pressure Temp. etc.

Enter type of Instrument

Go to Instrument Profile

Go to Wiring module

Go to New loop icon for creation of loop

Under loop no. create loop components

Duplication of loop can be created through “Duplicate” icon.

*

*

For batch loop creation, create a typical loop template in “Typical loop template.”

Note: Set the “Preferences” before starting the index module. All individual users machine should have the same “Preferences”.

Go to “Batch loop” creation select “typical loop” and give loop nos. and then client

“create” button.

Before selecting spec. format, check the format

is okay or not. Same way, create cable to be

attached with instrument.

Note: Do not go by tag nos.

Note: Do not create component first then attach

to loop no.

Note: Suffix loop cannot be created in batch. Only numeric

loops can be created.

Page 3: In Tools Handbook

PROCESS MODULE

Process data can be entered tag no. wise or line no.wise.

Line No.wise Process Data

In the module tool bar, “line” should be selected.

In the pop-up Window, “Line No”. should be selected.

Check the box for “liquid”, Gas/vapour, steam, etc.

Then the process data sheet opens for data entry.

Set the units before entering data.

Issue revision through revision button.

Save.

Choose another line and follow the above steps.

Now in “Action” menu, select “Propagate line data”.

In the pop-up Window, select the line no. and click “propogate”. There is a Window which

will show the no. of instruments in that line.

While propagating the process data for each instrument, there will be a pop Window where

“Release to Inst.” Is to be selected.

Tag No. wise Process Data

In the module tool bar “Instrument” shall be clicked.

In the pop-up Window, i.e. process data sheet, fill the data for the tag no. and save it.

Highlighted Fields

There are two types of highlighted fields only for those instruments whose sizing

calculations are to be done.

(a) Cyan colour highlighted field :

These fields are to be filled with data at process data sheet level and cannot be

changed at calculation sheet.

Page 4: In Tools Handbook

(b) Yellow highlighted field : These fields are also to be filled in process data sheet, but in calculation sheet, the

data can be changed, if required.

Page 5: In Tools Handbook

SPECIFICATION MODULE

There are two types of specification form:

(i) Single form

(ii) Multi form

A form can have more than one page.

Intools has some default spec. form as well as pages.

If you want to create your own specification form, then the following steps are to be

followed:

Open “Inst. Spec. Module”.

Select “Form Editor” & then “New Form”.

Select any page which we want to make a new form for specification.

Save it with the new form no. and a proper name.

Go to Index and Table Inst. Type and select the type of instrument for which this

form is applicable.

Go to “Profile” of the instrument and click on the drop down menu of “Instrument Spec.”

field and choose the new form no.

Go to Index browser, select all the tag nos. of that type of instrument, then right click

on them and select “Generate a Specification”.

Open “Inst spec.module”.

Select “Formats” and then “Open Formats” and select any “form” which will be made

multiform.

Give new name of the form and click “OK”.

New spec. form with “edit Header” Window pops-up.

Select the various fields and double click on it. These fields will come inside “edit

Header” box.

Click save.

FOR

SIN

GLE

FO

RM

FO

R M

ULT

I FO

RM

Page 6: In Tools Handbook

SPECIFICATION MODULE

Second page with the selected field pops up. Choose “Portrait” or “Landscape” and adjust

the columns as required.

Then go to module tool bar and click “Open spec.” and type instrument tag no. with the

form no. on which multiform was created and then click “okay”.

A Window “New Inst. Spec.” pops up. Select “Create new multitag inst. Spec.” and give

drg. No. as tag no. (Master tag no.) and also select “Format name”. Then click “okay”.

Select fluid state in the pop up Window.

New multiform spec. opens. With the master tag name

Go to “Multitag list” page and then click on “AddTag” on the module tool bar.

In the pop up tag no. Window click “find” then in the “Find tag” Window choose the

“Process function” and again click on “find”.

On the “search result” Window, select the tag nos. and click okay.

