instruction manual d2-3514 - …...communications module (recomm-485) and using it with dpi ac...

68
Instruction Manual RS485 DF1 Communications Module M/N RECOMM-485 D2-3514

Upload: others

Post on 27-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Instruction Manual

RS485 DF1 Communications Module

M/N RECOMM-485

D2-3514

Page 2: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

©2002 Rockwell Automation. All rights reserved.

The information in this manual is subject to change without notice.

Throughout this manual, the following notes are used to alert you to safety considerations:

Important: Identifies information that is critical for successful application and understanding of the product.

!ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.

Windows is a trademark of Microsoft Corporation.Reliance, SP600, VS Utilities, and DPI are trademarks of Rockwell Automation.

!ATTENTION: The drive may contain high voltages that can cause injury or death. Remove all power from the drive, and then verify power has been removed before installing or removing an RS485 DF1 module. Failure to observe these precautions could result in severe bodily injury or loss of life.ATTENTION: Only qualified electrical personnel familiar with drive and power products and the associated machinery should plan or implement the installation, start up, configuration, and subsequent maintenance of the product using an RS485 DF1 module. Read and understand this manual in its entirety before proceeding. Failure to observe these precautions could result bodily injury and/or damage to equipment. ATTENTION: DPI host products must not be directly connected together via RECBL-xxx cables. Unpredictable behavior due to timing and other internal procedures can result if two or more devices are connected in this manner. Failure to observe this precaution could result in bodily injury and/or damage to equipment.ATTENTION: If the RS485 DF1 module is transmitting controlI/O to the drive, the drive may fault when you reset the module. Determine how your drive will respond before resetting a module. Failure to observe this precaution could result bodily injury and/or damage to equipment. ATTENTION: Comm Flt Action (parameter 10) lets you determine the action of the module and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a hazard of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable or a faulted controller). Failure to observe this precaution could result bodily injury and/or damage to equipment. ATTENTION: When a system is configured for the first time, there may be unintended or incorrect machine motion. Disconnect the motor from the machine or process during initial system testing. Failure to observe this precaution could result in bodily injuryand/or damage to equipment.

Page 3: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Contents I

CONTENTSChapter 1 Introduction

1.1 Module Features............................................................ 1-11.2 Related Documentation ................................................. 1-21.3 Getting Assistance from Reliance Electric..................... 1-2

Chapter 2 Getting Started2.1 Required Equipment ...................................................... 2-22.2 Installation Checklist ...................................................... 2-3

Chapter 3 Installing the RS485 DF1 Module3.1 Preparing for an Installation........................................... 3-13.2 Commissioning the Module ........................................... 3-13.3 Connecting the Module to the Drive .............................. 3-33.4 Connecting the Module to the Network.......................... 3-63.5 Applying Power.............................................................. 3-7

Chapter 4 Configuring the RS485 DF1 Module4.1 Configuration Tools........................................................ 4-14.2 Using the LCD OIM to Configure the Module ................ 4-24.3 Setting the Node Address.............................................. 4-24.4 Setting the Data Rate .................................................... 4-34.5 Setting the Error-Checking Method ............................... 4-34.6 Setting the I/O Configuration ......................................... 4-44.7 Setting a Fault Action..................................................... 4-5

4.7.1 Setting the Fault Configuration Parameters ........ 4-64.7.2 Resetting the Module........................................... 4-6

4.8 Viewing the Module Configuration ................................. 4-8

Chapter 5 Using VS Utilities on the RS485 Network

Chapter 6 Troubleshooting the Module and Network6.1 Understanding the Status Indicators.............................. 6-1

6.1.1 DRIVE Status Indicator........................................ 6-26.1.2 MS Status Indicator ............................................. 6-36.1.3 NET A Status Indicator ........................................ 6-46.1.4 NET B Status Indicator ........................................ 6-5

6.2 Module Diagnostic Items ............................................... 6-56.3 Viewing and Clearing Events......................................... 6-7

Page 4: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

II RS485 DF1 Communications Module

Appendix A Technical Specifications...................................................... A-1

Appendix B RS485 DF1 Module Parameters .......................................... B-1

Appendix C Logic Command/Status Words............................................. C-1

Glossary ..................................................................................Glossary-1

Index ....................................................................................... Index-1

Page 5: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Contents III

List of Figures

Figure 2.1 – Components of the RS485 DF1 Module................................. 2-1

Figure 3.1 – Setting the Module’s Node Address ....................................... 3-2Figure 3.2 – Setting the Data Rate ............................................................. 3-2Figure 3.3 – DPI Ports and Internal Interface Cables ................................. 3-4Figure 3.4 – Mounting the Module .............................................................. 3-5Figure 3.5 – Typical Network Connections ................................................. 3-6

Figure 4.1 – Accessing the Module Parameters using the LCD OIM ......... 4-2Figure 4.2 – RS485 DF1 Node Address Screen on an LCD OIM............... 4-2Figure 4.3 – Data Rate Screen on an LCD OIM ......................................... 4-3Figure 4.4 – Error-Checking Method Screen on an LCD OIM .................... 4-3Figure 4.5 – I/O Configuration Screen on an LCD OIM .............................. 4-4Figure 4.6 – Fault Action Screen on an LCD OIM ...................................... 4-5Figure 4.7 – Reset Screen on an LCD OIM................................................ 4-7

Figure 5.1 – Typical RS485 DF1 Network .................................................. 5-1Figure 5.2 – Connecting to the Network ..................................................... 5-1Figure 5.3 – Node Selection Screen: Multiple Nodes Selected .................. 5-2Figure 5.4 – Results of Search of Selected Nodes..................................... 5-2Figure 5.5 – Result of Device Read Performed by VS Utilities ................... 5-3Figure 5.6 – Expanding Each Node............................................................ 5-3Figure 5.7 – Accessing the Parameters in the Selected Device................. 5-4

Figure 6.1 – Status Indicators (Location on Drive May Vary) ..................... 6-1Figure 6.2 – Viewing and Clearing Events Using an LCD OIM................... 6-7

Page 6: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

IV RS485 DF1 Communications Module

Page 7: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Contents V

List of Tables

Table 2.1 – Equipment Shipped with the RS485 DF1 Module.................... 2-2Table 2.2 – Required User-Supplied Equipment ........................................ 2-2

Table 4.1 – Configuration Tools.................................................................. 4-1Table 4.2 – Selections for Drive Response to Communication Fault.......... 4-5Table 4.3 – Fault Configuration Parameters ............................................... 4-6Table 4.4 – Module Configuration Status Parameters ................................ 4-8

Table 6.1 – DRIVE Status Indicator: State Definitions................................ 6-2Table 6.2 – MS Status Indicator: State Definitions ..................................... 6-3Table 6.3 – NET A Status Indicator: State Definitions ................................ 6-4Table 6.4 – NET B Status Indicator: State Definitions ................................ 6-5Table 6.5 – Module Diagnostic Items.......................................................... 6-5Table 6.6 – Event Codes and Descriptions................................................. 6-8

Page 8: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

VI RS485 DF1 Communications Module

Page 9: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Introduction 1-1

CHAPTER 1Introduction

This manual provides information about the RS485 DF1 Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar with installing, programming, and maintaining AC drives and networks.

The RS485 DF1 Communications module allows an RS485 DF1 Master device to access the SP600 drive using:

• Logic Command/Reference (Start, Stop, Reference, etc.)

• Logic Status Feedback

• Datalinks A-D

• Explicit Messages

It also allows VS Utilities configuration software (version 1.01 or higher) to connect to an SP600 drive using a Serial Converter module (RECOMM-232) and communicate with other SP600 drives using an RS485 connection.

The module is mounted in the drive and receives its required power from the drive. It can be used with other products that implement DPI, which is a peripheral communication interface. Refer to the documentation for your product for specific information about how it works with this module.

