Installation and maintenance manual

Central power supply system

CPS 220 / CPS 220 SKÜ / CPS 220 SV / CPS J-SV

Page 2: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 1 INOTEC Sicherheitstechnik GmbH 29.08.2007

Content: page

1. General information 2

2. Safety advice 2

3. Battery notes 2

4. Type-references of CPS 220 main-stations and CPUS 220 sub-stations 3

5. Mechanical design of CPS 220 main-stations and CPUS 220 sub-stations 4

6. Technical data 4

7. Installation example 5

8. Mounting the CPS 220 6

9. Mounting of the batteries 6

10. Electrical connection of the system 10

11. Turning on the central battery system 11

12. Internal units 12.1 BUS-interface module - BIF 12 12.2 Relay interface - RIF 5 13 12.3 Light switch monitor - LSA 8.1 15 12.4 Staircase light switch connection - TLS 18 12.5 Channel staircase light switch connection - TLS 5 20 12.6 Event printer - optional function 21 12.7 Disk drive - optional function 22 12.8 Circuit modules 24 12.9 CPS 220 / SV / ... with Joker Technology 31 12.10 Isolation supervision and tests 34

13. External units 13.1 3-phase-monitor - DPÜ 35 13.2 Remote display tableau - MTB 36 13.3 Phase selection connector - PAS 37 13.4 Modules and sub-stations with BUS-Connection 38

14. CPS unit programming 14.1 General information 45 14.2 Test menu 46 14.3 System programming 47 14.4 CPS unit programming 48 14.5 Info menu 49

15. Control module with controller function 15.1 General information 52 15.2 Controller connection 52 15.3 Programming the Sub-station addresses 52 15.4 Programming the controller 53 15.5 Update timers for all connected stations 53 15.6 Automatic ISO supervision with failure display 53

16. Further modules for CPS 220-Systems 16.1 Continous light circuit modules – DSM/L- DSM-U 54

17. Fan monitoring in the optional "Priorit" fire protection cabinet 56

18. Recurring examinations 57

19. Appendix: Copyforms for system documentations 57

Page 3: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 2 INOTEC Sicherheitstechnik GmbH 29.08.2007

1. General information

After unpacking the housings (battery and electronics housings) kindly check for complete delivery and whether there are any visible external damages. Furthermore, inform the forwarding agents at once about visible damages, as we do not accept complaints that reach us at a later time. Before starting the system take into consideration all references in the installation and maintainance manual! All guarantee claims cease in case of wrong installation or of any intervention on the products! Only original fuses are allowed to be used. The fuses on the outgoing side have are: Order no. 5 A - 080 005 Order no. 10 A - 080 006 In general original spare part must be used. Only printers of protection class II can be connected to the Centronics Interface of the control unit. A function test has to be initiated after each repair work on connected luminaires, in order to delete the failure messages displayed on the control module. (see 14.2.1)

2. Safety advice

The manual contains information for trained and qualified electricians. The system has to be operated within the design parameters and only in functional, undamaged condition. National safety standards and legal requirements have to be observed. Fuses in the system have to be shifted only when the central is in a "blocked" mode. (see 14.4.4) The system has to be disconnected from the battery first and next from mains supply prior to any work being carried out on the luminaires or other system components! (see 11)

3. Battery notes

The delivered batteries can be stored for max. 3 months without being charged! Prior to any test carried out the batteries must be charged for at least 24 hours. Old batteries have to be disposed as per national requirements.

!

!

!

!

Page 4: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 3 INOTEC Sicherheitstechnik GmbH 29.08.2007

4. CPS 220 central and CPUS 220 sub-central models

CPS 220 / ... / ...

0 without circuit modules

16 with max. 8 circuit modules types 2x3A or 1x6A (max 16 circuits)

32 with max. 16 circuit modules types 2x3A or 1x6A (max 32 circuits)

48 with max. 24 circuit modules types 2x3A or 1x6A (max 48 circuits)

SKÜ with circuit monitoring

SV with individual lamp monitoring of each luminaire

CPU ... 220 / ... / ... / Option F 30 (up to CPUS 220/.../32 in F 30 housing)

6 with max. 3 circuit modules types 2x3A or 1x6A

16 with max. 8 circuit modules types 2x3A or 1x6A (max 16 circuits)

32 with max. 16 circuit modules types 2x3A or 1x6A (max 32 circuits)

48 with max. 24 circuit modules types 2x3A or 1x6A (max 48 circuits)

SKÜ with circuit monitoring

SV with individual lamp monitoring of each luminaire

S in sheet steel housing

SB In sheet steel housing complete of 6 BUS- fitted circuits (only together with SKÜ or SV systems)

M Backplate assembly unit (without housing)

MB BUS-fitted backplat assembly unit complete with 6 circuits (only together with SKÜ or SV systems)

CPUSB 220/ ... /6/F30 recessed wall mounting panel F 30 (fire proof) (only together with SKÜ or SV systems)

Page 5: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 4 INOTEC Sicherheitstechnik GmbH 29.08.2007

5. Mechanical design of CPS 220 panels and CPUS 220 sub-stations

5.1. Rack with control module

5.2. Rack (max. 3) for circuit modules

5.3. Charger 3,0 A or 7,5 A (only with CPS 220 central)

6. Technical data

Connection voltage: 1 ~ N/PE, 230 V, 50/60 Hz 3 ~ N/PE, 230 V, 50/60 Hz Protection class: I Protection category: Battery housing: IP 20

Electronics housing: IP 54 * Temperature Range: -5°C to +35°C Total connectable load and maximum battery discharge current acc. to type label information. *Protection category IP 54 for the electronics compartement is only achieved after

replacing the rubber cable inlets against standard cable glands.

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

Netz

Ladeteil 220V / 7,5A

INOTEC

Ein

Batterie

10AT

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

Funktionstest g gggagbJSXHLXHBSKLHSX ÖHXÖJÄJSK 'K 'K OS*KNL ÖJÖLJXL ÖÄJ ASX ÖÄAK ÖL ANHLXJKNLXKMJ ÄXMJJKL ÖÄLMXNHÖ XNJKXJ ÄJÖ AJK ÖLK ÖKL Ö

OPERATION

CPS 220

01.07.95 12:00

U BATT: 220V I BATT +15.0A

Operation

Failure

Chargefailure

BAT.operation

INOTEC

KEY-BOARD

PrinterCENTRONICS

CPS 220/SV ISO

TEST

+

-

UH5AT

SU/SKÜ 2x3A

Si 5A T

Si 5A T

Si 5A T

Si 5A T

Ein

Ein

Stör ung

Stör ung

SU/SKÜ 2x3A

Si 5A T

Si 5A T

Si 5A T

Si 5A T

Ein

Ein

Stör ung

Stör ung

SU/SKÜ 2x3A

Si 5A T

Si 5A T

Si 5A T

Si 5A T

Ein

Ein

Stör ung

Stör ung

SU/SKÜ 2x3A

Si 5A T

Si 5A T

Si 5A T

Si 5A T

Ein

Ein

Stör ung

Stör ung

SU6SKÜ

Si 10A T

Si 10A T

Ein

Stör ung

SU/SKÜ 2x3A

Si 5A T

Si 5A T

Si 5A T

Si 5A T

Ein

Ein

Stör ung

Stör ung

SU6SKÜ

Si 10A T

Si 10A T

Ein

Stör ung

SU/SKÜ 2x3A

Si 5A T

Si 5A T

Si 5A T

Si 5A T

Ein

Ein

Stör ung

Stör ung

SU6SKÜ

Si 10A T

Si 10A T

Ein

Stör ung

SU/SKÜ 2x3A

Si 5A T

Si 5A T

Si 5A T

Si 5A T

Ein

Ein

Stör ung

Stör ung

SU6SKÜ

Si 10A T

Si 10A T

Ein

Stör ung

SU/SKÜ 2x3A

Si 5A T

Si 5A T

Si 5A T

Si 5A T

Ein

Ein

Stör ung

Stör ung

SU6SKÜ

Si 10A T

Si 10A T

Ein

Stör ung

SU6SKÜ

Si 10A T

Si 10A T

Ein

Stör ung

SU6SKÜ

Si 10A T

Si 10A T

Ein

Stör ung

SU6SKÜ

Si 10A T

Si 10A T

Ein

Stör ung

Mains

Charger 220V / 7,5A

INOTEC

ON

Battery

10AT

Page 6: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 5 INOTEC Sicherheitstechnik GmbH 29.08.2007

7. Installation example

Page 7: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 6 INOTEC Sicherheitstechnik GmbH 29.08.2007

8. Mounting of CPS system

The electronics and battery housings are to be set on top of each other at the installation site and they are to be connected to each other with the enclosed M8 screws. After mounting is complete, the system has to be fixed to the wall. It is necessary to leave a clearing between the housing and the wall for the sake of ventilation.

Three glands (with battery sets connected in parallel five) have to be mounted for battery cables and temperature measuring sensor (if delivered) between the electronics and the battery compartment. If the temperature measuring sensor is not included, the 3rd hole has to be covered with a blind plug (enclosed in the package).

9. Mounting of the batteries

Please check that the delivered batteries, pole connectors and battery cables are complete, and whether there are any mechanic damages. Remove the battery fuses F1 and F2 before connecting the batteries.

Put the batteries into place according to the below shown figure. Connect the pole connectors. Safety caps are to be put on the poles. More information regarding maintenance and care of the maintenance free batteries can be found on the enclosed battery instruction sheet.

The maintenance recommendations for batteries are an important part of the operation manual and have to be taken care of. Safety regulations regarding high dc-voltages must also be taken into consideration.

The fuses F1 and F2 must be inserted only after the installation of the whole CPS system is complete. (see 11)

Removing cover plate if required.

Page 8: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 7 INOTEC Sicherheitstechnik GmbH 29.08.2007

Battery size 17,6Ah, 25,8Ah, 32Ah, 44Ah, 52Ah , 70Ah and 73Ah Battery size 79 Ah, 89 Ah, 99 Ah and 120 Ah

Page 9: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 8 INOTEC Sicherheitstechnik GmbH 29.08.2007

Battery size 104Ah and 140Ah Battery size 149Ah

Page 10: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 9 INOTEC Sicherheitstechnik GmbH 29.08.2007

Battery size 199Ah

Page 11: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 10 INOTEC Sicherheitstechnik GmbH 29.08.2007

X 0

10. Electrical connection of the system

10.1. Connection to mains X1 a) 1-Phase

Connect mains to the terminals PE, N, L - terminal section -X1 b) 3 -Phases

Connect mains to the terminals PE, N, L1, L2, L3 - terminal section -X1, (3-phases-monitor is built-in and preconnected to terminals SL+/SL-). Additional terminals are provided if sub-stations are to be connected.

