insulator-type-tests.pdf

Upload: sorry2qaz

Post on 03-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Insulator-Type-Tests.pdf

    1/34

    TYPE TESTS ON DISC INSULATOR

    UNITS & STRINGS

  • 7/28/2019 Insulator-Type-Tests.pdf

    2/34

    TYPE TESTS ON DISC INSULATOR

    UNITS & STRINGS

    On single units

    Sl

    no

    Nature of test Reference: standard/document

    1 Verification of dimensions Approved drawing

    Disc diameter - do -

    Unit spacing - do -

    Creepage distance - do -

    Radial & axial run out - do -

    2 Thermal Mechanical

    performance test

    Powergrid tech specn & Cl 20 of IEC 383-

    1/93

    3 PF Voltage withstand and

    flashover test (Dry & Wet)

    Powergrid approved GTP & Cl 20 of IEC

    383-1/93

    4 LI withstand and flashover

    test (Dry)

    Powergrid approved GTP & Cl 20 of IEC

    383-1/935 Visible discharge & RIV

    test

    Powergrid approved GTP, IS 731/71 &

    IEC 437/97

    6 R id l t th IEC 797

  • 7/28/2019 Insulator-Type-Tests.pdf

    3/34

    On string with hardware fittings

    Sl

    no

    Nature of test Reference: standard/document

    1 PF voltage withstand

    (Wet)

    Cl 10 of IEC 383-2

    2 SI voltage withstand

    (Wet) - only on stringsused for 400 kV & above

    Cl 11 of IEC 383-2

    3 LI voltage withstand &

    flashover test (Dry)

    Cl 9 of IEC 383-2

    4 Voltage distribution Powergrid tech specn

    5 Mechanical strength test Powergrid tech specn

    6 Vibration test Powergrid tech specn7 Power arc test IEC 1467

    8 Artificial Pollution test

    (only on anti fog discs)

    IEC 507

  • 7/28/2019 Insulator-Type-Tests.pdf

    4/34

    TYPE TEST PROCEDURE

    TEST ON SINGLE UNITS

    1) Verification of dimensions

    Following physical dimensions shall be checked on 10 samples in

    accordance with the drawing approved by Powergrid.

    a) Disc diameter

    b) Unit spacing

    c) Creepage distance

    d) Verification of eccentricitye) Gauge check of socket cap & Ball pin

    Disc diameter

    a) Reference standard Approved drawing

    a) Purpose/critically oftesting

    Influences the creepage distance of the single unit andalso gap between insulator strings in case of double,

    triple & quad strings

    b) Test procedure Check the outer diameter of disc & verify compliance

  • 7/28/2019 Insulator-Type-Tests.pdf

    5/34

    Unit spacing

    a) Reference standard Approved drawing

    b) Purpose/critically of

    testing

    Influences the overall length of the string and hence the

    phase to ground clearances.

    c) Test procedure Check the ball pin to ball pin distance of the single unit

    & verify compliance with the drawing

    d) Acceptance criteria 120 kN 145 +/- 4 mm, 160 kN & 210 kN 170 +/- 5 mm.

    e) Instruments used Marking block & vernier height gauge

  • 7/28/2019 Insulator-Type-Tests.pdf

    6/34

    Creepage distance

    a) Reference: standard Approved drawing

    b) Purpose/critically of

    testing

    Influences the electrical performance especially under

    pollution

    c) Test procedure Using adhesive tape the shortest distance between thesocket cap & pin is measured accounting only the

    porcelain surface.

    d) Acceptance criteria Normal disc

    120 kN 315 mm + 60/- 0

    160 kN 330 mm + 40/- 0

    Anti fog

    120 kN 430 mm + 60/- 0

    160 kN 475 mm + 40/- 0

    e) Instruments used

    Steel scale & adhesive tape

  • 7/28/2019 Insulator-Type-Tests.pdf

    7/34

    Radial & axial run out

    a) Reference standard Approved drawing

    b) Purpose/critically of

    testing

    It is a measure of alignment of socket cap, porcelain and

    ball pin. Influences the mechanical strength of the unit

    c) Test procedure The insulator is placed under light tension between

    suitably mounted coupling pieces. The two coupling pieces

    shall be on the same axis and shall be free to rotate. Two

    dial gauges are arranged as shown so that they make

    contact with the maximum diameter and at the tip of the

    outer most rib. The insulator is rotated through 360 deg

    and the max variation in the readings of the dial gauges is

    recorded.

    d) Acceptance criteria Radial run out - < 3 % of disc dia

    Axial run out - < 4 % of disc dia

    e) Instruments used Dial gauge

  • 7/28/2019 Insulator-Type-Tests.pdf

    8/34

    Gauge check for ball & socket coupling

    a) Reference standard IEC 120

    b) Purpose/critically of

    testing

    It is carried out to verify the compliance of the ball &

    socket coupling with relevant gauges.

