index []powered by rosenberg gmbh forward curved direct drive centrigugal fans super vent single...
TRANSCRIPT
Saudi Arabia:Tel: +966 1 265 4551Fax: +966 1 265 4550
Dubai Head Office:Tel: +971 4 706 9777Fax: +971 4 706 9787
Abu Dhabi Branch:Tel: +971 2 645 0107Fax: +971 2 645 0167
Email: [email protected] 50708, DubaiUnited Arab Emirates
Cabinet Fan
SV-1
SUP ER VENTB y B e t a I n d u s t r i a l
T H E A I R M O V E M E N T G R O U P
Poweredby
INDEX pages
INTRODUCTION
CONSTRUCTION
PERFORMANCE CHART
ACOUSTIC DATA CHART
DIMENSION SHEET - SINGLE CABINET FANS
DIMENSION SHEET - TWIN CABINET FANS
PERFORMANCE GRAPH
WIRING DIAGRAM
ACCESSORIES
01
02
03
04
05
06
07-13
14-15
16
SUP ER VENTB y B e t a I n d u s t r i a l
SUPER VENTSINGLE AND TWIN CABINET FANS
Powered by Rosenberg Gmbh Forward Curved Direct Drive Centrigugal Fans
Super Vent Single & Twin Cabinet fans are general purpose ventilation units which have
highly versatile applications in modern ventilation systems.
These versatile low noise air movers provide reliable economical and effective ventilation.
The twin fan assures continuous operation. Each model of this series has two similar capacity
fans which enable flexibility of independent continuous or simultaneous operation.
ADVANTAGES
“ Compact and space saving design
”Housings are weather resistant, fabricated from pregalvanized sheet steel.
Stainless steel and aluminum casings are available on request.
“Epoxy or powder coating and acoustical insulation (on inner side of housing) can be
provided as optionals.
”External Rotor motor with built-in thermal overload protection.
“100% speed controllable external rotor motor.
”Extremely low starting current.
“Factory installed Back draft dampers as standard.
” 100% standby fan + 100% duty fan.
“ Powered by ROSENBERG Gmbh - double inlet forward curved direct drive centrigugal flow
fans.
“ Casing with double skin upon request.
APPLICATION
Super vent Single & Twin Cabinet fans are versatile in application. These fans can be used in
ventilation, recirculation and air conditioning systems for modern residential, commercial
and industrial zones. These fans can be used for inline, roof mounted or ceiling suspended
applications.
01
T H E A I R M O V E M E N T G R O U P
Poweredby
Introduction
SUP ER VENTB y B e t a I n d u s t r i a l
Fan Housing
Fans Housing made from heavy duty galvanized steel sheet with G90 coating. (Housing of
stainless steel or aluminum can also be provided on request. Additionally optional powder or
epoxy coating is available).
All cabinets have easy access to fan and motor by a removable top cover.
Impeller
Impeller is forward curved made from galvanized steel directly mounted external rotor
motor and dynamically and statically balanced in accordance with DIN / ISO 1940 G2.5 on
two levels.
Motor
The 100% speed controllable external rotor motor satisfies protection class IP 44 according to
DIN 40050. Maintenance free ball bearings closed on both sides, sealed for life. Motor winding
comply to insulation class F with moisture impregnation and built-in thermal overload protec-
tion.
Documentation
Manufactures declaration and operating instruction are according to machinery directive
89/392/EEC, CE identification in accordance wit hEMC-directive 89/336/EEC and low voltage
directive 73/23/EEC, are available from m/s Rosenberg on request.
Installation
Easy installation of cabinets with mounting brackets which are provided along with the cabi-
nets.
