Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513 1
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
• For single-phase line systems (where required)• For three-phases systems with or without neutral• Imbalance control for produced power• Monitoring of phase sequence• RTC function with operating hours counter• Self-protection components• "Power Save" mode for limit consumption• Input for auxiliary contact DDI• Input for remote control• Input for local control• Input for communication presence• Input (configurable auxiliary) for external alarm• Relay output command for Interface Device backup • Relay output for backup (for systems> 20kWp)• Measurement variables VLL, VLN, Hz, (recording min/max)• Measurement variables AL, AN, VA, W, VAr, PF (by
external CT) Recording the maximum and minimum• Measurement of voltage and current THD• Measure energy kWh, kVArh imported / exported total
/ partial
Product DescriptionProtection relayinterface with intelligentenergy meter integratedvisualization system withLCD display. The devicePI96 is configured to beused as a protectiverelay interface and iscompliant with standardCEI 0-21 technique inmanufacturing facilitiesenergy. The protectionrelay interface PI96 is
particularly suitable forthe measurement of themain variables as well asact as a protective relay.PI96 The device is basedon a modular conceptfor panel mounting IP65factor. This protectionrelay interface has 2relay outputs, one forthe control of the maindisconnect (InterfaceDevice) and the other to
ModelPower SupplyCommunicationOptions
Type SelectionModel
Panel mounting PI960021 Power Supply
115..230VCA, -20%/+15% H(48..62Hz)
Option 24VCC, -20%/+10% LCommunication
RS485/RS232 Ports S1
Ord. Key PI96 0021 H I6 R4 S1 XX
control the auxiliarydevice such as backupof the Interface Device insystems with an outputexceeding 20kWp inaccordance with therequirements ofStandard CEI 0-21. Thedevice is equipped withother PI96 2 relayoutputs for the control ofauxiliary functions (egrelease for imbalance of
power, etc.). Theprotection relay interfacePI96 is also providedwith two serialcommunication linesRS232 / RS485 forremote monitoring notonly of the values ofvoltage, frequency,current, power andenergy, but also forevents recorded.
Integrated Protection FunctionsCode/Protection Function Description
27.S1 minimal voltage set 1
27.S2 minimal voltage set 2
59.S1 maximal voltage set 1 EN 61000-4-30
59.S2 maximal voltage set 2
81<.S1 minimal frequency set 1
81<.S2 minimal frequency set 2
81>.S1 maximal frequency set 1
81>.S2 maximal frequency set 2
BF (Breaker Failure) Interface Device open failure
Power “IMBALANCE” imbalance control for produced power (only three-phases systems)
• SW programming block• Protection Degree IP65• Auxiliary power supply AC and DC
![Page 2: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/2.jpg)
2 Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
Interface protectionVoltage Setpoint
Upper Voltage (59.S1)* 1,1 Un*Average mean voltagemeasured on 10min.Every 3 seconds a newvalue of the previous 10minhas to be created andcompared to set valueAcc to CEI EN 61000-4-30Upper voltage (59.S2) 1,15 UnLower voltage (27.S1) 0,85 UnLower voltage (27.S2) 0,40 Un
Rated grid frequency 50HzFrequency setpoints
Higher frequency ( 81>.S1 ) 50,5HzLower frequency ( 81<.S1 ) 49,5HzHigher frequency ( 81>.S2 ) 51,5HzLower frequency ( 81<.S2 ) 47,5Hz
TimingsPower ON delay 30sUpper voltage protection(59.S1) ≤3sUpper voltage protection (59.S2) 200msLower voltage protection (27.S1) 400msLower voltage protection (27.S2) 200msHigher frequency protection(81>.S1) 100msLower frequency protection (81<.S1) 100msHigher frequency protection (81>.S2) 100ms or 1s (remote mode)Lower frequency protection (81<.S2) 100ms or 4s (remote mode)
Connection / reconnectioncondition
Condizioni sotto verifica U ≥ 85% ≤ 110% andf ≥ 49,90Hz ≤ 50,10Hz
Power ON delay /connection ≥ 30sReconnection forPI intervention ≤ 0,1s
Alarm and diagnostics messages
Events Notes
Max Number of events stored 1000 - FIFO - con data ed ora evento
Alarms
• Intervention for: 59.S1 or 59.S2, 27.S1 or 27.S2, 81>S1 or81>S2, 81<S1 or 81<S2.
