industrial control & monitoring products - diytrade - largest
TRANSCRIPT
Industrial Control &Monitoring Products
Alternating Relays
Time Delay Relays
Phase Monitor Relays
Voltage Monitor Relays
Current Monitor Relays
2
Who Uses Our Controls?A wide variety of challenges can be metby using our products. Our customerbase includes OEM’s who specifyMacromatic controls in their equipment,and end users who count on Macromaticprecision and reliability for their ownapplications. Our products are used in avariety of industries such as machinetool, automotive, material handling, pulp& paper, food & beverage,transportation, communications, water/wastewater and HVAC, among many.
Where to Buy?We are pleased to offer our completeline of products in the United States andCanada through a network of Preferred MacromaticDistributors. We have partners with national, regionaland local presence who stock and sell our products.Call us or visit us on the web to locate a distributor orsales representative near you.
Need Technical Help? Have Special Applications?Do you need help selecting or applying one of ourproducts? Don’t quite know what you need? Ourteam of engineers and technical advisors is availableto help you address your specific needs. Whether byhelping you decide which time delay relay function isrequired in your application or working with you ondesigning custom-engineered solutions for yourparticular need, we have the experience to help youone-on-one. Don’t hesitate to call us to discuss yourparticular application.
Why Choose Macromatic Controls?Long known for their precision and reliability,Macromatic products are increasingly the choice ofindustrial design engineers for use in new equipmentand are preferred by maintenance personnel asquality replacements in existing applications. We testeach product twice before it is shipped, and allproducts have an extensive warranty period longer
than most other manufacturers (contact Macromaticfor further details). Most standard and custom designproducts are UL recognized or listed and CSAapproved. We have obtained UL Listing on our plug-in products when used with our sockets. Manyproducts now carry the CE Mark.
What You Need, When You Need ItDon’t wait for something you need now. Macromaticoffers prompt delivery of standard products and caneven deliver many non-standard orders within sevento ten days, all without any special expediting feescharged by many manufacturers. We are dedicatedto being responsive, and that means you get what youneed when you need it, not weeks or months fromnow. Contact us or one of our Preferred Distributorsor Sales Representatives and we will provide you withan on-time solution.
Want to Learn More?You can reach us at 800-238-7474 or e-mail us [email protected]. Our customer serviceand technical assistance people are ready to help withyour questions or special needs. Or you can visit usat www.macromatic.com.
Your Choice for Industrial Controls
For 30 years, Macromatic has been producing industrial control & monitoring products. All are engineered andmanufactured in our U.S.-based facility in Menomonee Falls, Wisconsin (a Milwaukee suburb), utilizing a time-proven quality system to produce products that consistently meet your requirements for function, availability &value.
3
Since we continuously strive to improve and update our product offering, specifications are subject to change without notice.
“Macromatic” & “Time Ranger” are Registered Tradenames of Macromatic Controls LLC
Product Index
Index by Product Number .............................................................................................. 4
Phase Monitor RelaysProduct Summary ...................................................................................................... 5PCP Series Phase Reversal ....................................................................................... 6-7PLP Series Phase Loss & Phase Reversal ................................................................. 8-9PAP Series Phase Loss, Phase Reversal & Undervoltage .......................................... 10-11PMP Series Phase Loss, Phase Reversal, Phase Unbalance,
Undervoltage & Overvoltage ........................................................................... 12-13PMD Series Phase Loss, Phase Reversal, Phase Unbalance,
Undervoltage & Overvoltage ........................................................................... 14-15
Current Monitor Relays NEWProduct Summary ...................................................................................................... 17CM Series Standard ................................................................................................... 18-19CO Series Overcurrent ............................................................................................... 20-21CU Series Undercurrent ............................................................................................. 22-23
Voltage Monitor Relays NEWProduct Summary ...................................................................................................... 24VM Series Over/Under Voltage (Fixed Time Delay on Drop-Out) ................................ 25, 27VA Series Over/Under Voltage (Adjustable Time Delay on Drop-Out) ......................... 26-27VW Series Voltage Band (Window) ............................................................................ 28-29
Time Delay RelaysProduct Summary ...................................................................................................... 30-31Definition of Timing Functions .................................................................................... 32-33TR-5 Series Non-Programmable DPDT ..................................................................... 34-37TR-5 Series Non-Programmable 8 Pin SPDT............................................................. 38-39TR-6 Series Time Ranger Programmable Multi-Range .............................................. 40-43SS-6 & -8 Series Compact Non-Programmable .......................................................... 44SS-4 Series Non-Programmable with Quick Connect Terminals ................................. 45TD-7 Series Time Ranger Digital-Set Programmable ................................................. 46-47981 Series Time Ranger III Digital-Set Multi-Function Multi-Range ............................ 48-49Standard Modifications ............................................................................................... 50-51
Alternating RelaysFor 1 Switch Applications (SPDT& DPDT) .................................................................. 52-53For 2 Switch Applications (DPDT Cross-Wired) .......................................................... 54-55For 3 Switch Applications ........................................................................................... 56-57
Sockets & Accessories ................................................................................................... 16 & 58
4
Index By Product Number
70100 16 & 5870166 16 & 5870169-D 16 & 5870170-D 16 & 5870171-D 16 & 5870200 16 & 5870300 4870310 4870320 489816U1 48ARP012A2 52ARP012A2R 52ARP012A3 54ARP012A3R 54ARP012A6 52ARP012A6R 52ARP012A8 56ARP012A8R 56ARP024A2 52ARP024A2R 52ARP024A3 54ARP024A3R 54ARP024A6 52ARP024A6R 52ARP024A8 56ARP024A8R 56ARP120A2 52ARP120A2R 52ARP120A3 54ARP120A3R 54ARP120A6 52ARP120A6R 52ARP120A8 56ARP120A8R 56ARP240A2 52ARP240A2R 52ARP240A3 54ARP240A3R 54ARP240A6 52ARP240A6R 52ARP240A8 56ARP240A8R 56CMKP01A22 18CMKP01A28 18CMKP01A62 18CMKP01A68 18CMKP05A22 18CMKP05A28 18CMKP05A62 18CMKP05A68 18CMKP10A22 18CMKP10A28 18CMKP10A62 18CMKP10A68 18CMP01A22 18CMP01A28 18CMP01A62 18CMP01A68 18CMP05A22 18CMP05A28 18CMP05A62 18CMP05A68 18CMP10A22 18CMP10A28 18CMP10A62 18CMP10A68 18COKP01A22 20COKP01A28 20COKP01A62 20COKP01A68 20COKP05A22 20
COKP05A28 20COKP05A62 20COKP05A68 20COKP10A22 20COKP10A28 20COKP10A62 20COKP10A68 20COP01A22 20COP01A28 20COP01A62 20COP01A68 20COP05A22 20COP05A28 20COP05A62 20COP05A68 20COP10A22 20COP10A28 20COP10A62 20COP10A68 20CUP01A22 22CUP01A28 22CUP01A62 22CUP01A68 22CUP05A22 22CUP05A28 22CUP05A62 22CUP05A68 22CUP10A22 22CUP10A28 22CUP10A62 22CUP10A68 22PAP120 10PAP208 10PAP240 10PAP400 10PAP480 10PCP1 6PCP2 6PLP120 8PLP208 8PLP240 8PLP400 8PLP480 8PMD120 14PMD208 **PMD240 **PMD400 **PMD480 **PMD600 14PMDU 14PMP120 12PMP208 **PMP240 **PMP480 **PMPU 12SS-3062-xx **SS-3066-xx **SS-3068-xx **SS-3162-xx **SS-3166-xx **SS-3168-xx **SS-3262-xx **SS-3266-xx **SS-3268-xx **SS-3362-xx **SS-3366-xx **SS-3368-xx **SS-3562-xx **SS-3566-xx **SS-3568-xx **SS-40222-xx 45
SS-40228-xx 45SS-41622-xx 45SS-41628-xx 45SS-6262-xx 44SS-6266-xx 44SS-6268-xx 44SS-70166 ***SS-8062-xx 44SS-8066-xx 44SS-8068-xx 44SS-8162-xx **SS-8166-xx **SS-8168-xx **SS-8562-xx 44SS-8566-xx 44SS-8568-xx 44SS-8762-xx 44SS-8766-xx 44SS-8768-xx 44TD-70221 46TD-70222 46TD-70226 46TD-70228 46TD-70521 46TD-70522 46TD-70526 46TD-70528 46TD-70821 46TD-70822 46TD-70826 46TD-70828 46TD-71521 46TD-71522 46TD-71526 46TD-71528 46TD-71621 46TD-71622 46TD-71626 46TD-71628 46TD-78121 46TD-78122 46TD-78126 46TD-78128 46TR-50221-xx 34TR-50222-xx 34TR-50226-xx 34TR-50228-xx 34TR-50521-xx 34TR-50522-xx 34TR-50526-xx 34TR-50528-xx 34TR-50821-xx 34TR-50822-xx 34TR-50826-xx 34TR-50828-xx 34TR-51321-xx 35TR-51322-xx 35TR-51326-xx 35TR-51328-xx 35TR-51361-xx 38TR-51362-xx 38TR-51366-xx 38TR-51368-xx 38TR-51521-xx 35TR-51522-xx 35TR-51526-xx 35TR-51528-xx 35TR-51561-xx 38TR-51562-xx 38TR-51566-xx 38TR-51568-xx 38
TR-51621-xx 35TR-51622-xx 35TR-51626-xx 35TR-51628-xx 35TR-51661-xx 38TR-51662-xx 38TR-51666-xx 38TR-51668-xx 38TR-51721-xx 35TR-51722-xx 35TR-51726-xx 35TR-51728-xx 35TR-51761-xx 38TR-51762-xx 38TR-51766-xx 38TR-51768-xx 38TR-51821-xx 35TR-51822-xx 35TR-51826-xx 35TR-51828-xx 35TR-51861-xx 38TR-51862-xx 38TR-51866-xx 38TR-51868-xx 38TR-51921-xx 35TR-51922-xx 35TR-51926-xx 35TR-51928-xx 35TR-51961-xx 38TR-51962-xx 38TR-51966-xx 38TR-51968-xx 38TR-53121-xx 36TR-53122-xx 36TR-53126-xx 36TR-53128-xx 36TR-55121-xx 36TR-55122-xx 36TR-55126-xx 36TR-55128-xx 36TR-56121-xx 36TR-56122-xx 36TR-56126-xx 36TR-56128-xx 36TR-56521-xx 36TR-56522-xx 36TR-56526-xx 36TR-56528-xx 36TR-60221 40TR-60222 40TR-60226 40TR-60228 40TR-60521 40TR-60522 40TR-60526 40TR-60528 40TR-60821 40TR-60822 40TR-60826 40TR-60828 40TR-61321 41TR-61322 41TR-61326 41TR-61328 41TR-61521 41TR-61522 41TR-61526 41TR-61528 41TR-61621 41TR-61622 41TR-61626 41
Product * PageTR-61628 41TR-61721 41TR-61722 41TR-61726 41TR-61728 41TR-61821 41TR-61822 41TR-61826 41TR-61828 41TR-61921 41TR-61922 41TR-61926 41TR-61928 41TR-63121 42TR-63122 42TR-63126 42TR-63128 42TR-65121 42TR-65122 42TR-65126 42TR-65128 42TR-66121 42TR-66122 42TR-66126 42TR-66128 42TR-66521 42TR-66522 42TR-66526 42TR-66528 42TR-68129 **TR-68169 **VAKP012D 26VAKP024A 26VAKP024D 26VAKP048D 26VAKP110D 26VAKP120A 26VAP012D 26VAP024A 26VAP024D 26VAP048D 26VAP110D 26VAP120A 26VMKP012D 25VMKP024A 25VMKP024D 25VMKP048D 25VMKP110D 25VMKP120A 25VMP012D 25VMP024A 25VMP024D 25VMP048D 25VMP110D 25VMP120A 25VWKP012D 28VWKP024A 28VWKP024D 28VWKP048D 28VWKP110D 28VWKP120A 28VWP012D 28VWP024A 28VWP024D 28VWP048D 28VWP110D 28VWP120A 28
* The “-xx” suffix denotes the time range for non-programmable time delay relays. ** Contact Macromatic for more information.
Product * PageProduct * PageProduct * PageProduct * Page
5
Typical Connections
Load Side MonitoringWith the relay connected directly to the motor, the total feedlines are monitored. This connection should not be used withreversing motors.
Depending on the unit selected, it will protect three phaseequipment against:u phase loss - total loss of one or more of the three
phases. Also known as "single phasing." Typicallycaused by a blown fuse, broken wire, or worn con-tact. This condition would result in a motor drawinglocked rotor current during start-up. In addition, athree phase motor will continue to run after losing aphase, resulting in possible motor burn-out.
u phase reversal - reversing any two of the threephases will cause a three phase motor to run in theopposite direction. This may cause damage to drivenmachinery or injury to personnel. The conditionusually occurs as a result of mistakes made duringroutine maintenance or when modifications are madeto the circuit.
u phase unbalance - unbalance of a three phasesystem occurs when single phase loads are con-nected such that one or two of the lines (phases)carry more or less of the load. This could causemotors to run at temperatures above publishedratings.
u undervoltage - when voltage in all three lines of athree phase system drop simultaneously.
u overvoltage - when voltage in all three lines of athree phase system increase simultaneously.
Protection
Line Side MonitoringWith the relay connected before the motor starter, the motorcan be started in the reverse direction. However, the motor isunprotected against phase failures between the relay and themotor.
Phase Monitor Relays provide protection against premature equipment failure caused by voltage faults on 3 Phasesystems. All Macromatic Phase Monitor Relays are designed to be compatible with most Wye or Delta systems. InWye systems, a connection to a neutral is not required. Phase Monitor Relays protect against single phasing regard-less of any regenerative voltages.
The Reference Guide below provides general information on the different versions of Phase Monitor Relays offered byMacromatic (see Product Selection on the following pages for further details):
* In addition to the above approvals, all Plug-in Products are also UL Listed when used with the appropriate Macromatic socket.
PHASE MONITOR RELAYSProduct Summary
Series MountingStyle
PhaseLoss
PhaseReversal
PhaseUnbalance
UnderVoltage
OverVoltage
Time Delay onUndervoltage Approvals * See
Page
PCP Plug-in * P 6
PLP Plug-in * P P 8
PAP Plug-in * P P P (adj.) 50ms fixed 10
PMP Plug-in * P P P P (adj.) P (fixed) 0.1 - 20 sec. 12
PMD Surface P P P P (adj.) P (fixed) 0.1 - 20 sec. 14
6
PHASE MONITOR RELAYSPhase Reversal OnlyPCP Series Plug-in
u Protects against phasereversal
u One version works on 208-480V 3 Phase Systems
u LED indicates both normaland fault conditions
u Compact plug-in caseutilizing industry-standard8 pin octal socket
u 10A SPDT output contacts
u
The PCP Series Phase Monitor Relays provide protection against phase reversal ina compact plug-in design. One version will work on any 3 phase system from 208Vto 480V (a separate 120V-only version is also available). These devices aredesigned to be compatible with most Wye or Delta systems. In Wye systems, aconnection to a neutral is not required.
The relay is energized and the LED on when the sequence is correct. Any fault willde-energize the relay and turn off the LED. Re-energization is automatic uponcorrection of the fault condition.
* Requires a 600V-rated socket when used on system voltages greater than 300V.n See Page 16 for Sockets & Accessories
NOMINALMOUNTING VOLTAGE PRODUCT WIRING/
STYLE 50/60 Hz NUMBER SOCKETn
Plug-in 120V PCP1 8 Pin Octal70169-D
208-480V PCP2 *
(with appropriate socket)
DIAGRAM 23
7
PHASE MONITOR RELAYSPhase Reversal Only
PCP Series Plug-inApplication Data & Dimensions
Dimensions
Application Data
Phase Reversal:Unit trips if sequence of the three phases is anything other than A-B-C.
Output Contacts:10A SPDT @ 240V AC, 1/3HP @ 240V AC (N.O.), 1/6HP @ 240V AC (N.C.)
Life:Full Load: 100,000 operations
Response Times:Operate: 50msRelease: 50ms
Load (Burden):3VA
Temperature: -28o to 65oC (-20o to 150oF)
Transient Protection:10,000 volts for 20 microseconds
Mounting:Uses an 8 pin octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (MacromaticProduct Number 70169-D--see Page 16).
Indicator LED:Red LED on when all conditions are normal, and off when a fault condition has occurred.