02
T H E A I R M O V E M E N T G R O U P
Poweredby
Construction
SUP ER VENTB y B e t a I n d u s t r i a l
03
Performance Chart
T H E A I R M O V E M E N T G R O U P
Poweredby
Model Fan Code
Volt WattFrequency
(Hz)
Current(A)
Speed(RPM)
Air Flow(CMH)
Pressure(Pa)
IP
SV 150
SV 200
SV 225
SV 250
SV 315
SV 375
SV 375 A
SV 400
SV 400 A
SV 450
SV 500
SV 550
SV 600
2GDS15 120 x 126L
4GDS25 133 x 190L
4GDS25 146 x 180L
4GDF55 160 x 160L
DRAE 181-4L
DRAE 195-4L
DRAE 249-4L
DRAE 251-4L
DRAE 279-4
DRAE 281-4
DRAD 281-4
DRAD 315-6
DRAD 315-4
230
230
230
230
230/240
230/240
230/240
230/240
230/240
230/240
400/415
400/415
400/415
0.47
0.35
0.53
0.72
1.2/1.3
1.8/2.52
4.75/6.18
6.0/6.5
6.9/7.46
3.6
3.6
3.7/3.91
8.9/9.65
100
76
116
164
260/320
400/651
1070/1620
1350/1500
1550/1870
1900/2340
1900/2200
2100/2500
4800/6350
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
1640
1160
1110
1245
1010/1031
1150/1298
1100/1547
1240/1430
1160/1266
1140/1384
1140/1400
780/882
1350/1627
370/350
580/610
740
875/940
1300/1230
2100/2268
3400/4100
4400/4500
4500/4300
5800/4700
6650/7000
7400/8550
9500/9000
275/375
105/136
145/165
175/228
220/310
290/400
390/552
450/640
550/724
630/800
630/870
290/435
600/750
44
44
44
44
54
54
54
54
54
54
54
54
54
50/60 Hz 50/60 Hz50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
SUP ER VENTB y B e t a I n d u s t r i a l
04
Acoustic Data Chart
T H E A I R M O V E M E N T G R O U P
Poweredby
Model
SV 150
SV 200
SV 225
SV 250
SV 315
SV 375
SV 375A
SV 400
SV 400A
SV 450
SV 500
SV 550
SV 600
Fan Code
2GDS15 120X126L
4GDS25 133X190L
4GDS25 146X180L
4GDF55 160X160L
DRAE 181-4L
DRAE 195-4L
DRAE 249-4L
DRAE 280-6
DRAE 279-4
DRAE 281-4
DRAD 283-4
DRAD 315-6
DRAD315-4
63
35
40
43
44
48
47
49
47
53
56
57
53
61
125
35
40
43
43
48
48
47
45
51
54
55
51
59
250
37
38
42
43
56
59
45
43
49
52
53
49
57
500
36
36
38
39
41
40
47
45
51
54
55
51
59
1000
34
35
36
37
39
39
47
45
51
54
55
51
59
2000
31
34
33
34
39
36
42
40
46
49
50
46
54
4000dB(A)
@ 1 mtr.
30
31
28
29
34
29
31
29
35
38
39
35
43
41
45
47
48
51
52
54
52
58
62
62
58
66
FOR SINGLE & TWIN CABINETS FAN
OCTAVE BAND (Hz)
SUP ER VENTB y B e t a I n d u s t r i a l
05
Dimension Sheet
T H E A I R M O V E M E N T G R O U P
Poweredby
Model
SV 150/S
SV 200/S
SV 225/S
SV 250/S
SV 315/S
SV 375/S
SV 375A/S
SV 400/S
SV 400A/S
SV 450/S
SV 500/S
SV 550/S
SV 600/S
Fan Code
2GDS15 120X126L
4GDS25 133X190L
4GDS25 146X180L
4GDF55 160X160L
DRAE 181-4L
DRAE 195-4L
DRAE 249-4L
DRAE 280-6
DRAE 279-4
DRAE 281-4
DRAD 283-4
DRAD 315-6
DRAD315-4
A
306
420
420
430
475
614
734
471
734
734
734
834
834
B
80
94
94
114
124
118
178
192
178
178
178
216
216
C
146
232
232
202
227
378
378
357
378
378
378
402
402
D
260
298
298
344
410
478
618
720
652
720
720
720
720
E
80
93
93
100
145
145
145
145
145
145
145
145
145
F
146
234
234
230
185
324
444
451
444
444
444
544
544
G
140
247
247
347
347
390
434
587
496
587
587
648
648
SINGLE CABINET FANS
SINGLE CABINET FANS
All Dimensions are in mm
SUP ER VENTB y B e t a I n d u s t r i a l
06
Dimension Sheet
T H E A I R M O V E M E N T G R O U P
Poweredby
Model
SV 150/T
SV 200/T
SV 225/T
SV 250/T
SV 315/T
SV 375/T
SV 375A/T
SV 400/T
SV 400A/T
SV 450/T
SV 500/T
SV 550/T
SV 600/T
Fan Code
2GDS15 120X126L
4GDS25 133X190L
4GDS25 146X180L
4GDF55 160X160L
DRAE 181-4L
DRAE 195-4L
DRAE 249-4L