10.2. 24V-circuit - terminal section X2 The terminals SL+ and SL- are wire linked. If external 3-phase monitoring modules (DPÜ) are connected, the link has to be removed and the monitoring circuits are to be connected to the terminals SL+ and SL-.

10.3. External supervision: Data Bus - terminal section X2 External monitoring units are to be connected to the terminals R, T, G.

10.4. Other units - terminal section - X2 The units RIF 5, LSA 8.1, BIF and DPÜ are all connected at terminal section X2. A (optional) built-in SV-central (master control unit) has a wire-link between volt-free contact and terminals 1 and 2. If an external supervising unit (MTB) is installed, this can be conncected to the volt free contacts on the module RIF 5 (see 13.2)

10.5. Circuits to emergency luminaires - terminal section X3-X5 The circuits are to be connected to the terminals L, N, PE, on terminals in sections X3-X5: - X3 PE, N-, L+ 1.1 - - - PE, N-, L+ 8.2 - X4 PE, N-, L+ 9.1 - - - PE, N-, L+ 16.2 - X5 PE, N-, L+ 17.1 - - - PE, N-, L+ 24.2

10.6. Battery connection - terminal section X6 The battery cables have to be connected to the fuses F1(+) and F2(-) on. Battery sets connected in parallel have to be connected to + and – on terminal section X0. No fuses are installed in CPUS subs. The terminals U+/U- terminal section X6 are installed when sub-centrales are to be connected.

098

1

3456

7

2

X1 X2 X3 X4 X5 F1F2 + -

X6

Page 12: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 11 INOTEC Sicherheitstechnik GmbH 29.08.2007

10.7. Terminal operation

11. Turn on the central battery system

The following checks have to be carried out prior to switching mains supply on and the battery fuses are inserted:

- isolation test of final end circuits according to the regulations

- check the BUS and data cables for correct poling

- check the connection of external units according to this manual

- check the connection of the 24V-circuit (SL+/SL-)

- check the pole connection of the battery assembly: 1. of every single battery, and 2. of the whole battery set (fuses F1 and F2)

Powering-up the system - follow these steps:

1. Switch on power supply (turn on charger)

2. Insert the battery fuses

Note: The fuses in the system are to be replaced only when the system is in blocked mode! (see 14.4.4)

1. 2. 3. Removescrew driver

Pushto open

Screew driver type 01

Do not open under load condition!N-isolation terminalopen

Insertwire

Page 13: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 12 INOTEC Sicherheitstechnik GmbH 29.08.2007

12. Internal units

12.1. BUS-interface module - BIF

The BUS interface (BIF) is the connecting point between the system (CPS) and the external BUS fitted units as, for example, LSA 8.1, RIF 5, DPÜ-B, MTB-B, MTB-D and BUS-sub-stations for CPS 220. The BIF module shields the system from external influences on the BUS cable.

Connection

The BUS cables are connected via the +24V, ⊥, +BUS terminals. The maximum length of the cables to the external modules is 1500m for 1,5 mm². Similarly, attention has to be paid to the connection of the BUS cables to the different units, i.e polarity-changes within the bus-line are not allowed.

How to address the BUS-fitted units

The relative address has to be set as follows at the unit's address switch:

LSA 8.1 - max. 3 pcs. Addr. 1, 2, 3 (see 12.3) for RIF 5 Addr. 7 (see 12.2) for MTB Addr. 7 (see 13.4.3) for DPÜ Addr. 1 - 31 (see 13.4.2)

Internal wiring

Data line connection

990 013

Page 14: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 13 INOTEC Sicherheitstechnik GmbH 29.08.2007

Temperaturfühler Temp. sensor

Adresse 7 einstellen set address 7

Fernschalter Remote switch

potentialfreie Kontakte 24V/1A (DC) 230V/0,5A (AC) Volt free contacts

24V DC max. 100mA

Interne Verdrahtung, Firmenseitig internal wiring, factory set

12.2. Relay-interface - RIF 5

The unit carries the following function possibilities:

- Remote switching gear (i.e. key switch) that can be programmed for: - maintained and non maintained emergency light on / off or

- maintained emergency light on / off - Volt-free contacts for

- operation - battery operation - failure

- Battery sensor for temperature-controlled charging

Messages: - Contact 1 and 2 open Sum-failure - Contact 2/4 closed Operation - Contact 5/6 closed Battery operation

System status

Operation Sum-failure Battery operation

Failure 1-2

closed open closed

Operation 3-4 closed open open

Rel

ay c

on

tact

s

Battery operation 5-6

open open closed

The remaining contacts are currently still without function !

The RIF 5 module is factory-set with address 7. If the module is installed at a later time, address 7 has to be set.

Page 15: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 14 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.2.1. How to program the relay interface RIF 5

The RIF 5 module can be programmed at the control unit as follows:

Push menu key Push system prog. key Push prog. control panel key

push next key to continue until display shows: RIF/MTB-module is connected / not connected push change to choose connected

push next key to continue until display shows: func. of remote switch

push change key to choose EL+Main. are blocked or maintain is blocked

push next key to continue in order to go back to the main menu

12.2.2. Passive RIF 5

To the simple duplication of the volt-free contacts of the RIF 5 further RIF 5 modules (passive RIF) can be connected to the controller. At all additional RIF 5 address 0 has to be set. At the passive RIF 5 only the function of the volt-free contacts is given. All other connection options are without function. It may be set to address 7 to a maximum of 1 RIF 5.

Page 16: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 15 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.3. Light switch function - LSA 8.1 In order to be able to turn emergency- and standard mains luminaires ON and OFF via the same light switch the LSA 8.1 module can be used. Each of the 8 galvanically seperated channels can be used to monitor one light switch. If a switch is actuated any number of change-over device (SU/SV/SKÜ circuit modules) will be activated. The change-over devices are linked by software (programmed on the systems control unit). It is possible to assign two different channels to each circuit module.

12.3.1. How to program the LSA 8.1 The LSA 8.1 module can be programmed at the control unit as follows:

Push menu key Push system prog. key Push prog. control panel key

The system asks for number of LSA 8 modules push change key to choose between LSA 8 modules, … none, 1,2 or 3 … push next key LSA 8 /1 with / with out sub-circuit info push change key for selecting LSA 8/1 with or without sub-circuit info LSA 8/1 with display info on failed sub-dbs

(Option for selective switching on – only with LSA 8/INV) Push change key with/none

until display shows with Push next key in order to go back to the main menu

Under paragraph 12.8.1.2 you can read how to program the change-over modules for LSA 8.1.

If the LSA 8.1 modules are installed at a later time, the BUS cable has to be connected and the modules have to be set to the addresses 1 - 3.

12.3.2. Connection examples

LSA 8.1

Note: Emergency luminaires connected to a CPS-system are supplied with mains via the change-over devices.

PE N L

Netzleuchten General lighting

PE N L

Netzleuchten General lighting

PE N L

Netzleuchten General lighting

PE N L

Netzleuchten General lighting

Interne Verdrahtung Internal wiring

Page 17: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 16 INOTEC Sicherheitstechnik GmbH 29.08.2007

LSA 8.1 24V T

+24V

T

+24V

T

+24V

T

+24V

Interne Verdrahtung Internal wiring

LSA 8.1 inverted

L1L2L3NPE

UV 2

U<

L1NPE

UV 1

AllgemeinbeleuchtungGeneral lighting

AllgemeinbeleuchtungGeneral lighting

Page 18: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 17 INOTEC Sicherheitstechnik GmbH 29.08.2007

LSA 8.1 24V inverted

UV 1 UV 2

L3 L1L2 N

L1DPÜ

L2gem.VDE0108

L3

12 14 11

L3 L1L2 N

L1DPÜ

L2gem.VDE0108

L3

12 14 11

Page 19: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 18 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.4. Staircase light switch connection – TLS

Both standard interior and emergency lighting luminaires can be controlled via the TLS. An integrated timer allows to activate the lights for any time between 1 - 15 min. An internal converter in the TLS module supplies the glow lamps in the lighting push-buttons with power. Max. 25 illuminated push-buttons, each with 0,8 mA glow lamps or 13 push-buttons with 1,5 mA glow lamps can be connected to T+ and T-. The length of the cable to the push-buttons is max 500m. For the power supply of the mains luminaires each TLS-module has a volt-free contact (terminals 29 and 30) with a maximum switching load of 5A at 230V. The emergency lighting luminaires are supplied via the change-over devices of the CPS system.

All luminaires that are connected to the TLS can be programmed as maintained emergency light with the switch "maintained emergency light".

PE N L

further Push buttons

further Mains luminaires

TLS

BatterySi 3,15A T

On

Pushbutton

Maintainedlight

Page 20: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 19 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.4.1. How to program the TLS module

The TLS can be programmed at the control unit as follows:

Push Menu key Push System Prog. key Push prog. control panel key

push next key to continue until display shows TLS connection Push change key to choose between No TLS connected / 5-channel TLS / 1-channel TLS choose 1-channel TLS Push next key until display shows Number of 1-channel TLS Push change key to choose between none / 1 / 2 / 3 Push next key until display shows: TLS 1- time: 3 minutes Push change key to set time to 1 - 15 minutes Push next key until display shows TLS 2- time: Set TLS 2 as described above Push next key until display shows TLS 3- time: Set TLS 3 as described above Push next key in order to go back to the main menu

For programming of change-over devices to TLS modules see paragraph 12.8.1.3.