1.1 Module Features

The RS485 DF1 Communications module features the following:

• Switches that enable you to set a node address and network data rate before applying power to the drive. Alternatively, you can disable these switches and use parameters to configure these features.

• Status indicators that report the status of the drive communications, module, and network. They are visible both when the cover is opened and when it is closed.

• I/O, including Logic Command/Reference and up to four pairs of Datalinks that may be configured for your application using a parameter.

Page 10: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

1-2 RS485 DF1 Communications Module

• A number of tools to configure the module and connected drive. These tools include the LCD OIM and VS Utilities software.

• User-defined fault actions that determine how the module and the drive respond to communication disruptions on the network.

1.2 Related Documentation

Refer to the following related publications as necessary for more information. All of the publications are available from http://www.theautomationbookstore.com or http://www.reliance.com.

• D2-3485 SP600 AC Drive User Manual

• D2-3501 SP600 AC Drive User Manual (6SB401Series)

• D2-3488 VS Utilities Getting Results ManualOnline help installed with the software

• 1770-6.5.16 DF1 Protocol and Command Set Reference Manual

1.3 Getting Assistance from Reliance Electric

If you have any questions or problems with the products described in this instruction manual, contact your local Reliance Electric sales office.

For technical assistance, call 1-800-726-8112. Before calling, please review the troubleshooting section of this manual and check the Reliance drives website for additional information. When you call this number, you will be asked for the drive model number and this instruction manual number.

Page 11: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Getting Started 2-1

CHAPTER 2Getting Started

This chapter provides:

• A description of the RS485 DF1 module’s components

• A list of parts shipped with the module

• A list of user-supplied parts required for installing the module

• An installation checklist

� Status Indicators Four LEDs to indicate the status of the connected drive, module, and network. Refer to chapter 6 for more information about the LEDs.

� DPI Connector A 20-pin, single-row shrouded male header. An Internal Interface cable connects to this connector and one on the drive.

� RS485 DF1 Connector A 6-pin connector to which a 6-pin linear plug can be connected.

� Node Address Switches Switches to set the node address.

� Data Rate Switch Switch to set the RS485 DF1 data rate at which the module communicates.

Figure 2.1 – Components of the RS485 DF1 Module

Page 12: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

2-2 RS485 DF1 Communication Module

2.1 Required Equipment

Table 2.1 lists the equipment shipped with the RS485 DF1 module. When you unpack the module, verify that the package includes all of these items.

Table 2.2 lists user-supplied equipment also required to install and configure the module.

Table 2.1 – Equipment Shipped with the RS485 DF1 Module

Item Description

One RS485 DF1 Communication Module

One 2.54 cm (1 in) and one 15.24 cm (6 in) Internal Interface cable (only one of these cables is needed to connect the module to the drive)

One six-pin linear RS485 DF1 plug (connected to the RS485 DF1 connector on the module)

One grounding wrist strap

One RS485 DF1 Communication Module User Manual (D2-3415)

Table 2.2 – Required User-Supplied Equipment

Item Description

Small flathead or Phillips screwdriver

RS485 cable (Belden 3106A or equivalent is recommended)

Configuration tool, such as

• SP600 LCD OIM

• VS Utilities

• with Serial Converter Module (M/N RECOMM-232)

Page 13: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Getting Started 2-3

2.2 Installation Checklist

This section is designed to help experienced users start using the RS485 DF1 module. If you are unsure how to complete a step, refer to the referenced chapter.

✔ Step Action Refer to:

❒ 1 Review the safety precautions for the module.

Throughout this manual

❒ 2 Verify that the drive is properly installed. SP600 AC Drive User Manual

❒ 3 Commission the module.

Set a unique node address and the appropriate data rate using the switches on the module. If desired, you can disable the switches and use parameter settings instead.

Chapter 3

❒ 4 Install the module.

Verify that the drive is not powered. Then, connect the module to the network using an RS485 cable and to the drive using the Internal Interface cable. Use the captive screws to secure and ground the module to the drive.

Chapter 3

❒ 5 Apply power to the module.

Apply power to the drive. (The module receives power from the drive.) The status indicators should be green. Refer to chapter 6 for more information if there is a problem.

Chapter 3

❒ 6 Configure the module for your application.

Set the parameters for the following features as required by your application:

• I/O configuration

• Fault actions

Chapter 4

❒ 7 Apply power to the RS485 DF1 master.

Verify that the master and the network are installed and functioning in accordance with RS485 DF1 standards.

Page 14: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

2-4 RS485 DF1 Communication Module

Page 15: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Installing the RS485 DF1 Module 3-1

CHAPTER 3Installing the

RS485 DF1 Module

Chapter 3 provides instructions for installing the module on an SP600 drive.

3.1 Preparing for an Installation

Before installing the module, verify that you have all required equipment. Refer to chapter 2, Getting Started, for a list of equipment.

3.2 Commissioning the Module

To commission the module, you must set a unique node address on the network, the data rate used by the network, and the error-checking method. (Refer to the BCC and CRC entries in the Glossary for more information about these error-checking methods.)

Important: New settings are recognized only when power is applied to the module or it is reset. If you change a setting, cycle power or reset the module.

Important: To guard against device malfunction, you must wear a grounding wrist strap when installing the module.

Step 1. Set the module’s node address by rotating the node address switches to the desired value for each digit as shown in figure 3.1.

Important: Each node on the network must have a unique address.

!ATTENTION: The RS485 DF1 module contains ESD- (Electrostatic Discharge) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the module. Failure to observe these precautions could result in damage to equipment.

Page 16: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

3-2 RS485 DF1 Communications Module

Step 2. Set the Data Rate switch as shown in figure 3.2.

Setting Description

00 to 99 The node address used by the module if switches are enabled. The default switch setting is 01.

Important: If the Data Rate switch is set to “PGM” (Program), the module will use the setting of DF1 Addr Cfg (module parameter 3) for the node address. The default setting of this parameter is 1. Refer to chapter 4, Configuring the RS485 DF1 Module, for more information.

Figure 3.1 – Setting the Module’s Node Address

21

0

98

34

5

67

21

0

98

34

5

67

Setting Description

120024004800960019.2K38.4K

The module is set to the respective data rate.

PGM The module uses the setting of DF1 Rate Cfg (module parameter 5) for the data rate. 9600 is the default parameter setting. Refer to chapter 4, Configuring the RS485 DF1 Module for more information.

Figure 3.2 – Setting the Data Rate

2400

48009600

PGM

1200

19.2K

38.4K

Page 17: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Installing the RS485 DF1 Module 3-3

3.3 Connecting the Module to the Drive

Step 1. Remove power from the drive.

Step 2. Use static control precautions.

Step 3. Connect the Internal Interface cable to the DPI port on the drive and then to the DPI connector on the module. See figure 3.3.

Step 4. For 1-20 HP SP600 drives, fold the Internal Interface cable behind the module and mount the module on the drive using the four captive screws. See figure 3.4.

For frame 2 and larger SP600 drives, mount the module on the drive using the four captive screws to secure and ground it to the drive.

Important: All screws must be tightened since the module is grounded through a screw. The recommended tightening torque is 0.9 N-m (8 in-lb).

!ATTENTION: The SP600 drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before installing or removing a module. Failure to observe this precaution could result in severe bodily injury or loss of life.

Page 18: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

3-4 RS485 DF1 Communications Module

� DPI Connector

� RS485 Connector

� 15.24 cm (6 in) Internal Interface cable

� 2.54 cm (1 in) Internal Interface cable

Figure 3.3 – DPI Ports and Internal Interface Cables

RS485 DF1 Module

SP600 Drive1-20 HP

SP600 DriveFrame 2 and Larger

Page 19: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Installing the RS485 DF1 Module 3-5

Figure 3.4 – Mounting the Module

Module

Drive

SP600 Drive

Internal Interface cablefolded behind the moduleand in front of the drive

SP600 DriveFrame 2 and Larger

1-20 HP

Page 20: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

3-6 RS485 DF1 Communications Module

3.4 Connecting the Module to the Network

Step 1. Remove power from the drive.

