6 F 2 S 0 7 9 2 INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 © TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 )

Upload: ngokhanh

Post on 09-Mar-2018

217 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

6 F 2 S 0 7 9 2

INSTRUCTION MANUAL

TRIP CIRCUIT SUPERVISION RELAY

GKAD1

© TOSHIBA Corporation 2004 All Rights Reserved.

( Ver. 1.6 )

Page 2: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 1 ⎯

6 F 2 S 0 7 9 2

Safety Precautions Before using this product, please read this chapter carefully.

This chapter describes the safety precautions recommended when using the GKAD1. Before installing and using the equipment, this chapter must be thoroughly read and understood.

Explanation of symbols used Signal words such as DANGER, WARNING, and two kinds of CAUTION, will be followed by important safety information that must be carefully reviewed.

Indicates an imminently hazardous situation which will result in death or serious injury if you do not follow the instructions.

Indicates a potentially hazardous situation which could result in death or serious injury if you do not follow the instructions.

CAUTION Indicates a potentially hazardous situation which if not avoided, may result in minor injury or moderate injury.

CAUTION Indicates a potentially hazardous situation which if not avoided, may result in property damage.

DANGER

WARNING

Page 3: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 2 ⎯

6 F 2 S 0 7 9 2

• Exposed terminals Do not touch the terminals of this equipment while the power is on, as the high voltage generated is dangerous.

• Residual voltage Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It takes approximately 30 seconds for the voltage to discharge.

CAUTION

• Operating environment The equipment must only used within the range of ambient temperature, humidity and dust detailed in the specification and in an environment free of abnormal vibration.

• Ratings Before applying DC voltage to the equipment, check that they conform to the equipment ratings.

• Connection cable Carefully handle the connection cable without applying excessive force.

• Unit Do not disassemble the unit, as this may cause the unit to be damaged.

• Modification Do not modify this equipment, as this may cause the equipment to malfunction.

• Disposal When disposing of this equipment, do so in a safe manner according to local regulations.

WARNING

Page 4: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 3 ⎯

6 F 2 S 0 7 9 2

Contents Safety Precautions 1

1. Introduction 4

2. Application and Function 5 2.1 Application 5 2.2 Function 5 2.3 Connections 7

3. Hardware Structure 9

4. Installation 10 4.1 Receipt of Relays 10 4.2 Mounting 10 4.3 Electrostatic Discharge 10 4.4 Handling Precautions 10

5. Commissioning and Maintenance 11 General 11 5.2 Precautions 11 5.3 Preparation 11 5.4 Storage 11

Appendix A 13 Outline Diagram 14

Appendix B 15 Technical Data 16

Appendix C 19 Ordering 20

The data given in this manual are subject to change without notice. (Ver.1.6)

Page 5: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 4 ⎯

6 F 2 S 0 7 9 2

1. Introduction The GKAD1 is a trip circuit supervision relay, and is provided the following features:

- Trip circuit supervision in both closed and open positions of circuit breaker

- Detection and alarm of trip circuit supply failure and of circuit breaker tripping mechanism failure

- Single-phase or three-phase types available

- Compact size design

- Flush mounting

Page 6: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 5 ⎯

6 F 2 S 0 7 9 2

2. Application and Function 2.1 Application

The GKAD1 is used for monitoring of the circuit breaker tripping circuit. The GKAD1 issues an alarm if the GKAD1 detects trip circuit supply failure or circuit breaker tripping mechanism failure.

The GKAD1 has two models as shown in Table 2.1.

Table 2.1 GKAD1 Models

Model Configuration

GKAD1-12 Single-phase type

GKAD1-22 Three-phase type

2.2 Function

The GKAD1 monitors the circuit breaker tripping control, and Figure 2.1 shows a typical scheme. When the trip circuit is complete, a small current flows in photo-couplers PC1 and/or PC2, the circuit breaker auxiliary contacts and the trip coil. This current flows for both the breaker open and closed conditions.

