installation & operations manual sundial › wp-content › uploads › 2017 › 07 ›...

32
INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product Models: 30PV, 30PVF, 30PV+S, 30PVF+S Control Document Number: MAN-00117, Rev A

Upload: others

Post on 07-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

INSTALLATION & OPERATIONS MANUAL

SunDial™ 30 kW PV String Inverters

Product Models: 30PV, 30PVF, 30PV+S, 30PVF+S

Control Document Number: MAN-00117, Rev A

Page 2: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 1 of 31

Disclaimer

This document is provided “as is” and Ideal Power Inc. (IPWR) makes no

representations warranties, expressed or implied, with respect to the information

contained herein. IPWR has made reasonable efforts to ensure the accuracy of

information herein and at the time of publication. However, information is constantly

evolving and IPWR does not purport the information provided is correct, comprehensive

or exhaustive. This document is for informational purposes only. You should not act

upon information without consulting IPWR or its authorized distributors.

© Copyright 2017, Ideal Power Inc. All rights reserved. No parts of this document may

be reproduced in any form without the express written permission of IPWR. Ideal Power

Inc., and the Ideal Power logo are trademarks of Ideal Power Inc. All other trademarks

and service marks belong to their respective owners.

Page 3: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 2 of 31

Table of Contents

SECTION 1.0 INTRODUCTION AND PURPOSE .......................................................................................4 FCC COMPLIANCE ......................................................................................................................................... 5 RMA AND SERVICE CONTACT .......................................................................................................................... 5

SECTION 2.0 IMPORTANT SAFETY INSTRUCTIONS................................................................................6 SAFETY INSTRUCTIONS: ALL INSTALLATIONS ....................................................................................................... 6 SAFETY INSTRUCTIONS: BATTERY INSTALLATIONS ................................................................................................ 7 SAFETY INSTRUCTIONS: ADDITIONAL ................................................................................................................. 8

SAFETY INSTRUCTIONS: HANDLING ……………………………………………………………………………………………..………8

INTEGRATED SAFETY FEATURES ........................................................................................................................ 9

GROUND FAULT DETECTION – GROUND REFERENCED PV COMBINER ................................................................... 10 GROUND FAULT DETECTION – FLOATING PV COMBINER ..................................................................................... 10 DC OVER/UNDER VOLTAGE FAULT DETECTION ................................................................................................ 10 AC CURRENT FAULT DETECTION .................................................................................................................... 10 AC FREQUENCY AND VOLTAGE FAULT DETECTION............................................................................................. 11 REGULATORY INFORMATION.......................................................................................................................... 11

SECTION 3.0 SYSTEM SPECIFICATIONS .............................................................................................. 11

SECTION 4.0 UNPACKING AND MOUNTING THE INVERTER ................................................................ 12 INVERTER MOUNTING .................................................................................................................................. 13 CLEARANCES FOR INVERTER MOUNTING……………………………………………………………………………………………………..13 INVERTER REMOVAL AND PREPARATION FOR SHIPMENT .................................................................................... 16

SECTION 5.0 AC AND DC TERMINALS - WIRING AND INSTALLATION ................................................... 16 INVERTER GROUND ...................................................................................................................................... 17

AC WIRING ................................................................................................................................................ 17

AC EXTERNAL CIRCUIT PROTECTION AND DISCONNECT …………………………………………………………………………….……18

DC WIRING ................................................................................................................................................ 18

DC CONNECTION TERMINAL OVERVIEW .......................................................................................................... 18

DC WIRING OPTIONS ................................................................................................................................... 19

COMBINER OVERVIEW…………………………………………………………………………………………………………………………….19

PV STRING INVERTER………………………………………………………………………………………………………………………….……21

CONTROL AND GRID WIRING …………………………………………………………………………………………………………………….21

BATTERY WIRING ………………………………………………………………………………………………………………………….……….21

DC3 (BATTERY) EXTERNAL CIRCUIT PROTECTION AND DISCONNECT………………………………………………………………...21

GROUND-REFERENCED COMBINER …………………………………………………………………………………………………………...21

FLOATING COMBINER……………………………………………………………………………………………………………………………..22

VERIFICATION OF ELECTRICAL CONNECTIONS .................................................................................................... 23

SECTION 6.0 OPERATING AND SHUTDOWN CONDITIONS .................................................................. 24

SECTION 7.0 MAINTENANCE AND TROUBLESHOOTING...................................................................... 25 ANNUAL PREVENTIVE MAINTENANCE ............................................................................................................. 25 VERIFY PROPER AIRFLOW .............................................................................................................................. 26 POWER TERMINALS TORQUE CHECK ............................................................................................................... 26

Page 4: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 3 of 31

COOLING SYSTEM INSPECTION ....................................................................................................................... 27 INVERTER TROUBLESHOOTING ....................................................................................................................... 27 CLEARING GFDI FAULTS- GROUND REFERENCED APPLICATIONS .......................................................................... 28 CLEARING GFDI FAULTS - FLOATING APPLICATIONS .......................................................................................... 28 FRONT PANEL DISPLAY ................................................................................................................................. 28 INVERTER FAULT/STATUS CODES.................................................................................................................... 29

SECTION 8.0 FAULT OVERVIEW ......................................................................................................... 29 FAULT HANDLING ........................................................................................................................................ 29 FAULT LOGGING VIA MODBUS...................................................................................................................... 30

