introduction to power quality - fmcetfmcet.in/eee/ee2353(e)_uw.pdfintroduction to power quality ......

99
INTRODUCTION TO POWER QUALITY 1.1 INTRODUCTION This chapter reviews the power quality definition, standards, causes and effects of harmonic distortion in a power system. 1.2 DEFINITION OF ELECTRIC POWER QUALITY In recent years, there has been an increased emphasis and concern for the quality of power delivered to factories, commercial establishments, and residences. This is due to the increasing usage of harmonic-creating non linear loads such as adjustable-speed drives, switched mode power supplies, arc furnaces, electronic fluorescent lamp ballasts etc.[1]. Power quality loosely defined, as the study of powering and grounding electronic systems so as to maintain the integrity of the power supplied to the system. IEEE Standard 1159 defines power quality as [2]: The concept of powering and grounding sensitive equipment in a manner that is suitable for the operation of that equipment. In the IEEE 100 Authoritative Dictionary of IEEE Standard Terms, Power quality is defined as ([1], p. 855): The concept of powering and grounding electronic equipment in a manner that is suitable to the operation of that equipment and compatible with the premise wiring system and other connected equipment. Good power quality, however, is not easy to define because what is good power quality to a refrigerator motor may not be good enough for todays personal computers and other sensitive loads. 1.3 DESCRIPTIONS OF SOME POOR POWER QUALITY EVENTS

Upload: vandieu

Post on 11-Apr-2018

217 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

INTRODUCTION TO POWER QUALITY

1.1 INTRODUCTION

This chapter reviews the power quality definition, standards, causes and effects of

harmonic distortion in a power system.

1.2 DEFINITION OF ELECTRIC POWER QUALITY

In recent years, there has been an increased emphasis and concern for the quality of

power delivered to factories, commercial establishments, and residences. This is due to the

increasing usage of harmonic-creating non linear loads such as adjustable-speed drives, switched

mode power supplies, arc furnaces, electronic fluorescent lamp ballasts etc.[1]. Power quality

loosely defined, as the study of powering and grounding electronic systems so as to maintain the

integrity of the power supplied to the system. IEEE Standard 1159 defines power quality as [2]:

The concept of powering and grounding sensitive equipment in a manner that is suitable for the

operation of that equipment. In the IEEE 100 Authoritative Dictionary of IEEE Standard Terms,

Power quality is defined as ([1], p. 855): The concept of powering and grounding electronic

equipment in a manner that is suitable to the operation of that equipment and compatible with the

premise wiring system and other connected equipment. Good power quality, however, is not easy

to define because what is good power quality to a refrigerator motor may not be good enough for

today‟s personal computers and other sensitive loads.

1.3 DESCRIPTIONS OF SOME POOR POWER QUALITY EVENTS

Page 2: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

The following are some examples and descriptions of poor power quality “events.”

Fig. 1.1 Typical power disturbances [2].

A voltage sag/dip is a brief decrease in the r.m.s line-voltage of 10 to 90 percent of the

nominal line-voltage. The duration of a sag is 0.5 cycle to 1 minute. Common sources of sags are

Page 3: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

the starting of large induction motors and utility faults. A voltage swell is a brief increase in the r.m.s line-voltage of 110 to 180 percent of the

nominal line-voltage for duration of 0.5 cycle to 1 minute. Sources of voltage swells are line

faults and incorrect tap settings in tap changers in substations.

An impulsive transient is a brief, unidirectional variation in voltage, current, or both on a

power line. The most common causes of impulsive transients are lightning strikes, switching of

inductive loads, or switching in the power distribution system. These transients can result in

equipment shutdown or damage, if the disturbance level is high enough. The effects of transients

can be mitigated by the use of transient voltage suppressors such as Zener diodes and MOVs

(metal-oxide varistors).

An oscillatory transient is a brief, bidirectional variation in voltage, current, or both on a power

line. These can occur due to the switching of power factor correction capacitors, or transformer

ferroresonance.

An interruption is defined as a reduction in line-voltage or current to less than 10 percent of the

nominal, not exceeding 60 seconds in length. Another common power-quality event is

“notching,” which can be created by rectifiers that have finite line inductance. Voltage fluctuations are relatively small (less than 5 percent) variations in the r.m.s line-

voltage. These variations can be caused by cycloconverters, arc furnaces, and other systems that

draw current not in synchronization with the line frequency. Such fluctuations can result in

variations in the lighting intensity due to an effect known as “flicker” which is visible to the end

user.

A voltage “imbalance” is a variation in the amplitudes of three-phase voltages,

Page 4: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

relative to one another.

1.4 HARMONICS AS POWER QUALITY PROBLEM

Harmonic disturbances come generally from equipment with a non-linear voltage/current

characteristic. Nowadays a large part of industrial, commercial and domestic loads is non-linear,

making the distortion level on the low-voltage supply network a serious concern. As time goes

on, more and more equipment is being used that creates harmonics in power systems.

Conversely, more and more equipment is being used that is susceptible to malfunction due to

harmonics. Computers, communication equipment, and other power systems are all susceptible

to malfunction or loss of efficiency due to the effects of harmonics. For instance, in electric

motors, harmonic current causes AC losses in the core and copper windings. This can result in

core heating, winding heating, torque pulsations, and loss of efficiency in these motors.

Harmonics can also result in an increase in audible noise from motors and transformers and can

excite mechanical resonances in electric motors and their loads.

Harmonic voltages and currents can also cause false tripping of ground fault circuit

interrupters (GFCIs). These devices are used extensively in residences for local protection near

appliances. False triggering of GFCIs is a nuisance to the end user. Instrument and relay

transformer accuracy can be affected by harmonics, which can also cause nuisance tripping of

circuit breakers. Harmonics can affect metering as well, and may prompt both negative and

positive errors. High-frequency switching circuits such as switching power supplies, power

factor correction circuits, and adjustable-speed drives create high-frequency components that are

not at multiples of line frequency. Harmonic distortion can be considered as a sort of pollution of

the electric system which can cause problems if the sum of the harmonic currents exceeds certain

limits.

Page 5: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

1.5 HARMONICS AND THEIR CLASSIFICATION

A harmonic is defined as a component with a frequency that is an integer multiple of the

fundamental frequency. The harmonic number or harmonic order indicates the harmonic

frequency. The ratio of harmonic frequency to fundamental frequency is harmonic order.

Triplen harmonics are the harmonics whose orders are multiples of three. Zero-sequence

harmonics are also called homopolar harmonics. In a three-phase system homopolar currents are

a sum in the neutral conductor. Interharmonics are voltages or currents with a frequency that is a

non-integer multiple of the fundamental frequency. Another term is used namely, subharmonic,

which does not have any official definition. It is a particular case of an inter harmonic with a

frequency less than the fundamental frequency.

1.6 QUANTITIES DESCRIBING VOLTAGE AND CURRENT

DISTORTION

Voltage/current distortion can be characterized in either the time or the frequency

domain. Description in the time domain consists of finding the differences between the actual

distorted waveform values and the reference sinusoidal waveform values. The difficulty in

determining these differences by means of measurement causes this method of description is

seldom used. The distortion description in the frequency domain is commonly accepted.

Individual Harmonic Distortion (IHD)

It is the ratio between RMS value of individual harmonic and the rms value of the

fundamental component of a wave form.

IHDn = In

x 100 (1.1)

I1

Page 6: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

where In is the amplitude of current harmonic „n‟ and I1 is the amplitude of fundamental current .

Total Harmonic Distortion(THD)

The ratio of r.m.s. value of the sum of all the harmonic components up to a specified

order to the r.m.s. value of the fundamental component is called total harmonic distortion and

can be represented as

∞ In2

= 100 (1.2)

I12

=2

I1, I2, I3, I4,….. In, are r.m.s. values of harmonics 1,2,3,4,….n. Normally „n‟ is limited to 50. If

risk of resonance is less at higher orders then „n‟ is limited to 25.This parameter is used in low-

voltage, medium-voltage or high-voltage systems. Conventionally, current distortion parameters

are suffixed with „I‟, e.g. 35 % THDI, and voltage distortion figures with „V‟, e.g. 4 % THDV .

Peak Factor

Peak factor is the ratio of the peak value and r.m.s value of a periodic waveform, which

for a sinusoidal wave is 1.41. The logical consequence of this is that any other value means a

waveform distortion.

Crest Factor

Crest factor is the ratio of r.m.s value to average value of a wave form.

1.7 POWER QUALITY STANDARDS RELATED TO HARMONIC

DISTORTION

Page 7: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

IEEE standard 519(IEEE Std. 519-1992) was introduced in 1981and updated in 1992. It

offers recommended practices for controlling harmonics in electrical systems [1]. The IEEE has

also released IEEE Standard 1159 (IEEE Std. 1159-1995), which covers recommended methods

for measuring and monitoring power quality Standards, define recommended limits for events

that degrade power quality.

IEEE Standards 519 and 1159

IEEE Standard 519-1992 is titled “IEEE Recommended Practices and Requirements for

Harmonic Control in Electrical Power Systems.” The abstract of this standard are being used

today in industrial and commercial facilities for harmonics and reactive power control. The

standard covers limits to the various disturbances recommended to the power distribution

system. The 1992 standard is a revision of an earlier IEEE work published in 1981 covering

harmonic control. The basic themes of IEEE Standard 519 are two-fold. First, the utility has the

responsibility to produce good quality voltage sine waves. Secondly, end-use customers have the

responsibility to limit the harmonic currents their circuits draw from the line. The Table 1.1

shows the limits of individual current harmonics for a generation distribution system and the

Table 1.2 shows the limits of Voltage distortion at different voltage levels.

Table 1.1 Current distortion limits for general distribution systems[1] (120V through

69000V)

Maximum Harmonic Current Distortion(In percent of IL)

Individual Harmonic Order (Odd Harmonics)

ISC/IL <11 11≤h<17 17≤h<23 23≤h<35 35≤h TDD

Page 8: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

<20* 4.0 2.0 1.5 0.6 0.3 5.0

20<50 7.0 3.5 2.5 1.0 0.5 8.0

50<100 10.0 4.5 4.0 1.5 0.7 12.0

100<1000 12.0 5.5 5.0 2.0 1.0 15.0

>1000 15.0 7.0 6.0 2.5 1.4 20.0

Even harmonics are limited to 25% of the odd harmonic limits above.

*All power generation equipment is limited to these values of current

distortion, regardless of actual ISC/IL

Where ISC = maximum short-circuit current at PCC.

IL = maximum demand load-current (fundamental frequency component) at PCC.

h = Individual harmonic order. TDD=Total Harmonic distortion based on maximum demand load current (or) The total root-

sum-square harmonic current distortion expressed in percent of maximum demand load current.

Table 1.2 Voltage distortion limits [1]

Bus Voltage at PCC Individual Voltage Total Voltage

Distortion (%) Distortion THD (%)

69 kV and below 3.0 5.0

Page 9: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

69.001 kV through 161 kV 1.5 2.5

161.001 kV and above 1.0 1.5

1.8 SOURCES OF CURRENT HARMONICS The sources of harmonic currents and voltages in power systems can be distinguished in

to three groups of equipment.

1. Magnetic core equipment, like transformers, electric motors, generators, etc.

2. Conventional equipment, like Arc furnaces, arc welders, high-pressure discharge lamps,

etc.

3. Electronic and power electronic equipment.

1.8.1 Magnetic Core Equipment

Transformers

The magnetization curve of transformer is strongly non-linear and hence its location

within the saturation region causes distortion of the magnetizing current as shown in Fig.

1.2.These are not a significant source of harmonics under normal operating conditions. But when

the voltage is increased by even a small value and reaches saturation the magnetizing current

increases causing significant rise in harmonic content. The effects of switching transients which

propagate in the system can cause transformer saturation, sometimes over a large area.

Page 10: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Fig. 1.2 Transformer distorted magnetizing current and its harmonic spectrum.