    c) Test procedure The socket cap & ball pin of the insulator shall be

    checked with the relevant standard calibrated GO &

    NOT GO gauges. The samples shall comply with the

    standard gauges.

    d) Acceptance criteria Compliance with gaugese) Instruments used Standard Calibrated Gauges

  • 7/28/2019 Insulator-Type-Tests.pdf

    9/34

    2) Thermal Mechanical performance test

    a) Reference standard Powergrid tech specn &

    Cl 20 of IEC 383-1/93

    b) Purpose/critically of

    testing

    To check the mechanical performance of the samples

    under simultaneous tensile loading and extreme varying

    temperatures.c) Test procedure This test is carried out on 20 samples. The test is carried

    out in a specially constructed thermal chamber. A tensile

    load equal to 70 % of the specified EM load shall be

    applied and the temperature inside the chamber shall be

    varied from 30 deg to + 40 deg C in a duration of 24

    hours. Minimum tensile load of 70 % shall be maintained

    through out the 24 hours duration and shall be released

    and reapplied after every 24 hours. After completing 4cycles of 24 hours each, the tensile load shall be released &

    temperature brought down to the ambient and the units

    shall be subjected to EMS test. No failure during thermal

    cycles or during EMS test is permitted. After EMS test,

    Average (X) & Standard deviation (S) is calculated &

    statistically evaluated.

    d) Acceptance criteria No failure during thermal cycles or during EMS test is

    permitted. The test results shall meet the following

    criteria.

    X (R 3 ) h R i th t d EM t th

  • 7/28/2019 Insulator-Type-Tests.pdf

    10/34

    TYPICAL LOAD & TEMPERATURE CURVE

  • 7/28/2019 Insulator-Type-Tests.pdf

    11/34

    3) PF Voltage flashover & withstand test

    Dry conditiona) Reference standard IEC 383-1

    b) Purpose/critically oftesting

    To verify the flashover & withstand voltage of the singleunit using PF voltage under dry condition

    c) Test procedure The test is carried out on 3 samples. Voltage is applied to

    the ball pin of the insulator & the socket cap is earthed. 5

    flashovers are applied & average value obtained. The

    voltage is reapplied and maintained at the specified value

    for a duration of 1 minute & no flashover is permitted

    during this interval.. The test values are corrected to the

    standard atmospheric condition. The value obtained shall

    be greater than the specified value

    d) Acceptance criteria 120 kN F/o >75 kV, W/s >70 kV

    160 kN F/o >80 kV, W/s > 75 kV

    e) Instruments used PF testing transformer & arrangement for suspending the

    insulator in vertical condition

    Wet conditiona) Reference standard IEC 383-1

  • 7/28/2019 Insulator-Type-Tests.pdf

    12/34

    4) Dry LI voltage flashover & withstand test

    a) Reference standard IEC 383-1

    b) Purpose/criticall

    y of testing

    To verify the flashover & withstand voltage of the

    single unit using LI voltage under dry condition

    c) Test procedure The test is carried out on 3 samples

    d) Acceptance

    criteria

    120 kN 110 kV/120 kV

    e) Instruments

    used

    Impulse Generator

    5) Visible discharge & RIV test

    a) Reference standard IEC 60-1 & 437

    b) Purpose/critically

    of testing

    To verify the specified test voltage

    c) Test procedure The test is carried out on 3 samples

    d) Acceptance Visible Discharge voltage > 18 kV

  • 7/28/2019 Insulator-Type-Tests.pdf

    13/34

    f) Residual strength test

    a) Reference standard IEC 797

    b) Purpose/critically of

    testing

    Verification of the minimum mechanical

    strength of insulator stubs with out shed when

    used in string.

    c) Test procedure This test shall be carried out on 25 samples.

    Samples shall be subjected to temperature cycle

    test as per IEC 383-1. The sheds shall be broken

    using hammer blows and no part of the broken

    shed shall be greater than the maximum

    diameter of the socket cap. The stubs shall then

    be subjected to tensile load applied between themetal fittings and value recorded. Average (X)

    & Standard deviation (S) of the test values shall

    be calculated and compared with the factor k

    (0.65)

    d) Acceptance criteria (X 1.645 )/R 0.65

    e) Instruments used Tensile testing machine

  • 7/28/2019 Insulator-Type-Tests.pdf

    14/34

    g) Steep Front Wave test

    b) Reference

    standard

    Powergrid technical specification

    c) Purpose/critically

    of testing

    To verify the puncture withstand capability of

    insulator in air when subjected to impulse voltage

    of high rate of raise.

    d) Test procedure This test is carried out on 10 samples. Each

    insulator shall be subjected to 5 positive & 5

    negative impulses with effective rate of raise of

    2500 kV/micro sec. Subsequently the samples shall

    be subjected to PF flashover test under Dry

    condition.

