Industrial UPS, single and three phase output ENERTRONIC I Range

Internal power supply

UPS mains operation

UPS battery operation

Bypass operation

Parallel operation

Manual bypass

Overload

Inverter failure

Mains failure

Battery voltage low

LED Test

ENERTRONIC I

7843

70.0

5 GB

0

9/20

10

pau

s De

sign

& M

edie

n, B

ocho

lt

Subj

ect t

o al

tera

tions

. P

rinte

d on

chl

orin

e fre

e pa

per.

784370_05_enertron_i_gb_r1.qxd 01.10.2010 10:42 Uhr Seite 7

Page 2: Industrial UPS, single and three phase output ENERTRONIC... · Industrial UPS, single and three phase output ENERTRONIC I Range Internal power supply UPS mains operation UPS battery

General The requirement for power supply reliability is growing, dueto the increasing application of information and data carriersystems, text processing, automated production processesand complex data networks.

Irregularities due to loading of the public power supply bymajor users, peak-time use or by lightning strikes cannot beavoided. The result is: Mains voltage breaks, spikes and transients. (Fig. 1)

Static UPS’s are being installed increasingly for loads thatrequire AC voltages unaffected by interference on the mains e.g.

• Data processing installations • Process control computers • Air safety installations • Signalling, alarm systems • Telecommunication systems • Power- and Substations

Design Due to the use of IGBT transistors of the newest technologyin the rectifier and in the inverter, the new ENERTRONIC Irange fulfills the highest reliabilty for power supplies and isvery economical. This results in an input power factor of ≥ 0,99 and an inputdistortion factor of < 5 %.

The exceptional characteristics of this inverter in the ENERTRONIC I series results in very small dynamic voltagedeviations even in the case of one hundred percent loadchanges.

A combination of a 16-bit micro-controller and the latestpower electronics is responsible for controlling and monitoringof all rectifier, inverter and static switch functions with highestreliability. A static switch and a manual bypass switch areintegrated in the unit.

In the front of the cabinet there is a plastic foil keyboard with6 keys, 4 three coloured and 2 single coloured LED’s and amimic diagram.

ENERTRONIC I disposed for highest security

B E N N I N G W o r l d C l a s s P o w e r S o l u t i o n s2

Fig. 2: ENERTRONIC I UPS Fig. 1: Possible Irregularities

784370_05_enertron_i_gb_r1.qxd 01.10.2010 10:42 Uhr Seite 8

Page 3: Industrial UPS, single and three phase output ENERTRONIC... · Industrial UPS, single and three phase output ENERTRONIC I Range Internal power supply UPS mains operation UPS battery

ENERTRONIC I an uninterrupptible power supply

B E N N I N G W o r l d C l a s s P o w e r S o l u t i o n s 3

Function The static UPS not only has the task of supplying the connectedconsumers continuously and without interruption, but beyondthat to also provide a clear improvement of the voltage andfrequency quality in relation to the normal system. In normal

operation the load is supplied by the input autotransformer,rectifier, inverter and output transformer route. The ENERTRONIC I is designed to meet the highest UPS clas-sification VFI SS 111 in accordance with EN 62040-2.

Rectifier The rectifier consists of an IGBT bridge with power factor cor-rection (power factor = 1), converting the three phase mainsvoltage via an autotransformer (optional isolated transformer)into a controlled DC voltage to supply the inverter and torecharge the connected battery or to keep the battery in opti-mum capacity in float charge condition.

The rectifier is able to supply the fully loaded inverter and torecharge the discharged battery to 95 % of its capacity within12 hours.

The rectifier is equipped with a software controlled soft startto start the rectifier on a ramp after mains failure.

The restart of parallel systems is done in steps so that not allUPS’s are starting at the same time.

The rectifier is also equipped with an IU charging characteristicin accordance with the information of the battery manufac- turer, with the option of battery temperature compensation.

