indoor unit cs-mps12skh cs-mps15skh cs-mps18skh … · 5 2. specification model indoor/outdoor...

84
© Panasonic Corporation 2016 Order No: PAPAMY1611008CE Indoor Unit CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH Destination Brunei Cambodia Indonesia Myanmar Thailand Vietnam Please file and use this manual together with the service manual for Model No. CU-2S18SKH CU-3S27SBH CU-3S28SBH CU-4S27SBH CU-4S34SBH, Order No. PAPAMY1611007CE. WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public. It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service or repair the products dealt with in this service information by anyone else could result in serious injury or death. PRECAUTION OF LOW TEMPERATURE In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit. FAN SPEED AIR SWING AUTO COOL DRY FAN SPEED AIR SWING OFF/ON IMPORT ANT SAFETY NOTICE There are special components used in this equipment which are important for safety. These parts are marked by in the Schematic Diagrams, Circuit Board Diagrams, Exploded Views and Replacement Parts List. It is essential that these critical parts should be replaced with manufacturer’s specified parts to prevent shock, fire or other hazards. Do not modify the original design without permission of manufacturer. !

Upload: others

Post on 06-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

© Panasonic Corporation 2016

Order No: PAPAMY1611008CE

Indoor Unit CS-MPS9SKH

CS-MPS12SKHCS-MPS15SKHCS-MPS18SKHCS-MPS24SKHCS-MPS28SKH

DestinationBrunei

CambodiaIndonesiaMyanmarThailandVietnam

Please file and use this manual together with the service manual for Model No. CU-2S18SKH CU-3S27SBH CU-3S28SBH CU-4S27SBH CU-4S34SBH, Order No. PAPAMY1611007CE.

WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public. It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service or repair the products dealt with in this service information by anyone else could result in serious injury or death.

PRECAUTION OF LOW TEMPERATURE In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.

FAN SPEED

AIR SWING

MODE

T EM P

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1 2 3

OFFTIMER

ONTIMER

AUTO

COOL

DRY

FANSPEED

AIRSWING

SET CHECK CLOCK RESET

AC RC

T M P

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1 3

CHECK

IMPORTANT SAFETY NOTICEThere are special components used in this equipment which are important for safety. These parts are marked by in the SchematicDiagrams, Circuit Board Diagrams, Exploded Views and Replacement Parts List. It is essential that these critical parts should be replacedwith manufacturer’s specified parts to prevent shock, fire or other hazards. Do not modify the original design without permission ofmanufacturer.

!

Page 2: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

2

TABLE OF CONTENTS PAGE

1. Safety Precautions ............................................. 3 2. Specification ....................................................... 5 3. Location of Controls and Components .......... 22

3.1 Indoor Unit .................................................. 22 3.2 Outdoor Unit ............................................... 22 3.3 Remote Control .......................................... 22

4. Dimensions ....................................................... 23 4.1 Indoor Unit .................................................. 23

5. Refrigeration Cycle Diagram ........................... 25 6. Block Diagram .................................................. 26

6.1 CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH .......................................... 26

6.2 CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH .......................................... 26

7. Wiring Connection Diagram ............................ 27 7.1 Indoor Unit .................................................. 27

8. Electronic Circuit Diagram .............................. 29 8.1 Indoor Unit .................................................. 29

9. Printed Circuit Board ....................................... 31 9.1 Indoor Unit .................................................. 31

10. Installation Instruction ..................................... 33 10.1 Select the Best Location ............................. 33 10.2 Indoor Unit .................................................. 34

11. Operation Control ............................................. 38 11.1 Basic Function ............................................ 38 11.2 Indoor Fan Motor Operation ....................... 39 11.3 Airflow Direction .......................................... 39 11.4 Timer Control .............................................. 40 11.5 Random Auto Restart Control .................... 40 11.6 Indication Panel .......................................... 40

12. Servicing Mode ................................................. 41 12.1 Auto Off/On Button ..................................... 41 12.2 Remote Control Button ............................... 42

13. Troubleshooting Guide .................................... 43 13.1 Refrigeration Cycle System ........................ 43 13.2 Breakdown Self Diagnosis Function ........... 45 13.3 Error Code Table ........................................ 46 13.4 Troubleshooting Flowchart ......................... 48

14. Disassembly and Assembly Instructions ...... 74 14.1 CS-MPS9SKH CS-MPS12SKH

CS-MPS15SKH .......................................... 74 14.2 CS-MPS18SKH CS-MPS24SKH

CS-MPS28SKH .......................................... 78 15. Exploded View and Replacement Parts

List ..................................................................... 81 15.1 Indoor Unit .................................................. 81

Page 3: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

3

1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the

power plug and main circuit for the model installed. The caution items stated here must be followed because these important contents are related to safety. The

meaning of each indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.

WARNING This indication shows the possibility of causing death or serious injury.

CAUTION This indication shows the possibility of causing injury or damage to properties.

The items to be followed are classified by the symbols:

Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation,

care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.

WARNING

1. Do not modify the machine, part, material during repairing service.

2. If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.

3. Do not wrench the fasten terminal. Pull it out or insert it straightly.

4. Engage dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause water leakage, electrical shock or fire.

5. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.

6. Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock.

7. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.

8. For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.

9. This equipment is strongly recommended to install with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown. 10. Do not use joint cable for indoor / outdoor connection cable. Use the specified indoor / outdoor connection cable, refer to installation instruction

CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor / outdoor connection. Clamp the cable so that no external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.

11. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up or fire at the connection point of terminal, fire or electrical shock.

12. When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg.air etc. mix into refrigeration cycle (piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).

13. Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb up to outdoor unit and cross over the handrail and causing accident. 14. This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may cause electric shock in case equipment breakdown or insulation breakdown.

15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.

16. Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.

17. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may break and cause refrigerant gas leakage.

18. For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant. Using of existing (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury. Thickness or copper pipes used with R410A must be more than 0.6 mm. Never use copper pipes thinner than 0.6 mm. It is desirable that the amount of residual oil less than 40 mg/10 m. 19. During installation, before run the compressor, confirm the refrigerant pipes are fixed. Operation of compressor without fixing the piping, setting the valves at open condition, a burst may occur and cause injury.

This symbol denotes item that is PROHIBITED from doing.

Page 4: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

4

WARNING 20. During pump down operation, stop the compressor before remove the refrigerant piping. (Removal of refrigeration piping while compressor is

operating and valves are opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.)

21. After completion of installation or service, confirm there is no leakage or refrigerant gas. It may generate toxic gas when the refrigerant contacts with fire.

22. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts with fire.

23. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.

24. Must not use other parts except original parts describe in catalog and manual.

25. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.

CAUTION 1. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.

2. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

3. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may break and cause refrigerant gas leakage. 4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.

5. Select an installation location which is easy for maintenance.

6. Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C). Pb free solder will tend to splash when heated too high (about 1100°F / 600°C). 7. Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts. Take care of the liquid refrigerant, it may cause frostbite.

8. Installation or servicing work: It may need two people to carry out the installation or servicing work.

9. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

10. Do not sit or step on the unit, you may fall down accidentally.

11. Do not touch the sharp aluminum fins or edges of metal parts. If you are required to handle sharp parts during installation or servicing, please wear hand glove. Sharp parts may cause injury

Page 5: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

5

2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.10 2.80 3.50 1.10 3.20 4.00

BTU/h 3750 9550 11900 3750 10900 13600

kJ/h 3960 10080 12600 3960 11520 14400

Running Current A 3.65 3.40 4.50 4.20

Input Power W 220 750 1.00k 220 920 1.22k

EER W/W 5.00 3.73 3.50 5.00 3.48 3.28

kJ/hW 18.00 13.44 12.60 18.00 12.52 11.80

Indoor Noise (H / L / QLo) dB-A 40 / 29 / - 44 / 32 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG20K1

Motor Type AC / Induction (4 poles) AC / Induction (4 poles)

Input Power W 51 - 58 51 - 58

Output Power W 24 24

Speed

Lo rpm 680 720

Me rpm 840 890

Hi rpm 1000 1060

Moisture Removal L/h 1.6 1.8

Indoor Airflow

Lo m3/min (ft3/m) 6.90 (244) 6.95 (245)

Me m3/min (ft3/m) 8.26 (292) 8.92 (315)

Hi m3/min (ft3/m) 10.10 (355) 10.90 (385)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 870 (34-9/32)

Depth (I/D) mm (inch) 214 (8-7/16) 214 (8-7/16)

Weight Net (I/D) kg (lb) 9 (20) 9 (20)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 610 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 6: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

6

Model Indoor/Outdoor CS-MPS9SKH / CU-3S27SBH CS-MPS12SKH / CU-3S27SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.70 2.80 3.40 1.70 3.20 4.00

BTU/h 5800 9550 11600 5800 10900 13600

kJ/h 6120 10080 12240 6120 11520 14400

Running Current A 3.80 3.50 4.30 3.90

Input Power W 380 700 890 380 800 1.20k

EER W/W 4.47 4.00 3.82 4.47 4.00 3.33

kJ/hW 16.11 14.40 13.75 16.11 14.40 12.00

Indoor Noise (H / L / QLo) dB-A 40 / 29 / - 44 / 32 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG20K1

Motor Type AC / Induction (4 poles) AC / Induction (4 poles)

Input Power W 51 - 58 51 - 58

Output Power W 24 24

Speed

Lo rpm 680 720

Me rpm 840 890

Hi rpm 1000 1060

Moisture Removal L/h 1.6 1.8

Indoor Airflow

Lo m3/min (ft3/m) 6.90 (244) 6.95 (245)

Me m3/min (ft3/m) 8.26 (292) 8.92 (315)

Hi m3/min (ft3/m) 10.10 (355) 10.90 (385)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 870 (34-9/32)

Depth (I/D) mm (inch) 214 (8-7/16) 214 (8-7/16)

Weight Net (I/D) kg (lb) 9 (20) 9 (20)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 610 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 7: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

7

Model Indoor/Outdoor CS-MPS15SKH / CU-3S27SBH CS-MPS18SKH / CU-3S27SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.70 4.00 4.80 1.90 5.00 5.80

BTU/h 5800 13600 16400 6480 17100 19800

kJ/h 6120 14400 17280 6840 18000 20880

Running Current A 6.10 5.60 7.40 6.80

Input Power W 380 1.18k 1.48k 400 1.46k 1.89k

EER W/W 4.47 3.39 3.24 4.75 3.42 3.07

kJ/hW 16.11 12.20 11.68 17.10 12.33 11.05

Indoor Noise (H / L / QLo) dB-A 45 / 32 / - 47 / 38 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG30K1

Motor Type AC / Induction (4 poles) DC / Transistor (8 poles)

Input Power W 51 - 58 94.8

Output Power W 24 40

Speed

Lo rpm 720 930

Me rpm 900 1120

Hi rpm 1090 1300

Moisture Removal L/h 2.3 2.7

Indoor Airflow

Lo m3/min (ft3/m) 6.92 (244) 11.23 (397)

Me m3/min (ft3/m) 9.00 (318) 14.23 (503)

Hi m3/min (ft3/m) 11.20 (395) 17.08 (603)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 1070 (42-5/32)

Depth (I/D) mm (inch) 214 (8-7/16) 240 (9-15/32)

Weight Net (I/D) kg (lb) 9 (20) 12 (26)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 810 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 8: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

8

Model Indoor/Outdoor CS-MPS9SKH / CU-3S28SBH CS-MPS12SKH / CU-3S28SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.70 2.80 3.40 1.70 3.20 4.00

BTU/h 5800 9550 11600 5800 10900 13600

kJ/h 6120 10080 12240 6120 11520 14400

Running Current A 3.70 3.40 4.20 3.90

Input Power W 380 700 890 380 800 1.20k

EER W/W 4.47 4.00 3.82 4.47 4.00 3.33

kJ/hW 16.11 14.40 13.75 16.11 14.40 12.00

Indoor Noise (H / L / QLo) dB-A 40 / 29 / - 44 / 32 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG20K1

Motor Type AC / Induction (4 poles) AC / Induction (4 poles)

Input Power W 51 - 58 51 - 58

Output Power W 24 24

Speed

Lo rpm 680 720

Me rpm 840 890

Hi rpm 1000 1060

Moisture Removal L/h 1.6 1.8

Indoor Airflow

Lo m3/min (ft3/m) 6.90 (244) 6.95 (245)

Me m3/min (ft3/m) 8.26 (292) 8.92 (315)

Hi m3/min (ft3/m) 10.10 (355) 10.90 (385)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 870 (34-9/32)

Depth (I/D) mm (inch) 214 (8-7/16) 214 (8-7/16)

Weight Net (I/D) kg (lb) 9 (20) 9 (20)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 610 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 9: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

9

Model Indoor/Outdoor CS-MPS15SKH / CU-3S28SBH CS-MPS18SKH / CU-3S28SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.70 4.00 4.80 1.90 5.00 5.80

BTU/h 5800 13600 16400 6480 17100 19800

kJ/h 6120 14400 17280 6840 18000 20880

Running Current A 6.00 5.50 7.30 6.70

Input Power W 380 1.18k 1.48k 400 1.46k 1.89k

EER W/W 4.47 3.39 3.24 4.75 3.42 3.07

kJ/hW 16.11 12.20 11.68 17.10 12.33 11.05

Indoor Noise (H / L / QLo) dB-A 45 / 32 / - 47 / 38 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG30K1

Motor Type AC / Induction (4 poles) DC / Transistor (8 poles)

Input Power W 51 – 58 94.8

Output Power W 24 40

Speed

Lo rpm 720 930

Me rpm 900 1120

Hi rpm 1090 1300

Moisture Removal L/h 2.3 2.7

Indoor Airflow

Lo m3/min (ft3/m) 6.92 (244) 11.23 (397)

Me m3/min (ft3/m) 9.00 (318) 14.23 (503)

Hi m3/min (ft3/m) 11.20 (395) 17.08 (603)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 1070 (42-5/32)

Depth (I/D) mm (inch) 214 (8-7/16) 240 (9-15/32)

Weight Net (I/D) kg (lb) 9 (20) 12 (26)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 810 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 10: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

10

Model Indoor/Outdoor CS-MPS24SKH / CU-3S28SBH

Performance Test Condition JIS

Power Supply Phase, Hz Single, 50

V 220 240

Min. Mid. Max.

Coo

ling

Capacity

kW 1.90 6.00 6.20

BTU/h 6480 20500 21100

kJ/h 6840 21600 22320

Running Current A 9.30 8.60

Input Power W 400 1.92k 2.07k

EER W/W 4.75 3.13 3.00

kJ/hW 17.10 11.25 10.78

Indoor Noise (H / L / QLo) dB-A 48 / 39 / -

Indo

or F

an

Type Cross-flow fan

Material ASG30K1

Motor Type DC / Transistor (8 poles)

Input Power W 94.8

Output Power W 40

Speed

Lo rpm 1000

Me rpm 1200

Hi rpm 1400

Moisture Removal L/h 3.3

Indoor Airflow

Lo m3/min (ft3/m) 12.23 (432)

Me m3/min (ft3/m) 15.37 (543)

Hi m3/min (ft3/m) 18.50 (655)

Dimension

Height (I/D) mm (inch) 290 (11-7/16)

Width (I/D) mm (inch) 1070 (42-5/32)

Depth (I/D) mm (inch) 240 (9-15/32)

Weight Net (I/D) kg (lb) 12 (26)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2)

Drain Hose Inner Diameter mm 16.2

Length mm 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated)

Fin Type Slit Fin Row x Stage x

FPI 2 x 15 x 21

Size (W x H x L) mm 810 x 315 x 25.4

Air Filter Material Polypropelene

Type One-touch

Power Supply Outdoor

Power Supply Cord A -

Thermostat -

Protection Device -

DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23

Minimum °C 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 11: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

11

Model Indoor/Outdoor CS-MPS9SKH / CU-4S27SBH CS-MPS12SKH / CU-4S27SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.70 2.80 3.40 1.70 3.20 4.00

BTU/h 5800 9550 11600 5800 10900 13600

kJ/h 6120 10080 12240 6120 11520 14400

Running Current A 3.80 3.50 4.30 3.90

Input Power W 380 700 890 380 800 1.20k

EER W/W 4.47 4.00 3.82 4.47 4.00 3.33

kJ/hW 16.11 14.40 13.75 16.11 14.40 12.00

Indoor Noise (H / L / QLo) dB-A 40 / 29 / - 44 / 32 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG20K1

Motor Type AC / Induction (4 poles) AC / Induction (4 poles)

Input Power W 51 - 58 51 - 58

Output Power W 24 24

Speed

Lo rpm 680 720

Me rpm 840 890

Hi rpm 1000 1060

Moisture Removal L/h 1.6 1.8

Indoor Airflow

Lo m3/min (ft3/m) 6.90 (244) 6.95 (245)

Me m3/min (ft3/m) 8.26 (292) 8.92 (315)

Hi m3/min (ft3/m) 10.10 (355) 10.90 (385)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 870 (34-9/32)

Depth (I/D) mm (inch) 214 (8-7/16) 214 (8-7/16)

Weight Net (I/D) kg (lb) 9 (20) 9 (20)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 610 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 12: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

12

Model Indoor/Outdoor CS-MPS15SKH / CU-4S27SBH CS-MPS18SKH / CU-4S27SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.70 4.00 4.80 1.90 5.00 5.80

BTU/h 5800 13600 16400 6480 17100 19800

kJ/h 6120 14400 17280 6840 18000 20880

Running Current A 6.10 5.60 7.40 6.80

Input Power W 380 1.18k 1.48k 400 1.46k 1.89k

EER W/W 4.47 3.39 3.24 4.75 3.42 3.07

kJ/hW 16.11 12.20 11.68 17.10 12.33 11.05

Indoor Noise (H / L / QLo) dB-A 45 / 32 / - 47 / 38 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG30K1

Motor Type AC / Induction (4 poles) DC / Transistor (8 poles)

Input Power W 51 – 58 94.8

Output Power W 24 40

Speed

Lo rpm 720 930

Me rpm 900 1120

Hi rpm 1090 1300

Moisture Removal L/h 2.3 2.7

Indoor Airflow

Lo m3/min (ft3/m) 6.92 (244) 11.23 (397)

Me m3/min (ft3/m) 9.00 (318) 14.23 (503)

Hi m3/min (ft3/m) 11.20 (395) 17.08 (603)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 1070 (42-5/32)

Depth (I/D) mm (inch) 214 (8-7/16) 240 (9-15/32)

Weight Net (I/D) kg (lb) 9 (20) 12 (26)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 810 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 13: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