    e) Acceptance

    criteria

    Average of 3 PF flashovers shall not be lesser than

    95 % of the specified Dry PF flashover voltage. No

    puncture shall occur either during Impulse or PF

    voltage application

    f) Instruments used LI generator, PF test transformer

  • 7/28/2019 Insulator-Type-Tests.pdf

    15/34

    Typical wave shape

    Calculation of steepness

    Steepness = Voltage/Raise time

    Voltage = Y x Voltage scale x divider ratio x attenuation

  • 7/28/2019 Insulator-Type-Tests.pdf

    16/34

    h) Impact test

    i) Reference

    standard

    Powergrid tech specn & ANSI C 29.2

    j) Purpose/critically

    of testing

    To verify the withstand capability of insulator

    shed when subjected to mechanical impact.

    k) Test procedure 3 samples shall be subjected to specified Impact

    load applied to the outer most rim of the

    insulator. No breakage of the insulator shed is

    permitted. Subsequently the samples shall also

    pass PF frequent flashover test. No puncture shall

    occur during flashover test.

    l) Acceptance

    criteria

    7 N-m for up to 120 kN. 10N-m for above 160 kN

    disc insulators

    m)Instruments used Impact testing machine & PF test transformer

  • 7/28/2019 Insulator-Type-Tests.pdf

    17/34

    TEST ON STRINGS WITH HARDWARE FITTINGS

  • 7/28/2019 Insulator-Type-Tests.pdf

    18/34

    a. PF voltage withstand (Wet)

    a) Reference standard Cl 10 of IEC 383-2

    b) Purpose/critically

    of testing

    To verify the specified withstand voltage of the

    insulator string

    c) Test procedure In accordance with IEC

    d) Acceptance

    criteria

    220 kV 460 kV, 400 kV - 680 kV

    e) Instruments used PF Testing transformer

    b. SI voltage withstand (Wet)

    a) Reference standard Cl 11 of IEC 383-2

    b) Purpose/critically

    of testing

    To verify the specified withstand voltage of the

    insulator string under wet condition

    c) Test procedure In accordance with IEC

  • 7/28/2019 Insulator-Type-Tests.pdf

    19/34

    e) Instruments used Impulse Generator

    d. Voltage distribution (Dry)

    a) Reference standard Powergrid tech specn

    b) Purpose/critically

    of testing

    To measure the distribution of voltage across an

    energized disc insulator string

    c) Test procedure Sphere gap method, % VD = E/Vn x 100

    d) Acceptance

    criteria

    400 kV < 10 %

    e) Instruments used PF Testing transformer, Calibrated spheres

  • 7/28/2019 Insulator-Type-Tests.pdf

    20/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    21/34

    e. Radio Interference Voltage test

    a) Reference standard Powergrid tech specn

    b) Purpose/critically

    of testing

    To measure the Radio noise generated by the test

    sample when subjected to HV stress.

    c) Test procedure IEC 60437

    d) Acceptance

    criteria

    Noise level < 60 dB @ 305 kV for 400 kV strings

    e) Instruments used PF Testing transformer, Coupling capacitor,

    Radio noise meter

    f. Corona test

    a) Reference standard Powergrid tech specn

    b) Purpose/critically

    of testing

    To measure the Corona Inception & extinction

    voltage on the test sample

    c) Test procedure IS 731-1971

    d) Acceptancecriteria

    Extinction voltage > 320 kV for 400 kV strings

    e) Instruments used PF Testing transformer, dark test hall

  • 7/28/2019 Insulator-Type-Tests.pdf

    22/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    23/34

    h. Vibration test

    a) Reference standard Powergrid tech specn

    b) Purpose/critically

    of testing

    To verify the performance of the insulator set

    under Dynamic loading

    c) Test procedure Powergrid spec

    d) Acceptance

    criteria

    Shall withstand 10 million cycles of vibration

    under specified conditions

    e) Instruments used Vibration inducing equipment

  • 7/28/2019 Insulator-Type-Tests.pdf

    24/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    25/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    26/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    27/34

    i. Power Arc test

    a) Reference standard IEC 1467

    b) Purpose/critically

    of testing

    To verify the performance of the insulator set

    when subjected to Power Arcs

    c) Test procedure IEC 1467

    d) Acceptance

    criteria

    The string shall not separate after subjected to 3

    shots of 40 kA for a duration of 0.2 s, 0.2 s & 0.5 s.

    Subsequently the string shall withstand 80 % of

    the rated tensile load

    e) Instruments used Short circuit generator

  • 7/28/2019 Insulator-Type-Tests.pdf

    28/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    29/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    30/34

    j. Artificial Pollution withstand test

    a) Reference standard IEC 507

    b) Purpose/critically

    of testing

    To verify the performance of the insulators under

    polluted condition

    c) Test procedure IEC 507, Salt fog Method & Clean fog method

    d) Acceptance

    criteria

    The string shall withstand 3 voltage applications

    at specified Pollution level & testing conditions

    e) Instruments used PF testing transformer, Pollution chamber

  • 7/28/2019 Insulator-Type-Tests.pdf

    31/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    32/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    33/34

  • 7/28/2019 Insulator-Type-Tests.pdf

    34/34