CONTENTS INSTALLATION SAFETY INFORMATION ........ 3 GENERAL ................................. 3 INSPECTION ............................... 3 MAINTENANCE AND RENEWAL PARTS ........ 3 APPROVALS .............................. 3 INSTALLATION ............................ 4 SEQUENCE OF OPERATION ................ 14 START-UP ............................... 14 TROUBLE SHOOTING ...................... 18 TYPICAL WIRING DIAGRAM NOTES .......... 22 NOTES, CAUTIONS AND WARNINGS Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING . Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly. INSTALLATION INSTRUCTION CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT. SAVE THIS MANUAL SINGLE PACKAGED GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 2, 2-1/2, 3, 3-1/2 AND 4 NOMINAL TON 035-18868-001-A-0702 D*YP: 024 030 036 042 048

Upload: trinhminh

Post on 29-Apr-2019

212 views

Category:

Documents


0 download

TRANSCRIPT

CONTENTS

INSTALLATION SAFETY INFORMATION . . . . . . . . 3

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

MAINTENANCE AND RENEWAL PARTS . . . . . . . . 3

APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . 14

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

TROUBLE SHOOTING . . . . . . . . . . . . . . . . . . . . . . 18

TYPICAL WIRING DIAGRAM NOTES . . . . . . . . . . 22

NOTES, CAUTIONS AND WARNINGS

Installer should pay particular attention to the words: NOTE,CAUTION, and WARNING. Notes are intended to clarify ormake the installation easier. Cautions are given to preventequipment damage. Warnings are given to alert installerthat personal injury and/or equipment damage may result ifinstallation procedure is not handled properly.

INSTALLATIONINSTRUCTION

CAUTION: READ ALL SAFETY GUIDES BEFORE YOUBEGIN TO INSTALL YOUR UNIT.

SAVE THIS MANUAL

SINGLE PACKAGED GAS/ELECTRIC

AIR COOLED AIR CONDITIONERS

2, 2-1/2, 3, 3-1/2 AND 4 NOMINAL TON

035-18868-001-A-0702

D*YP: 024030036042048

035-18868-001-A-0702

2 Unitary Products Group

TABLE OF CONTENTS

INSTALLATION SAFETY INFORMATION . . . . . . . . 3

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

MAINTENANCE AND RENEWAL PARTS . . . . . . . . 3

APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5RIGGING OR HANDLING . . . . . . . . . . . . . . . . . . . . . . . . . 5DUCT WORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5ROOF CURB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . . . . 6SERVICE ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6POWER AND CONTROL WIRING . . . . . . . . . . . . . . . . . . 6COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9GAS CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9FLUE VENT HOOD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . 14HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14CIRCULATING FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14PRE-START CHECK LIST . . . . . . . . . . . . . . . . . . . . . . . 14OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . 14TO TURN OFF GAS TO UNIT . . . . . . . . . . . . . . . . . . . . 15POST-START CHECK LIST (GAS) . . . . . . . . . . . . . . . . 15MANIFOLD GAS PRESSURE ADJUSTMENT . . . . . . . . 15BURNER INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . 15HOT SURFACE PILOT INSTRUCTIONS . . . . . . . . . . . . 15ADJUSTMENT OF TEMPERATURE RISE . . . . . . . . . . 16

DIRECT DRIVE BLOWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

CHECKING GAS INPUT . . . . . . . . . . . . . . . . . . . . . . . . 16NATURAL GAS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

TROUBLE SHOOTING . . . . . . . . . . . . . . . . . . . . . . 18

TYPICAL WIRING DIAGRAM NOTES . . . . . . . . . 22

LIST OF FIGURES

1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . 42 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 53 FIELD WIRING DIAGRAM CONTROL WIRING . . . . . 74 POWER WIRING FIELD DIAGRAM . . . . . . . . . . . . . . 75 EXT SUPPLY CONN EXT SHUT-OFF . . . . . . . . . . . . 96 FLUE VENT OUTLET AIR HOOD . . . . . . . . . . . . . . . 107 UNIT DIMENSIONS - FRONT . . . . . . . . . . . . . . . . . . 128 UNIT DIMENSIONS - FRONT & BOTTOM . . . . . . . . 139 UNIT DIMENSIONS - BACK & BOTTOM . . . . . . . . . 1310 GAS VALVE - FRONT . . . . . . . . . . . . . . . . . . . . . . . . 1511 GAS VALVE - REAR . . . . . . . . . . . . . . . . . . . . . . . . . 1512 PROPER FLAME ADJUSTMENT . . . . . . . . . . . . . . . 1513 IGNITOR AND FLAME SENSOR ASSEMBLY . . . . . 1614 TYP WIRING DIA D*YP 024 (208/230-1-60 PS) . . . . 1915 TYP WIRING DIA D*YP(208/230-1-60 PS) . . . . . . . . 2016 TYP WIRING DIA D*YP(208/230-3-60 PS) . . . . . . . . 2017 TYP WIRING DIA D*YP(460-3-60 PS) . . . . . . . . . . . . 2118 TYPICAL WIRING DIAGRAM LEGEND . . . . . . . . . . 22