Step 2. Use static control precautions.

Step 3. Connect an RS485 cable to the network, and route it through the bottom of the drive.

Step 4. Connect a 6-pin linear plug to the RS485 cable.

Step 5. Connect the cable to the module.

See figure 3.5 for typical network connections.

!ATTENTION: The SP600 drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before installing or removing a module. Failure to observe this precaution could result in severe bodily injury or loss of life.

Terminal Signal Function

GND Chassis Ground1 Shield GND termination

SHIELD Shield Shield RC termination

COM Common Signal Common

B Signal B Tx Rx D-

A Signal A Tx Rx D+

TERM Termination2 Signal RC termination

Figure 3.5 – Typical Network Connections

1 The shield must be grounded at a single point on the network (jumper terminals SHIELD and GND).

2 Jumper terminals TERM and A on the modules at the end of the RS485 network. This enables a built-in RC termination network on the module.

Node 1 Node 2 Node "n"

TERMA B COMSHIE

LDGND

TERMA B COMSHIE

LDGND

TERMA B COMSHIE

LDGND

Page 21: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Installing the RS485 DF1 Module 3-7

3.5 Applying Power

Step 1. Close the door or reinstall the cover on the drive. The status indicators can be viewed on the front of the drive after power has been applied.

Step 2. Ensure that the module will have a unique address on the network and is set at the correct data rate. If a new data rate or address is needed, reset the switches (refer to Commissioning the Module, section 3.2).

Step 3. Apply power to the drive. The module receives its power from the connected drive. When you apply power to the product for the first time, the status indicators should be green after an initialization. If there is a problem, refer to chapter 6.

Step 4. If the Data Rate switch is set to “PGM,” use a configuration tool to set the data rate and node address parameters in the module (refer to chapter 4, Configuring the RS485 DF1 Module).

Step 5. Verify that the master and network are installed and functioning in accordance with RS485 DF1 standards.

!ATTENTION: Unpredictable operation may occur if parameter settings and switch settings are not compatible with your application. Verify that settings are compatible with your application before applying power to the drive. Failure to observe these precautions could result in severe bodily injury of loss of life.

Page 22: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

3-8 RS485 DF1 Communications Module

Page 23: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Configuring the RS485 DF1 Module 4-1

CHAPTER 4Configuring the

RS485 DF1 Module

Chapter 4 provides instructions and information for setting the parameters in the module.

For a complete list of parameters, refer to Appendix B, RS485 DF1 Module Parameters. For definitions of terms in this chapter, refer to the Glossary.

4.1 Configuration Tools

The module stores parameters and other information in its own non-volatile memory. Therefore, you must access the module to view and edit its parameters. Table 4.1 lists the tools that can be used to access the module parameters.

Table 4.1 – Configuration Tools

Tool Refer to:

VS Utilities Software VS Utilities online help

LCD OIM Section 4.2

Page 24: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

4-2 RS485 DF1 Communications Module

4.2 Using the LCD OIM to Configure the ModuleUse the procedure in figure 4.1 to access the parameters on the RS485 DF1 module using the LCD OIM. If you are unfamiliar with the operation of the LCD OIM, refer to the SP600 AC Drive User Manual (D2-3485 or D2-3501) for more information.

4.3 Setting the Node Address

If the Data Rate switch on the module is set to “PGM,” the value of module parameter 3 (DF1 Addr Cfg) determines the node address.

Step 1. Set the value of module parameter 3 (DF1 Addr Cfg) to a unique node address.

Step 2. Reset the module. Refer to section 4.7.2, Resetting the Module.

Figure 4.1 – Accessing the Module Parameters using the LCD OIM

P0: SP600

>> AutoStopped

Main Menu

Device Select

Use to selectRECOMM-485.

P0: SP600

>> AutoStopped

P5: RECOMM-485

>> AutoStopped

Main Menu

Parameters

Device: Port 0SP600RECOMM-485

Monitor Lang

Edit the RS485 DF1parameters using thesame techniques as fordrive parameters.

Use to highlightDevice Select icon

Figure 4.2 – RS485 DF1 Node Address Screen on an LCD OIM

Port 5 Device

RECOMM-485

Parameter #: 3DF1 Addr Cfg

10 <> 99

Default = 1

Page 25: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Configuring the RS485 DF1 Module 4-3

4.4 Setting the Data Rate

If the Data Rate switch on the module is set to “PGM,” the value of module parameter 5 (DF1 Rate Cfg) determines the RS485 DF1 data rate. Your application may require a different setting.

Step 1. Set the value of module parameter 5 (DF1 Rate Cfg) to the data rate at which your network is operating. Refer to figure 4.3.

Step 2. Reset the module. Refer to section 4.7.2, Resetting the Module.

4.5 Setting the Error-Checking Method

Two types of error-checking methods are used with the DF1 protocol: Cyclic Redundancy Check (CRC) and Block Check Character (BCC). (Refer to the Glossary for a description of each method.)

Step 1. Set the value of module parameter 24 (CRC/BCC) to the method used by the network as shown in figure 4.4.

Step 2. Reset the module. Refer to section 4.7.2, Resetting the Module.

Figure 4.3 – Data Rate Screen on an LCD OIM

Port 5 Device

RECOMM-485

Parameter #: 5DF1 Rate Cfg

39600 bps

Value Baud Rate0 1200 bps1 2400 bps2 4800 bps3 9600 bps (default)4 19.2 kbps5 38.4 kbps

Figure 4.4 – Error-Checking Method Screen on an LCD OIM

Port 5 Device

RECOMM-485

Parameter #: 24CRC/CBC

0BCC

Value Selection0 BCC (default)1 CRC

Page 26: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

4-4 RS485 DF1 Communications Module

4.6 Setting the I/O Configuration

The I/O configuration determines the type of data sent to the drive. This is a two-part process: enabling/disabling the data transmitted between the module and the drive, and identifying the data transmitted between the module and the master (i.e., scanner).

Step 1. Enable or disable the data transmitted between the module and the drive by setting the bits in module parameter 12 (DPI I/O Config).

A “1” enables the I/O. A “0” disables the I/O. Bit 0 is the right-most bit. In figure 4.5, it is highlighted and equals “1.”

Step 2. If Logic Command/Reference is enabled (default), configure the parameters in the drive to accept the Logic Command and Reference from the module. For example, set Speed Ref A Sel (SP600 drive parameter 90) to “Network” so that the drive uses the Reference from the module. Also, verify that SP600 drive parameter 89 (Logic Source Sel) is configured to receive the desired logic from the module.

Step 3. If you enabled one or more Datalinks (optional), configure parameters in the drive to determine the source and destination of data in the Datalink(s). Also, ensure that the RS485 DF1 module is the only module using the enabled Datalink(s).

Step 4. Reset the module. Refer to section 4.7.2, Resetting the Module.

The module is ready to receive I/O from the master (i.e., scanner). You must now configure the scanner to recognize and transmit I/O to the module.

Figure 4.5 – I/O Configuration Screen on an LCD OIM

Port 5 Device

RECOMM-485

Parameter #: 12DPI I/O Configx x x x x x x x x x x 0 0 0 0 1Cmd/Ref b00

Bit Description0 Logic Command/Reference (Default)1 Datalink A2 Datalink B3 Datalink C4 Datalink D

5 - 15 Not Used

Page 27: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Configuring the RS485 DF1 Module 4-5

4.7 Setting a Fault Action

By default, when communications are disrupted (for example, a cable is disconnected) or the scanner is idle, the drive responds by faulting if it is using I/O from the network.

You can configure a different response to communication disruptions using module parameter 10 (Comm Flt Action).

Set the value of module parameter 10 (Comm Flt Action) to the desired response as shown in table 4.2. See figure 4.6 for a sample LCD OIM Fault Action screen.