Selected tag nos. added to the multi tag list.

Template of a specification form: Common data of a particular spec form can be filled through Template of that particular

specification form.

Creation of Template: The following steps should be followed for creation of a template.

go to “Edit” menu and select ‘Form data Template editor’.

‘Select Spec Form’ window pops up. Choose the same specification form which earlier you

have created for that type of instrument. And give name as ‘template for spec form no

……’ / type of instrument’ and click ok.

The spec form opens, Fill the common data which you would like to copy to all the

instrument tags and then save it.

Page 7: In Tools Handbook

Now go to Index module ‘table’ menu. Open Instrument type table and select the type of

instrument for which the Template is made.

Open ‘profile’ of the instrument. Under ‘Copy data from Template’ drop down menu select

the template spec form which you have created. And then click ok. Now the original

specification format of the type of instrument will get / copy the data from the template.

SPEIFICATION MODULE SPEC. BINDER

In spec. binder, we can bind a group of specification data sheets for enquiry and give revision

status of the whole binder. In spec. binder, diff. type of specs. can be put together. For

example, Vortex, DP, PT spec. can be combined and float together as a single enquiry.

The following steps are to be followed in “Spec. Binder”.

Open “Spec. Binder” module.

Create new binder, give proper name.

Expand the new binder, there are following default folders are created by Intools

programe.

(a) Instrument spec. list.

This shows all the tag nos. Inst. Type rev. no. and page no.

(b) Form Notes. This notes of spec. form.

(c) General Notes.

Here, we can write note for the spec. binder.

(d) Specification sheet. Here we attached all the spec. sheets of inst. for the binder.

(e) Change Summary Report

This gives all the changes of all the specifications in the binder in report format.

Go to “Specification sheet” folder and right click on it and select “Assign Specification”.

In the “Find Tag” pop up Window, choose the tag no. from “search result” Window.

Page 8: In Tools Handbook

SPECIFICATION MODULE

SPEC. BINDER

After attaching all the tag nos. again right click on “spec. sheet” and select “spec.

change notification” option.

In the pop-up Window, “Spec. change Notification” column for “changed” against

each tag, change the status “Yes” or “No” depending on the spec. change of that

tag. Then click “okay”.

Then go to Binder level and right click on it and choose “Print”.

In “Print”, pop-up Window select “Working Issue” tick () on “show print review”

and click “okay”.

Note : In this “Working issue” print view all the revision fields will be highlighted as

it does for the next revision.

It is advisable to check all the revision fields before actually issuing formal revision.

Now again go back to binder level and right click on it and select “Revision”.

In the “Revision” pop up Window, fill the boxes as per the requirement for new

revision, click new and fill the revision columns and click “okay”.

Go to “Print” Window and select “Formal Issue” and revision no. and click “okay”.

Page 9: In Tools Handbook

SPECIFICATION

Go to spec. module

Go to “Form editor” & “New Form” & select spec. page

Save the page as New Form no.

Go to Index table and Inst. type and Inst. Profile and attach this new form.

Go to Index browser select same type of Inst. And right click and choose “Generate

Spec. sheet.

Go to Spec. binder and create different binders folders.

Under a particular binder, select “specification”. Then go to “Action” menu

and select “Assign Spec.”

Select the specifications which all are coming to this binder.

Under a particular binder, select “specification”. Then go to “Action” menu

and select “Assign Spec.”

Page 10: In Tools Handbook

HOOK-UP

Go to “Preferences” from file menu

Set the “Preferences” of “Loop” and “Hook-Up”

Go to Hook-Up module

Create different categories of “hook-up” header as project requirements.

Create sub-categories of hook-up and attach CAD drg with each sub-category of

hook-up.

Go to “Action” menu and select “Hook-up” type – Inst. Type.

Go to “sub-category” attach the tag nos. through right click on the sub-category

and go to “hook-up tag”.

Now from the table, select the correct tag no. for the relevant hook-up.

