installation and maintenance manual · 2017-05-24 · removal loosen the valve mounting screw, lift...

3
2 INTENDED CONDITIONS OF USE 2.1 Specifications SQ1000 specifications Note 1) Use dry air to prevent condensation at low temperatures. Note 2) Vibration resistance: No malfunction occurred in a one-sweep test between 45 and 2000Hz. Test was performed in the axial and right angle directions of the main valve and armature for both energized and de-energized states. Impact resistance: No malfunction resulted from the impact test using a drop impact tester. The test was performed one time each in the axial and right angle directions of the main valve and armature, for both energized and de-energized states. Note 3) Metal seal type only. [Except double (latching) type.] Note 4) Values for the low wattage (0.5W) specification. SQ2000 specifications Note 1) Use dry air to prevent condensation at low temperatures. Note 2) Vibration resistance: No malfunction occurred in a one-sweep test between 8.3 and 2000Hz. Test was performed in the axial and right angle directions of the main valve and armature for both energized and de-energized states. Impact resistance: No malfunction resulted from the impact test using a drop impact tester. The test was performed one time each in the axial and right angle directions of the main valve and armature, for both energized and de-energized states. Note 3) Values for the low wattage (0.5W) specification. 2.2 Piping SQ1000 Series Read this manual before using this product The information within this document is to be used by pneumatically trained personnel only. For future reference, please keep manual in a safe place. This manual should be read in conjunction with the current catalogue. 1 SAFETY RECOMMENDATION 1.1 General recommendation These safety instructions are intended to prevent a hazardous situation and/or equipment damage. These instructions indicate the level of potential hazard by label of "Caution", "Warning" or "Danger". To ensure safety, be sure to observe ISO4414 (Note1) , JIS B 8370 (Note2) and other safety practices. Note 1:ISO 4414:Pneumatic fluid power - General rules relating to systems. Note 2:JIS B 8370:Pneumatic system axiom. WARNING: The compatibility of pneumatic equipment is the responsibility of the person who designs the pneumatic system or decides its specifications. Since the products specified here are used in various operating conditions, their compatibility for the specific pneumatic system must be based on specifications or after analysis and/or tests to meet your specific requirements. Only trained personnel should operate pneumatically operated machinery and equipment. Compressed air can be dangerous if an operator is unfamiliar with it. Assembly, handling or repair of pneumatic systems should be performed by trained and experienced operators. Do not service machinery/equipment or attempt to remove components until safety is confirmed. Inspection and maintenance of machinery/equipment should only be performed after confirmation of safe locked-out control positions. When equipment is to be removed, confirm the safety process as mentioned above. Switch off air and electrical supplies and exhaust all residual compressed air in the system. Before machinery/equipment is re-started, ensure all safety measures to prevent sudden movement of cylinders etc. (Bleed air into the system gradually to create backpressure, i.e. incorporate a soft-start valve). Contact SMC if the product is to be used in any of the following conditions: Conditions and environments beyond the given specifications, or if product is used outdoors. Installations on equipment in conjunction with atomic energy, railway, air navigation, vehicles, medical equipment, food and beverage, recreation equipment, emergency stop circuits, press applications, or safety equipment. An application, which has the possibility of having negative effects on people, property, or animals, requiring special safety analysis. CAUTION: Ensure that the air supply system is filtered to 5 micron. 1.2 Conformity to standard This product is certified to and complies with the following standards: SQ2000 Series 2.3 Circuit Symbols 3 INSTALLATION WARNING: Do not install unless the safety instructions have been read and understood. 3.1 Environment WARNING: Do not use in an environment where the product is directly exposed to corrosive gases, chemicals, salt water, water or steam. Do not use in an explosive atmosphere. The product should not be exposed to prolonged sunlight. Use a protective cover. Do not mount the product in a location where it is subject to strong vibrations and/or shock. Check the product specifications for above ratings. Do not mount the product in a location where it is exposed to radiant heat. 3.2 Piping CAUTION: Before piping make sure to clean up chips, cutting oil, dust etc. When installing piping or fitting into a port, ensure that sealant material does not enter the port inside. When using seal tape, leave 1.5 to 2 threads exposed on the end of pipe/fitting. 3.3 Electrical connection CAUTION: When DC power is connected to a solenoid valve equipped with light and/or surge voltage suppressor, check for polarity indications. For polarity indications: No diode to protect polarity: if polarity connection is wrong, the diode in the valve or switching device at control equipment or power supply may be damaged. With diode to protect polarity: if polarity connection is wrong, the valve does not switch. CAUTION: Operator error could result in injury or equipment damage. WARNING: Operator error could result in serious injury or loss of life. DANGER: In extreme conditions, there is a possible result of serious injury or loss of life. D-sub connector Kit (25P) AXT100-DS25- Cable assembly Electrical wiring specifications SQ1/2000-TFJ38GB Installation and Maintenance Manual SQ1000/2000 Series, 5 Port solenoid Valve/Plug lead,And Plug-in EMC Directive 89/336/EEC EN 61000-6-2, EN55011 Low Voltage Directive 93/68/EEC DIN VDE 0580 Thread Appropriate tightening torque (Nm) Rc 1/8 7 to 9 Rc 1/4 12 to 14 015 030 050