Page 21: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 20 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.5. 5 channel staircase light switch connection - TLS 5 Both standard interior and emergency lighting luminaires can be controlled via the TLS. An integrated timer allows to activate the lights for any time between 1 - 15 min. Each of the 5 individual channels have terminals for the cables to the push-buttons and for the corresponding volt -free contacts. An internal converter in the TLS module supplies the glow lamps in the lighting pus-buttons with power. Max. 20 illuminated push-buttons, each with 0,8 mA glow lamps or 10 push-buttons with 1,5 mA glow lamps can be connected to ( 1/1 ....5/5 ). The length of the cable to the push-buttons is max 500m. For the power supply of the mains luminaires each TLS-module has a volt-free contact with a maximum switching load of 3A at 230V. The emergency lighting luminaries are supplied via the change-over devices of the CPS system.

12.5.1. How to program the TLS 5 module The TLS 5 can be programmed at the control unit as follows:

Push menu key Push system prog. key Push prog. control panel key

push next key until display shows TLS connection push change key to choose between No TLS connected / 5-channel TLS / 1-channel TLS choose 5-channel TLS push next key until display shows 5-channel TLS - time: 3 minutes push change key to set time to 1 - 15 minutes push next key in order to go back to the main menu For programming TLS modules settings see paragraph 12.8.1.4.

+ + + +24V 24V B US B US

INOTECTLS 5990 022

+-UBa tt

T 5 T 4 T 3 T 2 T 1

1122334455

Si40mAT

Si40mAT

Si40mAT

Si40mAT

Si40mAT

220VLogic

Ta

ste

r

Rel 5 Rel 4 Rel 3 Rel 2 Rel 1

12345 45 3 2 1 1

Re

lais

Ch

an

ne

l5

Ch

an

ne

l4

Ch

an

ne

l3

Ch

an

ne

l2

Ch

an

ne

l1

Push button 1

Push button 2

Push button 3

Push button 4

Push button 5

Battery220V

BUS-connection

Page 22: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 21 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.6. Event printer – optional function

The printer is installed at the factory and lists all data that is registered in the log with exact date and time.

12.6.1. How to program the printer

The printer can be controlled as follows at the control unit:

Push menu key Push system prog. key Push prog. control panel key

push next key until display shows built in printer push change key to choose Yes / No choose Yes

push next key in order to go back to the main menu

Funktionstest g gggagbJSXHLXHBSKLHSX ÖHXÖJÄJSK 'K 'K OS*KNL ÖJÖLJXL ÖÄJ ASX ÖÄAK ÖL ANHLXJKNLXKMJ ÄXMJJKL ÖÄLMXNHÖ XNJKXJ ÄJÖ AJK ÖLK ÖKL Ö

Funktionstest g gggagbJSXHLXHBSKLHSX ÖHXÖJÄJSK 'K 'K OS*KNL ÖJÖLJXL ÖÄJ ASX ÖÄAK ÖL ANHLXJKNLXKMJ ÄXMJJKL ÖÄLMXNHÖ XNJKXJ ÄJÖ AJK ÖLK ÖKL Ö

OPERATION

CPS 220

01.07.95 12:00

U BATT: 220V I BATT +15.0A

Operation

Failure

Chargefailure

BAT.operation

INOTEC

KEY-BOARD

PrinterCENTRONICS

CPS 220/SV ISO

TEST

+

-

UH5AT

Page 23: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 22 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.7. Disk drive – optional function

The disk drive is factory installed. All events are registered with exact date and time on the DOS-formatted disk in order to keep a logbook. The data stored on the disk can be evaluated/printed via the included windows-based program.

12.7.1. How to program the disk drive

Push menu key

Push system prog. key

Push prog. control panel key

push next key until display shows disc drive

push change key to choose Yes / No choose Yes

push next key to go back to the main menu

12.7.2. How to install the disk drive program on your PC

1. Insert disk in drive A: or B: 2. Select "Run" under the menu "File" in the "Program Manager" 3. Write "A:\install.exe" or "B:\install.exe" in the dialogue box 4. Confirm with "OK" 5. Write the name of the folder where INODISC shall be installed in the dialogue box "Choose folder"

and select "install" 6. Select "Yes" in the dialogue box "Install INODISC in folder C:\INODISC" in order to install the

program, or select "NO" in order to choose a new folder. 7. Answer "Yes" at the dialogue box "Create folder C:\INODISC" 8. The program will be installed and the program box "INODISC 1.0" will be created

12.7.3. How to read the logbook in the program

1. Remove disk from the disk drive in the system and insert it in the PC's disk drive 2. Start the INODISC 1.0 program 3. Choose disk drive under the menu "Logbook", and "Open logbook".The logbook will be opened

and a filed event is shown

4. With the keys and one can move to the previous or next filed event

5. With the keys I and I one can go to the first or the last event stored

6. Each filed event is shown with exact date and time Program menus

OPERATION

CPS 220

01.07.95 12:00

U BATT: 220V I BATT +15.0A

Operation

Failure

Chargefailure

BAT.operation

INOTEC

KEY-BOARD

PrinterCENTRONICS

CPS 220/SV ISO

TEST

+

-

UH5AT

Page 24: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 23 INOTEC Sicherheitstechnik GmbH 29.08.2007

Program menus

1. FILE Format disk formats disk in DOS-format Printer settings printer settings are done End program "Alt+X" closes INODISC 1.0 2. LOGBOOK Open logbook Opens logbook Print report prints the event shown Close window "STRG+F4" closes current window 3. REGISTRATIONS First shows first event Previous shows previous event Next shows next event Last shows last event Go to Chooses event according to event number 4. DIALOGUE BOX Next to each other arranges open windows next to each other Under each other arranges open windows under each other On top of each other arranges open windows on top of each other Arrange symbols arranges the symbol 5 HELP Content F1 shows contents of the help menu Use help with "Shift+F1" information on use Info information on INODISC version

Page 25: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 24 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.8. Circuit modules

12.8.1. Circuit modules SU/SV 2x3A and SU/SV 1x6A The circuit modules are to be installed in the CPS 220 SV and CPUS 220 SV systems. A maximum of 12 luminaires can be connected to each circuit module. For each circuit the terminals L, N, PE are available on the terminal sections X3, X4, X5

On the terminal sections X3, X4 and X5 the relative terminals are related to the modul's location. The assignment of the circuit modules to the terminal sections has to be carried out as follows:

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

Netz

Ladeteil 220V / 7,5A

INOTEC

Ein

Batterie

10AT

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

PE/L+1.1/N-1.1 X 3

PE/L+1.2/N-1.2 X 3

Slot 4

SK 4.1

SK 4.2

Slot 6

SK 6.1

SK 6.2

Slot 7

SK 7.1

SK 7.2

X 4 PE/L+9.1/N-9.1

X 4 PE/L+9.2/N-9.2

Slot 12

SK 12.1

SK 12.2

Slot 14

SK 14.1

SK 14.2

Slot 15

SK 15.1

SK 15.2

X 5 PE/L+17.1/N-17.1

X 5 PE/L+17.2/N-17.2

Slot 20

SK 20.1

SK 20.2

Slot 22

SK 22.1

SK 22.2

Slot 23

SK 23.1

SK 23.2

Slot 21 Slot 19

Slot 11 Slot 13

Slot 3 Slot 5

Slot 18

Slot 10

Slot 2

Slot 17

Slot 9

Slot 1 Slot 8

Slot 16

Slot 24

Page 26: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 25 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.8.1.1. How to program the SU/SV 2x3A and 1x6A modules push menu key push system Prog. key push circuit assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected / disconnected choose connected push place assignment key until display shows SU/SV 2x3A SK 1/1 Status: active push change key to choose between active / not active choose active push next key until display shows Status: … -light push change key to choose between NM-light / M-light / switch. M-L choose NM-light (non maint./maintained emergency light) push next key until display shows L1 discon. push change key to choose between connected / disconnected if a luminaire (adressed 01) is installed, choose connected if no luminaire (adressed 01) is installed, choose disconnected push next key until next luminaire, carry one as above for all connected luminaire OR push update desti. text key to enter location enter max. 20 letters with keyboard after having entered destination push F3 to obtain display L2 selected the programming steps for L02 are as for luminaire L01 program all luminaires until you reach luminaire no. L12 the display shows then SU/SV 2x3A SK1/2 the programming steps for circuit 1/2 are as for circuit 1/1 all other circuits are to be programmed as 1/1 push finish key when all circuits have been programmed

Prior to this an address has to be set on all connected emergency and escape route luminaires as per the relevant manual!

12.8.1.2. How to program the SU/SV module in connection with LSA 8.1

Before programming the SU/SV, the LSA 8.1 modules must already have been programmed in the control unit. (see 12.3.1) Two different channels of the LSA 8.1 can be assigned to each circuit change over module.

push menu key push system prog. key push assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected / disconnected choose connected push place assignment key until display of SU/SV 2x3A SK 1/1 status: active push change key to choose between active / not active choose active push next key until display shows status: … -light push change key to choose between NM-light / M-light / switch. M-L

Page 27: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 26 INOTEC Sicherheitstechnik GmbH 29.08.2007

choose switch. M-L push next key until display shows SU/SV 2x3A SK1/1 1. LSA-assignment push change key to choose none - LSA8/1 - LSA8/2 - LSA-8/3 choose relevant LSA-8 push next key until display shows LSA8/1 channel no. chan.: 1 push change key to choose between channel 1 - channel 8 select relevant channel push next key until display shows 2. LSA assignment program as for first LSA, see above In order to program the other circuit change-over modules repeat the above steps.

12.8.1.3. How to program the SU/SV module in connection with TLS

Before programming the SU/SV, the TLS module must already have been programmed in the control unit. (see 12.4.1)

push menu key push system prog. key push circuit assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected / disconnected choose connected push place assignment key until display shows SU/SV 2x3A SK 1/1 status: active push change key to choose between active / not active choose active push next key until display shows status: … -light push change key to choose between NM-light / M-light / switch. M-L choose switch. M-L push next key until display shows LSA 8 LSA 8 has to be programmed as described in paragraph 12.8.1.2 push next key until display shows TLS assignment: none push change key to choose between none / TLS1 / TLS2 / TLS3 choose relevant TLS push next key In order to program the other circuit modules repeat the above steps.