• Main contactor survey fault (PI) and internal fault.• External alarm state (Input 5), up to 4 programmable vir-
tual alarms.
Events recording Remote turn off, local control, external signal.
Threshold and timings settings
Feature Default Setting range Setting Steps
27.S1: minimal voltage set 10,85Un
0,4s0,2Un ÷ 1Un0,05s ÷ 5s
0,05Un0,05s
27.S2: minimal voltage set 20,4Un0,2s
0Un ÷ 1Un0,05s ÷ 5s
0,05Un0,05s
59.S1: maximal voltage set 1EN 61000-4-30
1,10Un≤ 3s
1,0Un ÷ 1,20Un-
0,01Un-
59.S2: maximal voltage set 21,15Un
0,2s1,0Un ÷ 1,3Un
0,05s ÷ 1s0,01Un0,05s
81<.S1: minimal frequency set 149,5Hz
0,1s47,0Hz ÷ 50,0Hz
0,05s ÷ 5s0,1Hz0,05s
81<.S2: minimal frequency set 247,5Hz
0,1s(1) o 4s(2)47,0Hz ÷ 50,0Hz
0,05s ÷ 5s0,1Hz0,05s
81>.S1: maximal frequency set 1 50,5Hz
0,1s50,0Hz ÷ 52,0Hz
0,05s ÷ 5s0,1Hz0,05s
81>.S2: maximal frequency set 251,5Hz
0,1s(1) o 1s(2)50,0Hz ÷ 52,0Hz
0,05s ÷ 5s0,1Hz0,05s
(1) Local Mode (2) Remote Mode In according to norm the setting of the timing for 81>.S2 and 81<.S2 can onlybe modified for the remote mode the remote mode. The local is always 0.1s.
![Page 3: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/3.jpg)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513 3
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
Reading Input SpecificationsRated Inputs
System type: 1Ph, 3Ph, 3Ph+NCurrent type Galvanic insulation
by means of built-in CT’sVoltage 230VLN/400VLL
Current range (by CT) 6ATotal Harmonic Distortion (THD) ±1% FS (FS: 100%)Temperature drift ≤ 200ppm/°CFrequency sample 3200 sample/s @ 50HzMeasures See “List of the variables
that can be connected to”Method TRMS measurements of
distorted wave forms.Coupling type Direct voltage,
by means of CT’sCrest factor ≤3 (15A max. peak)Current Overloads
Continuous 6A, @ 50Hz/60HzFor 500ms 120A, @ 50Hz/60Hz
Voltage OverloadsContinuous 1.2 UnFor 500ms 2 Un
Frequency 40 to 440 HzInput impedance
400VL-L > 1.6MΩ230VL-N > 1.6MΩ5(6)A < 0.2VA
Accuracy(Display + RS485) In: 5A, Imax: 6A;(@25°C±5°C,U.R.≤60%,48..62Hz) Un: 230VLN, 400VLL
Current 0.01In ÷ 0.05In: ± (0.5% RDG +2DGT)0.05In ÷ Imax:± (0.2% RDG +2DGT)
Phase-neutral voltage ± (0.2% RDG +1DGT)Phase-phase voltage ± (0.5% RDG +1DGT)Frequency ± 0.01Hz (45 ... 65Hz)Active and Apparent power 0.01In ÷ 0.05In @PF 1: ±
(1%RDG+1DGT)0.05In ÷ Imax @PF1: ± (0.5% RDG+1 DGT)0.05In ÷ Imax @PF0.5L, 0.8C: ± (2% RDG+1 DGT)
Reactive power 0.05In a 0.1In, senϕ = 0.5L/C: ± (4%RDG+1DGT)0.1In to Imax, senϕ = 0.5L/C: ± (3%RDG+1DGT)0.05In a Imax, senϕ=1: ± (3%RDG+1DGT)0.02In ÷ 0.05In, senϕ=1: ± (4%RDG+1DGT)
Active energy Classe A in according toEN50470-3
Reactive energy Class 3 in according to EN62053-23
Start up current 5mA
Signals I/ O specification
Funzione ingressi digitali Input 1 “Remote turn off”
Terminals 30-29 o 30-36Input 2 “External signal”
Terminals 31-29 o 31-36Input 3 “Local control”
Terminals 32-29 o 32-36Input 4 “Auxiliary contact PI”
Terminals 33-29 o 33-36Input 5 “free,
in the events memory”Terminals 34-29 o 34-36
Input 6 “Power Save input”Terminals 35-29 o 35-36
Digital Inputs typeInput Voltage LO < 0,5VInput Voltage HI 2,4V ÷ 25VdcClosed contact current < 1mAMax operating freq. ≤ 20Hz with 50% duty cycle
Relay outputsOutput 1 DDI
Terminals 21-22Output 2 Backup Breaker
Terminals 23-24Output 3 Operation Ok signalling
Terminals 25-26Output 4* Backup Relay 1 (DDI)
Terminals 27-28Ouput relays type
Contact configuration SPSTContact AC1 5A @ 250VacContact AC15 1A @ 250Vac
* In case of “Power Save”operation mode,the Relay 4 is de-energized.