Table of Figures

Figure 1: IPWR Approved Shipping Container………………………………………..……13

Figure 2: Enclosure Exterior …………………………………………………………………….…14

Figure 3: Door Clearance Guide……………………………………………………….……..….15

Figure 4: AC1 and DC2/DC3 Interconnect Boards….……………………………….…..17

Figure 5: Combiner Access Door………………………………………………….……….…….20

Figure 6: Bottom View of Combiner. …………………………………………………..…….20

Figure 7: Internal View of Ground Referenced Combiner……………….………....21

Figure 8: Internal View of Floating Combiner..………………………………………..…22

Figure 9: Front Panel LED…………..…………………………………………………………..….28

Table of Tables

Table 1: Inverter Safety Features…………………………………………………….……….….9

Table 2: Inverter Weight………………………………………………………………………….…14

Table 3: Terminal Tightening Torques …………………………………….……………...…17

Table 4: DC Wiring Nomenclature …..………………………………………………….…....18

Table 5: IEEE 1547.1 Default Voltage and Trip Time Ranges ……………………….25

Table 6: IEEE 1547.1 Default Frequency and Trip Time Ranges ……………….….25

Table 8: Fault Bit Mapping………………………………………………………..………….……30

Table 9: Fault Quick References Table…………………………………………..…….…….31

Page 5: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 4 of 31

Glossary of Terms

Acronym or Term Full Expression

AWG American Wire Gauge

CEC California Energy Commission

CPU Central Processing Unit

CSA Canadian Standards Association

DMM Digital Multi-Meter

FRU Field Replaceable Unit

GFDI Ground Fault Detection Current

IFM Insulation Fault Measurement

IMI Isolation Monitor Interrupter

Inverter Ideal Power Inverter, 30PV, 30PV+S, 30PVF, 30PVF+

LED Light Emitting Diode

MPPT Maximum Power Point Tracking

PCB Printed Circuit Board

PV Photovoltaic

SECTION 1.0 Introduction and Purpose

The purpose of this manual is to describe the proper installation, operation, maintenance,

and troubleshooting of the Ideal Power (“IPWR”) SunDial™ 30PV 30kW 3-Phase

Commercial String Inverter, as well as the SunDial™ Plus 30PV+S: 30kW 3-Phase

Commercial PV Inverter with Energy Storage.

The SunDial™ includes an integrated PV Combiner and DC Disconnect, and is

available in the following product configurations:

30PV: PV String Inverter with ground-referenced 6-String Combiner.

30PVF: 30kW 3-Phase PV String Inverter with floating 6-String Combiner.

30PV+S: 30kW 3-Phase PV String Inverter with grounded-referenced 6-String

Combiner, and factory installed energy storage port

30PVF+S: 30kW 3-Phase PV String Inverter with floating 6-String Combiner, and

factory installed energy storage port

+S Kit: a field upgrade kit. Will detailed in a separate installation document.

Page 6: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 5 of 31

The SunDial™ Series utilizes a novel Link Transformer coupled with IPWR’s patented

Power Packet Switching Architecture (“PPSA”) to deliver full galvanic isolation between

the AC grid and the PV Array. This isolation also delivers versatility PV Array wiring

options; both floating and ground-referenced unipolar PV Array are supported. Select

the appropriate Combiner model (floating or grounded), to support your specific

application.

The power ports for the SunDial™ Series include:

AC1: 3-Wire, 3-Phase unidirectional AC power output port.

DC2: DC port dedicated to PV Arrays.

DC3 (+S systems only): an auxiliary DC port dedicated to battery energy storage

systems.

FCC Compliance

Pending - This equipment has been designed to meet the limits for a Class A digital

device, pursuant to part 15, Part B of the FCC Rules.

RMA and Service Contact

Do not ship or return the Inverter without prior authorization from Ideal Power Inc.

A Return Material Authorization (RMA) number must first be obtained from Ideal Power’s

customer service department.

Use the following contact information for all technical support:

Mail Ideal Power 4120 Freidrich Lane Suite 100 Austin, TX 78744 Attn: Technical Support Email & Phone For technical support: [email protected] For warranty claims: [email protected] 512.264.1542 Online Warranty Registration www.idealpower.com/customers

Page 7: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 6 of 31

SECTION 2.0 IMPORTANT SAFETY INSTRUCTIONS

Inverter models covered in this manual: 30PV; 30PVF; 30VPV +S; 30PVF+S.

SAVE THESE INSTRUCTIONS

This manual contains important instructions for the Ideal Power 30PV; 30PVF; 30PV

+S; 30PVF+S PV Inverters. All wiring must be in accordance with the National Electric

Code ANSI/NFPA 70.

The following safety notices are used in this manual:

Danger - Procedures or situations that require action to prevent personal injury or damage to equipment.

Warning - Indicates a potentially hazardous situation that, if not avoided, can result in serious injury or death.

Important information: Includes key information for the operation of this equipment or specific instructions to maintain the warranty.

Safety Instructions: All Installations

Danger - This product includes Ground Fault Detection for both grounded and ungrounded operation of PV systems. All instructions regarding the configuration of this device must be followed. Failure to follow may result in injury, death, or damage to equipment. All GFDI related information will be marked with the symbol below:

Danger – To avoid an electric shock, verify that the Inverter’s external AC and DC

Disconnects are open (off). A minimum wait time of five (5) minutes is required after

Page 8: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 7 of 31

opening AC and DC Disconnects to assure that the Inverter’s internal capacitors have

discharged to zero voltage before performing any work on the Inverter. Utilize lockout

procedures to insure that both AC and DC Disconnects remain in the off position during

all service periods.

Warning – This photovoltaic rapid shutdown equipment (RSE) does not perform all of

the functions of a rapid shutdown system (RSS). This RSE must be installed with other

equipment to form a complete RSS that meets the requirements of NEC (NFPA 70)

section 690.12 for controlled conductors outside the array. Other equipment installed in

or on this PV system may adversely affect the operation of the PVRSS. It is the

responsibility of the installer to ensure that the completed PV system meets the rapid

shut down functional requirements. This equipment must be installed according to the

manufacturer’s installation instructions.

Safety Instructions: Battery Installations

Danger – The Inverter enclosure contains exposed high voltage conductors. The

enclosure’s front access and Combiner doors must remain closed, except during

installation, commissioning, or maintenance by trained service personnel. Do not open

or remove either door if extreme moisture is present (rain, snow, or heavy dew).

Danger – To avoid an electric shock, verify that the Inverter’s external AC and DC

Disconnects are open (off). A minimum wait time of five (5) minutes is required after

opening AC and DC Disconnects to assure that the Inverter’s internal capacitors have

discharged to zero voltage before performing any work on the Inverter. Utilize lockout

procedures to insure that both AC and DC Disconnects remain in the off position during

all service periods.