Select the type of Inst. from the type of Instrument table.

Note : Hook-up drg. Revision: Select sub-category and right click on it, then go to “Hook-up drg. list” and click on it. Then do the revision on that drg.

* For drg. Attachment, go to browser then go to “temp Instrumentation hook-up CAD drg.

Note : You can select more than one type of inst..

Generate hookup drg. In sub-cat. level by right click and choose “generate hookup.”

Go to hook up Table and go to “item Library” and create main library.

Again go to table and select “item sub-library”.

Go to “Item List” at the module icon.

List all types of hook-up materials to be used. Note : Serial no. of all the items should be same as used in hook-up drg.

Go to hook-up Manager and sub-category right click on it and select “hook-up items relevant to that hook-up drg.

Note : To get BOM go to sub-category or Main Header category and click “BOM” icon at module menu. For whole Plant BOM select all “Header categories” and click BOM.

Page 11: In Tools Handbook

WIRING MODULE

The wiring module is based on “Panel” and “Cable” concept. Any object which requires a

cable connection is called “Panel” and joining two panels are “Cable”. Each panel will

have terminals as per its requirement. Similarly, different types of cables will have different

types of wires in it.

So, panels will be following : Instrument, Junction Box, Marshalling Cabinet, System

Panels, etc. and cables will be single pair, multi pair, core cable, etc.

In wiring module, the following steps will be followed:

[Note : We are going to make instrument panel].

Open “Wiring module”.

Click on “Default” panel.

On pop-up “Default Panel Manager” right click and select “New Inst. Panel” and further

to “Device Panel (conventional)”.

Give a name of the “Device panel” and the device panel will be created with the name.

Now we have to provide terminals as per the instrument requirements.

Right click on newly created device panel and select “New” and then “Strip / I/O”.

On pop-up Window of “Strip Terminal configuration” click on “New” button.

In the pop-up Window of “Terminals in pattern” choose the no. of terminals as required.

Give a name to this new terminal strip. On the right hand side of the Window under

“Terminal numbering” tick mark the boxes as per requirement. Prefix-suffix with the

number also can be set here.

Note : Before creating the terminal strip, one should be very clear about the instrument wiring

and the number of terminals with its numbering philosophy.

After filling the information in the Window, click “Save”.

Now in the same Window, “Strip Terminal Configuration” click on “Create”. Now,

the same terminal strip will be created under the new “Device Panel”.

Note : Expand the “device panel” and see the terminal strip under it.

Page 12: In Tools Handbook

Similar way JB, Marshalling rack and system cabinet will be created.

Note : While creating JB, choose “JB (generic)”.

While creating MR, choose “Marshalling rack”.

While creating Syst. Cabinet, choose “DCS” or “PLC” in the pop up Window.

After creating these panels, create terminal strips in them as required.

For MR and Syst. Cabinet creation follow the approved drawing of the DCS vendor.

Inside any panel, we can create as many as different terminal strips.

I/O cards are to be created inside “DCS” panel while “FTA” or “Signal Conversion

Cards” can be created in MR or in “DCS” panel depending upon the system

philosophy.

Creation of “Apparatus”

Generally, “apparatus” are required when wiring connections on a device are dissimilar, i.e.

incoming wiring terminals and outgoing wiring terminals are different. For example, signal

splitter, “FTA” card or relay.

The following steps are to be followed to create an “Apparatus”.

Right click on the panel on which the “Apparatus” will be installed.

Go to “New” and further select “Apparatus”.

Give a name (relevant name like FTA, Relay, etc.) to it. Now, come down to the

“Apparatus Configuration” Window. Here, depending on the apparus wiring connection,

create “Left” and “right” terminal nos. accordingly and give number of terminals.

Depending upon the number of signals connected on a single “Apparatus” choose the

no. in “Number of apparatus-es” in the box. Then save it and after that click on “create”

to create the apparatus in the selected panel.