Interface settings table as inputs function
Operating mode configurationin “OP MODE” menù
InputsThresholdsfrequency
Timings forintervent
Input 2“External Signal”Terminals 31-29/36
Input 3“Local Control”
Terminals 32-29/36
“Loc”:Local operating mode
Not important Open Restrittive49,50kHz ÷ 50,50Hz
49,50Hz - 0,1s50,50Hz - 0,1s
Not important Close Permissive47,50kHz ÷ 51,50Hz
47,50Hz - 0,1s51,50Hz - 0,1s
“Rem”:Remote operating mode
Open Not important Restrittive49,50kHz ÷ 50,50Hz
49,50Hz - 0,1s50,50Hz - 0,1s
Close Not important Permissive47,50kHz ÷ 51,50Hz
47,50Hz - 4s51,50Hz - 1s
![Page 4: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/4.jpg)
4 Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
Serial Communication RS485Porta RS485
Type Multidrop, bidirectional(static and dynamic varia-bles).
Connection 2 fili, Half Duplex.Max distance 1000m,termination directly on instruments.
Address 247, selezionabie by front keyboard.
Protocol MODBUS/JBUS (RTU)
Dates (bidirectional)Dinamics (only reading) System variables and
phase-variables: see “List of variables measured”.
Statics (reading and writing) All configurationparameters.
Date format 1 bit for start, 8 bit for dates,no parity/parity, odd, parity1 bit for stop.
Communication speed Selectionable: 9,6k, 19,2k, 38,4k, 115,2k bit/s.
Devices in network 1/5 unit load. Max 160 device on the same network.
General specificationsOperating temperature -10 ÷ +55°C (14°F ÷ 131°F)
(U.R. 0 ÷ 90% not-condensing @ 40°C) In according to CEI 0-21
Storage temperature -30 ÷ +70°C (-22°F ÷ 158°F) (U.R. < 90% not-condensing @ 40°C)
Installation category Cat. IV (IEC60664, EN60664)Insulation According to CEI EN 60255-5
Pulse 1, 2/50µs: 5kV (CEI 0-16)Dielectric strength: >2kVACfor 1 minuteInsulation resistance:> 1000Mohm
EMCImmunity according to
CEI EN 50263 and EI EN60255-26, class B
Emissions according toCEI EN 60255-25 andCEI EN 55014-1, classe B
Protection degreeFront IP65Screw terminals IP20
Safety EN 60255-5,IEC60664, IEC61010-1EN60664, EN61010-1
Approvals CE, CEI 0-21:2012-06Connections Screw-type
Cable cross-section area Max. 2.5 mm2.Min./max. screws tightening torque: 0.4Nm/0.8Nm.
HousingDimensions (WxHxD) Module support:
96x96x82mmwith I/O modules
Max. depth behind the panel With 2 provided modules: 72mm
Material Front: ABS,Self-extinguishing: UL 94 V-0Back modules: PA66,Self-extinguishing: UL 94 V-0
Mounting Panel mountingWeight 450g
(packing included)
Power supply specificationsAuxiliary power supply H: 115 ÷ 230VCA, 48-62Hz
-20% +15%L: 24VCC
-20% +10%
Power consumptionH Standard mode 3,5W/8VAH “Power Save*” mode 2,7W/6VAL Standard mode 3,5WL “Power Save*” mode 2,7W
*Note: "Power Save" mode allows the reduction of self-consumption of PI96 in order to better achieve the autonomy of 5sfor the entire protection interface system (SPI).