13

Model Indoor/Outdoor CS-MPS9SKH / CU-34S34SBH CS-MPS12SKH / CU-4S34SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.70 2.80 3.40 1.70 3.20 4.00

BTU/h 5800 9550 11600 5800 10900 13600

kJ/h 6120 10080 12240 6120 11520 14400

Running Current A 3.60 3.30 4.10 3.80

Input Power W 380 700 890 380 800 1.20k

EER W/W 4.47 4.00 3.82 4.47 4.00 3.33

kJ/hW 16.11 14.40 13.75 16.11 14.40 12.00

Indoor Noise (H / L / QLo) dB-A 40 / 29 / - 44 / 32 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG20K1

Motor Type AC / Induction (4 poles) AC / Induction (4 poles)

Input Power W 51 - 58 51 - 58

Output Power W 24 24

Speed

Lo rpm 680 720

Me rpm 840 890

Hi rpm 1000 1060

Moisture Removal L/h 1.6 1.8

Indoor Airflow

Lo m3/min (ft3/m) 6.90 (244) 6.95 (245)

Me m3/min (ft3/m) 8.26 (292) 8.92 (315)

Hi m3/min (ft3/m) 10.10 (355) 10.90 (385)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 870 (34-9/32)

Depth (I/D) mm (inch) 214 (8-7/16) 214 (8-7/16)

Weight Net (I/D) kg (lb) 9 (20) 9 (20)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 610 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 14: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

14

Model Indoor/Outdoor CS-MPS15SKH / CU-4S34SBH CS-MPS18SKH / CU-4S34SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.70 4.00 4.80 1.90 5.00 5.80

BTU/h 5800 13600 16400 6480 17100 19800

kJ/h 6120 14400 17280 6840 18000 20880

Running Current A 6.00 5.50 7.50 6.90

Input Power W 380 1.24k 1.48k 400 1.55k 1.89k

EER W/W 4.47 3.23 3.24 4.75 3.23 3.07

kJ/hW 16.11 11.61 11.68 17.10 11.61 11.05

Indoor Noise (H / L / QLo) dB-A 45 / 32 / - 47 / 38 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG20K1 ASG30K1

Motor Type AC / Induction (4 poles) DC / Transistor (8 poles)

Input Power W 51 - 58 94.8

Output Power W 24 40

Speed

Lo rpm 720 930

Me rpm 900 1120

Hi rpm 1090 1300

Moisture Removal L/h 2.3 2.7

Indoor Airflow

Lo m3/min (ft3/m) 6.92 (244) 11.23 (397)

Me m3/min (ft3/m) 9.00 (318) 14.23 (503)

Hi m3/min (ft3/m) 11.20 (395) 17.08 (603)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 870 (34-9/32) 1070 (42-5/32)

Depth (I/D) mm (inch) 214 (8-7/16) 240 (9-15/32)

Weight Net (I/D) kg (lb) 9 (20) 12 (26)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 17 2 x 15 x 17

Size (W x H x L) mm 610 x 315 x 25.4 810 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 15: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

15

Model Indoor/Outdoor CS-MPS24SKH / CU-4S34SBH CS-MPS28SKH / CU-4S34SBH

Performance Test Condition JIS JIS

Power Supply Phase, Hz Single, 50 Single, 50

V 220 240 220 240

Min. Mid. Max. Min. Mid. Max.

Coo

ling

Capacity

kW 1.90 6.00 6.20 2.00 7.00 7.20

BTU/h 6480 20500 21100 6820 23900 24600

kJ/h 6840 21600 22320 7200 25200 25920

Running Current A 9.60 8.80 11.80 10.80

Input Power W 400 2.03k 2.07k 400 2.49k 2.77k

EER W/W 4.75 2.96 3.00 5.00 2.81 2.60

kJ/hW 17.10 10.64 10.78 18.00 10.12 9.36

Indoor Noise (H / L / QLo) dB-A 48 / 39 / - 48 / 39 / -

Indo

or F

an

Type Cross-flow fan Cross-flow fan

Material ASG30K1 ASG30K1

Motor Type DC / Transistor (8 poles) DC / Transistor (8 poles)

Input Power W 94.8 94.8

Output Power W 40 40

Speed

Lo rpm 1000 1000

Me rpm 1200 1250

Hi rpm 1400 1500

Moisture Removal L/h 3.3 3.9

Indoor Airflow

Lo m3/min (ft3/m) 12.23 (432) 12.23 (432)

Me m3/min (ft3/m) 15.37 (543) 16.15 (570)

Hi m3/min (ft3/m) 18.50 (655) 20.07 (709)

Dimension

Height (I/D) mm (inch) 290 (11-7/16) 290 (11-7/16)

Width (I/D) mm (inch) 1070 (42-5/32) 1070 (42-5/32)

Depth (I/D) mm (inch) 240 (9-15/32) 240 (9-15/32)

Weight Net (I/D) kg (lb) 12 (26) 12 (26)

Piping Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2) 6.35 (1/4) / 12.70 (1/2)

Drain Hose Inner Diameter mm 16.2 16.2

Length mm 550 550

Indoor Heat Exchanger

Fin Material Aluminium (Pre coated) Aluminium (Pre coated)

Fin Type Slit Fin Slit Fin Row x Stage x

FPI 2 x 15 x 21 2 x 15 x 21

Size (W x H x L) mm 810 x 315 x 25.4 810 x 315 x 25.4

Air Filter Material Polypropelene Polypropelene

Type One-touch One-touch

Power Supply Outdoor Outdoor

Power Supply Cord A - -

Thermostat - -

Protection Device - -

DRY BULB WET BULB DRY BULB WET BULB

Indoor Operation Range Maximum °C 32 23 32 23

Minimum °C 16 11 16 11

1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and

outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) 2. Specifications are subject to change without notice for further improvement.

Page 16: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

16

Multi split combination possibility: - A single outdoor unit enables air conditioning of up to two separate rooms for CU-2S18SKH. - A single outdoor unit enables air conditioning of up to three separate rooms for CU-3S27SBH, CU-3S28SBH. - A single outdoor unit enables air conditioning of up to four separate rooms for CU-4S27SBH, CU-4S34SBH.

Outdoor Unit

CU-2S18SKH CU-3S27SBH CU-3S28SBH CU-4S27SBH CU-4S34SBH

A B A B C A B C A B C D A B C D

Wal

l

2.8 kW MPS9SKH

3.2 kW MPS12SKH

4.0 kW MPS15SKH - -

5.0 kW MPS18SKH - -

6.0 kW MPS24SKH - - - - - - - - -

7.0 kW MPS28SKH - - - - - - - - - - - - Capacity range of connectable indoor units

From 5.6 kW to 6.4 kW

From 5.6 kW to 13.2 kW

From 5.6 kW to 13.2 kW From 5.6 kW to 13.4 kW From 5.6 kW to 17.4 kW

Pipi

ng L

engt

h

1 room maximum pipe length (m) 20 25 25 25 25

Allowable elevation (m) 10 15 15 15 15 Total allowable pipe length (m) 30 60 60 60 70

Total pipe length for maximum chargeless length (m)

20 30 30 35 45

Additional gas amount over chargeless length (g/m)

15 20 20 20 20

Note: “” : Available

Indoor Unit: CS-MPS9/12SKH Outdoor Unit: CU-2S18SKH

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (kW) Current, 50Hz, 220V / 240V (A)

MOISTURE REMOVAL VOLUME

l/h Total min ~ max Rating min ~ max

2 Room

2.8 + 2.8 4.80 1.50 ~ 5.80 1.34 0.25 ~ 1.72 6.50 / 6.05 1.5 + 1.5

2.8 + 3.2 5.00 1.50 ~ 5.90 1.52 0.25 ~ 1.74 7.40 / 6.90 1.5 + 1.6

3.2 + 3.2 5.00 1.50 ~ 6.00 1.43 0.25 ~ 1.78 6.75 / 6.25 1.5 + 1.5

Indoor Unit: CS-MPS9/12/15/18SKH Outdoor Unit: CU-3S27SBH

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) Current, 50Hz, 220V / 240V

(A)

MOISTURE REMOVAL VOLUME l/h Total min ~ max Rating min ~ max

2 Room

2.8 + 2.8 5.60 1.7 ~ 6.4 1750 420~ 2600 8.7 / 8.0 1.6 + 1.6

2.8 + 3.2 6.00 1.7 ~ 6.5 2010 420 ~ 2600 10.0 / 9.2 1.6 + 1.8

2.8 + 4.0 6.80 2.5 ~ 7.3 2420 550 ~ 3330 12.0 / 11.0 1.6 + 2.3

2.8 + 5.0 7.50 2.7 ~ 7.7 2810 530 ~ 3310 13.9 / 12.7 1.6 + 2.6

3.2 + 3.2 6.40 2.3 ~ 7.1 2290 570 ~ 3350 11.3 / 10.4 1.8 + 1.8

3.2 + 4.0 7.20 2.5 ~ 7.4 2770 550 ~ 3330 13.7 / 12.5 1.8 + 2.3

3.2 + 5.0 7.50 2.8 ~ 7.7 2760 530 ~ 3310 13.6 / 12.5 1.7 + 2.5

4.0 + 4.0 7.50 2.7 ~ 7.6 2870 540 ~ 3310 14.2 / 13.0 2.2 + 2.2

4.0 + 5.0 7.50 2.8 ~ 7.8 2600 530 ~ 3300 12.8 / 11.8 1.9 + 2.4

5.0 + 5.0 7.50 2.9 ~ 8.0 2440 520 ~ 3300 12.1 / 11.1 2.2 + 2.2

Page 17: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

17

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) Current, 50Hz, 220V / 240V

(A)

MOISTURE REMOVAL VOLUME l/h

Total min ~ max Rating min ~ max

3 Room

2.8 + 2.8 + 2.8 7.50 2.4 ~ 7.6 2740 580 ~ 3170 13.5 / 12.4 1.5 + 1.5 + 1.5

2.8 + 2.8 + 3.2 7.50 2.4 ~ 7.7 2690 580 ~ 3170 13.3 / 12.2 1.5 + 1.5 + 1.6

2.8 + 2.8 + 4.0 7.50 2.6 ~ 8.0 2490 600 ~ 3260 12.3 / 11.3 1.4 + 1.4 + 1.8

2.8 + 2.8 + 5.0 7.50 2.8 ~ 8.0 2250 600 ~ 2910 11.1 / 10.2 1.3 + 1.3 + 2.0

2.8 + 3.2 + 3.2 7.50 2.4 ~ 7.7 2690 580 ~ 3180 13.3 / 12.2 1.5 + 1.6 + 1.6

2.8 + 3.2 + 4.0 7.50 2.6 ~ 8.0 2450 600 ~ 3200 12.1 / 11.1 1.4 + 1.5 + 1.7

2.8 + 3.2 + 5.0 7.50 2.8 ~ 8.0 2250 600 ~ 2910 11.1 / 10.2 1.2 + 1.4 + 2.0

2.8 + 4.0 + 4.0 7.50 2.7 ~ 8.0 2290 600 ~ 3020 11.3 / 10.4 1.3 + 1.6 + 1.6

2.8 + 4.0 + 5.0 7.50 2.8 ~ 8.0 2170 580 ~ 2760 10.7 / 9.8 1.1 + 1.6 + 1.8

2.8 + 5.0 + 5.0 7.50 2.8 ~ 8.0 2070 520 ~ 2650 10.2 / 9.4 1.0 + 1.7 + 1.7

3.2 + 3.2 + 3.2 7.50 2.4 ~ 7.7 2650 590 ~ 3190 13.1 / 12.0 1.5 + 1.5 + 1.5

3.2 + 3.2 + 4.0 7.50 2.6 ~ 8.0 2450 600 ~ 3210 12.1 / 11.1 1.5 + 1.5 + 1.7

3.2 + 3.2 + 5.0 7.50 2.8 ~ 8.0 2250 600 ~ 2920 11.1 / 10.2 1.4 + 1.4 + 1.9

3.2 + 4.0 + 4.0 7.50 2.8 ~ 8.0 2290 600 ~ 2960 11.3 / 10.4 1.4 + 1.6 + 1.6

3.2 + 4.0 + 5.0 7.50 2.8 ~ 8.0 2170 580 ~ 2760 10.7 / 9.8 1.3 + 1.5 + 1.7

3.2 + 5.0 + 5.0 7.50 2.8 ~ 8.0 2060 520 ~ 2650 10.2 / 9.4 1.2 + 1.7 + 1.7

4.0 + 4.0 + 4.0 7.50 2.8 ~ 8.0 2170 590 ~ 2820 10.7 / 9.8 1.5 + 1.5 + 1.5

4.0 + 4.0 + 5.0 7.50 2.8 ~ 8.0 2070 540 ~ 2650 10.2 / 9.4 1.5 + 1.5 + 1.7

Indoor Unit: CS-MPS9/12/15/18/24SKH Outdoor Unit: CU-3S28SBH

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) Current, 50Hz, 220V / 240V

(A)

MOISTURE REMOVAL VOLUME l/h Total min ~ max Rating min ~ max

1 Room

2.8 2.80 1.7 ~ 3.4 700 380 ~ 890 3.7 / 3.4 1.6

3.2 3.20 1.7 ~ 4.0 800 380 ~ 1200 4.2 / 3.9 1.8

4.0 4.00 1.7 ~ 4.8 1180 380 ~ 1480 6.0 / 5.5 2.3

5.0 5.00 1.9 ~ 5.8 1460 400 ~ 1890 7.3 / 6.7 2.7

6.0 6.00 1.9 ~ 6.2 1920 400 ~ 2070 9.3 / 8.6 3.3

2 Room

2.8 + 2.8 5.60 1.7 ~ 6.7 1750 420~ 2340 8.6 / 7.9 1.6 + 1.6

2.8 + 3.2 6.00 1.7 ~ 6.7 2010 420~ 2340 9.8 / 9.0 1.6 + 1.8

2.8 + 4.0 6.80 2.5 ~ 7.6 2420 550 ~ 2990 11.8 / 10.8 1.6 + 2.3

2.8 + 5.0 7.50 2.7 ~ 8.0 2810 530 ~ 2980 13.7 / 12.6 1.6 + 2.6

2.8 + 6.0 7.50 2.7 ~ 8.0 2810 530 ~ 2980 13.7 / 12.6 1.5 + 2.8

3.2 + 3.2 6.40 2.3 ~ 7.4 2290 570 ~ 3010 11.2 / 10.3 1.8 + 1.8

3.2 + 4.0 7.20 2.5 ~ 7.7 2770 550 ~ 2990 13.5 / 12.4 1.8 + 2.3

3.2 + 5.0 7.50 2.8 ~ 8.0 2760 530 ~ 2970 13.5 / 12.4 1.7 + 2.5

3.2 + 6.0 7.50 2.8 ~ 8.0 2760 530 ~ 2970 13.5 / 12.4 1.6 + 2.7

4.0 + 4.0 7.50 2.7 ~ 7.9 2870 540 ~ 2980 14.0 / 12.9 2.2 + 2.2

4.0 + 5.0 7.50 2.8 ~ 8.1 2600 530 ~ 2970 12.7 / 11.6 1.9 + 2.4

4.0 + 6.0 7.50 2.8 ~ 8.1 2600 530 ~ 2970 12.7 / 11.6 1.7 + 2.5

5.0 + 5.0 7.50 2.9 ~ 8.3 2440 520 ~ 2970 11.9 / 10.9 2.2 + 2.2

5.0 + 6.0 7.50 2.9 ~ 8.3 2440 520 ~ 2970 11.9 / 10.9 2.0 + 2.3

6.0 + 6.0 7.50 2.9 ~ 8.3 2440 520 ~ 2970 11.9 / 10.9 2.2 + 2.2

Page 18: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

18

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) Current, 50Hz, 220V / 240V

(A)

MOISTURE REMOVAL VOLUME l/h Total min ~ max Rating min ~ max

3 Room

2.8 + 2.8 + 2.8 7.50 2.4 ~ 7.9 2740 580 ~ 2840 13.4 / 12.3 1.5 + 1.5 + 1.5

2.8 + 2.8 + 3.2 7.50 2.4 ~ 8.0 2690 580 ~ 2850 13.1 / 12.1 1.5 + 1.5 + 1.6

2.8 + 2.8 + 4.0 7.50 2.6 ~ 8.4 2490 600 ~ 2930 12.2 / 11.2 1.4 + 1.4 + 1.8

2.8 + 2.8 + 5.0 7.50 2.8 ~ 8.8 2250 600 ~ 3010 11.0 / 10.1 1.3 + 1.3 + 2.0

2.8 + 2.8 + 6.0 7.50 2.8 ~ 8.8 2250 600 ~ 3010 11.0 / 10.1 1.2 + 1.2 + 2.3

2.8 + 3.2 + 3.2 7.50 2.4 ~ 8.0 2690 580 ~ 2860 13.1 / 12.1 1.5 + 1.6 + 1.6

2.8 + 3.2 + 4.0 7.50 2.6 ~ 8.4 2450 600 ~ 2930 12.0 / 11.0 1.4 + 1.5 + 1.7

2.8 + 3.2 + 5.0 7.50 2.8 ~ 8.8 2250 600 ~ 3020 11.0 / 10.1 1.2 + 1.4 + 2.0

2.8 + 3.2 + 6.0 7.50 2.8 ~ 8.8 2250 600 ~ 3020 11.0 / 10.1 1.1 + 1.3 + 2.2

2.8 + 4.0 + 4.0 7.50 2.7 ~ 8.7 2290 600 ~ 3000 11.2 / 10.3 1.3 + 1.6 + 1.6

2.8 + 4.0 + 5.0 7.50 2.8 ~ 9.0 2170 580 ~ 3050 10.6 / 9.7 1.1 + 1.6 + 1.8

2.8 + 4.0 + 6.0 7.50 2.8 ~ 9.0 2170 580 ~ 3050 10.6 / 9.7 1.0 + 1.5 + 2.0

2.8 + 5.0 + 5.0 7.50 2.8 ~ 9.0 2070 520 ~ 2830 10.1 / 9.3 1.0 + 1.7 + 1.7

3.2 + 3.2 + 3.2 7.50 2.4 ~ 8.0 2650 590 ~ 2860 13.0 / 11.9 1.5 + 1.5 + 1.5

3.2 + 3.2 + 4.0 7.50 2.6 ~ 8.4 2450 600 ~ 2940 12.0 / 11.0 1.5 + 1.5 + 1.7

3.2 + 3.2 + 5.0 7.50 2.8 ~ 8.8 2250 600 ~ 3020 11.0 / 10.1 1.4 + 1.4 + 1.9

3.2 + 3.2 + 6.0 7.50 2.8 ~ 8.8 2250 600 ~ 3020 11.0 / 10.1 1.3 + 1.3 + 2.1

3.2 + 4.0 + 4.0 7.50 2.8 ~ 8.7 2290 600 ~ 3000 11.2 / 10.3 1.4 + 1.6 + 1.6

3.2 + 4.0 + 5.0 7.50 2.8 ~ 9.0 2170 580 ~ 3060 10.6 / 9.7 1.3 + 1.5 + 1.7

3.2 + 4.0 + 6.0 7.50 2.8 ~ 9.0 2170 580 ~ 3060 10.6 / 9.7 1.2 + 1.5 + 2.0

3.2 + 5.0 + 5.0 7.50 2.8 ~ 9.0 2060 520 ~ 2830 10.1 / 9.2 1.2 + 1.7 + 1.7

4.0 + 4.0 + 4.0 7.50 2.8 ~ 9.0 2170 590 ~ 3040 10.6 / 9.7 1.5 + 1.5 + 1.5

4.0 + 4.0 + 5.0 7.50 2.8 ~ 9.0 2070 540 ~ 2830 10.1 / 9.3 1.5 + 1.5 + 1.7

Indoor Unit: CS-MPS9/12/15/18SKH Outdoor Unit: CU-4S27SBH

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) Current, 50Hz, 220V / 240V

