Installation Manual for 008-0547-00, Rev. D Intrinsically Safe Transmitters, Option Code 2n PERSONAL INJURY WARNING DO NOT USE these products as safety or emergency stop devices or in any other ap- plication where failure of the product could result in personal injury. Failure to comply with these instructions could result in death or serious injury. WARNING The operator of this instrument is advised that if the equipment is used in a manner not specified in this manual, the protection provided by the equip- ment may be impaired. CAUTION Only qualified, service-trained personnel who are aware of the hazards involved should connect external wiring to these products. ATEX C US Sensing and Control CHAPTER 1 INTRODUCTION This installation manual is shipped with each transducer with an option code 2n amplifier. It supplements the Cali- bration Certificate that ships with each transducer that contains other important information. The most current information is available from our Web site. http://www.honeywell.com/sensotec CHAPTER 2. INTRINSICALLY SAFE INSTALLATION 2.1 Introduction 2.1.1 Intrinsic Safety A transducer ordered with option code 2n includes a 2-wire, 4 mA to 20mA am- plifier that has been certified as “intrinsi- cally safe” by the following recognized testing laboratories: Factory Mutual Research Corpora- tion (FM), United States of America Canadian Standards Association (CSA), Canada Central Laboratory for the Electric Industry (LCIE), France. LCIE is a European-approved certification body. “Intrinsic safety” insures that a circuit operated under normal and specified fault conditions is not capable of caus- ing ignition of the prescribed explosive atmosphere.

Upload: others

Post on 04-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Installation Manual for 008-0547-00, Rev. DIntrinsically Safe Transmitters, Option Code 2n

PERSONAL INJURY WARNING

DO NOT USE these products as safety or emergency stop devices or in any other ap-plication where failure of the product could result in personal injury.

Failure to comply with these instructions could result in death or serious injury.

WARNINGThe operator of this instrument is

advised that if the equipment is used in a manner not specified in this manual, the protection provided by the equip-ment may be impaired.

CAUTIONOnly qualified, service-trained personnel who are aware of the hazards involved should connect external wiring to these products.

ATEX

C US

Sensing and Control

CHAPTER 1 INTRODUCTIONThis installation manual is shipped with each transducer with an option code 2n amplifier. It supplements the Cali-bration Certificate that ships with each transducer that contains other important information. The most current information is available from our Web site.

http://www.honeywell.com/sensotec

CHAPTER 2. INTRINSICALLY SAFE INSTALLATION2.1 Introduction 2.1.1 Intrinsic Safety A transducer ordered with option code 2n includes a 2-wire, 4 mA to 20mA am-plifier that has been certified as “intrinsi-cally safe” by the following recognized testing laboratories:

• FactoryMutualResearchCorpora-tion(FM),UnitedStatesofAmerica

• CanadianStandardsAssociation(CSA),Canada

• CentralLaboratoryfortheElectricIndustry(LCIE),France.LCIEisaEuropean-approved certification body.

“Intrinsic safety” insures that a circuit operated under normal and specified fault conditions is not capable of caus-ing ignition of the prescribed explosive atmosphere.

Page 2: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

2 Honeywell • Sensing and Control

Intrinsically Safety Transmitters 008-0547-00, Rev. D

2.2 InstallationThe certification of each testing laboratory is valid when the transducer has been installed according to the installation drawings or certificates of conformity referenced in this chapter. The current versions of these installation drawings are available from our web site: http://www.honeywell.com/sensotec

2.2.1 FM Installation Drawings for I.S. ApplicationsFigure 2.1: FM-approved I.S. wiring, two single-channel barriers

Page 3: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Honeywell • Sensing and Control 3

Intrinsically Safety Transmitters 008-0547-00, Rev. D

Figure 2.2: FM-approved I.S. wiring, one dual-channel barrier

Page 4: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

4 Honeywell • Sensing and Control

Intrinsically Safety Transmitters 008-0547-00, Rev. D

2.2.2 CSA Installation Drawings for I.S. ApplicationsFigure 2.3: CSA-approved wiring, two single-channel barriers

Page 5: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Honeywell • Sensing and Control 5

Intrinsically Safety Transmitters 008-0547-00, Rev. D

Figure 2.4: CSA-approved wiring, one dual-channel barrier

Page 6: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

6 Honeywell • Sensing and Control

Intrinsically Safety Transmitters 008-0547-00, Rev. D

2.2.3 CSA Certificate of Compliance for Intrinsically Safe SystemsCopies of this certificate may be ob-tained by requesting document number 009-0028-01.

Page 7: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Honeywell • Sensing and Control 7

Intrinsically Safety Transmitters 008-0547-00, Rev. D

2.2.4 EC Product Markings and Spe-cial Conditions for Safe UseSpecial conditions for safe use:

• Ambient operating temperature: -40 °C to 93 °C

• Oninstallation,thecaseofthedevice shall either be isolated from grounded surfaces, or be at the same potential as associated apparatus ground.