Reset:Automatic upon correction of fault
Approvals:
File #E109466
2.9(74)
3.0(76)
1.7(43)
2.4 (60)
File #E109466
When used with Macromaticsocket 70169-D rated 600V
All Dimensions inInches (Millimeters)
8
PHASE MONITOR RELAYSPhase Loss & Phase ReversalPLP Series Plug-in
The PLP Series Phase Monitor Relays provide protection against phase loss &phase reversal in a compact plug-in design. These devices are designed to becompatible with most Wye or Delta systems. In Wye systems, a connection to aneutral is not required. Phase Monitor Relays protect against single phasingregardless of any regenerative voltages.
The relay is energized and the LED on when all three phases are present and inthe correct sequence. Any fault will instantaneously de-energize the relay and turnoff the LED. Re-energization is automatic upon correction of the fault condition.
* Requires a 600V-rated socket when used on system voltages greater than 300V.n See Page 16 for Sockets & Accessories
NOMINALMOUNTING VOLTAGE PRODUCT WIRING/
STYLE 50/60 Hz NUMBER SOCKETn
Plug-in 120V PLP120 8 Pin Octal70169-D
208V PLP208
240V PLP240
400V PLP400 *
480V PLP480 *
u Protects against phase loss& phase reversal
u LED indicates both normaland fault conditions
u Compact plug-in caseutilizing industry-standard8 pin octal socket
u 10A SPDT output contacts
u
DIAGRAM 23
(with appropriate socket)
9
PHASE MONITOR RELAYSPhase Loss & Phase Reversal
PLP Series Plug-inApplication Data & Dimensions
Dimensions
Application Data
Phase Loss:Unit trips on loss of any Phase A, B or C
Phase Reversal:Unit trips if sequence of the three phases is anything other than A-B-C.
Output Contacts:10A SPDT @ 240V AC, 1/3HP @ 240V AC (N.O.), 1/6HP @ 240V AC (N.C.)
Life:Full Load: 100,000 operations
Response Times:Operate: 50msRelease: 50ms
Load (Burden):3VA
Temperature: -28o to 65oC (-20o to 150oF)
Transient Protection:10,000 volts for 20 microseconds
Mounting:Uses an 8 pin octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (MacromaticProduct Number 70169-D--see Page 16).
Indicator LED:Red LED on when all conditions are normal, and off when a fault condition has occurred.
Reset:Automatic upon correction of fault
Approvals:
File #E109466File #E109466
When used with Macromaticsocket 70169-D rated 600V
2.9(74)
3.0(76)
1.7(43)
2.4 (60)
All Dimensions inInches (Millimeters)
10
PHASE MONITOR RELAYSPhase Loss, Phase Reversal & UndervoltagePAP Series Plug-in
The PAP Series Phase Monitor Relays provide protection against phase loss, phasereversal & undervoltage in a compact plug-in design. These devices are designedto be compatible with most Wye or Delta systems. In Wye systems, a connectionto a neutral is not required. Phase Monitor Relays protect against single phasingregardless of any regenerative voltages.
The relay is energized and the LED on when all three phase are present in thecorrect sequence at a voltage level above the undervoltage setting. The undervolt-age drop-out can be set at 75-95% of operating voltage. Any fault will instanta-neously de-energize the relay and turn off the LED. Re-energization is automaticupon correction of the fault condition.
* Requires a 600V-rated socket when used on system voltages greater than 300V.n See Page 16 for Sockets & Accessories
NOMINAL UNDER-MOUNTING VOLTAGE VOLTAGE PRODUCT WIRING/
STYLE 60 Hz RANGE NUMBER SOCKETn
Plug-in 120V 90-115V PAP120 8 Pin Octal70169-D
208V 156-198V PAP208
240V 180-230V PAP240
400V 300-380V PAP400 *
480V 360-460V PAP480 *
u Protects against phase loss,phase reversal & undervolt-age
u Undervoltage setting isadjustable from 75-95% ofnominal
u LED indicates both normaland fault conditions
u Compact plug-in caseutilizing industry-standard8 pin octal socket
u 10A SPDT output contacts
u
DIAGRAM 23
(with appropriate socket)
11
PHASE MONITOR RELAYSPhase Loss, Phase Reversal & Undervoltage
PAP Series Plug-inApplication Data & Dimensions
Dimensions
Application Data
All Dimensions inInches (Millimeters)
2.9(74)
3.5(89)
2.4 (60)
1.7(43)
Phase Loss:Unit trips on loss of any Phase A, B or C
Phase Reversal:Unit trips if sequence of the three phases is anything other than A-B-C.
Undervoltage:Adjustable over a range per product selection table. Unit trips when the average of all three lines is less than the adjusted setpoint.
Output Contacts:10A SPDT @ 240V AC, 1/3HP @ 240V AC (N.O.), 1/6HP @ 240V AC (N.C.)
Life:Full Load: 100,000 operations
Response Times:Operate: 50msRelease: 50ms
Load (Burden):3VA
Temperature: -28o to 65oC (-20o to 150oF)
Transient Protection:10,000 volts for 20 microseconds
Mounting:Uses an 8 pin octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (MacromaticProduct Number 70169-D--see Page 16).
Indicator LED:Red LED on when all conditions are normal, and off when a fault condition has occurred.
Reset:Automatic upon correction of fault
Approvals:File #E109466
File #E109466
When used with Macromaticsocket 70169-D rated 600V
12
u Universal voltage range of208-480V on PMPU providesthe flexibility to cover avariety of applications withone unit
u Protects against phase loss,phase reversal, phaseunbalance, undervoltage andovervoltage
u Variety of user-selectableand adjustable settings forthe ultimate in three-phaseprotection
u Automatic or Manual Reset
u Multi-Color LED indicatesnormal condition and definesfault to simplify troubleshoot-ing
u Compact plug-in caseutilizing industry-standard 8pin octal socket
u 10A SPDT output contacts
u
The PMP Series Phase Monitor Relays utilize a microprocessor-based design to provideprotection against phase loss, phase reversal, phase unbalance, undervoltage andovervoltage. The PMPU is a universal voltage product that works on any three-phasesystem voltage from 208-480V (a separate 120V version is available). These devices aredesigned to be compatible with most Wye or Delta systems. In Wye systems, a connectionto a neutral is not required. PMP Series products protect against unbalanced voltages orsingle phasing regardless of any regenerative voltages.
The relay is energized when the phase sequence and all voltages are correct. Any one offive fault conditions will de-energize the relay. As standard, re-energization is automaticupon correction of the fault condition. Manual reset is available if a momentary N.C. switchis wired to the appropriate terminals. A multi-color LED indicates normal condition and alsoprovides specific fault indication to simplify troubleshooting.
The PMP Series offers a variety of user-adjustable settings. The percent phase unbalanceis adjustable from 2-10%, and also has a “Disable” setting for those applications wherepoor voltage conditions could cause nuisance tripping. The undervoltage drop-out can beset at 80-95% of operating voltage (overvoltage setting is fixed at 110% of nominal). Theadjustable time delay drop-out on undervoltage (0.1-20 seconds) eliminates nuisancetripping caused by momentary voltage fluctuations. There is also an adjustable time delay(1-300 seconds) on both power up and restart after a fault has been cleared.
* Requires a 600V-rated socket when used on system voltages greater than 300V.n See Page 16 for Sockets & Accessories
OPERATINGMOUNTING VOLTAGE PRODUCT
STYLE 50/60 Hz NUMBER WIRING/SOCKET n
Plug-in 120V PMP120 8 Pin Octal70169-D
208-480V PMPU *
DIAGRAM 104
PHASE MONITOR RELAYSPhase Loss, Phase Reversal, PhaseUnbalance, and Under/Over VoltagePMP Series Plug-in
(with appropriate socket)
13
Hysteresis: 2 - 3%
Load (Burden): Less than 3VA
Temperature: -28o to 65oC (-20o to 150oF)
Mounting:Uses an 8 pin octal socket. Requires a 600V-rated socketwhen used on system voltages greater than 300V (MacromaticProduct Number 70169-D--see Page 16).
Indicator LED:
Reset:As standard, reset is automatic upon correction of fault. Whena momentary-contact N.C. switch is wired across the ManualReset terminals (6 & 7), the unit switches to manual resetmode and remote manual reset is available.
Approvals:
Phase Loss:Unit trips on loss of any Phase A, B or C.
Phase Reversal:Unit trips if rotation (sequence) of the three phases is anythingother than A-B-C.
Undervoltage:Adjustable from 80-95% of nominal voltage. Unit trips when theaverage of all three lines is less than the adjusted set point fora period longer than the adjustable time delay drop-out.
Overvoltage:Fixed at 110% of nominal voltage. Unit trips when the averageof all three lines is greater than the fixed set point for a periodlonger than the time delay drop-out.
Phase Unbalance:Adjustable from 2 - 10% unbalance. Unit trips when any one ofthe three lines deviates from the average of all three lines bymore than the adjusted set point . There is also a “Disable”setting adjustment that will turn off the Phase UnbalanceProtection if nuisance tripping is a problem.
Output Contacts:SPDT: 10A Resistive @ 240V AC/30V DC,1/2HP @ 120/240V AC
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Response Times:Power Up & Restart After Fault: 1 - 300 seconds adjustableDrop-out Due to Fault:
Phase Loss & Reversal 100ms fixedPhase Unbalance 2 seconds fixedUndervoltage 0.1 - 20 seconds adjustableOvervoltage Fixed Time Based on Inverse
Time Curve
PHASE MONITOR RELAYSPhase Loss, Phase Reversal, Phase
Unbalance, and Under/Over VoltagePMP Series Plug-in
Application Data & Dimensions
Application Data
Dimensions
1.7(43)
2.9(74)
3.0(77)
2.4(60)
Low Voltage & EMC DirectivesEN60947-1, EN60947-5-1
File #E109466
When used with Macromaticsocket 70169-D rated 600V
File #E109466
All Dimensions inInches (Millimeters)
LED Status Indicator
Green Steady Normal / Relay ON
Green Flashing Power Up / Restart Delay
Red Steady Unbalance
Red Flashing Undervoltage / Overvoltage
Amber Steady Reversal
Amber Flashing Loss
Green / Red Alternating Undervoltage / OvervoltageTrip Pending
Red / Amber Alternating Nominal Voltage Set Error* Applies to 208-480V units only.
*
14
u Universal voltage range of208-480V on PMDU pro-vides the flexibility to cover avariety of applications withone unit
u Protects against phase loss,phase reversal, phaseunbalance, undervoltage andovervoltage
u Variety of user-selectableand adjustable settings forthe ultimate in three-phaseprotection
u Automatic or Manual Reset
u Multi-Color LED indicatesnormal condition and definesfault to simplify troubleshoot-ing
u 45mm DIN-style surface-mount case
u 10A SPDT & SPNC outputcontacts
u
The PMD Series Phase Monitor Relays utilize a microprocessor-based design to provideprotection against phase loss, phase reversal, phase unbalance, undervoltage andovervoltage. The PMDU is a universal voltage product that works on any three-phasesystem voltage from 208-480V (separate 120V & 575V versions are available). Thesedevices are designed to be compatible with most Wye or Delta systems. In Wye systems,a connection to a neutral is not required. PMD Series products protect against unbalancedvoltages or single phasing regardless of any regenerative voltages.
The relay is energized when the phase sequence and all voltages are correct. Any one offive fault conditions will de-energize the relay. As standard, re-energization is automaticupon correction of the fault condition. Manual reset is available if a momentary N.C. switchis wired to the appropriate terminals. A multi-color LED indicates normal condition and alsoprovides specific fault indication to simplify troubleshooting.
The PMD Series offers a variety of user-adjustable settings. The percent phase unbalanceis adjustable from 2-10%, and also has a “Disable” setting for those applications wherepoor voltage conditions could cause nuisance tripping. The undervoltage drop-out can beset at 80-95% of operating voltage (overvoltage setting is fixed at 110% of nominal). Theadjustable time delay drop-out on undervoltage (0.1-20 seconds) eliminates nuisancetripping caused by momentary voltage fluctuations. There is also an adjustable time delay(1-300 seconds) on both power up and restart after a fault has been cleared.
u To order PMD units with a second N.O. contact instead of the N.C. (terminals 21-22),add a suffix “-A1” to the Product Number, i.e., PMDU-A1. To order PMD units withDPDT output contacts instead of one SPDT and one SPNC, but with no manual resetfeature, add a suffix “-A2” to the Product Number, i.e., PMDU-A2.
n See Page 16 for Accessories
OPERATINGMOUNTING VOLTAGE PRODUCT
STYLE 50/60 Hz NUMBER u WIRING nSurface-Mount 120V PMD120
208-480V PMDU
575V PMD600
DIAGRAM 105
PHASE MONITOR RELAYSPhase Loss, Phase Reversal, PhaseUnbalance, and Under/Over VoltagePMD Series Surface-Mount
15
Hysteresis: 2 - 3%
Load (burden): Less than 3VA
Temperature: -28o to 65oC (-20o to 150oF)
Mounting:Does not require a socket. Can either be mounted directly on35mm DIN track with no additional parts or to a back-panelwith two screws.
Indicator LED:
Reset:As standard, reset is automatic upon correction of fault. Whena momentary-contact N.C. switch is wired across the ManualReset terminals (5 & 6), the unit switches to manual resetmode and remote manual reset is available.
Approvals:
Phase Loss:Unit trips on loss of any Phase A, B or C.
Phase Reversal:Unit trips if rotation (sequence) of the three phases is anythingother than A-B-C.
Undervoltage:Adjustable from 80-95% of nominal voltage. Unit trips when theaverage of all three lines is less than the adjusted set point fora period longer than the adjustable time delay drop-out.
Overvoltage:Fixed at 110% of nominal voltage. Unit trips when the averageof all three lines is greater than the fixed set point for a periodlonger than the time delay drop-out.
Phase Unbalance:Adjustable from 2 - 10% unbalance. Unit trips when any one ofthe three lines deviates from the average of all three lines bymore than the adjusted set point . There is also a “Disable”setting adjustment that will turn off the Phase UnbalanceProtection if nuisance tripping is a problem.
Output Contacts: SPDT & SPNCN.O.: 10A Resistive @ 240V AC/30V DC, 1/2HP @ 240V ACN.C.: 10A Resistive @ 240V AC/30V DC, 1/3HP @ 240 VAC
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Response Times:Power Up & Restart After Fault: 1 - 300 seconds adjustableDrop-out Due to Fault:
Phase Loss & Reversal 100ms fixedPhase Unbalance 2 seconds fixedUndervoltage 0.1 - 20 seconds adjustableOvervoltage Fixed Time Based on Inverse
Time Curve
PHASE MONITOR RELAYSPhase Loss, Phase Reversal, Phase
Unbalance, and Under/Over VoltagePMD Series Surface-Mount
Application Data & Dimensions
Application Data
Dimensions
File #E109466
Low Voltage & EMC DirectivesEN60947-1, EN60947-5-1
2.7(70)
1.4 (35)
2.4(60)
1.8 (45) 4.4 (112)4.3 (110)
TWO 0.2 (5) MOUNTING HOLES
All Dimensions inInches (Millimeters)
LED Status Indicator
Green Steady Normal / Relay ON
Green Flashing Power Up / Restart Delay
Red Steady Unbalance
Red Flashing Undervoltage / Overvoltage
Amber Steady Reversal
Amber Flashing Loss
Green / Red Alternating Undervoltage / OvervoltageTrip Pending
Red / Amber Alternating Nominal Voltage Set Error* Applies to 208-480V units only.
*
16
SOCKETS & ACCESSORIES
Other Accessories
Sockets
* Plug-in Three-Phase Monitor Relays require a 600V-rated socket when used on system voltages greater than 300V.
All Dimensions inInches (Millimeters)
Product Number70169-D *
Product Number70170-D
Product Number70171-D
Description 8 Pin Octal 11 Pin Octal 11 Pin Spade (Blade)
Ratings 10A @ 600V * 10A @ 300V 10A @ 300V
Mounting 35MM DIN Rail /Direct Panel
35MM DIN Rail /Direct Panel
35MM DIN Rail /Direct Panel
Wire/Terminations
1 or 2 #12-22 /Pressure Wire Clamps
1 or 2 #12-22 /Pressure Wire Clamps
1 or 2 #12-22 /Pressure Wire Clamps
Approvals
Dimensions
35mm DIN Mounting Track (1 Meter Section)
Product Number 70100Hold Down SpringProduct Number 70166
17
Without External CT With External CT
ApprovalsAll Macromatic plug-in Current Monitor Relays are UL Component Recognized. They are also UL Listed when usedwith the appropriate Macromatic socket.