Upload: others

Post on 12-Mar-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation and Maintenance Manual · 2017-05-24 · Removal Loosen the valve mounting screw, lift the valve from the solenoid cover side and remove it by sliding it in the direction

2 INTENDED CONDITIONS OF USE

2.1 Specifications

SQ1000 specifications

Note 1) Use dry air to prevent condensation at low temperatures.Note 2) Vibration resistance: No malfunction occurred in a one-sweep test between 45

and 2000Hz. Test was performed in the axial and right angle directions of themain valve and armature for both energized and de-energized states.

Impact resistance: No malfunction resulted from the impact test using a drop impact

tester. The test was performed one time each in the axial and right

angle directions of the main valve and armature, for both energized

and de-energized states.

Note 3) Metal seal type only. [Except double (latching) type.]

Note 4) Values for the low wattage (0.5W) specification.

SQ2000 specifications

Note 1) Use dry air to prevent condensation at low temperatures.Note 2) Vibration resistance: No malfunction occurred in a one-sweep test between 8.3

and 2000Hz. Test was performed in the axial and right angle directions of themain valve and armature for both energized and de-energized states.

Impact resistance: No malfunction resulted from the impact test using a drop impact

tester. The test was performed one time each in the axial and right

angle directions of the main valve and armature, for both energized

and de-energized states.

Note 3) Values for the low wattage (0.5W) specification.

2.2 Piping

SQ1000 Series

Read this manual before using this product

� The information within this document is to be used by pneumatically trainedpersonnel only.

� For future reference, please keep manual in a safe place.

� This manual should be read in conjunction with the current catalogue.

1 SAFETY RECOMMENDATION

1.1 General recommendation

These safety instructions are intended to prevent a hazardous situation and/or

equipment damage. These instructions indicate the level of potential hazard by label of

"Caution", "Warning" or "Danger". To ensure safety, be sure to observe ISO4414 (Note1),

JIS B 8370 (Note2) and other safety practices.

Note 1:ISO 4414:Pneumatic fluid power - General rules relating to systems.

Note 2:JIS B 8370:Pneumatic system axiom.

WARNING:

• The compatibility of pneumatic equipment is the responsibility of the personwho designs the pneumatic system or decides its specifications.

�� Since the products specified here are used in various operating conditions, theircompatibility for the specific pneumatic system must be based on specifications orafter analysis and/or tests to meet your specific requirements.

• Only trained personnel should operate pneumatically operated machineryand equipment.

�� Compressed air can be dangerous if an operator is unfamiliar with it. Assembly,handling or repair of pneumatic systems should be performed by trained andexperienced operators.

• Do not service machinery/equipment or attempt to remove components untilsafety is confirmed.

�� Inspection and maintenance of machinery/equipment should only be performedafter confirmation of safe locked-out control positions.

�� When equipment is to be removed, confirm the safety process as mentioned above.Switch off air and electrical supplies and exhaust all residual compressed air in thesystem.

�� Before machinery/equipment is re-started, ensure all safety measures to preventsudden movement of cylinders etc. (Bleed air into the system gradually to createbackpressure, i.e. incorporate a soft-start valve).

• Contact SMC if the product is to be used in any of the following conditions:

�� Conditions and environments beyond the given specifications, or if product is usedoutdoors.

�� Installations on equipment in conjunction with atomic energy, railway, airnavigation, vehicles, medical equipment, food and beverage, recreationequipment, emergency stop circuits, press applications, or safety equipment.

�� An application, which has the possibility of having negative effects on people,property, or animals, requiring special safety analysis.

CAUTION:� Ensure that the air supply system is filtered to 5 micron.

1.2 Conformity to standardThis product is certified to and complies with the following standards:

SQ2000 Series

2.3 Circuit Symbols

3 INSTALLATION

WARNING:

� Do not install unless the safety instructions have been read and understood.