Page 28: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 27 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.8.1.4. How to program the SU/SV module in connection with TLS 5

Before programming the SU/SV, the TLS-5 module must already have been programmed in the control unit. (see 12.5.1)

push menu key push system prog. key push circuit assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected/disconnected choose connected push place assignment key until display shows SU/SV 2x3A SK 1/1 status: active push change key to choose between active / not active choose active push next key until display shows status: … -light push change key to choose between NM-light / M-light / switch. M-L choose switch. M-L push next key until display shows LSA 8 LSA 8 has to be programmed as described in paragraph 12.8.1.2 push next key until display shows TLS assignment: none push change key to choose between none / TLS1 / TLS2 / TLS3 /

TLS4 / TLS5 choose relevant TLS channel push next key In order to program the other circuit modules repeat the above steps.

Page 29: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 28 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.8.2. Circuit modules SU/SKÜ 2x3A and SU/SKÜ 1x6A

The circuit modules can be installed in the CPS 220 SKÜ and CPUS 220 SKÜ systems. Maximum 12 monitored luminaires can be connected to each circuit change-over device. For each circuit the terminals L, N, PE are available on the terminal sections X3, X4, X5.

The relevant circuit modules are assigned to unique terminals on the terminal sections X3, X4 and X5. The assignment of the circuit modules to the terminal sections and the terminals has to be carried out as described on page 23.

12.8.2.1. How to program the SU/SKÜ modules

push menu key push system prog. key push circuit assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected / disconnected choose connected push place assignment key until display shows SU/SKÜ 2x3A SK 1/1 status: active push change key to choose between active / not active choose active push next key until display shows status: … -light push change key to choose between NM-light / M-light / switch. M-L choose NM-light (non maintained / maintained emergency light) push next key until display shows current tolerance 5% push change key to change settings of current deviation

key change is + (encreases tolerance)

key change is - (decreases tolerance) push next key push edit destination key in order to enter luminaire location text of max. 20 letters with keyboard push F3 when text is complete the display shows then "next place" program the following places as above push end key in order to have the display showing Starting a new setting of SKÜ current? push Yes key Functiontest will be started with measure- ment of the value push No key The program goes back to the main menu

SU/SV 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SV 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SV 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SV 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

Netz

Ladeteil 220V / 7,5A

INOTEC

Ein

Batterie

10AT

SU6SV

Si 10AT

Si 10AT

Ein

Störung

SU6SV

Si 10AT

Si 10AT

Ein

Störung

SU/SV 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SV

Si 10AT

Si 10AT

Ein

Störung

SU/SV 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SV

Si 10AT

Si 10AT

Ein

Störung

SU/SV 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SV

Si 10AT

Si 10AT

Ein

Störung

SU6SV

Si 10AT

Si 10AT

Ein

Störung

SU6SV

Si 10AT

Si 10AT

Ein

Störung

SU6SV

Si 10AT

Si 10AT

Ein

Störung

SU/SV 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

Page 30: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 29 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.8.2.2. How to program the SU/SKÜ module in connection with LSA 8.1

As described in paragraph 12.8.1.2

12.8.2.3. How to program the SU/SKÜ module in connection with TLS As described in paragraph 12.8.1.3

12.8.2.4. How to program the SU/SKÜ module in connection with TLS 5 As described in paragraph 12.8.1.4

Page 31: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 30 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.8.3. Circuit modules SU 2x3A and SU 1x6A

The circuit modules can be installed in the CPS 220 and CPUS 220 centrals. Maximum 12 luminaires can be connected to each circuit. For each circuit module there is a set of L, N, PE terminals available on the terminal sections X3, X4 and X5.

The relevant circuit modules are assigned to unique terminals on the terminal sections X3, X4 and X5. The assignment of the circuit modules to the terminal sections and the terminals has to be carried out as described in paragraph 8.8.1. The function setting of each change-over device is done with a switch on the front plate (M = maintained em-light, NM = non maintained em-light).

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

Netz

Ladeteil 220V / 7,5A

INOTEC

Ein

Batterie

10AT

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU/SKÜ 2x3A

Si 5AT

Si 5AT

Si 5AT

Si 5AT

Ein

Ein

Störung

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

SU6SKÜ

Si 10AT

Si 10AT

Ein

Störung

Page 32: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 31 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.9. CPS 220 / SV / ... with JOKER Technology

12.9.1. General Information

Each J-SU/SV change-over device can supply and monitor up to 12 luminaires in three different modes (maintained-, non-maintained- or switched maintained - all in one mode or mixed modes) on one circuit. These switching modes are active in mains supply. A mains failure at the main distribution board or at any monitored supply will automatically switch all connected luminaires to battery operation, regardless of their mains switching mode.

12.9.2. Exit and safety-luminaires, modules with JOKER technologie Each module and luminaire suitable for Joker Technology is fitted with a switch (DL/BL = Maintained / Non-maintained mode) to set the luminaire switching mode for this component.

Switching mode:

Maintained: The switch on the electronic ballast or the monitoring

module has to be set to the DL (M)-position.

Non-maintained: The switch on the electronic ballast or the monitoring module has to be set to the BL (NM)-position.

Switched Maintained: The switch on the electronic ballast or the monitoring module has to be set to the BL (NM)-position. The input LS/NS on the modules and electronic ballasts is used to switch this luminaire, along with the standard mains lighting ON or OFF.

SU / SV - J 2x3A

Si 5A T

Si 5A T

Failure

NM - ON

M - ON

Failure

NM - ON

M - ON

Page 33: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 32 INOTEC Sicherheitstechnik GmbH 29.08.2007

Technical data Mains supply: 230V 50/60 Hz Battery supply: 176 - 264V DC

Load range: 5-120W (J-SV-Modul/S) 20-300W (J-SV-Modul.2/S) 2-30W (J-SV-Modul.3/S) 18-120W (J-SV-Modul.4/S)

Ambient temp.: -15°C ... +65°C Housing: Thermoplast Wiring: up to 2,5mm² single solid wire or 1,5mm² soldered flex-wire EMC: to DIN EN 55015

12.9.3. Exit and safety-luminaires, modules with JOKER technologie For individual lamp monitoring and of fluorescent lamps, halogen lamps, bulbs and glow-wire lamps. With address switch for luminaire identification and sense-input to allow switching along with the general lighting.

To be installed inside of luminaire.

Connection J-SV-Modul/S

J-EVG 4-13 SV/S and J-EVG 18 SV/S have to be connected as per above sketch.

Input

L+ N- Light switch

LS / NS Output L+ N-

230V~ 230V~ 230V~ 230V~ 0V 0V 220V- 230V~ 220V- 220V- 0V 220V-

0V 230V~ 0V 0V 0V 0V

Supply circuit from CPS 220 J/SV

EVG

Light switch

General lighting PE N L

0 F D C B A

9 8 1

3 4 5

6 7 2 N-

N-

L+ L+

Adresse

BL DL

J-SV-Modul / S

Eingang

LS NS 851 002

tc Tc=70°C max Temp.-Test

2–30

W

N- L+

BL DL Operation mode selection switch

(NM) (M)

Page 34: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 33 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.9.4. Programming the JOKER technology circuits For programming instructions of J-SU/SV 2x3A and J-SU/SV 1x6A see 12.8.1

Page 35: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 34 INOTEC Sicherheitstechnik GmbH 29.08.2007

12.10. Isolation supervision and tests The isolation supervision and test settings in the CPS 220 are integrated next to the control unit. When the system operates in mains power supply the battery circuit is supervised for isolation errors. At an isolation resistance <2,0 K /V the fault is shown on the display and a red LED "Failure" flashes to indicate this. Has the fault been cleared the system goes automatically back to "Normal Operation" and the red LED is turned off.

All connected circuits are included in the isolation supervision when the central is in battery operation, i.e. when a function test or battery duration test is carried out and in case of power supply interruption. If an isolation fault occurs, it will be shown in the control unit and logged. After the fault has been cleared this entry can be deleted only by carrying out a new function test. The isolation supervision can be tested by pressing the keys Test + or Test -. An isolation fault is shown on the control units display. The isolation error is set back when the key is released.

OPERATION

CPS 220

01.07.95 12:00

U BATT: 220V I BATT +15.0A

Operation

FAILURE

Chargefailure

BATTERYOperation

INOTEC

KEY-BOARD

PRINTERCENTRONICS

CPS 220/SV ISO

TEST

+

-

UH5AT

Page 36: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 35 INOTEC Sicherheitstechnik GmbH 29.08.2007

13. External units

13.1. 3-phase-monitor - DPÜ

In order to supervise the mains power supply the DPÜ can be installed directly in the local power sub-distribution boards. If a phase fails the DPÜ will interrupt the 24V-monitoring-circuit. This contact is wired to SL+/SL- on the terminal section X2 (remove wire link). If several local circuit fuses or sub-distribution boards are supervised, the DPÜs have to be connected in series. • LED-indication for L1, L2, L3 • phases in any order whatever • detection of failed or low voltage in three-phase-systems • suitable for single-phase monitoring • to IEC 255, VDE 0435, part 303 • for distribution board / panel mounting (DIN rail profiles) Technical data Nominal voltage : 230 V AC, 400 V AC Tolerance: 1,1 Un permanent Power consumption: ca. 3VA Nom.-frequency: 50/60 Hz Activation level: 0,85 Un Contacts: 1 change-over contact

Imax contact : 30V DC, 1A / 230V AC, 0,5 A (resistor load)

Ambient temp.: -20°C ... +60°C Protection: IP 20 (terminals)

IP 40 (housing) Housing: Thermoplast Wiring: up to 2,5mm² single solid wire or 1,5mm² soldered flex-wire EMC: to DIN EN 55015

L1L2L3NPE

Sub-db 1

General lighting

L1L2L3NPE

Sub-db 2

General lighting

L1

NPE

Sub-db 3

General lighting

Supply monitoring in single- and three-phase installation

Term

inal

rai

l X2

S

L+/S

L–

SL+ SL-

L1DPÜ

L2

L3

L1DPÜ

L2

L3

L1DPÜ

L2

L3

All luminaires in non-maintained or switched maintained mode change to maintained mode if the power supply fails on DPÜ-monitored sub-distribution panels. The CPS-controller display shows “Failure sub DB”.