(A)

MOISTURE REMOVAL VOLUMEl/h Total min ~ max Rating min ~ max

2 Room

2.8 + 2.8 5.60 1.7 ~ 6.4 1750 420 ~ 2600 8.7 / 8.0 1.6 + 1.6

2.8 + 3.2 6.00 1.7 ~ 6.5 2010 420 ~ 2600 10.0 / 9.2 1.6 + 1.8

2.8 + 4.0 6.80 2.5 ~ 7.3 2420 550 ~ 3330 12.0 / 11.0 1.6 + 2.3

2.8 + 5.0 7.50 2.7 ~ 7.7 2810 530 ~ 3310 13.9 / 12.7 1.6 + 2.6

3.2 + 3.2 6.40 2.3 ~ 7.1 2290 570 ~ 3350 11.3 / 10.4 1.8 + 1.8

3.2 + 4.0 7.20 2.5 ~ 7.4 2770 550 ~ 3330 13.7 / 12.5 1.8 + 2.3

3.2 + 5.0 7.50 2.8 ~ 7.7 2760 530 ~ 3310 13.6 / 12.5 1.7 + 2.5

4.0 + 4.0 7.50 2.7 ~ 7.6 2870 540 ~ 3310 14.2 / 13.0 2.2 + 2.2

4.0 + 5.0 7.50 2.8 ~ 7.8 2600 530 ~ 3300 12.8 / 11.8 1.9 + 2.4

5.0 + 5.0 7.50 2.9 ~ 8.0 2440 520 ~ 3300 12.1 / 11.1 2.2 + 2.2

3 Room

2.8 + 2.8 + 2.8 7.50 2.4 ~ 7.6 2740 580 ~ 3170 13.5 / 12.4 1.5 + 1.5 + 1.5

2.8 + 2.8 + 3.2 7.50 2.4 ~ 7.7 2690 580 ~ 3170 13.3 / 12.2 1.5 + 1.5 + 1.6

2.8 + 2.8 + 4.0 7.50 2.6 ~ 8.0 2490 600 ~ 3260 12.3 / 11.3 1.4 + 1.4 + 1.8

2.8 + 2.8 + 5.0 7.50 2.8 ~ 8.0 2250 600 ~ 2910 11.1 / 10.2 1.3 + 1.3 + 2.0

2.8 + 3.2 + 3.2 7.50 2.4 ~ 7.7 2690 580 ~ 3180 13.2 / 12.2 1.5 + 1.6 + 1.6

2.8 + 3.2 + 4.0 7.50 2.6 ~ 8.0 2450 600 ~ 3200 12.1 / 11.1 1.4 + 1.5 + 1.7

2.8 + 3.2 + 5.0 7.50 2.8 ~ 8.0 2250 600 ~ 2910 11.1 / 10.2 1.2 + 1.4 + 2.0

2.8 + 4.0 + 4.0 7.50 2.7 ~ 8.0 2290 600 ~ 3020 11.3 / 10.4 1.3 + 1.6 + 1.6

2.8 + 4.0 + 5.0 7.50 2.8 ~ 8.0 2170 580 ~ 2760 10.7 / 9.8 1.1 + 1.6 + 1.8

2.8 + 5.0 + 5.0 7.50 2.8 ~ 8.0 2070 520 ~ 2650 10.2 / 9.4 1.0 + 1.7 + 1.7

3.2 + 3.2 + 3.2 7.50 2.4 ~ 7.7 2650 590 ~ 3190 13.1 / 12.0 1.5 + 1.5 + 1.5

3.2 + 3.2 + 4.0 7.50 2.6 ~ 8.0 2450 600 ~ 3210 12.1 / 11.1 1.5 + 1.5 + 1.7

3.2 + 3.2 + 5.0 7.50 2.8 ~ 8.0 2250 600 ~ 2920 11.1 / 10.2 1.4 + 1.4 + 1.9

3.2 + 4.0 + 4.0 7.50 2.8 ~ 8.0 2290 600 ~ 2960 11.3 / 10.4 1.4 + 1.6 + 1.6

3.2 + 4.0 + 5.0 7.50 2.8 ~ 8.0 2170 580 ~ 2760 10.7 / 9.8 1.3 + 1.5 + 1.7

3.2 + 5.0 + 5.0 7.50 2.8 ~ 8.0 2060 520 ~ 2650 10.2 / 9.4 1.2 + 1.7 + 1.7

4.0 + 4.0 + 4.0 7.50 2.8 ~ 8.0 2170 590 ~ 2820 10.7 / 9.8 1.5 + 1.5 + 1.5

4.0 + 4.0 + 5.0 7.50 2.8 ~ 8.0 2070 540 ~ 2650 10.2 / 9.4 1.5 + 1.5 + 1.7

Page 19: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

19

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) Current, 50Hz, 220V / 240V

(A)

MOISTURE REMOVAL VOLUMEl/h Total min ~ max Rating min ~ max

4 Room

2.8 + 2.8 + 2.8 + 2.8 7.50 2.8 ~ 8.0 2060 520 ~ 2650 10.2 / 9.4 1.2 + 1.2 + 1.2 + 1.2

2.8 + 2.8 + 2.8 + 3.2 7.50 2.8 ~ 8.0 2060 520 ~ 2650 10.2 / 9.4 1.2 + 1.2 + 1.2 + 1.3

2.8 + 2.8 + 2.8 + 4.0 7.50 2.8 ~ 8.0 2060 520 ~ 2590 10.2 / 9.4 1.1 + 1.1 + 1.1 + 1.5

2.8 + 2.8 + 2.8 + 5.0 7.50 2.8 ~ 8.0 2060 520 ~ 2530 10.2 / 9.4 1.0 + 1.0 + 1.0 + 1.6

2.8 + 2.8 + 3.2 + 3.2 7.50 2.8 ~ 8.0 2060 520 ~ 2650 10.2 / 9.4 1.1 + 1.1 + 1.3 + 1.3

2.8 + 2.8 + 3.2 + 4.0 7.50 2.8 ~ 8.0 2060 520 ~ 2590 10.2 / 9.4 1.0 + 1.0 + 1.2 + 1.5

2.8 + 3.2 + 3.2 + 3.2 7.50 2.8 ~ 8.0 2060 520 ~ 2650 10.2 / 9.4 1.0 + 1.3 + 1.3 + 1.3

2.8 + 3.2 + 3.2 + 4.0 7.50 2.8 ~ 8.0 2060 520 ~ 2590 10.2 / 9.4 1.0 + 1.2 + 1.2 + 1.5

3.2 + 3.2 + 3.2 + 3.2 7.50 2.8 ~ 8.0 2060 520 ~ 2590 10.2 / 9.4 1.2 + 1.2 + 1.2 + 1.2

Indoor Unit: CS-MPS9/12/15/18/24/28SKH Outdoor Unit: CU-4S34SBH

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) EER ANNUAL

ENERGY CONSUMPTION

(kWh)

Current, 50Hz, 220V /

240V (A)

MOISTURE REMOVAL VOLUME

l/h Total min ~ max Rating min ~ max W/W CLASS

2 Room

2.8 + 2.8 5.60 2.4 ~ 5.8 1740 300 ~ 1860 3.22 A 870 8.5 / 7.8 1.6 + 1.6

2.8 + 3.2 6.00 2.4 ~ 6.7 1920 300 ~ 2360 3.13 B 960 9.3 / 8.5 1.6 + 1.8

2.8 + 4.0 6.80 2.4 ~ 7.2 2420 300 ~ 2760 2.81 C 1210 11.7 / 10.7 1.6 + 2.3

2.8 + 5.0 7.80 2.4 ~ 8.6 2680 280 ~ 3330 2.91 C 1340 12.9 / 11.8 1.6 + 2.7

2.8 + 6.0 8.80 2.5 ~ 9.1 3450 310 ~ 3640 2.55 E 1725 16.6 / 15.2 1.6 + 3.3

2.8 + 7.0 9.80 2.5 ~ 10.1 4140 310 ~ 4620 2.37 F 2070 20.0 / 18.3 1.6 + 4.0

3.2 + 3.2 6.40 2.4 ~ 7.2 2100 290 ~ 2620 3.05 B 1050 10.1 / 9.3 1.8 + 1.8

3.2 + 4.0 7.20 2.4 ~ 8.1 2620 290 ~ 3390 2.75 D 1310 12.6 / 11.6 1.8 + 2.3

3.2 + 5.0 8.20 2.5 ~ 9.1 2890 310 ~ 3490 2.84 C 1445 13.9 / 12.8 1.8 + 2.7

3.2 + 6.0 9.20 2.5 ~ 10.0 3570 310 ~ 4460 2.58 E 1785 17.2 / 15.8 1.8 + 3.3

3.2 + 7.0 10.00 2.5 ~ 10.4 4220 310 ~ 4800 2.37 F 2110 20.3 / 18.6 1.8 + 3.9

4.0 + 4.0 8.00 2.5 ~ 8.6 3240 320 ~ 3930 2.47 E 1620 15.6 / 14.3 2.3 + 2.3

4.0 + 5.0 9.00 2.5 ~ 10.0 3460 310 ~ 4460 2.60 D 1730 16.7 / 15.3 2.3 + 2.7

4.0 + 6.0 10.00 2.5 ~ 10.4 4460 310 ~ 4790 2.24 F 2230 21.5 / 19.7 2.3 + 3.3

4.0 + 7.0 10.00 2.5 ~ 10.4 4150 310 ~ 4800 2.41 E 2075 20.0 / 18.3 2.1 + 3.6

5.0 + 5.0 10.00 2.5 ~ 10.4 3610 300 ~ 4000 2.77 D 1805 17.4 / 16.0 2.7 + 2.7

5.0 + 6.0 10.00 2.5 ~ 10.4 3610 300 ~ 4000 2.77 D 1805 17.4 / 16.0 2.5 + 2.9

5.0 + 7.0 10.00 2.5 ~ 10.4 3470 300 ~ 3850 2.88 C 1735 16.7 / 15.3 2.4 + 3.2

6.0 + 6.0 10.00 2.5 ~ 10.4 3610 300 ~ 4000 2.77 D 1805 17.4 / 16.0 2.7 + 2.7

6.0 + 7.0 10.00 2.5 ~ 10.4 3470 300 ~ 3850 2.88 C 1735 16.7 / 15.3 2.5 + 2.9

7.0 + 7.0 10.00 2.5 ~ 10.4 3320 330 ~ 3690 3.01 B 1660 16.0 / 14.7 2.7 + 2.7

3 Room

2.8 + 2.8 + 2.8 8.40 2.9 ~ 8.7 2750 360 ~ 2880 3.05 B 1375 13.3 / 12.2 1.6 + 1.6 + 1.6

2.8 + 2.8 + 3.2 8.80 2.9 ~ 9.6 2880 390 ~ 3320 3.06 B 1440 13.9 / 12.7 1.6 + 1.6 + 1.8

2.8 + 2.8 + 4.0 9.60 2.9 ~ 10.1 3320 390 ~ 3770 2.89 C 1660 16.0 / 14.7 1.6 + 1.6 + 2.3

2.8 + 2.8 + 5.0 10.00 2.9 ~ 10.7 3180 390 ~ 3770 3.14 B 1590 15.3 / 14.1 1.6 + 1.6 + 2.5

2.8 + 2.8 + 6.0 10.00 2.9 ~ 10.7 3180 390 ~ 3770 3.14 B 1590 15.3 / 14.1 1.5 + 1.5 + 2.9

2.8 + 2.8 + 7.0 10.00 2.9 ~ 10.7 3110 390 ~ 3620 3.22 A 1555 15.0 / 13.7 1.4 + 1.4 + 3.0

2.8 + 3.2 + 3.2 9.20 2.9 ~ 10.1 2990 390 ~ 3690 3.08 B 1495 14.4 / 13.2 1.6 + 1.8 + 1.8

2.8 + 3.2 + 4.0 10.00 2.9 ~ 10.7 3540 390 ~ 4320 2.82 C 1770 17.1 / 15.6 1.6 + 1.8 + 2.3

2.8 + 3.2 + 5.0 10.00 2.9 ~ 10.7 3110 390 ~ 3700 3.22 A 1555 15.0 / 13.7 1.6 + 1.7 + 2.5

2.8 + 3.2 + 6.0 10.00 2.9 ~ 10.7 3110 390 ~ 3700 3.22 A 1555 15.0 / 13.7 1.5 + 1.6 + 2.7

2.8 + 3.2 + 7.0 10.00 2.9 ~ 10.7 3040 420 ~ 3540 3.29 A 1520 14.7 / 13.4 1.4 + 1.5 + 2.9

2.8 + 4.0 + 4.0 10.00 2.9 ~ 10.7 3540 390 ~ 4320 2.82 C 1770 17.1 / 15.6 1.6 + 2.2 + 2.2

2.8 + 4.0 + 5.0 10.00 2.9 ~ 10.7 3110 390 ~ 3620 3.22 A 1555 15.0 / 13.7 1.5 + 1.9 + 2.4

2.8 + 4.0 + 6.0 10.00 2.9 ~ 10.7 3110 390 ~ 3620 3.22 A 1555 15.0 / 13.7 1.4 + 1.8 + 2.5

2.8 + 4.0 + 7.0 10.00 2.9 ~ 10.7 2970 420 ~ 3540 3.37 A 1485 14.3 / 13.1 1.3 + 1.7 + 2.8

2.8 + 5.0 + 5.0 10.00 2.9 ~ 10.7 2830 430 ~ 3250 3.53 A 1415 13.6 / 12.5 1.4 + 2.3 + 2.3

2.8 + 5.0 + 6.0 10.00 2.9 ~ 10.7 2830 430 ~ 3250 3.53 A 1415 13.6 / 12.5 1.3 + 2.1 + 2.4

2.8 + 5.0 + 7.0 10.00 2.9 ~ 10.7 2760 460 ~ 3180 3.62 A 1380 13.3 / 12.2 1.2 + 1.9 + 2.6

2.8 + 6.0 + 6.0 10.00 2.9 ~ 10.7 2830 430 ~ 3250 3.53 A 1415 13.6 / 12.5 1.2 + 2.3 + 2.3

2.8 + 6.0 + 7.0 10.00 2.9 ~ 10.7 2760 460 ~ 3180 3.62 A 1380 13.3 / 12.2 1.1 + 2.2 + 2.5

2.8 + 7.0 + 7.0 10.00 2.9 ~ 10.7 2690 460 ~ 3110 3.72 A 1345 13.0 / 11.9 1.1 + 2.4 + 2.4

3.2 + 3.2 + 3.2 9.60 2.9 ~ 10.1 3110 390 ~ 3540 3.09 B 1555 15.0 / 13.7 1.8 + 1.8 + 1.8

3.2 + 3.2 + 4.0 10.00 2.9 ~ 10.7 3470 390 ~ 4160 2.88 C 1735 16.7 / 15.3 1.7 + 1.7 + 2.2

3.2 + 3.2 + 5.0 10.00 2.9 ~ 10.7 3040 390 ~ 3540 3.29 A 1520 14.7 / 13.4 1.6 + 1.6 + 2.4

Page 20: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

20

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) EER ANNUAL

ENERGY CONSUMPTION

(kWh)

Current, 50Hz, 220V /

240V (A)