Warning – These instructions DO NOT contain any information on the operation of

battery systems outside of this product. Refer the manufacturer for the battery system

for installation and servicing instructions.

Page 9: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 8 of 31

Safety Instructions: Additional

Danger – The Inverter enclosure contains exposed high voltage conductors. The

enclosure front access and Combiner doors must remain closed, except during

installation, commissioning, or maintenance by trained service personnel. Do not open

or remove either door if extreme moisture is present (rain, snow, or heavy dew).

Danger – Ensure that the equipment is adequately installed and grounded per this

manual and all applicable codes.

Danger – Do not leave foreign objects in the Inverter enclosure. Keep the area around

the enclosure clear of trash, debris, and other combustible materials.

Warning – Personnel Qualification: Inspections and operations requiring access to

lethal AC or DC voltages, should only be performed by qualified personnel.

Warning – All field wiring must conform to the codes set forth in the National Electric

Code ANSI/NFPA 70.

Warning – A separate AC and a separate DC disconnect must be installed with this

system.

Warning – Electrostatic Discharge (ESD) Damage: The Inverter contains ESD-

sensitive equipment. Failure to use ESD control measures while servicing the

equipment may result in component damage and void the warranty.

Warning – Service and maintain the Inverter in accordance with applicable Ideal Power

procedures. Discontinue Inverter use until all equipment defects and safety hazard have

been cured. Replace damaged warning and precautionary labels.

Safety Instructions: Handling

Warning – The SunDial™ Inverter, with combiner, weighs approximately 150 pounds. It

is designed to be transported and wall-mounted by two people, without the use of lift or

power equipment. If lift or power equipment is used to move, or lift the Inverter, follow all

safety rules. Failure to do so could result in personal injury or equipment damage.

Page 10: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 9 of 31

Integrated Safety Features

The 30PV; 30PVF; 30PV+S; and the 30PVF+S incorporate the following safety

features:

Table 1: Inverter Safety Features

Feature

Action

Hinged Front and

Combiner Doors

Prevents access to hazardous AC and DC voltages and

protects internal circuitry.

Integrated fused 6-

string Combiner with

lockable DC

Disconnect

Prevents access to hazardous DC voltages and protects

internal circuitry. Fuses protect field PV wiring.

DC Ground Fault

Detection

Takes Inverter off-line when DC input ground fault is

detected on either the DC2 or DC3 Ports. Both GFDI

(ground referenced connection) and IMI (floating

connection) are supported.

DC Overcurrent and

Overvoltage Detection.

The Inverter will shut down immediately if DC input

voltages or currents are out of range.

PV Arc-Fault Detection

Both versions of the PV Combiner incorporate an integral

Arc-fault detection. The Inverter will shut down

immediately if such a fault is detected. This will require a

site visit to reset the Inverter.

AC Overcurrent and

over/under Voltage

Detection.

The Inverter will shut down immediately if AC input

voltages or currents are out of range.

AC Frequency Out of

Range

The Inverter will shut down immediately if the grid

frequency is out of range.

Anti-islanding

protection

The Inverter will shut down immediately after detecting

any of the AC faults described above. A five (5) minute

restart timer is implemented on all grid-fault events.

Page 11: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 10 of 31

Ground Fault Detection – Ground Referenced PV Combiner (30PV / 30PV+S)

For ground referenced PV array connections, the negative leg of DC2 (PV) and the

negative leg of DC3 (Battery: +S systems only) are electrically common and referenced

to earth ground through a shared 1 A GFDI fuse to detect ground fault conditions. If

such conditions are detected, the Inverter is automatically taken off-line. The Inverter

will not attempt to restart until the fault condition is cleared, and AC Power is cycled.

If the ground fault detection fuse shared between DC2 and DC3 is blown as a result of a

fault event, it must be replaced in order for the Inverter to attempt restart. Faults are

indicated on the Front Panel Display, and are also available via the Modbus RTU or

Modbus TCP communication interfaces.

Ground Fault Detection – Floating PV Combiner (30PVF / 30PVF+S)

Floating PV Arrays and Batteries (+S option only) utilize an onboard “IMI” ground fault

detection scheme. This enables the Inverter to measure the conductors of the DC

Power source. If leakage to ground is present past the limits set in UL 1741 then the

unit will fault and prevent operation until the fault is cleared from the DC source(s).

Note that the negative legs of DC2 (PV Array) and DC3 (Battery: +S option only) are

electrically common, but remain floating, relative to earth ground.

In the event of an “IMI” fault, the fault can only be cleared by cycling AC power to

the unit.

DC Over/Under Voltage Fault Detection

The Inverter also has DC over-voltage (default is 1000 Vdc) and DC under-voltage

(default is 100 Vdc) detection circuitry. If these limits are exceeded the Inverter will shut

down, or if commanded to make power, will not start. These default limits are easily

changed via the Modbus interface; however, they cannot be programmed above the

1000 Vdc factory maximum.

AC Current Fault Detection

The output voltage is synchronized to the AC utility line. The Inverter operates as a

current source following the grid voltage waveform (“voltage-following”). Should the

Inverter experience an AC current fault condition, it is automatically taken off line. The

Inverter is shipped from the factory with a default five (5) minute restart countdown

timer.

Page 12: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 11 of 31

AC Frequency and Voltage Fault Detection

The quality of the power delivered to the utility line must meet or exceed the

requirements as specified in IEEE 1547a. If the utility frequency or voltage shifts outside

the regulatory specified limits, the Inverter will automatically detect the condition and

shutdown. The Inverter is shipped from the factory with a default five (5) minute restart

counter for AC over/under Frequency limit faults and AC over/under voltage limit faults.