Page 37: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 36 INOTEC Sicherheitstechnik GmbH 29.08.2007

13.2. Remote display tableau - MTB

The remote notifying tableau is to be connected to the RIF 5 module as shown in the drawing below. The maximum cable length allowed between the RIF 5 and MTB is 500m with a 0,8 mm² cable. Three LED`s and a switch are on the front of the MTB panel:

Green LED: operation Yellow LED: battery operation Red LED: sum-failure Switch ON: the corresponding panel is blocked Switch OFF: the corresponding panel is not blocked

13.2.1. How to program the RIF 5 module with the MTB The programming process for the remote display tableau in connection with the RIF 5 is described in paragraph 12.2.1.

Page 38: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 37 INOTEC Sicherheitstechnik GmbH 29.08.2007

13.3. Phase selection connector - PAS, optional

The PAS comes with 20A/63A/100A. It switches to a remaining healthy phase if one or two supply phases fail and ensures mains power supply continuity to the CPS system. The emergency lighting system changes to emergency operation only after all three phases failed. The PAS has to be mains connected to the terminals L1, L2, L3, N and PE with three phases. The connecting cables to the CPS central are to be connected to L, N and PE.

PE N L to

CPS-system

PE N L1 L2 L3

Main supply

Page 39: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 38 INOTEC Sicherheitstechnik GmbH 29.08.2007

13.4. Modules with BUS-Connection

13.4.1. General information

It is possible to connect the RIF 5 and LSA 8.1 units to the CPS externally via a BUS cable. The electrical connection and the programming of those modules is described in paragraphs 12.2.1 for the RIF 5 and in paragraphs 12.3.1 for the LSA 8.1. Further BUS-suitable units are shown on the following pages. If the modules are used externally, they have to be addressed as described in paragraph 12.1.

Page 40: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 39 INOTEC Sicherheitstechnik GmbH 29.08.2007

13.4.2. 3-phase-monitor with BUS - DPÜ/B To monitor the mains supply directly on a local lighting sub-distribution board the DPÜs can be connected directly inside. If a phase fails the 24V-circuit is interrupted and a failure message "sub.-dist. Failure" is shown at the same time on the emergency systems control unit display. Pushing the button INFO on the control unit shows the user all failed sub.-dist. boards with location. The contact 1-2 has to be connected to the terminals SL+ / SL-. If the 24V-circuit shall use the same cable as the BUS-line, the connection of the DPÜ-B must be carried out as shown below.

13.4.2.1 How to program the DPÜ/B

push Menu key push system progr. key push prog. control panel key

push next key until display shows number of DPÜ/B push change key to choose between none / 1-31

push next key until display shows DPÜ/B change destination push destination key in order to edit the location text push delete destin. text key - destinations will be deleted push change destin. text key - enter destination text via keyboard after text is completed push F3 and then continue key until the program asks you to enter the data for the next DPÜ B

push next key after completed all data initiate test of DPÜ/B

push yes key for testing the DPÜ/B push next key to go back to the main menu

Address setting is mandatory.

Wire link on last DPÜ/B.1 mandatory

Page 41: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 40 INOTEC Sicherheitstechnik GmbH 29.08.2007

13.4.3. BUS-fitted remote display tableau - MTB/B

The BUS-suitable MTB-B has to be connected directly to the BIF module. The maximum cable length between BIF and MTB-B module is 500m with 0,8 mm². At the MTB-B the address 7 has to be programmed.

Three volt-free contacts for external signalling are part of the MTB-B: Terminals 1 and 2 sum-failure contact open (n/o) Terminals 3 and 4 battery operation contact closed (n/c) Terminals 5 and 6 normal operation contact closed (n/c)

13.4.3.1. How to program the MTB/B

push Menu key push system prog. key push prog. control panel key

push next key until the display asks whether the RIF 5 Relay interface is connected push change key to choose between connected / not connected choose connected push next key to go back to the main menu

BIF in CPS or CPUS 990 013

Page 42: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 41 INOTEC Sicherheitstechnik GmbH 29.08.2007

13.4.4. BUS-fitted remote display tableau with printer - MTB/D

The BUS suitable MTB-D has to be connected directly to the BIF module. The maximum cable length between BIF and MTB-D is 100m at 1,5 mm². For the MTB-D the address 7 has to be programmed.

Pushing the button "FT" on the MTB-D releases a function test on the connected emergency lighting system.

13.4.4.1. How to program the MTB/D with printer

push menu key push system prog. key push prog. control panel key

push next key until the display asks whether there is an built in printer push change key to choose between Yes/No choose Yes push next key to go back to the main menu

BIF in CPS or CPUS 990 013

Page 43: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 42 INOTEC Sicherheitstechnik GmbH 29.08.2007

13.4.5. Light switch function - LSA 8.1 The LSA 8.1 can be installed in an external local distribution board. Maximum three different LSA 8.1 can be connected to the control unit of the emergency lighting system. The addresses 1, 2 and 3 have to be set on the external LSA 8.1 modules. The connection of the LSA 8.1 via a BIF module is described in paragraph 12.1. For programming and wiring example see paragraph 12.3.1 / 12.3.2.

Page 44: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 43 INOTEC Sicherheitstechnik GmbH 29.08.2007

13.4.6. BUS-Sub-Stations – CPUSB It is possible to connect BUS-compatible sub-stations to the CPS 220 SV and SKÜ. Therefore a BIF- module has to be used. Connection of BUS- sub station - Power supply at the terminals L, N, PE: max. 10 mm² - Battery power supply at the terminals B+ and B-. max. 10 mm² - Final Circuits 1-6 at the corresponding terminals L, N, PE. - BUS-cable at the terminals B, ⊥.

Addressing of sub-stations-

It is necessary to assign an address to each CPUS B for identification at the control unit. Maximum 8 BUS compatible sub-stations can be connected to each CPS 220/SV/...or CPS 220/SKÜ/.....system. How to program the circuits is described in the paragraph 12.8. How to program the circuits with JOKER Technology see paragraph 12.9.

Netz NetzL LN

St.-Kreis1L+N–

St.-Kreis2L+N–

St.-Kreis3L+N–

St.-Kreis4L+N–

St.-Kreis5L+N–

St.-Kreis6L+N–

IBBatt. Batt.B BN

0 1

23

456

78

9

Battery 220Vvia CPS main-station

Internal Panel-BUSvia BIF

Mains230V AC

0 1.1 / 1.2 2.1 / 2.2 3.1 / 3.21 4.1 / 4.2 5.1 / 5.2 6.1 / 6.22 7.1 / 7.2 8.1 / 8.2 9.1 / 9.23 10.1 / 10.1 11.1 / 11.2 12.1 / 12.24 13.1 / 13.2 14.1 / 14.2 15.1 / 15.25 16.1 / 16.2 17.1 / 17.2 18.1 / 18.26 19.1 / 19.2 20.1 / 20.2 21.1 / 21.27 22.1 / 22.2 23.1 / 23.2 24.1 / 24.28 keine Funktion9 keine Funktion

Adresse Stromkreis Stromkreis StromkreisPlatz 1 Platz 2 Platz 3links mitte rechts

AdresseinstellungINOTEC Sic herheitstec hnik GmbH

Page 45: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 44 INOTEC Sicherheitstechnik GmbH 29.08.2007

Assignment address/circuit at the controller unit

Address 0 Circuits 1.1 to 3.2 Address 1 Circuits 4.1 to 6.2 Address 2 Circuits 7.1 to 9.2 Address 3 Circuits 10.1 to 12.2 Address 4 Circuits 13.1 to 15.2 Address 5 Circuits 16.1 to 18.2 Address 6 Circuits 19.1 to 21.2 Address 7 Circuits 22.1 to 24.2 Addresses 8 and 9 are not allowed!

Sample: A project is equipped with two bus-substations and a CPS 220/SV/32. The 16 installed change-over devices (2x3 Amp or 1x6 Amp) occupy rack one (8 slots) and rack two (8 slots) of the CPS-220/SV/32. By this they use the addresses 1.1, 1.2 … 8.1, 8.2 (rack one) and 9.1, 9.2 ...16.1, 16.2 (rack two). The next free circuit numbers (17.1/17.2/18.1 and 18.2) should not be used and the first bus-sub station must be set to address “6” to use the circuits 19.1 to 21.2. The 2nd CPUSB must be set to address 7 for circuits 22.1 to 24.2.

Page 46: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 45 INOTEC Sicherheitstechnik GmbH 29.08.2007

14. How to program the control unit

14.1. General information

The control unit of the CPS 220 and CPUS 220 has a 4 line display each line with max. 20 letters. The LEDs to the left of the display indicate the sytems status:

LED green normal operation LED yellow battery operation LED red failure LED red charging failure

The 4 keys to the right of the display are used to program the control unit. It is possible to connect a printer with protection category II , to the centronics interface and a keyboard to the included port.

In normal operation the display gives the following information:

Battery voltage Battery current Date Time

If no entry is affected for approx 1 min., the controller will switch back to the main menu.

After activating the mains supply, the display shows the program version and the initializing of system and disk drive starts. After finishing the process the display shows the status for normal operation.

OPERATION

CPS 220

01.07.95 12:00

U BATT: 220V I BATT +15.0A

Operation

FAILURE

Chargefailure

BATTERYOperation

INOTEC

KEY-BOARD

PRINTERCENTRONICS

CPS 220/SV ISO

TEST

+

-

UH5AT

Page 47: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 46 INOTEC Sicherheitstechnik GmbH 29.08.2007

14.2. Test menu

14.2.1. How to start a function test - FT

push functiontest key The function test will be started and shown on the display. The yellow LED indicates battery operation

14.2.2. How to start a battery test - DT

push menu key push test menu key push start durationtest key

The battery duration test will be started and it will be shown on the display. The yellow LED indicates battery operation. The batteries supply will be maintained until the first deep discharging protection level has been reached.

14.2.3. How to stop a battery test

after one minute has passed from starting the DT push menu key push test menu key push stopp durationtest key

the battery test will be stopped.

