instruction manual for hcd450vdsrc - hytronik · hcd450vdsrc-20170109-a1 wire out infrared remote...

2
1. Technical Specifications Product type Independent DALI sensor (Daylight harvest) Operating voltage 120~277VAC 50/60Hz Switched power 2 x 2000W (resistive) 2 x 800W (capacitive) Power consumption < 1W Detection angle 360 o Detection range 10% / 50% / 100% Hold time 2s / 30s / 1min / 5min / 10min / 30min Stand-by time 0s / 10s / 1min / 10min / 30min / + Stand-by dimming level 10% / 20% / 30% Daylight threshold 2 ~ 50Lux , Disable Warmming-up time 20s Operating temperature -20 o C ~ +50 o C IP rating IP65 8 3. Functions Daylight sensor measures the available surrounding natural light, calculates how much electrical light is needed to reach the total lux expected. The demand is given to the LED driver by DALI signal, so as to deliver the needed amount of electric light. 3.1 Daylight Harvest (Daylight Regulating) Sometimes also know as “Potential-Free” or “Volt-Free” sensor, the dry contact sensors from Hytronik are designed to operate with external monitoring systems. They operate as conventional occupancy sensors, with the output available as shown in the table below: 3.2 Dry Contact Control Double “L” “N” terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block and assembly time. 3.3 Loop-in and loop-out HF Aisle Sensor with DALI Control HCD450VDSRC Installation and Instruction Manual 2. Instruction and Dimension Warnings: 1. Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations. 2. Disconnect supply before installing. 4. Wiring Diagram 5. Detection Pattern 0 24 Light level Time (hrs) Normal Electric Light Daylight controlled light Energy Saving Zone Natural light Hold time Stand-by time HCD450VDSRC-20170109-A1 Wire out Infrared remote receiver Daylight sensor Installation rack Sensor Antenna LED indication 125.5 135 115.4 95 L L L N N N N N 1 2 C O COM + 1-10V+ DALI - DALI 1-10V- 25 46 65 112.9 50.6 82.3 114 56 Detection State Contacts Made Presence Absence Nc - Com No - Com LED Driver LED Driver HCD450VDSRC Power N N N N L L N L L 1 L 2 1-10V + 1-10V - 1-10V + 1-10V - + DALI - DALI + DALI - DALI N L 1-10V + 1-10V - + DALI - DALI N N C O COM 25m x 6m coverage @ 8m mounting height 25m x 6m coverage @ 15m mounting height 50m detection length @ 5m mounting height

Upload: others

Post on 11-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Instruction manual for HCD450VDSRC - Hytronik · HCD450VDSRC-20170109-A1 Wire out Infrared remote receiver Daylight sensor Installation rack Sensor Antenna LED indication 125.5 135

1. Technical Specifications

Product type Independent DALI sensor (Daylight harvest)

Operating voltage 120~277VAC 50/60Hz

Switched power 2 x 2000W (resistive) 2 x 800W (capacitive)

Power consumption < 1W

Detection angle 360o

Detection range 10% / 50% / 100%

Hold time 2s / 30s / 1min / 5min / 10min / 30min

Stand-by time 0s / 10s / 1min / 10min / 30min / +

Stand-by dimming level 10% / 20% / 30%

Daylight threshold 2 ~ 50Lux , Disable

Warmming-up time 20s

Operating temperature -20oC ~ +50

oC

IP rating IP65

8

3. Functions

Daylight sensor measures the available surrounding natural light, calculates how much electrical light is needed to reach the total lux expected. The demand is given to the LED driver by DALI signal, so as to deliver the needed amount of electric light.

3.1 Daylight Harvest (Daylight Regulating)

Sometimes also know as “Potential-Free” or “Volt-Free” sensor, the dry contact sensors from Hytronik are designed to operate with external monitoring systems. They operate as conventional occupancy sensors, with the output available as shown in the table below:

3.2 Dry Contact Control

Double “L” “N” terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block and assembly time.

3.3 Loop-in and loop-out

HF Aisle Sensor with DALI Control HCD450VDSRCInstallation and Instruction Manual

2. Instruction and DimensionWarnings: 1. Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.2. Disconnect supply before installing.

