Installation Guidelineof FirePro Aerosol units for Kardex Remstar
KIT-04-Shuttle XP – FPC-2
Version 1, 19-06-2012
![Page 2: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/2.jpg)
Page 1
Installation Guideline of Aerosol Generators to Kardex remstar Filing System
“Shuttle XP – FPC2”
Step 1: Identify the locations of each part for installation as indicated in figure 1 of this manual.
FPC-2 modules Installation
Step 2: Install the FPC-2 modules at location X1, as indicated in figure 1 and figure 4.
Aerosol Generators, Installation and wiring
Step 3: From the FPC-2 module (any one of the two) install two cables (Fire resistive cable, RED color, 2 X1.5mm) to the location “point X2” (electronic boards and power supply metal box) as indicated figure 2.
Step 4: The metal box is separated in to two partitions. Install one Aerosol Generator, FP-40S, inside the left partition and install the second Aerosol Generator, FP-40S, inside the right partition as indicated in figure 2, point X2 and figure 5.
Step 5: Connect the Aerosol Generator (left partition) FP-40S to the first cable. The way how to
successfully connect the wires to the aerosol generator is indicated at pages 9 & 10.
Step 6: Remove the lamp at point FirePro GEN 1 of the first FPC-2 module and connect the other edge of the first cable (two wires) at point FirePro GEN 1of the first FPC-2 module as indicated at figure 3. No wire polarization is needed at points GEN 1.
Step 7: Connect the Aerosol Generator (right partition) FP-40S to the second cable. The way how to
successfully connect the wires to the aerosol generator is indicated at pages 9 & 10.
Step 8: Remove the lamp at point FirePro GEN 2 of first FPC-2 module and connect the other edge of the second cable (two wires) at point FirePro GEN 2 of first FPC-2 module as indicated at figure 3. No wire polarization is needed at points GEN 2.
Step 9: Install another cable (Fire resistive cable, RED color, 2 X1.5mm) from the first FPC-2 module
to the location point X3 (electronic boards) as indicated at figure 2.
Step 10: Install the Aerosol Generator FP-20SE inside the metal box as indicated in figure 2, point X3.
Step 11: Connect the Aerosol Generator FP-20SE to the cable. The way how to successfully connect the wires to the aerosol generator is indicated at pages 9 & 10.
Step 12: Remove the lamp at point FirePro GEN 3 of first FPC-2 module and connect the other edge of the cable (two wires) at point FirePro GEN 3 of first FPC-2 module as indicated at figure 3. No wire polarization is needed at points GEN 3.
Step 13: Install another cable (Fire resistive cable, RED color, 2 X1.5mm) from the first FPC-2
module to the location point X4 as indicated at figure 2.
Step 14: Install the Aerosol Generator FP-100S inside the metal box, to the left, as indicated in figure 2, point X4.
Step 15: Connect the Aerosol Generator FP-100S to the cable. The way how to successfully connect the wires to the aerosol generator is indicated at pages 9 & 10.
Step 16: Remove the lamp at point FirePro GEN 4 of first FPC-2 module and connect the other edge of the cable (two wires) at point FirePro GEN 4 of first FPC-2 module as indicated at figure 3. No wire polarization is needed at points GEN 4.
Step 17: Install another cable (Fire resistive cable, RED color, 2 X1.5mm) from the second FPC-2
module to the location X5 (motor) as indicated at figure 2.
Step 18: Install the Aerosol Generator FP-200S at vertical position above the motor (location X5) at a
distance of 30cm from the generator outlet holes and motor as indicated in figure 5.
![Page 3: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/3.jpg)
Page 2
Step 19: Be sure that the outlets of the Aerosol Generator are in line with the motor.
Step 20: Connect the Aerosol Generator FP-200S to the cable. The way how to successfully connect
the wires to the aerosol generator is indicated at pages 9 & 10.
Step 21: Remove the lamp at point FirePro GEN 1of the second FPC-2 module and connect the other
edge of the cable (two wires) at point FirePro GEN 1of second FPC-2 module as indicated at
figure 3. No wire polarization is needed at points GEN 1.