Regulatory Information

The 30PV; 30PVF; 30PV +S; 30PVF+S PV Inverters are certified to the following

standards for the North American market:

UL 1741: Standard for Battery Inverters, Inverters, Controllers, and

Interconnection System Equipment for Use with Distributed Energy Resources

IEEE 1547a: Distributed Resources Interconnection and Interoperability with the

Grid

UL 1998: Software in Programmable Components

SECTION 3.0 System Specifications

Maximum AC Input Voltage 528 Vac

Maximum DC Input Voltage 1000 Vdc

AC Operating Voltage Range 422 to 528 Vac

DC Operating Voltage Range 100 to 1000 Vdc

DC Maximum Input Current 60 A (10 A per PV string)

DC Minimum Start-up Current 1 A

AC Maximum Input Current 44 A

AC Minimum Start-up Current 1 A

Maximum Input Source Backfeed Current to Input Source

Pending

Maximum Input Source Backfeed Current to Input Source

Pending

Output Power Factor Range 0.95 Leading to 0.95 Lagging

Operating Frequency Range 57 to 64 Hz

Nominal AC Output Voltage 480 Vac

Nominal DC Output Voltage 750 Vdc

Nominal Output Frequency 60 Hz

Maximum AC Continuous Output Power 29.99 kW

Page 13: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 12 of 31

Maximum DC Continuous Power 30 kW

Maximum AC output fault current and duration TBD

Maximum DC output fault current and duration TBD

Maximum AC output overcurrent protection (software) 44 A RMS

Maximum DC output overcurrent protection (software)

60 A

DC Charging Output Voltage Range 100 to 1000 Vdc

Utility Interconnection Voltage and Frequency Trip Limits and Trip Times

UL 1547.1 Compliant, see Tables 6 and 7.

Synchronization In-rush Current TBD

Trip Time Accuracy TBD

Trip Limit Accuracy Voltage TBD

Trip Limit Accuracy Frequency TBD

Temperature Range (full power operation) -25 °C to 50 °C

Maximum Operating Temperature (output derated) 60 °C

Typical Efficiency 95%

Maximum Efficiency 95.5%

Tare Losses 15 W

External Power supply voltage range input to Inverter 18 to 26 Vdc

GFDI trip limit 1 A

IMI trip level < 3.8 k Ohms to ground

Communication Interfaces RS485 Modbus RTU-2W / Modbus TCP Over Ethernet

NEMA rating 3R

Weight Approximately 150 lbs.

SECTION 4.0 Unpacking and Mounting the Inverter

Two-man lift: Observe all safe practices while moving or mounting the Inverter. The

Inverter can be set safely on its back or vertical if properly supported until it’s ready to

be mounted.

Storage before installation: Store the Inverter in its original shipping container indoors in

a non-condensing environment between -40 °C to 85 °C.

Disposal of shipping material: Please adhere to all local recycling if you choose to

dispose of the shipping material.

Page 14: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 13 of 31

Figure 1: IPWR Approved Shipping Container

1. Box

2. Mounting Bracket

3. Mounting Hardware

4. Foam

5. Customer Quick Link Card

6. Inverter

Inverter Mounting

The SunDial™, when installed on its wall mounting bracket, weighs approximately 160

pounds. External dimensions are 20.7” W x 51.1” H x 16.6” D. The SunDial™ MUST

always be installed in a vertical upright position for final installation, as well as

evaluation purposes. Do not block cooling airflow to the bottom air intake filter, or the

exhaust output, which is located on the upper door face of the unit.

Clearances for Inverter Mounting:

1. Minimum bottom clearance requirement: Outdoors: 36 inches above ground;

Indoors: 18 inches above floor. Violation of this clearance will void the warranty.

2. Minimum front clearance requirement: 36 inches from the front of the Inverter

must be clear of flammable materials or obstructions.

3. Minimum side clearance requirement: 4 inches from the left and right sides of the

Inverter must be observed. The product label must be clearly visible at all times.

Page 15: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 14 of 31

Warning: The unit must be mounted upright and level for the closed loop liquid cooling

system to work correctly.

Figure 2: Enclosure Exterior

Step 1. Secure the wall mounting bracket to the desired surface using either a metal

Uni-strut type railing rated for the Inverters weight or a concrete wall. Ensure mounting

bracket is level within +/- 5 degree.

Step 2. Using a two-man lift procedure carefully lift the Inverter and set it on the

provided wall bracket.

Step 3. Secure the bottom two bolts located at the bottom plate of wall bracket to the

Inverter. Torque these to 40 inch-pounds.

Step 4. Confirm the Inverter is mounted level and that the minimum clearance has been

met.

Table 2: Inverter Weight

30PV /30PVF ˜150 lbs.

30PV+S / 30PVF+S ˜152 lbs.

Mounting Bracket ˜8 lbs.

Page 16: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 15 of 31

Figure 3: Door Clearance Guide

The Inverter installation must allow for the front door to swing freely open for service purposes. Although 90 and 180-degree swing angles are shown above, a minimum swing angle of 135 degrees is required to ensure that access for initial system wiring and ongoing maintenance of the unit is not compromised.

Page 17: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 16 of 31

Inverter Removal and Preparation for Shipment

1. Open AC Disconnect.

2. Open DC Disconnect(s).

3. Wait five (5) minutes for capacitors to discharge.

4. Open the enclosure’s hinged access front cover.

5. Disconnect the AC and DC power cables.

6. Disconnect the Conduit connections.

7. Disconnect Modbus Interface cables, and other low-voltage cables.

8. Disconnect chassis ground connections.

9. Close the front cover.

10. Remove the Inverter from the wall mount bracket.

11. Package the Inverter in IPWR approved packaging (Double wall, B/C fluting box,

and foam packing).

SECTION 5.0 AC and DC Terminals - Wiring and Installation

Tools Required:

-To open enclosure and Combiner doors – 3 mm Allen Wrench. -To connect field AC and DC wiring – flat blade Screwdriver. -To connect earth ground safety wiring - flat blade Screwdriver.

Danger – Do not remove or reconfigure the Inverter’s factory wiring. Contact Ideal

Power at [email protected].

Warning – Changing the Inverter’s DC jumper configuration as it was received from the

factory may result in unexpected or unsafe operation. DC jumper configuration must

match the approved field wiring configuration. Consult a certified professional before

changing the Inverter’s factory defaults. All ground-referenced and ungrounded

connections must be field wired to NEC NFPA 2015 standards.

Warning – All AC wire connections are to be made with UL listed 6-gauge wire rated for

600 Vac; 40 A. All wires shall be torqued to 50 inch-pounds.

Warning - The Inverter’s default configuration supports a 480 Vac line-to-line 60 Hz grid

connection.