Typical Installations
Pick-up Drop-out SeeType Series Setting Time Delay Setting Time Delay Page
Standard CMP Fixed (-5% Pick-up) Fixed 100ms *Adjustable Fixed 100ms * 18
CMKP (Across Monitored Range) Adjustable (50-95% Pick-up) Fixed 100ms *
Overcurrent COP Fixed (-5% Pick-up) Fixed 100ms *Adjustable 0.1-10 sec 20
COKP (Across Monitored Range) Adjustable Adjustable (50-95% Pick-up) Fixed 100ms *
UndercurrentCUP Fixed (+5% Drop-out) Fixed 100ms * Adjustable 0.1-10 sec 22
(Across Monitored Range) Adjustable
(Adjustable time delayon pick-up and fixedtime delay on drop-outcurrent settings)
(Fixed time delay onboth pick-up and drop-out current settings)
(Fixed time delay onpick-up and adjustabletime delay on drop-outcurrent settings)
*Fixed time delay eliminates nuisance tripping due to short current surges or drops.
Current Monitor Relays monitor AC single phase currents for over or under current conditions. A separate 24 or120VAC input (supply) voltage is required to power these units. Three current ranges are available: 0.1 – 1A;0.5 – 5A; and 1 – 10A. An external current transformer may be used to extend the range of these products (seeTypical Installations below). All versions are available in a compact plug-in case utilizing industry-standard 8 or 11 pinoctal sockets.
The Reference Guide below provides general information on the different versions of Current Monitor Relays offeredby Macromatic (see Product Selection on the following pages for further details):
CURRENT MONITOR RELAYSProduct Summary
18
The CM Series is used to detect either an overcurrent or undercurrent condition. The pick-up current setting is user-adjustable within one of three ranges as shown in the ProductSelection Table below. An externalcurrent transformer can be used toextend the range beyond 10amperes.
Choose between a fixed drop-outcurrent setting at 95% of theselected pick-up setting or anadjustable drop-out setting of 50-95% of the selected pick-upsetting. The relay will energizewhen the monitored AC current isabove the pick-up setting, and willde-energize when the monitored AC current is below the drop-out setting. The time delayon both pick-up and drop-out is fixed at 100ms (for products with adjustable time delay onpick-up, see page 20; for adjustable time delay on drop-out, see page 22).
u Monitors AC single phasecurrents
u Three separate currentmonitoring ranges covering0.1 - 10 amperes
u External CT can be used toextend ranges
u Adjustable Pick-up Settingwith either Fixed or Adjust-able Drop-out Setting
u LED indicates output relaystatus
u Choice of compact 8 PinSPDT or 11 Pin DPDT plug-in case
u 10A output contacts
u
DPDT 11 Pin Plug-inPick-up Drop-Out Input Current Range Product Wiring/Setting Setting Voltage Monitored Number Socket
Adjustable Fixed 24V AC 0.1 - 1A CMP01A28 11 Pin(At 95% of 0.5 - 5A CMP05A28 70170-DPick-Up) 1 - 10A CMP10A28
120V AC 0.1 - 1A CMP01A220.5 - 5A CMP05A221 - 10A CMP10A22
Adjustable Adjustable 24V AC 0.1 - 1A CMKP01A28(From 50-95% 0.5 - 5A CMKP05A28
of Pick-Up) 1 - 10A CMKP10A28120V AC 0.1 - 1A CMKP01A22
0.5 - 5A CMKP05A221 - 10A CMKP10A22 Diagram 22
CURRENT MONITOR RELAYSAC Plug-inCM Series Standard
SPDT 8 Pin Plug-inPick-up Drop-Out Input Current Range Product Wiring/Setting Setting Voltage Monitored Number Socket
Adjustable Fixed 24V AC 0.1 - 1A CMP01A68 8 Pin(At 95% of 0.5 - 5A CMP05A68 70169-DPick-Up) 1 - 10A CMP10A68
120V AC 0.1 - 1A CMP01A620.5 - 5A CMP05A621 - 10A CMP10A62
Adjustable Adjustable 24V AC 0.1 - 1A CMKP01A68(From 50-95% 0.5 - 5A CMKP05A68
of Pick-Up) 1 - 10A CMKP10A68120V AC 0.1 - 1A CMKP01A62
0.5 - 5A CMKP05A621 - 10A CMKP10A62 Diagram 21
Sockets & Accessories−Page 16 Application Data−Page 19Dimensions−Page 19
(with appropriate socket)
19
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Indicator LED: Green when Input Voltage is applied;Red when Relay is energized
Reset: Automatic. Contact Macromatic for informationon a product with a latching function--the relay remainsenergized even after the current drops below the drop-outsetting until a remote N.C. button is opened.
Mounting:Requires an 8 or 11 pin octal socket--see page 16.
Approvals:
Dimensions
Application Data
Input Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.
Load (Burden):Less than 5VA
Current Settings:Pick-up: Adjustable throughout current range monitoredDrop-out: Fixed at 95% of pick-up setting (CMP Series); or
Adjustable from 50-95% of pick-up setting (CMKPSeries)
Temperature:-28o to 55o C (-20o to 131o F)
Response Times:Pick-up: 100msDrop-out: 100ms
Output Contacts:10A Resistive @ 240V AC/30V DC, 1/2HP @ 240V AC (N.O.),1/3HP @ 240V AC (N.C.)
All dimensions are inches(millimeters)
CURRENT MONITOR RELAYSAC Plug-in
CM Series StandardApplication Data & Dimensions
2.4 (60)
2.9(74)
3.5(89)
1.7(43)
File #E109466
CMKPOnly
File #E109466
with appropriateMacromatic socket
20
The CO Series is used to detect an overcurrent condition. The pick-up current setting isuser-adjustable within one of three ranges as shown in the Product Selection Table below.An external current transformer canbe used to extend the range beyond10 amperes.
Choose between a fixed drop-outcurrent setting at 95% of theselected pick-up setting or anadjustable drop-out setting of 50-95% of the selected pick-up setting.The relay will energize when themonitored AC current is above thepick-up setting for a period longerthan the adjustable time delay of 0.1-10 seconds. This delay prevents nuisance trippingcaused by inrush currents. It will de-energize when the monitored AC current is below thedrop-out setting.
u Monitors AC single phasecurrents for overcurrentconditions
u Three separate currentmonitoring ranges covering0.1 - 10 amperes
u External CT can be used toextend ranges
u Adjustable Pick-up Settingwith either Fixed or Adjust-able Drop-out Setting
u Adjustable time delay of 0.1-10 seconds on pick-up
u LED indicates output relaystatus
u Choice of compact 8 PinSPDT or 11 Pin DPDT plug-in case
u 10A output contactsu
CURRENT MONITOR RELAYSAC Plug-inCO Series Overcurrent
11 Pin DPDT Plug-inPick-up Drop-Out Input Current Range Product Wiring/Setting Setting Voltage Monitored Number Socket
Adjustable Fixed 24V AC 0.1 - 1A COP01A28 11 Pin(At 95% of 0.5 - 5A COP05A28 70170-DPick-Up) 1 - 10A COP10A28
120VAC 0.1 - 1A COP01A220.5 - 5A COP05A221 - 10A COP10A22
Adjustable Adjustable 24V AC 0.1 - 1A COKP01A28(From 50-95% 0.5 - 5A COKP05A28
of Pick-Up) 1 - 10A COKP10A28120V AC 0.1 - 1A COKP01A22
0.5 - 5A COKP05A221 - 10A COKP10A22 Diagram 22
8 Pin SPDT Plug-inPick-up Drop-Out Input Current Range Product Wiring/Setting Setting Voltage Monitored Number Socket
Adjustable Fixed 24V AC 0.1 - 1A COP01A68 8 Pin(At 95% of 0.5 - 5A COP05A68 70169-DPick-Up) 1 - 10A COP10A68
120V AC 0.1 - 1A COP01A620.5 - 5A COP05A621 - 10A COP10A62
Adjustable Adjustable 24V AC 0.1 - 1A COKP01A68(From 50-95% 0.5 - 5A COKP05A68
of Pick-Up) 1 - 10A COKP10A68120V AC 0.1 - 1A COKP01A62
0.5 - 5A COKP05A621 - 10A COKP10A62 Diagram 21
Sockets & Accessories−Page 16 Application Data−Page 21Dimensions−Page 21
(with appropriate socket)
21
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Indicator LED: Green when Input Voltage is applied;Red Flashing when in time delay; and Red Steady whenRelay is energized.
Reset: Automatic. Contact Macromatic for informationon a product with a latching function--the relay remainsenergized even after the current drops below the drop-out setting until a remote N.C. button is opened.
Mounting:Requires an 8 or 11 pin octal socket--see page 16.
Approvals:
Dimensions
Application Data
Input Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.
Load (Burden):Less than 5VA
Current Settings:Pick-up: Adjustable throughout current range monitoredDrop-out: Fixed at 95% of pick-up setting (COP Series); or
Adjustable from 50-95% of pick-up setting (COKPSeries)
Temperature:-28o to 55o C (-20o to 131o F)
Response Times:Pick-up: Adjustable 0.1-10 secondsDrop-out: Fixed 100ms
Output Contacts:10A Resistive @ 240V AC/30V DC, 1/2HP @ 240V AC (N.O.),1/3HP @ 240V AC (N.C.)
All dimensions are inches(millimeters)
CURRENT MONITOR RELAYSAC Plug-in
CO Series OvercurrentApplication Data & Dimensions
2.4 (60)
2.9(74)
3.5(89)
1.7(43)
COKPOnly
File #E109466
File #E109466
with appropriateMacromatic socket
22
The CU Series is used to detect an undercurrent condition. The drop-out current setting isuser-adjustable within one of three ranges as shown in the Product Selection Table below.An external current transformer canbe used to extend the rangebeyond 10 amperes.
The pick-up current setting is fixedat +5% of the selected drop-outsetting. The relay will energizewhen the monitored AC current isabove the pick-up setting. It willde-energize when the monitoredAC current is below the drop-outsetting for a period longer than theadjustable time delay of 0.1-10seconds. This delay prevents nuisance tripping caused by momentary line dips. The relaywill energize when the current rises 5% above the drop-out setting.
u Monitors AC single phasecurrents for undercurrentconditions
u Three separate currentmonitoring ranges covering0.1 - 10 amperes
u External CT can be used toextend ranges
u Adjustable Drop-out Settingwith Fixed Pick-up Setting
u Adjustable time delay of 0.1-10 seconds on drop-out
u LED indicates output relaystatus
u Choice of compact 8 PinSPDT or 11 Pin DPDT plug-in case
u 10A output contactsu
CURRENT MONITOR RELAYSAC Plug-inCU Series Undercurrent
8 Pin SPDT Plug-inPick-up Drop-Out Input Current Range Product Wiring/Setting Setting Voltage Monitored Number SocketFixed Adjustable 24V AC 0.1 - 1A CUP01A68 8 Pin
(At +5% of 0.5 - 5A CUP05A68 70169-DDrop-Out) 1 - 10A CUP10A68
120V AC 0.1 - 1A CUP01A620.5 - 5A CUP05A621 - 10A CUP10A62
Diagram 21
Sockets & Accessories−Page 16 Application Data−Page 23Dimensions−Page 23
11 Pin DPDT Plug-inPick-up Drop-Out Input Current Range Product Wiring/Setting Setting Voltage Monitored Number SocketFixed Adjustable 24V AC 0.1 - 1A CUP01A28 11 Pin
(At +5% of 0.5 - 5A CUP05A28 70170-DDrop-Out) 1 - 10A CUP10A28
120V AC 0.1 - 1A CUP01A220.5 - 5A CUP05A221 - 10A CUP10A22
Diagram 22
(with appropriate socket)
23
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Indicator LED: Green when Input Voltage is applied;Red Flashing when in time delay; and Red Steady whenRelay is energized.
Reset: Automatic
Mounting:Requires an 8 or 11 pin octal socket--see page 16.
Approvals:
Dimensions
Application Data
Input Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.
Load (Burden):Less than 5VA
Current Settings:Pick-up: Fixed at 5% above adjustable drop-out settingDrop-out: Adjustable throughout current range monitored
Temperature:-28o to 55o C (-20o to 131o F)
Response Times:Pick-up: Fixed 100msDrop-out: Adjustable 0.1-10 seconds
Output Contacts:10A Resistive @ 240V AC/30V DC, 1/2HP @ 240V AC(N.O.), 1/3HP @ 240V AC (N.C.)
All dimensions are inches(millimeters)
CURRENT MONITOR RELAYSAC Plug-in
CU Series UndercurrentApplication Data & Dimensions
2.4 (60)
2.9(74)
3.5(89)
1.7(43)
File #E109466
File #E109466
with appropriateMacromatic socket
24
VOLTAGE MONITOR RELAYSProduct Summary
Voltage Monitor Relays monitor either AC single phase (50-60Hz) or DC voltages to protect equipment against voltage faultconditions. No separate supply (input) voltage is required on any Macromatic Voltage Monitor Relays. All versions are available ina compact plug-in case utilizing an 8 pin octal socket.
Macromatic offers two styles of Voltage Monitor Relays:
u Over/Under Voltage Relays--provides protection to equipment where either an over or under voltage condition is poten-tially damaging. When used as an under voltage relay, they provide protection to equipment that is required to operateabove a minimum voltage. When used as over voltage relays, they protect equipment against excessive voltage condi-tions. Over/Under Voltage Relays are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value.
u Voltage Band Relays--provides protection to equipment that is required to operate within an upper & lower voltage limit.As long as the operating voltage remains within an OVER & UNDER voltage range, the internal relay stays energized. Ifthe operating voltage falls outside this range, the relay will drop-out.
These products are summarized below:
Over/Undervoltage Relays
Voltage Band Relays
ApprovalsAll Macromatic plug-in Voltage Monitor Relays are UL Component Recognized. They are also UL Listed when usedwith the appropriate Macromatic socket.
SeriesPick-upVoltage
Drop-outVoltage
Time DelayDrop-Out
FunctionChart Page
VMP Adjustable 85-115% Nominal
Fixed at 95% ofPick-Up
Fixed 500ms * 25
VMKP Adjustable 85-115% Nominal
Adjustable 75-95% of Pick-up
Fixed 500ms * 25
VAP Adjustable 85-115% Nominal
Fixed at 95% ofPick-Up
Adjustable0.5-10 seconds
26
VAKP Adjustable 85-115% Nominal
Adjustable 75-95% of Pick-up
Adjustable0.5-10 seconds
26
SeriesOver Voltage
VoltageUnder Voltage
VoltageTime DelayDrop-Out
FunctionChart Page
VWP Adjustable100-125%of Nominal
Adjustable75-100%
of Nominal
Fixed 500ms * 28
VWKP Adjustable100-125%of Nominal
Adjustable75-100%
of Nominal
Adjustable0.5-10 seconds
28
*Fixed time delay eliminates nuisance tripping due to short voltage surges or drops.
25
VOLTAGE MONITOR RELAYSVM Series Over/Undervoltage
Fixed Time Delay on Drop-Out
Over/Under Voltage Relays provide protection to equipment where either an over orunder voltage condition is potentially damaging. They are designed to operate when theoperating voltage reaches a preset value and drop-out when the operating voltage dropsto a level below the preset value.
The pick-up voltage setting is user-adjustable from 85-115% of thenominal voltage rating. Asstandard, the VMP Series has adrop-out voltage setting fixed at95% of the pick-up voltage setting.An adjustable drop-out setting of75-95% of the pick-up setting isavailable on the VMKP Series.The relay energizes when themonitored voltage is above the pick-up setting. The relay de-energizes when the moni-tored voltage is below the drop-out setting for a period longer than the drop-out timedelay (T), which is a fixed 500ms for VM Series products. An adjustable time delay ondrop-out of 0.5-10 seconds is available (see Page 26).