Step 22: Install another cable (Fire resistive cable, RED color, 2 X1.5mm) from the second FPC-2
module to the location X6 (motor) as indicated at figure 2.
Step 23: Install the Aerosol Generator FP-200S at vertical position above the motor (location X6) at a
distance of 30cm from the generator outlet holes and motor as indicated in figure 5.
Step 24: Be sure that the outlets of the Aerosol Generator are in line with the motor.
Step 25: Connect the Aerosol Generator FP-200S to the cable. The way how to successfully connect
the wires to the aerosol generator is indicated at pages 9 & 10.
Step 26: Remove the lamp at point FirePro GEN 2 of the second FPC-2 module and connect the
other edge of the cable (two wires) at point FirePro GEN 2 of second FPC-2 module as
indicated at figure 3. No wire polarization is needed at points GEN 2.
Step 27: Don not remove the lamp at position FirePro GEN 3 & 4 of the second FPC-2 module if no
aerosol generator will be used.
Linear Head Detection cable installation
Step 28: Install the Linear Heat Detector (LHD) at the areas under protection (location X2, X3, X4,
X5, X6) as following and as indicated at figure 2:
Location X2: Inside the metal box (left & right partition) at upper level on the box metal cover plate,
fixed with clips, as indicated in figure 5.
Location X3: Inside the metal box at upper level on the box metal cover plate, fixed with clips, as
indicated in figure 5.
Location X4: Inside the metal box at upper level on the box metal cover plate, fixed with clips, as
indicated in figure 5.
Location X5: 2-3cm above motor, fixed with the use of a supporting bracket (find it locally), as
indicated in figure 5.
Location X6: 2-3cm above motor, fixed with the use of a supporting bracket (find it locally), as
indicated in figure 5.
Step 29: Remove the E.O.L. (End Of Line) resistance (6.8KΩ) from the “DETECTION” zone of the
first FPC-2 module and install it at the other end of the Linear Heat Detector (LHD) cable as
indicated in figure 3.
Step 30: Connect the LHD cable to the “DETECTION” zone of the first FPC-2 module as indicated to
figure 3.
Linking the two FPC-2 together
Step 31: Remove the E.O.L. (End Of Line) resistance (6.8KΩ) from the “DETECTION” zone of the
second FPC-2 module and install to the fire relay (COM, NO) of the first FPC-2 module as
indicated in figure 3.
![Page 4: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/4.jpg)
Page 3
Step 32: Connect a short cable (pair wire, in parallel with the EOL resistance) to the fire relay (COM,
NO) of the first FPC-2 module. Connect the other edge of the cable (two wires) to the
“DETECTION” zone of the second FPC-2 module as indicated to figure 3.
Power supply installation and wiring
Step 33: Install the power supply and the two batteries at a suitable location.
Step 34: Follow the wiring instructions as indicated at figure 3. Connect power to the first and second
FPC-2 modules.
Powering the system
Step 35: If everything is ok only the green leds on both FPC-2 modules will lit. If not an audible and
visible warning will take place. Disconnect the power and find which wire is disconnected.
Step 36: Upon successful commission close the top cover of the FPC-2 modules.
Kit Components (KIT-04-Shuttle XP - FPC2)
No Description/Details Model Quantity
1 Fire Detection & Extinguishant Module FPC-2 2
2 Back up Battery 7Ah 12V 24-107F -
3 Power Supply (24V/ 5A) O-82450S 1
4 Linear heat cable 105 deg. Celsius TH-105 25
5 Fire resistant cable [21m+2xH] 2 X1.5mm -
6 Mounting Clips ACLIP6mm 200
7 FirePro Aerosol Generator FP-200S 2
8 FirePro Aerosol Generator FP-100S 1
9 FirePro Aerosol Generator FP-40S 2
10 FirePro Aerosol Generator FP-20SE 1
Note: The batteries and the fire resistant cable can be purchased from the local market. Please let us know if
you want to be included in your kit.
