industrial buildings score card

Upload: ten-teng

Post on 03-Apr-2018

221 views

Category:

Documents


2 download

TRANSCRIPT

  • 7/29/2019 Industrial Buildings Score Card

    1/16

    Industrial Buildings Score Card Tool

    ver 1.1This Score Card is for scoping potential energy savings from Buildings

    energy measures at industrial sites

    This tool does not handle process heat recovery for building energy

    purposes, although inputs can be adjusted to approximate some

    possible heat recovery measures; nor does it treat appliances or office

    equipment. 10/22/2008

    This tool provides capabilities for a rough, quick assessment of energy

    used by buildings at a plant, and gives a quick assessment of energy

    measures, based on annual energy use and costs, that can be considered

    for further investigation.

    Go to the How-To Sheet (next sheet) to read directions on how to use

    this Score Card

  • 7/29/2019 Industrial Buildings Score Card

    2/16

    BUILDINGS

    Energy Savings Potential and Opportunities

    Buildings Energy Measures Score Card version 1.1

    How to Use this tool

    NOTES: Users enter total electricity use and fuel/steam estimates on the Energy sheet.

    Users may want to calculate total annual fuel/steam with a fuel calculator prior to entry.

    Cells for users to change are highlighted like this.

    STEP

    0 Go to the RESULTS sheet, Part 5, to see the example savings estimates

    1 Go to next sheet, PctFac, Part 1:

    1. Enter industry fraction(s) in column G, usually only one value will be needed

    The total in cell G33 should equal 100%

    2. If cell D16 is zero, then the value in cell D15 will be used in D19

    3. If cell D16 is NOT zero, then the value in cell D16 will be used in D19

    4. The value in cell D19 will be used on the Energy sheet to initially estimate energy

    2 Go to the sheet after that, Energy, Part 2:

    1. You must enter the total annual electricity and fuel/steam use for the applicable

    site where the buildings are located in row 11, columns B and C

    2. Electricity use is in kWh/yr, and Fuel/Steam use is in Million Btu/yr

    3. You must enter the total annual electricity and fuel/steam COSTS for the applicable

    site where the buildings are located in row 15, columns B and C

    4. This sheet sets the total Buildings electricity and fuel/steam use and costs

    Both energy use and costs for electricity and fuel/steam are estimatedThe values in row 30 are the annual Buildings use, and row 35 is annual costs

    5. The Buildings energy and energy cost total can be adjusted if needed

    Energy use adjustments are made by changing the percentages in row 28

    Energy COST adjustments are made by changing the percentages in row 33

    3 Go to the sheet after that, end-use, Part 3:

    1. You may not need to change anything on this sheet

    2. If you need to change some values, change in the yellow cells

    The sums shown in row 21, columns B and C should equal 100%

    4 Go to the "Scorecard" sheet, Part 4,

    Fill out or change the scorecard values according to your assessment of the plant buildings

    The assessment must cover the buildings included in the total energy data on the Energy sheet

    Do change the EXAMPLE entries that are there now, to reflect the building(s) being evaluated.

    Scorecard values indicate savings potential, so higher values mean more savings potential.

    5 Go to the sheet after that, RESULTS, Part 5:

  • 7/29/2019 Industrial Buildings Score Card

    3/16

    1. Results will be displayed here, both in energy units and $

    2. Nothing can be changed on this sheet

  • 7/29/2019 Industrial Buildings Score Card

    4/16

    BUILDINGS Part 1

    Percent Buildings Energy based on default Facilities Energy --------------->>>>Buildings Energy Measures Score Card version 1.1

    # 1 --> SELECT Typically only one industry

    NOTE: The percent value in item 'c' below will be used on Industry Default Quick PEP Industrythe next sheet to estimate Buildings electricity and Fractions Industry % of total t

    fuel/steam use. Adjustments to these estimates 0 Ag, Forestry, Fishing

    can also be made on the next sheet. 0 Chemical

    0 Aluminum / Alumina

    0 Cement

    Buildings energy is only a fraction of total energy use 0 Computers, Elec, Appl

    at industrial sites, sometimes small and sometimes large. 0 EAF Steel

    The defaults shown at the right are what Quick PEP assumes 0 Fab Metal Prod

    for facilities energy in specific industries, which will be used here as 1 Food, Bev, tobacco