A copy of the EC type Examination Certificate is available by requesting document 009-0027-01.

Page 8: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

8 Honeywell • Sensing and Control

Intrinsically Safety Transmitters 008-0547-00, Rev. D

Page 9: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Honeywell • Sensing and Control 9

Intrinsically Safety Transmitters 008-0547-00, Rev. D

2.2.5 ATEX Declaration of Conformity

Page 10: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

10 Honeywell • Sensing and Control

Intrinsically Safety Transmitters 008-0547-00, Rev. D

CHAPTER 3 NON-INCENDIVE INSTALLATION

3.1 Introduction 3.1.1 Non-IncendiveA transducer ordered with option code 2n includes a 2-wire, 4 mA to 20 mA amplifier that has been certified as “non-incendive” by the following recognized testing laboratories:

• FactoryMutualResearchCorporation(FM),UnitedStatesofAmerica

• CanadianStandardsAssociation(CSA),Canada

“Non-incendive” circuits are designed and constructed so that they are not capable under normal operating conditions or due to opening, shorting, or grounding of field wiring, of causing an ignition of the prescribed flammable gas or vapor.

3.2 InstallationThe certification of each testing laboratory is valid when the transducer has been installed according the installation drawings included in this chapter. The current versions of these installation drawings are available from our web site:

http://www.honeywell.com/sensotec

Page 11: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Honeywell • Sensing and Control 11

Intrinsically Safety Transmitters 008-0547-00, Rev. D

3.2.1 FM Installation Drawings for Non-Incendive ApplicationsFigure 3.1: FM-approved wiring, single or multiple barrier

Page 12: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

12 Honeywell • Sensing and Control

Intrinsically Safety Transmitters 008-0547-00, Rev. D

Figure 3.2: FM-approved wiring, Division 2 wiring practice

Page 13: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Honeywell • Sensing and Control 13

Intrinsically Safety Transmitters 008-0547-00, Rev. D

3.2.2 CSA Installation Drawings for Non-Incendive ApplicationsFigure 3.3: CSA-approved wiring, two single-channel barriers

Page 14: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

14 Honeywell • Sensing and Control

Intrinsically Safety Transmitters 008-0547-00, Rev. D

Figure 3.4: CSA-approved wiring, Division 2 wiring practice

Page 15: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Honeywell • Sensing and Control 15

Intrinsically Safety Transmitters 008-0547-00, Rev. D

3.2.3 CSA Certificate of Compliance for Non-Incendive SystemsCopies of this certificate may be obtained by requesting document number 009-0028-02.

RETURN PROCEDURECall, write, or visit us online for a return ma-terials authorization number before returning a unit for service. When returning a unit for service, take care to package all material so as to prevent shipping damage. Transporta-tion charges must be prepaid.

Please include a letter or report outlining the defect or complaint, as well as a description of how the device was being used. Also, give the name, telephone number, and complete mailingaddressoftheperson(s)acquaintedwith the equipment being serviced so we can contact them if necessary.

Wewilladviseyouofprice(ifapplicable)and delivery of the repaired/replaced device

within five days of receipt of the device.

CERTIFICATE OF CALIBRATION AND

TRACEABILITY

This is to certify that the products described herein meet in all material respects the speci-fications and performance requirements de-scribed in this application sheet. Test reports and other pertinent information are on file and available for inspections by your representa-tive and/or U.S. Government representative upon request. Calibration was performed with a test system incompliancewithANSI/NCSLZ540-1-1994utilizing a reference load cell and/or dead weights and an electronic indicator. The test system was within current calibration require-ments at the time of the test and is traceable to the National Institute of Standards Technol-ogy.

Page 16: Installation Manual for 008-0547-00, Rev. D Intrinsically ... · Call, write, or visit us online for a return ma-terials authorization number before returning a unit for service

Find out more

Honeywell serves its customers through a worldwide network of sales offices, representatives and distributors.Forapplicationassis-tance, current specifications, pricing or name of the nearest Authorized Distributor, contact your local sales office.

To learn more about Honeywell’s test and measurement products, call +1-614-850-5000, visit www.honeywell.com/sensotec, or e-mail inquiries to [email protected]

Sensing and Control

Honeywell

1985 Douglas Drive North

Golden Valley, MN 55422

www.honeywell.com

008-0547-00-D IL50 GLO September 2009Copyright © 2009 Honeywell International Inc. All rights reserved.

WARRANTY/REMEDY

Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Honeywell’s standard product warranty applies unless agreed to otherwise by Honeywell in writing; please refer to your order acknowledgement or consult your local sales office for specific warranty details. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace, at its option, without charge those items it finds defective. The foregoing is buyer’s sole remedy and is in lieu of all other warran-

ties, expressed or implied, including those of merchantability and fitness for a particular

purpose. In no event shall Honeywell be liable for consequential, special, or indirect dam-

ages.

While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application.

Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use.