![Page 5: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/5.jpg)
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Shuttle XP – FPC-2
Page 4
POINT X6
Aerosol Generator
1XFP-200S
Covers Electric motor
POINT X1
2XFPC-2
Fire Protection
Controller
Figure 1POINT X2
Aerosol Generators 2XFP-40S
Covers Electronic boards and
power supply
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – FPC-2 19/06/2012 Michaelides Loucas
POINT X5
Aerosol Generator 1XFP-200S
Covers Electric motor
POINT X4
Aerosol Generator 1X FP-100S
POINT X3
Aerosol Generator 1XFP-20S
Covers Electronic boards
![Page 6: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/6.jpg)
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Linear Heat Detector cable
Activation temperatures 105Co
Page 5
5K
1
POINT X1
Fire Protection
Controller FPC-2
E.O.L. resistance
6.8 KΩ
Point X6
Point X3
Figure 2
Point X1
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
2-3cm
Point X2
2-3cm
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – FPC-2 19/06/2012 Michaelides Loucas
Point X4
Shuttle XP – FPC-2
# 1 # 2
Point X5
Linear Heat detectorAerosol Generator FP-100S
2 X 1.5mm Fire Restive Cable
Aerosol Generator FP-20SE
Aerosol Generator FP-200S
Aerosol Generator FP-200S
Aerosol Generator FP-40SAerosol Generator FP-40S
2 X 1.5mm Fire Restive Cable
![Page 7: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/7.jpg)
+ -Detection24V in
+ -24V out
6K8
+ -
FirePro
Gen1
FirePro
Gen2
FirePro
Gen3
FirePro
Gen4
Test Lamps. Keep the test
lamp connected if no
aerosol generator will be
used.
FirePro Aerosol
Generator
FIRE FUALT
NO C NC NO C NC
Linear Heat
detector
Output Power
End of Line resistor 6.8K
FirePr
o ®FirePr
o ®
FirePr
o ®
FPC-2
Page 6
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Power Supply 24V DC
-+12V/7Ah
Battery
-+12V/7Ah
Battery
240VAC Power
Power Supply
24Vdc 5 A
Back up batteries
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – FPC-2 19/06/2012 Michaelides Loucas
Figure 3
240VAC Mains
+ -Detection24V in
+ -24V out
+ -
FirePro
Gen1
FirePro
Gen2
FirePro
Gen3
FirePro
Gen4 FIRE FUALT
NO C NC NO C NC
FirePr
o ®FirePr
o ®FirePr
o ®
FPC-2
Point X1
Shuttle XP – FPC-2
6K8
EOL Resistance of
the second FPC-2
First FPC-2 Second FPC-2
![Page 8: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/8.jpg)
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 7
2XFPC-2 modules
Figure 4
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – FPC-2 19/06/2012 Michaelides Loucas
Shuttle XP – FPC-2
2XFPC-2 modules
![Page 9: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/9.jpg)
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 8
Example: Aerosol Generator installation.
Example: Aerosol Generator
installed 30cm above motor
Example: L.H.D. Linear Heat
Detector 2-3 cm above motor
Example: L.H.D. Linear Heat Detector
Example: Clips
Figure 5REV. BYDATEDESCRIPTION
1.0 Shuttle XP – FPC-2 19/06/2012 Michaelides Loucas
Shuttle XP – FPC-2
![Page 10: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/10.jpg)
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 9
Activator cable
housing PART 1
Activator cable
housing PART 2
Connector
Connector
Pull back the
cable until the
edge of the
cable shield just
shown
Cable gland fixing component
UNIT 1
Cable gland & activator
cable housing
UNIT 2
Activator cables
Activator cables
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – FPC-2 19/06/2012 Michaelides Loucas
Shuttle XP – FPC-2
Step 3
Pull back the cable.Step 2
Connect the cable wires,
positive ( + ) & negative ( - ),
with aerosol unit connector
with any of the 2 non
polarized activator cables.