Page 13: In Tools Handbook

Now, after creating all “Typical” panels in the “Default” panel, open the “Panel” which is the

project specific panel. Then drag each created panel except instrument device panel in the

“Panel” and give name as per the naming philosophy i.e.

for JBs put the actual JB name

for MRs put the actual MR name

for System put the actual System Cabinet name

Creation of Instrument Device Panel :

Go to Inst. Index module. Select “Table” on the menu. Then go to “Instrument Type” and

select a type of instrument. Say “Pressure Transmitter” is selected. After selecting “PT” go to

profile and then its “Wiring & Control System” Window.

In the “Default Device Panel” box in the drop down table, choose the created device panel

which will suit to this type of instrument.

Similarly, after cable creation, attach a particular cable in the “Conventional Connections” box

by “new” button.

So now, for “PT” type of instrument a particular type of “Device Panel” & “Cable” is attached.

Now click “okay”.

Now go to index browser, select all the particular type of “PTs” and then right click on them

and select “Generate Device Panel & Cable”. All selected “PTs” will now be available in the

“panel” Window with tag nos.

Creation of Cables

All typical cables will be created in the “Default Cable”. For creating a cable (say 12 pair) the

following steps are to be followed:

Open “Default:” cable.

“Default Cable Manager” window pops-up.

Page 14: In Tools Handbook

Right click anywhere inside of the “cable Manager” box and select “cable”.

“Cable configuration” window pops-up. Click on “New” button, another window “New

Cable Configuration” pops-up. In the box of “Total No. of sets” choose 12 as we are

creating 12 pair signal cable and in the box of “default cable set” type choose “pair” or “pair

with shield”. Then ‘OK’ it.

Now, in the “cable configuration” window shows a 12 pair cable without pair no. but default

wire colour. Now, in the cable set, type pair #1, pair #2 …… pair #12 and give a name of

the cable. Then press “Apply” button and “save”. Now, in the same window, press

“create” button and “cable properties” window pops-up. Choose the glands as per the

cable diameter and click OK.

“Close” the “cable configuration” window. A new cable of 12 pair is created in the “Default

cable manager” with 12 sets of pair.

Like 12 pair cable, other typical cables can be created in the “Default Cable Manager”. Now,

open the “Cable” which is project specific cables. Drag a “multi pair cable” from the “Default

Cable Manager” to “Plant cable Manager” with a cable name. For example, JB NO.100-IM-

001, the multi pair cable No. is C-100-IM-001.

Like this, for all JBs, a particular cable should be dragged from “Default Cable Manager” to

“Plant Cable Manager” and give name to that cable.

Note: For Branch cables, do not drag them, instead attach them in the Instrument type profile.

Now, all possible panels with terminal strips and cables with wires are created in the “Plant

Panel” and “Plant Cable Manager”.

Actual wiring we will start after I/O assignment in the system panels.

Creation of I/O Cards Before I/O assignment, we have to create the rack, slot etc. in the system cabinet. The

following steps are to be followed:

Page 15: In Tools Handbook

Right click on a system cabinet and then select “new” and choose “Strip or I/O card”.

“Strip Terminal Configuration” window pops-up.

Give name as per type of card. Fill other information as per the card details i.e., total

number of terminals, number of terminals per channel, first channel starting at etc. and

terminal numbering philosophy. Then save it and then click “Create” button.

“I/O card Properties” window pop-up. Give a proper name and click on “Control Syst”.

In the “Control Syst” window, fill the details in the “Control System Details” boxes. i.e.,

a) System I/O type : Choose AI from drop down menu

b) Control Processor : Choose the controller

c) Choose the Rack : Say rack one, R1

d) Position (i.e slot no.) : Say 1

If it is redundant I/O, then click on “Define a redundant I/O”. Once you click on “redundant

I/O”, the secondary location boxes will be enabled. Fill the redundant I/O card location as

per the system design. Click ‘Ok”.