Motors and Generators

Similar to transformers, motors will also generate harmonic currents in order to produce a

magnetic field. Their contribution, however, is very small as the motor magnetizing

characteristic, due to the presence of an air gap, is much more linear compared to the transformer

magnetization characteristic. The pitch of motor winding can also be a cause of harmonic

currents. Typical motor windings have 5–7 slots per pole, which results in the generation of the

fifth or seventh harmonic. In spite of the fact they are incomparably smaller than high harmonics

in converter equipment, their presence is noticeable in the case of very large motors. Harmonics

also occur in generator voltage, since for both practical and economic reasons a spatial

distribution of the stator windings which could guarantee a purely sinusoidal voltage waveform

is neither advisable nor possible. The induced voltages are therefore slightly distorted, and

usually the third harmonic is the dominant one. It causes the third-harmonic current flow under

Page 11: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

generator load conditions.

1.8.2 Conventional Equipment

This category includes arc furnaces, arc welders, high-pressure discharge lamps etc.

Arc Furnaces

Distortion of arc furnace currents, and in consequence also of voltages, is an important

issue because of their common usage. Moreover, for technological reasons, arc furnaces are

presently operated at a lower power factor than in the past. One of the consequences of this is the

increasing rated power of the compensating capacitors. This results in lowering the resonant

frequency. As the amplitudes of high harmonics are of significant value in this range of the

spectrum, a magnification of the supply voltage harmonics may occur. Conditions of arc

discharge changes in subsequent phases of the heating process. The highest level of current

distortion occurs during the melting phase, whereas it is much lower in the other phases (air

refining and refining). With the occurrence of a liquid metal surface a short arc occurs, the

current fluctuations are smaller and the current waveform is closer to the sinusoidal one. A

typical amplitude spectrum of the current – during melting is shown in Fig. 1.3 and the harmonic

spectrum of arc furnace current during melting and refining phases are shown in Fig. 1.4. This

spectrum exhibits the dominant harmonics with the largest amplitudes and of orders being both

even and odd multiples of the fundamental frequency: 2, 3,….. It is regular for these amplitudes

to decrease quickly with the increase in the harmonic frequency. With increasing furnace power

the voltage distortion increases, while the current distortion decreases.

Page 12: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Fig. 1.3 Time graph of a furnace current during the starting phase of melting [2].

Fig. 1.4 Harmonic spectrum of an arc furnace current (a) During melting (b)

During refining[2].

Fluorescent Lighting

Electronic lighting ballasts have become popular recently because of their improved

efficiency compared to magnetic ballasts. These devices have unfortunately a great disadvantage

because of the harmonics they generate in the supply current. Today power factor corrected types

are available in order to reduce the harmonic problems, but at a cost. In any case, smaller units

are usually uncorrected. Compact fluorescent lamps (CFLs) are now sold as replacements for

tungsten filament bulbs. In these lamps, a small electronic ballast, installed in the connector

casing, controls a folded 8 mm diameter fluorescent tube. A typical harmonic current spectrum

for these devices is shown in Fig. 1.5. These types of lamps are widely used today leading to

serious harmonic problems.

Page 13: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Fig. 1.5 The current wave form of a compact fluorescent lamp and its Harmonic spectrum [2].

1.8.3 Electronic and Power Electronic Equipment

This category includes Switched mode power supplies, Rectifiers, Static

var compensators etc.

Switched Mode Power Supplies (SMPS)

The major part of modern electronic devices is fed by switched mode power supplies

(SMPS) with single-phase rectifiers with direct controlled rectification of the supply to charge a

reservoir capacitor from which the direct current for the load is derived in order to obtain the

output voltage and current required. With this approach, the main advantage is that the size, cost

and weight have been reduced and the power unit can be made with practically any form factor.

The disadvantage introduced is that now, instead of drawing continuous current from the supply,

the unit draws pulses of current which contain large amounts of third- and higher-order harmonic

components. Fig. 1.6 shows the waveform and spectrum of a typical current for most of presently

used electrical and electronic equipment (the current of a single- phase rectifier with a capacitive

Page 14: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

filter at the DC side). It can be clearly seen that the 3rd

,5th

and 7th

harmonic values are comparable to the fundamental component value. Fig. 1.6 Voltage waveform and harmonic spectrum of the current in a diode bridge with DC side

capacitive filter (THDi=130%)[2].

Three Phase Rectifier

All equipment containing static converters, UPS units and a.c./d.c. converters in general,

are based on a three-phase bridge, also known as a six-pulse bridge because there are six voltage

pulses per cycle (one per half cycle per phase) on the d.c. output. This bridge produces current

harmonics of order 6n±1 in supply networks. In theory, the magnitude of each harmonic should

be equal to the reciprocal of the harmonic number, so there would be 20% of the 5th harmonic

and 9% of the 11th harmonic, etc. Fig. 1.7 shows an example waveform of a thyristor bridge

current against the phase voltage. Commutation notches are clearly visible in the voltage

waveform.

Page 15: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Fig. 1.7 Waveform of the supply voltage and current of a six-pulse thyristor bridge with DC side

reactor[2].

Table 1.3 Current waveforms and their THD for various types of converters [2].

Page 16: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Static VAR Compensator

For thyristor‟s control angle α= π/2 (with respect to the positive zero crossing of the

supply voltage) the phase reactor current is sinusoidal. Increasing the control angle (α > π /2) not

only reduces the current value but also causes the current discontinuity. Harmonics of odd order

occur when control angles are identical for both thyristors in the switch T. The current

Page 17: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

waveforms and their THD for various types of converters are shown in Table 1.3.

1.9 EFFECTS OF HARMONICS

The voltage/current distortion effect is determined by the sensitivity of loads and power

sources which are influenced by the distorted quantities. The least sensitive are heating

equipment of any kind. The most sensitive equipment are those electronic devices which have

been designed assuming an ideal sinusoidal fundamental frequency voltage or current

waveforms.

1.9.1 Overheating of Phase and Neutral Conductors

The presence of harmonics in the current can lead to overloading problems both on phase

conductors and on the possible neutral conductor. Under the conditions of current deformation,

heat deformation inside the cable due to the Joule effect is evidently greater and the line capacity

is reduced. The neutral conductors can be overloaded without the neutral current exceeding the

nominal phase current. This issue is particularly important in low-voltage systems where

harmonic pollution by single-phase loads is an increasingly serious problem. Triplen harmonic

currents add arithmetically in the neutral conductor rather than summing to zero as do balanced

fundamental and other harmonic currents. Therefore neutral currents will be significantly higher

than the phase currents leading to overloading. In a star-connected three-phase system, if the

loads are not balanced, a current flows in the neutral conductor as a result of the vector sum of

the three-phase currents. Also in a three-phase power system feeding linear single-phase loads,

the current in the neutral conductor is rarely zero because the load on each phase is different.

1.9.2 Skin Effect The skin effect above 350 Hz becomes significant, causing additional loss and heating.

Page 18: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

The a.c. resistance to d.c. resistance ratio is dependent on conductor radius and is dependent on the current penetration thickness ( ), which can be expressed as

= 2 (1.4)

µ

where µ is the magnetic permeability(H/m),the frequency(rad/sec); andthe

resistivity(Ωm/m2)[2].

It is evident that is dependent on the frequency; in particular it decreases as frequency

increases. For this reason in harmonic rich environment the skin effect should be accounted and

cables should be properly derated. A possible solution is also provided by multiple cable cores or

laminated busbars which can be used as an alternative way to overcome this problem. It is also

important to pay attention to the fact that the mounting systems of busbars must be designed in

order to avoid mechanical resonance at harmonic frequencies.

1.9.3 Motors and Generators

Harmonics in the current causes increase in the r.m.s. value and increase in the effective

resistance of the windings due to the skin effect causing rise in stator and rotor winding losses as

a result rise in operating temperature. In electric motors even a small harmonic voltage distortion

give rise to additional magnetic flux and hence additional currents in the rotor winding and core

causing additional active power loss, temperature rise and increases in machine failure rate.

In a synchronous machine additional losses associated with high harmonics occur mainly

in the stator windings and damping cage. Most significant are the harmonics which form a

negative-sequence system, i.e. the 5th

, 11th

, 17th

, 23rd

…… the rise of stator and rotor winding

losses results from both the increase in the r.m.s current value, due to distortion, and the increase

Page 19: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

in the effective resistance of the windings, due to the skin effect. Flux produced by rotor

harmonic currents of an induction motor interacts with air gap flux and causes additional

harmonic torques. Positive-sequence harmonics produce a forward rotating field that adds to the

torque and supports the machine rotation, whereas the other harmonics (5th

, 11th

, 17th

, 23rd

,)

have the converse effect. Harmonic torque influence the instantaneous value of the resultant

torque and results in its fluctuation.

Mechanical oscillations of electric machines, supplied with distorted voltage, attain their

maximum values when the frequency of the motor torque variations is equal or close to the

mechanical resonance frequency of the motor and driven machine set. This phenomenon can also

occur in a turbine–generator set. The presence of harmonic currents in motor windings increases

the acoustic noise emission compared to that for sinusoidal waveforms. By affecting the air gap

flux distribution, harmonics can hamper the soft start of a motor or increase its slip.

1.9.4 Transformers

The effects of harmonics on transformers manifest in three ways:

Eddy current loss increases with the square of the harmonic order in a transformer.

These additional losses may result in a much higher operating temperature and a shorter life.

Additional Load Losses

For transformers feeding non-linear loads, additional losses depend on frequency of load

current. Additional losses have no univocal dependence from frequency. In the presence of

distorted currents, additional losses may be remarkably different from the case of sinusoidal

currents. If the harmonic contents are known, additional losses can be calculated in an analytic

way using the method of superposition to calculate the contribution of the various harmonics.

Page 20: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Additional No Load Losses

Non-sinusoidal waveforms lead to additional no-load losses, mainly localized in the

magnetic circuit. A d.c. component may occur mainly in LV networks of transformer, due to the

extensive use of electronic equipment in households and industry. However, its level is normally

low but it may be sufficient to drive transformer cores into saturation which can lead to

transformer failure or the generation of extra harmonics. It can also give rise to corrosion

processes and have a detrimental effect on protective systems or other loads sensitive to current

magnitude and distortion.

1.9.5 Capacitors

The increase in peak voltage value due to high harmonics results in additional dielectric

stress in capacitors. It may cause a partial discharge in the insulation, a foil short circuit and

result in permanent damage to the capacitor. Voltage harmonics produce additional currents

flowing through the capacitor which increase with the harmonic order as a result of the reduction

in capacitor equivalent impedance ZC ≈(nωC) −1

). This may result in capacitor current overload.

An excessive current through the capacitor bank results in additional losses and, consequently,

adverse effects such as fuses blowing, physicochemical processes in the dielectric resulting in

accelerated ageing of the insulation and reduced service life, permanent damage, etc. All these

effects can be dramatically magnified by the series or parallel resonance.

1.9.6 Light Sources

The increase in the supply voltage peak value may shorten the service life of

incandescent lamps. The discharge light sources, both fluorescent and high-pressure mercury

lamps, have a series current-limiting reactor which in connection with a commonly used input

Page 21: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

parallel capacitor forms a resonant circuit. A close-to-resonance state is the source of additional

losses.

1.9.7 Nuisance Tripping of Circuit Breakers

Harmonic current distortion affects the switching capability of breakers only when

breaking small currents, and has no effect on interrupting short-circuit currents. High harmonics

may increase the current derivative di/dt value at zero crossing (compared to that of a sine wave),

which hampers the current interruption process. Residual current circuit-breakers (RCCBs)

operate by summing the current in the phase and neutral conductors and then disconnecting the

power from the load when the result is not within the defined limit. In harmonic-rich

environments, the main issue that can occur is nuisance tripping, for two reasons.

-First of all, the RCCB, which is an electromechanical device, may not sum the higher-

frequency components correctly and therefore may trip erroneously.

-The second reason is that the harmonic generating loads usually electronic equipment, also

generates switching noise that must be filtered at the equipment‟s power connection. The filters

which are normally used for this purpose have a capacitor installed between line and neutral and

ground, leaking a small current to earth. This current value is limited by standards to less than

3.5 mA, but when equipment is connected to one circuit the total leakage current can reach a

value sufficient to trip the RCCB. This situation can be easily avoided by providing more

circuits, each supplying fewer loads.

In the case of miniature circuit-breakers (MCBs) nuisance tripping is usually caused by

the current flowing in the circuit being higher than that expected from calculation or simple

measurement due to the presence of harmonic currents.