Figure 2.1 Trip Circuit Supervision Scheme (1)

If the trip circuit supply is lost or if a connection becomes open circuit then the GKAD1 issues a trip circuit fail alarm and operates the target indicator. As for the sensitivity, the detection voltage and detection current are 40V or less and 1.5mA or less.

Figure 2.2 shows the special application of GKAD1 relay. This scheme ensures that all trip circuit wiring (tripping route) from the trip contact to the trip coil is supervised in either the breaker closed or open condition. At CB closed condition, the monitoring current flows in photo-coupler PC1. On the other hand, at CB open condition, the monitoring current flows in photo-couplers PC1 and PC2 via tripping cable and CB auxiliary contact 52b. Under both CB conditions, if tripping route/trip coil is disconnected, the monitoring current is interrupted and both PC1 and PC2 are off and the GKAD1 issues alarm.

t 0

0.4s

CB coil

52a 52b

Protection relay

Trip circuit( + )

( − )

PC1

PC2

GKAD1

14

13

16

15

18

17

1 3

4

≥1 1

LCP & GIS

2 0 t

0.4s

Target Indicator (Hand reset type)

D

Resistor

Page 7: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 6 ⎯

6 F 2 S 0 7 9 2

Figure 2.2 Trip Circuit Supervision Scheme (2)

Output Contacts The GKAD1 provides a normally close and two normally open contacts for the trip circuit fail alarm and a normally close contact for power supply fail alarm. (See Figures 2.3 and 2.4.)

The detection sensitivity for power supply fail is less than 60V.

CB coil

52a 52b

Protection relay

Trip circuit ( + )

( − )

PC1

PC2

GKAD1

14

13

16

15

18

17

1 3

4

≥1 1t 0

0.4s

LCP & GIS

2 0 t

0.4s

Target Indicator (Hand reset type)

D

Resistor

Page 8: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 7 ⎯

6 F 2 S 0 7 9 2

2.3 Connections

The GKAD1 auxiliary supply input has a nominal 110/125Vdc rating or 220/250Vdc rating.

The typical application and connection diagrams are shown in Figures 2.3 and 2.4. Figure 2.3 shows a single-phase application for GKAD1-12 and Figure 2.4 shows a three-phase application for GKAD1-22.

The two resistors on the PC1, PC3 and PC5 photo coupler circuits are added as shown in Figure 2.3 and 2.4 below in consideration of the fail-safe of relay failure. The resistors can function to prevent unwanted tripping due to relay internal circuit failure under CB closed condition.

CAUTION Do not connect anything to 5th-12th terminals in Figure 2.3. These are reserved in GKAD1-12.

1

14

13

16

15

18

17

20

19

56789

101112

No connection (reserved)

Protection relay

Trip circuit ( + )

Resistor PC1

PC2 ≥1 1

0.4s

D

Target Indicator (Hand reset type)

0 t

0.4s

1

22

GKAD1-12

3

4

t 0 2

CB coil

52a 52b

( − ) LCP & GIS

(Note) The dotted line shows the scheme (2) mentioned in Figure 2.2.

(-)

(+) DC SUPPLY

Voltage Regulator

POWER SUPPLY FAIL21

Figure 2.3 GKAD1-12 Typical Application Diagram

Page 9: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 8 ⎯

6 F 2 S 0 7 9 2

7

Trip circuit (A phase)

(-)

(+) DC SUPPLY

Voltage Regulator 1

POWER SUPPLY FAIL

20

19 21

22

≥1 1 t 0

0.4s

D

C-phase

14

13

16

15

18

17

≥1

Trip circuit (B phase)

Trip circuit (C phase)

Monitor input circuit

Monitor input circuit

CB coil

52a 52b

Protection relay

( + )

( − )

GKAD1-22

LCP & GIS

PC1

PC2

1 3

4

≥1 1t 0

0.4s

2

(Note) The dotted line shows the scheme(2) mentioned in Figure 2.2.