![Page 5: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/5.jpg)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513 5
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
Main functionsPassword Numeric code of 4 digits.
Default Password “0000”.System selection
System 3-Ph.+N 3-Phase (4-wire)System 3-Ph 3 Phase (3-wire)System 1-Ph 1-Phase (2-wire)
Transformer ratioTA 1.0 ÷ 9999.
If the currents and/orvoltages being measured exceed their maximum limits the display shows the error message “EEEE”.
FilterOperating range Selectable fro 0 to 100%
of the input display scaleFiltering coefficient Selectable from 1 to 32Filter action Measurements, analogue
signal retransmission, serialcommunication(fundamental variables: V, A,W and their derived ones).
DisplayingNumber of variables Up to 5 variables per page.
See “Front view”. Many different set of variables available (see “Display pages”) according to the application being selected. One page is freely programmable as combination of variables.
Backlight The backlight time is programmable from 0 (always on) to 255 minutes.
Harmonic analysis THD up to the 32ndharmonics on current and voltage.Details of the individual components are available by serial communication.
AlarmsVirtual Up to 4 in memory for the
different variables measu-red.
Working mode Up alarm and down alarm.Controlled variables The alarms can be connec-
ted to any instantaneous variable available in the table “List of the variables that can be connected to”.
Set-point adjustment From 0 to 100% of the display scale
Hysteresis From 0 to full scaleMin. response time 200ms, filters excluded.
Set-point on-time delay: “0 s”.Values Reset By means of the front key-
pad. It is possible to reset the following data:- all the max and dmd values.- total energies: kWh,kvarh;- partial energies: kWh,kvarh
ClockFunctions Universal clock and calendar.Time format Hour: minutes: seconds
with selectable 24 hours orAM/PM format.
Date format Day-month-year with selectable DD-MM-YY or MM-DD-YY format.
Battery life 10 yearsEnergie measure down counting of separate
countersTotal counters + kWh to 10 digit
- kWh to 10 digit+ kVArh to 10 digit- kVArh to 10 digitHours of operation
Partial counters + kWh to 10 digit- kWh to 10 digit+ kVArh to 10 digit- kVArh to 10 digit
Insulation between inputs and outputs
Measuring inputs Relay outputs Digital InputsCommunication
ports Aux power supply
Measuring inputs - 4kV 4kV 4kV 4kV
Relay outputs 4kV - 4kV 4kV 4kV
Digital Inputs 4kV 4kV - 4kV 4kV
Communicationports
4kV 4kV 4kV - 4kV
Aux power supply 4kV 4kV 4kV 4kV -
![Page 6: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/6.jpg)
6 Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
List of variables measured
No Variables 1-Phase System1-Phase Systemwithout neutral
1-Phase Systemwith neutral
Note
1 V L-N sis O # X sis = system = ∑ (1) (2)2 V L1 X # X (1) (2)3 V L2 O # X (1) (2)4 V L3 O # X (1) (2)5 V L-L sis O X X sis = system = ∑ (1) (2)6 V L1-2 # X X (1) (2)7 V L2-3 # X X (1) (2)8 V L3-1 # X X (1) (2)9 Ani O O X10 A L1 X X X (1) (2)11 A L2 O X X (1) (2)12 A L3 O X X (1) (2)13 VA sis X X X sis = system = ∑ (1) (2)14 VA L1 X # X (1) (2)15 VA L2 O # X (1) (2)16 VA L3 O # X (1) (2)17 var sis X X X sis = system = ∑ (1) (2)18 var L1 X # X (1) (2)19 var L2 O # X (1) (2)20 var L3 O # X (1) (2)21 W sis X X X sis = system = ∑ (1) (2)22 W L1 X # X (1) (2)23 W L2 O # X (1) (2)24 W L3 O # X (1) (2)25 PF sis X # X sis = system = ∑ (1) (2)26 PF L1 X # X (1) (2)27 PF L2 O # X (1) (2)28 PF L3 O # X (1) (2)29 Hz X X X (1) (2)30 Phase seq. O X X31 Asy VLL O X X Asymmetry32 Asy VLN O O X Asymmetry33 Run hours X X X34 kWh (+) X X X Total35 kvarh (+) X X X Total36 kWh (+) X X X Partial37 kvarh (+) X X X Partial38 kWh (-) X X X Total39 kvarh (-) X X X Total40 kWh (-) X X X Partial41 kvarh (-) X X X Partial42 A L1 THD X X X (1) (2)43 A L2 THD O X X (1) (2)44 A L3 THD O X X (1) (2)45 V L1 THD X O X (1) (2)46 V L2 THD O O X (1) (2)47 V L3 THD O O X (1) (2)48 V L1-2 THD X X X (1) (2)49 V L2-3 THD O X X (1) (2)50 V L3-1 THD O X X (1) (2)
(X) available; (O) not available (variable not available on display); (#) Not available (the page is not available);(1) Max value; (2) Dmd value.