Page 22: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

1.9.8 Increase in Earth Fault Currents

In power supply systems, with an isolated or resonant-earthed neutral point, earth-fault

currents may attain intolerably high values due to distorted voltage. This phenomenon is not

observed in solidly earthed or impedance-earthed systems, because the short-circuit impedance

has a resistive–inductive character and harmonic values are limited with frequency in a natural

way. In isolated or compensated power systems the short-circuit impedance within the usual

range of voltage harmonic frequencies has a resistive–capacitive character and it decreases with

frequency. Short-circuit currents, from the capacitance to earth, due to the voltage harmonics and

interharmonics, attain the values which do not ensure self-extinction of earth-fault arcs.

1.9.9 Converters and Electronic Equipment

Converter systems as well as most electronic equipment are sensitive to various disturbances,

including harmonics. The resulting irregularities in operation are associated with the following:

1. Zero-crossing noise -When harmonics or transients are present on the supply waveforms,

the rate of change of voltage at the zero crossing may become faster and then more

difficult to identify, leading to improper operation of zero crossing detectors, because

there may be several zero crossings per half cycle.

2. In line-commutated converter control systems, synchronized with the supply voltage zero

crossing, the voltage distortion around zero may result in the inequality of the control

angles of semiconductor devices. As a consequence, the converter generates non-

characteristic harmonics, including even and triplen harmonics, interharmonics and, in

particular cases, a d.c. component. Synchronization errors may also occur in the case of

comparison of two waveforms. Improper switching of semiconductor devices into the on-

Page 23: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

state is particularly hazardous in the inverter mode of operation.

3. Component failures will occur if the maximum value of supply voltage is increased due

to harmonic distortion.

4. Disturbed operation of diagnostic and protective devices.

5. Adverse impact on capacitors in power electronics systems, in other electronic

equipment, in overvoltage protection circuits, EMC filters, etc. IT equipment, as well as

programmable logic controllers, requires the THD factor and relative value of each

harmonic present in the supply network not to exceed specified limit values. Higher

distortion levels cause incorrect operation, errors or data loss, characteristic „humming‟

of disk drives, etc. This may lead to dangerous consequences, in particular for health

services, banking, air transport, etc.

1.9.10 Measuring Instruments

Measuring instruments are most often calibrated for sinusoidal quantities, and their use

under distorted conditions can be a source of errors. The error values depend on numerous

factors, such as type of measurement, type of instrument involved, order, magnitude and phase of

given harmonic, etc. The following remarks concern several, selected instruments used in

measurements.

Increase in True R.M.S.Value

Due to harmonic pollution the true r.m.s value of measured current will be higher than

the expected one leading to a wrong estimation of current values. Average reading meters will

then provide an under-measurement of up to 40 %, which can result in potentially dangerous

conditions: for example, circuit-breakers will be underrated with the consequent risk of failure

Page 24: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

and nuisance tripping. In addition, since cable ratings are given for particular installation

conditions such as heat dissipation capability and maximum working temperature, since

harmonic-polluted currents have higher r.m.s values than that measured by an averaging meter,

cables may be underrated and consequently reach hotter temperatures than expected, resulting in

degradation of the insulation, premature failure and risk of fire.

Errors in Energy Measurements

Voltage and current harmonics in an electromechanical energy meter will produce

additional harmonic torques acting upon the disk. These torques may act in the same, or in the

opposite direction as the main torque resulting in measurement errors.

1.9.11 Relay and Contactor Protective Systems

Contactor/relay operation may differ significantly in the presence of harmonic interference. The

response not only depends on the device type and manufacturer, but also varies with each piece

of equipment tested, as well as with changes in the characteristic features of the spectrum [8].

Contactor/relay sensitivity to current or voltage harmonics decreases with the increase of

harmonic order.

1.9.12 Telecommunications Interference

There are three main factors causing interference to telecommunication lines located in the

vicinity of power system.

1. Location of harmonic sources with respect to the telecommunications circuits, and

amplitudes and frequencies of disturbing components.

Page 25: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

2. The type and level of coupling in telecommunication circuits. The mechanism of the influence of extraneous disturbing factors on telecommunication circuits

can be that due to electromagnetic or electrostatic induction, or conduction.

3. Sensitivity of telecommunications circuits to external disturbances.

The interference occurs as a result of the coincidence of these three factors. Although this type of interference is still present, it now poses a lesser problem.

1.10 CONCLUSION

Power-quality standards address limits to harmonics and power-quality events at the point of common coupling in power systems. Emphasis is given to causes

and effects of current harmonics on different power system components.

Page 26: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Voltage Sags and Interruptions

Page 27: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Introduction

•  Voltage Sag:

A short duration reduction in rms voltage caused by faults on the power system and starting of large loads, such as motors.

Page 28: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

•  Interruption:

Momentary interruptions cause a complete loss of voltage and are a common result of the actions taken by utilities to clear transient faults on their systems.

Sustained interruptions of longer than 1 min are generally due to permanent faults.

Page 29: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Solutions at end-user level

•  Aim is to improve the reliability and performance of a process or

facility.

•  Types based on application:

1.  Protection for small loads less than 5kVA.

2.  Protection for equipment/s up to 300kVA.

3.  Protection for group of loads or complete facility at low-voltage

level.

4.  Protection at medium-voltage level or on the supply system.

Page 30: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Major technologies in the area

•  Ferroresonant transformers:

These are also called as constant-voltage transformers.

1:1 transformers with excitation. Output voltage is not

significantlyaffected by input voltage variations.

Page 31: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Voltage Sag improvement with ferroresonant transformer

Page 32: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Voltage sag vs ferroresonant transformer loading

Page 33: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Magnetic Synthesizers

Similar operating principle to that of ferroresonant transformers.

These are three phase devices and provide improved

voltage sagsupport and regulation for three-phase loads.

Page 34: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Block diagram of magnec synthesizer

Page 35: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Magnec Synthesizer voltage sag ride-through capability

Page 36: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Active Series Compensators

Injects voltage in series with the remaining voltage during

voltage sagcompensation.

Can be used for small single phase loads to large loads on

the mediumvoltage system (2MVA and larger).

Voltage boosting of about 50% is possible.

Page 37: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Operation of active series compensator

Page 38: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

On-line UPS

In this method, the load is always fed through the UPS.

Provides ride-through for power outages.

Provides very high isolation of the critical load form all

power linedisturbances.

Increases losses and may be unnecessary for protection of many loads.

Page 39: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Block diagram for On-line UPS

Page 40: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Standby UPS

Also known as off-line UPS.

During disturbance, a switch transfers a load to the battery backedinverter.

From CBEMA curve, 8ms is the lower limit on interruption

throughfor power-conscious manufacturers.

Therefore, transfer time of 4ms is considered ideal for

continuity ofoperation.

Does not provide transient protection like on-line UPS.

Page 41: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Block diagram for standby UPS

Page 42: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Hybrid UPS

Page 43: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Motor-Generator Sets

Page 44: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

•  From the diagram, it is clear that the motor is supplied through

the lines and drives the generator which provides power to load.

•  When line suffers disturbance, the inertia of the machines and

the flywheels maintain power of several seconds.

•  Disadvantages:

1.  Losses associated with the machines.

2.  Noise and maintenance may be issues with some installations.

3.  The frequency and voltage drop during interruptions as the

machine slows. This might not work well with some loads.

Page 45: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Flywheel Energy Storage Systems

Unlike in motor-generator set, these flywheels operate in a

vaccumand employ magnetic bearings to reduce standby losses.

These can rotate at speeds of 10,000 rpm or higher.

Energy stored is proportional to square of speed.

This high speed flywheel energy storage module can be used

in placeof the battery in any of the UPS mentioned earlier.

Page 46: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Flywheel used in Energy Storage Systems

Page 47: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Economics of different ride-through alternatives

•  Steps for economic evaluation to find the best option for

improving voltage sag performance are:

1.  Characterize the system power quality performance.

2.  Estimate the costs associated with the power quality variations.

3.  Characterize the solution alternatives in terms of

costs and effectiveness.

4.  Perform the comparative economic analysis.

Page 48: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Estimating costs for voltage sag events

•  Costs vary according to different industry types as well as also

with market conditions.

•  Costs might be higher if the end product is already in short supply.

•  If there is limited ability to make up for the lost production.

•  Cost od a power quality disturbance can be captured primarily

through three major categories:

1.  Product-related losses.

2.  Labor-related losses.

3.  Ancillary costs such as damaged equipment and penalties.

Page 49: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

•  Cost typically vary with severity of the power quality disturbance.

•  This relationship can be defined by a matrix of weighting factors.

•  Weighting factors are developed using the cost of momentary

interruption as base.

•  Voltage sags and other power quality variations will always have

an impact that is some portion of the total shutdown caused by

interruption.

Page 50: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

•  After the weighting factors are applied to an event, the costs of the

event are expressed in per unit of the cost of a momentary interruption.

•  Sum of the weighted events is the total cost of all the events

expressed in the number of equivalent momentary interruptions.

Page 51: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Example of weighng factors for different voltage sag magnitudes

Page 52: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Example of combining weighng factors with expected voltage sag performance to determine the total cost of power quality variaons

Page 53: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Characterizing the costs and

effectiveness for Solution Alternatives

•  Solution cost should include initial procurement and installation expenses, operating and maintenance expenses, and salvage value considerations if any.

•  Cost of the extra space requirements can be incorporated as a space

rental charge and included with other annual operating expenses.

•  The following table provides an example of initial costs and operating costs for some general technologies used to improve performance for voltage sags and interruptions:

Page 54: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Example cost of different types of Power Quality Improvement Technologies

Page 55: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

•  Besides the costs, the solution effectiveness of each alternative

needs to be quantified in terms of the performance improvement

that can be achieved.

•  It varies with the severity of the power quality disturbance.

•  The relationship can be defined by a matrix of “% voltage sags

avoided” values.

Page 56: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Percentage of voltage sags or interrupons in each category that are corrected

to level that will no longer cause equipment impacts in the facility

Page 57: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Performing Comparative Economic Analysis

•  Comparing the different alternatives used to improve performance

involves determining the total annual cost of each alternative.

•  This annual cost includes the costs associated with the power

quality costs and solution costs.

•  Power quality costs is the cost incurred because of the voltage sags

since the solutions do not typically eliminate these costs completely.

•  Solution cost is the annualized costs of implementing the solution.

•  Objective is to minimize these costs.

Page 58: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

•  The base case is the do-nothing solution having zero annual

power quality solution cost but highest annual power quality costs.

•  Most of the costs are annual costs by nature but the costs

associated purchasing and installations are one-time upfront costs.

•  These can be annualized using an appropriate interest rate and

assumed lifetime or evaluation period.

•  The chart shown in the next slide is based on an example and the

matrix of the weighted factors discussed earlier. From the chart, it

will be clear that all the options reduce the total annual costs. In

other words, any of them will have a net benefit on the facility.

Page 59: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Example of comparing soluon with the base case using total annualized costs

Page 60: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

•  Even though the best solution seems

to utility side (fast transfer switch),

more applied on the facility side.

be using equipment on the

commonly the solution is

•  The major assumption with the utility side solution is that a back

up feeder is provided without any charge other that equipment

and operating costs.

•  Thus, a better solution would be using a Dynamic Voltage

Restorer for protecting sensitive loads.

Page 61: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Next Lecture:

• 

T

h

e

n

e

xt

lecture will deal with the

“Fault locating using

Voltage and Current

Measurements”.

Various methods will be dealt such as

•  Impedance-Based Fault Location Methods.

•  Locating Incipient Faults.

•  Fault Current Profile.

Page 62: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

April 2005

TRANSIENT OVERVOLTAGES ON

TRANSIENT OVERVOLTAGES ON

THET ELECTRICITYIITY SUPPLYSUPPLY

NETWORKNET – CLASSIFICATION,I,

CAUSESCAUS AND PROPAGATION This Technical Note presents an overview of the transient overvoltages

that can occur on the electricity distribution network, how they are

classified, their causes, and how they propagate through the network.