NOMINAL PICK-UP DROP-OUT PRODUCT WIRING/VOLTAGEl VOLTAGE RANGE VOLTAGE RANGE* NUMBER SOCKET
24V AC 21-27V AC 20-26V AC VMP024A 8 Pin Octal120V AC 102-138V AC 97-131V AC VMP120A 70169-D
12V DC 10-14V DC 9-13V DC VMP012D24V DC 21-27V DC 20-26V DC VMP024D48V DC 41-55V DC 39-52V DC VMP048D110V DC 94-126V DC 89-121V DC VMP110D DIAGRAM 20
NOMINAL PICK-UP DROP-OUT PRODUCT WIRING/VOLTAGEl VOLTAGE RANGE VOLTAGE RANGE NUMBERn SOCKET
24V AC 21-27V AC 16-26V AC VMKP024A 8 Pin Octal120V AC 102-138V AC 77-131V AC VMKP120A 70169-D
12V DC 10-14V DC 8-13V DC VMKP012D24V DC 21-27V DC 16-26V DC VMKP024D48V DC 41-55V DC 32-52V DC VMKP048D110V DC 94-126V DC 71-121V DC VMKP110D DIAGRAM 20
Adjustable Pick-Up, Fixed Drop-Out Settings *Time Delay on Drop-out Fixed at 500ms
Adjustable Pick-Up & Drop-Out Settings **Time Delay on Drop-out Fixed at 500ms
u Monitors AC single phaseand DC voltages
u Wide range of user-adjust-able pick-up and drop-outsettings
u Fixed time delay on drop-outof 500ms
u LED indicates output relaystatus
u Compact plug-in caseutilizing industry standard 8pin octal socket
u 10A DPDT output contacts
u
Sockets & Accessories−Page 16 Application Data/Dimensions−Page 27
* Drop-out Voltage is fixed at 95% of the adjusted Pick-up Setting.
** Drop-out Voltage is adjustable from 75-95% of the adjusted Pick-up Setting.l Contact Macromatic for information on units above 120V.n These products replace those products previously sold with a suffix “-G”--contact
Macromatic for more information.
(with appropriate socket)
26
u Monitors AC single phaseand DC voltages
u Wide range of user-adjust-able pick-up and drop-outsettings
u Adjustable time delay ondrop-out of 0.5 - 10 seconds
u LED indicates output relaystatus
u Compact plug-in caseutilizing industry standard 8pin octal socket
u 10A DPDT output contacts
u
Over/Under Voltage Relays provide protection to equipment where an over or undervoltage condition is potentially damaging. They are designed to operate when theoperating voltage reaches a preset value and drop-out when the operating voltage dropsto a level below the preset value.
The pick-up voltage setting is user-adjustable from 85-115% of thenominal voltage rating. As stan-dard, the VAP Series has a drop-out voltage setting fixed at 95% ofthe pick-up voltage setting. Anadjustable drop-out setting of 75-95% of the pick-up setting isavailable on the VAKP Series. Therelay energizes when the moni-tored voltage is above the pick-upsetting. The relay de-energizes when the monitored voltage is below the drop-out settingfor a period longer than the drop-out time delay (T), which is adjustable from 0.5-10seconds for VA Series products. A time delay on drop-out fixed at 500ms is available(see Page 25).
NOMINAL PICK-UP DROP-OUT PRODUCT WIRING/VOLTAGEl VOLTAGE RANGE VOLTAGE RANGE* NUMBER SOCKET
24V AC 21-27V AC 20-26V AC VAP024A 8 Pin Octal120V AC 102-138V AC 97-131V AC VAP120A 70169-D
12V DC 10-14V DC 9-13V DC VAP012D24V DC 21-27V DC 20-26V DC VAP024D48V DC 41-55V DC 39-53V DC VAP048D110V DC 94-126V DC 89-121V DC VAP110D DIAGRAM 20
* Drop-out Voltage is fixed at 95% of the adjusted Pick-up Setting.
NOMINAL PICK-UP DROP-OUT PRODUCT WIRING/VOLTAGEl VOLTAGE RANGE VOLTAGE RANGE NUMBER SOCKET
24V AC 21-27V AC 16-26V AC VAKP024A 8 Pin Octal120V AC 102-138V AC 77-131V AC VAKP120A 70169-D
12V DC 10-14V DC 8-13V DC VAKP012D24V DC 21-27V DC 16-26V DC VAKP024D48V DC 41-55V DC 32-52V DC VAKP048D110V DC 94-126V DC 71-121V DC VAKP110D DIAGRAM 20
Adjustable Pick-Up, Fixed Drop-Out Settings *Adjustable Time Delay on Drop-out from 0.5 - 10 Seconds
Adjustable Pick-Up & Drop-Out Settings **Adjustable Time Delay on Drop-out from 0.5 - 10 Seconds
** Drop-out Voltage is adjustable from 75-95% of the adjusted Pick-up Setting.
Sockets & Accessories−Page 16 Application Data/Dimensions−Page 27
l Contact Macromatic for information on units above 120V.
VOLTAGE MONITOR RELAYSVA Series Over/UndervoltageAdjustable Time Delay on Drop-Out
(with appropriate socket)
27
Response Times:Operate: 500msRelease: Fixed 500 ms (VMP & VMKP Series)
Adjustable 0.5 - 10 Seconds (VAP & VAKP Series)
Indicator LED: Red Steady when Relay is energized; Greenwhen Relay is Off.
Transient Protection:10,000 volts for 20 microseconds
Reset: Automatic. Contact Macromatic for information onhow to order a unit with Manual Reset.
Approvals:
Dimensions
Application Data
Voltage Tolerance:+25%/-50% of nominal voltage; AC voltages are 50-60Hz;No separate supply (input) voltage is required.
Load (Burden): Less than 3VA
Voltage Settings:Pick-up: Adjustable from 85-115% of nominal voltageDrop-out: Fixed at 95% of the pick-up setting (VMP & VAP Series)
Adjustable from 75-95% of pick-up setting (VMKP &VAKP Series)
Temperature:-28o to 55o C (-20o to 131o F)
Output Contacts:10A Resistive @ 240V AC/30V DC, 1/2HP @ 240V AC (N.O.),1/3HP @ 240V AC (N.C.)
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
VOLTAGE MONITOR RELAYSVM & VA Series Over/Undervoltage
Application Data & Dimensions
2.4 (60)
2.9 (74)
3.5 (89)1.7 (43)
All Dimensions inInches (Millimeters)
VMKP & VAKPOnly
Overvoltage RelayProvides protection to equipment that cannot handle excessvoltages. Uses a normally closed contact (N.C.). As long as themonitored voltage remains below the maximum voltage theequipment can withstand (Pick-Up Setting), the relay remains de-energized and the N.C. contact remains closed, keeping the loadenergized. If the operating voltage increases beyond the maxi-mum rating of the equipment, the relay energizes and the N.C.contact opens, turning off the load. When the voltage falls belowthe Drop-Out Setting (hysteresis), the relay de-energizes and theN.C. contact re-closes, turning on the load.
Undervoltage RelayProvides protection to equipment that is required tooperate above a certain minimum voltage. Uses anormally open contact (N.O.). As long as the monitoredvoltage is above the minimum value required (Pick-UpSetting), the relay will energize and the N.O. contactcloses, turning on the load. If the voltage drops below theDrop-out Setting (the minimum voltage required minusthe hysteresis), the relay will de-energize and the N.O.contact will re-open, turning off the load.
These relays can be used as either overvoltage or undervoltage relays, depending on the output contact used:
Operating Modes
File #E109466
File #E109466
with appropriateMacromatic socket
28
VOLTAGE MONITOR RELAYSVW Series Voltage Band
u Monitors AC single phaseand DC voltages
u Provides voltage band(window) protection
u Wide range of user-adjust-able Over Voltage andUnder Voltage settings
u Fixed or adjustable timedelay on drop-out
u LED indicates output relaystatus
u Compact plug-in caseutilizing industry standard 8pin octal socket
u 10A DPDT output contactsu
Voltage Band Relays provide protection to equipment that is required to operatewithin an upper & lower voltage limit. As long as the operating voltage remainswithin an OVER & UNDER voltage range, the internal relay stays energized. Ifthe operating voltage falls outside this range, the relay will drop-out.
When nominal operatingvoltage with a value betweenthe UPPER & LOWERsetting is applied, the internalrelay will energize (Pick-up).If the operating voltage fallsoutside the preset OVER trippoint (adjustable 100-125%of nominal) or UNDER trippoint (adjustable 75-100% of nominal) for a period longer than the drop-out timedelay (T), the relay will de-energize (Drop-out). When the voltage returns tonormal (within the preset OVER & UNDER trip points), the unit automaticallyresets and the relay energizes. Choose between a unit with fixed drop-out time of500ms or one with an adjustable 0.5-10 second drop-out time.
NOMINAL OVER VOLTAGE UNDER VOLTAGE PRODUCT WIRING/VOLTAGEl RANGE RANGE NUMBER SOCKET
24V AC 24-30V AC 18-24V AC VWKP024A 8 Pin Octal120V AC 120-150V AC 90-120V AC VWKP120A 70169-D
12V DC 12-15V DC 9-12V DC VWKP012D24V DC 24-30V DC 18-24V DC VWKP024D48V DC 48-60V DC 36-48V DC VWKP048D110V DC 110-137V DC 83-110V DC VWKP110D DIAGRAM 20
Adjustable Drop-Out Time Delay 0.5 - 10 Seconds
NOMINAL OVER VOLTAGE UNDER VOLTAGE PRODUCT WIRING/VOLTAGEl RANGE RANGE NUMBER SOCKET
24V AC 24-30V AC 18-24V AC VWP024A 8 Pin Octal120V AC 120-150V AC 90-120V AC VWP120A 70169-D
12V DC 12-15V DC 9-12V DC VWP012D24V DC 24-30V DC 18-24V DC VWP024D48V DC 48-60V DC 36-48V DC VWP048D110V DC 110-137V DC 83-110V DC VWP110D DIAGRAM 20
Fixed Drop-Out Time Delay (500ms)
Sockets & Accessories-Page 16 Application Data/Dimensions-Page 29
l Contact Macromatic for information on units above 120V.
(with appropriate socket)
29
Response Times:Operate: 500msRelease: Fixed 500 ms (VWP Series)
Adjustable 0.5 -10 Seconds (VWKP Series)
Output Contacts:10A Resistive @ 240V AC/30V DC, 1/2HP @ 240V AC (N.O.),1/3HP @ 240V AC (N.C.)
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Transient Protection:10,000 volts for 20 microseconds
Approvals:
Dimensions
Application Data
Voltage Tolerance:+25%/-50% of nominal voltage; AC voltages are 50-60Hz;No separate supply (input) voltage is required.
Load (Burden): Less than 3VA
Voltage Settings:Over Voltage: 100-125% of Nominal VoltageUnder Voltage: 75-100% of Nominal Voltage
Temperature:-28o to 55o C (-20o to 131o F)
Indicator LED: Red Steady when Relay is energized; Greenwhen Relay is Off.
Reset: Automatic. Contact Macromatic for information on howto order a unit with Manual Reset.
VOLTAGE MONITOR RELAYSVW Series Voltage Band
Application Data & Dimensions
All Dimensions inInches (Millimeters)
VWKP Only
2.4 (60)
2.9 (74)
3.5 (89)1.7 (43)
File #E109466
File #E109466
with appropriateMacromatic socket
30
TIME DELAY RELAYSProduct Summary
Macromatic offers a wide variety of time delay relays and accessories. Each one has different features and operatingcharacteristics, allowing you to choose the exact product to meet your needs. Our time delay relays are available ineither programmable or non-programmable versions. We offer both single or multiple function time delay relays.Choose between SPDT or DPDT relay outputs. Time delay relays are available as plug-in units for use with industrystandard 8 & 11 pin octal or 11 pin blade sockets, or as an open board version for OEM applications. Choose betweenanalog or digital-set time delay relays. Refer to the Selection Table on these two pages for more information.
StandardNon-Programmable
Single-RangePlug-in
Time RangerMulti-Range
ProgrammablePlug-in
CompactNon-Programmable
Single-RangePlug-in
Series TR-5 TR-6 SS-6 & SS-8
Timing FunctionsAvailable
* On Delay* Interval On* Flasher* Off Delay* Single Shot* Watchdog* Repeat Cycle* Delayed Interval
* On Delay* Interval On* Flasher* Off Delay* Single Shot* Watchdog* Repeat Cycle* Delayed Interval
* On Delay* Interval On* Off Delay* Single Shot
Timing RangesAvailable
20 separate timing rangesfrom 0.02 Seconds to 24
Hours
16 field-programmable timingranges covering up to 2Hours (24 Hours on DualKnob units) in one unit
6 separate timing rangesfrom 0.02 to 300 Seconds
Output Contacts DPDT or SPDT10A @ 240V AC10A @ 28V DC
1/2HP @ 240V AC1/3HP @ 120V AC
B300/R300
DPDT10A @ 240V AC10A @ 28V DC
1/2HP @ 240V AC1/3HP @ 120V AC
B300/R300
SPDT5A @ 120V AC5A @ 28V DC
1/6HP @ 120V AC
Input Voltages 12V AC/DC,24V AC/DC,
120V AC/DC &240V AC
12V AC/DC,24V AC/DC,
120V AC/DC &240V AC
12V AC/DC,24V AC/DC &
120V AC
Approvals
See Page 34-39 40-43 44
with appropriate socket with appropriate socket with appropriate socket
31
TIME DELAY RELAYSProduct Summary
See pages 32 & 33 for a detailed description of all timing functions available. If you have any questions regarding theselection or application of time delay relays, either visit our on-line Technical Resource Center (www.macromatic.com)or call us at 800-238-7474.
Need modifications such as fixed time delays, remote adjustments or special pin configurations? We can do most ofthese modifications within our normal lead-times. See pages 50 & 51 for more information.
with appropriate socket
Spade BaseNon-Programmable
Single RangePlug-in
Time RangerDigital-Set
Multi-RangeProgrammable
Plug-in
Time Ranger IIIDigital-Set
Multi-FunctionMulti-Range
Programmable
Series SS-4 TD-7 981
Timing FunctionsAvailable
* On Delay* Off Delay
* On Delay* Interval On* Flasher* Off Delay* Single Shot
Available in both singlefunction & multifunction
All in One Unit:* On Delay* Interval On* Flasher* Off Delay (2 versions)* Interval On/Off Delay* On Delay/Off Delay* Delayed Interval
Timing RangesAvailable
3 separate timing rangesfrom 0.1 to
300 Seconds
0.05 Seconds to999 Hours
programmable timing range
0.1 Seconds to9,999 Hours
programmable timing range
Output Contacts DPDT12A @ 240V AC12A @ 30V DC
1/2HP @ 240V ACB300/R300
DPDT10A @ 240V AC10A @ 28V DC
1/2HP @ 240V AC1/3HP @ 120V AC
B300/R300
SPDT3A @ 240V AC5A @ 30V DC
1/2HP @ 240V AC
Input Voltages 12V AC/DC,24V AC/DC &
120V AC
12V AC/DC,24V AC/DC,
120V AC/DC &240V AC
24-240V AC &12-240V DC in one unit
Approvals
See Page 45 46-47 48-49
with appropriate socket
32
Function Operation Timing Chart
ON DELAYDelay on OperateDelay on Make
INTERVAL ONInterval
OFF DELAYDelay on ReleaseDelay on De-EnergizationDelay on Drop-Out
SINGLE SHOTOne ShotMomentary Interval
Understanding the differences between all the functions available in time delay relays can sometimes be a daunting task. Tobegin with, time delay relays are simply control relays with a time delay built in. Their purpose is to control an event based ontime.
Typically, time delay relays are initiated or triggered by one of two methods:u application of input voltage (On Delay, Interval On, Flasher, Repeat Cycle & Delayed Interval)u opening or closing of a trigger signal (Off Delay, Single Shot, Watchdog & Triggered Delayed Interval)
These trigger signals can be one of two designs: a control switch (dry contact), i.e., limit switch, push button, float switch, etc., orby voltage (commonly known as a power trigger).
To help understand, some definitions are important:u Input Voltage-control voltage applied to the input terminals. Depending on the function, input voltage will either initiate
the unit or make it ready to initiate when a trigger signal is applied.u Trigger Signal-on certain timing functions, a trigger signal is used to initiate the unit after input voltage has been applied.
As noted above, this trigger signal can either be a control switch (dry contact switch) or a power trigger (voltage).u Output (Load)-every time delay relay has an internal relay (usually mechanical) with contacts that open & close to control
the load. They are represented by the dotted lines in the wiring diagrams. Note that the user must provide the voltage topower the load being switched by the output contacts of the time delay relay.
Below and on the following page are both written and visual descriptions on how the common timing functions operate. A TimingChart shows the relationship between Input Voltage, Trigger Signal (if present) and Output Contacts. If you cannot find a productto fit your requirements or have any questions, Macromatic’s Application Engineers offer technical information along with productselection and application assistance. Just call us at 800-238-7474 or e-mail us at [email protected].