MOISTURE REMOVAL VOLUME

l/h Total min ~ max Rating min ~ max W/W CLASS

3 Room

3.2 + 3.2 + 6.0 10.00 2.9 ~ 10.7 3040 390 ~ 3540 3.29 A 1520 14.7 / 13.4 1.6 + 1.6 + 2.6

3.2 + 3.2 + 7.0 10.00 2.9 ~ 10.7 2970 420 ~ 3470 3.37 A 1485 14.3 / 13.1 1.5 + 1.5 + 2.9

3.2 + 4.0 + 4.0 10.00 2.9 ~ 10.7 3390 390 ~ 4160 2.95 C 1695 16.3 / 15.0 1.7 + 2.1 + 2.1

3.2 + 4.0 + 5.0 10.00 2.9 ~ 10.7 3040 420 ~ 3540 3.29 A 1520 14.7 / 13.4 1.6 + 1.9 + 2.3

3.2 + 4.0 + 6.0 10.00 2.9 ~ 10.7 3040 420 ~ 3540 3.29 A 1520 14.7 / 13.4 1.5 + 1.7 + 2.5

3.2 + 4.0 + 7.0 10.00 2.9 ~ 10.7 2970 420 ~ 3470 3.37 A 1485 14.3 / 13.1 1.5 + 1.7 + 2.7

3.2 + 5.0 + 5.0 10.00 2.9 ~ 10.7 2760 460 ~3180 3.62 A 1380 13.3 / 12.2 1.5 + 2.2 + 2.2

3.2 + 5.0 + 6.0 10.00 2.9 ~ 10.7 2760 460 ~ 3180 3.62 A 1380 13.3 / 12.2 1.5 + 2.0 + 2.4

3.2 + 5.0 + 7.0 10.00 2.9 ~ 10.7 2690 460 ~ 3110 3.72 A 1345 13.0 / 11.9 1.4 + 1.9 + 2.5

3.2 + 6.0 + 6.0 10.00 2.9 ~ 10.7 2760 460 ~ 3180 3.62 A 1380 13.3 / 12.2 1.4 + 2.3 + 2.3

3.2 + 6.0 + 7.0 10.00 2.9 ~ 10.7 2690 460 ~ 3110 3.72 A 1345 13.0 / 11.9 1.3 + 2.2 + 2.4

3.2 + 7.0 + 7.0 10.00 2.9 ~ 10.7 2700 470 ~ 3110 3.70 A 1350 13.0 / 11.9 1.2 + 2.3 + 2.3

4.0 + 4.0 + 4.0 9.99 2.9 ~ 10.7 3390 390 ~ 4080 2.95 C 1695 16.3 / 15.0 1.9 + 1.9 + 1.9

4.0 + 4.0 + 5.0 10.00 2.9 ~ 10.7 2970 420 ~ 3540 3.37 A 1485 14.3 / 13.1 1.7 + 1.7 + 2.2

4.0 + 4.0 + 6.0 10.00 2.9 ~ 10.7 2970 420 ~ 3540 3.37 A 1485 14.3 / 13.1 1.7 + 1.7 + 2.4

4.0 + 4.0 + 7.0 10.00 2.9 ~ 10.7 2900 420 ~ 3400 3.45 A 1450 14.0 / 12.8 1.6 + 1.6 + 2.5

4.0 + 5.0 + 5.0 10.00 2.9 ~ 10.7 2760 460 ~ 3180 3.62 A 1380 13.3 / 12.2 1.7 + 2.1 + 2.1

4.0 + 5.0 + 6.0 10.00 2.9 ~ 10.7 2760 460 ~ 3180 3.62 A 1380 13.3 / 12.2 1.6 + 1.9 + 2.3

4.0 + 5.0 + 7.0 10.00 2.9 ~ 10.7 2690 460 ~ 3110 3.72 A 1345 13.0 / 11.9 1.5 + 1.8 + 2.4

4.0 + 6.0 + 6.0 10.00 2.9 ~ 10.7 2760 460 ~ 3180 3.62 A 1380 13.3 / 12.2 1.5 + 2.2 + 2.2

4.0 + 6.0 + 7.0 10.00 2.9 ~ 10.7 2690 460 ~ 3110 3.72 A 1345 13.0 / 11.9 1.5 + 2.0 + 2.3

5.0 + 5.0 + 5.0 9.99 2.9 ~ 10.7 2570 510 ~ 2970 3.89 A 1285 12.4 / 11.4 1.9 + 1.9 + 1.9

5.0 + 5.0 + 6.0 10.00 2.9 ~ 10.7 2630 510 ~ 2970 3.80 A 1315 12.7 / 11.6 1.8 + 1.8 + 2.2

5.0 + 5.0 + 7.0 10.00 2.9 ~ 10.7 2570 510 ~ 2970 3.89 A 1285 12.4 / 11.4 1.7 + 1.7 + 2.3

5.0 + 6.0 + 6.0 10.00 2.9 ~ 10.7 2630 510 ~ 2970 3.80 A 1315 12.7 / 11.6 1.7 + 2.0 + 2.0

4 Room

2.8 + 2.8 + 2.8 + 2.8 10.00 2.9 ~ 10.6 3220 420 ~ 3770 3.11 B 1610 15.5 / 14.2 1.5 + 1.5 + 1.5 + 1.5

2.8 + 2.8 + 2.8 + 3.2 10.00 2.9 ~ 10.6 3150 420 ~ 3680 3.17 B 1575 15.2 / 13.9 1.5 + 1.5 + 1.5 + 1.6

2.8 + 2.8 + 2.8 + 4.0 10.00 2.9 ~ 10.8 3150 430 ~ 3850 3.17 B 1575 15.2 / 13.9 1.5 + 1.5 + 1.5 + 1.8

2.8 + 2.8 + 2.8 + 5.0 10.00 2.9 ~ 10.8 2930 470 ~ 3520 3.41 A 1465 14.1 / 12.9 1.4 + 1.4 + 1.4 + 2.2

2.8 + 2.8 + 2.8 + 6.0 10.00 2.9 ~ 11.0 2930 470 ~ 3690 3.41 A 1465 14.1 / 12.9 1.3 + 1.3 + 1.3 + 2.4

2.8 + 2.8 + 2.8 + 7.0 10.00 2.9 ~ 11.0 2930 500 ~ 3610 3.41 A 1465 14.1 / 12.9 1.2 + 1.2 + 1.2 + 2.5

2.8 + 2.8 + 3.2 + 3.2 10.00 2.9 ~ 10.6 3070 430 ~ 3600 3.26 A 1535 14.8 / 13.6 1.5 + 1.5 + 1.6 + 1.6

2.8 + 2.8 + 3.2 + 4.0 10.00 2.9 ~ 10.8 3070 430 ~ 3770 3.26 A 1535 14.8 / 13.6 1.4 + 1.4 + 1.5 + 1.8

2.8 + 2.8 + 3.2 + 5.0 10.00 2.9 ~ 10.8 2930 500 ~ 3440 3.41 A 1465 14.1 / 12.9 1.3 + 1.3 + 1.5 + 2.1

2.8 + 2.8 + 3.2 + 6.0 10.00 2.9 ~ 11.0 2930 500 ~ 3610 3.41 A 1465 14.1 / 12.9 1.2 + 1.2 + 1.4 + 2.3

2.8 + 2.8 + 3.2 + 7.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.1 + 1.1 + 1.3 + 2.5

2.8 + 2.8 + 4.0 + 4.0 10.00 2.9 ~ 10.8 3070 430 ~ 3770 3.26 A 1535 14.8 / 13.6 1.3 + 1.3 + 1.7 + 1.7

2.8 + 2.8 + 4.0 + 5.0 10.00 2.9 ~ 11.0 2930 500 ~ 3610 3.41 A 1465 14.1 / 12.9 1.2 + 1.2 + 1.6 + 2.0

2.8 + 2.8 + 4.0 + 6.0 10.00 2.9 ~ 11.0 2930 500 ~ 3610 3.41 A 1465 14.1 / 12.9 1.2 + 1.2 + 1.6 + 2.3

2.8 + 2.8 + 4.0 + 7.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.1 + 1.1 + 1.5 + 2.4

2.8 + 2.8 + 5.0 + 5.0 10.00 2.9 ~ 11.0 2800 560 ~ 3460 3.57 A 1400 13.5 / 12.4 1.2 + 1.2 + 1.8 + 1.8

2.8 + 2.8 + 5.0 + 6.0 10.00 2.9 ~ 11.2 2800 560 ~ 3540 3.57 A 1400 13.5 / 12.4 1.1 + 1.1 + 1.7 + 2.1

2.8 + 3.2 + 3.2 + 3.2 10.00 2.9 ~ 10.8 3070 460 ~ 3680 3.26 A 1535 14.8 / 13.6 1.5 + 1.6 + 1.6 + 1.6

2.8 + 3.2 + 3.2 + 4.0 10.00 2.9 ~ 10.8 3070 460 ~ 3680 3.26 A 1535 14.8 / 13.6 1.4 + 1.5 + 1.5 + 1.7

2.8 + 3.2 + 3.2 + 5.0 10.00 2.9 ~ 11.0 2860 510 ~ 3610 3..50 A 1430 13.8 / 12.6 1.3 + 1.5 + 1.5 + 2.0

2.8 + 3.2 + 3.2 + 6.0 10.00 2.9 ~ 11.0 2860 510 ~ 3610 3.50 A 1430 13.8 / 12.6 1.2 + 1.4 + 1.4 + 2.3

2.8 + 3.2 + 3.2 + 7.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.1 + 1.3 + 1.3 + 2.4

2.8 + 3.2 + 4.0 + 4.0 10.00 2.9 ~ 10.8 3070 460 ~ 3680 3.26 A 1535 14..8 / 13.6 1.3 + 1.5 + 1.7 + 1.7

2.8 + 3.2 + 4.0 + 5.0 10.00 2.9 ~ 11.0 2860 510 ~ 2530 3.50 A 1430 13.8 / 12.6 1.2 + 1.4 + 1.6 + 1.9

2.8 + 3.2 + 4.0 + 6.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.1 + 1.3 + 1.5 + 2.2

2.8 + 3.2 + 4.0 + 7.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13..8 / 12.6 1.1 + 1.2 + 1.5 + 2.3

2.8 + 3.2 + 5.0 + 5.0 10.00 2.9 ~ 11.2 2800 560 ~ 3540 3.57 A 1400 13.5 / 12.4 1.1 + 1.3 + 1.8 + 1.8

2.8 + 3.2 + 5.0 + 6.0 10.00 2.9 ~ 11.2 2800 560 ~ 3540 3.57 A 1400 13.5 / 12.4 1.1 + 1.2 + 1.7 + 2.0

2.8 + 4.0 + 4.0 + 4.0 10.00 2.9 ~ 11.0 3000 460 ~ 3770 3.33 A 1500 14.5 / 13.3 1.2 + 1.6 + 1.6 + 1.6

2.8 + 4.0 + 4.0 + 5.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.1 + 1.6 + 1.6 + 1.8

2.8 + 4.0 + 4.0 + 6.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.1 + 1.5 + 1.5 + 2.1

2.8 + 4.0 + 5.0 + 5.0 10.00 2.9 ~ 11.2 2800 560 ~ 3540 3.57 A 1400 13.5 / 12.4 1.1 + 1.5 + 1.7 + 1.7

3.2 + 3.2 + 3.2 + 3.2 10.00 2.9 ~ 10.8 3000 460 ~ 3600 3.33 A 1500 14.5 / 13.3 1.5 + 1.5 + 1.5 + 1.5

3.2 + 3.2 + 3.2 + 4.0 10.00 2.9 ~ 10.8 3000 460 ~ 3600 3.33 A 1500 14.5 / 13.3 1.5 + 1.5 + 1.5 + 1.7

3.2 + 3.2 + 3.2 + 5.0 10.00 2.9 ~ 11.0 2860 510 ~ 3530 3.50 A 1430 13.8 / 12.6 1.4 + 1.4 + 1.4 + 2.0

Page 21: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

21

Indoor unit capacity Cooling

Cooling Capacity (kW) Input Power (W) EER ANNUAL

ENERGY CONSUMPTION

(kWh)

Current, 50Hz, 220V /

240V (A)

MOISTURE REMOVAL VOLUME

l/h Total min ~ max Rating min ~ max W/W CLASS

4 Room

3.2 + 3.2 + 3.2 + 6.0 10.00 2.9 ~ 11.0 2860 510 ~ 3530 3.50 A 1430 13.8 / 12.6 1.3 + 1.3 + 1.3 + 2.3

3.2 + 3.2 + 3.2 + 7.0 10.00 2.9 ~ 11.2 2860 520 ~ 3610 3.50 A 1430 13.8 / 12.6 1.2 + 1.2 + 1.2 + 2.4

3.2 + 3.2 + 4.0 + 4.0 10.00 2.9 ~ 11.0 3000 460 ~ 3770 3.33 A 1500 14.5 / 13.3 1.4 + 1.4 + 1.6 + 1.6

3.2 + 3.2 + 4.0 + 5.0 10.00 2.9 ~ 11.0 2860 510 ~ 3530 3.50 A 1430 13.8 / 12.6 1.3 + 1.3 + 1.6 + 1.8

3.2 + 3.2 + 4.0 + 6.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.3 + 1.3 + 1.5 + 2.1

3.2 + 3.2 + 4.0 + 7.0 10.00 2.9 ~ 11.2 2860 550 ~ 3610 3.50 A 1430 13.8 / 12.6 1.2 + 1.2 + 1.5 + 2.3

3.2 + 3.2 + 5.0 + 5.0 10.00 2.9 ~ 11.2 2800 600 ~ 3540 3.57 A 1400 13.5 / 12.4 1.3 + 1.3 + 1.7 + 1.7

3.2 + 3.2 + 5.0 + 6.0 10.00 2.9 ~ 11.2 2800 600 ~ 3540 3.57 A 1400 13.5 / 12.4 1.2 + 1.2 + 1.7 + 2.0

3.2 + 4.0 + 4.0 + 4.0 10.00 2.9 ~ 11.0 3000 460 ~ 3770 3.33 A 1500 14.5 / 13.3 1.4 + 1.6 + 1.6 + 1.6

3.2 + 4.0 + 4.0 + 5.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.3 + 1.5 + 1.5 + 1.7

3.2 + 4.0 + 4.0 + 6.0 10.00 2.9 ~ 11.2 2860 510 ~ 3690 3.50 A 1430 13.8 / 12.6 1.2 + 1.5 + 1.5 + 2.0

3.2 + 4.0 + 5.0 + 5.0 10.00 2.9 ~ 11.2 2810 600 ~ 3540 3.56 A 1405 13.5 / 12.4 1.2 + 1.5 + 1.7 + 1.7

4.0 + 4.0 + 4.0 + 4.0 10.00 2.9 ~ 11.2 3000 470 ~ 3850 3.33 A 1500 14.5 / 13.3 1.5 + 1.5 + 1.5 + 1.5

4.0 + 4.0 + 4.0 + 5.0 10.00 2.9 ~ 11.2 2860 520 ~ 3610 3.50 A 1430 13.8 / 12.6 1.5 + 1.5 + 1.5 + 1.7

Page 22: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

22

3. Location of Controls and Components 3.1 Indoor Unit

3.2 Outdoor Unit

3.3 Remote Control

POWER

TIMER

Horizontal airflow direction louver• Manually adjustable.

Remote control receiverMaximum distances: 8m

Vertical airflowdirection louver• Do not adjust by hand

Front Panel

Aluminium fin

Air filters

Auto OFF/ON button• Use when remote control is misplaced

or a malfunction occurs.

Anti-bacterial filter

POWER (Green)TIMER (Orange)

Indicator

Air inlet (rear)

Air inlet (side)

Air outlet

FAN SPEED

AIR SWING

MODE

TEMP

OFF/ON

TIMERSET

CANCEL

ON

OFF

1 2 3

OFFTIMER

ONTIMER

AUTOCOOL

DRY

FANSPEEDAIRSWING

SET CHECK CLOCK RESET

AC RC

TEMP

OFF/ON

TIMERSET

CANCEL

ON

OFF

1 3

CHECK

Remote control display

OFF/ON

Operation mode

Temperature settingFan speed selection

Air flow directionselection

Timer setting

Clock setting

Page 23: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

23

4. Dimensions

4.1 Indoor Unit

4.1.1 CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH

Unit: mm

FAN SPEED

A IR SW ING

M O D E

TEMP

O F F /O N

T IM E R

S E T

C A N C E L

O N

O F F

1 2 3

O FF

T IM ER

ON

T IM E R

A U TO

COO L

D RY

FA N

SP E ED

A IR

SW IN G

SET CHECK CLOCK RESET

AC RC

TEMP

O F F /O N

T IM E R

S E T

C A N C E L

O N

O F F

1 3

CHECK

(214

)29

0

61.1

45

214

1~21~2 870

115

(41~61)360

Liquid sideGas side

1256060

<Side View> <Side View>

<Top View>

<Front View>

<Bottom View>

<Rear View>

Air intakedirection

Air outletdirection

Left pipinghole

Right pipinghole

<Remote Control Holder>

51

61

497.2

128

14593

241.5 241.5128

Rightpipinghole

Leftpipinghole

Installationplate

Indoor unitexternaldimensionsline

432439

13.5

264.

2

2247

120

<Remote Control>

Relative position between the indoor unit and the installation plate <Front View>

Page 24: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

24

4.1.2 CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH

240

<Bottom View>

Unit : mm

FAN SPEED

A IR SW ING

M O D E

TEMP

O F F / O N

T IM E R

S E T

C A N C E L

O N

O F F

1 2 3

O F F

T IM ER

O N

T IM ER

A U TO

CO O L

D R Y

FA N

SP EE D

A IR

SW IN G

SET CHECK CLOCK RESET

AC RC

TEMP

O F F / O N

T IM E R

S E T

C A N C E L

O N

O F F

1 3

CHECK

240

<Top View>

<Side View> <Side View>

Air intakedirection

<Front View>

1~2

290

61.1

45

Right pipinghole

47 22

120

<Remote Control>

1~21070

Air outletdirection

Left pipinghole

11560

12560

<Remote Control Holder>

51

61

Liquid sideGas side

360 (41~61)

<Rear View>

Relative position between the indoor unit and the installation plate <Front View>

Rightpipinghole

13.5

264.

3

128241.5

532

Leftpipinghole

Installationplate

Indoor unitexternaldimensionsline

128241.5

748

539

219269

Page 25: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

25

5. Refrigeration Cycle Diagram

COOLING

INDOOR

INTAKETEMP.

SENSOR

PIPETEMP.