![Page 7: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/7.jpg)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513 7
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
Display, LED’s and commandsDisplay refresh time ≤ 100 msDisplay 4 lines, 4-DGT, 1 lines,
10-DGTType LCD, single colour white
backlightDigit dimensions 4-DGT: h 11 mm; 10-DGT:
h 7 mmInstantaneous variables read-out 4-DGTEnergies variables read-out Imported Total/Partial:
8+2DGT, 9+1DGT or 10DGT;Exported Total/Partial: 8+2DGT, 9+1DGT or 10DGT (with “-“ sign).
Run-hour counter 8+2 DGT (99.999.999 hours and 59 minutes max)
Overload status EEEE indication when the value being measured is exceeding the “Continuousinputs overload” (maximummeasurement capacity),
Max. and Min. indicationIstant variables 4 digits: 0,000 ÷ 9999 Energy 10 digits:
0,00 ÷ 9.999.999.999with automat scale:8+2 DGT, 9+1 DGT, 10 DGT
Key-pad Variable selection,programming of instrumentoperating parameters,readings "dmd", "max",list of inquiry interventions, reset total and partial energy.
Front position LEDsL1 59 protection trippingL2 27 protection trippingL3 81> protection trippingL4 81< protection tripping4 LED fixed Main contactor failure
(backup contactor)4 LED blinking Self Diagnosis failurekWh pulsating Flashing frequency
proportional to consump-tion of instant energy.
Back position LEDsOn the base Green as power-onOn the communication modules Two LEDs: one for TX (green)
and one for RX (amber)
1. Key-padTo program the configuration parameters and scroll thevariables on the display.
2. DisplayLCD-type with alphanumeric indications to:- display configuration parameters;- display all the measured variables.
3. Energy LEDRed LED blinking proportional to the energy being measured.Flashing frequency proportional to the consumption of instantenergy (only with TA).
4. LED di AllarmeThe alarm LED identify which type of threshold has beenexceeded:- 81<- 81>- 27- 59
5. Main bar-graphGraphical display of the percentage of power generatedcompared to the installed capacity (for instrument with currentmeasurements by CT).
Front Panel Description
![Page 8: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/8.jpg)
21 22 23 24 25 26 27 28
29 30 31 32 33 34 35 36
8 Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513
Wiring diagrams, inputs / outputs
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
25
26
27
28
21
22
23
24
OUTPUT 4AS OUTPUT 1
4 RELAY OUTPUTS
OUTPUT 1DEVICE INTERFACE
OUTPUT 2BACKUP
OUTPUT 3PI OK/FAULT
33
34
35
36
29
30
31
32
AUX CONTACT FROM INTER(for DEVICE)
POWER SAVE
REMOTE EVENT
6 DIGITAL INPUTS
REMOTE TURN OFF
COM
COM
EXTERNAL SIGNAL
LOCAL CONTROL
M F I6 R4 module
15 14 13 12 11 10
1 2 3 4 5 6 7 8 9
Terminal block layout (back view)
I/O Module
Basic Module
41 42 43 44 45 46 47 48
RS485 RS232
RS232 / RS485 Serial Communication Ports
RS232/485 Serial ComModule
ATTENTION: you have to apply on power cable the filter which isincluded in the package of the PI96.Inside the package there is a ferrite that must be used to eliminate anynoise on the digital inputs. For this purpose, you have to apply this fil-ter on power cable wire that is connected to terminal 14 or 15.