TIME DELAY RELAYSDefinition of Timing Functions
Upon application of input voltage, the preset timebegins. At the end of the preset time, the relay isenergized. Input voltage must be removed andreapplied to reset the time delay & de-energizethe relay.
Upon application of input voltage, the relay isenergized and the preset time begins. At the endof the preset time, the relay is de-energized. Inputvoltage must be removed and reapplied to resetthe time delay.
Upon application of input voltage, the time delayrelay is ready to accept trigger signals. Uponapplication of the trigger signal, the relay isenergized. Upon release of the trigger signal, thepreset time begins. At the end of the preset time,the relay is de-energized. Any application of thetrigger signal during the preset time will keep therelay energized & reset the time delay.
Upon application of input voltage, the time delayrelay is ready to accept trigger signals. Uponapplication of the trigger signal, the relay isenergized and the preset time begins. During thepreset time, the trigger signal is ignored. Thetime delay relay is reset by applying the triggersignal when the relay is not energized.
33
Function Operation Timing Chart
WATCHDOGRetriggerable Single Shot
FLASHER
REPEAT CYCLEOff/On Delay
REPEAT CYCLEOn/Off Delay
DELAYEDINTERVALSingle Cycle
DELAYEDINTERVAL(TRIGGERED)Single Cycle
Upon application of input voltage, the time delayrelay is ready to accept trigger signals. Uponapplication of the trigger signal, the relay isenergized and the preset time begins. At the endof the preset time, the relay is de-energized unlessthe trigger signal is closed and opened prior totime out (before preset time elapses). Continuouscycling of the trigger signal at a rate faster than thepreset time will cause the relay to remain ener-gized.
Upon application of input voltage, the preset time(T1) begins. At the end of the preset time, the relayis energized and remains in that condition for thepreset time (T1). At the end of this time, the relay isde-energized and the sequence repeats until inputvoltage is removed.
Upon application of input voltage, a preset delaybegins (OFF). At the end of the preset delay, therelay is energized and remains in that condition fora second, independently adjustable preset time(ON). At the end of this time, the relay is de-energized and the sequence repeats until inputvoltage is removed.
Upon application of input voltage, the relay isenergized and a preset delay begins (ON). At theend of the preset delay, the relay is de-energizedand remains in that condition for a second,independently adjustable preset time (OFF). At theend of this time, the relay is energized and thesequence repeats until input voltage is removed.
Upon application of input voltage, a preset delaybegins (OFF). At the end of the preset delay, therelay is energized and remains in that condition fora second, independently adjustable preset time(ON). At the end of the second preset time, therelay is de-energized. Input voltage must beremoved and reapplied to reset the time delayrelay.
Upon application of input voltage, the time delayrelay is ready to accept trigger signals. Uponapplication of the trigger signal, a preset delaybegins (OFF). At the end of the preset delay, therelay is energized and remains in that condition fora second, independently adjustable preset time(ON). At the end of the second preset time, therelay is de-energized. During both the OFF time &the ON time, the trigger signal is ignored.
TIME DELAY RELAYSDefinition of Timing Functions
34
TIME DELAY RELAYSNon-Programmable Plug-inOn Delay, Interval & Flasher
Timing Ranges
u Each unit has a single timingrange
u Choose from 20 separatetiming ranges from0.02 Seconds to 24 Hours
u Uses industry-standard 8 pinoctal sockets
u 10A DPDT output contacts
u
For Fixed Time Delay (at no additional charge), add suffix “F”and time delay desired to basic Product Number, i.e., TR-50222-F5S is an On Delay with a time delay fixed at 5 seconds.
SINGLE KNOB UNITSINPUT PRODUCT
VOLTAGE NUMBER ** WIRING/FUNCTIONn 50/60Hz. SOCKETSp
ON DELAY 120V AC/DC TR-50222-**12V AC/DC TR-50226-** 8 PIN OCTAL p24V AC/DC TR-50228-** 70169-D
240V AC TR-50221-**INTERVAL ON 120V AC/DC TR-50522-**
12V AC/DC TR-50526-**24V AC/DC TR-50528-**
240V AC TR-50521-**FLASHER 120V AC/DC TR-50822-**
12V AC/DC TR-50826-**24V AC/DC TR-50828-**
240V AC TR-50821-**
COMPLETE PRODUCTNUMBER USING 2 DIGIT CODE
FROM TABLE BELOW
DIAGRAM 1
Sockets & Accessories−Page 58 Application Data−Page 37Dimensions−Page 37 Standard Modifications−Pages 50-51
** TIMING RANGE TABLECOMPLETE PRODUCT NUMBER USING TWO DIGIT CODE
FROM TABLE BELOW
i.e., TR-50222-04
Time Delay Range Code Time Delay Range Code 0.02 - 2 Sec. 03 6 Sec. - 10 Min. 22
0.05 - 5 Sec. 04 9 Sec. - 15 Min. 14 0.1 - 10 Sec. 05 0.3 - 30 Min. 15 0.15 - 15 Sec. 06 0.6 - 60 Min. 16 0.3 - 30 Sec. 07 1.2 - 120 Min. 17 0.6 - 60 Sec. 08 1.8 - 180 Min. 18 1.2 - 120 Sec. 09 2.4 Min. - 4 Hr. 19 1.8 - 180 Sec. 10 4.8 Min. - 8 Hr. 20 3 - 300 Sec. 12 7.2 Min. - 12 Hr. 21 4.5 - 450 Sec. 13 14.4 Min. - 24 Hr. 23
withappropriate
socket
p Note: if these products are ordered with the Remote Adjust Potentiometer modification(suffix -Rx), they will require an 11 pin octal socket−see Page 50 for more information.
n See Pages 32-33 for definitions & explanations of Timing Functions.
35
TIME DELAY RELAYSNon-Programmable Plug-inOff Delay, Single Shot & Watchdog
u Each unit has a single timingrange
u Choose from 20 separatetiming ranges from0.02 Seconds to 24 Hours
u Uses industry-standard11 pin octal sockets
u 10A DPDT output contacts
u
For Fixed Time Delay (at no additional charge), add suffix “F” andtime delay desired to basic Product Number, i.e., TR-51622-F5Sis an Off Delay with a time delay fixed at 5 seconds.
SINGLE KNOB UNITSINPUT PRODUCT
VOLTAGE NUMBER ** WIRING/FUNCTIONnp 50/60Hz. SOCKETS
OFF DELAY 120V AC/DC TR-51622-** 11 PIN OCTALControl Switch Trigger 12V AC/DC TR-51626-** 70170-D
24V AC/DC TR-51628-**240V AC TR-51621-**
SINGLE SHOT 120V AC/DC TR-51522-**Control Switch Trigger 12V AC/DC TR-51526-**
24V AC/DC TR-51528-**240V AC TR-51521-**
WATCHDOG 120V AC/DC TR-51322-**Control Switch Trigger 12V AC/DC TR-51326-**
(Retriggerable 24V AC/DC TR-51328-**Single Shot) 240V AC TR-51321-**OFF DELAY 120V AC/DC TR-51922-** 11 PIN OCTAL
Power Trigger 12V AC/DC TR-51926-** 70170-D24V AC/DC TR-51928-**
240V AC TR-51921-**SINGLE SHOT 120V AC/DC TR-51722-**Power Trigger 12V AC/DC TR-51726-**
24V AC/DC TR-51728-**240V AC TR-51721-**
WATCHDOG 120V AC/DC TR-51822-**Power Trigger 12V AC/DC TR-51826-**(Retriggerable 24V AC/DC TR-51828-**Single Shot) 240V AC TR-51821-**
COMPLETE PRODUCTNUMBER USING 2 DIGIT CODE
FROM TABLE BELOW
DIAGRAM 2
Timing Ranges
p 8 Pin SPDT versions of these functions are available−see Page 38.
** TIMING RANGE TABLECOMPLETE PRODUCT NUMBER USING TWO DIGIT CODE
FROM TABLE BELOW
i.e., TR-51622-04
Time Delay Range Code Time Delay Range Code 0.02 - 2 Sec. 03 6 Sec. - 10 Min. 22
0.05 - 5 Sec. 04 9 Sec. - 15 Min. 14 0.1 - 10 Sec. 05 0.3 - 30 Min. 15 0.15 - 15 Sec. 06 0.6 - 60 Min. 16 0.3 - 30 Sec. 07 1.2 - 120 Min. 17 0.6 - 60 Sec. 08 1.8 - 180 Min. 18 1.2 - 120 Sec. 09 2.4 Min. - 4 Hr. 19 1.8 - 180 Sec. 10 4.8 Min. - 8 Hr. 20 3 - 300 Sec. 12 7.2 Min. - 12 Hr. 21 4.5 - 450 Sec. 13 14.4 Min. - 24 Hr. 23
withappropriate
socket
n See Pages 32-33 for definitions & explanations of Timing Functions.
DIAGRAM 4
Sockets & Accessories−Page 58 Application Data−Page 37Dimensions−Page 37 Standard Modifications−Pages 50-51
36
TIME DELAY RELAYSNon-Programmable Plug-inRepeat Cycle & Delayed Interval
Timing Ranges
u Each unit has a single timingrange
u Choose from 20 separatetiming ranges from0.02 Seconds to 24 Hours
u Independently adjustable ON& OFF times on dual knobtimers
u Uses industry-standard 8 or11 pin octal sockets
u 10A DPDT output contacts
u
For Fixed Time Delay (at no additional charge), add suffix “F”and time delay desired to basic Product Number, i.e., TR-53122-F5S is a Repeat Cycle with a time delay fixed at 5 seconds.
COMPLETE PRODUCTNUMBER USING 2 DIGIT CODE
FROM TABLE BELOW
* All Dual Knob units have independently selectable & adjustable ON & OFF times. Toorder a Dual Knob unit with the same ON & OFF timing ranges, complete the ProductNumber by adding one two-digit code from the table below, i.e., a TR-55122-08 is aRepeat Cycle unit with both the ON time & OFF time adjustable between 0.6 - 60seconds. To order a Dual Knob unit with different ON & OFF timing ranges, completethe Product Number by adding two different two-digit codes from the table below. Thefirst suffix indicates the first timing range of the unit and the second suffix indicates thesecond timing range, i.e., a TR-53122-05-12 is a Repeat Cycle unit with an OFF timingrange first of 0.1-10 seconds and an ON timing range second of 3-300 seconds.
** TIMING RANGE TABLECOMPLETE PRODUCT NUMBER USING TWO DIGIT CODE
FROM TABLE BELOW
i.e., TR-55122-04
Time Delay Range Code Time Delay Range Code 0.02 - 2 Sec. 03 6 Sec. - 10 Min. 22
0.05 - 5 Sec. 04 9 Sec. - 15 Min. 14 0.1 - 10 Sec. 05 0.3 - 30 Min. 15 0.15 - 15 Sec. 06 0.6 - 60 Min. 16 0.3 - 30 Sec. 07 1.2 - 120 Min. 17 0.6 - 60 Sec. 08 1.8 - 180 Min. 18 1.2 - 120 Sec. 09 2.4 Min. - 4 Hr. 19 1.8 - 180 Sec. 10 4.8 Min. - 8 Hr. 20 3 - 300 Sec. 12 7.2 Min. - 12 Hr. 21 4.5 - 450 Sec. 13 14.4 Min. - 24 Hr. 23
withappropriate
socket
n See Pages 32-33 for definitions & explanations of Timing Functions.
DIAGRAM 1
DIAGRAM 2
Sockets & Accessories−Page 58 Application Data−Page 37Dimensions−Page 37 Standard Modifications−Pages 50-51
DUAL KNOB UNITS *INPUT PRODUCT
VOLTAGE NUMBER ** WIRING/FUNCTIONn 50/60Hz. SOCKET
REPEAT CYCLE 120V AC/DC TR-53122-**(OFF Time First Followed 12V AC/DC TR-53126-** 8 PIN OCTAL
By ON Time 24V AC/DC TR-53128-** 70169-Dand Repeating) 240V AC TR-53121-**
REPEAT CYCLE 120V AC/DC TR-55122-**(ON Time First Followed 12V AC/DC TR-55126-**
By OFF Time 24V AC/DC TR-55128-**and Repeating) 240V AC TR-55121-**
DELAYED INTERVAL 120V AC/DC TR-56122-**(OFF Time Followed by 12V AC/DC TR-56126-**
ON Time Followed by OFF 24V AC/DC TR-56128-**State Until Reset) 240V AC TR-56121-**
11 PIN OCTALDELAYED INTERVAL 120V AC/DC TR-56522-** 70170-DControl Switch Trigger 12V AC/DC TR-56526-**(OFF Time Followed by 24V AC/DC TR-56528-**
ON Time Followed by OFF 240V AC TR-56521-**State Until Reset)
37
TIME DELAY RELAYSNon-Programmable Plug-in
Application Data & Dimensions
Insulation Voltage:2,000 volts
Output Contacts:DPDT 10A @ 240V AC/28V DC,1/2HP @ 240V AC, 1/3HP @ 120V ACB300 & R300; AC15 & DC13
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Compatibility:On all units triggered by input voltage or by a control switch, donot use a solid state switch to initiate the timing sequence-problems with leakage current could occur. On all units with apower trigger, do not use a solid state switch with leakagecurrent exceeding 0.5ma. Contact Macromatic Controls foradditional information.
Triggering Off Delay, Single Shot or Watchdog Units:Timing sequence must be initiated only after input voltage isapplied to unit. Minimum required trigger switch closure time is0.1 seconds.
Approvals:
Application Data
File #E109466
Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.DC Operation: +10/-15% of nominal.
Load (Burden):2 VA
Setting Accuracy:Maximum Setting (Adjustable): +5%, -0%Minimum Setting (Adjustable): +0%, -50%Fixed Time Delay: > 2 Seconds +1%
0.1 - 2 Seconds +5%
Repeat Accuracy (constant voltage and temperature):> 2 Seconds Delay +0.1%0.1 - 2 Seconds Delay +2%
Reset Time:On Delay/Interval/Repeat Cycle/Delayed Interval: 0.1 SecondsOff Delay/Single Shot/Watchdog/Triggered Delayed Interval: 0.04 Seconds
Start-up Time:(Time from when power is applied until unit is timing)120 & 240V units 0.05 Seconds12, 24 & 48V units 0.08 Seconds
Maintain Function Time:(Time unit continues to time after power is removed)0.01 Seconds for all units
Temperature:12-120V Input Voltage: -28o to 65oC (-18o to 150oF)240V Input Voltage: -28o to 50oC (-18o to 122oF)
File #LR45565 Low Voltage &EMC Directives
EN60947-1, EN60947-5-1
withappropriatesocket
File #E109466
Dimensions
2.4(60)
1.7(43)
2.9(74)
3.5(89)
All Dimensions inInches (Millimeters)
38
Timing Ranges
u These are 8 pin 10A SPDTversions of our standard 11pin DPDT products
u Each unit has a single timingrange from 0.02 Seconds to24 Hours
u Uses industry-standard 8 pinoctal socket
u
For Fixed Time Delay (at no additional charge), add suffix “F” andfixed time delay desired to basic Product Number,i.e.,TR-51662-F5S is an Off Delay with a time delay fixed at 5 seconds.