SENSOR

LIQUIDSIDE

2-WAYVALVE

3-WAYVALVE

GASSIDE

HEAT EXCHANGER(EVAPORATOR)

Page 26: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

26

6. Block Diagram 6.1 CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH

6.2 CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH

1

2

3

SSR

301

C330

THERMALFUSE

FUSE

CR

303

L301

C-FM

FAN MOTORFMSC

(INDOOR UNIT)

1

2

3

THERMALFUSE

FUSE

FM

(INDOOR UNIT)

SC

Page 27: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

27

7. Wiring Connection Diagram 7.1 Indoor Unit

7.1.1 CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH

Resistance of Indoor Fan Motor Windings

MODEL CS-MPS9SKH / CS-MPS12SKH / CS-MPS15SKH

CONNECTION CWA921447

BLUE-YELLOW 336 Ω

YELLOW-RED 306 Ω

Note: Resistance at 25°C of ambient temperature.

t

t

RECTIFICATIONCIRCUIT

COMMUNICATIONCIRCUIT

GROUNDINGTERMINAL

TO OUTDOORUNIT

1

W

23

BL

EVAPORATOR

AC303(WHT)

AC306(BLK)

AC304(RED)

G301(GRN)

FUSE301T3.15A L250V

NOISE FILTERCIRCUIT

TEMP.FUSE102°C (3A)

TOOUTDOORUNIT

TERMINALBOARD

R

Y/G

G

ELECTRONIC CONTROLLER(MAIN)

SUCTION TEMP. SENSOR (THERMISTOR)

PIPING TEMP. SENSOR 1 (THERMISTOR)

ELECTRONIC CONTROLLER (DISPLAY & RECEIVER)

CN–DISP(YLW)

FAN MOTORCIRCUIT

FAN MOTOR

M1~

CN–R

MT

(WHT

)CN

–STM

1(W

HT)

UP DOWNLOUVER MOTOR

1

4

HAJEM-A

(WHT

)

1

4

1 BRROYP 5

5

4

1M

1

1

35

1

1

5 1

63

CN–DISP(WHT)

CN–FB(WHT)

CN–PCFM(WHT)

CN–T

H(RED

)

W W WW W

R

BR

W

Y

B

O

REMOTE CONTROLLER

AUTO SW(SW01)

CN–CNT(WHT)

1 5

Page 28: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

28

7.1.2 CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH

t

t

RECTIFICATIONCIRCUIT

COMMUNICATIONCIRCUIT

GROUNDINGTERMINAL

TO OUTDOORUNIT

1

W

23

BL

EVAPORATOR

AC303(WHT)

AC306(BLK)

AC304(RED)

G301(GRN)

FUSE301T3.15A L250V

NOISE FILTERCIRCUIT

TEMP.FUSE102°C (3A)

TOOUTDOORUNIT

TERMINALBOARD

R

Y/G

G

ELECTRONIC CONTROLLER(MAIN)

SUCTION TEMP. SENSOR (THERMISTOR)

PIPING TEMP. SENSOR 1 (THERMISTOR)

ELECTRONIC CONTROLLER (DISPLAY & RECEIVER)

CN–DISP(YLW)FAN MOTOR

M

CN–R

MT

(WHT

)CN

–STM

1(W

HT)

UP DOWNLOUVER MOTOR

1

4

1 BRROYP 5

5

4

1M

65

4

7

1

1

5 1

61

CN–DISP(WHT)

CN–FM(WHT)

CN–T

H(RED

)W W WW W

BY

WBL

R

REMOTE CONTROLLER

AUTO SW(SW01)

HAJEM-A

(WHT

)

1

4

CN–CNT(WHT)

1 5

Page 29: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

29

8. Electronic Circuit Diagram 8.1 Indoor Unit

8.1.1 CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH

REMOTE CONTROLLER

0

10

-10 10 20 30 40 500

20

30

40

50

60

70

Temperature (°C)

Resis

tanc

e(K)

Sensor (Thermistor)Characteristics

Pipe temp. SensorIntake Air temp. Sensor

FAN SPEED

AIR SWING

MODE

TEMP

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1 2 3

OFFTIMER

ONTIMER

AUTO

COOL

DRY

FANSPEED

AIRSWING

SET CHECK CLOCK RESET

AC RC

TEMP

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1 3

CHECK

t

t

RECTIFICATIONCIRCUIT

COMMUNICATIONCIRCUIT

GROUNDINGTERMINAL

TO OUTDOORUNIT

1

W

23

BL

EVAPORATOR

AC303(WHT)

AC306(BLK)

AC304(RED)

G301(GRN)

FUSE301T3.15A L250V

NOISE FILTERCIRCUIT

TEMP.FUSE102°C (3A)

TOOUTDOORUNIT

TERMINALBOARD

R

Y/G

G

ELECTRONIC CONTROLLER(MAIN)

SUCTION TEMP. SENSOR (THERMISTOR)

PIPING TEMP. SENSOR 1 (THERMISTOR)

ELECTRONICCONTROLLER(DISPLAY &RECEIVER)

CN–DISP(YLW)

FAN MOTORCIRCUIT

FAN MOTOR

M1~

CN–RMT(WHT)

CN–STM1(WHT)

UP DOWNLOUVER MOTOR

1

4

HAJEM-A(WHT)

1

4

1 BRROYP 5

5

4

1M

1

1

35

1

1

5 1

6

3

CN–DISP(WHT)

CN–FB(WHT)

CN–PCFM(WHT)

CN–TH(RED)

W W WW W

R

BR

W

Y

B

O

CN–CNT(WHT)

1 5

R3310k

C100.01u

R3510k

C110.01u

5V

5V

5V

*R54

*C45*C49

*R3710k

*C47

*C48

12V

12V1

2

3

4

5

6

7

16IC03

15

14

13

12

11

10GND

VCC

8

9

R47 R46

R61 C27

5V

R62

R88

R87

C25C55

C54

5V12V5V

*C57

*L6*L5

*C56 C511000p

C521000p

R8210K

R9010k

SW01

R42

R43C4

5V

5V

C3

R39

*C14 *C15

5V

*R89*R40

5V

*R41

*C30*C33

LED202

R202LED201

R201

3

54

21

GND

GNDGND

VccVout

IC201

5V

R209

C202C201

GND-A

+

R855.1k

Page 30: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

30

8.1.2 CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH

t

t

RECTIFICATIONCIRCUIT

COMMUNICATIONCIRCUIT

GROUNDINGTERMINAL

TO OUTDOORUNIT

1

W

23

BL

EVAPORATOR

AC303(WHT)

AC306(BLK)

AC304(RED)

G301(GRN)

FUSE301T3.15A L250V

NOISE FILTERCIRCUIT

TEMP.FUSE102°C (3A)

TOOUTDOORUNIT

TERMINALBOARD

R

Y/G

G

ELECTRONIC CONTROLLER(MAIN)

SUCTION TEMP. SENSOR (THERMISTOR)

PIPING TEMP. SENSOR 1 (THERMISTOR)

CN–DISP(YLW)

FAN MOTOR

M

CN–RMT(WHT)

CN–STM1(WHT)

UP DOWNLOUVER MOTOR

1

4

1 BRROYP 5

5

4

1M

65

4

7

1

1 6

1 CN–FM(WHT)

CN–TH(RED)

W W WW W

BY

WBL

R

HAJEM-A(WHT)

1

4

CN–CNT(WHT)

1 5

ELECTRONICCONTROLLER(DISPLAY &RECEIVER)

5 1 CN–DISP(WHT)

LED202

R202LED201

R201

3

54

21

GND

GNDGND

VccVout

IC201

5V

R209

C202C201

GND-A

+

0

10

-10 10 20 30 40 500

20

30

40

50

60

70

Temperature (°C)

Resis

tanc

e(K)

Sensor (Thermistor)Characteristics

Pipe temp. SensorIntake Air temp. Sensor

FAN SPEED

AIR SWING

MODE

TEMP

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1 2 3

OFFTIMER

ONTIMER

AUTO

COOL

DRY

FANSPEED

AIRSWING

SET CHECK CLOCK RESET

AC RC

TEMP

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1 3

CHECK

R3310k

C100.01u

R3510k

C110.01u

5V

5V

5V

*R54

*C45*C49

*R3710k

*C47

*C48

R855.1k

12V

12V1

2

3

4

5

6

7

16IC03

15

14

13

12

11

10GND

VCC

8

9

R47 R46

R61 C27

5V

R62

R88

R87

C25C55

C54

REMOTE CONTROLLER

5V12V5V

*C57

*L6*L5

*C56 C511000p

C521000p

R8210K

R9010k

SW01

R42

R43C4

5V

5V

C3

R39

*C14 *C15

5V

R89*R40

Page 31: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

31

9. Printed Circuit Board 9.1 Indoor Unit

9.1.1 Main Printed Circuit Board

CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH 9.1.1.1

CN-PCFM

RY-PWR

AC303 (WHT)

SW01

CN-FBCN-RMTCN-CNT

CN-STM1

CN-DISP

CN-TH

HAJEM-A

JP1 (Random Auto Restart Enable/Disable)

Page 32: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

32

CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH 9.1.1.2

9.1.2 Indicator & Receiver Printed Circuit Board

SW01CN-FM

CN-RMT

CN-CNT

CN-STM1

CN-DISP

CN-TH

HAJEM-A

JP1 (Random Auto Restart Enable/Disable)

RY-PWR

AC303 (WHT)

CN-DISP

Page 33: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

33

10. Installation Instruction10.1 Select the Best Location

10.1.1 Indoor Unit Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. There should not be any heat source or steam near the unit. There should not be any obstacles blocking the air circulation. A place where air circulation in the room is good. A place where drainage can be easily done. A place where noise prevention is taken into consideration. Do not install the unit near the door way. Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. Recommended installation height for indoor unit shall be at least 2.5 m.

10.1.2 Indoor Unit Installation Diagram

dnebottonnoitnettAnoitceridgnipiPup drain hose(Front side)

RightRear

Right

Rightbottom

LeftRear Left bottom

Left

Vinyl tape

Remote control holder fixing screws 6

Remote control holder 5

Remotecontrol 3

• This illustration is for explanation purposes only.The indoor unit will actually face a different way.

• Respective outdoor unit installation procedure shallrefer to instruction manual provided in the outdoorunit packaging.

It is advisable to avoid more than 2 blockagedirections. For better ventilation & multiple-outdoor installation, please consult authorizeddealer/specialist.

• Carry out insulation afterchecking for gas leaks andsecure with vinyl tape.

Attaching the remote control holder to the wall

Insulation of piping connections

50 mmor more

50mm

ormore

(Left and right are identical)

Installation plate 1

Sleeve ( )

Bushing-Sleeve ( )

Bend the pipe asclosely on the wall aspossible, but be carefulthat it doesn’t break.

Saddle ( )

Putty ( )(GumType Sealer)

Vinyl tape (wide) ( )• Apply after carryingout a drainage test.

• To carry out thedrainage test,remove the air filtersand pour water intothe heat exchanger.

Installation parts youshould purchase ()

Page 34: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

34

10.2 Indoor Unit

10.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent it from the vibration.

The center of installation plate should be at more than 1 at right and left of the wall. The distance from installation plate edge to ceiling should more than 2. From installation plate center to unit’s left side is 3. From installation plate center to unit’s right is 4. B : For left side piping, piping connection for liquid should be about 5 from this line. : For left side piping, piping connection for gas should be about 6 from this line.

1 Mount the installation plate on the wall with 5 screws or more (at least 5 screws). (If mounting the unit on the concrete wall, consider using anchor bolts.) o Always mount the installation plate horizontally by aligning the marking-off line with the thread and using

a level gauge. 2 Drill the piping plate hole with ø70 mm hole-core drill.

o Line according to the left and right side of the installation plate. The meeting point of the extended line is the center of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The hole center is obtained by measuring the distance namely 128 mm for left and right hole respectively.

o Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side.

10.2.2 To Drill a Hole in the Wall and Install a Sleeve of Piping

1 Insert the piping sleeve to the hole. 2 Fix the bushing to the sleeve. 3 Cut the sleeve until it extrudes about 15 mm

from the wall.

CAUTION

When the wall is hollow, please be sure to use the sleeve for tube assembly to prevent dangers caused by mice biting the connection cable.

4 Finish by sealing the sleeve with putty or

caulking compound at the final stage.

WallWall Wall

Installationplate 1

2 screw

More than 1 More than 1

MeasuringTape

Indoor unit

241.5 mm

128mm

128mm

241.5 mm

128mm

Morethan 2

ModelDimension

1 2 3 4 5 6

MPS9***, MPS12***,MPS15*** 490 mm 82 mm 439 mm 432 mm 93 mm 145 mm

MPS18***, MPS24***,MPS28***

590 mm 82 mm 539 mm 532 mm 219 mm 269 mm

15 mm

ø70 mm through hole

Approx. 5 - 7 mm

Putty or caulking compound

Sleevefor tubeassembly

Bushing for tubeassembly

Wall

Indoor Outdoor

Page 35: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

35

10.2.3 Indoor Unit Installation

For the Right Rear Piping 10.2.3.1

For the Right and Right Bottom 10.2.3.2Piping

For the Embedded Piping 10.2.3.3

(This can be used for left rear piping and bottom piping also.)

Do not turn over the unit without it’s shock absorber during pull out the piping.It may cause intake grille damage.Use shock absorber during pull out the piping to protect the intake grille from damage.

PUSHPUSHPUSHPUSH

PipingPiping

Shock absorberIntake grille

pull out the piping

pull out the piping

Install the Indoor Unit

Pull out the Indoor piping

Step-2

Secure the Indoor Unit

Insert the connection cable

Step-1

Step-3

Step-4

Install the Indoor Unit

Pull out the Indoor piping

Step-2

Step-1

Insert the connection cableStep-3

Secure the Indoor UnitStep-4

• Use a spring bender or equivalent to bend the piping so that the piping is notcrushed.

• When determining the dimensions of the piping, slide the unit all the way to the lefton the installation plate.

• Refer to the section “Cutting and flaring the piping”.

Bend the embedded piping

Cut and flare the embedded piping

Replace the drain hose

Pull the connection cable into Indoor Unit

• The inside and outside connection cable can be connected without removing thefront grille.

• Please refer to “Connecting the piping” column in outdoor unit section.(Below steps are done after connecting the outdoor piping and gas-leakageconfirmation.)

Connect the piping

• Please refer to “Insulation of piping connection” column as mentioned inindoor/outdoor unit installation.

Install the Indoor Unit

Secure the Indoor Unit

Insulate and finish the piping

Step-1

Step-2

Step-3

Step-4

Step-5

Step-6

Step-7

Step-8

Insert the connection cable

Secure the Indoor Unit

1. Press the lower left and right side of the unit againstthe installation plate until hooks engageswith their slot(sound click).

In case of the cover is cut, keep the cover at therear of chassis as shown in the illustration for futurereinstallation.(Left, right and 2 bottom covers for piping.)

How to keep the cover

Install the indoor unit

Hook the indoor unit onto the upper portion ofinstallation plate. (Engage the indoor unitwith the upper edge of the installation plate).Ensure thehooksareproperly seated on theinstallation plate by moving it in left and right.

Right Rear piping

To take out the unit, pushthe marking at thebottom unit, and pull it slightlytowards you to disengage thehooks from the unit.

Right and Right Bottom piping

Guidesurface Connection cable

About70 – 80 mm

Connection cableGas sidepiping

Liquid sidepiping

Drain hose

Cover for thebottom piping

Cover for thebottom piping

Tape it with pipingin a position asmentioned in Fig.

below.

Cover forthe rightpiping

Piping

Drainhose

Cover forthe leftpiping

Cover for piping

Cover forthe bottompiping

Tape it with pipingin a position asmentioned in Fig.

below.

Cover forthe rightpiping

Piping

Drain hose

Cover forthe leftpiping

Drain hose

Sleeve forpiping hole

Indoor unit

Hooks atinstallationplate

Piping

Installationplate

Unit’shook

marking

Page 36: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

36

10.2.4 Connect the Cable to the Indoor Unit 1 The inside and outside connection cable can

be connected without removing the front grille. 2 Connection cable between indoor unit and

outdoor unit shall be approved polychloroprene sheathed 4 x 1.5 mm2 flexible cord, type designation 60245 IEC 57 or heavier cord. Do not use joint connection cable. Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short.

Note: Secure the connection cable onto the control board with the holder. Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively. Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.

Rear view for left piping installation

Drain cap Drain hose

Adjust the pipingslightly downwards.

Drain hose

Connection cable

PVC tubefor drainhose

Indoor unit

72 mm

Piping

Cable

Apply putty orcaulking materialto seal the wallopening.

Connectioncable

Piping

More than

470 mm

More t

han

1150 m

m

PVC tube (VP-65) for pipingand connection cable

PVC tube for drain hose (VP-30)PVC tube fordrain hose (VP-20)

Morethan

700mm

• In case of left piping how to insert theconnection cable and drain hose.

Drain hosefrom main unit

(For the right piping, follow the sameprocedure)

• How to pull the piping and drain hose out, in case of theembedded piping.

Replace the drain hose

Sleeve for piping hole

Drain hose

Piping

Connectioncable

More than1150 mm

Cable

45°

Drainhose

Piping

Terminals on the indoor unit

Colour of wires

Terminals on the outdoor unit

1 2 3

1 2 3

WARNING

This equipment must be properly earthed.

• Secure the connection cable onto the control boardwith the holder.

1 2 3

Indoor andoutdoorConnectioncable

Holder

Earth Wirelonger thanothersAC wiresfor safetyreason

TerminalBoard

Page 37: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

37

10.2.5 Wire Stripping and Connecting Requirement

10.2.6 Cutting and Flaring the Piping 1 Please cut using pipe cutter and then remove the burrs. 2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.

Turn the piping end down to avoid the metal powder entering the pipe. 3 Please make flare after inserting the flare nut onto the copper pipes.

10.2.7 Pump down method when reuse existing piping (R22 model) for R410A model Compressor oil of R22 model is insoluble in compressor oil of R410A model. The mixing of compressor oil may cause damage of compressor. Possibility of Mixing To Reuse Old Piping Reuse of piping of R22 model is dangerous because of its

compressor oil. Reuse the piping of R22 model only when it is unavoidable, eg.

concealed piping. When reuse piping of R22 model, pump down must be carried out

properly to ensure compressor oil which is remained inside piping is collected away.

Piping of R22 model can be reused only when air conditioner is properly pumped down.

The purpose of pump down is to collect back the compressor oil (which is mixed with refrigerant and circulating inside refrigeration cycle) properly into the outdoor unit of air conditioner.

10.2.8 Proper pump down method

1 Operate air conditioner at cooling mode for 10~15 minutes.

2 After 10~15 minutes of pre operation, close 2 way valve. After 3 minutes, close 3 way valve.

3 Take out air conditioner unit.

4 Install New Refrigerant air conditioner.

In case pump down cannot be done, please flush the piping using R410A refrigerant.

WARNING

RISK OF FIREJOINING OFWIRESMAY CAUSEOVERHEATINGAND FIRE.

OR

OROR

Wire stripping

No loose strandwhen inserted

10±1mm

5 mmor more

Indoor/outdoorconnectionterminal board

(gap between wires)

Conductorfully inserted

Conductorover inserted

Conductor notfully inserted

ACCEPT PROHIBITED PROHIBITED

Use complete wire without joining.

Use approved socket and plug with earth pin.

Wire connection in this area must follow tonational wiring rules.

Do not joint wires

1. To cut

When properly flared, the internal surface of theflare will evenly shine and be of even thickness.Since the flare part comes into contact with theconnections, carefully check the flare finish.

Inclined Surfacedamaged

Cracked Uneventhickness

3. To flare

Bar

Handle

CoreYoke

Clamp handle

Bar 0 – 0.5 mm

Copperpipe

Reamer

2. To remove burrs

Point down

Pipe

Red arrow mark

Improper flaring

Most Important ProcessPurpose: To make the oil& refrigerant mix together.They are in separatedcondition whenair conditioneris stopped.

Mixed refrigerant & oilwill be collected intooutdoor unit.

Only very smallamount of oil remaininside piping, which isacceptable.

Page 38: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

38

11. Operation Control 11.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operation mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air temperature.

11.1.1 Internal Setting Temperature Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting processes. These shifting processes are depending on the air conditioner settings and the operation environment. The final shifted value will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit.