3.1 Environment

WARNING:

� Do not use in an environment where the product is directly exposed to corrosivegases, chemicals, salt water, water or steam.

� Do not use in an explosive atmosphere.

� The product should not be exposed to prolonged sunlight. Use a protective cover.

� Do not mount the product in a location where it is subject to strong vibrationsand/or shock. Check the product specifications for above ratings.

� Do not mount the product in a location where it is exposed to radiant heat.

3.2 Piping

CAUTION:� Before piping make sure to clean up chips, cutting oil, dust etc.

� When installing piping or fitting into a port, ensure that sealant material does notenter the port inside. When using seal tape, leave 1.5 to 2 threads exposed on theend of pipe/fitting.

3.3 Electrical connection

CAUTION:� When DC power is connected to a solenoid valve equipped with light and/or surge

voltage suppressor, check for polarity indications.

� For polarity indications:

�� No diode to protect polarity: if polarity connection is wrong, the diode in thevalve or switching device at control equipment or power supply may bedamaged.

�� With diode to protect polarity: if polarity connection is wrong, the valve doesnot switch.

CAUTION: Operator error could result in injury or equipment damage.

WARNING: Operator error could result in serious injury or loss of life.

DANGER: In extreme conditions, there is a possible result of serious

injury or loss of life.

D-sub connector Kit (25P)

AXT100-DS25-

Cable assembly

Electrical wiring specifications

SQ1/2000-TFJ38GB

Installation and Maintenance ManualSQ1000/2000 Series, 5 Port solenoid Valve/Plug lead,And Plug-in

EMC Directive 89/336/EEC EN 61000-6-2, EN55011

Low Voltage Directive 93/68/EEC DIN VDE 0580

Thread Appropriate tightening torque (Nm)

Rc 1/8 7 to 9

Rc 1/4 12 to 14

015030050

Page 2: Installation and Maintenance Manual · 2017-05-24 · Removal Loosen the valve mounting screw, lift the valve from the solenoid cover side and remove it by sliding it in the direction

Flat ribbon cable Kit

Cable assembly

Electrical wiring specifications

PC Wiring System Compatible Flat Ribbon Cable Kit

Electrical wiring specifications

Direct electrical entry type

Wiring Specifications/Positive COM Specifications

Wiring Specifications/Negative COM Specifications (optional)

Serial Transmission Kit

Indicator light/surge voltage suppressorIndicator lights are all positioned on one side for both single solenoid and doublesolenoid types. For double, 3 position, and 4 position dual 3 port types, 2 colours are

used to indicate the energization of A side or B side.

3.4 Mounting1. If air leakage increases or equipment does not operate properly, stop

operation.

After mounting or maintenance, connect the compressed and power supplies, andperform appropriate function and leakage tests to confirm that the unit is mountedproperly.

2. Instruction manual

Mount and operate the product after reading the manual carefully andunderstanding its contents. Also keep the manual where it can be referred to asnecessary.

3. Painting and coating

Warnings or specifications printed or pasted on the product should not be erased,removed or covered up. Furthermore, confirm before painting the resin parts,because this may cause an adverse effect depending on the solvent.

Adding Manifold StationsAs shown in the table below, wiring specifications for spare connectors are based on tothe remaining number of connector pins (remaining number of pins against themaximum number of solenoids for each kit). The following procedures are for usingspare connectors to add stations.

Spare connector wiring

Steps for adding stations1) Loosen the clamp screw on the U side end plate and open the manifold.2) Mount the manifold block to be added3) Open the junction cover and attach the spare connector. Match the station position of

the added station and the spare connector station number.4) Press on the end plate to eliminate any space between the manifold blocks and

tighten the clamp screw.

Mounting and Removal of Valves� Insert the hook of the valve into the fitting on the manifold block, then push the

valve down into place and tighten the mounting screw.

� Tighten the screw with the appropriate tightening torque shown below:

� When pushing the valve down, press it on the area near the manual override. Becareful not to push the solenoid cover.

Note) When using the negative COM specification, use valves

for negative COM.

Note) When using the negative COM

specification, use valves for negative COM.

For details on the PC Wiring System, refer to

catalogue "PC Wiring System" (CAT.ES02-20).