Changes to this parameter take effect immediately. A reset is not required.

!ATTENTION: Module parameter 10 (Comm Flt Action) lets you determine the action of the module and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set the parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a risk of injury or equipment damage.

Table 4.2 – Selections for Drive Response to Communication Fault

Value Action Description

0 Fault (default) The drive is faulted and stopped (Default).

1 Stop The drive is stopped, but not faulted.

2 Zero Data The drive is sent 0 for output data after a communications disruption. This does not command a stop.

3 Hold Last The drive continues in its present state.

4 Send Flt Cfg The drive is sent the data that you set in the fault configuration parameters 14 through 23 (Flt Cfg Logic through Flt Cfg D2 In).

Figure 4.6 – Fault Action Screen on an LCD OIM

Port 5 Device

RECOMM-485

Parameter #: 10Comm Flt Action

0Fault

Page 28: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

4-6 RS485 DF1 Communications Module

4.7.1 Setting the Fault Configuration Parameters

If you set module parameter 10 (Comm Flt Action) to “Send Flt Cfg,” the values in the parameters shown in table 4.3 are sent to the drive after a communications fault occurs. You must set these parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not required.

4.7.2 Resetting the Module

Changes to switch settings or some module parameters require that you reset the module before the new settings take effect. You can reset the module by cycling power to the drive or by using module parameter 9 (Reset Module).

Table 4.3 – Fault Configuration Parameters

Parameter Number Name Description

14 Flt Cfg Logic A 16-bit value sent to the drive for Logic Command.

15 Flt Cfg Ref A 32-bit value (0 to 4294967295) sent to the drive as a Reference or Datalink.

Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most significant word of the value must be set to zero (0) or a fault will occur.

16 - 23 Flt Cfg x1 In Flt Cfg x2 In

!ATTENTION: If the module is transmitting control I/O to the drive, the drive may fault when you reset the module. Determine how your drive will respond before resetting a connected module. Failure to observe this precaution could result in bodily injury or damage to equipment.

Page 29: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Configuring the RS485 DF1 Module 4-7

Set module parameter 9 (Reset Module) to “Reset Module.” See figure 4.7.

When you enter 1 (“Reset Module”) the module is immediately reset. When you enter 2 (“Set Defaults”) the module sets all module parameters to their factory-default settings. The module should be reset after performing a “Set Defaults.”

The value of this parameter is restored to 0 (“Ready”) after the module is reset.

Figure 4.7 – Reset Screen on an LCD OIM

Port 5 Device

RECOMM-485

Parameter #: 9Reset Module

1Reset Module

Value Description0 Ready (default)1 Reset Module2 Set Defaults

Page 30: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

4-8 RS485 DF1 Communications Module

4.8 Viewing the Module Configuration

The parameters in table 4.4 provide information about how the module is configured. You can view these parameters at any time.

Table 4.4 – Module Configuration Status Parameters

No. Name Description01 DPI Port The port to which the module is connected. This will usually be

port 5.02 DPI Data Rate The data rate used by the drive. This data rate is set in the

drive and the module detects it.04 DF1 Addr Actual The node address actually used by the module. This will be

one of the following values:

• The address set by the Node Address switches on the module.

• The value of module parameter 3 (DF1 Addr Cfg) if the switches have been disabled.

06 DF1 Rate Actual The DF1 data rate actually used by the module. This will be one of the following values:

• The data rate set by the Data Rate switch on the module.• The value of module parameter 5 (DF1 Rate Cfg) if the

switches have been disabled.07 Ref/Fdbk Size The size of the Reference/Feedback (16 bits or 32 bits). It is

set in the drive and the module automatically uses the correct size.

08 Datalink Size The size of the Datalinks (16 bits or 32 bits). It is set in the drive and the module automatically uses the correct size.

11 Active Cfg The source from which the module address and data rate are taken. This will either be switches on the module or parameters in EEPROM. It is determined by the switch settings on the module.

13 DPI I/O Active The I/O used by the module. The value of this parameter will be equal to the value of module parameter 12 (DPI I/O Config) unless the parameter was changed and the module was not reset.

Bit Definitions0 = Cmd/Ref1 = Datalink A2 = Datalink B3 = Datalink C4 = Datalink D5 = Not Used6 = Not Used7 = Not Used

25 CRC/BCC Act The actual error-checking method selected.26 Dup Msg Detect Determines if the module ignores messages with duplicate

TNS IDs. Normally set to Enable (default). Set to Disable if using a ProSoft 3150-DFM module or any device that does not increment the TNS ID.

BitDefault 10000x xx

0123457 6

Page 31: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Using VS Utilities on the RS485 Network 5-1

CHAPTER 5Using VS Utilities

on the RS485 Network

Chapter 5 provides instructions for configuring VS Utilities (version 1.01 or higher) to access SP600 drives on the RS485 network. Figure 5.1 shows a typical RS485 DF1 network.

To connect to the network using VS Utilities:

Step 1. Select Explore > Connect > Network as shown in figure 5.2.

Figure 5.1 – Typical RS485 DF1 Network

Figure 5.2 – Connecting to the Network

RECOMM-232Serial ConverterModule

SP600 DrivesPC RunningVS Utilities

VS Utilities

Page 32: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

5-2 RS485 DF1 Communications Module

Step 2. Select Single to connect to a single node on the network. Select Multiple to connect to multiple nodes and enter the node range (figure 5.3).

“Offline” or “Online” text will be displayed next to the number to show if the particular node is present on the network. In this example, two nodes with DF1 addresses of 1 and 2 will be accessed.

Step 3. Click Connect.

VS Utilities will perform a search within the range of the selected nodes and list them as shown in figure 5.4.

Figure 5.3 – Node Selection Screen: Multiple Nodes Selected

Figure 5.4 – Results of Search of Selected Nodes

VS Utilities

Page 33: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Using VS Utilities on the RS485 Network 5-3

Step 4. Click on each node to have VS Utilities perform a device read as shown in figure 5.5. A “+” will appear to the left of the node upon completion.

Step 5. Click on the “+” for each node to expand the information as shown in figure 5.6.

Figure 5.5 – Result of Device Read Performed by VS Utilities

Figure 5.6 – Expanding Each Node

VS Utilities

Node 1: - SP600 Node 2: - SP600

Node 2: - SP600

Node 1: - SP600 0 - SP600 240V 4.2A

1 - LCD OIM 2 - RECOMM-232 RS232 DF1 5 - RECOMM-485 RS485 DF1

0 - SP600 240V 4.2A 1 - LCD OIM 5 - RECOMM-485 RS485 DF1

VS Utilities

Node 2: - SP600

Page 34: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

5-4 RS485 DF1 Communications Module

Step 6. Click on the desired item to access its parameters as shown in figure 5.7.

Figure 5.7 – Accessing the Parameters in the Selected Device

Node 1: - SP600 0 - SP600 240V 4.2A

1 - LCD OIM 2 - RECOMM-232 RS232 DF1 5 - RECOMM-485 RS485 DF1

Node 2: - SP600 0 - SP600 240V 4.2A 1 - LCD OIM 5 - RECOMM-485 RS485 DF1

VS Utilities

Page 35: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Troubleshooting the Module and Network 6-1

CHAPTER 6Troubleshooting theModule and Network

Chapter 6 contains information for troubleshooting the RS485 DF1 module and the network.

6.1 Understanding the Status Indicators

The module has four status indicators. They can be viewed on the module or through the drive cover. (See figure 6.1.)

➀➁➂

➀➁➂➃

NumberStatus

Indicator Description Refer to...

➀ DRIVE DPI Connection Status Section 6.1.1

➁ MS Module Status Section 6.1.2

➂ NET A DF1 Status Section 6.1.3

➃ NET B DF1 Traffic Section 6.1.4

Figure 6.1 – Status Indicators (Location on Drive May Vary)

Page 36: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

6-2 RS485 DF1 Communications Module

6.1.1 DRIVE Status Indicator

Table 6.1 – DRIVE Status Indicator: State Definitions

Status Cause Corrective Action

Off The module is not powered or is not connected properly to the drive.