11.1.2 Cooling Operation

Thermostat control 11.1.2.1 Compressor is OFF when intake Air Temperature - Internal Setting Temperature < -0.5°C. Compressor is ON after waiting for 3 minutes, if the Intake Temperature - Internal Setting Temperature >

Compressor OFF point.

11.1.3 Soft Dry Operation

Thermostat control 11.1.3.1 Compressor is OFF when Intake Temperature - Internal Setting Temperature < -1.0°C. Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >

Compressor OFF point.

Automatic Operation 11.1.3.2 This mode can be set using remote control and the operation is decided by indoor intake air temperature. During operation mode judgment at the beginning of the Auto Mode operation, indoor fan motor (with speed of

Lo-) is running for 30 seconds to detect the indoor intake air temperature. The operation mode is decided based on below chart. After the operation mode is decided, the unit operation will follow the respective operation mode control.

Remote Control Setting Temperature 16°C ~ 30°C

Indoor Air Temperature Shifting

Outdoor Air Temperature Shifting

Setting Temperature Limit Checking (Min: 16°C; Max: 33°C)

Internal Setting Temperature

Cooling operation Soft Dry

operation

Indoor intake Air Temp

23°C

Page 39: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

39

11.2 Indoor Fan Motor Operation

11.2.1 Basic Rotation Speed Manual Fan Speed

o Fan motor’s number of rotation is determined according to remote control setting.

Remote control

Tab Hi Me+ Me Me- Lo Auto Fan Speed

o According to room temperature and setting temperature, indoor fan speed is determined automatically. o The indoor fan will operate according to pattern below.

Fan Speed a b c d e f g h a b

Higher

Medium Lower

[1 pattern : 10s] Feedback control

o Immediately after the fan motor is started, feedback control is performed once every second. o During fan motor on, if fan motor feedback ≥ 2550 rpm or <50 rpm continuously for 10 seconds, the fan

motor error counter increased; fan motor is then stopped and restarted. If the fan motor error counter increased to 7, then H19 – fan motor error is detected. Operation stopped and could not be restarted.

11.3 Airflow Direction There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by

vertical vanes). Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat

exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).

11.3.1 Vertical Airflow

Operation Mode

Airflow Direction

Vane Angle (°) 1 2 3 4 5

Cooling Auto 10 ~ 40

Manual 10 17.5 25 32.5 40

Soft Dry Auto 10 ~ 40

Manual 10 17.5 25 32.5 40

MPS9/12/15SK

Operation

Mode Airflow

Direction Vane Angle (°)

1 2 3 4 5

Cooling Auto 5 ~ 35

Manual 5 12.5 20 27.5 35

Soft Dry Auto 5 ~ 35

Manual 5 12.5 20 27.5 35

MPS18/24SK/28SK

Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated above. When the air conditioner is stopped using remote control, the vane will shift to close position.

Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions of the vane are as figure below. When the air conditioner is stopped using remote control, the vane will shift to close position.

Close position

MPS9/12/15SK

Side View

135°

45 5

3

2

1

Close position

MPS18/24/28SK

Side View

140°

4

3

2

1

Page 40: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

40

11.3.2 Horizontal Airflow The horizontal airflow direction louvers can be adjusted manually by hand.

11.4 Timer Control

11.4.1 ON Timer Control ON timer can be set using remote control, where the unit with timer set will start operation earlier than the setting time. This is to provide a comfortable environment when reaching the set ON time. 60 minutes before the set ON time, indoor (at fan speed of Lo-) and outdoor fan motor start operation for 30 seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting time. From the above judgment, the decided operation will start operation earlier than the set time as shown below.

11.4.2 OFF Timer Control OFF timer can be set using remote control, where the unit with timer set will stop at set OFF time. Notes:

1 By pressing ON/OFF operation button, the ON Timer or OFF Timer setting will not be cancelled. 2 To cancel the previous timer setting, press CANCEL button. 3 To activate the previous timer setting, press SET button. 4 If main power supply is switched off, the Timer setting will be cancelled.

11.5 Random Auto Restart Control When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within

three to four minutes. There are 10 patterns to be selected randomly after power supply resumes. This control is not applicable during OFF/ON Timer setting. This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.

11.6 Indication Panel LED POWER TIMER

Color Green Orange Light ON Operation ON Timer Setting ON Light OFF Operation OFF Timer Setting OFF

Note: If POWER LED blinks, the possible operation of the unit is operation mode judgment, or ON timer sampling. If TIMER LED blinks, there is an abnormal operation occurs.

15 min

10 min

5 min

Indoor intake air temperature (°C)

30

25

30 35Outdoor air temperature (°C)

Cooling / Soft Dry

Page 41: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

41

12. Servicing Mode 12.1 Auto Off/On Button

Auto OFF/ON Button Pressed Auto OFF/ON

Button Pressed

5 sec

Auto Operation Test Run Operation (Forced Cooling Operation)

Stop

1 AUTO OPERATION MODE The Auto Operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be used to operate air conditioner with limited function if remote control is misplaced or malfunction.

2 TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)

The Test Run Operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds. A “beep” sound will be heard at the fifth seconds, in order to identify the starting of this operation. The Auto OFF/ON button may be used together with remote control to set / change the advance setting of air conditioner operation.

3 REMOTE CONTROL NUMBER SWITCH MODE The Remote Control Number Switch Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 11 seconds (3 “beep” sounds will occur at 11th seconds to identify the Remote Control Number Switch Mode is in standby condition), press “AC Reset” button and then press any button at remote control to transmit and store the desired transmission code to the EEPROM. There are 4 types of remote control transmission code could be selected. The indoor unit will only operate when received signal with same transmission code from remote control. This could prevent signal interference when there are 2 or more units installed nearby together. To change remote control transmission code, short or open jumpers at the remote control printed circuit board.

Remote Control Printed Circuit Board Jumper A (J-A) Jumper B (J-B) Remote Control No.

Short Open A (Default) Open Open B Short Short C Open Short D

4 REMOTE CONTROL RECEIVING SOUND OFF/ON MODE

The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound OFF/ON Mode is in standby condition) and press “AC Reset” button and then press “Check” button at remote control. Press Auto OFF/ON button to toggle remote control receiving sound. - Short “beep”: Turn ON remote control receiving sound. - Long “beep”: Turn OFF remote control receiving sound. After Auto OFF/ON button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON Mode is restarted.

J - BJ - A

Auto Operation Test Run Operation (Forced Cooling Operation)

Remote Control Number Switch Mode

Remote Control Receiving Sound OFF/ON

Beep Beep x 2 Beep x 3 Beep x 4

5 sec 8 sec 11 sec 16 sec

Main unit always continue Test Run (forced cooling) operation.

Press “AC Reset”, then any key at remote control

Press “AC Reset”, then “Check” at remote control

Page 42: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

42

12.2 Remote Control Button

12.2.1 SET Button To check remote control transmission code and store the transmission code to EEPROM

o Press “Set” button for more than 10 seconds by using pointer. o Press “Timer Set” button unit a “beep” sound is heard as confirmation of transmission code change.

12.2.2 RESET (RC) Button To clear and restore the remote control setting to factory default.

o Press once to clear the memory.

12.2.3 TIMER To change indoor unit indicators’ intensity:

o Press continuously for 5 seconds.

12.2.4 TIMER To change remote control display from Degree Celsius (°C) to Degree Fahrenheit (°F)

o Press continuously for 10 seconds.

Page 43: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

43

13. Troubleshooting Guide

13.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right.

Normal Pressure and Outlet Air Temperature (Standard)

Gas Pressure

MPa (kg/cm2G)

Outlet air Temperature

(°C)

Cooling Mode 0.9 ~ 1.2 (9 ~ 12) 12 ~ 16

Condition: Indoor fan speed = High Outdoor temperature = 35°C at cooling mode.Compressor operate at rated frequency

Different in the intake and outlet

air temperatures Normal

Value of electric current during operation

Dusty condenser preventing heat radiation

Excessive amount of refrigerant

Gas side pressure

Inefficient compressor

Insufficient refrigerant

Clogged strainer or capillary cube

Measuring the air temperature different

Measuring electric current during operation

Measuring gas side pressure

More than 8°C (15 minutes after an

operation is started) at cooling mode.

Less than 8°C at the cooling mode

Higher than specified

Cooling Mode High

Low

Low

Lower than specified

Page 44: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

44

13.1.1 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current

Condition of the air conditioner

Cooling Mode Low Pressure High Pressure Electric current during operation

Insufficient refrigerant (gas leakage)

Clogged capillary tube or strainer

Short circuit in the indoor unit

Heat radiation deficiency of the outdoor unit

Inefficient compression

• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.

Page 45: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

45

13.2 Breakdown Self Diagnosis Function

13.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code) Once error occurred during operation, the unit will stop its operation, and Timer LED blinks. Although Timer LED goes off when power supply is turned off, if the unit is operated under a breakdown

condition, the LED will ON again. In operation after breakdown repair, the Timer LED will not blink. The last error code (abnormality) will be stored

in IC memory.

13.2.2 To Make a Diagnosis 1 Timer LED starts to blink and the unit automatically stops the operation. 2 Press the CHECK button on the remote control continuously for 5 seconds. 3 “- -“ will be displayed on the remote control display.

Note: Display only for “- -“ (No signal transmission, no receiving sound and no Power LED blinking)

4 Press the TIMER or button on the remote control. The code “H00” (no abnormality) will be displayed and signal will be transmit to the main unit.

5 Each press of the button ( or ) will increase error code number and transmit error code signal to the main unit.

6 When the latest abnormality code on the main unit and code transmitted from the remote control are matched, Power LED will light up for 30 seconds and a “beep” sound (continuously for 4 seconds) will be heard. If no codes are matched, Power LED will light up for 0.5 seconds and no sound will be heard.

7 The breakdown diagnosis mode will be canceled unless pressing the CHECK button continuously for 5 seconds or operating the unit for 30 seconds.

8 The LED will be off if the unit is turned off or the RESET button on the main unit is pressed.

13.2.3 To Display Memorized Error Code (Protective Operation) 1 Turn power on. 2 Press the CHECK button on the remote control. 3 “- -“ will be displayed on the remote control display.

Note: Display only for “- -“ (No signal transmission, no receiving sound and no Power LED blinking) 4 Press the TIMER or button on the remote control. The code “H00” (no abnormality) will be displayed

and signal will be transmit to the main unit. 5 Each press of the button ( or ) will increase error code number and transmit error code signal to the main

unit. 6 When the latest abnormality code on the main unit and code transmitted from the remote control are matched,

Power LED will light up for 30 seconds and a “beep” sound (continuously for 4 seconds) will be heard. If no codes are matched, Power LED will light up for 0.5 seconds and no sound will be heard.

7 The breakdown diagnosis mode will be canceled unless pressing the CHECK button continuously for 5 seconds or operating the unit for 30 seconds.

8 The same diagnosis can be repeated by turning power on again.

13.2.4 To Clear Memorized Error Code after Repair (Protective Operation) 1 Turn power on (in standby condition). 2 Press the AUTO button for 5 seconds (a “beep” sound is heard) on the main unit to operate the unit at

Forced Cooling Operation Mode. 3 Press the CHECK button on the remote control for about 1 second with a pointed object to transmit signal to

main unit. A “beep” sound is heard, and the Error Code is cleared.

13.2.5 Temporary Operation (Depending On Breakdown Status) 1 Press the Auto OFF/ON button on the main unit (a “beep” sound is heard) to operate the unit. (Remote

control is enable again). 2 The unit can be temporarily be used until repaired.

Error Code Operation Temporary items H23 Cooling Emergency Operation

with limited power H27, H28 Cooling

FAN SPEED

AIR SWING

MODE

TEMP

OFF/ON

TIMER

SET

CANCEL

ON

OFF

12

3

OFFTIMER

ONTIMER

AUTOCOOLDRY

FANSPEEDAIRSWING

SET CHECK CLOCKRESET

ACRC

TEMP

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1

3

CHECK

Checkbutton

Page 46: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

46

13.3 Error Code Table Diagnosis

display Abnormality / Protection

control Abnormality Judgment

Protection Operation Problem Check location

H00 No memory of failure — Normal operation — —

H11 Indoor/outdoor abnormal communication

After operation for1 minute

Indoor fan only operation can start by entering into force cooling operation

Indoor/outdoor communication not establish

Indoor/outdoor wire terminal Indoor/outdoor PCB Indoor/outdoor connection

wire

H12 Indoor unit capacity unmatched

90s after power supply —

Total indoor capability more than maximum limit or less than minimum limit, or number of indoor unit less than two

Indoor/outdoor connection wire

Indoor/outdoor PCB Specification and

combination table in catalogue

H14 Indoor intake air temperature sensor abnormality Continuous for 5s —

Indoor intake air temperature sensor open or short circuit

Indoor intake air temperature sensor lead wire and connector

H15 Compressor temperature sensor abnormality Continuous for 5s —

Compressor temperature sensor open or short circuit

Compressor temperature sensor lead wire and connector

H16 Outdoor current transformer (CT) abnormality — — Current transformer faulty

or compressor faulty Outdoor PCB faulty or

compressor faulty

H19 Indoor fan motor mechanism lock

Continuous happen for 7 times — Indoor fan motor lock or

feedback abnormal

Fan motor lead wire and connector

Fan motor lock or block

H23 Indoor heat exchanger temperature sensor abnormality

Continuous for 5s — Indoor heat exchanger temperature sensor open or short circuit

Indoor heat exchanger temperature sensor lead wireand connector

H25 Indoor ion device abnormality Port is ON for 10s during ion device off — — ion device PCB

H27 Outdoor air temperature sensor abnormality Continuous for 5s —

Outdoor air temperature sensor open or short circuit

Outdoor air temperature sensor lead wire and connector

H28 Outdoor heat exchanger temperature sensor abnormality

Continuous for 5s — Outdoor heat exchanger temperature sensor open or short circuit

Outdoor heat exchanger temperature sensor lead wireand connector

H30 Outdoor discharge pipe temperature sensor abnormality

Continuous for 5s — Outdoor discharge pipe temperature sensor open or short circuit

Outdoor discharge pipe temperature sensor lead wireand connector

H33 Indoor / outdoor misconnection abnormality — — Indoor and outdoor rated

voltage different Indoor and outdoor units

check

H34 Outdoor heat sink temperature sensor abnormality

Continuous for 2s — Outdoor heat sink temperature sensor open or short circuit

Outdoor heat sink sensor

H36 Outdoor gas pipe temperature sensor abnormality Continuous for 5s Heating protection

operation only

Outdoor gas pipe temperature sensor open or short circuit

Outdoor gas pipe temperature sensor lead wire and connector

H38 Indoor/Outdoor mismatch (brand code) — — Brand code not match Check indoor unit and

outdoor unit

H39 Abnormal indoor operating unit or standby units

3 times happen within 40 minutes —

Wrong wiring and connecting pipe, expansion valve abnormality, indoor heat exchanger sensor open circuit

Check indoor/outdoor connection wire and connection pipe

Indoor heat exchanger sensor lead wire and connector

Expansion valve and lead wire and connector

H41 Abnormal wiring or piping connection — —

Wrong wiring and connecting pipe, expansion valve abnormality

Check indoor/outdoor connection wire and connection pipe

Expansion valve and lead wire and connector

H59 ECONAVI sensor abnormality Continuous for 25s — ECONAVI sensor open or short circuit

ECONAVI sensor (defective or disconnected)

ECONAVI PCB

H64 Outdoor high pressure sensor abnormality

Continuous for 1 minute —

High pressure sensor open circuit during compressor stop

High pressure sensor Lead wire and connector

Page 47: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

47

Diagnosis display

Abnormality / Protection control

Abnormality Judgment

Protection Operation Problem Check location

H70 Light sensor abnormality Continuous for 24 hours, 15 days — Light sensor open or short

circuit Light sensor (defective or

disconnect)

H97 Outdoor fan motor mechanism lock

2 times happen within 30 minutes — Outdoor fan motor lock or

feedback abnormal

Outdoor fan motor lead wire and connector

Fan motor lock or block

H98 Indoor high pressure protection — — Indoor high pressure

protection (Heating)

Check indoor heat exchanger Air filter dirty Air circulation short circuit

H99 Indoor operating unit freeze protection — — Indoor freeze protection

(Cooling)

Check indoor heat exchanger Air filter dirty Air circulation short circuit

F11 4-way valve switching abnormality “*”

4 times happen within 30 minutes — 4-way valve switching

abnormal 4-way valve Lead wire and connector

F17 Indoor standby units freezing abnormality

3 times happen within 40 minutes —

Wrong wiring and connecting pipe, expansion valve leakage, indoor heat exchanger sensor open circuit

Check indoor/outdoor connection wire and pipe

Indoor heat exchanger sensor lead wire and connector

Expansion valve lead wire and connector

F90

System and compressor microcomputer communication error (for S10*** only)

2 times happen within 5 seconds — — Compressor

Outdoor PCB

F90 Power factor correction (PFC) circuit protection

4 times happen within 10 minutes — Power factor correction

circuit abnormal Outdoor PCB faulty

F91 Refrigeration cycle abnormality

2 times happen within 20 minutes — Refrigeration cycle

abnormal Insufficient refrigerant or

valve close

F93 Compressor abnormal revolution

4 times happen within 20 minutes — Compressor abnormal

revolution Power transistor module

faulty or compressor lock

F94 Compressor discharge overshoot protection

4 times happen within 30 minutes — Compressor discharge

pressure overshoot Check refrigeration system

F95 Outdoor cooling high pressure protection

4 times happen within 20 minutes — Cooling high pressure

protection Check refrigeration system Outdoor air circuit

F96 Power transistor module overheating protection

4 times happen within 30 minutes — Power transistor module

overheat PCB faulty Outdoor air circuit (fan motor)

F97 Compressor overheating protection

3 times happen within 30 minutes — Compressor overheat Insufficient refrigerant

F98 Total running current protection

3 times happen within 20 minutes — Total current protection

Check refrigeration system Power source or compressor

lock

F99 Outdoor direct current (DC) peak detection

Continuous happen for 7 times — Power transistor module

current protection Power transistor module

faulty or compressor lock Note: “ * ” – For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has abnormality. The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the CHECK button at remote control. Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote control signal receiving sound is changed from one “beep” to four “beep” sounds.

Page 48: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

48

13.4 Troubleshooting Flowchart

13.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions During startup and operation of cooling, the data received from outdoor unit in indoor unit signal transmission is

checked whether it is normal. Malfunction Caused Faulty indoor unit PCB. Faulty outdoor unit PCB. Indoor unit-outdoor unit signal transmission error due to wrong wiring. Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the

indoor and outdoor units. Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform. Troubleshooting

Check the indoor-outdoor units’ connection wires.