Inverter The inverter power block changes DC voltage into a single or three phase sinusoidal AC voltage with constant amplitudeand stable frequency. The output voltage is independent ofline disturbances or power failures.The unit works with an IGBT inverter bridge with pulse widthmodulation having a high efficiency in the partial load rangeas well as achieving a low distortion factor at non linear load.

In the event of mains interruption or failure, the battery con-nected to the DC input is brought in automatically and with -out interruption to supply current. If the battery becomesdischarged this is reported. If the battery discharge limit isexceeded, the inverter automatically turns off and a warningis given shortly before the discharged voltage limit is reached.

Automatic change-over of the load to the bypass mains or a suitable spare supply occurs if the supply from the inverterfalls outside the preset tolerances.

140 %

120 %

100 %

80 %

60 %

40 %

20 %

0 %0 0,2 0,4 0,6 0,8 1 0,8 0,6 0,4 0,2 0

leading laggingpower factor

Fig. 4: Available inverter apparent output power depending onpower factor

Fig. 3: Interior view

784370_05_enertron_i_gb_r1.qxd 01.10.2010 10:42 Uhr Seite 5

Page 4: Industrial UPS, single and three phase output ENERTRONIC... · Industrial UPS, single and three phase output ENERTRONIC I Range Internal power supply UPS mains operation UPS battery

B E N N I N G W o r l d C l a s s P o w e r S o l u t i o n s

Internal manual bypassEach UPS is equipped with a maintenance bypass withmanually operated switch. When operated, the ENERTRONIC Iis completely disconnected from the load. The supply to theload is now directly from the mains via the manual bypass.(Fig. 5)

ENERTRONIC Imulti utilities

4 5

Parallel OperationFor redundancy or increased output power, up to eightENERTRONIC I units can be connected in parallel, operating inan active load-sharing mode with active and passive master.

Half load parallel operation is achieved using two separatebus bars, connected with a coupling switch. The state of thecoupling switch is relayed to the microprocessor, via anauxiliary contact.

OptionFor power plant applications where higher than normal faultthree phase clearing current is required, it is possible tospecify an option for 4 x I nominal system output. Dependingon the output power, a bigger cabinet may be required.

A change back can only occur to a functioning inverter, and isin everycase uninterrupted even if the mains should fail on atest change-over.

The static bypass consists of a microprocessor-controlledanti parallel thyristor block. It can be activated manually witha push button, in order to test the change-over. The change-over from inverter to the mains and back takes place in asynchronised operation without a break.

The static bypass has an overload capability of 150 % for10 min. and 500 % (single phase output) and 1000 % (threephase output) for 100 ms.After the presence of an overload or a short-circuit, it auto-matically resets the load to the inverter, if normal operation ispossible.

Static BypassThe static bypass of the UPS facilitates uninterrupted change-over to direct mains supply (bypass mains), keeping within thespecified tolerances. The change-over can be initiated manu-ally or automatically by a control signal. The µP monitoring isautonomous and prevents incorrect operation of the UPS andany illogical switching functions of the static bypass.

Thus, for example, an uninterrupted change-over, whetherautomatic or manual, is only possible when the voltage, fre-quency and phase conditions of the inverter are synchronisedwith the bypass mains. Mains frequency deviations, which lieoutside the preset tolerances cause blocking of the change-over, or if the inverter fails, a change-over with an interruption.

outputtransformer

inputtransformer

battery(external)

outputcontactor

inputcontactormains

input

inverterrectifier

outputbreaker

inputbreaker UPS

outputbypassinput

static bypass

man. bypass

Fig. 5: Block diagram

784370_05_enertron_i_gb_r1.qxd 01.10.2010 10:42 Uhr Seite 1

Page 5: Industrial UPS, single and three phase output ENERTRONIC... · Industrial UPS, single and three phase output ENERTRONIC I Range Internal power supply UPS mains operation UPS battery

ENERTRONIC Iall-purpose

5 B E N N I N G W o r l d C l a s s P o w e r S o l u t i o n s

There is a 4-line, 80-digit LC display in the operating sectionfor reading information and/or for clear guidance by themenu. Control of the operating section takes place via thedisplay controller, which communicates over the CAN buswith the controller board.In addition, the most important operating and fault signalsare indicated by 13 single LED’s.

