    FLOW

  • 8/14/2019 INSTRU PPT.pptx

    2/130

    Over the past 60 years, the importance offlow measurement has grown, not onlybecause of its widespread use for accountingpurposes, such as the custody transfer offluid from supplier to consumer, but alsobecause of its application in manufacturingprocesses.

  • 8/14/2019 INSTRU PPT.pptx

    3/130

    Food & beverage Medical

    Mining & metallurgical

    Oil & gas transport Petrochemical

    Power generation

    Distribution

  • 8/14/2019 INSTRU PPT.pptx

    4/130

    Velocity it is a measure of speed & directionof an object or when related to fluids, it issimply the rate of flow of fluid particles in apipe.

  • 8/14/2019 INSTRU PPT.pptx

    5/130

    Laminar flow of a liquid occurs when itsaverage velocity is comparatively low & thefluid particles tend to move smoothly inlayers

  • 8/14/2019 INSTRU PPT.pptx

    6/130

    Turbulent flow occurs when the flowvelocity is high & the particles no longer flowsmoothly in layers & turbulence or a rollingeffect occurs.

  • 8/14/2019 INSTRU PPT.pptx

    7/130

    Viscosity is a property of a gas or liquid thatis a measure of its resistance to motion orflow.

    Dynamic viscosity measured in poise orcentipoise

    Kinematic viscosity measured in stokes orcentistokes

  • 8/14/2019 INSTRU PPT.pptx

    8/130

  • 8/14/2019 INSTRU PPT.pptx

    9/130

    Early flow measurement was centred roundthe question of disputation: how much hashe got versus how much have I got. Asearly as 5000 BC flow measurement was used

    to control the distribution of water throughthe ancient aqueducts of the early Sumeriancivilisations from the Tigris and Euphratesrivers. Such systems were very crude, basedon volume per time: e.g. diverting flow in onedirection from dawn to noon, and diverting itin another direction from noon to dusk.

  • 8/14/2019 INSTRU PPT.pptx

    10/130

    The first major milestone in the field of flowtechnology occurred in 1738 when the Swissphysicist Daniel Bernoulli published hisHydrodynamica in which he outlined theprinciples of the conservation of energy for flow.In it he produced an equation showing that anincrease in the velocity of a flowing fluidincreases its kinetic energy while decreasing itsstatic energy. In this manner a flow restriction

    causes an increase in the flowing velocity and afall in the static pressure the basis of todaysdifferential pressure flow measurement.

  • 8/14/2019 INSTRU PPT.pptx

    11/130

    The word turbine is derived from the Latinspinning top and although the ancient Greeksground flour using horizontal turbine wheels,the idea of using a spinning rotor or turbine

    to measure flow did not come about until1790 when the German engineer, ReinhardWoltman, developed the first vane-typeturbine meter for measuring flow velocities inrivers and canals.

  • 8/14/2019 INSTRU PPT.pptx

    12/130

    Other types of turbine meter followed. In thelate 1800sLester Pelton built the first Peltonwater wheel that turned as a result of water

    jets impinging on buckets attached around

    the outside of the wheel. And in 1916Forrest Nagler designed the first fixed- bladepropeller turbine.

  • 8/14/2019 INSTRU PPT.pptx

    13/130

    A third milestone occurred in 1832 when MichaelFaraday attempted an experiment to use his lawsof electromagnetic induction to measure flow.With the aim of measuring the water flow of theRiver Thames, Faraday lowered two metalelectrodes, connected to a galvanometer, into theriver from Waterloo Bridge. The intent was tomeasure the induced voltage produced by theflow of water through the earthsmagnetic field.

    The failure of Faraday to obtain any meaningfulresults was probably due to electrochemicalinterference and polarization of the electrodes.

  • 8/14/2019 INSTRU PPT.pptx

    14/130

    The last milestone occurred only three yearsafter Faraday conducted his originalexperiment when, in 1835, Gaspar Gustav deCoriolis, made the discovery of what is now

    termed the Coriolis effect, which led, nearly acentury and a half later, to the developmentof the highly accurate direct measurementmass flow Coriolis meter.

  • 8/14/2019 INSTRU PPT.pptx

    15/130

    The cost of many liquids & gases are basedon the measured flow through a pipelinemaking it necessary to accurately measure &control the rate of flow for accounting

    purposes.