Is there any wiring error?

Disconnect terminal 3 wire and measure Vdc between terminal2 & 3 from the outdoor unit.

Reconnect terminal 3 wire and measure Vdc between terminal2 & 3 from the outdoor unit.

Is the Vdc fluctuate between 20-50 Vdc?

Is the Vdc fluctuate between 20-70 Vdc?

When abnormality indication starts again.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Replace indoor unit PCB.

Replace indoor PCB.

Correct the indoor-outdoor unitsconnection wires.

NO

NO

NO

YES

YES

Caution

Page 49: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

49

13.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused Wrong models interconnected. Wrong indoor unit or outdoor unit PCBs mounted. Indoor unit or outdoor unit PCBs defective. Indoor-outdoor unit signal transmission error due to wrong wiring. Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor

and outdoor units. Troubleshooting

Check the indoor and outdoor unit connection wires.

Check indoor and outdoor units model number.

Is indoor unit and outdoor unit model numbers matched?

Check the spare part numbers of the indoor and outdoor unitPCBs and compare with their Part Lists.

Matched compatibility?

Is there any wiring error?

When abnormality indication starts again.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Correct the indoor-outdoor unit’s connection wires.

Change for the specified indoor or outdoor unitPCB.

Replace the indoor and outdoor unit PCBs.

Match the compatible model(s).

NO

NO

NO

YES

YES

YES

Caution

Page 50: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

50

13.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling, the temperatures detected by the indoor intake air temperature sensor

are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

Check the connector connection:Turn off the power.Check the connector connection.

Is the connector connection normal?

When abnormality indication starts again.

For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Connector poor contact.Correct the connection.

Defect in indoor unit PCB.Replace the indoor unit PCB.

Defect in indoor intake air temperature sensor.Replace the indoor intake air temperature sensor.

Check the indoor intake air temperature sensor:Plug out connector from the indoor unit PCB.Measure the resistance of the indoor intake airtemperature sensor.

Is the measured resistance of the indoor intake airtemperature sensor matches the value specified in itscharacteristic chart?

NO

NO

YES

YES

0

10

-10 10 20 30 40 500

20

30

40

50

60

70

Temperature (°C)

Resis

tanc

e(k)

Sensor (Thermistor)Characteristics

Pipe temp. SensorIntake Air Temp. Sensor

Caution

Page 51: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

51

13.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling, the temperatures detected by the outdoor compressor temperature

sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

When abnormality indication starts again.

For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Connector poor contact.Correct the connection.

Defect in outdoor compressor temperature sensor.Replace the outdoor compressor temperature sensor.

Defect in outdoor unit PCB.Replace the outdoor unit PCB.

Turn off the power.Check the connector connection.

YES

YES

0

10

20

20 40 60 80 100 120 140

30

40

50

60

70

Temperature (°C)

Resis

tanc

e(k)

Compressor Temp. Sensor(Thermistor) Charateristics

Check the connector connection:

Plug out connector from the outdoor unit PCB.Measure the resistance of the outdoor compressortemperature sensor.

Check the outdoor compressor temperature sensor:

Is the connector connection normal?

Is the measured resistance of the outdoor compressortemperature sensor matches the value specified in itscharacteristic chart?

NO

NO

Caution

Page 52: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

52

13.4.5 H16 (Outdoor Current Transformer Open Circuit) Malfunction Decision Conditions A current transformer (CT) is detected by checking the compressor running frequency (≥ rated frequency) and

CT detected input current (less than 1.14A) for continuously 20 seconds. Malfunction Caused CT defective. Outdoor PCB defective. Compressor defective (low compression). Troubleshooting

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Check the functionality of current transformer (CT).

Is the CT open circuit?

Is the running current less than 0.65 A and suction pressure120 psi?

Force heating operation and measure:

When abnormality indication starts again.

NO

NO

YES

YES

Running current.

Replace the outddoor PCB.

Replace Compressor due to compressor lowcompression.

Check for gas leaking source; Repair or replacedefected part(s).

Suction pressure.

Caution

Page 53: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

53

13.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor

(feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused Operation stops due to short circuit inside the fan motor winding. Operation stops due to breaking of wire inside the fan motor. Operation stops due to breaking of fan motor lead wires. Operation stops due to Hall IC malfunction. Operation error due to faulty indoor unit PCB. Troubleshooting

Turn off power supply and rotate fan by hand.

When abnormality indication starts again.

Replace fan motor.Does fan rotate smoothly?

Turn power supply on and operate fan.

Does it rotate? Stop fan motor.

Check the rotation feedback output from fan motor.

Rotate the fan motor by hand, is the rotationfeedback voltage 15Vdc (pin 7 & 4) generated?

Turn off power supply and disconnect fan motor connector,then turn power on.

Check the output of fan motor from indoor PCB.

Is the motor power supply voltage~325Vdc (pin 1 & 4)generated?

Is the motor control voltage 15Vdc (pin 5 & 4) generated?

Operate the fan, is the rotation command voltage 1~5Vdc(pin 6 & 4) generated?

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Replace indoor PCB.

Replace fan motor.

Caution

Page 54: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

54

13.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling, the temperatures detected by the indoor heat exchanger temperature

sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

When abnormality indication starts again.

For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Connector poor contact.Correct the connection.

Defect in outdoor unit PCB.Replace the outdoor unit PCB.

Defect in outdoor intake air temperature sensor.Replace the outdoor intake air temperaturesensor.

NO

NO

YES

YES

0

10

-10 10 20 30 40 500

20

30

40

50

60

70

Temperature (°C)

Resis

tanc

e(k)

Sensor (Thermistor)Characteristics

Pipe temp. SensorIntake Air Temp. Sensor

Check the connector connection:Plug out connector from the indoor unit PCB.

Is the connector connection normal?

Measure the resistance of the indoor pipe temperaturesensor.

Check the outdoor air temperature sensor:

Is the measured resistance of the outdoor intake airtemperature sensor matches the value specified in itscharacteristic chart?

Plug out connector from the outdoor unit PCB.Measure the resistance of the outdoor intake airtemperature sensor.

Caution

Page 55: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

55

13.4.8 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling, the temperatures detected by the outdoor air temperature sensor are

used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

Check the connector connection:

Is the measured resistance of the outdoor air temperaturesensor matches the value specified in its characteristicchart?

Is the connector connection normal?

When abnormality indication starts again.

For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Turn off the power.Check the connector connection.

Defect in outdoor air temperature sensor.Replace the outdoor air temperature sensor.

Defect in outdoor unit PCB.Replace the outdoor unit PCB.

NO

NO

YES

YES

Check the outdoor air temperature sensor:Plug out connector from the outdoor unit PCB.Measure the resistance of the outdoor air temperaturesensor.

Connector poor contact.Correct the connection.

0

10

-10 10 20 30 40 500

20

30

40

50

60

70

Temperature (°C)

Resis

tance

(k)

Sensor (Thermistor)Characteristics

Outdoor Air SensorOutdoor Heat ExchangerSensor

Caution

Page 56: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

56

13.4.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling, the temperatures detected by the outdoor pipe temperature sensor are

used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

Is the measured resistance of the outdoor heat exchangertemperature sensor matches the value specified in itscharacteristic chart?

Is the connector connection normal?

When abnormality indication starts again.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

No

No

YES

YES

Check the outdoor heat exchanger temperature sensor:Plug out connector from the outdoor unit PCB.Measure the resistance of the outdoor heat exchangertemperature sensor.

0

10

-10 10 20 30 40 500

20

30

40

50

60

70

Temperature (°C)

Resis

tanc

e(k)

Sensor (Thermistor)Characteristics

Outdoor Air SensorOutdoor Heat ExchangerSensor

Check the connector connection:Turn off the power.Check the connector connection.

Connector poor contact.Correct the connection.

Defect in outdoor unit PCB.Replace the outdoor unit PCB.

Defect in outdoor heat exchangertemperature sensor.Replace the outdoor heat exchangertemperature sensor.

Caution

Page 57: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

57

13.4.10 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling, the temperatures detected by the outdoor discharge pipe temperature

sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

When abnormality indication starts again.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Is the measured resistance of the outdoor discharge pipetemperature sensor matches the value specified in itscharacteristic chart?

Is the connector connection normal?

YES

YES

Check the outdoor discharge pipe temperature sensor:Plug out connector from the outdoor unit PCB.Measure the resistance of the outdoor discharge pipetemperature sensor.

Check the connector connection:Turn off the power.Check the connector connection.

Connector poor contact.Correct the connection.

Defect in outdoor unit PCB.Replace the outdoor unit PCB.

Defect in outdoor discharge pipetemperature sensor.Replace the outdoor discharge pipetemperature sensor.

NO

NO

Caution

Page 58: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

58

13.4.11 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused Wrong models interconnected. Wrong indoor unit and outdoor unit PCBs used. Indoor unit or outdoor unit PCB defective. Troubleshooting

When abnormality indication startsagain.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

H33 occurs right after installation?

Has the indoor and outdoor modelmatched in voltage rating?

H33 occurs intermittently duringoperation? (unit has operatednormally before)

H33 occurs right after servicingand has never occur before?

Has the PCB (indoor or outdoor)being replaced?

Confirm the replaced PCB partnumber versus listed in ServiceManual.

Has the AC power input droppedmore than 50% of rating? (in mostcases customers do not aware ofthe voltage drop but the installedarea has known power supplyissue).

Check DC Voltage afterrectification at outdoor or indoorPCB. DC Voltage drops below180 Vdc.

Has the AC power input droppedmore than 50% of rating?

Change outdoor main,indoor main and PCB.

Match the compatible model(follow specification).

Change outdoor PCB.

Replace with correct PCB.

Match the compatible model(follow specification).

YES

YESYES

YES

NO

NO

NO NO

NO

NO

Caution

Page 59: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

59

13.4.12 H34 (Outdoor Heat Sink Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling, the temperatures detected by the outdoor heat sink temperature sensor

are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

When abnormality indication starts again.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Is the measured resistance of the outdoor discharge pipetemperature sensor matches the value specified in itscharacteristic chart?

Is the connector connection normal?

YES

YES

Check the outdoor discharge pipe temperature sensor:Plug out connector from the outdoor unit PCB.Measure the resistance of the outdoor discharge pipetemperature sensor.

Check the connector connection:Turn off the power.Check the connector connection.

Connector poor contact.Correct the connection.

Defect in outdoor unit PCB.Replace the outdoor unit PCB.

Defect in outdoor discharge pipetemperature sensor.Replace the outdoor discharge pipetemperature sensor.

NO

NO

Caution

Page 60: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

60

13.4.13 H36 (Outdoor Gas Pipe Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling, the temperatures detected by the outdoor gas pipe temperature sensor

are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

When abnormality indication starts again.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Is the measured resistance of the outdoor discharge pipetemperature sensor matches the value specified in itscharacteristic chart?

Is the connector connection normal?

YES

YES

Check the outdoor discharge pipe temperature sensor:Plug out connector from the outdoor unit PCB.Measure the resistance of the outdoor discharge pipetemperature sensor.

Check the connector connection:Turn off the power.Check the connector connection.

Connector poor contact.Correct the connection.

Defect in outdoor unit PCB.Replace the outdoor unit PCB.

Defect in outdoor discharge pipetemperature sensor.Replace the outdoor discharge pipetemperature sensor.

NO

NO

Caution

Page 61: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

61

13.4.14 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. Operation stops due to breaking of wire inside the fan motor. Operation stops due to breaking of fan motor lead wires. Operation stops due to Hall IC malfunction. Operation error due to faulty outdoor unit PCB. Troubleshooting

Turn off power supply and rotate fan by hand.

When abnormality indication starts again.

Replace fan motor.Does fan rotate smoothly?

Main outdoor PCB transistor faulty.

Fan motor faulty.

Turn off power supply and disconnect CN-MTR2 connector.Connect inverter checker to CN-MTR2 then turn power on.

Check the output of fan motor from outdoor PCB.

Is all 6 LED on and off periodically?

Check fan motor winding U-V, V-W, U-W. Is value consistent inall readings?

Is the fan motor rotation start and stop intermittently duringinitial running?

NO

NO

NO

Replace outdoor PCB.

Replace fan motor.

YES

YES

YES

YES

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Caution

Page 62: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

62

13.4.15 H98 (Indoor High Pressure Protection) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions During operation, the temperature detected by the indoor pipe temperature sensor is above 60°C. Malfunction Caused Clogged air filter of the indoor unit. Dust accumulation on the indoor unit heat exchanger. Air short circuit. Detection error due to faulty indoor pipe temperature sensor. Detection error due to faulty indoor unit PCB. Troubleshooting

Check the air passage.

When abnormality indication starts again.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Provide sufficient air passage.

Clean the air filter.

Clean the indoor unit heat exchanger.

Replace the indoor pipe temperaturesensor.

Replace the indoor unit PCB.

Is there any short circuit?

Check the indoor unit air filter.

Is the air filter dirty?

Check the dust accumulation on the indoor unit heat exchanger.

Is the indoor unit heat exchanger dirty?

Check the indoor pipe temperature sensor.

Does it conform to the sensor characteristic chart?

YES

YES

YES

NO

NO

NO

Caution

Page 63: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

63

13.4.16 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Malfunction Decision Conditions Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C). Malfunction Caused Clogged air filter of the indoor unit. Dust accumulation on the indoor unit heat exchanger. Air short circuit. Detection error due to faulty indoor pipe temperature sensor. Detection error due to faulty indoor unit PCB. Troubleshooting

When abnormality indication starts again.

Check the air passage.

Is there any short circuit?

Is the air filter dirty?

Is the indoor unit heat exchanger dirty?

Does it conform to the sensor characteristic chart?

Check the dust accumulation on the indoor unit heatexchanger.

Check the indoor heat exchanger temperaturesensor.

Check the air filter.

YES

YES

YES

YES

NO

NO

NO

NO

Provide sufficient air passage.

Clean the air filter.

Replace the indoor unit PCB.

Replace the indoor unit PCB.Defect in indoor unit PCB.

Clean the indoor unit heatexchanger.

For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Caution

Page 64: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

64

13.4.17 F11 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions When cooling operation, when indoor pipe temperature or indoor heat exchanger temperature sensor is above

45°C. Malfunction Caused Faulty connector connection. Faulty indoor pipe temperature sensor. Faulty indoor main PCB. Troubleshooting

When abnormality indication starts again. For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.

Replace the indoor main PCB.

Correct loose or broken cable / connector.

Replace the indoor pipe temperaturesensor.

YES

YES

0

10

-10 10 20 30 40 500

20

30

40

50

60

70

Temperature (°C)

Resis

tanc

e(k)

Sensor (Thermistor)Characteristics

Pipe temp. SensorIntake Air Temp. Sensor

Check the indoor pipe temperature sensor connection.

Does it cable connection loose or connector broken?

Check the indoor pipe temperature characteristic.

Does it conform to specification?

The problem still occur after replacing thesensor.

NO

NO

Caution

Page 65: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

65

13.4.18 F17 (Indoor Standby Units Freezing Abnormality) Malfunction Decision Conditions When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor

pipe temperature is below -1.0°C. Remark: When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to other indoor unit(s).

Malfunction Caused Wrong wiring connection. Faulty sensor. Faulty expansion valve. Troubleshooting

For safety reason and to prevent componentbreakdown, always switch off the power beforeremove and connect the component.

When abnormality starts again

Check the indoor pipe temperaturethermistor:

Plug out connector (CN-TH) from theindoor unit PCB

ReplaceOutdoor PCB

Measure the resistance of the indoor heatexchanger temperature thermistor

Is the measured resistance of the indoorpipe temperature thermistor matches thevalue specified in its characteristic chart?

The 4-way valve may have been damaged orwrongly connected between discharge andsuction tube

Problem occurs in heating mode only?

Is 4-way solenaid valve being energised?

Defect in indoor pipe temperaturethermistorReplace the indoor pipe temperaturethermistor

4-way valve not working(not energize)

Check CN-HOTconnection(4-way valve connector)

Check V-coil attach tosolenoid valve

Check valve v-coilcontinuity

Measure voltagesupplied to CH-HOT atthe start of heating

YES

OK

NoGood

4 WAYS VALVE

COIL COMPLETE

YELLOWCN-HOT(WHT)

1

2

YELLOW

NoGood

Nocontinuity

(open)

OK

OK

No supply

YES

Outdoor PCB fault

Reserve solenoid valve faulty

Replace Outdoor PCB

Check connecting tubes to 4-way valve

Replace the 4-way valve

Remove CN-HOT.Measure continuityof the coil

Reconnect CN-HOT(4-way valve connector)

Attach and screw the V-coilto solenoid valve

ReplaceV-coil only

V-coil faultCN-HOT

4 WAYSVALVE

(VH9-2)

Outdoor PCB fault

YES

NO

NO

NO, it happen in cooling/dry as well

OK (Depending on 4-way valve model)

1 2 3

Caution

Page 66: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

66

13.4.19 F90 (Power Factor Correction Protection) Malfunction Decision Conditions During startup and operation of cooling, when Power Factor Correction (PFC) protection circuitry at the outdoor

unit main PCB senses abnormal high DC voltage level. Malfunction Caused DC voltage peak due to power supply surge. DC voltage peak due to compressor windings not uniform. Faulty outdoor PCB. Troubleshooting

When abnormality indication starts again.

Check the supply voltage.

Supply voltage as specified?

Operate the system. Verify PFC abnormality by measuring DCvoltage between P (+) and N (-) terminal at the outdoor unit PCB.

Is the DC voltage between P (+) and N (-) terminal normalbetween 285 ~ 315 Vdc?

Are the compressor’s winding resistance (U-V, V-W, W-U).

YES

YES

YES

NO

NO

NO

Correct the power supply.

Turn off the power supply and disconnect the harness U, Vand W.

Check the compressor winding resistance:

Measure the winding resistance between U-V, V-W and W-U.

Replace the outdoor unit PCB.

For safety reason and to preventcomponent breakdown, alwaysswitch off the power before removeand connect the component.

(~285 Vdc)Replace the outdoor unit PCB.Defect in PFC circuitry.

Replace the compressor.

Caution

Page 67: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

67

13.4.20 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions During cooling, compressor frequency = Fcmax. During cooling operation, running current: 0.65A < I < 1.65A. During cooling, indoor intake - indoor pipe < 4°C.