INPUT PRODUCTVOLTAGE NUMBER ** WIRING/
FUNCTIONn 50/60Hz. SOCKETSp
OFF DELAY 120V AC/DC TR-51662-**Control Switch Trigger 12V AC/DC TR-51666-** 8 PIN OCTAL
24V AC/DC TR-51668-** 70169-D p240V AC TR-51661-**
SINGLE SHOT 120V AC/DC TR-51562-**Control Switch Trigger 12V AC/DC TR-51566-**
24V AC/DC TR-51568-**240V AC TR-51561-**
WATCHDOG 120V AC/DC TR-51362-**Control Switch Trigger 12V AC/DC TR-51366-**
(Retriggerable 24V AC/DC TR-51368-**Single Shot) 240V AC TR-51361-**OFF DELAY 120V AC/DC TR-51962-** 8 PIN OCTAL
Power Trigger 12V AC/DC TR-51966-** 70169-D p24V AC/DC TR-51968-**
240V AC TR-51961-**SINGLE SHOT 120V AC/DC TR-51762-**PowerTrigger 12V AC/DC TR-51766-**
24V AC/DC TR-51768-**240V AC TR-51761-**
WATCHDOG 120V AC/DC TR-51862-**Power Trigger 12V AC/DC TR-51866-**(Retriggerable 24V AC/DC TR-51868-**Single Shot) 240V AC TR-51861-**
COMPLETE PRODUCTNUMBER USING 2 DIGIT CODE
FROM TABLE BELOW
TIME DELAY RELAYSNon-Programmable Plug-in8 Pin SPDT VersionsOff Delay, Single Shot & Watchdog
Sockets & Accessories−Page 58 Application Data−Page 39Dimensions−Page 39 Standard Modifications−Pages 50-51
** TIMING RANGE TABLECOMPLETE PRODUCT NUMBER USING TWO DIGIT CODE
FROM TABLE BELOW
i.e., TR-51662-04
Time Delay Range Code Time Delay Range Code 0.02 - 2 Sec. 03 6 Sec. - 10 Min. 22
0.05 - 5 Sec. 04 9 Sec. - 15 Min. 14 0.1 - 10 Sec. 05 0.3 - 30 Min. 15 0.15 - 15 Sec. 06 0.6 - 60 Min. 16 0.3 - 30 Sec. 07 1.2 - 120 Min. 17 0.6 - 60 Sec. 08 1.8 - 180 Min. 18 1.2 - 120 Sec. 09 2.4 Min. - 4 Hr. 19 1.8 - 180 Sec. 10 4.8 Min. - 8 Hr. 20 3 - 300 Sec. 12 7.2 Min. - 12 Hr. 21 4.5 - 450 Sec. 13 14.4 Min. - 24 Hr. 23
withappropriate
socket
p Note: if these products are ordered with the Remote Adjust Potentiometer modification(suffix -Rx), they will require an 11 pin octal socket−see Page 50 for more information.
n See Pages 32-33 for definitions & explanations of Timing Functions.
DIAGRAM 11
DIAGRAM 37
39
TIME DELAY RELAYSNon-Programmable Plug-in
8 Pin SPDT VersionsApplication Data & Dimensions
Insulation Voltage:2,000 volts
Output Contacts:DPDT 10A @ 240V AC/28V DC,1/2HP @ 240V AC, 1/3HP @ 120V ACB300 & R300; AC15 & DC13
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Compatibility:On all units triggered by a control switch, do not use a solidstate switch to initiate the timing sequence-problems withleakage current could occur. On all units with a power trigger,do not use a solid state switch with leakage current exceeding0.5ma. Contact Macromatic Controls for additional information.
Triggering Off Delay, Single Shot or Watchdog Units:Timing sequence must be initiated only after input voltage isapplied to unit. Minimum required trigger switch closure time is0.1 seconds.
Approvals:
Application Data
File #E109466
Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.DC Operation: +10/-15% of nominal.
Load (Burden):2 VA
Setting Accuracy:Maximum Setting (Adjustable): +5%, -0%Minimum Setting (Adjustable): +0%, -50%Fixed Time Delay: > 2 Seconds +1%
0.1 - 2 Seconds +5%
Repeat Accuracy (constant voltage and temperature):> 2 Seconds Delay +0.1%0.1 - 2 Seconds Delay +2%
Reset Time:Off Delay/Single Shot/Watchdog: 0.04 Seconds
Start-up Time:(Time from when power is applied until unit is timing)120 & 240V units 0.05 Seconds12, 24 & 48V units 0.08 Seconds
Maintain Function Time:(Time unit continues to time after power is removed)0.01 Seconds for all units
Temperature:12-120V Input Voltage: -28o to 65oC (-18o to 150oF)240V Input Voltage: -28o to 50oC (-18o to 122oF)
File #LR45565 Low Voltage &EMC Directives
EN60947-1, EN60947-5-1
withappropriatesocket
File #E109466
Dimensions
2.4(60)
1.7(43)
2.9(74)
3.5(89)
All Dimensions inInches (Millimeters)
40
TIME DELAY RELAYSTime Ranger TM ProgrammableMulti-Range Plug-inOn Delay, Interval On & Flasher
SINGLE KNOB UNITSINPUT VOLTAGE PRODUCT WIRING/
FUNCTIONn 50/60Hz. NUMBER SOCKETSON DELAY 120V AC/DC TR-60222
12V AC/DC TR-60226 8 PIN OCTAL24V AC/DC TR-60228 70169-D
240V AC TR-60221INTERVAL ON 120V AC/DC TR-60522
12V AC/DC TR-6052624V AC/DC TR-60528
240V AC TR-60521FLASHER 120V AC/DC TR-60822
12V AC/DC TR-6082624V AC/DC TR-60828
240V AC TR-60821
DIAGRAM 1
u Each unit has 16 timingranges built-in
u Selecting a range is easyusing a rotary switch (nomath is required or DIPswitches to set)
u Timing ranges up to 2 hours
u Uses industry-standard 8 pinoctal sockets
u 10A DPDT output contacts
u
Dial TimingSetting Range
A 0.1 - 0.25 Sec.B 0.2 - 0.5 Sec.C 0.3 - 1 Sec.D 0.5 - 2 Sec.E 1 - 4 Sec.F 2 - 8 Sec.G 4 - 15 Sec.H 8 - 30 Sec.I 15 - 60 Sec.J 30 - 120 Sec.K 1 - 4 Min.L 2 - 8 Min.M 4 - 15 Min.N 8 - 30 Min.O 15 - 60 Min.P 30 - 120 Min.
Timing Ranges
Select one of the 16 built-in time ranges by setting the rotary switchper a chart on the unit and adjust within that range using the knobon top:
SINGLE KNOB UNITS
Sockets & Accessories−Page 58 Application Data−Page 43Dimensions−Page 43 Standard Modifications−Pages 50-51
withappropriate
socket
n See Pages 32-33 for definitions & explanations of Timing Functions.
41
SINGLE KNOB UNITSINPUT VOLTAGE PRODUCT WIRING/
FUNCTIONn 50/60Hz. NUMBER SOCKETSOFF DELAY 120V AC/DC TR-61622 11 PIN OCTAL
Control Switch Trigger 12V AC/DC TR-61626 70170-D24V AC/DC TR-61628240V AC TR-61621
SINGLE SHOT 120V AC/DC TR-61522Control Switch Trigger 12V AC/DC TR-61526
24V AC/DC TR-61528240V AC TR-61521
WATCHDOG 120V AC/DC TR-61322Control Switch Trigger 12V AC/DC TR-61326
(Retriggerable 24V AC/DC TR-61328Single Shot) 240V AC TR-61321OFF DELAY 120V AC/DC TR-61922 11 PIN OCTAL
Power Trigger 12V AC/DC TR-61926 70170-D24V AC/DC TR-61928
240V AC TR-61921SINGLE SHOT 120V AC/DC TR-61722Power Trigger 12V AC/DC TR-61726
24V AC/DC TR-61728240V AC TR-61721
WATCHDOG 120V AC/DC TR-61822Power Trigger 12V AC/DC TR-61826(Retriggerable 24V AC/DC TR-61828Single Shot) 240V AC TR-61821
DIAGRAM 2
u Each unit has 16 timingranges built-in
u Selecting a range is easyusing a rotary switch (nomath is required or DIPswitches to set)
u Timing ranges up to 2 hours
u Uses industry-standard11 pin octal sockets
u 10A DPDT output contacts
u
TIME DELAY RELAYSTime Ranger TM Programmable
Multi-Range Plug-inOff Delay, Single Shot & Watchdog
Dial TimingSetting Range
A 0.1 - 0.25 Sec.B 0.2 - 0.5 Sec.C 0.3 - 1 Sec.D 0.5 - 2 Sec.E 1 - 4 Sec.F 2 - 8 Sec.G 4 - 15 Sec.H 8 - 30 Sec.I 15 - 60 Sec.J 30 - 120 Sec.K 1 - 4 Min.L 2 - 8 Min.M 4 - 15 Min.N 8 - 30 Min.O 15 - 60 Min.P 30 - 120 Min.
Timing Ranges
Select one of the 16 built-in time ranges by setting the rotary switchper a chart on the unit and adjust within that range using the knobon top:
SINGLE KNOB UNITS
withappropriate
socket
n See Pages 32-33 for definitions & explanations of Timing Functions.
DIAGRAM 4
Sockets & Accessories−Page 58 Application Data−Page 43Dimensions−Page 43 Standard Modifications−Pages 50-51
42
TIME DELAY RELAYSTime Ranger TM ProgrammableMulti-Range Plug-inRepeat Cycle & Delayed Interval
u Each unit has 16 timingranges built-in
u Selecting a range is easyusing a rotary switch (nomath is required or DIPswitches to set)
u Timing ranges up to 24hours
u Independently selectable &adjustable ON & OFF timeson dual knob timers
u Uses industry-standard 8 or11 pin octal sockets
u 10A DPDT output contacts
u
DUAL KNOB UNITS *INPUT VOLTAGE PRODUCT WIRING/
FUNCTIONn 50/60Hz. NUMBER SOCKETSREPEAT CYCLE 120V AC/DC TR-63122
(OFF Time First Followed 12V AC/DC TR-63126 8 PIN OCTALBy ON Time 24V AC/DC TR-63128 70169-D
and Repeating) 240V AC TR-63121REPEAT CYCLE 120V AC/DC TR-65122
(ON Time First Followed 12V AC/DC TR-65126By OFF Time 24V AC/DC TR-65128
and Repeating) 240V AC TR-65121DELAYED INTERVAL 120V AC/DC TR-66122(OFF Time Followed by 12V AC/DC TR-66126
ON Time Followed by OFF 24V AC/DC TR-66128State Until Reset) 240V AC TR-66121
11 PIN OCTALDELAYED INTERVAL 120V AC/DC TR-66522 70170-DControl Switch Trigger 12V AC/DC TR-66526(OFF Time / ON Time / 24V AC/DC TR-66528OFF State Until Reset) 240V AC TR-66521
* All Dual Knob units have independently selectable & adjustable ON & OFF times.
Dial TimingSetting Range
A 0.6 - 2.5 Sec.B 1.5 - 5 Sec.C 2.5 - 10.5 Sec.D 5 - 21 Sec.E 10 - 42 Sec.F 0.4 - 1.4 Min.G 0.7 - 2.8 Min.H 1.5 - 5.5 Min.I 3 - 11 Min.J 5.5 - 22.5 Min.K 11 - 45 Min.L 0.4 - 1.5 Hr.M 0.8 - 3 Hr.N 1.5 - 6 Hr.O 3 - 12 Hr.P 6 - 24 Hr.
Timing Ranges
Select one of the 16 built-in time ranges by setting the rotary switchper a chart on the unit and adjust within that range using the knobon top:
DUAL KNOB UNITS
withappropriate
socket
n See Pages 32-33 for definitions & explanations of Timing Functions.
DIAGRAM 1
DIAGRAM 2
Sockets & Accessories−Page 58 Application Data−Page 43Dimensions−Page 43 Standard Modifications−Pages 50-51
43
Insulation Voltage:2,000 volts
Output Contacts:DPDT 10A @ 240V AC/28V DC,1/2HP @ 240V AC, 1/3HP @ 120V ACB300 & R300; AC15 & DC13
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Compatibility:On all units triggered by input voltage or by a control switch, donot use a solid state switch to initiate the timing sequence-problems with leakage current could occur. On all units with apower trigger, do not use a solid state switch with leakagecurrent exceeding 0.5ma. Contact Macromatic Controls foradditional information.
Triggering Off Delay, Single Shot or Watchdog Units:Timing sequence must be initiated only after input voltage isapplied to unit. Minimum required trigger switch closure time is0.1 seconds.
Approvals:
Application Data
File #E109466
Dimensions
Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.DC Operation: +10/-15% of nominal.
Load (Burden):2 VA
Setting Accuracy:Maximum Setting (Adjustable): +5%, -0%Minimum Setting (Adjustable): +0%, -50%
Repeat Accuracy (constant voltage and temperature):> 2 Seconds Delay +0.1%0.1 - 2 Seconds Delay +2%
Reset Time:On Delay/Interval/Repeat Cycle/Delayed Interval: 0.1 SecondsOff Delay/Single Shot/Watchdog/Triggered Delayed Interval: 0.04 Seconds
Start-up Time:(Time from when power is applied until unit is timing)120 & 240V units 0.05 Seconds12, 24 & 48V units 0.08 Seconds
Maintain Function Time:(Time unit continues to time after power is removed)0.01 Seconds for all units
Temperature:12-120V Input Voltage: -28o to 65oC (-18o to 150oF)240V Input Voltage: -28o to 50oC (-18o to 122oF)
File #LR45565 Low Voltage &EMC Directives
EN60947-1, EN60947-5-1
TIME DELAY RELAYSTime Ranger TM Programmable
Multi-Range Plug-inApplication Data & Dimensions
withappropriatesocket
File #E109466
2.4(60)
1.7(43)
2.9(74)
3.5(89)
All Dimensions inInches (Millimeters)
44
TIME DELAY RELAYSCompact Non-ProgrammablePlug-in
u Compact, economical designwith standard features forbasic applications
u 6 separate timing rangesfrom 0.2 to 300 seconds
u 5A SPDT output contacts
u Uses industry-standard 8 pinoctal sockets
u
PRODUCTINPUT NUMBER ** WIRING/
FUNCTION n VOLTAGE SOCKETl
ON DELAY 120V AC SS-6262-** 8 Pin Octal12V AC/DC SS-6266-** 70169-D24V AC/DC SS-6268-**
INTERVAL ON 120V AC SS-8062-**12V AC/DC SS-8066-**24V AC/DC SS-8068-**
DIAGRAM 5OFF DELAY 120V AC SS-8562-** 8 Pin Octal
12V AC/DC SS-8566-** 70169-D24V AC/DC SS-8568-**
SINGLE SHOT 120V AC SS-8762-**12V AC/DC SS-8766-**24V AC/DC SS-8768-**
DIAGRAM 6
l See Page 58 for Sockets & Accessories.
COMPLETE PRODUCTNUMBER USING 2 DIGIT CODE
FROM TABLE BELOW LEFT
Temperature:0o to 60oC (32o to 140oF)
Compatibility:Do not use a solid state switch toinitiate the timing sequence-problemswith leakage current could occur.Contact Macromatic Controls foradditional information.
Transient Protection:10,000 volts for 20 microseconds
Output Contacts:SPDT 5A Resistive @ 120V AC/28V DC, 1/6HP @ 120VAC
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Approvals:
Timing Ranges
** TIMING RANGE TABLECOMPLETE PRODUCT NUMBER USINGTWO DIGIT CODE FROM TABLE BELOW
i.e., SS-6262-04Time Delay Range Code 0.2 - 5 Sec. 04 0.5 - 15 Sec. 06 1 - 30 Sec. 07 2 - 60 Sec. 08 6 - 180 Sec. 10 10 - 300 Sec. 12
For Fixed Time Delay: (at no additionalcharge), add suffix “F” and time delaydesired to basic Product Number, i.e.,SS-6262-F5S is an On Delay fixed at 5seconds.
Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.DC Operation: +10/-15% of nominal.
Load (Burden):Less than 3 VA
Setting Accuracy:Maximum Setting: +10%, -0%Minimum Setting: +0%, -50%Fixed Time Delay: > 2 Seconds +2%
0.1 - 2 Seconds +5%
Repeat Accuracy:> 2 Seconds Delay +2%0.1 - 2 Seconds Delay +5%
Reset Time:0.2 Seconds
Triggering Off Delay & Single Shot Units:Timing sequence must be initiated only after inputpower is applied to unit. Minimum requiredtrigger switch closure time is 0.1 seconds.
Application Data
File #E109466
2.2 (56)1.4(36)
1.4 (36)
2.4 (61)
n See Pages 32-33 for definitions & explanations of Timing Functions.
All Dimensions inInches (Millimeters)
with appropriate socket
with appropriatesocket
45
u Industry-standard .187" quickconnect terminals
u On Delay or Off Delay timingfunctions
u 3 separate timing ranges upto 300 seconds
u 12A DPDT output contacts
u
Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.DC Operation: +10/-15% of nominal.
Load (Burden):Less than 3 VA.
Setting Accuracy:Maximum Setting: +10%, -0%Minimum Setting: +0%, -50%Fixed Time Delay: > 2 Seconds +2%
0.1 - 2 Seconds +5%
Repeat Accuracy:> 2 Seconds Delay +2%0.1 - 2 Seconds Delay +5%
Compatibility:On Off Delay units, do not use a solid stateswitch to initiate the timing sequence-problemswith leakage current could occur. ContactMacromatic Controls for additional information.