4. Wiring Diagram

5. Detection Pattern

0 24

Light level

Time (hrs)

Normal Electric Light

Daylight controlled lightEnergy Saving Zone

Natural light

Hold time

Stand-by time

HCD450VDSRC-20170109-A1

Wire out

Infrared remote receiverDaylight sensor

Installation rack

Sensor Antenna

LED indication

12

5.5

135115.4

95

L L

L

N N

N

N N1

2

C OCOM

+

1-10V+ DALI -

DALI1-10V-

25

46

65

11

2.9

50

.6

82

.3

11456

Detection State Contacts Made

Presence

Absence Nc - Com

No - Com

LED Driver

LED Driver

HCD450VDSRC

Power

N

N

N

N

L

L

NL

L1

L2

1-10V +

1-10V -

1-10V +1-10V -

+

DALI -

DALI

+DALI -DALI

NL1-10V +1-10V -

+DALI -DALI

N

N

C

O

COM

25m x 6m coverage @ 8m mounting height 25m x 6m coverage @ 15m mounting height 50m detection length @ 5m mounting height

Page 2: Instruction manual for HCD450VDSRC - Hytronik · HCD450VDSRC-20170109-A1 Wire out Infrared remote receiver Daylight sensor Installation rack Sensor Antenna LED indication 125.5 135

7. Trouble Shooting

Description of the Button Functions (remote control HRC-05)

MALFUNCTION CAUSE REMEDY CAUSE REMEDY

The fixture does not light up

The fixture is always on

Check detection area setting

The fixture is on when it should not

Incorrect daylight threshold setting

Continued movement in the detection zone

Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows

Detection zone not targeted

Faulty fixture

No power supply

Adjust daylight threshold setting

Replace fixture

Check power to sensor

Check detection area setting

Adjust zone, change installation site

6.

HCD450VDSRC-20170109-A1

Hytronik Industrial Ltd. | www.hytronik.com3rd Floor, block C, complex building, 155#, Bai'gang road south, Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023Tel: 86-752-2772020 Fax: 86-752-2777877

Permanent ON/OFF [ ]1. Press button , to select permanent ON or permanent OFF mode.2. Press button to resume automatic operation. (Please refer to explanation below)

Auto Mode [ ]Press button to in initiate automatic mode.The sensor starts working and all settings remain as before the light was switched ON/OFF.

RESET [ ]

1

2

2 3 4

button 1

button 2

Press button , all settings go back to the values as below:Detection range: 100% Hold-time: 5min Stand-by period: 10min Stand-by dimming level: 10% Daylight sensor: disabled

3

button 3

Test 2s function [ ]1.Press button , the sensor goes into testmode (hold time 2s). N.B. the stand-by period and daylight sensor settings are disabled in test mode.2.Press button to exit from this mode, and the sensor settings are changed accordingly.

8

3 4 11

button 8

Ambient daylight threshold [ ]Press button , the latest surrounding lux value overwrites previous lux value learned, and is set as the daylight threshold. This feature enables the fixture to function well in any environment.

10

button 10

Power output [ ]Press button , the output shifts between 80% and 100%, for energysaving purposes.

5

button 5

Dim +/- [ ]Press button to adjust the light brightness between 10%~100% during hold-time. “+” increases the light level, “-” will decrease the light level.

9

button 9

Lux disable [ ]Press button , the built-in daylight sensor is disabled, the light will always operate upon detection regardless of ambient light level.

14

button 14

Button is disabled. 15

Manual override/ Semi-auto [ ]button 15

Detection range [ ]Press buttons in zone to set detection range at 100%/50%/10%.6

zone 6

Hold time [ ]Press buttons in zone to set hold time at 30s / 1min / 5min / 10min / 30min.

11

zone 11

Stand-by period [ ]Press buttons in zone to set the stand-by period at 0s / 10s / 1min / 10min / 30min / +∞.Note: “0s” means on/off control; “+∞” means bi-leve of dimming control, the light will never switch off. (i.e. the light remains at the stand-by dimming level until motion is detected.)

12

zone 12

Stand-by dimming level [ ]Press buttons in zone to set the stand-by dimming level at 10%/20%/30%.

7

zone 7

Daylight sensor [ ]Press buttons in zone to set daylight sensor at 2lux / 10lux / 50lux.13

zone 13

5

94

11

12

Stand-by dimming level

Detection range

ON/OFF Auto Mode Reset

Power80%

Test2s

10% 20%

30s 1min

100%

30min10min5min

0s 10s 1min

30%

SC1 SC2

SC3

Scene mode

10min

50% 10%

30min

Hold-time

Stand-by period

5min

LuxDisable

2Lux

10Lux

50Lux

Daylight Sensor

SC4

Power100% +

-Dim

M/A

312

7

8

6 10

13

14

15

HRC-05

Note: the buzzer beeps one time when RC receives signal successfully

There are 4 scene modes built into the remote control for different applications:

Scene mode options [ ]zone 4

Scene options

Detection range

Hold time

Stand-by period

Stand-by dimming leve

Daylight sensor

SC1 SC2 SC3 SC4

100% 100% 100% 100%

10% 10% 10% 10%

1min 5min 10min 10min

2Lux 2Lux 10Lux 50Lux

10min 10min 30min + 8

6 11

13

12

7

Note: the end-user can fine tune the settings by pressing buttons of detection range / hold time / stand-by period / stand-by dimming level /daylight sensor , the last setting will over-write that feature of the pre-set scene.