  • 8/14/2019 INSTRU PPT.pptx

    16/130

  • 8/14/2019 INSTRU PPT.pptx

    17/130

    One of the most important primary propertiesof a fluid (liquid or gas) is its viscosity itsresistance to flow or to objects passingthrough it.

  • 8/14/2019 INSTRU PPT.pptx

    18/130

  • 8/14/2019 INSTRU PPT.pptx

    19/130

  • 8/14/2019 INSTRU PPT.pptx

    20/130

    The viscosity of a fluid also depends onpressure but, surprisingly, pressure has lesseffect on the viscosity of gases than onliquids.

    A pressure increase from 0 to 70 bar (in air)results in only an approximate 5% increase inviscosity. However, with methanol, forexample, a 0 to 15 bar increase results in a10-fold increase in viscosity.

  • 8/14/2019 INSTRU PPT.pptx

    21/130

  • 8/14/2019 INSTRU PPT.pptx

    22/130

  • 8/14/2019 INSTRU PPT.pptx

    23/130

  • 8/14/2019 INSTRU PPT.pptx

    24/130

    In a frictionless pipe in which there is noretardation at the pipe walls, a flat idealvelocity profile would result in which all thefluid particles move at the same velocity

  • 8/14/2019 INSTRU PPT.pptx

    25/130

    At low flow rates the fluid particles move instraight lines in a laminar manner witheach fluid layer flowing smoothly pastadjacent layers with no mixing between the

    fluid particles in the various layers. As aresult the flow velocity increases from zero,at the pipe walls, to a maximum value at thecentre of the pipe and a velocity gradient

    exists across the pipe.

  • 8/14/2019 INSTRU PPT.pptx

    26/130

    The shape of a fully developed velocity profilefor such a laminar flow is parabolic, with thevelocity at the centre equal to twice the meanflow velocity. Clearly, if not corrected for,

    this concentration of velocity at the centre ofthe pipe can compromise the flowcomputation.

  • 8/14/2019 INSTRU PPT.pptx

    27/130

    As the velocity increases further theindividual paths start to intertwine and crosseach other in a disorderly manner so thatthorough mixing of the fluid takes place.

    This is termed turbulent flow.

  • 8/14/2019 INSTRU PPT.pptx

    28/130

  • 8/14/2019 INSTRU PPT.pptx

    29/130

    Obstructions in a pipe, such as bends,elbows, reducers, expanders, strainers,control valves, and T-pieces, can all affect theflow profile in a manner that can severely

    affect measurement accuracy. Such disturbedflow, which should not be confused withturbulent flow, gives rise to a number ofeffects that include:

  • 8/14/2019 INSTRU PPT.pptx

    30/130

    Swirl fluid rotation about the pipe axis.

    Vortices areas of swirling motion with highlocal velocity which are often caused byseparation or a sudden enlargement in pipe

    area.

    Asymmetrical profile

    Symmetrical profile with high core velocity

    caused by a sudden reduction in pipe area.

  • 8/14/2019 INSTRU PPT.pptx

    31/130

  • 8/14/2019 INSTRU PPT.pptx

    32/130

  • 8/14/2019 INSTRU PPT.pptx

    33/130

    The onset of turbulence is often abrupt andto be able to predict the type of flow presentin a pipe, for any application, use is made ofthe Reynolds number, Re a dimensionless

    number given by:

  • 8/14/2019 INSTRU PPT.pptx

    34/130

    Irrespective of the pipe diameter, type offluid, or velocity, Reynoldsshowed that theflow is:

    Laminar: Re < 2000

    Transitional: Re = 2000 - 5000

    Turbulent: Re > 4000

  • 8/14/2019 INSTRU PPT.pptx

    35/130

    Volumetric flow rate The volumetric flow rate, Q,represents the total volume of fluid flowingthrough a pipe per unit of time and is usuallyexpressed in litres per second (l/s) or cubicmetres per hour (m3/h). The measurement of

    volumetric flow rate is most frequently achievedby measuring the mean velocity of a fluid as ittravels through a pipe of known cross sectionalarea A.

  • 8/14/2019 INSTRU PPT.pptx

    36/130

    The term velocity is often used very loosely todescribe the speed at which the fluid passes apoint along the pipe. In reality, most modernflowmeters measure either the point velocity

    or the mean velocity.