Recycle Time: 0.1 Seconds
Temperature: -28o to 65oC (-20o to 150oF)
Application Data
n See Pages 32-33 for definitions & explanations of Timing Functions.l See Page 58 for Sockets & AccessoriesFor Fixed Time Delay: (at no additional charge), add letter "F" and time delay desired to basicProduct Number, i.e., SS-40222-F5S, is an On Delay with time delay fixed at 5 seconds.
Triggering Off Delay Timers:Timing sequence must be initiated onlyafter input power is applied to unit.Minimum required trigger switch closuretime is 0.1 seconds.
Transient Protection:10,000 volts for 20 microseconds
Output Contacts:DPDT 12A Resistive @ 240V AC/30V DC, 1/2HP @240VAC
Life:Mechanical: 10,000,000 operationsFull Load: 30,000 operations
Approvals:
DIAGRAM 26
File#E109466
File#LR45565
DIAGRAM 25
INPUT TIME DELAY PRODUCT WIRING/FUNCTION n VOLTAGE RANGE NUMBER SOCKETl
ON DELAY 120V AC/DC 0.1-10 Sec. SS-40222-05 .187” Quick Connect1-180 Sec. SS-40222-10 70171-D3-300 Sec. SS-40222-12
24V AC/DC 0.1-10 Sec. SS-40228-051-180 Sec. SS-40228-103-300 Sec. SS-40228-12
OFF DELAY 120V AC/DC 0.1-10 Sec. SS-41622-05 .187” Quick Connect1-180 Sec. SS-41622-10 70171-D3-300 Sec. SS-41622-12
24V AC/DC 0.1-10 Sec. SS-41628-051-180 Sec. SS-41628-103-300 Sec. SS-41628-12
TIME DELAY RELAYSNon-Programmable with
Quick Connect Terminals
Low Voltage &EMC Directives
EN60947-1,EN60947-5-1
All Dimensions inInches (Millimeters)
2.4 (60)
1.7(43)
2.9(74) 3.5
(89)
with appropriatesocket
with appropriatesocket
46
Single Function ProductsINPUT PRODUCT WIRING/
FUNCTION VOLTAGE NUMBER SOCKETSON DELAY 120V AC/DC TD-70222
12V AC/DC TD-70226 8 PIN OCTAL24V AC/DC TD-70228 70169-D
240V AC TD-70221INTERVAL ON 120V AC/DC TD-70522
12V AC/DC TD-7052624V AC/DC TD-70528
240V AC TD-70521FLASHER 120V AC/DC TD-70822
12V AC/DC TD-7082624V AC/DC TD-70828 DIAGRAM 1
240V AC TD-70821OFF DELAY 120V AC/DC TD-71622 11 PIN OCTAL
12V AC/DC TD-71626 70170-D24V AC/DC TD-71628
240V AC TD-71621SINGLE SHOT 120V AC/DC TD-71522
12V AC/DC TD-7152624V AC/DC TD-71528
240V AC TD-71521
DIAGRAM 2
u Available in either Single-Function or Multi-Functionversions (with five user-selectable modes)
u Pushbutton Thumbwheelsfor digital set of time delay &function (TD-781 series only)
u 50ms - 999 hour program-mable time range
u Uses industry-standard 8 or11 pin octal sockets
u 10A DPDT output contacts
u LED indicates timing modeand time out conditions
u
TIME DELAY RELAYSTime Ranger TM Digital-SetProgrammable Multi-RangePlug-in
withappropriate
socket
Multi-Function ProductINPUT PRODUCT WIRING/
FUNCTION VOLTAGE NUMBER SOCKETSMULTI-FUNCTION 120V AC/DC TD-78122 11 PIN OCTAL(5 Field-Selectable 12V AC/DC TD-78126 70170-D
Functions in one unit) 24V AC/DC TD-78128u On Delay 240V AC TD-78121u Off Delayu Interval Onu Single Shotu Flasher
DIAGRAM 121
Sockets & Accessories−Page 58 Application Data−Page 47Dimensions−Page 47
The TD-7 series of time delay relays offer an easy and accurate way to select any timedelay between 50ms & 999 hours. Programming is accomplished by using a pushbuttonthumbwheel to select one of seven built-in time ranges and three pushbutton thumbwheelsto digitally set the time delay required. This method provides a greater setting accuracythan is found on other units with an analog potentiometer. An LED indicates timing modeand time out condition.
The TD-7 series comes in two versions: a single function product or a multi-functionproduct. The TD-781 multi-function unit has a fifth pushbutton thumbwheel to select one offive built-in functions.
Single-FunctionMulti-Function
47
Output Contacts:DPDT 10A @ 240V AC/28V DC,1/2HP @ 240V AC, 1/3HP @ 120V ACB300 & R300; AC15 & DC13
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Compatibility:Do not use a solid state switch to initiate the timing sequence-problems with leakage current could occur. Contact Macro-matic Controls for additional information.
Triggering Off Delay or Single Shot Units:Timing sequence must be initiated only after input voltage isapplied to unit. Minimum required trigger switch closure time is0.1 seconds.
LED:Flasher Mode: Flashes during “ON” time; continuous on
during “OFF” timeAll Other Modes: Flashes during timing; continuous on after
time out.
Approvals:
Application Data
Dimensions
Voltage Tolerance:AC Operation: +10/-15% of nominal at 50/60 Hz.DC Operation: +10/-15% of nominal.
Load (Burden):3 VA
Setting Accuracy: +1% of set time or +50ms, whichever is greater.
Repeat Accuracy (constant voltage and temperature):+0.1% of set time or +0.02 seconds, whichever is greater.
Reset Time:On Delay/Interval/Flasher: 0.1 SecondsOff Delay/Single Shot: 0.04 Seconds
Start-up Time:(Time from when power is applied until unit is timing)120 & 240V units 0.05 Seconds12, 24 & 48V units 0.08 Seconds
Maintain Function Time:(Time unit continues to time after power is removed)0.01 Seconds for all units
Temperature:12-120V Input Voltage: -28o to 65oC (-18o to 150oF)240V Input Voltage: -28o to 50oC (-18o to 122oF)
Insulation Voltage:2,000 volts
TIME DELAY RELAYSTime Ranger TM Digital-Set
Programmable Multi-Range Plug-inApplication Data & Dimensions
withappropriatesocket
File #E109466
File #E109466 File #LR45565 Low Voltage &EMC Directives
EN60947-1, EN60947-5-1
All Dimensions inInches (Millimeters)2.4
(60)
2.9(74)
3.0(77)
1.7(43)
48
TIME DELAY RELAYSTime Ranger TM IIIDigital-SetMulti-FunctionMulti-Range
u 8 field-selectable functions inone unit
u Push-button thumbwheels fordigital-setting of time delay
u Universal AC/DC inputvoltage
u LCD display
u 0.1 Second to 9,990 Hoursprogrammable timing range
u Panel, track or surfacemounting
u 1/16 DIN style case
u 3A SPDT output contacts
u
INPUT PRODUCT WIRING/FUNCTION VOLTAGE NUMBER SOCKETSn
8 FIELD- SEE DIAGRAMSSELECTABLE 24-240V AC 50/60Hz 9816U1 ON PAGE 49FUNCTIONSu & 12-240V DC 11 Pin Octal
Voltage Tolerance:+10% of rated voltage.
Load (Burden):Less than 3 VA
Repeat Accuracy:+0.3%, +0.05 seconds (includes variationdue to voltage and temperature changes).
Setting Accuracy:+0.5%, +0.05 seconds maximum.
Recycle Time:0.5 seconds maximum.
Application Data
Temperature:-10o to 55oC (14o to 131oF)
Output Contacts:SPDT 3A Resistive @ 250V ACSPDT 5A Resistive @ 28V DC
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Approvals:
File #E170213 File #LR701134
Sockets & Accessories
PANEL CUTOUT
PRODUCTDESCRIPTION NUMBER11 Pin Octal Socket (Surface or Track Mounting) 70170-Dn11 Pin Octal Socket (Back Mounting) 70300Panel Mounting Adaptor 70310Protective Cover 70320
70300 70310
70320
u Functions Include: On Delay, Flasher, Interval/Off Delay, Off Delay (2 Versions), Interval,Delayed Interval and On Delay/Off Delay (see Page 49 for Further Details)
n See below for Sockets & Accessories.
All dimensions are inches(millimeters)
n See Page 58
All Dimensions inInches
(Millimeters)
49
FUNCTION OPERATION TIMING CHART
Upon application of control power, the preset time begins. At the end of the preset time, therelay contacts transfer. Control power must be removed and reapplied to reset the timedelay relay.
Upon application of control power, the time delay relay is ready to accept trigger signals.Upon closure of the Start switch, the preset time begins. At the end of the preset time, therelay contacts transfer. Any closure of the Start switch is ignored until reset. The time delayrelay is reset by closing the Reset switch or removing the control power.
Upon application of control power, the preset time begins. At the end of the preset time, therelay contacts transfer and remain in that condition for the preset time. At the end of thistime, the relay contacts return to their normal condition and the sequence repeats untilcontrol power is removed.
Upon application of control power, the time delay relay is ready to accept trigger signals.Upon closure of the Start switch, the preset time begins. At the end of the preset time, therelay contacts transfer and remain in that condition for the preset time. At the end of thistime, the relay contacts return to their normal condition and the sequence repeats until theReset switch is closed or control power is removed.
Upon application of control power, the time delay relay is ready to accept trigger signals.Upon closure or opening of the Start switch, the relay contacts transfer and the preset timebegins. At the end of the preset time, the relay contacts return to their normal condition.Any closure or opening of the Start switch during timing causes the time to reset.
Upon application of control power, the time delay relay is ready to accept trigger signals.Upon closure of the Start switch, the relay contacts transfer and hold. Upon release of theStart switch, the preset time begins. At the end of the preset time, the relay contacts returnto their normal condition. Any application of the Start switch will reset the time.
Upon application of control power, the relay contacts transfer and the preset time begins.At the end of the preset time, the contacts return to their normal condition. Control powermust be removed and reapplied to reset the time delay relay.
Upon application of control power, the time delay relay is ready to accept trigger signals.Upon closure of the Start switch, the relay contacts transfer and the preset time begins. Atthe end of the preset time, the contacts return to their normal condition. Any closure of theStart switch is ignored until reset. The time delay relay is reset by closing the Reset switchor removing the control power.
Upon application of control power, the preset time begins. At the end of the preset time, therelay contacts transfer and remain in that condition for the preset time. At the end of thistime, the relay contacts return to their normal condition and the sequence stops. Powermust be removed and reapplied to reset the time delay relay.
Upon application of control power, the time delay relay is ready to accept trigger signals. Atthe end of the preset time, the relay contacts transfer and remain in that condition for thepreset time. At the end of this time, the relay contacts return to their normal condition andthe sequence stops. Power must be removed and reapplied to reset the time delay relay.
Upon application of control power, the time delay relay is ready to accept trigger signals.Upon closure of the Start switch, the preset time begins. At the end of the preset time, therelay contacts will transfer. Upon opening of the Start switch, the preset time begins. At theend of the preset time, the output contacts return to their normal condition.
Upon application of control power, the time delay relay is ready to accept trigger signals.Closure of the Start switch is ignored. Upon release of the Start switch, the relay contactstransfer and the preset time begins. At the end of the preset time, the relay contacts returnto their normal condition. Opening the Start switch during timing resets the time.
MODE A On-Delay Standard(Diagram 7)
Triggered(Diagram 9)
MODE B Flasher Standard(Diagram 7)
Triggered(Diagram 9)
MODE C Interval/ (Diagram 8)Off-Delay
MODE D Off-Delay (I) (Diagram 8)
MODE E Interval Standard(Diagram 7)
Triggered(Diagram 9)
MODE F Delayed Standard Interval (Diagram 7)
Triggered(Diagram 9)
MODE H Off-Delay (II) (Diagram 8)
MODE G On-Delay/ (Diagram 8)Off-Delay
DIAGRAM 8 DIAGRAM 9DIAGRAM 7
TIME DELAY RELAYSTime Ranger TM III Digital-Set Multi-Function
Multi-Range
50
TIME DELAY RELAYSStandard Modifications
All of our Catalog-Listed Time Delay Relays can be adapted for different applications. Below is a list of various Situa-tions, Solutions and Ordering Information to illustrate many of these modifications. Please contact Macromatic if youhave any questions or need additional information before ordering any products with these modifications.
Situation: I know exactly what timedelay I need and therefore, do not needa unit with an adjustable time range.
Situation: I have an 11 pin time delayrelay where all the pins match the wiringdiagram shown in your catalog (andbelow) except the control switch (triggerswitch) is connected to pins other thanpins 5 and 6.
Situation A: I want to mount a timedelay relay in an enclosure, but wouldlike to adjust the time delay from outsidethe enclosure instead of having to openthe door.
Situation B: I need to replace a timedelay relay that is already connected to aremote potentiometer with a knownvalue.
Solution: Macromatic offers productswhere the adjustment potentiometer isremoved and the unit comes with onespecific (non-adjustable) time range, i.e.,5 seconds, 1 minute, etc. These areproducts with a “fixed” time delay.
Solution: Macromatic can build a timedelay relay triggered by a control switch(i.e., Off Delay, Single Shot, Watchdog)with any pin configuration required tomeet your application.
Solution: Macromatic can build mosttime delay relays with an optional remoteadjustment feature. The potentiometerusually supplied with the product isremoved, and the product is setup foruse with a customer-supplied remotepotentiometer to be connected to pins 5& 7. Units that are normally 8 pin willhave an 11 pin configuration. Units thatare normally 11 pin will have the controlswitch connected between pins 2 & 6(instead of the standard 5 & 6). For othercontrol switch pin configurations, contactMacromatic for ordering information.
To order: Any time delay relay fixed ata factory set delay time, replace thenormal two digit suffix indicatingadjustable time range with the suffixFxxt where xx is the specific time delaydesired and t is the time interval(seconds, minutes or hours), i.e., aTR-51622-F10S is an Off Delay fixed at10 Seconds.
To order: Any time delay relay with aspecial control switch configuration, usethe following chart to determine whichsuffix provides the correct configurationneeded, i.e., a TR-51522-05T9 is aSingle Shot with the control switchbetween pins 7 & 10 instead of 5 & 6:
To order: Any time delay relay with aremote adjustment feature and an 11pin header, use the following chart todetermine which suffix matches thevalue of the remote potentiometer, i.e.,a TR-50222-04R6 is an On Delay withan 11 pin header, setup for a 750Kremote potentiometer to be connectedto pins 5 & 7:
** NOTE: A 500K potentiometer (R5) is theonly value that can be used with a TimeRanger Programmable Time Delay Relay(those catalog numbers that begin with aTR-6).
Normal 8 pin productwith 11 pin configura-tion for Remote Adjust
Normal 11 pin product withconfiguration for Remote
Adjust (2-6 Control Switch)
Standard 11 pin timedelay relay, i.e., Off
Delay, Single Shot, orWatchdog
Control ControlSwitch Switch
Connected Add Connected AddTo Pins Suffix * To Pins Suffx *
2-5 T1 5-10 T62-6 T2 6-7 T72-7 T3 6-10 T85-7 T5 7-10 T9
* NOTE: These suffixes apply only todifferent control switch pin configuations.The input voltage and output pin configura-tions remain as shown at left. For otherconfigurations, contact Macromatic.
Standard 11 pin modifiedwith a 2-6 control switch
(Suffix T2)
Standard 11 pin modifiedwith a 6-10 control switch
(Suffix T8)
NOTE: The configuration of the input voltageand output contacts has not been changed.
Remote Pot Add Remote Pot AddValue Suffix Value Suffix250K R3 1.5M R8300K R4 2M R9
500K ** R5 2.5M R10750K R6 5M R11 1M R7
51
TIME DELAY RELAYSStandard Modifications
Solution: Macromatic can build any TRSeries time delay relay that is normallyan 11 pin product with an 8 pin base.This modified product will be SPDT onlyinstead of the normal DPDT of the 11 pinversion.
Solution: Macromatic can build anytime delay relay that is normally an 8 pinproduct with an 11 pin base.
Solution: A time delay relay with a fastreset of 0.05 seconds is available.
Solution: Macromatic can modify oursingle knob programmable Time Rangerproducts that normally come with a 2hour maximum setting to have a range of0.6 seconds to 24 hours (same as ourdual knob units).
Solution: As standard, power triggeredtime delay relays must use the samevoltage for both input voltage & triggervoltage. However, Macromatic offers anoption on any power triggered unit tohave a voltage different than the inputvoltage.