Integral Energy, your local Network Operator or the Integral Energy

Power Quality and Reliability Centre can give you additional advice if

you have particular concerns with these issues. Summary Transient overvoltages in electrical transmission and distribution networks result from the unavoidable effects of lightning strikes and network switching operations. These overvoltages have the potential to result in large financial losses each year due to damaged equipment and lost production. Transient overvoltages can be classified as being either impulsive e.g.

transients resulting from lightning strikes, or oscillatory e.g. transients

resulting from network switching. These transients move through the distribution network in different ways

depending on their frequency content. The lower frequency oscillatory

transients propagate in essentially the same way as the 50 Hz

fundamental voltage. However, impulsive transients tend to move in a

very different way which can give unexpected consequences. A full

study of their effects requires travelling wave analysis. Contents

Introduction Classification of transient overvoltages Causes of transient overvoltages Propagation through the network References and additional reading Integral Energy Power Quality and Reliability Centre

Page 63: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

1.7 Introduction Transient overvoltages in electrical transmission and distribution

networks result from the effects of lightning strikes and switching operations and are hence unavoidable. They are of very short duration (microseconds to milliseconds) and can be of large magnitude. Transient overvoltages and other power quality disturbances cause billions of dollars of losses each year worldwide due to damaged equipment and lost production [1]. They are also known as surges or spikes but will be referred to in this Technical Note by their more correct technical name of transient overvoltages.

This Technical Note will classify transient overvoltages, detail what

causes them, and explain how they travel through the distribution

network. A subsequent Technical Note (in preparation) will describe the

impact of transient overvoltages on network and customer equipment,

and suggest ways to either protect distribution networks and customer

equipment or prevent the transient overvoltage from occurring. Classification of A transient overvoltage can be defined as the response of an electrical

transient network to a sudden change in network conditions, either intended or overvoltages accidental, (e.g. a switching operation or a fault) or network stimuli (e.g.

a lightning strike). A transient is a natural part of the process by which the power system moves from one steady state condition to another. Its duration is in the range of microseconds to milliseconds.

Transient overvoltages can be classified into two broad categories:

3. Impulsive 4. Oscillatory

2.1 Impulsive An impulsive transient is a sudden, non-power frequency change in the

Transients steady state condition of the voltage and/or current waveforms that is essentially in one direction, either positive or negative, with respect to those waveforms. The most common cause of this type of transient is lightning. Figure 1 shows a typical impulsive transient (at point X) occurring on a normal voltage waveform. The magnitude of such a transient can be many times larger than the peak value of the normal voltage waveform.

Voltage

X

Time

Figure 1: A typical impulsive transient shown at point X.

1

Page 64: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Impulsive transients are usually characterised by their rise and decay times and peak value. This is illustrated in Figure 2 which is a magnification of point X in Figure 1. The vertical axis scale in Figure 2 is relative to the peak value of the transient with the zero value being at point X on the power frequency waveform in Figure 1. The rise time

(front time) T1 considered is usually calculated as 1.67 times the time T for the transient to rise from 30% to 90% of the peak value, and the

decay time (time to half value) T2 is usually the time from the virtual beginning of the transient to the time that its magnitude has fallen to 50% of the peak value [2]. The waveform shown in Figure 2 would be

called a T1/T2 waveform where T1, T2 are expressed in µs. A 1.2/50 waveform (1.2 µs front time, 50 µs time to half value) with some peak

value of Vpk (e.g. 95 kV for 11 kV systems) is often specified as a standard lightning impulse test waveform.

Voltage

Time

Figure 2: Characterisation of impulsive transient.

2.2 Oscillatory An oscillatory transient is a sudden, non-power frequency change in the Transients steady state condition of the voltage and/or current waveforms that

swings (oscillates) both positively and negatively with respect to the normal voltage waveform. The frequency of this oscillation can be quite high. Figure 3 shows a typical oscillatory transient (at point Y) occurring

on a normal voltage waveform.

Voltage Y

Time

Figure 3: A typical oscillatory transient shown at point Y.

2

Page 65: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Oscillatory transients are described by their magnitude, predominate frequency and decay time (duration). They can be subdivided into low, medium and high frequency categories.

An oscillatory transient with a primary frequency component less than 5 kHz, and duration from 0.3 ms to 50 ms, is considered a low frequency transient according to the classification given in IEEE Standard 1159-1995 [3]. This category of phenomena is frequently encountered on sub-transmission and distribution systems and is caused by several types of switching event. The most frequent event is capacitor bank energisation. Capacitor bank energisation typically results in an oscillatory voltage transient with a predominant frequency between 300 and 900 Hz and a peak magnitude between 1.3 and 1.5 times the crest voltage of the 50 Hz waveform. Oscillatory transients associated with ferroresonance and transformer energisation also fall into this category.

An oscillatory transient with a predominant frequency component between 5 and 500 kHz and a duration measured in tens of microseconds is termed a medium frequency transient. A typical example would be the transients generated by back-to-back capacitor energisation and cable switching.

Finally, oscillatory transients with a predominant frequency component greater than 500 kHz and a typical duration in microseconds are considered high frequency transients. These transients often occur when an impulsive transient excites the natural frequency of the local power system network.

3. Causes of As indicated in Section 2, transient overvoltages that occur in

transient distribution systems have two main causes: overvoltages • Lightning strikes

Network switching operations 6. Overvoltages due Lightning is an electrical discharge in the air between clouds, between

to lightning different charge centres within the same cloud, or between cloud and earth (or earthed object). Even though more discharges occur between or within clouds, there are enough strokes that terminate on the earth to cause problems to power systems and sensitive electronic equipment. When lightning strikes occur in or near an electricity distribution system, lightning currents are generated and conducted through the power system into connected equipment. Large impulsive transient overvoltages are produced as a result of this current flow.

Lightning can strike directly to the phase conductors of overhead power lines producing very high magnitude transient overvoltages. Peak current can be up to 200 kA with voltages over 1 MV. This situation usually causes power system faults that eventuate into supply interruptions and voltage sags throughout the distribution network. Lightning can also strike the overhead earth wire (shield wire) that is sometimes installed above the phase conductors to protect them from a direct lightning strike, or the tower or power pole itself. This can lead to what is known as a back-flashover to the phase conductors as the voltage on the earth wire or tower rises to become much greater than the voltage on the phase conductors.

3

Page 66: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

In addition to direct strikes, lightning can induce currents and voltages on power lines without touching them (known as an indirect strike). The large electromagnetic fields produced by lightning discharges can couple into the power network and produce induced transients. Currents produced in this manner are usually less than 2 kA with

voltages less than 100 kV.

Another situation where an impulsive type of transient can occur is where overhead conductors at a higher voltage level physically fall on to lower voltage mains, a condition sometimes called high voltage injection or intermix [4]. Initially, a wavefront will travel from the point of contact with a magnitude equal to the instantaneous difference between the voltages on the clashing conductors – this can be quite significant for the lower voltage system. This wavefront will be reflected and refracted at points of discontinuity of surge impedance in the overhead network and will quickly die out due to the losses inherent in the distribution network. See Section 4.1 for details about surge impedance and

travelling waves.

3.2 Overvoltages due Switching operations within the distribution network are a major cause to network of oscillatory transient overvoltages. Such operations include switching switching of utility capacitor banks, switching of circuit breakers to clear network

faults, and switching of distribution feeders to rearrange the network for

maintenance or construction.

Capacitor banks are installed by utilities at various locations on their transmission and distribution networks to provide reactive power for voltage support. They are switched in and out depending on the level of support needed at any one time. When a discharged capacitor is energised, the voltage of the busbar to which it is attached will momentarily collapse. This occurs because the voltage across a capacitor cannot change instantaneously. This is followed by an oscillatory recovery that usually lasts for ½ a cycle or more. The overshoot associated with this oscillation can result in a voltage that has a theoretical peak value of two times the maximum value of the 50 Hz sine wave but typically is no more than 1.5 times, as mentioned above. An example of a capacitor switching waveform is shown in Figure 4. The same effect can occur when a capacitor is switched off and a re- strike occurs (i.e. the circuit recovery voltage causes the dielectric between the switch contacts to break down and capacitor current is re- established).

Figure 4: Voltage and current transients resulting from

capacitor bank energisation [5].

4

Page 67: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Capacitor switching transients can be magnified to quite high values as they pass to a lower voltage level if certain network conditions are met. This can occur when transients originating in the medium voltage (MV) distribution network move into the low voltage (LV) network and there are power factor correction (PFC) capacitors present at LV consumers’ installations. Such a situation is given in Figure 5 which shows an

MV/LV network supplied by an MV feeder with inductance L1. A

switched capacitor C1 is connected to the MV busbar. The series combination of the outgoing MV feeder and the MV/LV transformer has

an inductance of L2. PFC capacitors C2 are connected to the LV busbar. Magnification occurs when the predominant frequency of the switching transient is approximately equal to the resonant frequency of the LV system.

MV L2 LV load

L1

C2

C1

Figure 5: Power system network conducive to magnification of

capacitor switching transients With reference to Figure 5, this situation can be represented

mathematically as:

L1C1 ≅ L2C2

where L1 = system source inductance seen from MV

busbar C1 = capacitance of switched capacitor L2 = inductance of step-down transformer

and associated MV feeder C2 = capacitance of LV PFC capacitor

In practice, voltage magnification can occur over a wide range of step-

down transformer and PFC capacitor sizes, and can lead to peak

voltages on the end-user busbar up to 4 times the normal 50 Hz crest

voltage. Apart from capacitor switching, oscillatory transient overvoltages can occur when circuit breakers clear faults on the distribution network. Waveforms associated with such a situation are shown in Figure 6. During time period ‘a’, fault current is flowing (arcing) between the circuit breaker contacts as they are opening, the arc voltage increasing in magnitude as they move further apart. Time period ‘b’ commences when the current reaches zero value and the gap between the contacts is sufficiently large that it will withstand the transient recovery voltage (TRV) imposed on it by the network. The predominant frequency of this TRV is determined by the system inductance and capacitance seen from the circuit breaker terminals looking upstream into the network. This frequency can be tens of kHz and the peak voltage can be up to twice the normal 50 Hz crest voltage. The situation is made worse if the circuit breaker controls an overhead feeder and it is allowed to perform reclose operations to restore supply and/or help clear faults. In this

5

Page 68: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

case, the oscillatory transient could be applied to the distribution

network up to 4 times in under one minute.

a b

Figure 6: Typical oscillatory transient resulting from clearing of network

faults [6]. 4. Propagation The propagation of transient overvoltages through the distribution

through the network will depend on their frequency content. Consequently, the network propagation of impulsive and very high frequency oscillatory transients

will be far more influenced by the stray and distributed inductance and capacitance of the distribution system than low frequency oscillatory transients.

4.1 Impulsive and very These types of transient move through the distribution network as

high frequency travelling waves of current and voltage. There can be waves travelling oscillatory near the speed of light in both directions simultaneously away from the transients source of the disturbance. This is illustrated in Figure 7 for a lightning

strike. For waves travelling in each direction, current and voltage are related to each other by the surge impedance Z0 of the distribution network. Z0 is purely resistive so voltage and current waveforms have the same shape.

Z0 can be calculated from the distributed inductance L and distributed capacitance C of the distribution feeder as follows:

Z0 = CL , Ω

Typical values of Z0 for overhead lines range from 300 to 500 ȍ and for

cables from 30 to 60 ȍ.

Wave velocity is:

v = 1

, m/s

LC

For overhead lines, v is near the speed of light (3x108 m/s). For

underground cables, it is typically between one half to two thirds of this value.

6

Page 69: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

i

Uv Travelling

i/2 i/2 waves

Iv

Z0 Z0

Figure 7: Travelling waves due to a lightning strike. As travelling current and voltage waves move through the distribution network, they will meet points of discontinuity where the surge impedance changes. Such points include open ends, overhead-underground connections, transformers, etc. At such points, these travelling waves are both reflected back towards their origin and transmitted onwards with magnitudes that depend on the relative values of the surge impedances involved. For even a relatively small distribution network, this can lead to the establishment of a very complex system of travelling waves which add and subtract possibly producing quite high voltages at some sites. Fortunately these travelling waves rapidly decay as they spread out from their point of origin due to the losses associated with the distribution network and its connected loads.