Step 1
Pass the prepared cable
through the Unit 1 = Cable
gland fixing component
Unit 2 = Cable gland &
Activator Cable housing
![Page 11: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/11.jpg)
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 10
Activator cable
housing PART 1
Activator cable
housing PART 2
Spanner key # 22Cable gland fixing
component UNIT 1
Cable gland & activator
cable housing UNIT 2Spanner key # 22
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – FPC-2 19/06/2012 Michaelides Loucas
Shuttle XP – FPC-2
Step 4
Hold the cable avoiding the
turning of the connector within
housing while turning by hand
the activator cable housing
(part 1) with activator cable
housing (part 2).
Step 5
By using two spanner keys
Connect Unit 1 (cable gland
fixing component) with Unit 2
(Cable gland & activator
cable).
![Page 12: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/12.jpg)
PART LIST
Pos
ition
Qua
ntity
Denomination Type /
1 C20TOCSTOP OUTLET COVER PLATE123
1 CABLE HOUSING
4C20HTSHOUSING TUBE1
1 C20BOCSBOTTOM OUTLET COVER PLATE
DWG. Number
2 1
3
4
Top View Iso View (Top)
Front View Side View
Bottom View
Iso View(Bottom)
55.0
Installation Options
Fixing Drills
Condenced aerosol generator FP-20ESDRAWING NUMBER: ID-20ESDATE: 15/04/10
TITLE:INSTALLATION DRAWING
Isometric View of Bracket
C204080CH
205
5 1 BRACKET C20BR
5
102
![Page 13: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/13.jpg)
1
3 2
4
5
Top View Iso View (Top)
Front View Side View
Bottom View
Iso View(Bottom)
76.0
Installation Options
Fixing Drills
Condenced aerosol generator FP-80SDRAWING NUMBER: ID-80SDATE: 15/04/10
TITLE:INSTALLATION DRAWING
Isometric View of Bracket
224.
5
PART LIST
1 1
Pos
ition
Qua
ntity
Denomination
THERMOCONECTOR
Type /
2 C80TOCPSTOP OUTLET COVER PLATE134
1 CABLE HOUSING
5C80HTSHOUSING TUBE1
1 C80BOCPSBOTTOM OUTLET COVER PLATE
C1-2-5THC
DWG. Number
C204080CH
6 17 1
BRACKET PART1 C4080BRS1BRACKET PART2 C4080BRS2
6
7
Ø6.0
96
![Page 14: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/14.jpg)
PART LIST
1 1
Pos
ition
Qua
ntity
Denomination
THERMOCONECTOR
Type /
2 C1-2-5IGNIGNITER1
3
4
1 ANGLE BRACKET SUPPORT
5
C1HTHOUSING TUBE1
1 C1HECHOUSING EXIT COVER
C1-2-5THC
DWG. Number
Condenced aerosol generator FP-100S
1
2
3
4
5
Top View Iso View (Top)
Front View Side View
Bottom View Iso View(Bottom)
Installation Options
Fixing Drills
21.5
Ø6.0
C1-2-5ABS
DRAWING NUMBER: ID-100SDATE: 15/04/10
TITLE:INSTALLATION DRAWING
26.0
![Page 15: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/15.jpg)
1
2
3
4
6
Top ViewIso View (Top)
Front View Side View
Bottom View Iso View(Bottom)
Installation Options
Fixing Drills
21.5
Ø6.0
Condenced aerosol generator FP-200SDRAWING NUMBER: ID-200SDATE: 15/04/10
TITLE:INSTALLATION DRAWING
26.0
PART LIST
1 1
Pos
ition
Qua
ntity
Denomination
THERMOCONECTOR
Type /
2 CABLE HOUSING13
5
1 ANGLE BRACKET SUPPORT
611 C2HECHOUSING EXIT COVER
C1-2-5THC
DWG. Number
C1-2-5ABSC1-2-5CH
4C2HTHOUSING TUBE
1 ROUND BRACKET "A" C1-2-5RBR
7 1 M8BOLT & NUT8 1 M6BOLT & NUT
5
7
8
144
206
92.0
![Page 16: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/16.jpg)