Remaining connector pins 4 pins or more 3 pins 2 pins 1 pin 0 pin

Spare connector wiring 2 for double 1 for double 1 for 1 for None

wiring wiring (on the double single

low no. station wiring wiring

side) 1 for

single wiring

SQ1000 0.17 to 0.23NM

SQ2000 0.25 to 0.35NM

SQ1/2000-TFJ38GB

2026

123

Double wiring (connected to SOL. A and SOL. B) is used for the internal wiring of each station regardless of valve and option types.Mixed single and double wiring is available as an option.

Page 3: Installation and Maintenance Manual · 2017-05-24 · Removal Loosen the valve mounting screw, lift the valve from the solenoid cover side and remove it by sliding it in the direction

Removal� Loosen the valve mounting screw, lift the valve from the solenoid cover side and

remove it by sliding it in the direction of arrow 3

Mounting and Removal of Manifold with DIN RailRemoving Manifold from DIN Rail1) Loosen the end plate clamping screws on both sides until they turn freely.

(The screws do not come out.)2) Remove the manifold from the DIN rail by lifting it from the solenoid cover side.

Mounting manifold on DIN RailThe procedure is the reverse of that above. After tightening the clamping screw on oneside, push on the opposite end plate so that there are no gaps between the manifoldblocks and then tighten the other clamping screw.

3.5 Lubrication

CAUTION:� SMC products have been lubricated for life at manufacture, and do not require

lubrication in service.

� If a lubricant is used in the system, use turbine oil Class 1(no additive), ISO VG32.Once lubricant is used in the system, lubrication must be continued because theoriginal lubricant applied during manufacturing will be washed away.

� Contact SMC regarding Class 2 turbine oil (with additives), ISO VG32.

4 SETTINGS AND PROGRAMMINGManual Override - UseManual Override - Use to switch the main valve

Push type (tool required)Push the manual override all the way in using a small screwdriver, etc.

Push type (tool required)2 position double (latching) type

� Turn the manual override 180º clockwise until the mark alignswith "A" and push into lock in the set condition (flow from P to A).

� Turn the manual override 180º counter clockwise until the markaligns with "B" and push in to return to the reset condition (flowfrom P to B).

<Caution>Do not turn the manual override when it is pushed in, as this may cause damage. The construction is such that the operating force is different on sides A and B.

Locking type (tool required)

� The manual override is locked by pushing clockwise to release it.it allthe way in and turning it 90º clockwise using a small flat headscrewdriver. Turn it counter clockwise to release

Slide locking type (SQ2000 only)The manual override is locked by sliding it all the way to the pilot valve side (ON side)with a small flat head screwdriver or finger. Slide it to the fitting side (OFF side) torelease it. In addition, it can also be used as a push type by using a screwdriver, etc.,

of Ø2 or less.

5 MAINTENANCEan

WARNING:

� Not following proper procedures could cause the product to malfunction and couldlead to damage to the equipment or machine.

� If handled improperly, compressed air can be dangerous. Assembly, handling andrepair of pneumatic system should be performed by qualified personnel only.

� Drain: remove condensate from the filter bowl on a regular basis.

� Shutdown before maintenance: before attempting any kind of maintenance makesure the supply pressure is shut off and all residual air pressure is released fromthe system to be worked on.

� Start-up after maintenance: apply operating pressure and power to the equipmentand check for proper operation and possible air leaks. If operation is abnormal,please verify product set-up parameters.

� Do not make any modification to the product

� Do not disassemble the product, unless required by installation or maintenanceinstructions.

� When equipment is removed, first confirm that measures are in place to preventdropping of work pieces and run-away of equipment, etc. Then cut the supplypressure and power, and exhaust all compressed air from the system using itsresidual pressure release function. Furthermore, with a 3 position closed center

type, release the compressed air that remains between the valve and cylinder inthe same manner. When the equipment is to be started again after remounting orreplacement, first confirm that measures are in place to prevent lurching ofactuators, etc., and then confirm that the equipment is operating normally.

� Valves should be switched at least once every 30 days to prevent malfunction. (Usecaution regarding the air supply.)

� When the manual override is operated, connected equipment will be actuated.Confirm safety before operating.

Replacing Cylinder Port FittingsCylinder port fittings are available in cassette type and can be replaced easily.Fittings are secured with a clip that is inserted from the topside of the valve. Removethe clip with a flat head screw driver, etc., to replace the fittings.To mount a fitting, insert the fitting assembly until it stops and reinsert the clip to itsdesignated position.

*Part numbers above are for one fitting; however, order them in 10 piece units.

<Caution>Do not scratch or put foreign matter on the O-rings as this will cause air leakage.