    the Buildings energy percent. You can also set the percent here. 0 Foundries

    0 Furniture and related

    # 2 CHANGE the percent, item 'b' below if needed 0 Glass and glass products0 Heavy machinery

    Setting the percent of energy used by buildings 0 Integrated SteelIf you set a percent other than zero in 'b' it will be used instead: 0 Mining (except oil and gas)

    a. Current default percent = 15.00% 0 Non-metallic mineral products

    b. Percent to use instead = 0.00% 0 Oil and Gas extraction

    0 Petroleum and Gas products

    The percent value here will be used 0 Petroleum Refining

    c. Percent that will be used = 15.00% 0 Plastic and Rubber products

    0 Primary Metals

    0 Printing, Pub, allied

    0 Textiles, Apparel, Leather Goods

    0 Transportation equipment

    0 Wood products, Pulp, Paper

    0 Other

    100.00% Industry fractions should add

  • 7/29/2019 Industrial Buildings Score Card

    5/16

    is needed.

    acilities Energyat is facilities energy

    16% 0.00%

    8% 0.00%

    3% 0.00%

    0% 0.00%

    40% 0.00%

    8% 0.00%

    19% 0.00%

    15% 15.00%

    15% 0.00%

    16% 0.00%

    8% 0.00%

    35% 0.00%

    7% 0.00%0% 0.00%

    16% 0.00%

    16% 0.00%

    16% 0.00%

    8% 0.00%

    16% 0.00%

    16% 0.00%

    16% 0.00%

    22% 0.00%

    29% 0.00%

    7% 0.00%

    16% 0.00%

    o 100%. 15.00%

  • 7/29/2019 Industrial Buildings Score Card

    6/16

    BUILDINGS Part 2

    Energy Estimate and Buildings EnergyBuildings Energy Measures Score Card version 1.1

    This tool needs an estimate of annual buildings electricity use and fuel/steam use.

    So this sheet indicates what the estimate will be and allows changes.

    Enter for: TOTAL SITE, all energy, including process

    ACTUAL or Electricity Fuel/SteamESTIMATE kWh/yr Million Btu/yr

    Use a fuel 20,000,000 100,000calculator, if

    available, to derive Electricity Fuel/Steamthese values $/yr $/yr

    $1,600,000 $700,000

    CALCULATED Electricity Fuel/Steam

    BUILDINGS ENERGY kWh/yr Million Btu/yr based on item 'c' on 3,000,000 15,000PctFac sheet

    Electricity Fuel/Steam$/yr $/yr

    $240,000 $105,000

    ADJUSTBUILDINGS ENERGY

    if needed Electricity Fuel/SteamPercent of calculated: 100% 100%

    kWh/yr Million Btu/yr

    values here will be used: 3,000,000 15,000

    Electricity Fuel/SteamPercent of calculated: 100% 100%

    $/yr $/yr

    values here will be used: $240,000 $105,000

    for total site applicable to buildings being surveyed

    Energy Use Adjustment

  • 7/29/2019 Industrial Buildings Score Card

    7/16

    BUILDINGS Part 3

    Energy End-Use and Maximum Savings Percent BreakoutsBuildings Energy Measures Score Card version 1.1

    DEFAULT energy end-use percentages can be changed here if needed \/

    If you need to change the end-use percent breakouts, change values in columns 'B' and 'C'

    If you need to change the maximum percent savings, change values in columns 'D' and 'E'

    SPECIFY end-use energy savings percentages of Buildings Energy as appropriate

    The Max percents in columns 'D' and 'E' are the MAXIMUM COMPOSITE percents for

    each system area representative of typical maximum percents for a range of buildings,

    if ALL reasonable energy measures related to the specific system could be installed.