Rectifier:· input voltage(each phase/phase orphase/neutral conductor)

Inverter:· output voltage (withthree phase outputphase/phase or phase/neutral conductor)· frequency

Fig. 6: Front Panel

· input current of each phase· frequency

· output current (withthree phase outputof each phase)· apparent power· real power

Front PanelThe operation of the UPS is made by a plastic foil keyboardwith 6 keys, 4 three coloured and 2 single coloured LED’s.There is a mimic diagram on the operating section. Theoperating condition and any operational disturbances are re-presented by the multi colour LED’s. (Fig. 6)

Internal power supply

UPS mains operation

UPS battery operation

Bypass operation

Parallel operation

Manual bypass

Overload

Inverter failure

Mains failure

Battery voltage low

LED Test

ENERTRONIC I

Technical DataENERTRONIC I 3-1 with three phase input and single phase output - DIN Type: D400 E230/...../2 rfg-UEG....Nominal power cos. � 0,8: [kVA] 30, 40, 50, 60, 80, 100, 120

Type ENERTRONIC I UPS Nominal output power (cos. �=0,8 ind.): [kVA] 30 40 50 60 80 100 120

Inverter data ENERTRONIC I 3-1 Inverter input voltage: [V] 187 - 264 Nominal input real power (with load cos. �=0,8 ind.):

[kW] 25,5 34,4 42,5 51,1 68,1 - -

Nominal output real power (cos. �=1): [kW] 24 32 40 48 64 - -Nominal output current (cos. �=0,8): [A] 130 173 217 260 347 - -Nominal output current (cos. �=1): [A] 104 139 173 208 278 - -Nominal output voltage: [V] 230 V (adjustable ± 5%) Nominal output frequency: [Hz] 50 Transformer: galvanically isolated Voltage tolerance:

- static [%] ± 1 - dynamic with 100% load change [%] < 5

Regulation time: [msec] < 10 Angle deviation: < 1° Frequency tolerance:

- mains synchronised [%] ± 1 (synchronisation range ± 4) - self synchronised [%] ± 0,1

Distortion factor (acc. EN 62040-1): - linear load [%] < 1 - non linear load [%] < 5

Crest factor: ≥ 3 Overload: [%] 150% 60 sec., 125% 10 min.Short-circuit behaviour: [%] 300% 3 sec.

Inverter itself is short circuit proof, switch OFF after max. 3 seconds if bypass mains is not available (EN 62040)

Inverter efficiency with nominal load (cos. � 0,8):

[%] ≥ 92 ≥ 94

784370_05_enertron_i_gb_r1.qxd 01.10.2010 10:42 Uhr Seite 2

Page 6: Industrial UPS, single and three phase output ENERTRONIC... · Industrial UPS, single and three phase output ENERTRONIC I Range Internal power supply UPS mains operation UPS battery

B E N N I N G W o r l d C l a s s P o w e r S o l u t i o n s

ENERTRONIC I all-purpose

6

Battery: · voltage · charge/discharge current

Bypass:· input voltage (with three phase output phase/phase or phase/neutral conductor)

An event recorder stores each occurring event (push buttonoperation, switching events and error) with date and time. Upto 1200 entries can be stored.

The following information is indicated via 6 volt free changeover contacts:

· mains operation (mains OK) · manual bypass activated · battery operation · low battery voltage · bypass operation · common alarm

As serial interfaces a RS232 and RS485 each with MODBusprotocol is provided as standard, additionally an analogue out-put with 0 or 4 to 20 mA is included which can be programmedwith an internal value, e.g. output power.