![Page 9: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/9.jpg)
AUX SUPPLY115...230VCA(opz. 24VCC)
FROMAUX SUPPLY
VOLTAGEMEASUREMENT
CONTROLINPUTS
*SEE NOTE2
CURRENTMEASUREMENT
ONLY FOR PLANTS WITH POWER IMBLANCE POSSIBILITY
FUSES:supply 115...230VCA, -20%/+15%:F=250V[T] 630mAALIM. 24VCC, -20%/+10%:F=250V[T] 3,15A
*NOTE1::FOR POWER UP TO 20kW,YOU HAVE TO APPLY A JUMPERBETWEEN TERMINALS 33 AND 36 (or 29)IN PLACE OF THE CONTACT Active Power POSITIVE DIRECTION
INPUT 4:BACKUP
for POWERUP TO Pn>20kW
I/O MODULE BASIC MODULE
TOGRID
OUPUT 1: DDI
MAX 250V5A AC1
INTERFACEDEVICE (DDI)AUX POWER
SUPPLY
GENERATION
INTERFACEDEVICE (DDI)
AUX CONTACT(for BACKUP)
*SEE NOTE1
*NOTE2:!!! WARNING !!!
!!! DANGER OF SHORT-CIRCUIT !!!ONLY FOR
THREE-PHASES SYSTEM WITHOUT NEUTRALINSTALL A JUMPER BETWEEN L3-N
14 15 10
L1
L2
L3
N
11 12 13
S1
TA1
L1 L2- + L3 N
TA2 TA3
S2 S1 S2 S1 S2
1 2 4 5 7 8
S2 S2 S2
3 6 923 2433
~
~
DDI
363531 3229 30 34
COM
EXTERNAL SIGNAL
REMOTE OFF
LOCAL CONTROL
REMOTE EVENT
POWER SAVE
OUPUT 2:BACKUP
MAX 250V5A AC1
TO BACKUPDEVICE
(for POWER UP TOPn>20kW)
21 22
DDI
VOLTAGEMEASUREMENT
CONTROL INPUTS
10 13
L1 N
FROMAUX POWER SUPPLY
DISABLEBACKUP
FUNCTION
33
AUX SUPPLY115-230VCA(opz. 24VCC)
CURRENTMEASUREMENT
DDI
OPTIONAL WIRING (not required by Norm)FOR POWER AND ENERGY MEASURES
Active PowerPOSITIVE DIRECTION
I/O MODULE BASIC MODULE
TOGRID
OUTPUT 1: DDIMAX 250V 5A AC1
INTERFACE DEVICE (DDI)AUX POWER SUPPLY
GENERATION
14 15
L1
N
S1
TA
- + S2
1 2
S2
321 22
~
~
DDI
FUSES:SUPPLY 115...230VCA, -20%/+15%:F=250V[T] 630mAALIM. 24VCC, -20%/+10%:F=250V[T] 3,15A
363531 3229 30 34
COM
SEGNALE ESTERNO
TELEDISTACCO
COMANDO LOCALE
EVENTO REMOTO
POWER SAVE
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. REV0 070513 9
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
THREE-PHASES SYSTEM 3Ph+N (4 WIRES, WITH NEUTRAL), 3Ph (3 WIRES, WITHOUT NEUTRAL)
MONO-PHASE SYSTEM 1Ph
Three-Phases System Wiring diagrams
Mono-Phase System Wiring diagrams
![Page 10: Interface protection Monitoring Relay Type PI96 In according … · 2013-07-08 · • Measurement variables AL, AN, VA, W, VAr, PF (by external CT ... Voltage Setpoint Upper](https://reader030.vdocument.in/reader030/viewer/2022021705/5b4a05427f8b9a403d8be953/html5/thumbnails/10.jpg)
96,00
96
,00
85,90
20,20 29,70 16,00 20,00
910
+1,8mm
I/O MODULE (ALWAYS INCLUDED)
Dimensions of modules
10 Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network REV0 070513
Interface protection Monitoring Relay Type PI96In according to CEI 0-21 technical norm
Dimensions and Panel cut-out
COMMUNICATION MODULE (ALWAYS INCLUDED)
I/O Module Serial Com ModuleRS232/485