A final point to note is that network components and connected equipment respond differently to impulsive and very high frequency oscillatory transients than to the normal 50 Hz mains voltage. Reactors and transformers will look capacitive and capacitors will look inductive to such transients due to lead inductances and stray capacitances. To a

first approximation these effects can be modelled using discrete element circuits. Typical high frequency transient models are illustrated below:

Capacitor:

RL is lead resistance.

RD

L is lead inductance (of the

order of µH).

RD represents dielectric

RL L C

loss (responsible for

capacitor heating at higher

frequencies).

C is the capacitance of the

capacitor.

Reactor:

R L

C

R is winding resistance. C is the combined effect of inter-turn capacitance and capacitance to earth (of the order of nF). L is the inductance of the reactor.

7

Page 70: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Transformer (single-phase equivalent with losses ignored):

Cps

Cpg is the effective

capacitance of the

primary winding to

Lp Ls earth.

Cps is the effective

Cpg L

m C

sg inter-winding

capacitance.

Csg is the effective

n:1

capacitance of the

secondary winding to

earth.

Capacitances are of

the order of nF.

Lp and Ls are the primary and secondary winding leakage inductances,

respectively. Lm is the magnetising inductance of the transformer (usually ignored because of its relatively large size). At high frequencies, the distributed capacitances of the transformer dominate the turns ratio and hence they determine the magnitude of the transient that passes through the transformer.

4.2 Low frequency These transients are typically due to utility capacitor switching and have

oscillatory maximum frequency components less than 2 kHz. As such, they transients propagate through the network in essentially the same way as the 50 Hz

fundamental voltage, passing through step-down transformers according to the turns ratio with little attenuation [7]. Discrete element circuit analysis can thus be used to study them.

5. References and [1] D. Chapman, “The Cost of Poor Power Quality”, Power Quality

additional reading Application Guide, Section 2.1, Copper Development Association of

UK, November 2001.

[2] AS 1931.1-1996, “High-voltage test techniques – Part 1:

General definitions and test requirements”.

[3] IEEE Standard 1159-1995, “Recommended practice on

monitoring electric power”.

[4] V. Smith and V. Gosbell, “Theoretical investigation of accidental contact between distribution lines of dissimilar voltage”, AUPEC

2004, Brisbane, Sept. 2004.

[5] BMI, “Handbook of Power Signatures”, 2nd edition, 1993.

[6] A. Greenwood, “Electrical transients in power systems”, 2nd

edition, Wiley-Interscience, 1991.

[7] AS/NZS 61000.4.7:1999, “Electromagnetic compatibility (EMC) – Part 4.7: Testing and measurement techniques – General guide on harmonics and interharmonics measurements and instrumentation,

for power supply systems and equipment connected thereto”.

[8] R. Dugan et al, “Electrical power systems quality”, 2nd edition, McGraw-Hill, 2002.

8

Page 71: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

6. Integral Energy In July 1996, Integral Energy set up Australia’s first Power Quality Power

Quality and Centre at the University of Wollongong. As of July 2004, the Centre

Reliability Centre adopted its present name indicating a shift in emphasis to include reliability of supply. The Centre’s objective is to work with industry to improve the quality and reliability of the electricity supply to industrial, commercial and domestic users. The Centre specialises in research into the monitoring, assessment and control of network and other disturbances affecting the quality of voltage supply, providing input to national and international standards bodies, training in power quality and reliability issues at all levels, and specialised consultancy services for solution of power quality and reliability problems. You are invited to contact the Centre if you would like further advice on quality of supply.

ABOUT THE AUTHORS Vic Smith is the Research Engineer with the Integral Energy Power Quality and Reliability Centre.

Venthanar Ilango (recently deceased) was a Professional Officer in the

School of Electrical, Computer and Telecommunications Engineering at

the University of Wollongong.

Sarath Perera is the Technical Director of the Integral Energy Power Quality and Reliability Centre and a Senior Lecturer in the School of Electrical, Computer and Telecommunications Engineering at the University of Wollongong.

Vic Gosbell is Professor of Power Engineering in the School of Electrical, Computer and Telecommunications Engineering at the University of Wollongong and is Technical Advisor to the Integral Energy Power Quality and Reliability Centre.

Duane Robinson is a Senior Lecturer in the School of Electrical,

Computer and Telecommunications Engineering at the University of

Wollongong. The Integral Energy Power Quality and Reliability Centre

sponsors his position.

Page 72: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

2

Power-quality Monitoring

2.1 Introduction Instrumentation for the measurement of conducted disturbances in power systems

has undergone great development during the last decade. From the first

instrumentation designed for general-purpose measurements, up to the current

highly improved transients recorders, this kind of device has continuously evolved,

becoming increasingly more specialised. In addition to the evolution of the

hardware, there has also been significant activity in all topics related to the

development of software for the analysis of measurements. In fact, managing

records of power-quality (PQ) events is a problem that is growing day by day.

Power-quality (PQ) monitoring should consider some basic questions:

When to monitor. It is easy to program a power-quality survey after a

problem has appeared. The difficulty lies in being able to do that before the

problem arises, using a predictive approach.

Where to connect. A correct choice of the instrumentation location in the

power system is essential in order to draw valid conclusions. What instrument should be used. The choice between hand-held, portable

or fixed equipment has to be made as a function of the time the instrument

has to measure, the number of channels and the kind of disturbances we are

looking for. What magnitudes should be measured. Sometimes a general survey has to

be done, so all the power-quality indices have to be measured. In other

cases, we are only interested in specific parameters. How to postprocess the registered data. After the measurement has been

done, raw data and events have to be analysed in order to obtain

conclusions.

Page 73: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

16 2.2 State-of-the-art In the spring of 1989 the European Union published the Directive 89/338/CEE

[1,2], which started the countdown for the application of harmonized regulations

relative to electromagnetic compatibility in the European Union. Currently, the

regulatory process has still not finished, but there is an extensive set of standards

that covers almost all aspects of electromagnetic compatibility (EMC) regulations.

It is obvious that EMC is an up -to-date topic, and not only for political reasons.

The spectacular growth that has occurred during the last two decades in the

utilization of power electronics in almost all kinds of electronic devices has given

rise to an increase in the distortion of the distribution network. This growth in the

number of electronic devices has not been accompanied, in many cases, by an

improvement in the quality of the electronic designs. What is worse, most of them

are extremely sensitive to the existing disturbances in the distribution network, so

they exhibit malfunction during their operation under disturbed networks. These

and other reasons are the motivation behind active research work on PQ

instrumentation. 2.2.1 Historical Background Two decades ago, the available instrumentation for power-quality assessment did

not exist, and at best, they had a general purpose like oscilloscopes or spectrum

analysers. The use of general-purpose instruments provided raw data that had to be

postprocessed in order to obtain any conclusion. In other cases, the engineers and

technicians were equipped with real root mean square (rms) voltmeters and

ammeters, so the analysis used to be a difficult task only available to experts.

The existing instrumentation that can be utilized for power-quality evaluation

could be classified into two sets according to their degree of specialization:

1.8 General-purpose instrumentation. 1.9 Specific-purpose instrumentation.

2.2.2 General-purpose Instrumentation Basically, general-purpose instrumentation includes oscilloscopes and spectrum

analysers. Spectrum analysers can be also divided according to the procedure of

analysis:

Digital signal analysers. These utilize the fast Fourier transform (FFT) or

similar techniques to compute the spectrum of the signal.

Analog signal analysers. These are based on parallel banks of analog filters

than can be tuned in order to obtain the value of the spectrum components.

Page 74: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 17

The analysers that use the FFT have standardized features, and in commercial

format they are provided with bandwidths from 0 Hz up to 20, 100 and even 200

kHz. These equipments usually have 1 or 2 input channels, though some of them

can have 4, 8 or 16: it being possible to carry out graphical representations of the

signals in both time and frequency domains. Another characteristic to evaluate, in

this type of meter, is the possibility of doing zooms of specific ranges of the

spectrum of the signals. In many cases, it is also possible to use different

windowing (rectangular, triangular, etc.) during the sampling process.

The analysers based on parallel banks of filters were, historically, the first ones

to appear. The basic principle behind them is quite simple. A set of analogical

bandpass filters divide the spectrum into bands whose union makes it possible to

reconstruct the spectrum of the original signal. The main drawbacks are the cost

and the complexity, reasons for which their use is reduced to applications of very

high accuracy in which cost is a secondary factor. The bandwidth of these

analysers is in the 100 kHz range, and they are capable of achieving resolutions of

1 Hz.

Whatever the structure of the meter, it is important to be able to have offline

access to the measured information, in order to postprocess the measured data. The

majority of the systems that use the FFT provide an output of information in RS232

or IEEE-488 format, with the possibility of programming the instrumentation

externally, and to do some type of remote control. Nowadays, many of them also

have an ethernet interface, so that they can be connected to a local area network or

The internet.

Another important feature is the number of different windows that can be used

with them in the process of sampling, usually between 2 and 12. The resolution of

the analog-to-digital converter (ADC) is another parameter that changes from one

device to another. The majority have between 12 and 16 bits, though many of the

existing oscilloscopes have only 8 bits.

With regard to the possibility of analysing interharmonics, some

instrumentation devices provide up to 3200 spectral lines free of aliasing and

distortions in a bandwidth of 128 kHz. Working in real time, the bandwidths allow

the majority of the equipments to go beyond 10 kHz. 2.2.3 Specialised-purpose Instrumentation Two decades ago the instrumentation to monitor power quality was only a

prototype that one could find in some research laboratories. Today, there is a

competitive market.

Table 2.1 summarizes the most important features of the instrumentation

designed specifically for power-quality measuring. Also included here are the

characteristics of an open platform named MEPERT that has been developed at the

Page 75: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

18 Electrical Engineering Department of the University of Cantabria [3–5]. MEPERT

is shown in Figure 2.1.

Table 2.1. Typical parameters of a power-quality meter

Type of application Hand-held Portable Fixed installation

User interface Alphanumeric Graphic Oscilloscope Text Blackbox

Measured parameters DC voltage and current Harmonics and interharmonics Ground resistivity Power factor Flicker Power / energy Transients (> 200 µs) Impulses (< 200 µs) Dips Overvoltages Imbalance Frequency Other disturbances

Type of meter Trends Energy Spectrum analyser Transients recorder

Type of communication RS-232 Ethernet TCP/IP Modem Power-line communication Other

In general, this type of system makes it possible to carry out the evaluation of

any type of conducted disturbance: variations of the nominal frequency of the

supply, variations in the magnitude of the voltage supply, transients, flicker,

imbalance, harmonics, interharmonics, dips and interruptions as defined by the

standard EN 50160 [6]. In many cases they have, in addition, specialized software

able to analyse the stored measurements [7,8].

In 1990, the Electric Power Research Institute (EPRI), which is the organization

that coordinates the research on electrical systems in the USA, had already

established projects with Electrotek Concepts for the development of an integral

software for disturbances analysis [9].

Page 76: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 19

Figure 2.1. PQ meter open platform designed at the Department of Electrical Engineering,

University of Cantabria

In the above-mentioned project, an instrumentation developed by BMI was in

use. Power-quality surveys are not new. In fact, there are references [10,11] from

1993 that summarize the state of the distribution network in the eastern part of the

USA.

Since the beginning of the 1990s, it has been possible to find commercial

power-quality meters that do not limit their analysis to harmonics. This study

includes more than 5400 points/month of information over two years. The

implemented software was designed at Electrotek Concepts by a research team led

by E. Gunther.

Nevertheless, and in spite of the fact that there exist documents that specify the

requirements for the measurement of harmonics and interharmonics (IEC 61000-4-

7) [12], flicker (IEC 61000-4-15) [13], and some other disturbances, there is still no

document that draws together all the aspects and specifications necessary for the

development of a global power-quality meter. Figure 2.2 includes the results

obtained from the comparison of a set of commercial power-quality meters from

different manufacturers [5].

From the point of view of the available communications, it is possible to say

that in the 50% of the cases the remote management of the instrumentation is

implemented by means of modems. The remaining 50% is distributed in almost

equal parts between one native ethernet interface and TCP/IP.