DRAE 280-6
DRAE 279-4
DRAE 281-4
DRAD 283-4
DRAD 315-6
DRAD315-4
A
532
476
746
746
826
1110
1290
1290
1290
1290
1290
1452
1452
B
80
84
84
114
124
118
178
192
178
178
178
216
216
C
146
232
232
202
227
378
378
257
378
378
378
402
402
D
260
298
298
344
410
478
618
720
652
720
720
720
720
E
80
93
93
100
145
145
145
145
145
145
145
145
145
F
372
560
560
546
536
820
1000
1000
1000
1000
1000
1162
1162
G
140
247
247
347
347
390
434
587
496
587
587
648
648
TWIN CABINET FANS
TWIN CABINET FANS
All Dimensions are in mm
SUP ER VENTB y B e t a I n d u s t r i a l
07
Performance Graph
T H E A I R M O V E M E N T G R O U P
Poweredby
SV 150
SV 200
SV 225
SUP ER VENTB y B e t a I n d u s t r i a l
08
Performance Graph
T H E A I R M O V E M E N T G R O U P
Poweredby
SV 250
SV 315
SV 375
SUP ER VENTB y B e t a I n d u s t r i a l
09
Performance Graph
T H E A I R M O V E M E N T G R O U P
Poweredby
SV 375
SV 400
SV 400 A
SUP ER VENTB y B e t a I n d u s t r i a l
10
Performance Graph
T H E A I R M O V E M E N T G R O U P
Poweredby
SV 450
SV 500
SV 550
SUP ER VENTB y B e t a I n d u s t r i a l
11
Performance Graph
T H E A I R M O V E M E N T G R O U P
Poweredby
SV 600
SUP ER VENTB y B e t a I n d u s t r i a l
12
Wiring Diagram
T H E A I R M O V E M E N T G R O U P
Poweredby
SINGLE PHASE STANDARD VERSION AUTO CHANGE OVER PANEL(Input current highter than 6A)
SINGLE PHASE STANDARD VERSION AUTO CHANGE OVER PANEL(Input current highter than 6A)
SUP ER VENTB y B e t a I n d u s t r i a l
Single & Three Phase Direct Drive Super Vent Single & Twin Cabinet Fans.
Units are supplied with independent terminal connections to the motor and air-flow
switches, facilitating wiring into any approved control system.
An electrical isolator (by others) must be provided to enable motors and sensing switches to
be isolated from the electrical supply when required for maintenance or any other purpose.
Links are factroy fitted as shown on the wiring diagrams to minimize installation costs.
These links may be removed as necessary to suit individual installation requirement.
Controls (Twin Fans)
This control provides manual selection of either fan for duty sharing or test purposes through
a selector switch in addition to automatic changeover on fan failure; loss of air flow is
detected by the selected fan sensing switch (a normally closed switch, open when airflow is
correct.)
The switch closes to bring into operation the standby fan to maintain full extraction.
At the same time a local failure warning lamp lights and remote warning indicator (if
installed) is energized, integral fuses protect the control and associated wiring.
This control unit provides automatic duty sharing facilities, as well as the automatic change
over on fan failure described for the unit.
An incorporated timing mechanism brings alternative fans to operation at 12 hourly inter-
vals, ensuring optimum duty sharing and thus maximum bearing life. An overide switch is
fitted to allow manual selection test purposes.
13
T H E A I R M O V E M E N T G R O U P
Poweredby
Accessories
Saudi Arabia:Tel: +966 1 265 4551Fax: +966 1 265 4550
Dubai Head Office:Tel: +971 4 706 9777Fax: +971 4 706 9787
Abu Dhabi Branch:Tel: +971 2 645 0107Fax: +971 2 645 0167
Email: [email protected] 50708, DubaiUnited Arab Emirates
Cabinet Fan
SV-1