Note: If any card is taking double width, then click on “Double width” box.

Now, a particular I/O card has been created in the selected system cabinet. Similarly, create

all other cards in that cabinet. If any type of card is more than one, then you can “Duplicate”

the card instead of creating a new one. Right click on the card and select “Duplicate”.

I/O Assignment

The steps are as follows :

Go to “Plant Panel” and select any system cabinet.

Expand the system cabinet. Choose a particular I/O card; Say AI card.

Page 16: In Tools Handbook

In the module menu bar click on “I/O”

OR

right click on the card and select “I/O Assign” on the pop-up window.

I/O assignment” window pops-up. This window is divided vertically into halves. In the left

half, all the tags which are yet to assign will be shown. (i.e. only a particular type of signal

i.e., A1, A0, D1 D0 etc.). On the right half, is the particular card and its channel numbers.

Now, drag a tag no. from left half and release it on a particular channel on the second half.

Like this, I/Os can be assigned against each card.

Before actual wiring the following activities are to be completed :

i. All the ‘Panels’ with terminal strips in the “Plant Panel Manager” i.e. instrument

device panel, JB, MR and System Cabinet.

ii. All types of cable in “Plant Cable Manager”

iii. All the types of instrument in the Index browner mode should be assigned

“Generate device panel and cabinet”.

Now to start with wiring module, we should always start from the field side and then

progress towards control room side.

Since the instrument is already attached with cable, we shall start connection from field

JB.

The following steps are to be followed :

Go to a particular JB and expand it.

Select terminal strip and then click “Connection” on module menu bar.

The JBs terminal strip opens. Now click on “Cables” on module menu.

All unconnected instruments are available in the “Plant Cable Manager”. Drag the

instrument cable on the screw of the JB terminal (left side)

A window “Cable Connection Definition” pops up. Choose “Connection type” from

the drop down menu and click on “Connect “ button.

Page 17: In Tools Handbook

The instrument will be connected on the left hand side of the JB.

After connecting all the instruments on the left hand side of the JB, drag the multi

pair cable from the “Plant Cable Manager” and release it on the right hand side

screw of the JB terminal strip.

The multi pair is now connected to the JB.

Note : Now on the JB terminal strip you can see that the tag no. on the left hand side

are automatically propagated to the right hand side. At the same time cable nos.

branch as well as multi pair cable are seen.

After the JB connection, the other end of multi pair cable is to be connected to the

Marshalling rack.

Open “particular Marshalling Cabinet’s terminal strip in “Plant Panel Manager”

window.

Select the terminal strip where the multi pair cable will be connected. Right click on

the terminal strip and choose “Connect” or click on “Connect” at the module menu

bar.

“Connection” window of marshalling strip pops-up.

Drag the multi pair cable of he connected JB and drop on the left hand side, screw

terminal of the terminal strip.

Note : In the “Cable Connection Definition” window select “2in a row” connection type

for all cable sets. (This is because for shield no terminal is used, a common shield bar

at the bottom is generally used).

The tag nos. on the JB are now propagated upto the marshalling cabinet.

Now on the right hand side the terminal strip will be connected to “FTA” or “signal

stabilizing card”. Here we have to carryout cross wiring.

Page 18: In Tools Handbook

Before cross wiring let us go to I/O card level, I/O card should be connected to ‘FTA’

through prefab. cable.

Create a prefab cable in the similar way of cable creation in default cable manager

and then bring the same in “Plant Cable Manager” with a cable name.

Then go to DCS I/O card and click “Connection” and drop the prefab cable (which

connects the I/O card and the FTA).

(Note : On the left hand side al the tags assigned to this I/O card will be seen).

Now go to “FTA” card which was created in the marshalling cabinet. (This may be

an apparatus). Select the “FTA” and click “Connection”.

Terminal strip of DTA pops-up. Now open the “Plant Cable Manager” and select the

prefab cable (which was connected to I/O card) and expand it.