• Securely connect the module to the drive using the Internal Interface cable.

• Apply power to the drive.

Flashing Red

The module is not receiving a ping message from the drive.

• Verify that cables are securely connected.

• Cycle power to the drive.

Solid Red

The drive has refused an I/O connection from the module.

Another DPI peripheral is using the same DPI port as the module.

Important: Cycle power to the product after making any of the following corrections:

• Verify that all DPI cables are securely connected and not damaged. Replace cables if necessary.

• Verify that the DPI Host supports Datalinks.

• Configure the module to use a Datalink that is not already being used by another peripheral.

Orange The module is connected to a product that does not support Reliance Electric DPI communications.

• Connect the module to a product that supports Reliance Electric DPI communications (for example, SP600 drives).

Flashing Green

The module is establishing an I/O connection to the drive or module parameter 12 (DPI I/O Config) is configured for all I/O disabled.

• Verify the settings in module parameter 12 (DPI I/O Config).

• Normal behavior if no DPII/O is enabled. No action is required.

Solid Green

The module is properly connected and is communicating with the drive.

• No action is required.

Page 37: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Troubleshooting the Module and Network 6-3

6.1.2 MS Status Indicator

Table 6.2 – MS Status Indicator: State Definitions

Status Cause Corrective Action

Off The module is not powered.

• Securely connect the module to the SP600 drive using the Internal Interface cable.

• Apply power to the drive.

Flashing Red

The module has failed the firmware test.

• Clear faults in the module.

• Cycle power to the drive.

• If cycling power does not correct the problem, the parameter settings may have been corrupted. Reset defaults and reconfigure the module.

• If resetting defaults does not correct the problem, flash the module with the latest firmware release.

Solid Red

The module has failed the hardware test.

• Cycle power to the drive.

• Replace the module.

Flashing Green

The module is operational but is not transferring I/O data.

• Place the scanner in RUN mode.

• Program the controller to recognize and transmit I/O to the module.

• Configure the module for the program in the controller.

• Normal behavior if no DPI I/O is enabled.

Solid Green

The module is operational and transferring I/O data.

• No action required.

Page 38: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

6-4 RS485 DF1 Communications Module

6.1.3 NET A Status Indicator

Table 6.3 – NET A Status Indicator: State Definitions

Status Cause Corrective Actions

Off The module is not powered or the module is not properly connected to the network.

• Securely connect the module to the drive using the Internal Interface cable.

• Correctly connect the RS485 cable to the DF1 plug.

• Apply power to the drive.

Flashing Green

The module is properly connected, but it is not communicating with any devices on the network.

• Place the controller in RUN, or apply power to the peer device that will send I/O.

• Program a controller or peer device to recognize and transmit I/O to the module.

• Configure the module for the program in the controller or the I/O from the peer source.

Solid Green

The module is properly connected and communicating on the network.

• No action required.

Flashing Red

A network connection has timed out.

• Place the scanner in RUN, or apply power to the peer device that will send I/O.

• Check the amount of traffic on the network.

Page 39: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Troubleshooting the Module and Network 6-5

6.1.4 NET B Status Indicator

6.2 Module Diagnostic Items

Table 6.5 lists diagnostic items that can be accessed using VS Utilities software or the LCD OIM.

Table 6.4 – NET B Status Indicator: State Definitions

Status Cause Corrective Actions

Off The module is not receiving data over the network.

• Place the controller in RUN, or apply power to the peer device that will send I/O.

• Program a controller peer device to recognize and transmit I/O to the module.

• Configure the module for the program in the controller or the I/O from the peer device.

Flashing Green

The module is receiving data over the network.

• No action required.

Table 6.5 – Module Diagnostic Items

No. Event Description

1 Common Logic Cmd

The current value of the Common Logic Command being transmitted to the host by this peripheral.

2 Prod Logic Cmd The current value of the Product Specific Logic Command being transmitted to the host by this peripheral.

3 Reference The current value of the Product Specific Reference being transmitted to the host by the peripheral.

4 Common Logic Sts The current value of the Common Logic Status being received from the host by this peripheral.

5 Product Logic Status

The current value of the Product Specific Status being received from the host by this peripheral.

6 Feedback The current value of the Product Specific Feedback being received from the host by this peripheral.

Page 40: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

6-6 RS485 DF1 Communications Module

7891011121314

Datalink A1 InDatalink A2 InDatalink B1 InDatalink B2 InDatalink C1 InDatalink C2 InDatalink D1 InDatalink D2 In

The current value of the specified Datalink In being transmitted to the host by the module. If the module has not enabled the Datalink, the value is 0.

1516171819202122

Datalink A1 OutDatalink A2 OutDatalink B1 OutDatalink B2 OutDatalink C1 OutDatalink C2 OutDatalink D1 OutDatalink D2 Out

The current value of the specified Datalink Out being received from the host by the module.

23 Field Flash Cnt The current value of the Field Flash Counter (that is, the number of times this device has been flash updated).

24 DPI Rx Errors The current value of the DPI CAN Receive Error Counter register.

25 DPI Tx Errors The current value of the DPI CAN Transmit Error Counter register.

26 Clear DF1 Counts Ready = No action.Enable = Clears all DF1 counter parameters.

27 DF1 Packets Sent The number of DF1 packets sent by the peripheral.

28 DF1 Packets Rcvd The number of DF1 packets received by the peripheral.

29 Undelivered Msgs Reports the number of DF1 packets that were sent by the peripheral, but not acknowledged.

30 ENQs Received Reports the number of ENQ requests received by the peripheral.

31 NAK Bak Packet The number of responses received (BCC or CRC calculated by peripheral did not match that in the packet).

32 NAK No Memory The number of requests received by the peripheral that could not processed due to insufficient memory available to buffer the incoming packet.

33 Duplicate Msgs The number of duplicate messages received by the peripheral. A duplicate message is detected when the SRC, TNS, and CMD files of two consecutive messages are identical.

Table 6.5 – Module Diagnostic Items (Continued)

No. Event Description

Page 41: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Troubleshooting the Module and Network 6-7

6.3 Viewing and Clearing Events

The module maintains an event queue that reports the history of its actions. You can view the event queue using an LCD OIM orVS Utilities software.

To View and Clear Events Using an LCD OIM

Use the procedure shown in figure 6.2 to access the event queue using the LCD OIM. Note that you must have the RECOMM-485 module as the selected device to access the event queue.

34 PCCC I/O Timeout The I/O communication timeout value (secs) before the action selected in module parameter 10 (Comm Flt Action) is taken.

35 Data Rate SW The value of the Data Rate switch on the module.

36 Node Address SW The value of the Node Address switch on the module.

Table 6.5 – Module Diagnostic Items (Continued)

No. Event Description

Figure 6.2 – Viewing and Clearing Events Using an LCD OIM

Diagnostics:

Device VersionOIM Version

View Event Queue

P0: RECOMM-485

Stopped Auto

Main Menu

Diagnostics

EvtQ# : E#xxxxxOnline @ 500kbps

1

Clrqu

Highlight Diagnostics icon

Highlight itemMonitor Lang

>>

Press F2 key toclear event queue

Page 42: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

6-8 RS485 DF1 Communications Module

Events

Many events in the event queue occur under normal operation. If you encounter unexpected communications problems, the events may help you or Reliance Electric personnel troubleshoot the problem. Table 6.6 lists events that may appear in the event queue.

Table 6.6 – Event Codes and Descriptions

Code Event Description

1 No Event Empty event queue entry.

2 DPI Bus Off Flt A bus-off condition was detected on DPI. This event may be caused by loose or broken cables or by noise.