Monitor input circuit

PC3

PC4

5

8

≥1 1 t 0

0.4s

6

D

B-phase

Target Indicator (Hand reset type)

D

A-phase

11

PC5

PC6

9

12

10

Resistor

0 t

0.4s

0 t

0.4s

0 t

0.4s

Figure 2.4 GKAD1-22 Typical Application Diagram

Page 10: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 9 ⎯

6 F 2 S 0 7 9 2

3. Hardware Structure The Figure 3.1 shows a hardware structure of GKAD1. The GKAD1-12 is a single phase type and has one target indicator.

A-PHASE

B-PHASE

C-PHASE

TRIP CIRCUIT FAIL

POWER

TRIP CIRCUIT SUPERVISION RELAY

TARGET INDICATOR

TARGET RESET LEVER (Push it left to reset Target)

Figure 3.1 Front View of GKAD1-22

Page 11: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 10 ⎯

6 F 2 S 0 7 9 2

4. Installation 4.1 Receipt of Relays

On receiving the GKAD1 relays, carry out the acceptance inspection immediately. In particular, check for damage during transportation, and if any is found, contact the vendor.

Always store the unit in a clean, dry environment.

4.2 Mounting

Refer to Appendix A for details of mechanical fixings.

4.3 Electrostatic Discharge

CAUTION

The printed circuit board (PCB) within the GKAD1 relay is not intended to be a removable module. Do not remove the PCB from the unit case, since electronic components on the PCB are very sensitive to electrostatic discharge. If it is absolutely essential to take the PCB out of the case, do not touch the electronic components and terminals with your bare hands. Additionally, always put the PCB in a conductive anti-static bag when storing it.

4.4 Handling Precautions

A person's normal movements can easily generate electrostatic potential of several thousand volts. Discharge of these voltages into semiconductor devices when handling electronic circuits can cause serious damage, which often may not be immediately apparent but the reliability of the circuit will have been reduced.

The electronic circuits are completely safe from electrostatic discharge when housed in the case. Do not expose them to risk of damage by removing the PCB unnecessarily.

The unit incorporates the highest practicable protection for its semiconductor devices. However, if it becomes necessary to remove the PCB, precautions should be taken to preserve the high reliability and long life for which the equipment has been designed and manufactured.

CAUTION

• Before removing the PCB, ensure that you are at the same electrostatic potential as the equipment by touching the case.

• Handle only the edges of the PCB. Avoid touching the electronic components, PCB surface or connectors.

• Do not pass the PCB to another person without first ensuring you are both at the same electrostatic potential. Shaking hands achieves equipotential.

• Place the PCB on an anti-static surface, or on a conducting surface which is at the same potential as yourself.

• Do not place the PCB in a polystyrene tray.

It is strongly recommended that detailed investigations on electronic circuitry should be carried out in a Special Handling Area such as described in the IEC 60747.

Page 12: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 11 ⎯

6 F 2 S 0 7 9 2

5. Commissioning and Maintenance General

Test personnel must be familiar with general relay testing practices and safety precautions to avoid personal injuries or equipment damage.

5.2 Precautions

CAUTION

• Ensure that the auxiliary supply connections are properly fixed to their terminals. • Before turning on the power, check that the polarity and voltage of the power supply are

correct.

• Turn off the auxiliary supply before checking the interior of the relay.

• While the power is on, do not mount/dismount the PCB.

Failure to observe any of the precautions above may cause damage or malfunction of the relay. Refer to section 4.4 for information on handling precautions.

5.3 Preparation

Test equipment The following test equipment is required for the commissioning tests.

• DC power supply.

• Calibrated voltmeter.

Visual inspection After unpacking the product, check for any damage to the case. If there is any damage, the internal module might also have been affected. Contact the vendor.