Malfunction Caused Refrigerant shortage (refrigerant leakage) Poor compression performance of compressor. 2/3 way valve closed. Detection error due to faulty indoor intake air or indoor pipe temperature sensors. Troubleshooting

Check the indoor air intake and pipetemperature sensors.

When F91 indication happens. For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Replace the indoor intake air or pipetemperature sensor.

Open 2/3 way valve.

Repair the pipe flare or union nuts.Reclaim and recharge refrigerant.

Replace the capillary tube or dryer.

Replace outdoor unit PCB &compressor.

Procedure complete.

NO

NO

NO

NO

YES

YES

YES

YES

Does it conform to the sensorcharacteristic chart?

2/3-way valve opened?

Check for gas leaking.

Charge for a specified amount of freshrefrigerant.

Refrigerant cycle abnomality error again?

Oil oozing out from the 2/3 way valve?

Capillary tube or dryer clogged?

Caution

Page 68: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

68

13.4.21 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused Compressor terminal disconnect. Outdoor PCB malfunction. Troubleshooting

When F93 indication happens. For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

IPM defective.

Replace compressor.

Replace outdoor unit PCB.YES

Turn off power supply. Disconnect U, Vand W wires.

Check with inverter checker.

Normal? NO

Caution

Page 69: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

69

13.4.22 F95 (Cooling High Pressure Abnormality) Malfunction Decision Conditions During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the outdoor pipe temperature sensor. Malfunction Caused Outdoor pipe temperature rise due to short circuit of hot discharge air flow. Outdoor pipe temperature rise due to defective of outdoor fan motor. Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor. Outdoor pipe temperature rise due to defective outdoor unit PCB. Troubleshooting

When F95 indication happens. For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

YES

YES

YES

Check the outdoor unit installationcondition (during cooling or soft-dryoperation).

Is there any improper heat radiation?

Is outdoor fan motor operating?

Check the outdoor pipe temperaturesensor.

Does it conform to the sensorcharacteristic charts?

NO

NONO

Reinstall the outdoor unit.

Replace the outdoor fan motor.

Replace compressor.

Replace outdoor unit PCB.

Remove the obstacle(s).Clean the outdoor heat exchanger.

Caution

Page 70: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

70

13.4.23 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling, when IPM temperature data (100°C) is detected by the IPM temperature sensor. Malfunction Caused IPM overheats due to short circuit of hot discharge air flow. IPM overheats due to defective of outdoor fan motor. IPM overheats due to defective of internal circuitry of IPM. IPM overheats due to defective IPM temperature sensor. Troubleshooting

When F96 indication happens. For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Check the outdoor unit installationcondition (during cooling or soft-dryoperation).

Is there any improper heat radiation?YES

YES

NONO

Reinstall the outdoor unit.

Replace the outdoor fan motor.

Remove the obstacle(s).Clean the outdoor heat exchanger.

Defect in IPM.Replace the outdoor unit PCB.

Is outdoor fan motor operating?

Caution

Page 71: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

71

13.4.24 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooling, when compressor tank temperature data (112°C) is detected by the compressor tank temperature sensor. Malfunction Caused Refrigerant shortage (refrigerant leakage). 2/3 way valve closed. Detection error due to faulty compressor tank temperature sensor. Troubleshooting

When F97 indication happens. For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Replace the compressor tanktemperature sensor.

Repair the pipe flare or union nuts.Reclaim and recharge refrigerant.

Open the 2/3 way valve.

Replace the capillary tube or dryer.

Procedure complete.

Check the compressor tank temperaturesensor.

Does it conform to the sensorcharacteristic chart?

2/3 way valve closed?

Check for gas leakage.

Is Oil oozing out from the 2/3 way valve?

Capillary tube or dryer clogged?

Charge a specified amount of freshrefrigerant.

Refrigerant cycle abnormality errorhappens again?

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

Replace outdoor unit PCB.Replace outdoor unit compressor.

Caution

Page 72: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

72

13.4.25 F98 (Input Over Current Detection) Malfunction Decision Conditions During cooling operation, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running. Malfunction Caused Over-current due to compressor failure. Over-current due to defective outdoor unit PCB. Over-current due to defective inverter main circuit electrolytic capacitor. Over-current due to excessive refrigerant. Troubleshooting

For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Replace the outdoor unit PCB.

Repair the pipe flare or union nuts.Reclaim and recharge refrigerant.

Reclaim and recharge with correctamount of refrigerant.

Replace outdoor unit PCB.Replace outdoor unit compressor.

When F98 indication happens.

Get restarted and measure the inputcurrent.

Turn off power supply. Check the maincircuit electrolytic capacitor.

Is Input current > 16.8A?

Normal?

Check refrigerant amount.

Excess refrigerant?

YES

YES

YES

NO

NO

NO

NO

Caution

Page 73: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

73

13.4.26 F99 (Output Over Current Detection) Malfunction Decision Conditions During operation of cooling, when an output over-current (18.5A) is detected by checking the current that flows in the inverter DC peak sensing circuitry. Malfunction Caused DC peak due to compressor failure. DC peak due to defective power transistor(s). DC peak due to defective outdoor unit PCB. Troubleshooting

Checking the power transistor. Never touch any live parts for at least 10 minutes after turning off the circuit breaker. If unavoidable necessary to touch a live part, make sure the power transistor’s supply voltage is below 50V using

the tester. For the UVW, make measurement at the Faston terminal on the board of the relay connector.

Tester’s negative terminal Power transistor (+) UVW Power transistor (-) UVW Tester’s positive terminal UVW Power transistor (+) UVW Power transistor (-)

Normal resistance Several kΩ to several MΩ Abnormal resistance 0 or ∞

For safety reason and to prevent componentbreakdown, always switch off the powerbefore remove and connect the component.

Replace the outdoor unit PCB.

Compressor defective due to windingshorted.Replace compressor.

Outdoor electronic circuit defect due topower transistor short.Replace the outdoor unit PCB.

When F99 indication happens.

Get restarted and measure the inputcurrent.

Are the compressor’s winding resistance(U-V, V-W or U-W) shorted?

Input current > 18.5A?

NO

Turn off the power and disconnectthe harnesses U, V and W.Measure the winding resistancebetween U-V, V-W and W-U.

Check the compressor winding resistance:

NO

YES

YES

Caution

Page 74: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

74

14. Disassembly and Assembly Instructions WARNING

High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks.

14.1 CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH

14.1.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures

To Remove Front Grille 14.1.1.1

Figure 1

To Remove Electronic Controller 14.1.1.2

Figure 2

2. Remove 2 caps and 2 screws at thebottom of discharge vane.

3. Hold both sides of the front grille andremove it by pulling up and towardyourself gently.

1. Lift to open the horizontal vanegently.

4. Remove the controlboard cover byreleasing the hook.

Hook

Page 75: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

75

Figure 3 Figure 4

To Remove Discharge Grille 14.1.1.3

Figure 5

To Remove Control Board 14.1.1.4

Figure 6

8. Pull out the mainelectronic controllerhalfway.

7. Remove screw to removeterminal board completeand earth wire.

9. Detach connectors as labeled from theelectronic controller. Then pull out maincontroller gently.

6. Detach the CN-DISPconnector then removethe indicator complete.5. Detach the Earth wire.

CN-PCFM

RY-PWR connector(Black and Brown)

AC303 (White)

CN-FB

CN-STM1

CN-TH

10. Pull out to remove the drain hosefrom the discharge grille.

11. Then pull the discharge grilledownward gently to dismantle it.

Discharge Grille

12. Remove 4 screws holding thecontrol board then pull out thecontrol board.

Page 76: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

76

To Remove Cross Flow Fan and Indoor Fan Motor 14.1.1.5

Figure 7

Figure 8

Figure 9

13. Remove the screw that holdingthe cross flow fan and fan motoraxis.

14. Remove the screw from theevaporator.

Holdfast

15. Remove the bearing by pulling itout gently.

18. Fan motor can be removed after theremoval of cross flow fan.

Reminder: To reinstall the fan motor, adjustthe fan motor connector to 45° towards youbefore fixing control board.

16. Push the holdfast to the left and lift up the evaporator.

17. Remove the cross flow fan from the unit bypulling it to the left and downward.

Evaporator

Page 77: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

77

Figure 10

Reminder: To reinstall the cross flowfan, ensure cross flow fan is in line asshown in figure 10.

Cross Flow Fan

Page 78: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

78

WARNING

High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks.

14.2 CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH

14.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures

To Remove Front Grille 14.2.1.1

Figure 1

To Remove Electronic Controller 14.2.1.2

Figure 2

Figure 3 Figure 4

2. Remove 3 caps and 3 screws at thebottom of the discharge vane and 1 screwat the front grille.

1. Lift to open the horizontal vaneand intake grille gently.

3. Hold both sides of the frontgrille and remove it by pullingup and toward yourself gently.

4. Remove the controlboard cover byreleasing the 2 hooks.

2 hooks (left hand side)

8. Pull out the mainelectronic controllerhalfway.

9. Detach connectors as labeled fromthe electronic controller. The pull outmain controller gently.

7. Remove screw toremove terminalboard completeand earth wire.

6. Detach indicator connector then removethe indicator complete.

5. Detach the Earth wire screw.

CN-FM

CN-STM1

CN-TH

RY-PWR connector(Black and Brown)

AC303 (WHT)

Page 79: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

79

To Remove Discharge Grille 14.2.1.3

Figure 5

To Remove Control Board 14.2.1.4

Figure 6

To Remove Cross Flow Fan and Indoor Fan Motor 14.2.1.5

Figure 7

10. Pull out to remove the drain hose(behind the discharge grille)from the discharge grille outlet.

11. Then pull the discharge grilledownward gently to dismantle it.

Discharge Grille

12. Remove 4 screws holdingthe control board then pullout the control board.

13. Remove the screw that holding thecross flow fan and fan motor axis.

Page 80: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

80

Figure 8

Figure 9

Figure 10

15. Remove the screw from the evaporator.

Holdfast

14. Remove the bearingby pulling it out gently.

18. Fan motor can be removed afterthe removal of cross flow fan.

Reminder: To reinstall the fan motor,please adjust the connector to 45°with fan motor before fixing control board.

17. Remove the cross flow fan from the unitby pulling it to the left and downward.

16. Push the holdfast to the left and lift up the evaporator.

Evaporator

Reminder: To reinstall the cross flowfan, ensure cross flow fan is in line asshown in figure 10.

Cross Flow Fan

Page 81: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

81

15. Exploded View and Replacement Parts List 15.1 Indoor Unit

15.1.1 CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH

Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.

CWH55025J

CWH55051J

I/II/I I/I I/I I/IO/I

12

2415

36

33

45

46 47 48 49 50 51

40

44

34

25

1 27

2317

12A16

26

34

28

29

30

39

9

37

35

7

38

8

41

42

43

40A

13

25

36A

10

Page 82: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

82

SAFETY REF. NO. PART NAME & DESCRIPTION QTY CS-MPS9SKH CS-MPS12SKH CS-MPS15SKH REMARK 1 CHASSIS COMPLETE 1 CWD50C1901 ← ←

2 FAN MOTOR 1 CWA921447 ← ← O 3 CROSS-FLOW FAN COMPLETE 1 CWH02C1076 ← ← 4 BEARING ASS’Y 1 CWH64K007 ← ← 5 SCREW - CROSS-FLOW FAN 1 CWH551146 ← ← 7 EVAPORATOR 1 ACXB30C02630 CWB30C3338 ← 8 FLARE NUT (LIQUID) 1 CWT251048 ← ← 9 FLARE NUT (GAS) 1 CWT251031 CWT251049 ← 10 CLIP FOR SENSOR 1 CWH32142 ← ← 11 CONTROL BOARD CASING 1 CWH102449 ← ←

12 TERMINAL BOARD COMPLETE 1 CWA28C2357 ← ← 12A PARTICULAR PIECE - TERMINAL 1 CWD933137 ← ←

13 ELECTRONIC CONTROLLER - MAIN 1 ACXA73C09300 ACXA73C09310 ACXA73C09320 O

15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA746716 ← ← O 16 SENSOR COMPLETE 1 CWA50C2122 ← ← 17 PARTICULAR PIECE 1 CWD933067 ← ← 23 CONTROL BOARD TOP COVER 1 CWH131467 ← ← 24 INDICATOR HOLDER 1 CWD933406 ← ← 25 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ← ← 26 DISCHARGE GRILLE COMPLETE 1 CWE20C3236 ← ← 27 BACK COVER CHASSIS 1 CWD933233 ← ← 28 FULCRUM 1 CWH621131 ← ← 29 VERTICAL VANE 8 CWE241374 ← ← 30 CONNECTING BAR 2 CWE261251 ← ← 33 AIR SWING MOTOR 1 CWA981264 ← ← O 34 CAP - DRAIN TRAY 1 CWH521259 ← ← 35 HORIZONTAL VANE COMPLETE 1 CWE24C1385 ← ← 36 REMOTE CONTROL COMPLETE 1 CWA75C3716-1 ← ← O 36A REMOTE CONTROL HOLDER 1 CWH361078 ← ← 37 FRONT GRILLE COMPLETE 1 ACXE10C01220 ← ← O 38 INTAKE GRILLE COMPLETE 1 CWE22C1958 ← ← O 39 GRILLE DOOR COMPLETE 1 CWE14C1090 ← ← 40 AIR FILTER 2 CWD001279 ← ← 40A ANTI-BACTERIAL FILTER 1 CWD00C1280 ← ← 41 SCREW - FRONT GRILLE 2 XTT4+16CFJ ← ← 42 CAP - FRONT GRILLE 2 CWH521227 ← ← 43 DRAIN HOSE 1 CWH851174 ← ← 44 INSTALLATION PLATE 1 CWH361134 ← ← 45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ← ← 46 OPERATING INSTRUCTION 1 ACXF55-04690 ← ← 47 INSTALLATION INSTRUCTION (ENGLISH) 1 ACXF60-04950 ← ← 48 INSTALLATION INSTRUCTION (CHINESE) 1 ACXF60-04960 ← ←

49 INSTALLATION INSTRUCTION (B. INDONESIA) 1 ACXF60-04970 ← ←

50 INSTALLATION INSTRUCTION (THAI) 1 ACXF60-04980 ← ←

51 INSTALLATION INSTRUCTION (VIETNAMESE) 1 ACXF60-04990 ← ←

(Note) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock.

Page 83: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

83

15.1.2 CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH

Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.

CWH55025J

CWH55051J

I/I I/IO/I I/I I/I I/I

35

30

31

29

34

25

13

16

1

40

34

5

8

37

3839

27

44

23

11

12

244315

46 47 48

36

26

33

4142

45

9 7

240A

12A

36A

49 50 51

17

10

28

Page 84: Indoor Unit CS-MPS12SKH CS-MPS15SKH CS-MPS18SKH … · 5 2. Specification Model Indoor/Outdoor CS-MPS9SKH / CU-2S18SKH CS-MPS12SKH / CU-2S18SKH Performance Test Condition JIS JIS

84

SAFETY REF. NO. PART NAME & DESCRIPTION QTY CS-MPS18SKH CS-MPS24SKH CS-MPS28SKH REMARK 1 CHASSIS COMPLETE 1 CWD50C1902 ← ←

2 FAN MOTOR 1 L6CBYYYL0037 ← ← O 3 CROSS-FLOW FAN COMPLETE 1 CWH02C1077 ← ← 4 BEARING ASS’Y 1 CWH64K007 ← ← 5 SCREW - CROSS-FLOW FAN 1 CWH551146 ← ← 7 EVAPORATOR 1 ACXB30C02640 CWB30C2783 ← 8 FLARE NUT (LIQUID) 1 CWT251048 ← ← 9 FLARE NUT (GAS) 1 CWT251049 CWT251032 ← 10 CLIP FOR SENSOR 1 CWH32142 ← ← 11 CONTROL BOARD CASING 1 CWH102449 ← ←

12 TERMINAL BOARD COMPLETE 1 CWA28C2357 ← ← 12A PARTICULAR PIECE - TERMINAL 1 CWD933137 ← ←

13 ELECTRONIC CONTROLLER - MAIN 1 ACXA73C09330 ACXA73C09340 ACXA73C09350 O

15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA746716 ← ← O 16 SENSOR COMPLETE 1 CWA50C2122 ← ← 17 PARTICULAR PIECE 1 CWD933067 ← ← 23 CONTROL BOARD TOP COVER 1 CWH131467 ← ← 24 INDICATOR HOLDER 1 CWD933406 ← ← 25 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ← ← 26 DISCHARGE GRILLE COMPLETE 1 CWE20C3243 ← ← 27 BACK COVER CHASSIS 1 CWD933031 ← ← 28 FULCRUM 2 CWH621138 ← ← 29 VERTICAL VANE 11 CWE241374 ← ← 30 CONNECTING BAR 1 CWE261260 ← ← 31 CONNECTING BAR 1 CWE261263 ← ← 33 AIR SWING MOTOR 1 CWA981241 ← ← O 34 CAP - DRAIN TRAY 1 CWH521259 ← ← 35 HORIZONTAL VANE COMPLETE 1 CWE24C1392 ← ← 36 REMOTE CONTROL COMPLETE 1 CWA75C3716-1 ← ← O 36A REMOTE CONTROL HOLDER 1 CWH361078 ← ← 37 FRONT GRILLE COMPLETE 1 ACXE10C01230 ← ← O 38 INTAKE GRILLE COMPLETE 1 CWE22C1959 ← ← O 39 GRILLE DOOR COMPLETE 1 CWE14C1090 ← ← 40 AIR FILTER 2 CWD001283 ← ← 40A ANTI-BACTERIAL FILTER 1 CWD00C1280 ← ← 41 SCREW - FRONT GRILLE 4 XTT4+16CFJ ← ← 42 CAP - FRONT GRILLE 3 CWH521227 ← ← 43 DRAIN HOSE 1 CWH851174 ← ← 44 INSTALLATION PLATE 1 CWH361098 ← ← 45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ← ← 46 OPERATING INSTRUCTION 1 ACXF55-04690 ← ← 47 INSTALLATION INSTRUCTION (ENGLISH) 1 ACXF60-04950 ← ← 48 INSTALLATION INSTRUCTION (CHINESE) 1 ACXF60-04960 ← ←

49 INSTALLATION INSTRUCTION (B. INDONESIA) 1 ACXF60-04970 ← ←

50 INSTALLATION INSTRUCTION (THAI) 1 ACXF60-04980 ← ←

51 INSTALLATION INSTRUCTION (VIETNAMESE) 1 ACXF60-04990 ← ←

(Note) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock.

Printed in Malaysia FZ1116-0