3 Ping Time Flt A ping message was not received on DPI within the specified time.

4 Port ID Flt The module is not connected to a correct port on a DPI product.

5 Port Change Flt The DPI port changed.

6 Host Sent Reset The DPI product issued this because it was reset.

7 EEPROM Sum Flt The EEPROM in the module is corrupt.

8 Online @ 125 kbps The module and DPI product are communicating at 125 kbps.

9 Online @ 500 kbps The module and DPI product are communicating at 500 kbps.

10 Bad Host Flt The module was connected to an incompatible product.

11 Dup. Port Flt Another peripheral with the same port number is already in use.

12 Type 0 Login The module has logged in for type 0 control.

13 Type 0 Time Flt The module has not received a type 0 status message within the specified time.

14 DL Login The module has logged into a Datalink.

15 DL Reject Flt The host rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral.

16 DL Time Flt The module has not received a Datalink message within the specified time.

17 Control Disabled The module has sent a “Soft Control Disable” command to the DPI product.

18 Control Enabled The module has sent a “Soft Control Enable” command to the DPI product.

19 PCCC IO Time Flt The module has not received a PCCC control message within the specified timeout interval.

Page 43: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Troubleshooting the Module and Network 6-9

20 Normal Startup The module successfully started up.

21 Message Timeout A Client-Server message sent by the peripheral was not completed.

22 DPI Fault Msg The DPI host has faulted.

23 DPI Fault Clear The DPI host transitioned from a faulted to a non-faulted state.

24 Flt Cfg Error At least one of the Fault Configuration parameters contains a value greater than 65535 and the DPI product expects a 16-bit value.

25 DF1 NAK NAK received.

26 Manual Reset The module was reset by the user.

27 Language CRC Bad The language text memory segment is corrupt.

Table 6.6 – Event Codes and Descriptions (Continued)

Code Event Description

Page 44: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

6-10 RS485 DF1 Communications Module

Page 45: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Technical Specifications A-1

APPENDIX A Technical

Specifications

Communications

Electrical

Mechanical

Environmental

NetworkProtocolData Rates

DF11200, 2400, 4800, 9600, 19.2 K, 38.4 K, PGM

If the Data Rate switch is set to “PGM,” the module will use the setting of module parameter 5 (DF1 Rate Cfg) for the data rate.

Drive Protocol Data Rates

DPI125 K or 500 K

Consumption Drive 150 mA at 5 VDC supplied through the drive

DimensionsHeightLengthWidth

16 mm (0.625 in)86 mm (3.34 in)81 mm (3.16 in)

Weight 60 g (2 oz)

TemperatureOperatingStorage

-10 to +50° C (14 to 149° F)-40 to +85° C (-40 to 185° F)

Relative Humidity 5 to 95% non-condensing

Atmosphere Important: The module must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapor, or dust. If the module is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.

Page 46: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

A-2 RS485 DF1 Communications Module

Regulatory ComplianceUL 508C and CUL

CE EN61800-3

Page 47: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

RS485 DF1 Module Parameters B-1

APPENDIX BRS485 DF1 Module

Parameters

The following information is provided for each module parameter along with its description:

About Parameter Numbers

The parameters in the RS485 DF1 module are numbered sequentially. However, depending on the configuration tool used, they may have different numbers.

Parameter Number: Unique number assigned to each parameter.

Parameter Name: Unique name assigned to each parameter.

Range: Predefined parameter limits or selections.

Default: Factory default setting.

Type: Read Only or Read/Write.

Reset Required: Module must be reset before parameter value is recognized.

Configuration Tool Numbering Schemes

• VS Utilities

• OIM

The module parameters begin with parameter 1. For example, parameter 01 (DPI Port) is parameter 1 as indicated by the manual.

Page 48: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

B-2 RS485 DF1 Communications Module

Displays the port to which the module is connected. This will usually be port 5.

Displays the data rate used by the drive. This rate is set in the drive and the module detects it.

Sets the node address if the Data Rate Switch on the module is set to “PGM” (Program).

Displays the DF1 node address actually used by the module.

1 DPI PortRange: 0 to 7

Default: 5

Type: Read Only

Reset Required: N/A

2 DPI Data RateRange: 0 = 125 Kbps

1 = 500 Kbps

Default: 0 = 125 Kbps

Type: Read Only

Reset Required: N/A

3 DF1 Addr CfgRange: 0 to 254

Default: 1

Type: Read/Write

Reset Required: Yes

4 DF1 Addr ActualRange: 0 to 254

Default: 1

Type: Read Only

Reset Required: N/A

Page 49: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

RS485 DF1 Module Parameters B-3

Sets the DF1 data rate if the Data Rate switch on the module is set to “PGM” (Program).

Displays the DF1 data rate actually used by the module.

Displays the size of the Reference/Feedback. The drive determines the size of the Reference/Feedback.

Displays the size of each Datalink word. The drive determines the size of Datalinks.

5 DF1 Rate CfgRange: 0 = 1200 bps

1 = 2400 bps2 = 4800 bps3 = 9600 bps4 = 19.2 kbps5 = 38.4 kbps

Default: 3 = 9600 bps

Type: Read/Write

Reset Required: Yes

6 DF1 Rate ActualRange: 0 = 1200 bps

1 = 2400 bps2 = 4800 bps3 = 9600 bps4 = 19.2 kbps5 = 38.4 kbps

Default: 3 = 9600 bps

Type: Read Only

Reset Required: Yes

7 Ref/Fdbk SizeRange: 0 = 16-bit

1 = 32-bit

Default: 0 = 16-bit

Type: Read Only

Reset Required: N/A

8 Datalink SizeRange: 0 = 16-bit

1 = 32-bit

Default: 0 = 16-bit

Type: Read Only

Reset Required: N/A

Page 50: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

B-4 RS485 DF1 Communications Module

This parameter is a command. It resets the module if set to “Reset Module.” It restores the module to factory default settings if set to “Set Defaults.” No action is taken if set to “Ready.” The parameter resets to “0 = Ready” after the command is performed.

Sets the action that the module takes when the module detects that RS485 DF1 communications have been disrupted. This setting is effective only if I/O that controls the drive is transmitted though the module.

9 Reset ModuleRange: 0 = Ready (No action)

1 = Reset Module2 = Set Defaults (Restores module to factory-default

settings)

Default: 0 = Ready

Type: Read/Write

Reset Required: No

!ATTENTION: If the module is transmitting I/O that controls the drive, the drive may fault when you reset the module. Determine how your drive will respond before resetting a connected module. Failure to observe this precaution could result in bodily injury or damage to equipment.

10 Comm Flt ActionRange: 0 = Fault

1 = Stop2 = Zero Data3 = Hold Last4 = Send Flt Cfg

Default: 0 = Fault

Type: Read/Write

Reset Required: No

!ATTENTION: Comm Flt Action (module parameter 10) lets you determine the action of the module and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Take precautions to ensure that the setting of this parameter does not create a hazard of injury or equipment damage. Failure to observe this precaution could result in bodily injury or damage to equipment.

Page 51: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

RS485 DF1 Module Parameters B-5

Displays the source from which the module node address and data rate are taken. This will either be switches on the module or parameters in EEPROM. The source is determined by the settings of the switches on the module. See chapter 3, Installing the RS485 DF1 Module, for more information about the switches.

Configures the I/O that is transferred through the module. See figure B.1

11 Active CfgRange: 0 = Switches

1 = EEPROM

Default: 0 = Switches

Type: Read Only

Reset Required: N/A

12 DPI I/O CfgRange: See figure B.1.

Default: xxx0 0001

Type: Read/Write

Reset Required: Yes

Figure B.1 – DPI I/O Config (Parameter 12)

000 10xxx01234567

1= I/O Enabled0= I/O Disabledx =Not Used

Cmd/R

ef

Datal

ink A

Datal

ink B

Datal

ink C

Datal

ink D

Not U

sed

Not U

sed

Not U

sed

Page 52: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

B-6 RS485 DF1 Communications Module

Displays the I/O that the module is actively transmitting. The value of this parameter will usually be equal to the value of module parameter 12 (DPI I/O Cfg). See figure B.2.