Build-in Silencer ElementsA filter element is built into the manifold base end plate. When the element becomesdirty and clogged, this will cause trouble such as a drop in the cylinder speed, etc.Therefore, replace the element regularly.

To replace an element, remove the cover on the topside of the end plate and removethe old element with a flat head screwdriver, etc.

6 LIMITATIONS OF USE

WARNING:

� Do not exceed any of the specifications laid out in section 2 of this document or thespecific product catalogue.

Operating Environment

1. Do not use valves in atmospheres of corrosive gases, chemicals, salt water, water orsteam, or where there is direct contact with them.

2. Do not use in an explosive atmosphere.3. Do not use in locations subject to vibration or impact. Confirm the specifications in

the main section of the catalog.4. A protective cover, etc., should be used to shield valves from direct sunlight.5. Shield valves from radiated heat generated by nearby heat sources.6. Employ suitable protective measures in locations where there is contact with water

droplets, oil or welding spatter, etc.7. When solenoid valves are mounted inside a control panel or are energized for

extended periods of time, employ measures to radiate excess heat so thattemperatures remain within the valve specification range.

Extended periods of continuous energization

Use the low power consumption specification (0.5W) if valves will be continuouslyenergized for extended periods of time or the energized period will be longer than thede-energized period. Use the low power consumption specification (0.5W) especiallywhen three or more adjacent stations on a manifold are continuously energized,because the temperature increases substantially. For 2 position double latching type,use the type with energy saving circuit SQ 2 - __-X11.

Momentary energization (double solenoid type)

If a double solenoid valve will be operated with momentary energization, it should beenergized for at least 0.1 second (20mS or more for 2 position double latching type).However, malfunction may occur due to load conditions on the secondary side. In thatcase energize until the cylinder moves to the stroke end. Furthermore, when using adouble solenoid valve for air blowing, energize when performing the air blowing.

Leakage voltage

Particularly when using a C-R element (surge voltage suppressor) for protection of theswitching element, take note that leakage voltage will increase due to leakage currentflowing through the C-R element, etc

Limit the amount of residual leakage voltage to the following values:

2% or less of rated voltage

Operation of solenoid valves with an SSR

Malfunction may occur when the minimum load current of the SSR is larger than theload current of solenoid valves. Consider the element specifications in the catalog toselect an SSR.

Surge voltage suppressorIf a general diode such as zener diode or ZNR is not used in the surge voltagesuppressor on the controller side, be aware that there will be a residual voltageaccording to the protective element and rated voltage. Moreover, the residual voltageof the diode is approximately 1V.

Low temperature operationValves can be operated at a temperature as low as -10°C unless otherwise indicated inthe specifications for each valve, however, measures should be taken to avoidsolidification or freezing of drainage and moisture, etc.

Operation for air blowingWhen using solenoid valves for air blowing, use an external pilot type. When using aninternal pilot and an external pilot on the same manifold, a pressure drop caused byair blowing may affect the internal pilot valve. Also, supply to the external pilot portcompressed air within the pressure range prescribed in the specifications; and with 2position double (double solenoid), always energize when air blowing.

Mounting orientationIn the case of 2 position single or 4 position dual 3 port valves, the mountingorientation is unrestricted. In the case of 2 position double (double solenoid) or 3position valves, mount so that the spool valve is horizontal.

7 EUROPEAN CONTACT LIST

7.1 SMC Corporation

Country Telephone Country Telephone

Austria (43) 2262-62 280 Italy (39) 02-92711

Belgium (32) 3-355 1464 Netherlands (31) 20-531 8888

Czech Republic (420) 5-414 24611 Norway (47) 67 12 90 20

Denmark (45) 70 25 29 00 Poland (48) 22-548 50 85

Finland (358) 9-859 580 Portugal (351) 22 610 89 22

France (33) 1-64 76 1000 Spain (34) 945-18 4100

Germany (49) 6103 4020 Sweden (46) 8 603 12 00

Greece (30) 1- 342 6076 Switzerland (41) 52-396 3131

Hungary (36) 23 511 390 Turkey (90) 212 221 1512

Ireland (353) 1-403 9000 United Kingdom (44) 1908-56 3888

7.2 Websites

SMC Corporation www.smcworld.com

SMC Europe www.smceu.com

When a manifold contains a large number of stations and is difficult to remove all at once, separate

the manifold into several sections before removing it.

With DC coil

SQ1/2000-TFJ38GB

If it difficult to loosen the screw, loosen it while pressing the valve gently on the area near the

manual override.