Warning – Grounding the Inverter must be done using the provided ground lug.

Page 18: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 17 of 31

Important information: - Ideal Power’s SunDial™ Inverters feature AC power

interfaces that are galvanically isolated from all DC source(s).

Figure 4: AC1 and DC2/DC3 Interconnect Boards (+S version shown)

Table 3: Terminal Tightening Torques

Terminal Block Location Wire Size / Torque

AC Compression Terminals: T4,T5,T6

Bottom of AC1 Wiring Interconnect Board

#4-6 AWG / 62 Inch-pound

DC Compression Terminals: T5,T6,T7,T8,T9, T10

Bottom of DC2/DC3 Wiring Interconnect Board

#4-6 AWG / 62 Inch-pound

Ground Terminal Below AC1 Wiring Interconnect Board

#4-6 AWG / 62 Inch-pound

Inverter Ground

The Inverter has an Earth Ground compression terminal that supports up to 4-gauge

wire for ground connections. All terminations are made to bare wire, using a flat blade

screwdriver drive head. No crimping is required when making the ground connection.

AC Wiring

Connect the 3-480 Vac phase legs to terminals T4, T5, and T6; (Phase A, Phase B, and

Phase C), utilizing the compression terminals as described above. The order of the

phases is not critical as the Inverter will sense and follow the AC grid. All power is

Page 19: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 18 of 31

made between the phase legs. No neutral connection is required, or provided on the

SunDial™ Series. Torque all connections as outlined in Table 3.

AC External Circuit Protection and Disconnect

The SunDial™ must be installed with external circuit protection. A 50A 3-Phase 3-wire

AC breaker, rated at 480 Vac is commonly used for such purposes. In some jurisdictions,

this circuit breaker may also be approved for use as a safety disconnect. However, Ideal

Power recommends that you confirm specific AC disconnect requirements with your local

Authority Having Jurisdiction (“AHJ”). Some utilities may require an external “red-handle”

lockable disconnect, in additional to the protection breaker.

DC Wiring

Table 4: DC Wiring Nomenclature

Terminal Description Used by 30PV /

30PVF Used by 30PV+S /

30PVF+S

T7 +DC2* YES YES

T8 -DC2 (DC Common)* YES YES

T9 -DC3 (DC Common) NO YES

T10 +DC3 NO YES

T5, T6 GFDI Sense Internally

connected

Internally

connected

*Factory wired to Combiner output.

DC Connection Terminal Overview

T7 is the positive PV connection for DC2. T8 is the negative PV connection for

DC2. These DC power connections are factory wired to the Combiner. Do not

disturb or change these connections.

T10 is the positive battery connection for DC3. T9 is the negative battery

connection for DC3. These DC power connections are utilized by the 30PV+S /

30PVF+S only.

GFDI sense inputs (T5, T6) are factory internally connected. Do not make a

Page 20: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 19 of 31

connection to these terminals as this would interfere with the GFDI function.

Note that the negative input for DC2 (T8: DC COM) and the negative input for

DC3 (T9: DC COM: +S option only) are wired together and are electrically

common behind the Filter Chokes installed on DC2 and DC3 (+S option only).

DC Wiring Options

The DC2 Port supports either ground-referenced monopolar, or floating PV connections,

depending upon the Combiner type selected.

If a floating Combiner is selected, the battery connected to DC3 (30PVF+S only)

MUST also be floating, and cannot be referenced to earth ground.

If a ground-referenced Combiner is selected, the battery connected to DC3

(30PV+S only) will be ground-referenced,.

Note that there are configuration jumpers on the DC2/DC3 Interconnect Board.

These jumpers are factory configured to support either the floating, or ground-

referenced Combiner type. Do not disturb or change these connections.

Note that the floating and ground-referenced Combiners are unique and different

equipment designs. They are not interchangeable.

Combiner Overview

Access to both the enclosure and the Combiner requires a 3 mm Allen Wrench. The

Combiner’s DC Disconnect must be in service position (facing left) to open the Combiner

door. The DC Disconnect is “ON” when facing up or down. For lockout purposes, the DC

Disconnect must face right. The Combiner and enclosure doors are both hinged on the

left side.

Both versions of the Combiner feature three 1-inch conduit fittings located on the

Combiner bottom access panel. The conduit fittings simplify the routing and termination

of AC1 and DC3 (+S option only) power cables, as well as low-voltage control

wiring. Once routed through the Combiner, the AC and DC power is terminated on the

AC1 and DC2/DC3 interconnect boards. Low-voltage control wiring is terminated to the

control board, located on the upper left side of the enclosure. Use the left-most Conduit

fitting, as well as the two cable-guides provided in the enclosure to route and contain low-

voltage wiring.

Page 21: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 20 of 31

The Combiner’s base includes three (3) one-inch flexible conduit fittings for low-voltage

control, AC, and DC3 battery connections (+S option only). Both versions of the Combiner

also include 6-pairs of MC4-type bulkhead connectors for field-termination of PV Strings.

Packaged within each Combiner are 6-pairs of field-crimpable MC4-type connectors

(crimp tool is not provided). The internal designs of the ground-referenced Combiners

are notably different in layout, component count, and location. The ground-referenced

Combiner utilizes six (6) string fuses, located on the positive leg of the string inputs. The

floating Combiner utilizes 12-string fuses, one on each positive, as well as each negative

string input.

Figure 5: Combiner Access Door

Figure 6: Bottom View of Combiner

Page 22: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 21 of 31

Figure 6 provides a bottom view of the Combiner. Both the floating and ground-

referenced versions of the Combiner share this common set of connectors.

PV String Wiring Up to six (6) PV strings are terminated to the 12 Amphenol MC4 bulkhead connectors

located in the center of Figure 6. The blue plugs shown are removed and discarded

prior to termination. A total of 6-female and 6-male 10-gauge Amphenol MC4 crimp

connectors are provided by Ideal Power (bubble-packed in the Combiner), for field

wiring and termination.