Sets the Logic Command data that is sent to the drive if module parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and communications are disrupted.

The bit definitions will depend on the product to which the module is connected.

Sets the Reference data that is sent to the drive if module parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and communications are disrupted.

Important: If the drive uses a 16-bit Reference, the most significant word of this value must be set to zero (0) or a fault will occur.

13 DPI I/O ActiveRange: See figure B.2.

Default: xxx0 0001

Type: Read Only

Reset Required: N/A

Figure B.2 – DPI I/O Active (Parameter 13)

000 10xxx01234567

1= I/O Enabled0= I/O Disabledx =Not Used

Cmd/R

ef

Datal

ink A

Datal

ink B

Datal

ink C

Datal

ink D

Not U

sed

Not U

sed

Not U

sed

14 Flt Cfg LogicRange: 0000 0000 0000 0000 to 1111 1111 1111 1111

Default: 0000 0000 0000 0000

Type: Read/Write

Reset Required: No

15 Flt Cfg RefRange: 0 to 4294967295

Default: 0

Type: Read/Write

Reset Required: No

Page 53: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

RS485 DF1 Module Parameters B-7

Sets the data that is sent to the Datalink in the drive if module parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and communications are disrupted.

Important: If the drive uses a 16-bit Reference, the most significant word of this value must be set to zero (0) or a fault will occur.

Selects the method of error detection for data communications. This setting must match the method used by the software or controller communicating with the module.

Displays the actual method of error detection used.

1617181920212223

Flt Cfg A1Flt Cfg A2Flt Cfg B1Flt Cfg B2Flt Cfg C1Flt Cfg C2Flt Cfg D1Flt Cfg D2Range: 0 to 4294967295

Default: 0

Type: Read/Write

Reset Required: No

24 CRC/BCC CfgRange: 0 = BCC (Block Check Character)

1 = CRC (Cyclic Redundancy Check)

Default: 0 = BCC

Type: Read/Write

Reset Required: Yes

25 CRC/BCC ActRange: 0 = BCC (Block Check Character)

1 = CRC (Cyclic Redundancy Check)

Default: 0 = BCC

Type: Read Only

Reset Required: N/A

Page 54: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

B-8 RS485 DF1 Communications Module

Enables/disables duplicate message detection by the module. Normally, this is set to “Enable” (default). Set to “Disable” if using a ProSoft 3150-DFM module or any device that does not increment the TNS (transaction number) ID.

26 Dup Msg DetectRange: 0 = Disable

1 = Enable

Default: 1 = Enable

Type: Read/Write

Reset Required: No

Page 55: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Logic Command/Status Words C-1

APPENDIX CLogic Command/

Status Words

Appendix C provides the definitions of the Logic Command/Logic Status words that are used for some products that can be connected to the RS485 DF1 module. If you do not see the Logic Command/Logic Status for the product that you are using, refer to your product’s documentation.

C.1 SP600 Drives

Logic Command Word

Logic Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description

x Stop 0 = Not Stop1 = Stop

x Start1 0 = Not Start1 = Start

x Jog 0 = Not Jog1 = Jog

x Clear Faults 0 = Not Clear Faults1 = Clear Faults

x x Direction 00 = No Command01 = Forward Command10 = Reverse Command11 = Hold Direction Control

x Local Control 0 = No Local Control1 = Local Control

x MOP Increment

0 = Not Increment1 = Increment

x x Accel Rate 00 = No Command01 = Accel Rate 1 Command10 = Accel Rate 2 Command11 = Hold Accel Rate

x x Decel Rate 00 = No Command01 = Decel Rate 1 Command10 = Decel Rate 2 Command11 = Hold Decel Rate

Page 56: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

C-2 RS485 DF1 Communications Module

Logic Status Word

x x x Reference Select

000 = No Command001 = Ref. 1 (Ref A Select)010 = Reserved011 = Ref. 3 (Preset 3)100 = Ref. 4 (Preset 4)101 = Ref. 5 (Preset 5)110 = Ref. 6 (Preset 6)111 = Ref. 7 (Preset 7)

x MOP Decrement

0 = Not Decrement1 = Decrement

1 A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.

Logic Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description

Logic Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status Description

x Ready 0 = Not Ready1 = Ready

x Active 0 = Not Active1 = Active

x Command Direction

0 = Reverse1 = Forward

x Actual Direction

0 = Reverse1 = Forward

x Accel 0 = Not Accelerating1 = Accelerating

x Decel 0 = Not Decelerating1 = Decelerating

x Alarm 0 = No Alarm1 = Alarm

x Fault 0 = No Fault1 = Fault

x At Speed 0 = Not At Reference1 = At Reference

x x x Local Control

000 = Port 0 (TB)001 = Port 1010 = Port 2011 = Port 3100 = Port 4101 = Port 5110 = Port 6111 = No Local

Page 57: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Logic Command/Status Words C-3

x x x x Reference 0000 = Ref A Auto0001 = Reserved0010 = Preset 2 Auto0011 = Preset 3 Auto0100 = Preset 4 Auto0101 = Preset 5 Auto0110 = Preset 6 Auto0111 = Preset 7 Auto1000 = Term Blk Manual1001 = DPI 1 Manual1010 = DPI 2 Manual1011 = DPI 3 Manual1100 = DPI 4 Manual1101 = DPI 5 Manual1110 = DPI 6 Manual1111 = Jog Ref

Logic Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status Description

Page 58: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

C-4 RS485 DF1 Communications Module

Page 59: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Glossary Glossary-1

GLOSSARY

BCC (Block Check Character) - A technique for error detection in data communications. A character is added to a transmission block, which is compared with a second BCC computer by the receiver to determine if the transmission is error free.

controller - Also called programmable logic controller. A solid-state control system that has a user-programmable memory for storage of instructions to implement specific functions such as I/O control, logic, timing, counting, report generation, communication, arithmetic, and data file manipulation. A controller consists of a central processor, input/output interface, and memory. See also scanner.

CRC (Cyclic Redundancy Check) - A commonly used technique for error detection in data communications. A polynomial algorithm is performed on the data, and the resultant checksum is appended at the end of the frame. The receiving device performs a similar algorithm.

data rate - The speed at which data is transferred on the RS485 DF1 network. Each device on an RS485 DF1 network must be set for the same data rate. You can set the RS485 DF1 module to 1200, 2400, 4800, 9600, 19.2 K or 38.4 kbps.

Datalink - A type of pointer used by some SP600 drives to transfer data to and from the controller. Datalinks allow specified parameter value(s) to be accessed or changed without using explicit messages. When enabled, each Datalink consumes either four bytes or eight bytes in both the input and output image table of the controller. The drive determines the size of Datalinks.

DF1 - A Rockwell Automation Datalink layer protocol that combines features of subcategories D1 (data transparency) and F1 (two-way simultaneous transmission with embedded responses) of ANSI x3.28 specification.

DPI (Drive Peripheral Interface) - A peripheral communication interface used by various Reliance Electric drives and power products.

DPI peripheral - A device that provides an interface between DPI and a network or user. Peripheral devices are also referred to as “modules” and “adapters.” The RS485 DF1 module and SP600 OIM are examples of DPI peripherals.