Now go to the wire level and drag and drop one by one on the right hand side of

the terminal strip.

(Note: You can see the tag nos. are also seen on right hand side after connecting

the wire).

Cross Wiring :

Now, we have completed wiring from field instrument to JB to Marshalling cabinet and

other side from DCS I/O to FTA card one side.

Between field side marshalling terminal and FTA card we have to connect. This is to be

done by cross wiring.

The following steps are to be followed :

Go to marshalling cabinet terminal strip where the cable of the JB is connected and

select it at the same time to the FTA terminal strip and select the same.

Page 19: In Tools Handbook

After selecting both of them go to the module menu bar and click “Cross Wire”.

“Cross Wire” window pops-up. Select primary strip as marshalling strip and

secondary strip as FTA strip.

Now you can see both sides the tag nos.

Click on the screw terminal of any tag on MR-strip and then click on the terminal on

FTA-strip of the same tag. Thus a single wire is cross wired. Like this one by one

all the tags will be connected.

Note : on FTA strip window, after each wire connection a “screw” will pop-up on the

left side of each terminal).

Now all the connections were made. To see whether the connections are made O.K or

not go to “Loop Drg.” module, go to loop no. and then go to “generate” and select

“Point to Point Wiring Dia.” to view the connection.

Jumper Connection :

Whenever jumper connection is required go to that terminal strip and click

“Connection”.

The terminal strip opens

Now click on “Jumper” button below at the module menu bar.

Select the terminals where the jumper is to be made, choose which side of the

terminals and colour and then click “O.K”.

Now the jumper connection is made, and the selected terminals are highlighted with

colours chosen.

Local Signals :

Local signals are those signals whose wiring is not starting from the actual instruments

(i.e. no branch cable by IC). Some of the local signals are as follows :

Page 20: In Tools Handbook

a) MCC Control Signals : These signals (i.e. running start / stop, current etc.) are

wired by EL up to an interface cabinet where from IC connects the signals into

DCS / PLC system. So, wiring is to be done from interface panel.

b) Pump Seal Signals : Some times IC consider a common pump seal contact

instead of individual pressure and level switch signals. This is because to reduce

I/O count at system In that case, we consider the common signal as a “Local

Signal” in Intools.

c) Double Limit switch connection from a common JB.

Local signal should be considered as an I/O in the system, but do not generate any

“device panel & cable” for it. Since the multi pair cable or a pair cable will be connected

from the intermediate terminal strip.

For such local signals wiring, following steps are to be followed :

Go to “Default Panel” and select “Device Panel (Conv)”.

Now in this new device panel create the number of terminals as required for the

local signal.

Then drag and drop this panel to “Plant Panel”.

Open the terminal strip of the newly created “Local Signal”.

Double click on the right hand side screw terminal.

A “Terminal Connection” window pops-up, click on “Signals”.

Window of “Local Signal” pops-up.

Select the tag no. of the local signals and click “Create” one by one and then

“Close” the window.

Now in “Terminal Connection” window, on the right hand side box, under signal all

these tags (local Signals) will be listed.

Now select a tag and connect its wire to the particular terminal no. from the drop

down box and also give “Sequence” and “Signal Level” and then click save.

Similar way connect all the wires of the “Local Tag”.

Now the “Local Signal” tag will be propagated on the terminal strip.

Page 21: In Tools Handbook

LOOP DRAWINGS

Preferences

Open the “Loop Drawing” module. In the menu bar, go to “File” menu and select

“Preferences”. Expand the “Loop Drawing” in the preference window and click on “General”.