  • 8/14/2019 INSTRU PPT.pptx

    37/130

    The point velocity is the flow velocity in alocalised region or point, in the fluid and is,generally of little use in practice. It is usedmainly in research to determine, for example,

    velocity profiles or flow patterns.

  • 8/14/2019 INSTRU PPT.pptx

    38/130

    The mean flow velocity, can be obtained bymeasuring the volumetric flowrate, Q, anddividing it by the cross-sectional area of thepipe, A:

  • 8/14/2019 INSTRU PPT.pptx

    39/130

  • 8/14/2019 INSTRU PPT.pptx

    40/130

    If we want to measure the rate at which wateris flowing along a pipe. A very simple way ofdoing this is to catch all the water coming outof the pipe in a bucket over a fixed time

    period. Measuring the weight of the water inthe bucket and dividing this by the time takento collect this water gives a rate ofaccumulation of mass. This is know as the

    mass flow rate.

  • 8/14/2019 INSTRU PPT.pptx

    41/130

    More commonly we need to know the volumeflow rate - this is more commonly know asdischarge. (It is also commonly, butinaccurately, simply called flow rate). The

    symbol normally used for discharge is Q. Thedischarge is the volume of fluid flowing perunit time.

  • 8/14/2019 INSTRU PPT.pptx

    42/130

  • 8/14/2019 INSTRU PPT.pptx

    43/130

    Flow rate is the volume of fluid passing agiven point in a given amount of time & istypically measured in gpm, cfm, or lpm.

    Total flow is the volume of liquid flowing

    over a period of time & is measured ingallons, cubic feet, liters, and so on.

    Energy loses in flowing fluids are caused byfriction bet. the fluid & containment walls &by fluid impacting an object

  • 8/14/2019 INSTRU PPT.pptx

    44/130

  • 8/14/2019 INSTRU PPT.pptx

    45/130

    The continuity equation states that if theoverall flow rate in a system is not changingwith time, the flow rate in any part of thesystem is constant.

    Q=AVWhere: Q flow rate

    V average velocity

    A cross-sectional area of pipe

  • 8/14/2019 INSTRU PPT.pptx

    46/130

  • 8/14/2019 INSTRU PPT.pptx

    47/130

    If liquids are flowing in a tube with differentcross section areas, i.e., A1 and A2, as isshown in Fig. 7.2b, the continuity equationgives:

  • 8/14/2019 INSTRU PPT.pptx

    48/130

  • 8/14/2019 INSTRU PPT.pptx

    49/130

    The Bernoulli equation gives the relationbetween pressure, fluid velocity, andelevation in a flow system. The equation isaccredited to Bernoulli (1738).

  • 8/14/2019 INSTRU PPT.pptx

    50/130

  • 8/14/2019 INSTRU PPT.pptx

    51/130

    Losses are accounted for by pressure lossesand fall into two categories. Firstly, thoseassociated with viscosityand the frictionbetween the constriction walls and the

    flowing fluid, and secondly, those associatedwith fittings, such as valves, elbows, tees, andso forth.

  • 8/14/2019 INSTRU PPT.pptx

    52/130

    Frictional losses. They are losses from liquidflow in a pipe due to friction between theflowing liquid and the restraining walls of thecontainer. These frictional losses are given

    by:

  • 8/14/2019 INSTRU PPT.pptx

    53/130

    Fitting losses are losses due to couplings andfittings, which are normally less than thoseassociated with friction and are given by:

  • 8/14/2019 INSTRU PPT.pptx

    54/130

  • 8/14/2019 INSTRU PPT.pptx

    55/130

  • 8/14/2019 INSTRU PPT.pptx

    56/130

    Differential pressure measurements can bemade for flow rate determination when a fluidflows through a restriction. The restrictionproduces and increase in pressure which can

    be directly related to flow rate.

  • 8/14/2019 INSTRU PPT.pptx

    57/130

    Differential pressure flow rate meters arebased on a physical phenomenon in which arestriction in the flow line creates a pressuredrop that bears a relationship to the flow

    rate. This physical phenomenon is based on two

    well-known equations: the equation ofcontinuity and Bernoullis equation.

  • 8/14/2019 INSTRU PPT.pptx

    58/130

    Orifice plate Venturi tube

    Flow nozzle

    Dall tube

  • 8/14/2019 INSTRU PPT.pptx

    59/130

    The orifice plate is the simplest and mostwidely used differential pressure flowmeasuring element and generally comprises ametal plate with a concentric round hole

    (orifice) through which the liquid flows.