Page 60: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Glossary-2 RS485 DF1 Communications Module

DPI product - A device that uses the DPI communications interface to communicate with one or more peripheral devices. For example, a motor drive such as a SP600 drive is a DPI product. In this manual, a DPI product is also referred to as “product” or “host.”

fault action - Determines how the module and connected product act when a communications fault (for example, a cable is disconnected) occurs or when the scanner is switched out of run mode. The former uses a communications fault action, and the latter uses an idle fault action.

fault configuration - When communications are disrupted (for example, a cable is disconnected), the module and SP600 drive can respond with a user-defined fault configuration. The user sets the data that is sent to the drive in the fault configuration parameters (parameters 15 (Flt Cfg Logic) through 24 (Flt Cfg D2 In)). When a fault action parameter is set to use the fault configuration and a fault occurs, the data from these parameters is sent as the Command Logic, Reference, and/or Datalink(s).

flash update - The process of updating firmware in the module. The module can be flash updated using the X-Modem protocol and a RECOMM-232 serial converter.

hold last - When communications are disrupted (for example, a cable is disconnected), the module and SP600 drive can respond by holding last. Hold last results in the drive receiving the last data received via the RS485 DF1 connection before the disruption. If the drive was running and using the reference from the module, it will continue to run at the same reference.

II/O data - I/O data, sometimes called “implicit messages” or “input/output,” transmit time-critical data such as a Logic Command and Reference. The terms “input” and “output” are defined from the scanner’s point of view. Output is transmitted by the scanner and consumed by the module. Input is transmitted by the module and consumed by the scanner.

Logic Command/Logic Status - The Logic Command is used to control the SP600 drive (for example, start, stop, direction). It consists of one 16-bit word of input to the module from the network. The definitions of the bits in this word depend on the drive.

The Logic Status is used to monitor the SP600 drive (for example, operating state, motor direction). It consists of one 16-bit word of output from the module to the network. The definitions of the bits in this word depend on the drive.

Page 61: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Glossary Glossary-3

module - Devices such as drives, controllers, and computers usually require a module to provide a communication interface between them and a network such as RS485 DF1. An module reads data on the network and transmits it to the connected device. It also reads data in the device and transmits it to the network.

The RS485 DF1 module connects SP600 drives to an RS485 DF1 network. Modules are sometimes also called “adapters,” “cards,” “embedded communication options,” “gateways,” and “peripherals.”

node address - An RS485 DF1 network can have as many as 255 devices connected to it. Each device on the network must have a unique node address from 0 to 254.

non-volatile storage (NVS) - NVS is the permanent memory of a device. Devices such as the module and drive store parameters and other information in NVS so that they are not lost when the device loses power. NVS is sometimes called “EEPROM.”

operator interface module (OIM) - A device that can be used to configure and control a SP600 drive.

PCCC (Programmable Controller Communications Command) - The protocol used by some controllers to communicate with devices on a network. Some software products (for example, VS Utilities) also use PCCC to communicate.

ping - A message that is sent by a DPI product to its peripheral devices. They use the ping to gather data about the product, including whether it can receive messages and whether they can log in for control.

Reference/Feedback - Reference is used to send a reference (for example, speed, frequency, torque) to the product. It consists of one word of input to the module from the network. The size of the word (either a 16-bit word or 32-bit word) is determined by the drive.

Feedback is used to monitor the speed of a product. It consists of one word of output from the module to the network. The size of the word (either a 16-bit word or 32-bit word) is determined by the drive.

scanner - A separate module (of a multi-module controller) or a built-in component (of a single-module controller) that provides communication with modules connected to a network. See also controller.

status indicators - LEDs that are used to report the status of the module, network, and drive. They are on the module and can be viewed on the front cover of the drive when the drive is powered.

Page 62: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Glossary-4 RS485 DF1 Communications Module

Type 0/Type 1/Type 2 Control - When transmitting I/O, the module can use different types of messages for control. The Type 0, Type 1, Type 2 control events help Reliance Electric personnel identify the type of message that a module is using.

transaction number (TNS) - A two-byte field in a DF1 message packet that is used in combination with the SRC (source node of the message) and CMD (command code) bytes to uniquely identify every message packet. The TNS typically increments each time a new DF1 message is sent. The reply message will contain the same TNS value.

VS Utilities software - A Windows-based software tool for monitoring and configuring Reliance Electric products and modules. VS Utilities can be used to configure the RS485 DF1 module and SP600 drives.

zero data - When communications are disrupted (for example, a cable is disconnected), the module and drive can respond with zero data. Zero data results in the drive receiving zero as values for command data. If the drive was running and using the reference from the module, it will stay running but at zero reference.

Page 63: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Index Index-1

INDEX

AActive Cfg (11), B-5assistance, technical, 1-2

BBCC (Block Check Character), 4-3

Cchecklist, installation, 2-3Comm Flt Action (10), B-4communications specifications, A-1configuration tools, 4-1configuring the module, 4-1 to 4-8connecting the module to the drive, 3-3connecting the module to the

network, 3-6CRC (Cyclic Redundancy Check, 4-3CRC/BCC Act (25), B-7CRC/BCC Cfg (24), B-7Cyclic Redundancy Check (CRC), 4-3

DData Rate switch, location of, 2-1Datalink Size (8), B-3DF1 Addr Actual (4), B-2DF1 Addr Dfg (3), B-2DF1 Rate Act (6), B-3DF1 Rate Actual (6), B-3DF1 Rate Cfg (5), B-3dimensions, module, A-1DPI connector, 2-1DPI Data Rate (2), B-2DPI I/O Active (12), B-6DPI I/O Config (12), B-5DPI Port (1), B-2DPI ports, 3-4DRIVE status indicator, 6-2Dup Msg Detect (26), B-8

Eerror-checking method, setting, 4-3events

codes and descriptions, 6-8viewing and clearing, 6-7

Ffault action, setting, 4-5fault configuration parameters,

setting, 4-6Flt Cfg A1 (16), B-7Flt Cfg A2 (17), B-7Flt Cfg B1 (18), B-7Flt Cfg B2 (19), B-7Flt Cfg C1 (20), B-7Flt Cfg C2 (21), B-7Flt Cfg D1 (22), B-7Flt Cfg D2 (23), B-7Flt Cfg Logic (14), B-6Flt Cfg Ref (15), B-6

II/O configuration, 4-4installation

checklist, 2-3required equipment, 2-2

installing the module, 3-1 to 3-7Internal Interface cables, 2-2, 3-4

LLCD OIM see OIMLEDs, see status indicatorsLogic Command/Status words, C-1 to

C-3

Mmanuals, related, 1-2mechanical specifications, A-1

Page 64: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

Index-2 RS485 DF1 Communications Module

moduleapplying power to, 3-7components, 2-1configuration, viewing, 4-8configuring, 4-1 to 4-8connecting to drive, 3-3connecting to network, 3-6diagnostic items, 6-5dimensions, A-1features, 1-1installing, 3-1 to 3-7parameters, B-1 to B-8resetting, 4-6specifications, A-1troubleshooting, 6-1 to 6-9

MS status indicator, 6-3

NNET A status indicator, 6-4NET B status indicator, 6-5network connections, 3-6network example, 5-1network, troubleshooting, 6-1 to 6-9node address

setting with parameter, 4-2setting with switches, 3-1

Node Address switches, location of, 2-1

OOIM (Operator Interface Module)

configuring the module with, 4-2

Pparameter descriptions, B-1 to B-8power consumption, A-1power, applying to module, 3-7protocol, A-1publications, related, 1-2

RRef/Fdbk Size (7), B-3regulatory compliance, A-2Reliance Electric, getting assistance

from, 1-2Reset Module (9), B-4resetting the module, 4-6RS485 DF1 connector, 2-1

Sspecifications, module, A-1status indicators, 2-1, 6-1

Ttechnical assistance, 1-2troubleshooting, 6-1 to 6-9

VVS Utilities, using on RS485

network, 5-1 to 5-4

Page 65: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar
Page 66: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar
Page 67: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar
Page 68: Instruction Manual D2-3514 - …...Communications module (RECOMM-485) and using it with DPI AC drives, such as SP600 drives. It is intended for qualified electrical personnel familiar

U.S. Drives Technical Support Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives

Publication D2-3514 – August 2002 Copyright © 2002 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.