Control and Grid Wiring The 1-inch conduit fittings located to the left of the MC4 connectors support low-voltage

and AC1 (AC power) connections to the Inverter. Both low-voltage control as well as

the AC power wiring pass through the Combiner; for termination on the Control Board

and the AC1 Interconnect Board.

Battery Wiring The 1-inch conduit fittings located to the right of the MC4 connectors support the DC3

battery wiring connection for SunDial™ +S systems. This wiring passes through the

Combiner for termination on the DC3 (T10) and DC COM (T9) terminals which are located

on the D2/DC3 Interconnect Board. The conduit fitting may be field replaced as necessary

to support other conduit types. This is not utilized in PV-only applications.

DC3 (Battery) External Circuit Protection and Disconnect

The 30PV+S must be installed with external fused circuit protection on its DC3 (battery)

power port. A 1000 Vdc rated, 100 A fused PV Disconnect is commonly used for such

purposes. However, Ideal Power recommends that you confirm specific DC disconnect

and safety requirements with your local Authority Having Jurisdiction (“AHJ”).

Figure 7: Internal View of Ground-Referenced Combiner

Page 23: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 22 of 31

Ground-Referenced Combiner

The 30PV and 30PV+S SunDial™ Inverters utilize a circuit that references the negative

leg of the combined PV Strings to earth ground via Ground Fault Detection Interface

(GFDI) circuit, which senses DC fault currents. The 1 A fault fuse located on the

DC2/DC3 Interconnect Board will open whenever a ground fault on DC COM of > 1 A is

encountered. The fuse must be replaced; the fault condition must be cleared; and the

Inverter AC power must be cycled, to clear the Inverter’s internal GFDI fault. This is

known as a “lock-down” fault, requiring a site visit to clear.

The ground-referenced Combiner utilizes six (6) “touch-safe” string fuses located on the

positive leg of each string input, the six (6) negative String legs are not fused.

The combined positive legs are connected internally to DC2 (T7) on the DC2/DC3

Interconnection Board, which is located in the main enclosure, above the Combiner.

The combined negative legs are connected internally to DC COM (T8) on the DC2/DC3

Interconnection Board.

A PV arc-fault detection circuit is mounted above the fuse holders, with its detection

toroid mounted to the immediate right. A detected arc-fault is a lock-down fault

condition, requiring a site visit to clear. See Section 8.0 for more fault details.

Floating Combiner

The 30PVF and 30PVF+S SunDial™ Inverters utilize an IMI circuit for the detection of

ground faults. Describing the operation of this fault detection circuit is beyond the scope

of this manual, however, like the GFDI circuit described above, an IMI-detected ground

fault on DC COM is a lock-down fault requiring a site visit to clear.

Figure 8: Internal View of Floating Combiner

Page 24: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 23 of 31

Verification of Electrical Connections

Use the following procedure to verify final Inverter wiring after completing the AC, DC,

and Ground wiring as detailed in Section 5.0. High voltages are present and only qualified

personnel following safety procedures detailed in Section 2.0 should attempt the

following:

1. Open all AC and DC Disconnects

2. Open the enclosure front door and the Combiner door

3. Close the external AC Disconnect connected to Port AC1

a. Using a DMM on the AC voltage scale, verify that 480 Vac 3-Phase power is

present on the AC terminals. Measurements from each individual phase-leg

to ground should read approximately 277 Vac

b. If observed AC measurements do not meet the above requirements,

immediately open the AC Disconnect and remedy AC wiring faults

4. Close the external DC Disconnect connected to Port DC3 (only applies to models

30PV+S / 30PVF+S)

a. Using a DMM on the DC voltage scale, measure the the battery DC input

voltages (T9 and T10)

b. If observed DC voltages are higher than 1000 Vdc or outside of battery

design expectations, open the DC Disconnect and remedy DC wiring faults.

c. Measure voltage from T9 (DC3 Common) to earth ground and confirm the

following:

i. For a ground-referenced Combiner application, voltage between T9

and earth ground should read “0” volts, or

ii. For a floating Combiner application, the voltage should read other than

zero. Then meaure the voltage from T10 (DC3 positive) to earth

ground: the sum of these two measured voltages should be equal to

the observed battery voltage

5. Open all string fuses in the Combiner

a. Install the first PV string by connecting it’s MC4 negative and postive

connectors to the leftmost pair of MC4 bulkhead connectors

b. Using a DMM on the DC voltage scale, measure the the PV string DC open

circuit voltages

Page 25: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 24 of 31

i. For ground-referenced applications, meaure the voltage between earth

ground and the appropriate string fuse input lug, or

ii. For floating applications, measure the voltage between the positive

input lug of the appropriate string fuse and it’s corresponding negative

lug.

c. If observed DC voltages are higher than 1000 Vdc or outside of PV array

open-circuit (Voc) design expectations, remedy DC string wiring faults

d. Close string fuse

6. Repeat Steps 5a through 5d for remaining strings. Ensure that all open circuit

voltages match one-another within a few volts. Remedy any string wiring faults if

encountered, before closing remaining string fuses

7. Once all string voltages are measured and closed, close and secure the Combiner

door, and rotate the Combiner DC Disconnect to the closed (up) postion

a. Using a DMM on the DC voltage scale, measure the the combined PV DC

input open circuit (Voc) voltages between DC2 Com (T8) and DC2+ (T7)

b. If observed DC voltages are not within a few volts of previously measured PV

open circuit voltages, open the DC Disconnect, and return to Step 5

c. Measure voltage from T8 (DC2 Common) to earth ground and confirm the

following:

i. For a ground-referenced Combiner application, voltage between T8

and earth ground should read “0” volts, or

ii. For a floating Combiner application, the voltage should read other than

zero. Then meaure the voltage from T7 (DC2 positive) to earth

ground: the sum of these two measured voltages should be equal to

the observed PV array open circuit voltage (Voc)

8. Close and secure the enclosure front door

SECTION 6.0 Operating and Shutdown Conditions

The Inverter is shipped in an idle power state, and will not respond to power export or

import commands, as commanded via Modbus, until the following conditions are met:

All external AC and DC Disconnects are closed.

Page 26: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 25 of 31

No DC Port input ground faults have been detected.

DC Port input voltages are within the specified operating range, as set by the

Modbus Interface.