  • 8/14/2019 INSTRU PPT.pptx

    60/130

  • 8/14/2019 INSTRU PPT.pptx

    61/130

  • 8/14/2019 INSTRU PPT.pptx

    62/130

    The orifice is offset from the centre and isusually set at the bottom of the pipe bore.This configuration is mainly used inapplications where the fluid contains heavy

    solids that might become trapped andaccumulate on the back of the plate. With theorifice set at the bottom, these solids areallowed to pass. A small vent hole is usuallydrilled in the top of the plate to allow gas,

    which is often associated with liquid flow, topass.

  • 8/14/2019 INSTRU PPT.pptx

    63/130

    It should be noted, however, that the vent holeadds an unknown flow error and runs the risk ofplugging.

    Eccentric plates are also used to measure theflow of vapours or gases that carry smallamounts of liquids (condensed vapours), sincethe liquids will carry through the opening at thebottom of the pipe.

    The coefficients for eccentric plates are not as

    reproducible as those for concentric plates, andin general, the error can be 3 to 5 times greaterthan on concentric plates.

  • 8/14/2019 INSTRU PPT.pptx

    64/130

    The opening in a segmental orifice plate is acircular segment comparable to a partiallyopened gate valve. This plate is generallyemployed for measuring liquids or gases that

    carry non-abrasive impurities, which arenormally heavier than the flowing media suchas light slurries, or exceptionally dirty gases.

  • 8/14/2019 INSTRU PPT.pptx

    65/130

    The measurement of differential pressurerequires that the pipe is tapped at suitableupstream (high pressure) and downstream(low pressure) points. The exact positioning

    of these taps is largely determined by theapplication and desired accuracy.

  • 8/14/2019 INSTRU PPT.pptx

    66/130

  • 8/14/2019 INSTRU PPT.pptx

    67/130

  • 8/14/2019 INSTRU PPT.pptx

    68/130

    Pipe taps are a compromise solution and arelocated 2 pipe diameters upstream and 8pipe diameters downstream. Whilst notproducing the maximum available differential

    pressure, pipe taps are far less dependent onflow rate and orifice size.

  • 8/14/2019 INSTRU PPT.pptx

    69/130

    Simple construction. Inexpensive.

    Robust

    Easily fitted between flanges.

    No moving parts. Large range of sizes and opening ratios.

    Suitable for most gases and liquids as well assteam.

    Price does not increase dramatically with size.

    Well understood and proven.

  • 8/14/2019 INSTRU PPT.pptx

    70/130

    Permanent pressure loss of head is quite high. Inaccuracy, typically 2 to 3%. Low turndown ratio, typically from 3 to 4:1. Accuracy is affected by density, pressure and

    viscosity fluctuations.

    Erosion and physical damage to the restriction affectsmeasurement accuracy. Viscosity limits measuring range. Requires straight pipe runs to ensure accuracy is

    maintained. Pipeline must be full (typically for liquids). Output is not linearly related to flowrate. Multiple potential leakage points

  • 8/14/2019 INSTRU PPT.pptx

    71/130

    The venturi flow meter, while considered anobstruction flow meter, is less of anobstruction than the orifice type. It still doeshave a certain amount of pressure drop, but

    it is significantly less than the orifice typemeter.

  • 8/14/2019 INSTRU PPT.pptx

    72/130

  • 8/14/2019 INSTRU PPT.pptx

    73/130

    Less significant pressure drop acrossrestrictions

    Less unrecoverable pressure loss

    Requires less straight pipe up & downstream

  • 8/14/2019 INSTRU PPT.pptx

    74/130

    More expensive Bulky requires large section for installation

  • 8/14/2019 INSTRU PPT.pptx

    75/130

    The flow nozzle is used mainly in highvelocity applications or where fluids are beingdischarged into the atmosphere. It differsfrom the nozzle venturi in that it retains the

    'nozzle' inlet but has no exit section.

  • 8/14/2019 INSTRU PPT.pptx

    76/130

    A flow nozzle consists of a restriction with anelliptical contour approach section thatterminates in a cylindrical throat section.Pressure drop between the locations one pipediameter upstream and one-half pipediameter downstream is measured. Flownozzles provide an intermediate pressuredrop between orifice plates and venturi tubes;also, they are applicable to some slurry

    systems that would be otherwise difficult tomeasure.