Unit ratings Check that the items described on the nameplate on the front of the unit conform to the user’s specification. The items are: relay type and model, and auxiliary DC supply voltage rating.

5.4 Storage

The spare relay should be stored in a dry and clean room. Based on IEC Standard 60255-0 the storage temperature should be −25°C to +70°C, but the temperature of 0°C to +40°C is recommended for long-term storage.

Page 13: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 12 ⎯

6 F 2 S 0 7 9 2

Page 14: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 13 ⎯

6 F 2 S 0 7 9 2

Appendix A

Outline Diagram

Page 15: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 14 ⎯

6 F 2 S 0 7 9 2

Outline Diagram

GKAD1 Outline and Panel Cutout Diagram

Cover

Panel cut-out

83 +1.0/−0

186

+0/−

0.5

TB: M3.5 Ring terminal

149 21 13.5

192

89

185

1 2

3 4

5 6

7 8

9 10

11 12

13 14

15 16

17 18

19 20

21 22

Terminal Block(TB) Arrangement (Rear View)

Page 16: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 15 ⎯

6 F 2 S 0 7 9 2

Appendix B

Technical Data

Page 17: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 16 ⎯

6 F 2 S 0 7 9 2

Technical Data

Ratings DC auxiliary supply: 110/125Vdc (Operative range: 88 - 150Vdc),

220/250Vdc (Operative range: 176 - 300Vdc) Superimposed AC ripple on DC supply: ≤ 12% DC supply interruption: ≤ 50ms at 110V Function Trip circuit supervision Detection voltage: 40V or less for 110V/125Vdc

70V or less for 220V/250Vdc Detection current: 1.5mA or less for 110V/125Vdc

1.5mA or less for 220V/250Vdc Power supply fail Detection voltage: less than 60V Burden DC auxiliary supply: ≤ 2.5W Binary input circuit ≤ 0.5W per input at 110/125Vdc

(Current: ≤ 4mA at 110/125Vdc) Output Contacts Number 3: trip circuit fail alarm (2NO, 1NC)

1: power supply fail alarm Ratings: Make and carry: 4A continuously

Make and carry: 10A, 220Vdc for 0.5s (L/R=5ms) Break: 0.1A, 220Vdc (L/R=40ms)

Durability: Make and carry: 10000 operations Break: 100000 operations

Mechanical Design Weight Case colour Installation

1.5kg Munsell No. N1.5 Flush mounting

Environmental Performance Test Standards Details

Atmospheric Environment Temperature IEC60068-2-1/2 Operating range: -10°C to +55°C.

Storage / Transit: -25°C to +70°C. Humidity IEC60068-2-3 56 days at 40°C and 93% relative humidity. Enclosure Protection

IEC60529 IP50

Mechanical Environment Vibration IEC60255-21-1 Response - Class 1

Endurance - Class 1 Shock and Bump IEC60255-21-2 Shock Response Class 1

Shock Withstand Class 1 Bump Class 1

Seismic IEC60255-21-3 Class 1

Page 18: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 17 ⎯

6 F 2 S 0 7 9 2

High Voltage Environment Dielectric Withstand

IEC60255-5 2kVrms for 1 minute between all terminals and earth.2kVrms for 1 minute between independent circuits. 1kVrms for 1 minute across normally open contacts.

High Voltage Environment High Voltage Impulse

IEC60255-5 Three positive and three negative impulses of 5kV(peak), 1.2/50μs, 0.5J between all terminals and between all terminals and earth.

Electromagnetic Environment High Frequency Disturbance / Damped Oscillatory Wave

IEC60255-22-1 Class 3, IEC61000-4-12

1MHz 2.5kV applied to all ports in common mode. 1MHz 1.0kV applied to all ports in differential mode.

Electrostatic Discharge

IEC60255-22-2 Class 3, IEC61000-4-2

6kV contact discharge. 8kV air discharge.