Digital inputs: · EMERGENCY POWER · inhibit battery charging OFF (EPO) · generator operation · remote ON/OFF · inhibit bypass operation

As an option an additional relay card with 6 relays and anadditional interface card with a RS232 and RS485 can be buildin, also a Profibus interface and network interface (TCP/IP)can be added.

· remaining back up time · remaining capacity

· input current (with threephase output of eachphase) · frequency

Technical Data ENERTRONIC I 3-3 with three phase input and three phase output - DIN Type: D400 D400/...../2 rfg-UDG.... Nominal power cos. � 0,8: [kVA] 30, 40, 50, 60, 80, 100, 120

Type ENERTRONIC I UPS Nominal output power (cos. �=0,8 ind.): [kVA] 30 40 50 60 80 100 120

Inverter data ENERTRONIC I 3-3 Inverter input voltage: [V] 187 - 264 Nominal input real power (with load cos. �=0,8 ind.):

[kW] 25,5 34,4 42,5 51,1 68,1 85,1 102

Nominal output real power (cos. �=1): [kW] 24 32 40 48 64 80 96 Nominal output current (cos. �=0,8): [A] 43,3 57,7 72,1 86,6 115 144 173 Nominal output current (cos. �=1): [A] 34,6 46,2 57,7 69,3 92,4 115 138 Nominal output voltage: [V] 3/N 400 V (adjustable ± 5%) Nominal output frequency: [Hz] 50 Transformer: galvanically isolated Voltage tolerance:

- static [%] ± 1 - 50% asymmetric load [%] ± 1 - 100% asymmetric load [%] ± 3 - dynamic with 100% load change [%] < 5

Regulation time: [msec] < 10 Angle deviation:

- symmetric load < 1° - 50% asymmetric load < 2° - 100% asymmetric load < 3°

Frequency tolerance: - mains synchronised [%] ± 1 (synchronisation range ± 4) - self synchronised [%] ± 0,1

Distortion factor (acc. EN 62040-1): - linear load [%] < 1 - non linear load [%] < 5

Crest factor: ≥ 3 Overload: - 3ph [%] 150% 60 sec., 125% 10 min.

- 1ph / N [%] 220% 60 sec., 180% 10 min. Short-circuit behaviour: - 3ph [%] 200% 3 sec.

- 1ph / N [%] 350% 3 sec. Inverter itself is short circuit proof, switch OFF after

max. 3 seconds if bypass mains is not available (EN 62040) Inverter efficiency with nominal load (cos. � 0,8):

[%] ≥ 92 ≥ 94

784370_05_enertron_i_gb_r1.qxd 01.10.2010 10:42 Uhr Seite 3

Page 7: Industrial UPS, single and three phase output ENERTRONIC... · Industrial UPS, single and three phase output ENERTRONIC I Range Internal power supply UPS mains operation UPS battery

B E N N I N G W o r l d C l a s s P o w e r S o l u t i o n s

ENERTRONIC I General data

76

Technical Data

Type ENERTRONIC I UPS Nominal output power (cos. �=0,8 ind.): [kVA] 30 40 50 60 80 100 120

Rectifier data ENERTRONIC I 3-1 and 3-3 Max. input power: [kVA] 32,7 43,5 54,4 65,2 78,1 108 129Nominal input power without battery charging: [kVA] 27,2 36,2 45,3 54,3 72,2 90,2 108Nominal input current without battery charging (at 400 V): [A] 39,2 52,3 65,4 78,4 104 130 155Max. input current with high rate charging (at 400 V): [A] 47,2 62,8 78,5 94,1 112 155 186Transformer: autotransformer (optional galvanically isolated) Input power factor: [cos. �] ≥ 0,99 ( 0,97 already at 25% load ) Nominal input voltage: [V] 3/N 400 V ± 15% Nominal input frequency: [Hz] 50 Hz ± 5% Mains distortion (at 100% load): [%] ≤ 5 Current ripple: < 5 A / 100 Ah