Page 77: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

20

PORTABLE 21% ALFANUMERIC

36%

37% 31%

HAND-HELD

GRAPHIC

OSCILLOSCOPE

FIXED 0% PAPER

INSTALLATION 27% 0%

48% BLACK BOX

(a) (b)

DISTURBANCES

6% 2% 4%

MODEM

25% ETHERNET

TRENDS

33%

TCP_IP

ENERGY

50%

SPECTRUM

55%

TRANSIENTS

25%

(c) (d)

Figure 2.2. Classification of commercial PQ meters by different criteria. (a) Type of meter;

(b) Type of user’s interface; (c) Type of measurements; (d) Type of communication

interface

2.3 Instrumentation Architecture The voltages and currents to be measured can be accessible directly or indirectly in

the case of LV and MV/HV systems, respectively. EURELECTRIC [14]

established a basic architecture of the measuring system that is shown in Figure

2.3.

The term instrumentation spans, theoretically, Vs to Ge, though in general it is

assumed that a power-quality meter includes all the elements from Vm to Ge. This

means that the measuring transformers can be considered as an independent

system.

This dichotomy of the measuring system can be also observed in the standards,

which define specific documents for the instrument transformers and the rest of the

electronic system. In addition, Figure 2.4 shows the basic architecture of a power-

quality meter.

Page 78: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 21

Vg (Power system Vm (input

magnitudes) magnitudes)

Instrumentation Measurement

transformer unit

Gm (measured

magnitudes)

Post-processing

unit

Ge (postprocessed magnitudes)

Figure 2.3. Main elements of a PQ instrumentation system

V/I signals from

the transducers

Signal Analog-to-digital Digital signal

conditioning

converter processing

Control Data storage and

subsystem management

Communication Postprocessing

module

Figure 2.4. Basic architecture of a power quality-meter

2.3.1 Safety Use of PQ Instrumentation The safety of both the operators and the instrumentation used in the measurement

of electrical magnitudes is an aspect that is considered to be an annex to the

intrinsic problem of measurement, since in general it is transparent to the user. It

seems to be evident that if a manufacturer wants to sell an instrument to monitor

the evolution of the rms value of an intensity up to a maximum value of 100 A, the

equipment will be capable of supporting at the very least the above-mentioned

intensity without suffering any type of damage or malfunction either transitorily or

permanently. This type of guarantee is, in many cases, obvious for the users, but

perhaps not so much for the designers and manufacturers of the instrument, who

must submit the designs to a series of tests that guarantee their safety.

Page 79: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

22

The measure of voltages and currents with portable equipment constitutes

generally risky work, so that it is necessary to reduce or to eliminate any situation

of potential risk for the user, the instrumentation or the installation. In many cases

the problem can be worse, because there could appear overvoltages or overcurrents

that go over and above the nominal values established by the standards, so that it is

necessary to introduce additional measures of protection. In order to guarantee the

safety of persons and equipment, there exist some regulations that must be

followed when the instrument is acquired.

The equipment must indicate clearly the maximum voltage for every type of

measurement (DC or AC). In addition, the test points must also indicate the

maximum voltage that they support, since, in general, they are not permanently

connected to the instrumentation, and therefore, they can be exchanged by others of

different characteristics. The equipments have, in general, protection fuses, which

will have to clearly indicate the maximum current and the performance speed.

The probes must be suitably isolated, and at the same time the connections with

the instrumentation must assure the separation of parts under voltage. If it is

necessary to replace some internal element such as fuses or batteries, it will be

necessary to give clear warning of the obligation to disconnect the equipment from

parts with voltage.

All the previous points must be taken into account for designers and users, who

must not forget the existence of regulations relative to safety in equipment. The

basic sources of information are: European Union (CENELEC), specific regional

Procedure of Canada (CSA), United Kingdom (UL), Germany (VDE), Spain

(UNESA) or Switzerland (GS) just to mention some, and that must be certified in

order to be sold in the above-mentioned countries; in the case of the European

Union, the equipments have to bear the mark CE.

As an example, the standard IEC 61010-1 [15] relative to the safety

requirements for electrical equipment for measuring, controlling or use in a

laboratory establishes a classification according to different criteria, based on the

type of isolation:

5. Basic, which refers to equipment whose parts under voltage, in normal

working conditions, have levels below 30 rms volts, 42.4 peak volts or 60

DC volts.

6. Double, for all other equipment, or those that are not connected to ground.

Page 80: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 23 2.3.2 Number of Channels From the point of view of instrumentation design, one of the most important

aspects to consider is related to the input channels. First, it is necessary to establish

the number of channels. Due to economic criteria, the choice of the number of

channels is based on a specification of minimal needs. Figure 2.5 establishes a

criterion for the classification of the number of measuring channels according to

the application.

Number of channels

selection

Single-phase system

Three-phase systems

1 V Product assessment

Load assessment

1 I

V (EN 50160)

V and I

3 V

LV/MV HV measurement

measurement

3 V

USA

EUROPE 3 I

4 V 3 V

5 I 4 I

Figure 2.5. Diagram for number and type of input channels

One of the most interesting aspects of the structure shown in Figure 2.5 focuses

on the difference in measurement needs on low voltage networks between USA

and Europe. The distribution networks in USA are based on the connection of

single -phase loads or unbalanced three-phase loads, principally in an open triangle

form, which originates the need to control the current of the neutral. In addition, it

is quite common for the distribution in medium voltage also to be based on four

wires. On the other hand, in Europe, the distribution is based on three-wire

systems. This means that if there is any current flowing to ground it can be

considered a fault.

In the USA, it is quite usual to install the protection wire, so it is necessary to

monitor the voltage between neutral and ground in order to detect certain faults.

The measurement of this voltage requires a channel with a very small range of

measurement. In Europe, it is normal to meet systems of isolated neutral or neutral

connected to ground by means of a high impedance, which is why the

Page 81: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

24 measurement of these voltages and the associated current to ground is not

important in many cases.

Voltage measurement can be classified according to two different approaches:

common unified and independent channels. 2.3.3 Common Unified Channels In this type of measurement, all voltage channels have the same reference. From a

practical point of view they are characterized by having N+1 measurement wires

for the monitored voltage, with N being the number of channels. It is a

measurement system quite commonly used at present, especially in the USA,

where the distribution systems have the neutral conductor connected to ground.

This structure is valid only for distribution systems with a neutral conductor. In

some cases, if the neutral conductor is not accessible, an artificial one is created.

Nevertheless, the utilization of an artificial neutral for the measurement of phase to

neutral voltages is subjected to the hypothesis of having a symmetrical voltage.

Figure 2.6 shows a three-phase system where only points A, B and C are

accessible. To be able to measure the phase to neutral voltages, a high-impedance

wye -balanced three-phase load is used, which does not modify the network.

A

B

Ia

N LOAD

Ib

C

Ic

R R R

N’

Figure 2.6. Equivalent circuit of virtual wye load for phase to neutral measurements

If the three-phase system, the voltages for which we are trying to measure, is

balanced, the point N is equal to N’ and then the neutral point of the fictitious load

does not suffer any displacement with regard to the neutral of the generating

system or, in other words, the phase voltages are the distribution network voltages.

If the voltages to be measured constitute an unbalanced three-phase system, the

measured phase voltages are different from the distribution -network phase

voltages. In this case, infinite solutions can be found for the phase voltages, thus it

is not possible to measure the real ones.

Page 82: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 25

Since, in general, it is not possible to establish whether a distribution network is

balanced from the measurement of the phase to phase voltages, the conclusions

obtained from these kinds of measurements must be avoided. 2.3.4 Independent Input Channels This type of input-channel arrangement constitutes the most widely used

architecture. From a practical point of view it also enables the unification of all the

input-channel references. In a general case, completely independent measurements

can be done without additional elements. The latter possibility can be really

interesting in cases in which different voltages without common references have to

be monitored, since it can be the case of different measurement points in

substations (e.g. different potential transformers). 2.3.5 Transducers The aim of transducers is to provide a small voltage signal (with typical amplitudes

between –10 and 10 V), which are proportional to the levels of voltage and current

that have to be measured. In general, a correct utilization of the transducers means

that their frequency response has to be completely characterised, both in magnitude

and phase.

Although according to EURELECTRIC [14], voltage and current transducers

are physically independent from the instrumentation, it is very important to have a

good understanding of the basic criteria for their correct selection and utilization.

An appropriate selection of current transducers has to take into consideration,

among others, the following features: nominal values, geometry, maximum value,

accuracy, range of frequencies to measure, etc.

There are some different technologies available for current measurement. Table

2.2 summarizes a comparison between current transducers for low-voltage usage.

Potential transformers (PT) usually have an accuracy greater than 1% between

40 Hz and 1500 kHz. At MV and HV the capacitive effects become more

dominant. From a practical point of view, the accuracy itself is not as important as

their linearity. This is because voltage harmonics are computed as a percentage of

fundamental, and not as absolute, values. The phase displacement in that range is

typically over 40 minutes or more.

On the other hand, current transformers (CT) have an accuracy of over ±0.5%

for frequencies from 20 to 1000 Hz. The performance at 1 kHz starts to decrease

and the maximum bandwidth is about 10 kHz.

Independently of the kind of current transducer being used, all of them have a

set of common parameters that have to be understood. Figure 2.7 shows the

equivalent electric circuit for a generic current transducer.

Page 83: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

26

Table 2.2. Current transducer comparison Input Over-range Accuracy Sensitivity Bandwidth Security

Range Capacity

Resistive + + ++++ ++++ ++++ +

Shunt DC-100 MHz No

Inductive ++++ +++ ++ isolation

++ ++ +++

±0.5% 20 Hz–1 kHz Single

0.5º isolation

Hall effect ++++ +++ + ++ +++ ++++

±1% 1.5-3.0 DC–50 kHz Double

1.5º V/FSA isolation

Rogowski ++++ +++ + + +++ ++++

Coil ±1% 0.2 1 Hz–10 MHz Double

1.5º V/FSA isolation

Optical +++++ +++++ ++ + ++++ +++++

Double

isolation

Ip

rt

Is G

Rb Vs Vo

Figure 2.7. Equivalent circuit of a generic current transducer

The circuit shown in Figure 2.7 allows us to obtain the relation between the

current Ip that has to be measured and the proportional output voltage Vo,

I p = Vo rt

(2.1) GRp

where,

Ip is the current to be measured,

Vs is the voltage before the amplifier,

Vo is the output voltage,

G is the amplifier gain.

Page 84: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 27

From the point of view of the user of the instrumentation, the most important

aspects are: transformation ratio, measurement range, bandwidth and geometric

dimensions. The manufacturer is required to provide the curves of magnitude and

phase versus frequency. In [16 -18] some procedures are commented on in order to

accomplish the contrast of PQ meters and transducers. Figure 2.8 shows the Fluke

6100A, which is a commercial test system that can be used for instrumentation and

current transducer tests.

One of the problems that is still not completely solved in the design of

instrumentation for power-quality measurements in high-voltage systems is the

direct measurement of voltage and current, especially when transitory phenomena

have to be registered.

Classical instrument transformers include both current transformer (CTs) and

potential or voltage transformers (VTs). These kinds of devices are designed for 50

or 60 Hz, so their behaviour at high frequency could exhibit nonlinearities and

other unwanted effects.

Figure 2.8. PQ meters and transducers test and calibration unit Fluke 6100A

One of the solutions to this problem can be the utilization of optical

transducers. In the early stages, optical elements were introduced only in the signal

transmission between the classical transducer and the instrumentation. In recent

years, much effort has been made towards the design of totally optical transducers

[19].

In formal terms, the current that is passing through a conductor can be

expressed as the integral of the magnetic field in a closed path that includes the

conductor. This is,

I p = Hdl (2.2) where,

Page 85: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

28

I p is the current to be measured, H is the magnetic field, dl is the closed path of integration.

The previous equation serves as a background for the design and manufacturing

of the classic transducers that are used nowadays, and it also, certainly, constitutes

the theoretical basis for optical transducers.

In a basic form, optical transducers are physical devices that modify some of

the properties of the light that travels through them, because they have been

immersed in a magnetic field, the intensity of which changes with time. One of the

most used phenomena is named the “Faraday’s effect” or the “magneto-optic

effect” in the technical literature.