Radiated RF Electromagnetic Disturbance

IEC60255-22-3 Class 3, IEC61000-4-3

Field strength 10V/m for frequency sweeps of 80MHz to 1GHz and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450, 900 and 1890MHz.

Fast Transient Disturbance

IEC60255-22-4, IEC61000-4-4

4kV, 2.5kHz, 5/50ns applied to all inputs.

Conducted RF Electromagnetic Disturbance

IEC60255-22-6, IEC61000-4-6

10Vrms applied over frequency range 150kHz to 100MHz. Additional spot tests at 27 and 68MHz.

Conducted Disturbance over freq. Range 15Hz to 150kHz

IEC61000-4-16Class 3 Varying voltages applied in common mode as follows: 15Hz to 150Hz: 10V → 1Vrms (20dB/decade) 150Hz to 1.5kHz: 1Vrms 1.5kHz to 15kHz: 1 → 10Vrms (20dB/decade) 15kHz to 150kHz: 10Vrms

Power Frequency Disturbance

IEC60255-22-7 300V 50Hz for 10s applied to ports in common mode.100V 50Hz for 10s applied to ports in differential mode.

Surge Immunity IEC61000-4-5

1.2/50μs surge in common/differential modes: PSU and I/O ports: 2kV/1kV (peak)

Conducted and Radiated Emissions

IEC60255-25 EN55022 Class A

Conducted emissions: 0.15 to 0.50MHz: <79dB (peak) or <66dB (mean) 0.50 to 30MHz: <73dB (peak) or <60dB (mean) Radiated emissions: 30 to 230MHz: <30dB 230 to 1000MHz: <37dB

Power Frequency Magnetic Field

IEC61000-4-8Class 4 Field applied at 50Hz with strengths of: 30A/m continuously, 300A/m for 1 second.

Page 19: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 18 ⎯

6 F 2 S 0 7 9 2

Page 20: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 19 ⎯

6 F 2 S 0 7 9 2

Appendix C

Ordering

Page 21: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 20 ⎯

6 F 2 S 0 7 9 2

Ordering

Trip Circuit Supervision Relay Type: Trip Circuit Supervision Relay GKAD1 Model: Single-phase type 12 Three-phase type 22 Monitored DC circuit voltage and DC auxiliary supply rating:

110V/125V 11 220V/250V 22

GKAD1

Page 22: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions

⎯ 21 ⎯

6 F 2 S 0 7 9 2

Version-up Records Version

No. Date Revised Section Contents

0.0 Feb. 20, 2004 -- First issue. 0.1 May 19, 2004 2.2

2.3 Appendix B

Modified the description. (Added the detection sensitivity of GKAD1.) Added the CAUTION. Added the detection sensitivity of GKAD1.

1.1 Feb. 17, 2005 2.2 2.3 Appendix B

Modified the description (sensitivity) and Figures 2.1 and 2.2. Modified Figures 2.3 and 2.4. Modified the description.

1.2 Dec. 06, 2005 2.3 Connections Appendix B

Modified the description and Figures 2.3 and 2.4(resistor). Added ‘Mechanical Design’.

1.3 Jun. 05, 2006 2.2 2.3

Modified Figures 2.1 and 2.2. Modified the description and Figures 2.3 and 2.4.

1.4 Dec. 21, 2007 2.2 Appendices

Modified the description. Modified Appendix B and added ‘Appendix C Ordering’.

1.5 Nov. 11, 2008 2.2 Appendix B.

Modified the description. (detection sensitivity of power supply fail) ditto

1.6 Jun. 08, 2009 2.2 2.3

Modified Figures 2.1 and 2.2. Modified Figures 2.3 and 2.4.

Page 23: INSTRUCTION MANUAL TRIP CIRCUIT … GKAD1 is a trip circuit supervision relay, and is provided the following features: - Trip circuit supervision in both closed and open positions