Weight Gross 310gr Tolerance +/- 5%
Net
MODEL FP 20SE
Mass of Extinguishing material 20gr
Activation Mode/s Electrical 6-24VD/C, min. 0.8A for 3-4 sec
FirePro Systems Ltd is the manufacturer of the FirePro products
Activator Type Heating Element with 2.3Ω(ohm) Resistance
Maximum 5mA
Self Activation Temp 300℃Classes of Fire A, B, C, F
Testing Electrical Current
20gr
Operation (Discharge) Time 5 - 10 Seconds
Discharge Outlets Two Directions Outlet
Dimension 165mm x 32mm ( incl connector housing)
Fire Extinguishing Aerosol systems
Technical Data Sheet
FP 20SE
![Page 17: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/17.jpg)
Weight
FirePro Systems Ltd is the manufacturer of the FirePro products
Activator Type Heating Element with 2.3Ω(ohm) Resistance
Maximum 5mA
Self Activation Temp 300
℃
Classes of Fire A, B, C, F
Testing Electrical Current
40gr
Operation (Discharge) Time 5 - 10 Seconds
Discharge Outlets Two Direction Outlet
Dimension 140mm x 51mm ( incl connectors housing)
Gross 610gr Tolerance +/- 5%
Net
MODEL FP 40S
Mass of Extinguishing material 40gr
Activation Mode/s Electrical 6-24VD/C, min. 0.8A for 3-4 sec
Thermally activated Thermocord at 172
℃
Fire Extinguishing Aerosol systems
Technical Data Sheet
FP 40S
![Page 18: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/18.jpg)
Weight Gross 1370gr Tolerance +/- 5%
Net
MODEL FP 100S
Mass of Extinguishing material 100gr
Activation Mode/s Electrical 6-24VD/C, min. 0.8A for 3-4 sec
Thermally activated Thermocord at 172
℃
FirePro Systems Ltd is the manufacturer of the FirePro products
Activator Type Heating Element with 2.3Ω (ohm) Resistance
Maximum 5mA
Self Activation Temp 300
℃
Classes of Fire A, B, C, F
Testing Electrical Current
100gr
Operation (Discharge) Time 5 - 10 Seconds
Discharge Outlets One Direction Outlet
Dimension 120 mm x 84 mm ( plus connector housing)
Fire Extinguishing Aerosol systems
Technical Data Sheet
FP 100S
![Page 19: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/19.jpg)
Weight
FirePro Systems Ltd is the manufacturer of the FirePro products
Activator Type Heating Element with 2.3Ω(ohm) Resistance
Maximum 5mA
Self Activation Temp 300
℃
Classes of Fire A, B, C, F
Testing Electrical Current
200gr
Operation (Discharge) Time 5 - 10 Seconds
Discharge Outlets One Direction Outlet
Dimension 150 mm x 84 mm (plus connector housing)
Gross 1840gr Tolerance +/- 5%
Net
MODEL FP 200S
Mass of Extinguishing material 200gr
Activation Mode/s Electrical 6-24VD/C, min. 0.8A for 3-4 sec
Thermally activated Thermocord at 172
℃
Fire Extinguishing Aerosol systems
Technical Data Sheet
FP 200S
![Page 20: Installation Guideline€¦ · End of Line resistor 6.8K FirePr o ® o ® FPC-2. Page 6. D C B A 4 3 2 1 D C B A 4 3 2 1. Power Supply 24V DC +-12V/7Ah Battery +-12V/7Ah Battery](https://reader036.vdocument.in/reader036/viewer/2022070916/5fb69ef171599654102406d9/html5/thumbnails/20.jpg)
FirePro Systems6 Koumandarias Street, PO Box 54080, CY-3720 Limassol, Cyprus - EU Tel.: +357 25 379999 | Fax: +357 25 354432 | Email: [email protected] www.firepro.com