To understand the mechanism that gives rise to this effect, it is necessary to

know that a beam of light with an arbitrary polarization can be expressed as a

combination of two orthogonal components polarized linearly, or as a combination

of two orthogonal components circularly polarized. An analogy can be established

between these circular basic elements and the components of positive and negative

sequence in a three-phase system.

Magnetic field lines

Ip

conductor

Light source Polarimeter Polarimeter Light detector

Optical L

Faraday D

element sensor

Polarization

state

Figure 2.9. Structure of a current transducer based on the Faraday effect

The Faraday effect is, basically, a process of optical modulation, that is, a

process of rotation of the plane of polarization of a beam of light polarized linearly,

and proportional to the magnetic field that is passing through the material. The

variation between the angle of rotation and the intensity that flows through the

conductor is a constant named Verdet’s constant. The law that defines the angle of

rotation is,

θ = µrν ∫H.dl (2.3)

Page 86: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 29 where,

θ is the rotation that the light beam component undergoes when it passes through

the material, µr is the relative permeability of the medium, 7. is Verdet’s constant.

The following problem to solve is rooted in the fact that it is difficult to

measure the degree of polarization of the light directly, hence it is necessary to

perform a previous transformation of the degree of polarization of the light in

optical power (square of the field E). This transformation is done by means of a

light polarimeter. Figure 2.9 shows the block diagram of a Faraday-effect sensor.

The measure of the intensity is computed as a ratio between the input and output

optical power.

There are also optical voltage transformers. These are based on an electro-

optical effect that produces a rotation of the polarization plane.

As a conclusion, it can be said that optical sensors for current measurement are

small, accurate and do not suffer from the isolation problems, lack of accuracy and

poor frequency response of the classic transformers. Nevertheless, they have not

led, at least at present, to a reduction in volume compared with the conventional

instrument transformer, since the electrical companies demand elements similar to

the classical ones, in order to be able to replace them without mechanical changes. 2.3.6 Signal-conditioning Module The signal-conditioning module acts as an interface between the transducers and

the analog- to-digital converter. It can be seen as a glue element between the

analog and digital worlds. Their main objectives can be summarized as follows:

4. To provide galvanic isolation between the power system and the user of the

instrumentation.

5. To amplify and/or to attenuate adequately the voltage or current signals in

order to obtain the maximum dynamic signal range, guaranteeing in this

way a high signal-to-noise ratio.

6. To avoid aliasing problem by means of low-frequency filters.

Figure 2.10 shows a block diagram of this module, where the described

elements can be seen.

Page 87: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

30

V/I signals from

the transducers To the data

Programmable

Isolation amplifier adquisition module

Antialiasing

Amplification /

Controlled gain filter

attenuation

Control

subsystem

Figure 2.10. Diagram block of the signal-conditioning module 2.3.7 Analog-to-digital Converter The analog-to-digital converter (ADC) is the module that has the responsibility of

translating the signal from the analog to the digital domain. It carries out two basic

tasks [20]:

• i) Signal discretization. This is the process of periodic sampling of the

signal using the Nyquist–Shannon theorem [21]. It allows us to obtain a

sequence of samples x[n] obtained from a continuous-time signal x(t).

• ii) Signal quantization. This is a mathematical transformation that assigns a

fixed-point binary number to a sampled signal value that belongs to the real

numbers.

The resolution of analog-to -digital converters in power- quality

instrumentation has values between 8 and 24 bits. Other values can also be found,

but are not typical.

From a numerical point of view, quantification is a nonlinear transformation

that produces an error. The error range depends on the number of bits of the ADC

and the input range. 2.3.8 Signal-processing Module The signal-processing module is the core of the instrumentation. It includes the

task manager, which controls the device and the set of algorithms that compute the

power-quality indexes, the file manager and the communication facilities. The

main features of this module are:

• Reprogrammed firmware. This characteristic allows us to programme and

to reschedule the functionality of the system without hardware

modification, which reduces the development costs enormously. For

instance, a system can be updated to measure harmonics with different

Page 88: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

algorithms or standards without changing the hardware.

Page 89: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 31

• System stability. This involves repeatability of the implementation and of

the response. It is easy to understand that a digital system provides the

same answer to the same question. This is not so with analog systems,

where the response is a function of the temperature, age, humidity, etc. • Suitable for implementing adaptive algorithms and special functions such

as linear phase filters. The utilization of numerical algorithms allows

external errors due to changes in the operating conditions to be corrected

dynamically. • Able to compress and store measurement data. It is not necessary to

highlight here the importance of computers in the storage, treatment and

recovery of information. • User-friendly interfaces. The utilization of graphical user interfaces (GUIs)

facilitates the interaction of the user with the instrument. • Low power consumption. These kinds of devices have a power

consumption less than 3 VA.

2.4 PQ Instrumentation Regulations Standards provide a common reference framework that allows us to compare the

qualities of the products that we, as consumers, use in our daily lives. The set of

standards that regulate power-quality measurements belongs to different groups of

documents. Firstly, the whole regulation that defines the technical characteristics of

the instrumentation. Secondly, the measuring procedures and finally, the legal

limits of the power -quality indices.

In Spain, the legal framework began with Law 54/1997, which was later given

greater depth in Law 1955/2000.

Almost all the technical documents are generated by IEC and CENELEC, and

have to be applied in all of the European Union. In 1996 the European Commission

ratified the directive 89/336/EEC [1]. This has been applied since 1996 and can be

considered as the first step in a series that facilitates the globalization of power-

quality procedures. The compliance with these standards is shown by the CE

marking of the product. This global framework enables the European power-

quality-meter manufacturers to gain access to a wider market. Among others, the

most active groups that define and publish standards and reference documents are:

• IEC. International Electrotechnical Commission. • CENELEC. European Committee for Electrotechnical Standardisation.

There are other standards within the European union, at the local level, like:

• UNESA. Spanish Standards Institute. • BSI. British Standards Institute.

Page 90: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

32

Figure 2.11 shows the standards structure both in Europe and Spain. The

countries that are included in the European Union have to harmonize the

CENELEC documents and requirements to their national standards. On the other

hand, CENELEC also adopts, in some cases, international regulations, like those

generated by the International Electrotechnical Commission (IEC). This fact can be

readily observed if the standard reference is compared in the IEC and CENELEC

environments. The same happens with the Spanish standard editor UNESA. A

good example could be the standard IEC 61000-4-7, which defines the

characteristics of the instrumentation for harmonic and interharmonic

measurement. At the European level, this standard has been adopted by CENELEC

in Europe as EN 61000-4-7 and by UNESA in Spain as UNE EN 61000-4-7.

In the USA, the Institute of Electrical and Electronic Engineers (IEEE) is

working on the new standard IEEE 1159 [22] entitled “Recommended Practice on

Monitoring Electric Power Quality”. This work is sponsored by the Power Quality

Subcommittee of the IEEE Power Engineering Society.

Figure 2.12 shows the Dranetz PX5, a power-quality meter that fulfils the

standard IEC 61000-4-30 [23]. Among other available synchronization techniques,

the utilization of the GPS could be a good tool for synchronizing power-quality

meters in different locations.

Generic standards are general-purpose documents that all electrical equipment

should comply with. One example is the standard IEC 61000-6, which has been

adapted by CENELEC as EN 50081 (generic emission standard) and EN 50082

(generic immunity standard).

From the electrical point of view, a device can be considered a product or part

of the distribution network.

From one point of view, product standards cover the aspects of specific product

lines where the application of the generic standard would not be the right choice.

From another, network standards include the documents that cover different

aspects related with the power system: general considerations, description and

classification of the environmental levels, emissions and immunity limits, testing

and measuring techniques, installation and mitigation guidelines, generic standards

and miscellaneous topics.

As an example, IEC 61000 (EN 61000) covers almost all aspects related with

low and high-frequency disturbances.

The IEC 61000-4- 30 [23] defines the methods for measurement and

interpretation of results for power-quality parameters in 50/60 Hz AC power-

supply systems.

Page 91: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 33

Product standards.

e.g. EN 50160

IEC

610

00-4

-7 (E

N

6100

0-4-

7)

Har

mon

ican

dint

erha

rmon

icm

easu

rem

ent

IEC

61

00

0-4

-15

(E

N 6

10

00

-4-1

5)

Flic

ke

rme

ter.

Fu

nctio

na

l a

nd

de

sig

n

IEC

610

00-4

-30

(EN

610

00-4

-30)

Pow

er-

qual

itym

easu

rem

entm

etho

ds

IEC

610

00-1

(EN

610

00-1

)Gen

eral

cons

ider

atio

ns

IEC

610

00-2

(E

N 6

1000

-

2)D

escr

iptio

nofe

nviro

nmen

talle

vels

IEC

610

00

-4 T

esti

ng

an

d

me

as

ure

me

nt

tec

hn

iqu

es

Network standards. e.g. IEC 61000 (EN 61000)

Generic standards. e.g. IEC 61000-6 (EN 50081, EN 50082)

Directive 89/336/CEE

Figure 2.11. Structure of the standards related to PQ measurement

The basic aim of this document is to define measurement methods that will

make it possible to obtain reliable, repeatable and comparable results

independently of the power-quality-meter manufacturer. The standard does not

provide information about instrumentation design. This kind of information is

devoted to other standards like IEC 61000-4-7 and IEC 61000-4-15. 2.5 Harmonic Monitoring Both harmonics and interharmonics can be measured using various techniques. In

order to obtain results that can be compared between different equipments and

manufacturers, a standard document has been published by the IEC, CENELEC

and other regional agencies like the Spanish AENOR. The standard IEC 61000 -4-

7 [12] defines a general guide on harmonics and interharmonics measurements and

Page 92: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

34 instrumentation, for power-supply systems and equipment connected thereto. The

basic architecture of digital equipment based on the FFT is shown in Figure 2.13.

Figure 2.12. Dranetz-BMI PX-5 power-quality meter

In a first step the input signal is low filtered in order to fulfill the Nyquist–

Shannon sampling theorem. This element is also named an antialiasing filter. The

cutoff frequency is fixed to the 50th harmonic. The filtered signal is sampled and

stored using a frequency that is obtained with a phase-locked loop (PLL).

transient harmonic data storage classifier evaluation

Antialiasing Mean value low-pass filter sample & hold windowing

f(t) FFT arithmetic

ADC

unit

Tw

Magnitude and phase Synchronized sampling components (Cn,φn) frequency

Real and imaginary components (a

n,b

n)

Phase locked loop (PLL)

Figure 2.13. Block diagram of the FFT harmonic meter proposed by the IEC 61000-4-7

The FFT is then applied to a block of 2k samples included in a period Tw=NT0,

where N is an integral number and T0 is the fundamental period of the signal. The

sampling frequency is then fs=2k/(NT0). The block of 2

k samples is sometimes

multiplied by a window function that reduces the spectral leakage. The FFT

subsystem computes the Fourier coefficients an and bn of frequencies fh=h/Tw for

h=0, 1, 2, …, 2k–1

. The terms n=h/N with n∈Z are the nth harmonic of the

fundamental frequency.

Page 93: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 35

The standard defines almost all the basic aspects of the harmonics and

interharmonics measurement: accuracy, type of application, hardware architecture,

FFT application, evaluation methods, data-aggregation method, immunity test, etc. 2.6 Flicker Monitoring Flicker measurement can be done according to the IEC 61000-4-15 [13]. This document defines the architecture and some test procedures that have to be

followed in order to obtain the harmonized flicker perception Pst and Plt. The block

diagram of the IEC flickermeter is shown in Figure 2.14.

The flickermeter has two main parts. The first one attempts to simulate the

behaviour of the set lamp-eye-brain, considering the lamp as incandescent with a

power of 60 W. The second part is focused on the statistical analysis of the

instantaneous flicker perception.