There are no sensed fault conditions, as defined in Section 7.0.

AC grid voltage and frequency are within specified IEEE 1547.1 default ranges,

and islanding is not detected. Voltage and Frequency Ranges are detailed

below.

Table 5: IEEE 1547.1 Default Voltage and Trip Time Range

Voltage Range (expressed as % of base voltage)

Clearing Time (s)

Clearing Time: adjustable up to, and including (s)

V < 45 0.16 0.16

45 < V < 60 1 11

60 < V < 88 2 21

110 < V < 120 1 13

V > 120 0.16 0.16

Table 6: IEEE 1547.1 Default Frequency and Trip Time Range

Default Settings Ranges of Adjustability

Function Frequency (Hz)

Clearing Time (s)

Frequency (Hz)

Clearing Time: adjustable up to, and including (s)

UF1 < 57 0.16 56 to 60 10

UF2 < 59.5 2 56 to 60 300

OF1 > 60.5 2 60 to 64 300

OF2 62 0.16 60 to 64 10

SECTION 7.0 Maintenance and Troubleshooting

Annual Preventive Maintenance

The procedures in this section are to be performed only by qualified personnel.

Page 27: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 26 of 31

Danger: HIGH VOLTAGE

To eliminate high voltages inside the Inverter enclosure:

All DC Disconnects must be open

All AC Disconnects must be open

Wait at least five (5) minutes for internal capacitors to discharge

DO NOT open the enclosure door or Combiner door until the Inverter has been

rendered safe in this manner. High DC voltages may be present on terminals of an open

GFDI Fuse if the DC Disconnect is NOT open.

Verify Proper Airflow

Check the bottom airflow intake filter and ensure that the forced air intake and exhaust

vents on the bottom and at the top front of the Inverter are not obstructed. Note that

under low-power conditions fan speeds and noise levels are quite low.

Remove and clean the filter if the airflow is restricted due to dust or other debris.

Replace the filter, if soiled.

Power Terminals Torque Check

Annually re-torque the power terminals to the specified torque levels in Table 3.

1. Open both external DC Disconnects and lock in the open position.

2. Open the external AC Disconnect and lock in the open position.

3. Wait at least five (5) minutes for the Inverter internal capacitors to discharge to safe

voltage levels.

4. Open the enclosure front door.

5. Using a DMM on the DC voltage scale, measure all DC input voltages, to verify that

DC line capacitors have bled down to a safe voltage level.

6. Using a DMM on the AC voltage scale, measure the AC input voltages, to verify tat

AC line capacitors have bled down to a safe voltage level.

Page 28: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 27 of 31

WARNING: Measure T7 to T8, T10 to T9, and from each terminal to chassis GND, to

ensure that all voltages have bled down to a safe level.

7. Using a calibrated torque wrench fitted with an appropriate flat screwdriver tip,

tighten the terminals listed in to the specified torque levels in Table 3 (torque levels

conform to UL 1741: Table 66.1).

Cooling System Inspection

1. With the Inverter operating, verify that the fan is operating correctly, with no

appreciable bearing or mechanical noise.

2. Safely shut down the Inverter as detailed above (re-torque power connections), and

inspect the heat exchanger for blockage or damage.

3. If the heat exchanger is blocked or damaged contact Ideal Power.

4. With the Inverter shut down, remove and inspect bottom fan intake filter by removing

the retaining thumbscrew. Clean filter carefully with compressed air and re-

assemble.

5. If the fan is noisy or otherwise suspect, contact Ideal Power for a replacement unit and installation instructions.

Inverter Troubleshooting

The procedures in this section are to be performed only qualified personnel.

Danger: HIGH VOLTAGE

To eliminate high voltages inside the Inverter enclosure:

All DC Disconnects must be open

All AC Disconnects must be open

Wait at least five (5) minutes for internal capacitors to discharge

DO NOT open the enclosure front door until the Inverter has been rendered safe in this

manner. High DC voltages may be present on terminals of an open GFDI Fuse if the DC

Disconnect is NOT open.

Page 29: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 28 of 31

Clearing GFDI Faults- Ground Referenced Applications

In the event of a detected ground fault the Inverter will cease exporting or importing

power. The fault will be noted on the front panel display. If the fault exceeds 1 A, the

ground fault detection fuse will open. The DC2 Port (30PV) and the DC3 Port (30PV+S)

both share a ground fault detection circuit and fuse. If a ground fault is indicated,

inspection and repair of wiring should be referred to qualified personnel. Once the

ground fault is remedied, check the front panel display for an indication that the

detected ground fault condition has cleared. If the display indicates the ground fault

interruption fuse has opened, follow the procedure below to replace the ground fault

fuse. Use an identical 508 Series 3AB 1 A fuse type for replacement.

Clearing GFDI Faults - Floating Applications

In the event of a detected ground fault the Inverter will cease exporting or importing

power. The fault will be noted on the front panel display. In floating applications, an IMI

impedance sensing circuit is utilized.

If a ground fault is indicated, inspection and repair of wiring should be referred to

qualified personnel. Once the ground fault is remedied, check the front panel display for

an indication that the detected ground fault condition has been cleared.

Front Panel Display

The SunDial™ front panel display features five (5) LED signals:

• FAULT LED: blinking red if Inverter has an active fault, solid red if Inverter has

GFDI/IMI/fan lockdown fault, dark otherwise

• AC PORT LED: blue if AC1 has voltage >= 120V (line-to-line)

• PV PORT LED: blue if PV/DC2 has voltage >= low-lim register

• EXPORT LED: blue if Inverter is converting power (blinking 1 Hz to 6 Hz rate

proportional to power level, i.e. blink faster if higher power)

Figure 9: Front Panel LED

Page 30: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 29 of 31

Inverter Fault/Status Codes

A more comprehensive set of Fault and Status codes shown is available via the Modbus

RTU and/or the Modbus TCP Interface. Refer to Application Note 302 (DOC-00037) for

monitoring and managing SunDial™ faults via the Modbus Interface. Portions of that

document are detailed in Section 8.0.

