insulator strings for substations 66-500kv - ribe- · pdf file66 / 145 / 245 / 300 / 420 / 500...
TRANSCRIPT
![Page 1: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/1.jpg)
Insulator strings for substations 66-500kV
![Page 2: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/2.jpg)
Differences between OHL and S/S strings
Breaking loads(substations max. ca. 130kN, OHL higher)
Short circuit currents(substations usually 40-80 kA1s, OHL lower)
Conductor arrangements(OHL always jumper, substations dead ends)
Clearances acc. to EN61284
Quantities
![Page 3: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/3.jpg)
Standardisation basics (1) Uniform tower attachment
String attachment scheme
Tension string ->
Suspension string ->
Plan View:
Conductor perpendicular to the hinge direction
![Page 4: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/4.jpg)
Standardisation basics (2) „End“ clamps separate
PAK = Compression type.
DAK = Bolted cover type.
BAK = U-bolted type.
HK = Simple suspensiontype
KAK = Wedge type
![Page 5: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/5.jpg)
Standardisation basics (3) Performance values
Voltage levels66 / 145 / 245 / 300 / 420 / 500 kV
Short- current withstand levels40 / 50 / 63 / 80 kA1s
Insulator typesCap & pin / long-rod / polymeric
Breaking loadminimal 130 kN, usually 160kN and more
![Page 6: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/6.jpg)
Standardisation basics (4) Conductor arrangements
A = single conductor o
W = duplex (Horizontal) o o
S = duplex (Vertical) oo
D = triplex (2 on top) o oo
E = triplex (1 on top) oo o
![Page 7: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/7.jpg)
Standardisation basics (5) Conductor arrangements
F = triplex (flat) o o o
Q = Quadruple (#) o oo o
T = Quadruple (flat) o o o o
H = specials
![Page 8: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/8.jpg)
Sensitive topics – string arrangements
Dead End -> Corona
if Un > 245kV
T-derivation -> Corona if Un > 245kV
Suspension (run)
= OK
Tension with jumper
= OK
![Page 9: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/9.jpg)
Sensitive topics – clamps arrangements
![Page 10: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/10.jpg)
Sensitive topics – short circuit currents
![Page 11: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/11.jpg)
Numbering system for insulator strings
Seq. Value DescriptionKK String for cap and pin insulatorsKL String for longrod insulators
3 1, 2 Number of insulator strains4 A , H String type: A=tension , H=suspension5 0, 1, 2,
4, 5Voltage levels(0=<66kV, 1=<150kV, 2=245kV,4=420kV,5=525kV)
6 Conductors and their arrangementA "A" = single conductorW "W" = Duplex cond.in horizontal planeS "S" = Duplex cond.in vertical planeD "D" = Triplex cond. (2 on top)E "E" = Triplex cond. (1 on top)F "F" = Triplex cond. (flat arrangement)Q "Q" = Quadruple cond. (rectangular arrangement)T "T" = Quadruple cond. (flat arrangement)H "H" = Special arrangement (line traps)
7 "-" "+" "#" Cap and pin size: "-"= 16 IEC, "+"= 20 IEC, "#"= 24 IEC8+9 00 - 99 Varianion 10 S Optional for tension strings with turnbuckles
1+2
![Page 12: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/12.jpg)
Catalogue – RIBE-Strings.xls (1)
Use the filter – option to find the string
![Page 13: Insulator strings for substations 66-500kV - Ribe- · PDF file66 / 145 / 245 / 300 / 420 / 500 kV Short- current withstand levels. 40 / 50 / 63 / 80 kA1s Insulator types. ... W "W"](https://reader034.vdocument.in/reader034/viewer/2022051320/5aab9c5f7f8b9a9c2e8c1f6e/html5/thumbnails/13.jpg)
Catalogue – RIBE-Strings.xls (2)
Click for 2D / 3D - preview