14.2.4. How to program new test times

14.2.4.1. How to program a new test time for FT (factory setting 7 days)

push menu key push test menu key push new time of test key push new time of FT key the display will then show: automatical FT push change key to choose between Yes/No choose Yes push next key until display shows time of test FT test cycle: 1 day push change key to choose between 1-15 days push next key until display shows time of test FT 10:00 push change and continue to set the time push back key to go back to the main menu

Page 48: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 47 INOTEC Sicherheitstechnik GmbH 29.08.2007

14.2.4.2. How to program a new test time for DT (factory setting 365 days) push menu key push test menu key push new time of test key push new time of DT key the display will then show automatical DT push change key to choose between Yes/No choose Yes push next key until display shows date for DT 01-08 (first of august) push change key and next input key to enter the date after input is completed the display will show time of DT

10:00 push change and next place to enter the time push back key after input is complete push main menu

14.3. How to program the system

14.3.1. How to change the date push menu key push system prog. key push update new time key push change date key set the date using the next input and change keys push back key after input is complete to go back to the main menu

14.3.2. How to change the time push menu key push system prog. key push update new time key push change time key set the time using the next input and change keys push back key to go back to the main menu

14.3.3. How to change a weekday push menu key push system prog. key push update new time key push change weekday key push change key to set weekday push back to go back to main menu

Page 49: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 48 INOTEC Sicherheitstechnik GmbH 29.08.2007

14.4. How to program the CPS unit

14.4.1. How to connect to a SV-central push menu key push system prog. key push prog. control panel key push next key until display shows system connected to SV-device Yes / No push change key to choose Yes push next key to change system's address push change key to choose between address 1-32 push next key to go back to main menu

14.4.2. Manual reset push menu key push system prog. key push prog. control panel key push next key until display shows with / without manual reset push change key to choose with manual reset push next key to go back to the main menu

14.4.3. Battery operation delay time push menu key push system prog. key push prog. control panel key push next key until display shows

with / without delay time push change key to choose with delay time push next key until display shows with delay time delay time: 1 min. push change key to choose between 1-15 minutes. push next key to go back to main menu

14.4.4. How to block the CPS central push menu key push system prog. key push prog. control panel key push next key until display shows CPS system is blocked / not blocked push change key to choose blocked push next key to go back to the main menu

14.4.5. Function remote switch push menu key push system prog. key push prog. control panel key push next key until display shows function of remote swit. push change key to select maintained or EL+Main. push next key to go back to the main menu

Page 50: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 49 INOTEC Sicherheitstechnik GmbH 29.08.2007

14.4.6. How to program the printer port push menu key push system progr. key push progr. CPS modul key push next key until display shows print-out of central configuration push Yes key to receive a print-out push No key to go back to main menu

14.4.7. Test deep discharge protection push menu key push system prog. key push prog. control panel key push next key until display shows Deep discharge protection test push Yes key Test is carried out push next key to go back to main menu

14.4.8. Menu options programmed by the factory

function of the control unit System- / Sub-station- / Controller-function battery information System identification number

14.5. Information menu

14.5.1. System information

14.5.1.1. Circuit information push menu key push information key push system information key push circuit information key the display will show place no.: 1 push information key the display will show information corresponding to place no.: 1 push back key to continue push next place key the display shows information as above carry on for all other places, to end push previous menu key to go back to the to sub-menu for system information or main menu

14.5.1.2. Battery information push menu key push information key push system info key push battery information key the display will show time of last battery duration test xxx minutes push next key until display shows battery information push back key to go back to the to sub-menu for system information or main menu

Page 51: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 50 INOTEC Sicherheitstechnik GmbH 29.08.2007

14.5.1.3. Control unit information

push menu key push information key push system information key push control panel info key until display shows program version - Ver.: A 11.H 12 (depending on actual version) push next key until display shows system number shunt unit version push previous menu key to go back to the to sub-menu for system information or main menu

14.5.2. Failure information push menu key push information key push failure info key until display shows failure information push print key in order to receive a print-out of actual failures of the complete CPS system installed push view key in order to see eventual errors on the display push next key in order to see the further faults after the last fault is shown, the program goes back to main menu

14.5.3. Disk information push menu key push information key push floppy / logbook key push floppy information key in order to see the information stored on the floppy push previous menu key in order to go back to the main menu key

14.5.4. Logbook

14.5.4.1. Delete logbook push menu key push information key push floppy / logbook key push logbook key push clear logbook key the display will show the following message Warning, all data will be lost push clear key in order to delete all data in the logbook push previous menu key in order to go back to the floppy/logbook sub-menu

Page 52: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 51 INOTEC Sicherheitstechnik GmbH 29.08.2007

14.5.4.2. Show logbook

push menu key push information key push floppy / logbook key push logbook key push display logbook key the display will show the last entry in the logbook push and keys you can scroll through the logbook all entries will be shown with date and time push previous menu key in order to go back to the floppy/logbook sub-menu

14.5.4.3. Print logbook - print all registrations push menu key push information key push floppy / logbook key push logbook key push print logbook key in order to initiate a print-out of the logbook push all items printing in order to receive a print-out of all events push abort printing key Display: print-out stopped push previous menu key in order to go back to the floppy/logbook sub-menu

14.5.4.4. Print logbook - print a selection push menu key push information key push floppy / logbook key push logbook key push printing a part key the display will then show the text start print item: xxx push change key and next display address in order to enter the number of event where the print-out shall start from push print key the display asks then for how many events shall be printed use the keys and to enter the number of events to be printed 1-99 registrations can be selected push print key the selected registrations will be printed push abort printing key in order to stop the print-out the system goes back to the floppy/logbook sub-menu push previous menu key in order to go back to the main menu

Page 53: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 52 INOTEC Sicherheitstechnik GmbH 29.08.2007

15. Control module with controller function

15.1. General information Control modules with Controller Function (one Controller for max. 8 sub- stations) Special features:

1. FT and BT starting at the same time for all connected stations.

2. The timers of all connected substations can work in line with the controller.

3. Blocking of FT and BT is possible on every sub-station

4. Data communication failures and other failures can be identified for

each station

5. ISO-failure test for all main system, sub-stations and all connected luminaires and display of current and voltage

6. Remote display of failure info for all sub-stations via controller and

RIF 5 / MTB

7. Remote blocking of all sub-stations via controller and RIF 5 / MTB Failure infos of sub-stations will not be logged in the logbook of the controller but in the sub-stations own control module logbook.

15.2. Controller connection All connected sub-stations need to be linked to the controller via a R-T-G line. Looping from one sub-station to the next ones is allowed. The max. cable length allowed with 1.5mm² is 2000m.

15.3. Programming the Sub-station addresses All connected sub-stations must have an individual address ( 1 - 8 ).

To do this the sub-station control modules must be programmed as follows: push menu key push system prog. key push prog. control panel key push next key until display shows system connection to SV- Central push change key to choose YES / NO Choose YES push next key select address with change key push next key to go back to main menu

Page 54: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 53 INOTEC Sicherheitstechnik GmbH 29.08.2007

15.4. Programming the controller

A mandatory requirement to use a control module in CONTROLLER function is to select "NO" when programming the step "system connected to SV-central"

push menu key push system prog. key push prog. control panel key push next key until display shows Module as controller push change key to choose YES / NO choose YES push next key until display shows Number of Sub-stations push change key and set total sub-station number (max. 8) push next key until display shows blocking of all sub-stations valid push change key to choose YES / NO YES All connected sub.-stations can be blocked at the same time NO Only main station can be blocked push next key to go back to main menu

15.5. Update timers for all connected stations push menu key push system prog. Key push prog. control panel key push set time key carry on as described in 10.3.1 - 10.3.3 push next key until display shows update of all system timers push change key to choose YES / NO choose YES Display shows: Delete FT and DT on all connected systems choose NO all sub-station take the preselected FT- and DT-times from the controller.

15.6. Automatic ISO supervision with failure display

The controller offers the possibility to do a detail-test resulting in a display info with the faulty sub-station and the final circuit

push menu key push system prog. key push next key until display shows Automatic ISO-detection - Yes / No push change key and choose Yes the ISO test starts Display info: Faulty substations / circuits will be flagged up on the display push next key carry on with the test As long as new ISO-faults exist they will be displayed, after last fault is displayed push next key to go back to main menu

Page 55: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 54 INOTEC Sicherheitstechnik GmbH 29.08.2007

General lighting

Emergencyluminaire

Light switch

PENL

Ausgang

N-

N-

L+

L+

Geeignet für Anlagen gem. DIN VDE 0108 / 10.89EMC:

INO

TEC

DSM / L.1

Ein

gang

LS

NS890 412

U :N

ta:gem. EN 55015

AC 230V 50 / 60HzDC 176 - 264 V

-15 bis 50°C

tcTc=70°C max

Temp.-Test

60

0W

ma

x

230 V A C

O+

O-

220 V DC

CPS Central

16. Further modules for CPS 220 systems

16.1. Continuous light circuit modules - DSM/L – DSM/U

DSM modules can be installed in order to switch mains luminaires and emergency luminaires together. DSM-U modules are to be installed in the local distribution boards, DSM-L modules are to be installed in luminaires that are already present. The connection of the DSM modules to the CPS 220 system has to be made as shown in the drawing below. When mains is present on terminals LS and NS, the connected emergency luminaires (terminals 0+/0-) are turned off. Actuating the switch contact turn all mains and emergency luminaires on. If the local mains sub.-distribution board fails, will also cause the connected emergency staircase luminaires to be turned on, in this case the DSM module has a phase monitor function. The circuits of the CPS system with DSM modules have to be programmed as maintained light, see paragraphs 12.8.1.1 / 12.8.2.1 / 12.8.3. If the CPS system switches over to emergency light operation, all connected emergency luminaires will be supplied from the batteries, no matter of the type of switching mode.