    (reasonable means up to 10-yr simple payback period)

    Column 'B' Column 'C' Column 'D' Column 'E' Column 'F' Column 'G'

    Electricity Fuel/Steam Electricity Fuel/Steam Electricity Fuel/Steam(%) (%) (%) (%) (%) (%)

    Envelopes 5% 17% 30% 30% 2% 5%

    Lighting 30% 0% 60% 0% 18% 0%

    Space Conditioning 30% 70% 50% 50% 15% 35%

    Ventilation 20% 10% 30% 30% 6% 3%

    Miscellaneous 15% 3% 0% 100% 0% 3%SUM 100% 100% 41% 46%

    The sum of columns B and C should be 100%

    If significant daylighting opportunities exist, the max percent electricity savingsin column 'D' under Lighting may need to be increasedFuel/Steam domestic hot water energy would be entered under misc if neededIf process heat recovery for space heating is considered possible, increase thethe column 'E' percentage Fuel/Steam value under "space conditioning" to 70%If process heat recovery for domestic water heating is considered possible,increase the column 'B' percentage Fuel/Steam value under "misc" to 3%, and

    increase the column 'E' percentage Fuel/Steam value under "misc" to 100%, or

    choose another combination that appears appropriate.

    Buildings energy breakout

    percents by system type

    (miscellaneous iseverything else)

    Maximum composite

    percent savings

    considered achievable if

    all measures from a range

    of buildings could be

    installed (do not change

    unless you are sure)

    Max percent Result for

    Buildings Energy

    Facility End-Use

  • 7/29/2019 Industrial Buildings Score Card

    8/16

    BUILDINGS Part 4

    Scorecard Questions, higher means more savings potentialBuildings Energy Measures Score Card version 1.1

    YES = '1' for this sheet The example responses here should be changed

    enter percents as percents, not fractions to represent your buildings.required YOUR YOUR MAX

    response Response POTENTIAL POTENTIAL

    E1

    Enter percent of total building wall and

    roof/attic areas of all heated and/or cooled

    buildings that could have insulation (or

    additional insulation) added?

    percent 50 25 50

    E2

    Could large unsealed openings or broken

    windows in walls or roofs be sealed or

    re aired?

    1 / 0 for

    yes/no1 20 20

    E3

    Could other major air leakage paths in a

    significant fraction of buildings or facilities

    be sealed?

    1 / 0 for

    yes/no0 10

    E4Could large expanses of glass that are not

    needed be insulated?

    1 / 0 for

    yes/no0 10

    E5

    Could large loading dock building sections

    that do not have air sealing to limit air

    infiltration have air sealing installed?

    1 / 0 for

    yes/no0 5

    E6

    In buildings with air conditioning, could

    large window or glazing sections that allow

    excessive solar heat to enter be covered or

    insulated?

    1 / 0 for

    yes/no0 5

    TOTAL 45.00

    required YOUR YOUR MAX

    response Response POTENTIAL POTENTIAL

    L1

    If a large amount of daylight is presently

    provided in most spaces, could electric

    lighting be dimmed in response if not

    already?

    1 / 0 for

    yes/no0 15

    L2

    What percent of total floor area is lit by older

    fluorescent (T12) or incandescent lighting

    that could be retrofit to T8?

    percent 75 18.75 25

    L3

    What percent of total floor area has lighting

    left on all the time or most of the time when

    little or no activity is occurring? Or lights

    cannot be turned off due to lack of

    switchin ?

    percent 75 37.5 50

    L4

    What percent of indoor lighting could be

    reduced by removing lamps? Or what

    percent could have task lighting installed and

    overhead li hts be ke t off?

    percent 0 25

    L5

    Could use of outdoor lighting be reduced?

    And could outdoor lighting be switched to

    fluorescent with motion sensor control?

    1 / 0 for

    yes/no0 10

    L6

    Can high-bay lighting be switched to

    fluorescent with motion sensor control or

    can fixtures be lowered and wattage

    reduced?

    1 / 0 for

    yes/no0 10

    TOTAL 56.25

    required YOUR YOUR MAX

    response Response POTENTIAL POTENTIAL

    The total percent of L2

    not exceed 100

    The responses for L2 and L4 are mutually exclusive

    and should not exceed 100. So choose either one or

    the other, or split the percents.

    Building Envelopes / Infiltration

    e responses e ow app y on y obuildings or facilities that are heated and/or

    cooled.

    Lighting / Daylighting

    All the responses below apply mainly to

    buildings or facilities that are significantly lit

    by electric lighting.