Battery data Recommended number of battery cells: 106 - 116 Max. charging current: [A] 20 27 34 41 55 69 83

General data Over all efficiency (AC to AC) without battery charging:

- 100% load 88,4 88,4 88,4 88,4 88,7 88,5 88,5 - 75% load 88,7 88,7 88,7 88,7 89,1 88,9 88,9 - 50% load 89,0 89,0 89,0 89,0 89,5 89,1 89,1

Heat dissipation: - 100% load [kW] 3,2 4,2 5,2 6,3 8,4 10,4 12,6Noise level with 1 m distance: [dB(A)] 63 65 67 Permitted ambient temp.: [°C] 0 to +40 (daily average ≤ 35) Relative humidity: [%] 5 - 95 without condensing Permitted installation height: [m] < 1000 m above sea level without derating Humidity class: DIN/IEC 721 2-1-09/86 Protection degree: IP 20 (DIN/VDE 0470 part 11/92 IEC 529) / others optional Radio interference: EN 50091-2 standard class A (optional class B) Dimensions (Width x Depth x Height): [mm] 800 x 800 x 2000 (optional 2200 height)

(max. 30 kVA single phase and 60 kVA three phase output) [mm] 1600 x 800 x 2000 (optional 2200 height)

(max. 80 kVA single phase and 120 kVA three phase output) Cooling: forced cooled with speed controlled, redundant and monitored fans, build in the air inlet, equipped with air flaps,

which close in case of fan failure, fans can be changed from front, power blocks and transformers are temperaturemonitored, prewarning will be sent out, after temperature increase switch OFF, air inlet from front, air outlet from top

Cable entry: from bottom (optional from top with cable cabinet, width 200 mm) Painting: RAL 7035, structured power coating

Static bypass Nominal voltage: [V] 230 / 400 Nominal frequency: [Hz] 50 Over load: - 10 min. [%] 150

- 100 msec. [%] ENERTRONIC I 3-1: 500, ENERTRONIC I 3-3: 1000 Transfer limits: [%] U ± 10; F ± 5 Inverter/Bypass transfer time:

- inverter failure [msec] < 1 - overload or manual transfer [msec] < 1

interlock when transfer was activated 5 times within a minute Bypass/inverter transfer time: [msec] < 1

Other options, e.g. bypass transformer on request.

784370_05_enertron_i_gb_r1.qxd 01.10.2010 10:42 Uhr Seite 4

Page 8: Industrial UPS, single and three phase output ENERTRONIC... · Industrial UPS, single and three phase output ENERTRONIC I Range Internal power supply UPS mains operation UPS battery

B E N N I N G W o r l d C l a s s P o w e r S o l u t i o n s

www.benning.de

3

7843

70.0

5 GB

0

9/20

10

pau

s De

sign

& M

edie

n, B

ocho

lt

Subj

ect t

o al

tera

tions

. P

rinte

d on

chl

orin

e fre

e pa

per.

ISO14001

ISO9001

Natural Resources

Energy Efficiency

CO2

SCC

BENNING worldwideAustriaBenning GmbH Elektrotechnik und ElektronikEduard-Klinger-Str. 9A-3423 St. Andrä-WördernTel. 0 22 42 / 3 24 16-0 Fax 0 22 42 / 3 24 23E-Mail: [email protected]

BelarusIOOO BENNING Belarusul. Derzinskogo, 50BY-224030, BrestTel. 0162 / 22 07 21Fax 0162 / 22 07 21E-Mail: [email protected]

BelgiumBenning Belgium Power ElectronicsZ. 2 Essenestraat 16B-1740 TernatTel. 02 / 58 287 85Fax 02 / 58 287 69E-Mail: [email protected]

CroatiaBenning Zagreb d.o.o. Trnjanska 61HR-10000 ZagrebTel. 1 / 63 12 280Fax 1 / 63 12 289E-Mail: [email protected]