DSM / L.1 Maintained circuit switch module for luminaire installation:

Technical data Mains supply: 230V 50/60 Hz Battery supply: 176 - 264V DC Contact: 1 n/o Max. load: 600W Ambient temp.: -15°C ... +50°C Housing: Thermoplast Wiring: up to 2,5mm² single solid wire or 1,5mm² soldered flex-wire EMC: to DIN EN 55015

Supply IN Sense-Input OUT

L+ N- LS / NS O+ O-

230V~ 230V~ 0V

230V~ 0V 230V~

220V- 230V~ 220V-

220V- 0V 220V-

0V 230V~ 0V

0V 0V 0V

Page 56: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 55 INOTEC Sicherheitstechnik GmbH 29.08.2007

DSM / U.1 Maintained circuit switch module for panel mounting / DIN-rail mounting

Technical data Mains supply: 230V 50/60 Hz Battery supply: 176 - 264V DC Contact: 1 n/o Max. load: 600W Ambient temp.: -15°C ... +40°C Housing: Thermoplast Wiring: up to 2,5mm² single solid wire or 1,5mm² soldered flex-wire EMC: to DIN EN 55015

CPS

Light switch

General lighting

Emergency luminaires

PE N L

DSM / U . 1

Eingang L+ N- L+ N-

O+ / O-

A usgang LS O+

NS O- Schalteing

Ein L+ / N-

LS / NS

DC AC

890 413

Page 57: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 56 INOTEC Sicherheitstechnik GmbH 29.08.2007

17. Fan monitoring in the optional "Priorit" fire protection cabinet Type: NL91.172.084 / NL31.172.084, dim. 1970x1002x780mm

The function of the exhaust fan in the optionally available "Priorit" fire protection cabinet F30 / F90 is checked by means of a differential pressure guardian. At a change of the adjusted differential pressure the volt free change-over contact changes. The volt free change-over contact is connected to terminal section X11:

- 1 – NC (normally-closed) - 2 – NO (normally-open) - 3 – COM (incoming line)

Page 58: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 57 INOTEC Sicherheitstechnik GmbH 29.08.2007

!

18. Recurring examinations

18.1. General Electric plants must be tested regularly.

18.2. Electric plants for safety purposes

18.2.1. Inspection a) Testing of the preparing-values of the protection devices through inspection: annual b) Testing of the load connected to the power source for safety purposes with regard to the capacity

of the power source: annual

18.2.2. Testing and measuring a) function test of the change-over devices: annual b) capacity test for the battery: annual c) function test of isolation monitoring systems: semi-annual

18.3. Battery inspection and –monitoring According to DIN EN 50272-2 batteries and their operating units have to be checked regularly for proper function and safety. The following checks must be done: Charger voltage values Voltage of every single battery block and the whole battery Electrolyte density and filling level (if necessary) Cleanness and consistence Correct fit of pole connectors Ventilation Plugs and valves Battery temperature

Defective battery blocks have to be replaced directly! Divergent or special inspection- and monitoring points as well as their test cycles are to be taken from the operating instructions of the respective battery manufacturer.

18.4. Reports to recurring inspection

18.4.1. Test report The recurring tests and results are to be documented in logbooks. The documentation is to be kept for at least 4 years.

18.4.2. Battery test report Minimal information, which hast to be logged in the test report of the annual battery checks: Room temperature Charge voltage Charge current Discharge current Voltage of every single battery block

… at the beginning and the end of battery operation The annual test report is the basis for eventual guarantee claims.

19. Appendix

Copyforms for system documentation

Page 59: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 58 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals CPS 220 Project: Panel:

X 1 PE PE N

Mains(L, N, PE)

N L

L

Throughwiring to further sub-stations (L, N, PE)

X 2 SL + SL –

24 V - monitoring loop, external phase monitor

R T G

Data cable for external supervision

RIF 5 installed RIF 5 not installed +24V/⊥

1 2 3 4 5 6 7 8 9

10 FS+ FS–

T+

RIF 5

T–

Temperature sensor battery (if required)

installed not installed installed not installed installed not installed

L1 N1

Channel 1 Channel 1 Channel 1

L2 N2

Channel 2 Channel 2 Channel 2

L3 N3

Channel 3 Channel 3 Channel 3

L4 N4

Channel 4 Channel 4 Channel 4

L5 N5

Channel 5 Channel 5 Channel 5

L6 N6

Channel 6 Channel 6 Channel 6

L7 N7

Channel 7 Channel 7 Channel 7

L8

LSA 8.1

1 - 3 pcs.

N8 Channel 8 Channel 8 Channel 8

X 3 1.1 Terminal X 3 Total current X 3 ↓↓↓↓ Circuit 1.1 - 8.2

8.2

For details see following pages

X 4 + 9.1 Terminal X 4 Total current X 4 ↓↓↓↓ Circuit 9.1 - 16.2

16.2

For details see following pages

X 5 + 17.1 Terminal X 5 Total current X 5

↓↓↓↓ Circuit 17.1 - 24.2 24.2

For details see following pages

X 6 = U+ Total current Panel U–

Battery connection

Page 60: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 59 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals CPUS 220 Project: Panel:

X 1 PE PE N

Mains(L, N, PE)

N L

L

Throughwiring to further sub-stations (L, N, PE)

X 2 SL + SL –

24 V - monitoring loop, external phase monitor

R T G

Data cable for external supervision

RIF 5 installed RIF 5 not installed +24V/⊥

1 2 3 4 5 6 7 8 9

10 FS+ FS– T+

RIF 5

T–

Temperature sensor battery (if required)

installed not installed installed not installed installed not installed

L1 N1

Channel 1 Channel 1 Channel 1

L2 N2

Channel 2 Channel 2 Channel 2

L3 N3

Channel 3 Channel 3 Channel 3

L4 N4

Channel 4 Channel 4 Channel 4

L5 N5

Channel 5 Channel 5 Channel 5

L6 N6

Channel 6 Channel 6 Channel 6

L7 N7

Channel 7 Channel 7 Channel 7

L8

LSA 8.1

1 - 3 pcs.

N8 Channel 8 Channel 8 Channel 8

X 3 1.1 Terminal X 3 Total current X 3 ↓↓↓↓ Circuit 1.1 - 8.2

8.2

For details see following pages

X 4 + 9.1 Terminal X 4 Total current X 4 ↓↓↓↓ Circuit 9.1 - 16.2

16.2

For details see following pages

X 5 + 17.1 Terminal X 5 Total current X 5

↓↓↓↓ Circuit 17.1 - 24.2 24.2

For details see following pages

X 6 = U+ Total current sub-station U+

Battery-supply sub-station

U– U–

Throughwiring to further CPUS (+,-)

Page 61: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 60 INOTEC Sicherheitstechnik GmbH 29.08.2007

Connection plan Circuit CPS Terminal strip X 3

Project:

Panel: CPUS 220:

Terminal strip

Slot intern

al

NM 1)

M 2)

LSA 8 3)

TLS 4)

Joker 5) Terminal X 3 Cable-

no. Name Area Current

(A)

1/1 1.1 N- L+ PE

1/2 1.2 N- L+ PE

2/1 2.1 N- L+ PE

2/2 2.2 N- L+ PE

3/1 3.1 N- L+ PE

3/2 3.2 N- L+ PE

4/1 4.1 N- L+ PE

4/2 4.2 N- L+ PE

5/1 5.1 N- L+ PE

5/2 5.2 N- L+ PE

6/1 6.1 N- L+ PE

6/2 6.2 N- L+ PE

7/1 7.1 N- L+ PE

7/2 7.2 N- L+ PE

8/1 8.1 N- L+ PE

8/2 8.2 N- L+ PE

1) NM= Non-maintained light Total current

2) M = Maintained light

3) LSA 8.1 = Light switch monitor (1 - 3 )

4) TLS = Staircase lightswitch (1 - 3 )

5) Joker = Joker-Circuit

Page 62: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 61 INOTEC Sicherheitstechnik GmbH 29.08.2007

Connection plan circuit CPS Terminal strip X 4

Project:

CPS 220: CPUS 220:

Terminal strip

Slot intern

al

NM 1)

M 2)

LSA 8 3)

TLS 4)

Joker 5) Terminal X 4 Cable-

no.. Name Area Current

(A)

1/1 9.1 N- L+ PE

1/2 9.2 N- L+ PE

2/1 10.1 N- L+ PE

2/2 10.2 N- L+ PE

3/1 11.1 N- L+ PE

3/2 11.2 N- L+ PE

4/1 12.1 N- L+ PE

4/2 12.2 N- L+ PE

5/1 13.1 N- L+ PE

5/2 13.2 N- L+ PE

6/1 14.1 N- L+ PE

6/2 14.2 N- L+ PE

7/1 15.1 N- L+ PE

7/2 15.2 N- L+ PE

8/1 16.1 N- L+ PE

8/2 16.2 N- L+ PE

1) NM= Non-maintained light Total current

2) M = Maintained light

3) LSA 8.1 = Light switch monitor (1 - 3 )

4) TLS = Staircase lightswitch (1 - 3 )

5) Joker = Joker-Circuit

Page 63: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 62 INOTEC Sicherheitstechnik GmbH 29.08.2007

Connection plan circuit CPS Terminal strip X 5

Project:

CPS 220: CPUS 220:

Terminal strip

Slot intern

al

NM 1)

M 2)

LSA 8 3)

TLS 4)

Joker 5) Terminal X 5 Cable-

no.. Name Area Current

(A)

1/1 17.1 N- L+ PE

1/2 17.2 N- L+ PE

2/1 18.1 N- L+ PE

2/2 18.2 N- L+ PE

3/1 19.1 N- L+ PE

3/2 19.2 N- L+ PE

4/1 20.1 N- L+ PE

4/2 20.2 N- L+ PE

5/1 21.1 N- L+ PE

5/2 21.2 N- L+ PE

6/1 22.1 N- L+ PE

6/2 22.2 N- L+ PE

7/1 23.1 N- L+ PE

7/2 23.2 N- L+ PE

8/1 24.1 N- L+ PE

8/2 24.2 N- L+ PE

1) NM= Non-maintained light Total current

2) M = Maintained lightt

3) LSA 8.1 = Light switch monitor (1 - 3 )

4) TLS = Staircase lightswitch (1 - 3 )

5) Joker = Joker-Circuit

Page 64: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 63 INOTEC Sicherheitstechnik GmbH 29.08.2007

Connection plan, final end circuits CPS - Terminal strip X 3 Project: CPS 220: CPUS 220

Operation mode: NM 1) M 2) LSA 3) TLS 4 Joker 5)

Area: Terminal strip X3 1.1 - 8.2

Name: Cable-No..:

Location (max. 20 characters) Current

(A) Circuit-No..