    Space Conditioning

  • 7/29/2019 Industrial Buildings Score Card

    9/16

    HC1

    Enter percent of total building floor areas of

    all heated and/or cooled buildings that do

    not reduce space conditioning during periods

    of low occupancy or non-work hours now,

    but could do so?

    percent 70 14 20

    HC2

    Enter percent of total building floor areas of

    all heated and/or cooled buildings that heat

    and cool air supply at the same time

    (simulataneous heating and cooling fighting

    each other), that could have this energy-

    wastin situation corrected?

    percent 25 7.48502994 30

    HC3

    If boilers or boiler heat supply could be shut

    off to building systems during mild and hot

    weather -- OR if process heat recovery could

    supply some space heating, and this is not

    currently done, could either shutoff orheat

    recovery be implemented?

    1 / 0 for

    yes/no0 15

    HC4 If too much air is supplied for heating andcooling, could this flow be reduced?

    1 / 0 foryes/no

    0 15

    HC5

    If there are significant building areas that are

    heated and/or cooled that do not need to be

    conditioned, could space conditioning be

    turned off or disconnected in these areas?

    1 / 0 for

    yes/no0 15

    HC6If excess heating or cooling is provided for

    any reason, could the excess be reduced?

    1 / 0 for

    yes/no1 5 5

    TOTAL 26.49

    required YOUR YOUR MAX

    response Response POTENTIAL POTENTIAL

    V1

    If makeup air or exhaust systems are

    operating at a static pressure higher than

    needed to provide required functionality,

    could static pressure be reduced?

    1 / 0 for

    yes/no0 20

    V2

    If makeup air or exhaust systems are

    operating at flow rates higher than needed to

    provide required functionality, could flow

    rates be reduced?

    1 / 0 for

    yes/no0 40

    V3

    If excessive outdoor air for ventilation, based

    on CO2 readings, is provided for human

    occupancy in non-process areas (see chart

    for CO2 readings), could the excess outdoor

    air be reduced?

    1 / 0 for

    yes/no0 20

    V4

    If air over 150 F is exhausted to atmosphere

    with no heat recovery, could heat be

    recovered for useful purposes?

    1 / 0 for

    yes/no0 10

    V5

    Could enthalpy wheels, heat pipes, or other

    devices be used to recover total enthalpy in

    exhaust air flows?

    1 / 0 for

    yes/no0 10

    TOTAL 0.00

    required YOUR YOUR MAX

    response Response POTENTIAL POTENTIAL

    W1

    Can process heat recovery be used to heat

    domestic hot water? Enter the percent of

    domestic hot water that could be heated.

    percent 50 50 100

    TOTAL 50.00

    Miscellaneous hot water

    All the responses below apply to ventilation

    provided by building space conditioning, makeup

    air, aor exhaust systems.

    All the responses below apply mainly to buildings

    or facilities that are significantly heated and/or

    cooled, and do not include mopajor ventilation

    systems or envelope effects (handled under other

    categories).

    Ventilation

  • 7/29/2019 Industrial Buildings Score Card

    10/16

    BUILDINGS Part 5

    RESULTSBuildings Energy Measures Score Card version 1.1

    Nothng can be changed on this sheet.

    Estimated Buildings Energy Savings Potentials

    Buildings Energy System

    Scorecard

    Potential

    out of 100

    Electricity Fuel/Steam Electricity

    kWh/yr Million Btu/yr $/yr

    Envelopes 45 20,250 344 $1,620

    Lighting 56 303,750 0 $24,300

    Space Conditioning 26 119,183 1,390 $9,535

    Ventilation 0 0 0 $0

    Miscellaneous (incl hot water) 50 0 225 $0TOTAL 443,183 1,960 $35,455

  • 7/29/2019 Industrial Buildings Score Card

    11/16

    Fuel/Steam

    $/yr

    $2,410

    $0

    $9,733

    $0

    $1,575$13,718

  • 7/29/2019 Industrial Buildings Score Card

    12/16

    Buildings Energy Measures Score Card version 1.1

    SCOPE The buildings score card addresses the potential energy savings of building energy

    systems found at industrial sites in four major categories of envelope / infiltration,

    lighting, space conditioning, and ventilation. Users can obtain savings estimates for

    any or all of the four major system types.