  • 8/14/2019 INSTRU PPT.pptx

    77/130

  • 8/14/2019 INSTRU PPT.pptx

    78/130

    The main disadvantage of the flow nozzle isthat the permanent pressure loss is increasedto between 30 to 80% of the measureddifferential pressure depending on its

    design.

  • 8/14/2019 INSTRU PPT.pptx

    79/130

    Accuracy is only slightly less than for theventuri tube ( 1 to 1.5 %) and it is usuallyonly half the cost of the standard venturi. Inaddition it requires far less space for

    installation and, because the nozzle can bemounted between flanges or in a carrier,installation and maintenance are much easierthan for the venturi.

  • 8/14/2019 INSTRU PPT.pptx

    80/130

    Although many variations of low-loss metershave appeared on the market, the best-known and most commercially successful isthe Dall tube.

  • 8/14/2019 INSTRU PPT.pptx

    81/130

    The Dall tube is virtually throatless and has a

    short steep converging cone that starts at astepped buttress whose diameter is somewhatless than the pipe diameter. Following anannular space at the 'throat', there is a diverging

    cone that again finishes at a step.

  • 8/14/2019 INSTRU PPT.pptx

    82/130

    The Dall tube has the lowest insertion lossbut is not suitable for use with slurries.

  • 8/14/2019 INSTRU PPT.pptx

    83/130

    The orifice is the simplest, cheapest, easiest toreplace, least accurate, more subject to damageand erosion, and has the highest loss.

    The Venturi tube is more difficult to replace,most expensive, most accurate, has high toler-

    ance to damage and erosion, and the lowestlosses of all the three tubes.

    The flow nozzle is intermediate between theother two and offers a good compromise.

    The Dall tube has the advantage of having thelowest insertion loss but cannot be used withslurries.

  • 8/14/2019 INSTRU PPT.pptx

    84/130

  • 8/14/2019 INSTRU PPT.pptx

    85/130

    The elbow can be used as a differential flowmeter. Figure 7.6a shows the cross section of anelbow. When a fluid is flowing, there is adifferential pressure between the inside andoutside of the elbow due to the change in

    direction of the fluid. The pressure difference isproportional to the flow rate of the fluid.

    The elbow meter is good for handling particulatesin solution, with good wear and erosion resistancecharacteristics but has low sensitivity.

  • 8/14/2019 INSTRU PPT.pptx

    86/130

    A number of factors contribute to the differentialpressure that is produced and, subsequently, it isdifficult to predict the exact flow rate accurately.Some of these factors are:

    force of the flow onto the outer tapping

    turbulence generated due to cross-axial flow atthe bend

    differing velocities between outer and innerradius of flow

    pipe texture relationship between elbow radius and pipe

    diameter.

  • 8/14/2019 INSTRU PPT.pptx

    87/130

    The pilot static tube shown is an alternativemethod of measuring the flow rate, but hassome disadvantages in measuring flow, inthat it really measures the fluid velocity at the

    nozzle.

    Because the velocity varies over the crosssection of the pipe, the Pilot static tubeshould be moved across the pipe toestablish an average velocity, or the tubeshould be calibrated for one area.

  • 8/14/2019 INSTRU PPT.pptx

    88/130

    Other disadvantages are that the tube canbecome clogged with particulates and thedifferential pressure between the impact andstatic pressures for low flow rates may not be

    enough to give the required accuracy.

  • 8/14/2019 INSTRU PPT.pptx

    89/130

    The variable area flowmeter is a reversedifferential pressure meter used to measurethe flow rate of liquids and gases.

  • 8/14/2019 INSTRU PPT.pptx

    90/130

    The instrument generally comprises avertical, tapered glass tube and a weightedfloat whose diameter is approximately thesame as the tube base.

  • 8/14/2019 INSTRU PPT.pptx

    91/130

    In operation, the fluid or gas flows throughthe inverted conical tube from the bottom tothe top, carrying the float upwards. Since thediameter of the tube increases in the upward

    direction the float rises to a point where theupward force on the float created bydifferential pressure across the annular gap,between the float and the tube, equals the

    weight of the float.