Joker- function

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

NM

M Luminaire 1

SM

NM Luminaire 2 M SM

NM M

Luminaire 3 SM

NM Luminaire 4 M SM

NM M

Luminaire 5 SM

NM Luminaire 6 M SM

NM M

Luminaire 7 SM

NM Luminaire 8 M SM

NM M

Luminaire 9 SM

NM Luminaire 10 M SM

NM M

Luminaire 11 SM

NM Luminaire 12 M SM

Total current

1) NM = Non-maintained light Joker-Function

2) M = Maintained light NM = Non-maintained light

3) LSA 8.1 = Light switch monitor (1 - 3 ) M = Maintained light

4) TLS = Staircase lightswitch (1 - 3 ) SM = Switched maintained light 5) Joker = Joker-circuit

Page 65: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 64 INOTEC Sicherheitstechnik GmbH 29.08.2007

Connection plan, final end circuits CPS - Terminal strip X 4 Project: CPS 220: CPUS 220

Operation mode: NM 1) M 2) LSA 3) TLS 4 Joker 5)

Area: Terminal strip X4 9.1 - 16.2

Name: Cable-No..:

Location (max. 20 characters) Current

(A) Circuit-No..

Joker- function

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 NM

M Luminaire 1

SM

NM Luminaire 2 M SM

NM M

Luminaire 3 SM

NM Luminaire 4 M SM

NM M

Luminaire 5 SM

NM Luminaire 6 M SM

NM M

Luminaire 7 SM

NM Luminaire 8 M SM

NM M

Luminaire 9 SM

NM Luminaire 10 M SM

NM M

Luminaire 11 SM

NM Luminaire 12 M SM

Total current

1) NM = Non-maintained light Joker-Function

2) M = Maintained light NM = Non-maintained light

3) LSA 8.1 = Light switch monitor (1 - 3 ) M = Maintained light

4) TLS = Staircase lightswitch (1 - 3 ) SM = Switched maintained light 5) Joker = Joker-circuit

Page 66: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 65 INOTEC Sicherheitstechnik GmbH 29.08.2007

Connection plan, final end circuitsCPS - Terminal strip X 5 Project: CPS 220: CPUS 220

Operation mode: NM 1) M 2) LSA 3) TLS 4 Joker 5)

Area: Terminal strip X5 17.1 - 24.2

Name: Cable-No..:

Location (max. 20 characters) Current

(A) Circuit-No.

Joker- function

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 NM

M Luminaire 1

SM

NM Luminaire 2 M SM

NM M

Luminaire 3 SM

NM Luminaire 4 M SM

NM M

Luminaire 5 SM

NM Luminaire 6 M SM

NM M

Luminaire 7 SM

NM Luminaire 8 M SM

NM M

Luminaire 9 SM

NM Luminaire 10 M SM

NM M

Luminaire 11 SM

NM Luminaire 12 M SM

Total current

1) NM = Non-maintained light Joker-Function

2) M = Maintained light NM = Non-maintained light

3) LSA 8.1 = Light switch monitor (1 - 3 ) M = Maintained light

4) TLS = Staircase lightswitch (1 - 3 ) SM = Switched maintained light 5) Joker = Joker-circuit

Page 67: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 66 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals - sub central CPUS B Address: 0

N

N Mains

L L

Throughwiring to further sub-stations (L, N, PE)

N - Circuit 1

N - Circuit ref. Control module 1/1

L + L +

N Circuit 2

N - Circuit ref. Control module 1/2

L+ L +

N Circuit 3

N - Circuit ref. Control module 2/1

L+ L +

N Circuit 4

N - Circuit ref. Control module 2/2

L+ L +

N Circuit 5

N - Circuit ref. Control module 3/1

L+ L +

N Circuit 6

N - Circuit ref. Control module 3/2

L+ L +

B B

+24V + 24V

⊥⊥⊥⊥ ⊥⊥⊥⊥

BUS-connections

Batt. + Batt. +

Battery-supply Sub-station (+, –)

Batt. - Batt. -

Throughwiring to further CPUS-B (+, –)

PE PE PE PE PE

PE - connections

Page 68: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 67 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals - sub central CPUS B Address: 1

N

N Mains

L L

Throughwiring to further sub-stations (L, N, PE)

N - Circuit 1

N - Circuit ref. Control module 4/1

L + L +

N Circuit 2

N - Circuit ref. Control module 4/2

L+ L +

N Circuit 3

N - Circuit ref. Control module 5/1

L+ L +

N Circuit 4

N - Circuit ref. Control module 5/2

L+ L +

N Circuit 5

N - Circuit ref. Control module 6/1

L+ L +

N Circuit 6

N - Circuit ref. Control module 6/2

L+ L +

B B

+24V + 24V

⊥⊥⊥⊥ ⊥⊥⊥⊥

BUS-connections

Batt. + Batt. +

Battery-supply Sub-station (+, –)

Batt. - Batt. -

Throughwiring to further CPUS-B (+, –)

PE PE PE PE PE

PE - connections

Page 69: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 68 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals - sub central CPUS B Address: 2

N

N Mains

L L

Throughwiring to further sub-stations (L, N, PE)

N - Circuit 1

N - Circuit ref. Control module 7/1

L + L +

N Circuit 2

N - Circuit ref. Control module 7/2

L+ L +

N Circuit 3

N - Circuit ref. Control module 8/1

L+ L +

N Circuit 4

N - Circuit ref. Control module 8/2

L+ L +

N Circuit 5

N - Circuit ref. Control module 9/1

L+ L +

N Circuit 6

N - Circuit ref. Control module 9/2

L+ L +

B B

+24V + 24V

⊥⊥⊥⊥ ⊥⊥⊥⊥

BUS-connections

Batt. + Batt. +

Battery-supply Sub-station (+, –)

Batt. - Batt. -

Throughwiring to further CPUS-B (+, –)

PE PE PE PE PE

PE - connections

Page 70: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 69 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals - sub central CPUS B Address: 3

N

N Mains

L L

Throughwiring to further sub-stations (L, N, PE)

N - Circuit 1

N - Circuit ref. Control module 10/1

L + L +

N Circuit 2

N - Circuit ref. Control module 10/2

L+ L +

N Circuit 3

N - Circuit ref. Control module 11/1

L+ L +

N Circuit 4

N - Circuit ref. Control module 11/2

L+ L +

N Circuit 5

N - Circuit ref. Control module 12/1

L+ L +

N Circuit 6

N - Circuit ref. Control module 12/2

L+ L +

B B

+24V + 24V

⊥⊥⊥⊥ ⊥⊥⊥⊥

BUS-connections

Batt. + Batt. +

Battery-supply Sub-station (+, –)

Batt. - Batt. -

Throughwiring to further CPUS-B (+, –)

PE PE PE PE PE

PE - connections

Page 71: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 70 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals - sub central CPUS B Address: 4

N

N Mains

L L

Throughwiring to further sub-stations (L, N, PE)

N - Circuit 1

N - Circuit ref. Control module 13/1

L + L +

N Circuit 2

N - Circuit ref. Control module 13/2

L+ L +

N Circuit 3

N - Circuit ref. Control module 14/1

L+ L +

N Circuit 4

N - Circuit ref. Control module 14/2

L+ L +

N Circuit 5

N - Circuit ref. Control module 15/1

L+ L +

N Circuit 6

N - Circuit ref. Control module 15/2

L+ L +

B B

+24V + 24V

⊥⊥⊥⊥ ⊥⊥⊥⊥

BUS-connections

Batt. + Batt. +

Battery-supply Sub-station (+, –)

Batt. - Batt. -

Throughwiring to further CPUS-B (+, –)

PE PE PE PE PE

PE - connections

Page 72: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 71 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals - sub central CPUS B Address: 5

N

N Mains

L L

Throughwiring to further sub-stations (L, N, PE)

N - Circuit 1

N - Circuit ref. Control module 16/1

L + L +

N Circuit 2

N - Circuit ref. Control module 16/2

L+ L +

N Circuit 3

N - Circuit ref. Control module 17/1

L+ L +

N Circuit 4

N - Circuit ref. Control module 17/2

L+ L +

N Circuit 5

N - Circuit ref. Control module 18/1

L+ L +

N Circuit 6

N - Circuit ref. Control module 18/2

L+ L +

B B

+24V + 24V

⊥⊥⊥⊥ ⊥⊥⊥⊥

BUS-connections

Batt. + Batt. +

Battery-supply Sub-station (+, –)

Batt. - Batt. -

Throughwiring to further CPUS-B (+, –)

PE PE PE PE PE

PE - connections

Page 73: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 72 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals - sub central CPUS B Address: 6

N

N Mains

L L

Throughwiring to further sub-stations (L, N, PE)

N - Circuit 1

N - Circuit ref. Control module 19/1

L + L +

N Circuit 2

N - Circuit ref. Control module 19/2

L+ L +

N Circuit 3

N - Circuit ref. Control module 20/1

L+ L +

N Circuit 4

N - Circuit ref. Control module 20/2

L+ L +

N Circuit 5

N - Circuit ref. Control module 21/1

L+ L +

N Circuit 6

N - Circuit ref. Control module 21/2

L+ L +

B B

+24V + 24V

⊥⊥⊥⊥ ⊥⊥⊥⊥

BUS-connections

Batt. + Batt. +

Battery-supply Sub-station (+, –)

Batt. - Batt. -

Throughwiring to further CPUS-B (+, –)

PE PE PE PE PE

PE - connections

Page 74: Installation and maintenance manual Central power supply system CPS 220 / CPS 220 … ·  · 2016-04-14Installation and maintenance manual Central power supply system CPS 220 / CPS

Installation and maintenance manual for central power supply system CPS 220

708 001 C 73 INOTEC Sicherheitstechnik GmbH 29.08.2007

Terminals - sub central CPUS B Address: 7

N

N Mains

L L

Throughwiring to further sub-stations (L, N, PE)

N - Circuit 1

N - Circuit ref. Control module 22/1

L + L +

N Circuit 2

N - Circuit ref. Control module 22/2

L+ L +

N Circuit 3

N - Circuit ref. Control module 23/1

L+ L +

N Circuit 4

N - Circuit ref. Control module 23/2

L+ L +

N Circuit 5

N - Circuit ref. Control module 24/1

L+ L +

N Circuit 6

N - Circuit ref. Control module 24/2

L+ L +

B B

+24V + 24V

⊥⊥⊥⊥ ⊥⊥⊥⊥

BUS-connections

Batt. + Batt. +

Battery-supply Sub-station (+, –)

Batt. - Batt. -

Throughwiring to further CPUS-B (+, –)

PE PE PE PE PE

PE - connections