Czech RepublicBenning CR s.r.o.Zahradní ul. 894CZ-293 06 Kosmonosy(Mladá Boleslav)Tel. 3 26 72 10 03Fax 3 26 72 25 33E-Mail: [email protected]

FranceBenning Conversion d’énergie43, avenue Winston ChurchillB.P. 418F-27404 Louviers CedexTél. 0 / 2.32.25.23.94Fax 0 / 2.32.25.08.64E-Mail: [email protected]

GermanyBenning Elektrotechnik und Elektronik GmbH & Co.KGFactory I: Münsterstr. 135-137Factory II: Robert-Bosch-Str. 20 D-46397 BocholtTel. 0 28 71/ 93-0 Fax 0 28 71/ 9 32 97E-Mail: [email protected]

Great-BritainBenning Power Electronics (UK) Ltd.Oakley House Hogwood LaneFinchampsteadGB-Berkshire RG 40 4QWTel. 0118 9731506 Fax 0118 9731508E-Mail: [email protected]

HungaryBenning Kft.Power ElectronicsRákóczi út 145H-2541 LábatlanTel. 033 / 50 76 00Fax 033 / 50 76 01E-Mail: [email protected]

ItalyBenning Conversione di Energia S.r.LVia 2 Giugno 1946, 8/BI-40033 Casalecchio di Reno (BO)Tel. 0 51 / 75 88 00 Fax 0 51 / 61 67 655 E-Mail: [email protected]

NetherlandsBenning NLPower ElectronicsPeppelkade 42NL-3992 AK HoutenTel. 0 30 / 6 34 60 10 Fax 0 30 / 6 34 60 20E-Mail: [email protected]

PolandBenning Power Electronics Sp. z o.o.Korczunkowa 30PL-05-503 GloskówTel. 0 22 / 7 57 84 53 Fax 0 22 / 7 57 84 52E-Mail: [email protected]

P. R. China Benning Power Electronics (Beijing) Co., Ltd.Tongzhou Industrial Development Zone 1-B BeiEr Street CN-101113 Beijing Tel. 010 61568588 Fax 010 61506200 E-Mail: [email protected]

Russian FederationOOO Benning Power ElectronicsMoscow region,Domodedovskiy district,Domodedovo, Severny zone,Tel. (495) 967 68 50Fax (495) 967 68 51E-Mail: [email protected]

SlovakiaBenning Slovensko, s.r.o.Kukuričná 17SK-83103 BratislavaTel. 02 / 44459942Fax 02 / 44455005E-Mail: [email protected]

South AmericaBenning Office South AmericaLavalle 637AR-1876 Bernal, Buenos AiresArgentinaTel. 54/ 911 5498 2515E-Mail: [email protected]

South East AsiaBenning Power Electronics Pte Ltd85, Defu Lane 10#05-00SGP-Singapore 539218Tel. (65) 6844 3133Fax (65) 6844 3279E-Mail: [email protected]

SwedenBenning Sweden ABBox 990, Hovslagarev. 3BS-19129 SollentunaTel. 08 / 6239500Fax 08 / 969772E-Mail: [email protected]

SwitzerlandBenning Power Electronics GmbHIndustriestrasse 6CH-8305 DietlikonTel. 044 / 8057575Fax 044 / 8057580E-Mail: [email protected]

SpainBenning Conversión de Energía S.A.C/Pico de Santa Catalina 2Pol. Ind. Los LinaresE-28970 Humanes, MadridTel. 91/ 6048110Fax 91/ 6048402E-Mail: [email protected]

UkraineBenning Power Electronics 3 Sim'yi Sosninykh str. UA-03148 KyivTel. 044 / 501 40 45 Fax 044 / 273 57 49 E-Mail: [email protected]

U.S.A.Benning Power Electronics, Inc.11120 Grader StreetUSA-Dallas, TX 75238Tel. 214 5531444Fax 214 5531355E-Mail: [email protected]

784370_05_enertron_i_gb_r1.qxd 01.10.2010 10:42 Uhr Seite 6