Solution: Macromatic offers a longdistance control switch option. Thisoption will minimize the problems relatingto noise that could caused false trigger-ing of the time delay relay.
Situation: I want to use an 8 pin socket,but according to your catalog, the timedelay relay I have selected is an 11 pinunit.
Situation: I have an 11 pin socket inplace and wired, but according to yourcatalog, the time delay relay I want touse is an 8 pin unit.
Situation: I need the time delay relay torecycle faster than the factory standardof 0.1 seconds.
Situation: I need a longer time delayrange than the 2 hour maximum avail-able on the Macromatic programmableTime Ranger single knob functions, i.e.,On Delay, Interval On, Off Delay, etc.
Situation: I have a power triggered timedelay relay (Off Delay, Single Shot orWatchdog) with 120VAC input voltage,but would like to trigger it with a 5VDCcomputer generated voltage.
Situation: The control switch used toinitiate a time delay relay is a greatdistance from the product and I amexperiencing problems triggering therelay.
To order: See Page 38 for orderinginformation. NOTE: this option isavailable on TR Series products only.
To order: Any standard 8 Pin timedelay relay modified to an 11 Pin base,add the suffix H to the end of theProduct Number, i.e., a TR-60222-H is aprogrammable On Delay time delayrelay with an 11 pin base configured asshown at left.
To order: Any time delay relay with afast reset time, add the suffix N to theend of the Product Number, i.e., aTR-60222-N is an programmable OnDelay with a fast reset time of 0.05seconds.
To order: Any single knob program-mable Time Ranger time delay relaywith a 24 hour time range, add the suffixU to the end of the Product Number, i.e.,a TR-60222-U would be an On Delaywith a programmable time range of 0.6seconds - 24 hours.
To order: Any time delay relay with aspecial power trigger voltage, use thefollowing chart to determine which suffixprovides the correct power triggervoltage, i.e., a TR-51922-05TV05 is aPower Triggered Off Delay with 120Vinput voltage and a 5V trigger voltage:
To order: Any time delay relay with along distance control switch option, addthe suffix Y to the end of the ProductNumber, i.e., a TR-61622-Y is aprogrammable Off Delay with a longdistance control switch.
11 Pin DPDT 8 Pin SPDT
Standard 8 Pin DPDT Special 11 Pin DPDT
Voltage Input AddNeeded (AC/DC) Suffix
5 TV0512 TV1224 TV24120 TV120
Other Call MacromaticNormal Power Trigger Special Power Trigger
52
ALTERNATING RELAYSSPDT & DPDT
Alternating Relays are used in special applications where the optimization of loadusage is required by equalizing the run time of two loads. This alternating action isinitiated by a control switch, such as a float switch, manual switch, timing relay,pressure switch, or other isolated contact. Each time the initiating switch isopened, the output relay contacts will change state, thus alternating the two loads.Two LED indicators show the status of the output relay.
The Alternating Relays listed on this page can be used with one or two controlswitches & are available in either SPDT or DPDT output configurations (see"Typical Installations" on Page 53 for more information). For products with DPDTCross-Wired output configurations to be used with one, two or three controlswitches, see Page 54.
Each version is available with an optional three position selector switch. Thisallows the unit to alternate the two loads as normal, or lock the relay to one load orthe other. By locking the Alternating Relay to one load, the other load can beremoved for service without rewiring the first load for continuous operation. Theselector switch has a low profile to prevent any accidental changes in status.
n See Page 58 for Sockets & Accessories.
OUTPUT CONTROL PRODUCTCONTACTS VOLTAGE NUMBER WIRING/SOCKETnSPDT 12V AC ARP012A6w/o Selector Switch 24V AC ARP024A6
120V AC ARP120A6 8 Pin Octal240V AC ARP240A6 70169-D
SPDT 12V AC ARP012A6Rw/ Selector Switch 24V AC ARP024A6R
120V AC ARP120A6R240V AC ARP240A6R
DPDT 12V AC ARP012A2w/o Selector Switch 24V AC ARP024A2
120V AC ARP120A2 11 Pin Octal240V AC ARP240A2 70170-D
DPDT 12V AC ARP012A2Rw/ Selector Switch 24V AC ARP024A2R
120V AC ARP120A2R240V AC ARP240A2R
DIAGRAM 17
DIAGRAM 18
u For duplex loads
u Can be used with one or twoControl Switches
u Control voltages of 12, 24,120 & 240V AC
u Compact plug-in designutilizing industry-standard 8or 11 pin octal socket
u 10A SPDT or DPDT OutputConfiguration
u Optional low profile selectorswitch to lock in onesequence
u 2 LED’s indicate relay status
u
with appropriatesocket
53
ALTERNATING RELAYSSPDT & DPDT
Application Data & Dimensions
Typical Installations
In the off state (Figure A), the Control Switch is open, the Alternating Relay is in the LOAD A position, and both loads (M1 & M2)are off. When the Control Switch closes, it energizes the first load (M1). The red LED marked “LOAD A” glows. As long as theControl Switch remains closed, M1 remains energized. When the Control Switch opens, the first load (M1) is turned off and theAlternating Relay toggles to the LOAD B position. When the Control Switch closes again, it energizes the second load (M2). Thered LED marked “LOAD B” glows. When the Control Switch opens, the second load (M2) is turned off, the Alternating Relaytoggles back to the LOAD A position, and the process can be repeated again. On relays with DPDT contacts, two pilot lights canbe used for remote indication of LOAD A or LOAD B status.
To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along with two auxiliary contacts isrecommended as shown in Figure B.
Application Data
Dimensions
1.7(43)
2.9(74)
3.1(79)
2.4 (60)
All Dimensions inInches (Millimeters)
Voltage Tolerances: +10%/-15% of control voltage at 50/60Hz.
Load (Burden): Less than 3VA
Output Contacts:10A Resistive @ 240V AC/30V DC,1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240VAC (N.C.)
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Temperature: -28o to 65oC (-20o to 150oF)
Transient Protection: 10,000 volts for 20 microseconds
Indicator LED's: 2 LED's marked LOAD A and LOAD B
Optional Selector Switch Settings:ALTERNATELOCK LOAD ALOCK LOAD B
Approvals:
File #LR45565File #E109466
withappropriatesocketFile #E109466
Figure A Figure B
54
ALTERNATING RELAYSDPDT Cross-Wired
u For duplex loads
u Can be used with two orthree Control Switches
u Control voltages of 12, 24,120 & 240V AC
u Compact plug-in designutilizing industry-standard8 pin octal socket
u 10A DPDT Cross-WiredOutput Configuration whenadditional capacity isrequired
u Optional low profile selectorswitch to lock in onesequence
u 2 LED’s indicate relay status
u
Alternating Relays are used in special applications where the optimization of loadusage is required by equalizing the run time of two loads. They are also usedwhere additional capacity is required in case of excess load requirements. Thisalternating action is initiated by a control switch, such as a float switch, manualswitch, timing relay, pressure switch, or other isolated contact. Each time theinitiating switch is opened, the output relay contacts will change state, thus alternat-ing the two loads. Two LED indicators show the status of the output relay.
The Alternating Relays listed on this page are available in DPDT Cross-Wiredoutput configurations, and can be used with one, two or three control switches.See "Typical Installations" on Page 55 for more information. For products withSPDT or DPDT output configurations, see Page 52.
Each version is available with an optional three position selector switch. Thisallows the unit to alternate the two loads as normal, or lock the relay to one load orthe other. By locking the Alternating Relay to one load, the other load can beremoved for service without rewiring the first load for continuous operation. Theselector switch has a low profile to prevent any accidental changes in status.
n See Page 58 for Sockets & Accessories.
OUTPUT CONTROL PRODUCTCONTACTS VOLTAGE NUMBER WIRING/SOCKETn
DPDT CROSS- 12V AC ARP012A3 8 Pin OctalWIRED 24V AC ARP024A3 70169-Dw/o Selector Switch 120V AC ARP120A3
240V AC ARP240A3
DPDT CROSS- 12V AC ARP012A3RWIRED 24V AC ARP024A3Rw/ Selector Switch 120V AC ARP120A3R
240V AC ARP240A3R
DIAGRAM 19
with appropriatesocket
55
Application Data
ALTERNATING RELAYSDPDT Cross-Wired
Application Data & Dimensions
Typical Installations
In the off state, both the LEAD Control Switch and the LAG Control Switch are open, the Alternating Relay is in the LOAD Aposition, and both loads are off. When the LEAD Control Switch closes, it energizes the first load (M1). The red LED marked“LOAD A” glows. As long as the LEAD Control Switch remains closed, M1 remains energized. If the LAG Control Switch closes, itenergizes the second load (M2). When the LAG Control Switch opens, the second load (M2) is turned off. When the LEADControl Switch opens, the first load (M1) is turned off and the Alternating Relay toggles to the LOAD B position. When the LEADControl Switch closes, it turns on the second load (M2). The red LED marked “LOAD B” glows. If the LAG Control Switch closes,it will energize the first load (M1). When the LAG Control Switch opens, the first load (M1) is turned off. When the LEAD ControlSwitch opens, the second load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the process canbe repeated again.
To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along with two auxiliary contacts isrecommended as shown in Figure B.
Dimensions
1.7(43)
2.9(74)
3.1(79)
2.4 (60)
All Dimensions inInches (Millimeters)
Voltage Tolerances: +10%/-15% of control voltage at 50/60Hz.
Load (Burden): Less than 3VA
Output Contacts:10A Resistive @ 240V AC/30V DC,1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240VAC (N.C.)
Life:Mechanical: 10,000,000 operationsFull Load: 100,000 operations
Temperature: -28o to 65oC (-20o to 150oF)
Transient Protection: 10,000 volts for 20 microseconds
Indicator LED's: 2 LED's marked LOAD A and LOAD B
Optional Selector Switch Settings:ALTERNATELOCK LOAD ALOCK LOAD B
Approvals:
Figure A Figure B
File #LR45565File #E109466
withappropriatesocketFile #E109466
56
ALTERNATING RELAYSFor 3 Switch Applications(Lead-Lag-Stop)Sequence On-Simultaneous OFF
u Works with 3 ControlSwitches - LEAD, LAG andSTOP
u Utilizes Sequence On -Simultaneously Off(S.O.S.O.) Operation
u Replaces Separate Compo-nents in Duplex Panel,Saving Space and ReducingLabor
u Protects against Failures ofBoth STOP & LEADSwitches
u Control Voltages of 12, 24,120 & 240V AC
u Compact Plug-in DesignUtilizing Industry-Standard 8Pin Octal Socket
u Optional low profile selectorswitch to lock in one se-quence
u 2 LED’s indicate relay status
u
Macromatic Alternating Relays for Three Switch Applications offer a number ofunique advantages over standard duplex units:
l Combines standard DPDT cross-wired Alternating Relay, contactor auxiliarycontacts and control relay into one compact & economical product, thusreducing the cost of the panel by saving space, reducing the number of com-ponents and minimizing assembly labor.
l Works with three switches instead of just one or two − LEAD, LAG and STOP.l Sequence On - Simultaneous Off (S.O.S.O.) Operation − the two loads are
energized sequentially, but remain on together until the STOP switch isopened.
l Protects against failure of the STOP and LEAD switches − if both switches fail,the two pump motors will be energized simultaneously when the LAG switch isclosed.
See "Typical Installations" on Page 57 for more information.
Alternating Relays from Macromatic are available with an optional three positionselector switch. This allows the unit to alternate the two loads as normal, or lockthe relay to one load or the other. By locking the Alternating Relay to one load, theother load can be removed for service without rewiring the first load for continuousoperation. The selector switch has a low profile to prevent any accidental changesin status.
OUTPUT CONTROLCONTACTS VOLTAGE PRODUCT NUMBER WIRING/SOCKETnDPDT CROSS- 12V AC ARP012A8 8 Pin OctalWIRED 24V AC ARP024A8 70169-DFor 3 Switch Operation 120V AC ARP120A8w/o Selector Switch 240V AC ARP240A8
DPDT CROSS- 12V AC ARP012A8RWIRED 24V AC ARP024A8RFor 3 Switch Operation 120V AC ARP120A8Rw/ Selector Switch 240V AC ARP240A8R
n See Page 58 for Sockets & Accessories.DIAGRAM 58
with appropriatesocket
57
Voltage Tolerances: +10%/-15% of control voltage at 50/60Hz.
Load (Burden): Less than 3VA
Output Contacts:10A Resistive @ 240V AC/30V DC,1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240VAC (N.C.)
Life:Mechanical: 10,000,000 operationsFull Load: 150,000 operations
Temperature: -28o to 65oC (-20o to 150oF)
Transient Protection: 10,000 volts for 20 microseconds
Indicator LED's: 2 LED's marked LOAD A and LOAD B
Optional Selector Switch Settings:ALTERNATELOCK LOAD ALOCK LOAD B
Approvals:
Typical Installations
DPDT Cross-Wired for Three Switch ApplicationsIn the OFF state, all three switches are open, theAlternating Relay is in the LOAD A position, and bothloads are off. No action happens with the AlternatingRelay or either load when the STOP Switch closes.When the LEAD Switch closes, Load #1 (M1) turns on.When the LAG Switch closes, Load #2 (M2) turns on.Both loads remain on as long as all three switches areclosed.
When the LAG Switch opens, Load #2 (M2) remains onbecause the STOP Switch is still closed. When theLEAD Switch opens, Load #1 (M1) remains on becausethe STOP Switch is still closed. When the STOP Switchopens, both Load #1 (M1) and Load #2 (M2) are turnedoff simultaneously. The Alternating Relay toggles to theLOAD B position. The entire cycle is then repeated, butwith Load #2 (M2) energized first followed by Load #1(M1).
This type of operation is known as “Sequence On -Simultaneously Off (S.O.S.O.)”-the two loads areenergized sequentially, but remain on together until theSTOP switch is opened.
If both the STOP Switch and LEAD Switch fail to closeand turn on the first load, both loads will be turned onsimultaneously when the LAG Switch is closed.
Dimensions
1.7(43)
2.9 (74)
3.1 (79)
2.4 (60)
ALTERNATING RELAYSFor 3 Switch Applications
Application Data & Dimensions
Application Data
All Dimensions inInches (Millimeters)
withappropriatesocket
File #E109466 File #E109466
58
SOCKETS & ACCESSORIES
Other Accessories
Sockets
* Plug-in Three-Phase Monitor Relays require a 600V-rated socket when used on system voltages greater than 300V.
Product Number70169-D *
Product Number70170-D
Product Number70171-D
Description 8 Pin Octal 11 Pin Octal 11 Pin Spade (Blade)
Ratings 10A @ 600V * 10A @ 300V 10A @ 300V
Mounting 35MM DIN Rail /Direct Panel
35MM DIN Rail /Direct Panel
35MM DIN Rail /Direct Panel
Wire/Terminations
1 or 2 #12-22 /Pressure Wire Clamps
1 or 2 #12-22 /Pressure Wire Clamps
1 or 2 #12-22 /Pressure Wire Clamps
Approvals
Dimensions
DIN Mounting Track (1 Meter Section)
Product Number 70100
All Dimensions inInches (Millimeters)
Hold Down SpringProduct Number 70166
At Macromatic, we are committedto providing you with the rightproduct, at the right time and at
the right price.
STANDARD PRODUCTSu Time Delay Relaysu Alternating Relaysu Phase Monitoring Relaysu Voltage Monitoring Relaysu Current Monitor Relays
CUSTOM DESIGNSu Save money with a dedicated design to fit
your applicationu Proprietary design protection offeredu Agency approvals available
TECHNICAL SUPPORTu Dedicated engineering teamu One-on-one assistanceu Application selection helpu Technical troubleshooting aid
u Toll free help line
CUSTOMER SERVICEu Total Quality Program responsive to your
needsu Short lead times on small quantity ordersu Never a charge for expedited deliveryu Local support through distributors & sales
representativesu No minimum orders on standard products
For Details Contact us at800-238-7474 u 262-781-3366
FAX 262-781-4433www.macromatic.com
Alternating Relays
Time Delay Relays
Phase Monitor Relays
Voltage Monitor Relays
Current Monitor Relays
The Right ProductThe Right TimeThe Right Price
Macromatic ControlsW134 N5345 Campbell Dr
Menomonee Falls, WI 53051
800-238-7474- u 262-781-3366 u Fax 262-781-4433Web: www.macromatic.com u Email: [email protected]