For AutoCAD loop drawing, the following fields should be tick marked:

a) Use macro function

b) Display references to wiring reports automatically

c) Explode block in AutoCAD

d) Create “error.log” file

e) Select “Microstation SE/J” in microstation version

f) Select “Text” in “Autocad 2000 micro result type”

g) Select “Decending” in “Revision macro order”

h) Select date format as per project philosophy.

i) Select “per loop” in “Generation option”

j) Select “visible” in “Generation dialog box”

k) Select “Autocad” in “Default Generation Method”

Loop drawing module is basically divided in 3-parts:

i) Border

ii) Logo

iii) Wiring blocks

Loop drawings can be generated in the following softwares:

i) Autocad

ii) Micro station

iii) Smart Sketch

Out of these, we will consider “AutoCAD” which is widely used as drafting tool.

After completing the setting in “General” go to the next folder “CAD file location” and click on it.

The following things should be set:

a) CAD folder : C:\Program files\Autocad\acad2004

[This, basically the path where executable “AutoCAD” program file is located]

Page 22: In Tools Handbook

b) CAD configuration folder : C:\Program files\Autocad\acad2004

[This is the location of CAD configuration file]

c) CAD Function Folder : I:\CAD\Cad Func. [I drive is Intools server] This is to locate the “Cad func.” File location in Intools. The

software uses CAD function files when translating the macros.

d) Open drawing files from : I:\CAD\DWG

[This is to locate the folder where the drawings are saved and further open]

e) Drawing Block Folder :I:\CAD\Blocks

[This is to locate the default block files]

f) Tick on “Save drawing automatically” box

g) Output Drawing Folder : C:\Documents & setting\UUMU…….\Desktop

[This is the place where the loop drawings will be saved]

After setting the above fields, click “OK”.

Now click on the “Block type” on the module menu bar.

“Block Types” window pops-up. Click “New”

Another window “Block type properties” pops-up. Give name to “Block type” and “Block

type Description”.

[Note: Tick on the box for “set category as general” if you want that block should

appear in all the loop drawing. For example, “Border” and “Logo” blocks are to

be ticked].

Newly created block will appear in the “Block type” window. Click OK.

Now, click on “Blocks” on the module menu bar.

A window “Blocks” pops-up. Select the newly created block type.

Select “Block” in the drop down of “select a column heading”

Then click on “New” on the right hand side of window.

“Block Properties” window pops-up. Give block name & description. In the “Drawing block

file” browse and go to I:\CAD\Blocks\AI and choose the relevant block.

Note: In the “origin” field X & Y origins are to be set to place the selected block in the loop

sheet. If more than one block are to be placed, then Y origin are to be set in such a

way that two blocks should not be printed one above another. By giving the value we

adjust the X & Y coordinate of the blocks in the loop sheet.

Page 23: In Tools Handbook

Click “OK”, now the new block and descriptions will appear in the “Blocks” window listing

area.

Click again “OK” and save it.

Similar way, we should create “Border”, “Logo” blocks and set them as “General” block. Now

after creating the above blocks, we have to assign the drawing to the instrument type.

Click “Assign” button on the module menu bar.

“Block Instrument type assignment” window pops-up. Scroll down on the type of

instrument and select the type of instrument and then click on “assign” on the pop-up

window.

“Assign blocks to instrument type” window pops-up. Select the block type which is

relevant for the particular type of window and click OK. “Border” & “Logo” block also

should be selected. After assigning all the blocks click “Close”.

Now, click “Select loop” on the module menu bar. Type the loop number which loop

drawing is to be made.

“Loop Manager” window pops-up with the loop number. Right click on the loop number

and choose “generate loop drawings”.

“Generate loop drawings” window pops-up.

Select the following in the pop-up window.

i) Generation method : CAD

ii) Tick mark on “use macro function”, “per loop” and click “OK”.

After generating the loop diagram, we now put the revision marking on the loop.

We can mark the revision on individual drawing, as well as in a group of drawing.

Select all the loops in the “loop manager” Window and right click on them and select “Loop drg

list”.

“Loop Drg List” Window pops-up. Again select all the loops and click on “revisions” button.

“Revisions” Window pops-up. Select the revision method and click “new”. Fill the relevant

column and click “OK”.

Get more free e-books on Instrumentation at www.ebookstore.co.in