    APPROACH The approach differs from the typical Best Practice view of scoring how good things

    are, since best practice energy systems in buildings have been found to be very poor

    too often. This situation occurs because building systems are complicated and

    people find surprisingly many ways to make systems not work properly. In addition,

    because most people are unaware of how best practice systems can become very

    poor in actual use, they would often be unable to answer correctly how "good" their

    systems are. So the Score Card instead asks users to identify major potential areas

    for improvement, based on typical measures found in industrial plants by the IAC

    program.

    The Buildings Systems Score Card will help users to:

    a) Develop a greater awareness of potential building energy measures;

    b) Identify possible major categories of building system measures to reduce

    energy costs;

    c) Provide users with rough estimates of total energy savings for each system type

    and the total for all four types.

    AUDIENCE FOR THE TOOL The audience for this tool is facility managers or facility energy managers for

    industrial plants.

    HOW TO USE BUILDINGS SCORE

    CARD

    Users enter the answers to the questions for each energy system type. The answers

    to the questions generate scores that are applied to the facilities energy percentagesdeveloped by the Industrial Technolgies Program for specific industies (see second

    followin sheet < PeuPct> .

    RESULTS Results of the Score Card are presented for each of the four major energy systems

    and a total. The savings potentials are given both in energy units and dollars for the

    energy categories of Electricity and Fuel Use/Steam.

    MAXIMUM SAVINGS POTENTIAL

    METHODOLOGY

    The calculations in this version use a fixed maximum percentage possible savings

    for each of the four major system types by energy category of electricity and

    fuel/steam. This percentage is now fixed for all industries, and extensive analysis is

    expected to be needed to develop these values for each industry individually.

    DOCUMENTATION

    PURPOSE OF THE BUILDINGS

    SCORE CARD

  • 7/29/2019 Industrial Buildings Score Card

    13/16

    required scored MAX YOUR

    response response POTENTIAL POTENTIAL

    E

    E1

    percent entered of total building wall and

    roof/attic areas of all heated and/or cooled

    buildings that could have insulation (or

    additional insulation) added?

    percentpercent

    entered50 D/2

    E2

    Could large unsealed openings or broken

    windows in walls or roofs be sealed or

    repaired?

    yes/no 1 20 zero or E

    E3

    Could other major air leakage paths in a

    significant fraction of buildings or facilities

    be sealed?

    yes/no 1 10 zero or E

    E4Could large expanses of glass that are not

    needed be insulated?yes/no 1 10 zero or E

    E5

    Could large loading dock building sections

    that do not have air sealing to limit airinfiltration have air sealing installed?

    yes/no 1 5 zero or E

    E6

    In buildings with air conditioning, could

    large window or glazing sections that allow

    excessive solar heat to enter be covered or

    insulated?

    yes/no 1 5 zero or E

    100

    required scored MAX YOUR

    response response POTENTIAL POTENTIAL

    L1

    If significant daylight is presently available

    in most spaces, could electric lighting be

    dimmed in response if not already?

    yes/no 1 15 zero or E

    L2

    What percent of total floor area is lit by older

    fluorescent (T12) or incandescent lighting

    that could be retrofit to T8?

    percentpercent

    entered25 D/4

    L2 and L4 are mutually exclusive, so

    users should typically not score both

    at the same time.

    Buildings Score Card Factors

    Building Envelopes / Infiltratione responses e ow app y on y o

    buildings or facilities that are heated and/or

    cooled.

    Lighting / Daylighting

    All the responses below apply mainly to

    buildings or facilities that are significantly lit

    by electric lighting.

  • 7/29/2019 Industrial Buildings Score Card

    14/16

    L3

    What percent of total floor area has lighting

    left on all the time or most of the time when

    little or no activity is occurring? Or lights

    cannot be turned off due to lack of

    switchin ?

    percentpercent

    entered50 D/2

    L4

    What percent of indoor lighting could be

    reduced by removing lamps? Or what

    percent could have task lighting installed andoverhead li hts be ke t off?

    percentpercent

    entered

    25 D/4

    L5

    Could use of outdoor lighting be reduced?