  • 8/14/2019 INSTRU PPT.pptx

    92/130

  • 8/14/2019 INSTRU PPT.pptx

    93/130

    The simplest method of measuring the

    rotor speed is by means of a magnet,fitted within the rotor assembly, thatinduces a single pulse per revolution inan externally mounted pick-up coil.

  • 8/14/2019 INSTRU PPT.pptx

    94/130

    The Woltman meter, used primarily as a watermeter, is very similar in basic design to theturbine meter. The essential difference is thatthe measurement of rotation is carried out

    mechanically using a low friction gear trainconnecting the axle to the totalizer.

  • 8/14/2019 INSTRU PPT.pptx

    95/130

  • 8/14/2019 INSTRU PPT.pptx

    96/130

  • 8/14/2019 INSTRU PPT.pptx

    97/130

    Electromagnetic flowmeters, also known asMagflows or Magmeters, have now been inwidespread use throughout industry for morethan 40 years and were the first of modern

    meters to exhibit no moving parts and zeropressure drop.

  • 8/14/2019 INSTRU PPT.pptx

    98/130

    The principle of the EM flowmeter is based onFaraday's law of induction that states that if aconductor is moved through a magnetic field avoltage will be induced in it that is proportionalto the velocity of the conductor.

    Electromagnetic flow meters can only beused in conductive liquids

  • 8/14/2019 INSTRU PPT.pptx

    99/130

    used in conductive liquids. The device consists of two electrodes

    mounted in the liquid on opposite sides of

    the pipe. A magnetic field is generatedacross the pipe perpendicular to theelectrodes. The conducting fluid flowingthrough the magnetic field generates avoltage between the electrodes, which can

    be measured to give the rate of flow. Themeter gives an accurate linear outputvoltage with flow rate. There is noinsertion loss and the readings areindependent of the fluid characteristics,

    but it is a relatively expensive instrument.

  • 8/14/2019 INSTRU PPT.pptx

    100/130

    no pressure drop short inlet/outlet sections (5D/2D) insensitive to flow profile changes (laminar to turbulent) rangeability of 30:1 or better inaccuracy of better than 0.2% of actual flow over full

    range

    no recalibration requirements bi-directional measurement no taps or cavities no obstruction to flow not limited to clean fluids

    high temperature capabilities, high pressure capabilities; volumetric flow can be installed between flanges andcan be made from corrosion resistance materials at lowcost.

  • 8/14/2019 INSTRU PPT.pptx

    101/130

  • 8/14/2019 INSTRU PPT.pptx

    102/130

    Vortex flowmeters for industrial flowmeasurement were first introduced in themid-1970s but the technology was poorlyapplied by several suppliers. As a result, the

    technology developed a bad reputation andseveral manufacturers dropped thetechnology. However, since the mid-1980smany of the original limitations have been

    overcome and vortex flowmetering hasbecome a fast growing flow technology.

  • 8/14/2019 INSTRU PPT.pptx

    103/130

    Vortex meters are based on the phenomenon knownas vortex shedding that takes place when a fluid (gas,steam or liquid) meets a non-streamlined obstacle termed a bluff body. Because the flow is unable tofollow the defined contours of the obstacle, theperipheral layers of the fluid separate from itssurfaces to form vortices in the low pressure area

    behind the body.

  • 8/14/2019 INSTRU PPT.pptx

    104/130

    These vortices are swept downstream to form aso-called Karman Vortex Street. Vortices areshed alternately from either side of the bluffbody at a frequency that, within a given Reynoldsnumber range, is proportional to the mean flow

    velocity in the pipe.

  • 8/14/2019 INSTRU PPT.pptx

    105/130

    Vortices formed can be measuredultrasonically

    Vortex flow meters are mostly applied to highflow rates.

    At low flow rates, the vortex frequency tendsto be unstable.

  • 8/14/2019 INSTRU PPT.pptx

    106/130

  • 8/14/2019 INSTRU PPT.pptx

    107/130

  • 8/14/2019 INSTRU PPT.pptx

    108/130

    Includes devices used to measure the totalquantity of fluid flowing or the volume ofliquid in a flow

    Positive displacement meters use containers

    of known size, which are filled and emptiedfor a known number of times in a given timeperiod to give the total flow volume.

    Common instruments are Piston flow meter &

    nutating disc flow meter.