It produces the short-term flicker severity index Pst with a 10 -min period

between samples and the long-term flicker severity index Plt every 2 h. simulation of the set lamp-eye-brain

Block 1 Block 2 Block 3 Ran

gese

lect

or

Block 4 Block 5

unit

D e m o d u l a t i o n a n d q u a d r a t i c m u l t i p l i e r

filter

Q u a d r a t i c m u l t i p l i e r a n d l o w - p a s s f i l t e r ( 3 0 0 m s )

A D C S t a t i s t i c a l c l a s s i f i e r D a t a m a n a g e m e n t a n d s t o r a g e

variable

range selector gain

f(t) Band-pass Eye

calibration filter response

input transformer weighting filter

input voltage Instantaneous Range selector

(rms value) flicker perception 1 minute integrator

output data

Output data

Figure 2.14. Block diagram of a flickermeter based on the IEC 61000-4-15

2.7 Data Postprocessing Power-quality instrumentation should have not only good hardware architecture,

but also powerful software that permits the measured data to be managed and

analysed. Figure 2.15 shows the architecture of a postprocessing application.

Page 94: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

36

Power Quality

Signal

Data translator classificator

meters

Software Data translator

Signal

simulators Parameter

extractor

Relays Data translator

Signal

Database

Disturbances Statistical Report Signal Limits viewer analysis writing analyser analysis

Power-quality applications

Figure 2.15. Architecture of a power-quality postprocessing system

In a complementary way, a power-quality survey involves the postprocessing

analysis after the measurements. The analysis can be supported by specialized tools

with some degree of automation [24–34]. The most powerful tools include some

kind of automatic disturbance classification.

Disturbance classification includes all aspects related with the problem of

determining the degree of similarity between a signal and a set of classes that act as

a dictionary of reference. This problem involves three main actors: i) the unknown

signal to be classified. ii) the database with the classes of reference and iii) the set

of classification algorithms.

In spite of the fact that multiple classification methods or data-mining

techniques can be used, it is possible to compile them into three large families:

• Statistical classification or theoretical decision methods. The foundation of

this type of method consists in obtaining an index that allows the degree of

similarity between the unknown signal and the information stored in the

database to be quantified. Euclidean distance classifiers belong to this set

of groups, where they use the Euclidean distance between two points in a

multidimensional space. This space can be obtained as the Fourier

transform or the wavelet transform of the signal. • Syntactic classification, which uses a structural representation of the

disturbance and an expert system in order to model human know-how. • Classification based on nonlinear methods. The utilization of neural nets is

included here. Supervised learning can be considered a classic method of

classification. Correlation methods can be also included here. They exhibit

Page 95: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 37

a good behaviour when the signals are distorted with white noise. Another

method to be included here is the use of the geometrical properties of the

phase-space representation of the signal. 2.8 Management of PQ Files Some years ago, the interchange of information stored by different equipments was

difficult and almost impossible. This came about because the manufacturers had

their own format files. In order to solve this problem, some standards have been

defined, providing a way to store and interchange power-quality data with a well-

known structure. The most important formats are the IEEE Standard C37.111

“COMTRADE” [35] and the power-quality data-interchange format “PQDIF” [36]. 2.8.1 COMTRADE The IEEE defined in 1991 the standard C37.111 entitled “IEEE Standard Common

Format for Transient Data Exchange (COMTRADE) for Power Systems”. This

work was sponsored by the Power System Relaying Committee of the IEEE Power

Engineering Society.

The main purpose of this standard was to define a common format for the data

files and exchange medium needed for the interchange of various types of fault,

test, or simulation data. Among others, the standard defines as sources of data the

following: digital fault recorders, analog tape recorders, digital protective relays,

transient simulation programs and analog simulators. 2.8.2 PQDIF The power-quality data-interchange format, also known as PQDIF was developed

by the Electric Power Research Institute (EPRI) and one of its contractors,

Electrotek Concepts, Inc. The main aim of this project was to develop a vendor-

independent interchange format for power-quality-related information. This power-

quality data-interchange format (PQDIF) has been in use since 1995.

In 1996, EPRI and Electrotek placed PQDIF in the public domain to facilitate

the interchange of power-quality data between interested parties. EPRI and

Electrotek have also offered the format, sample source code, and documentation to

the IEEE 1159.3 task force as a possible initial format to meet that group’s

requirements.

Page 96: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

38 2.9 Summary The evaluation of the future evolution of this type of instrumentation is always a

complex topic, since it involves, besides the classical problems of electronic

instrumentation, new aspects that are independent from the process of

measurement.

From a technical point of view, current meters are capable of registering all the

phenomena of interest: harmonics, flicker, dips, transients, imbalance, etc., with the

possibility of registering the measurement in a constant way or by means of trigger

mechanisms such as thresholds, slopes, logical events, etc.

An aspect to improve is the synchronization between different equipments for

the accomplishment of measurements synchronized in geographically distributed

environments. In this respect there are already developing projects that are starting

to use advantages such as the GPS (global positioning system), which is a set of

satellites provided with synchronized clocks, and that act in a way that might be

seen as a universal time base, which is accessible from almost any part of the

world.

As regards control and remote monitoring, it is important to be able to include

the equipment in an integral system of measurement. In order to do that, it is

necessary to establish common protocols for all the manufacturers, and to facilitate

the interchange of data between them.

The current trend is focusing on the use of standardized protocols such as MMS

(manufacturing message specification), which is simply a protocol meeting the OSI

stack. It has been designed for the control and remote monitoring of industrial

devices such as PLCs (programmable logic controller), or instrumentation devices,

allowing remote access to variables, programs, tasks and events.

However, it is necessary not only to standardize the communication protocols,

but also to establish mechanisms that define the types of allowed information and

their structure. In this sense, PQDIF constitutes a good example that can be used as

a starting point.

In short, power-quality meters have evolved enormously over the last few

decades, so the next steps will have to be directed towards the standardization of

information and protocols and towards the development of software for the

automatic analysis of the measurements according to international standards. References [1] Directive EMC 89/336/EEC of 23 May 1989 on the approximation of the laws of the

Member States relating to electromagnetic compatibility. Official Journal of the

European Union. Nº L 139/19.

Page 97: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

Power-quality Monitoring 39 [2] Directive 92/31/EEC of 28 April 1992 amending Directive 89/336/EEC on the

approximation of the laws of the Member States relating to electromagnetic

compatibility. Nº L 126/11. [3] Eguíluz L.I., Mañana M., Lara; P., Lavandero J.C., Benito P. MEPERT I: Electric

disturbance and energy meter. International Conference on Industrial Metrology.

Zaragoza. October 1995. [4] Eguiluz L.I., Manana M., Lavandero J.C., Voltage distortion influence on current

signatures in non-linear loads. Proceedings of the IEEE Power Engineering Society

Transmission and Distribution Conference. Seattle. 2000; 2: 1165–1170. [5] Mañana M. Contributions to the representation, detection and classifications of power

disturbances. PhD Thesis (in Spanish). University of Cantabria. 2000.

[6] CENELEC EN 50160. Voltage characteristics of electricity supplied by public

distribution systems (1999).

[7] Gunther E., Grebe T. Visualization of power system data using a PC-based GUI

interfaz”. First European Conference on Power System Transients. Lisbon. 1993.

[8] Ribeiro P.F., Celio R. Advanced techniques for voltage quality analysis: unnecessary

sophistication or indispensable tools. Ref. A-2.06. PQA’94 Amsterdam 1994.

[9] Gunther E.W., Thompson J.L., Dwyer R., Mehta, H. Monitoring Power Quality

Levels on Distribution Systems. PQA’92. Atlanta, Georgia 1992.

[10] Gunther E.W., Sabin D.D., Mehta H. Update on the EPRI Distribution Power Quality

Monitoring Project. PQA’93. San Diego. November 1993. [11] Sabin D., Grebe T., Sundaram A. Preliminary Results for Eighteen Months of

Monitoring from the EPRI Distribution Power Quality Project. PQA’95. New York.

May 1995. [12] IEC 61000-4-7. Electromagnetic Compatibility (EMC). Part 4: Testing and

Measurement Techniques. Section 7: General Guide on Harmonics and

Interharmonics measurements and Instrumentation for Power Supply Systems and

Equipment Connected thereto (2002).

[13] IEC 61000-4-15. Electromagnetic compatibility (EMC) - Part 4: Testing and

measurement techniques - Section 15: Flickermeter - Functional and design

specifications (2003). [14] EURELECTRIC. Measurement Guide for Voltage Characteristics (1995).

[15] IEC 61010-1. Safety requirements for electrical equipment for measurement, control

and laboratory use Part 1: General requirements (2001).

[16] Ramboz J. Machinable Rogowski Coil, Design, and Calibration. IEEE Transactions

on Instrumentation and Measurement 1996; 45(2):

[17] Arseneau R. Calibration system for power quality instrumentation. Proceedings of the

IEEE Power Engineering Society Transmission and Distribution Conference 2002. pp.

1686-1689. [18] Svensson S. Verification of a calibration system for power quality instruments. IEEE

Transactions on Instrumentation and Measurement 1998; 47(5): 1391–1394. [19] Emerging Technologies Working Group; Fiber Optic Sensors Working Group.

“Optical Current Transducer for Power Systems: A review”. IEEE Transactions on

Power Delivery 1994; 9(4). [20] Gordon B. Linear Electronic A/D Conversion Architectures, Their Origins,

Parameters, Limitations and Applications. IEEE Transactions on CAS 1978; 25(7).

[21] Oppenheim A.; Schafer R.; Discrete-Time Signal Processing. Prentice-Hall. (1989). [22] IEEE 1159. Recommended Practice for Monitoring Electric Power Quality (1995).

[23] IEC 61000-4-30. Electromagnetic compatibility (EMC) - Part 4-30: Testing and

measurement techniques - Power quality measurement methods (2003).

Page 98: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be

40 M. Mañana Canteli [24] Daniels R. Power Quality Monitoring Using Neural Networks. Proceedings of the

First International Forum on Applications of Neuronal Networks to Power Systems

1991; pp 195-197. [25] Collins J.J., Hurley W.; Application of Expert Systems and Neural Networks to the

Diagnosis of Power Quality Problems. PQA’94. Amsterdam. A-2.03. 1994.

[26] Gaouda A., Salama M., Sultan M.; Automated Recognition System for Classifying

and Quantifying The Electric Power Quality. 8th International Conference on

Harmonics and Quality of Power 1998; 1: 244–248. [27] Perunicic B., Mallini M., Wang Z., Lui Y. Power Quality Disturbance Detection and

Classification Using Wavelets and Artificial Neural Networks. 8th Int. Conf. On

Harmonics and Quality of Power 1998; 1: 77–82. [28] Angrisani L., Daponte, P., D’Apuzzo, M. A method for the automatic detection and

measurement of transients. Part II: Applications. Measurement: Journal of the

International Measurement Confederation 1999; 25(1): 31–40.

[29] Parihar P., Liu E. Identification, Classification and Correlation of Monitored Power

Quality Events. Power Engineering Society Winter Meeting 1999; 1: 437–441. [30] Parsons A., Grady M., Powers, E. A Wavelet-Based Procedure for Automatically

Determining the Beginning and End of Transmission System Voltage Sags. Power

Engineering Society Winter Meeting 1999; 2: 1310–1313. [31] Morcos M., Ibrahim, W. Electric Power Quality and Artificial Intelligence: Overview

and Applicability. IEEE Power Engineering Review 1999; 6: 5–10.

[32] Santoso S, Lamoree, J, Grady, W M, Powers E J, Bhatt S C. Scalable PQ event

identification system. IEEE Transactions on Power Delivery 2000; 15(2): 738–743.

[33] Eguiluz L.I., Mañana M., Lavandero J.C. Disturbance classification based on the

geometrical properties of signal phase-space representation. PowerCon 2000. Perth.

International Conference on Power System Technology. Proceedings 2000; 3: 1601–

1604.

[34] Kezunovic M., Liao Y. Automated analysis of power quality disturbances. IEE

Conference Publication 2001; 2(482).

[35] IEEE C37.111. Standard Common Format for Transient Data Exchange

(COMTRADE) for Power Systems (1991). [36] IEEE 1159.3. IEEE Recommended Practice for the Transfer of Power Quality Data

(2003).

Page 99: INTRODUCTION TO POWER QUALITY - Fmcetfmcet.in/EEE/EE2353(E)_uw.pdfINTRODUCTION TO POWER QUALITY ... to define because what is good power quality to a refrigerator motor may not be