    And could outdoor lighting be switched to

    fluorescent with motion sensor control?

    yes/no 1 10 zero or E

    L6

    Can high-bay lighting be switched to

    fluorescent with motion sensor control or can

    fixtures be lowered and wattage reduced?

    yes/no 1 10 zero or E

    125

    required scored MAX YOUR

    response response POTENTIAL POTENTIAL

    HC1

    percent entered of total building floor areas

    of all heated and/or cooled buildings that do

    not reduce space conditioning during periods

    of low occupancy or non-work hours now,

    but could do so?

    percentpercent

    entered20 D/5

    HC2

    percent entered of total building floor areas

    of all heated and/or cooled buildings that heat

    and cool air supply at the same time

    (simulataneous heating and cooling fighting

    each other), that could have this energy-wasting situation corrected?

    percentpercent

    entered30 D/3.34

    HC3

    If boilers or boiler heat supply could be shut

    off to building systems during mild and hot

    weather, and this is not currently done, could

    this shutoff be implemented?

    yes/no 1 15 zero or E

    HC4If too much air is supplied for heating and

    cooling, could this flow be reduced?yes/no 1 15 zero or E

    So the scores for L2 and L4 are the

    same and the score total is 125

    instead of 100.

    Space Conditioning

    All the responses below apply mainly to buildings

    or facilities that are significantly heated and/orcooled, and do not include mopajor ventilation

    systems or envelope effects (handled under other

    categories).

  • 7/29/2019 Industrial Buildings Score Card

    15/16

    HC5

    If there are significant building areas that are

    heated and/or cooled that do not need to be

    conditioned, could space conditioning be

    turned off or disconnected in these areas?

    yes/no 1 15 zero or E

    HC6If excess heating or cooling is provided for

    any reason, could the excess be reduced?yes/no 1 5 zero or E

    100

    required scored MAX YOUR

    response response POTENTIAL POTENTIAL

    V1

    If makeup air or exhaust systems are

    operating at a static pressure higher than

    needed to provide required functionality,

    could static ressure be reduced?

    yes/no 1 20 zero or E

    V2

    If makeup air or exhaust systems are

    operating at flow rates higher than needed to

    provide required functionality, could flowrates be reduced?

    yes/no 1 40 zero or E

    V3

    If excessive outdoor air for ventilation, based

    on CO2 readings, is provided for human

    occupancy in non-process areas (see chart for

    CO2 readings), could the excess outdoor air

    be reduced?

    yes/no 1 20 zero or E

    V4

    If air over 150 F is exhausted to atmosphere

    with no heat recovery, could heat be

    recovered for useful ur oses?

    yes/no 1 10 zero or E

    V5

    Could enthalpy wheels, heat pipes, or other

    devices be used to recover total enthalpy in

    exhaust air flows?

    yes/no 1 10 zero or E

    100

    required scored MAX YOURresponse response POTENTIAL POTENTIAL

    W1

    Can process heat recovery be used to heat

    domestic hot water? Enter the percent of

    domestic hot water that could be heated.

    percentpercent

    entered100 zero or E

    Miscellaneous hot water

    Ventilation

    All the responses below apply to ventilation

    provided by building space conditioning, makeup

    air, aor exhaust systems.

  • 7/29/2019 Industrial Buildings Score Card

    16/16

    Quick-PEP default percentages for facility energy use

    Electricity Fuel/SteamIndustry (%) (%)

    Ag, Forestry, Fishing 16% 5%

    Chemical 8% 2%Aluminum / Alumina 3% 3%

    Cement 0% 0%

    Computers, Elec, Appl 40% 30%

    EAF Steel 8% 4%Fab Metal Prod 19% 20%

    Food, Bev, tobacco 15% 5%

    Foundries 15% 14%Furniture and related 16% 5%

    Glass and glass products 8% 3%

    Heavy machinery 35% 51%Integrated Steel 7% 2%

    Mining (except oil and gas) 0% 0%

    Non-metallic mineral products 16% 5%Oil and Gas extraction 16% 5%

    Petroleum and Gas products 16% 5%

    Petroleum Refining 8% 1%Plastic and Rubber products 16% 14%

    Primary Metals 16% 5%Printing, Pub, allied 16% 5%Textiles, Apparel, Leather Goods 22% 7%

    Transportation equipment 29% 38%

    Wood products, Pulp, Paper 7% 1%Other 16% 5%