  • 8/14/2019 INSTRU PPT.pptx

    109/130

    The oscillating or rotating piston meterconsists of a stainless steel housing and arotating piston. The only moving part in themeasuring chamber is the oscillation piston

    which moves in a circular motion.

  • 8/14/2019 INSTRU PPT.pptx

    110/130

    The number of times the piston traverses thecylinder in a given time frame gives the totalflow.

    The meter has high accuracy but is expensive

  • 8/14/2019 INSTRU PPT.pptx

    111/130

    The term nutation is derived from the action of aspinning top whose axis starts to wobble anddescribe a circular path as the top slows down.

    In a nutating disc type meter the displacementelement is a disc that is pivoted in the centre of a

    circular measuring chamber. The lower face ofthe disc is always in contact with the bottom ofthe chamber on one side, and the upper face ofthe disc is always in contact with the top of thechamber on the opposite side. The chamber istherefore divided into separate compartments ofknown volume.

    Liquid enters through the inlet connection on

  • 8/14/2019 INSTRU PPT.pptx

    112/130

    Liquid enters through the inlet connection onone side of the meter and leaves through an

    outlet on the other side successively fillingand emptying the compartments and movingthe disc in a nutating motion around a centrepivot. A pin attached to the disc's pivot point

    drives the counter gear train.

  • 8/14/2019 INSTRU PPT.pptx

    113/130

    Although there are inherently more leakagepaths in this design, the nutating disk meteris also characterised by its simplicity andlow-cost.

    It tends to be used where longer meter life,rather than high performance, is required, forexample, domestic water service. The meteris also suitable for use under high

    temperatures and pressures.

  • 8/14/2019 INSTRU PPT.pptx

    114/130

  • 8/14/2019 INSTRU PPT.pptx

    115/130

    By measuring the flow and knowing thedensity of a fluid, the mass of the flow can bemeasured. Mass flow instruments includeconstant speed impeller turbine wheel-spring

    combinations that relate the spring force tomass flow and devices that relate heattransfer to mass flow.

  • 8/14/2019 INSTRU PPT.pptx

    116/130

    A mass flow meter, also known as an inertialflow meter is a device that measures massflow rate of a fluid traveling through a tube.The mass flow rate is the mass of the fluid

    traveling past a fixed point per unit time.

    The mass flow meter does not measure thevolume per unit time (e g cubic meters per

  • 8/14/2019 INSTRU PPT.pptx

    117/130

    volume per unit time (e.g., cubic meters persecond) passing through the device; it

    measures the mass per unit time (e.g.,kilograms per second) flowing through thedevice.

  • 8/14/2019 INSTRU PPT.pptx

    118/130

  • 8/14/2019 INSTRU PPT.pptx

    119/130

    Dry particulate flow rate can be measured asthe particulate are being carried on aconveyer belt with the use of a load cell. Tomeasure flow rate it is only necessary to

    measure the weight of material on a fixedlength of the conveyer belt.

  • 8/14/2019 INSTRU PPT.pptx

    120/130

  • 8/14/2019 INSTRU PPT.pptx

    121/130

  • 8/14/2019 INSTRU PPT.pptx

    122/130

    A weir is essentially a dam mounted at rightangles to the direction of flow, over which theliquid flows.

    For the associated equation to hold true andaccurate flow measurement determined, thestream of water leaving the crest (the nappe)

  • 8/14/2019 INSTRU PPT.pptx

    123/130

    stream of water leaving the crest (the nappe),should have sufficient fall. This is called free

    or critical flow, with air flowing freely beneaththe nappe so that it is aerated. Should thelevel of the downstream water rise to a pointwhere the nappe is not ventilated, the

    discharge rate may be inaccurate anddependable measurements cannot beexpected.

  • 8/14/2019 INSTRU PPT.pptx

    124/130

    The discharge equation (head vs. flow rate),without end contractions, is:

    where:

    q = flow rate; k = constant; L = length ofcrest; and h = the head.

    Generally, this means that for a 1 % change inflow, there will be a 0.7 % change in the level.

  • 8/14/2019 INSTRU PPT.pptx

    125/130

  • 8/14/2019 INSTRU PPT.pptx

    126/130

    Many different types of sensors can be usedfor flow measurements. The choice of anyparticular device for a specific applicationdepends on a number of factors such as-

    reliability, cost, accuracy, pressure range,temperature, wear and erosion, energy loss,ease of replacement, particulates, viscosity,and so forth.