SECTION 8.0 Fault Overview

As noted earlier, the system is installed in an “all Ports idle” configuration state.

No Port-to-Port power transfers can or will occur until the system is configured

and commanded to move power by the system controller.

Without the system controller present, or an appropriate means to command and

monitor the Inverter via the Modbus RTU or Modbus TCP interface, other than

the front panel display, there is no means to configure, command, or monitor the

Inverter.

If an Abort fault is active, or a Lockdown fault has occurred, the Inverter will not

respond to power commands until the fault has cleared.

Fault Handling

An Ideal Power Inverter allows for a partly automated fault handling system which

operates broadly as follows. When a fault limit is reached or exceeded during operation,

the Inverter will shut down and flag an Active Fault. Provided the Inverter is being run in

Automatic Mode, once the fault condition has passed the Inverter will clear the Active

Fault flag, increment a counter on the associated Occurred Fault then initiate a count-

down timer.

Once a count-down timer reaches zero the Inverter will attempt to reconnect and

resume operating as it was prior to the fault. The Inverter may also be operated in

Manual Mode which is intended for manual test or troubleshooting operation. If run in

Manual Mode, the Inverter will not automatically attempt a restart after a fault

countdown.

The Inverter has 53 possible faults each of which are assigned one of the severity

categories below:

Info: increments the fault counter only – not detailed in this section

Alert: increments the fault counter only – not detailed in this section

Alarm: fault is logged – not detailed in this section.

Abort 0: fault is logged and unit is stopped. Reconnect timer 0 is used for restart.

Abort 1: fault is logged and unit is stopped. Reconnect timer 1 is used for restart.

Page 31: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 30 of 31

Abort 2: fault is logged and unit is stopped. Reconnect timer 2 is used for restart.

Lockdown: fault is logged, unit stops, and requires an AC power cycle to restart.

The severity levels determine if the fault is simply recorded or whether the Inverter

should be automatically shut down. Fault categories Abort 0-2 are associated with a

count-down timer. For these faults, an external acknowledgement or fault reset is not

required as is sometimes demanded by other equipment employing latching fault states.

Some faults are not automatically recoverable, such as is the case with a mechanical

fan failure, or open ground-fault fuse. These select faults are not assigned a reconnect

timer and typically require in-person intervention.

Abort 0 faults are associated with IEEE 1547 voltage & frequency grid limit

disconnection are assigned to reconnect timer #0 which has a factory default setting of

300 seconds (5 minutes) to comply with that utility interconnection code requirement.

Timers #1 and #2 are 20 seconds by default.

Changing the duration of reconnect timer #0 may invalidate your utility

interconnection agreement. Do not change this Inverter setting without utility

review and approval.

Fault Logging via Modbus

The hexadecimal fault set registers be decoded into four, 16-bit binary data fields to

determine what faults are currently active. The right most “word” indicates if a fault

between 0 to 15 is active; the next word indicates any fault between 16 and 31 which is

active, and so forth.

Table 8: Fault Bit Mapping

Fault

Set b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

2 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32

3 63 62 61 60 59 58 67 56 55 54 53 52 51 50 49 48

Page 32: INSTALLATION & OPERATIONS MANUAL SunDial › wp-content › uploads › 2017 › 07 › SunDialSeri… · INSTALLATION & OPERATIONS MANUAL SunDial™ 30 kW PV String Inverters Product

Installation & Operations Manual SunDial™ Series PV Inverter Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S MAN-00117, Rev A Page 31 of 31

For example: if Fault Set 1 were read via Modbus as hex 0C00; this translates to

0000.0000.0011.0000 in 16-bit binary format. That binary number Indicates that fault 26

and fault 27 are currently active. Note that fault positions 53 to 63 are reserved for

future use (gray colored cells in above table).

Table 9: Fault Quick Reference Table

Fault Description Severity Fault Description Severity

0 GFDI Fault Lockdown 26 AC under voltage level 1 trip Abort 0

1 IMI Fault Lockdown 27 AC under voltage level 2 trip Abort 0

2

Power module heatsink temperature fault Abort 1

28 AC under voltage level 3 trip Abort 0

3 Control board temperature fault Abort 1 29 AC under voltage level 4 trip Abort 0

4 24V auxiliary supply under voltage Abort 1 30 AC over voltage level 1 trip Abort 0

5 Fan fault Lockdown 31 AC over voltage level 2 trip Abort 0

6 DC differential over voltage Abort 1 32 AC over voltage level 3 trip Abort 0

7 DC differential under voltage Abort 1 33 AC over voltage level 4 trip Abort 0

8 Link over voltage Abort 2 34 AC under frequency level 1 trip Abort 0

9 Link starving Abort 2 35 AC under frequency level 2 trip Abort 0

10 Link over current Abort 2 36 AC under frequency level 3 trip Abort 0

11 IGBT VCES over voltage 1 Abort 2 37 AC under frequency level 4 trip Abort 0

12 IGBT VCES over voltage 2 Abort 2 38 AC over frequency level 1 trip Abort 0

13 IGBT VCES over voltage 3 Abort 2 39 AC over frequency level 2 trip Abort 0

14 IGBT VCES over voltage 4 Abort 2 40 AC over frequency level 3 trip Abort 0

15 AC A-B hard switch Abort 2 41 AC over frequency level 4 trip Abort 0

16 AC B-C hard switch Abort 2 42 Watchdog timeout Abort 2

17 AC C-A hard switch Abort 2 43 Emergency Stop Abort 0

18 DC2 input hard switch Abort 2 44 Sensing fault Abort 2

19 DC2 output hard switch Abort 2 45 Arc fault Abort 0

20 DC3 input hard switch Abort 2 46 Comms processor initiated shutdown Abort 2

21 DC3 output hard switch Abort 2 47 AC Surge detect Abort 1

22 Link state timer check Abort 2 48 AC switch breakdown voltage exceeded Abort 2

23 Bad link start Abort 2 49 DC switch breakdown voltage exceeded Abort 2

24 Invalid method/settings Abort 2 50 Precharge timeout Alarm

25 Island detected Abort 0 51 Link differential over voltage Abort 2

52 Link primary over voltage to ground Abort 2

End of Document.