LIST OF TABLES

1 UNIT APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . 42 UNIT WEIGHTS AND CENTER OF GRAVITY . . . . . . . 53 NATURAL GAS APPLICATION DATA . . . . . . . . . . . . . 84 PROPANE (LP) GAS APPLICATION DATA . . . . . . . . . 85 NATURAL GAS PIPE SIZING CHART . . . . . . . . . . . . . 96 PROPANE (LP) GAS PIPE SIZING CHART . . . . . . . . . 97 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 119 UNIT DIMENSIONS FRONT . . . . . . . . . . . . . . . . . . . . 1210 UNIT MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . 1211 GASE RATE - CUBIC FEET PER HOUR . . . . . . . . . . 17

035-18868-001-A-0702

Unitary Products Group 3

INSTALLATION SAFETY INFORMATION

Read these instructions before continuing this applianceinstallation. This is an outdoor combination heating and cool-ing unit. The installer must assure that these instructions aremade available to the consumer and instruct the consumer toretain them for future reference.

1. Refer to the furnace rating plate for the approved type ofgas for this furnace.

2. Install this furnace only in a location and position asspecified on pages 4 and 5 of these instructions.

3. Never test for gas leaks with an open flame. Use com-mercially available soap solution made specifically forthe detection of leaks when checking all connections, asspecified on pages 3 and 10 of these instructions.

4. Always install furnace to operate within the furnace’sintended temperature-rise range with the duct systemand within the allowable external static pressure range,as specified on the unit name/rating plate, specified onpages 8 and 16 of these instructions.

5. This equipment is not to be used for temporary heatingof buildings or structures under construction.

GENERAL

Model D*YP units are cooling/heating air conditionersdesigned for outdoor installation. Only gas piping, electricpower and duct connections are required at the point ofinstallation.

The gas-fired heaters have hot surface to pilot ignition. Thetubular heat exchangers are aluminized steel.

Installer should pay particular attention to the words; NOTE,CAUTION, and WARNING. NOTES are intended to clarify ormake the installation easier. CAUTIONS are given to preventequipment damage. WARNINGS are given to alert theinstaller that personal injury and/or equipment damage mayresult if installation procedure is not handled properly.

INSPECTION

As soon as a unit is received, it should be inspected for possi-ble damage during transit. If damage is evident, the extent ofthe damage should be noted on the carrier's freight bill. Aseparate request for inspection by the carrier's agent shouldbe made in writing. Refer to Form 50.15-NM for additionalinformation.

MAINTENANCE AND RENEWAL PARTS

Refer to User’s, Maintenance and Service Information Man-ual, Part No. 035-15485-001.

APPROVALS

Design certified by CSA listed as follows:

1. For use as a forced air furnace with cooling unit.

2. For outdoor installation only.

3. For installation directly on combustible flooring or, inU.S., on wood flooring or Class A; B; C roof coveringmaterial.

4. For installation on combustible material.

5. For use with natural gas and/or propane (LP) gas.

Not suitable for use with conventional venting systems.FIRE OR EXPLOSION HAZARD

FAILURE TO FOLLOW THE SAFETY WARN-INGS EXACTLY COULD RESULT IN SERIOUSINJURY, DEATH OR PROPERTY DAMAGE.

NEVER TEST FOR GAS LEAKS WITH AN OPENFLAME. USE A COMMERCIALLY AVAILABLESOAP SOLUTION MADE SPECIFICALLY FORTHE DETECTION OF LEAKS TO CHECK ALLCONNECTIONS. A FIRE OR EXPLOSION MAYRESULT CAUSING PROPERTY DAMAGE, PER-SONAL INJURY OR LOSS OF LIFE.

THIS PRODUCT MUST BE INSTALLED INSTRICT COMPLIANCE WITH THE ENCLOSEDINSTALLATION INSTRUCTIONS AND ANYAPPLICABLE LOCAL, STATE, AND NATIONALCODES INCLUDING BUT NOT LIMITED TO,BUILDING, ELECTRICAL AND MECHANICALCODES.

IMPROPER INSTALLATION MAY CREATE ACONDITION WHERE THE OPERATION OF THEPRODUCT COULD CAUSE PERSONAL INJURYOR PROPERTY DAMAGE.

035-18868-001-A-0702

4 Unitary Products Group

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the follow-ing national and local safety codes.

1. National Electrical Code ANSI/NFPS No. 70 or CanadianElectrical Code Part 1, C22.1 (latest editions).

2. National Fuel Gas Code Z223.1 or CSA B149.1 Installa-tion Code.

3. Local gas utility requirements.

4. Local plumbing and waste water codes and other appli-cable local codes.

Refer to Table 1 for unit application data and to Tables 3 and4 for gas heat application data.

If components are to be added to a unit to meet local codes,they are to be installed at the dealer's and/or the customer'sexpense.

Size of unit for proposed installation should be based on heatloss/heat gain calculations made in accordance with industryrecognized procedures identified by the Air ConditioningContractors of America.

LOCATION

Use the following guidelines to select a suitable location forthese units.

1. Unit is designed for outdoor installation only.

2. Condenser must have an unlimited supply of air. Wherea choice of location is possible, position unit on eithernorth or east side of building.

3. For ground level installation, a level pad or slab shouldbe used. The thickness and size of the pad or slab used

FIGURE 1: PRODUCT NOMENCLATURE

D 0 4 50- F

PRODUCT CATEGORY

D = Single Package Air Conditioner

PRODUCT GENERATION

A = 1st Generation

PRODUCT IDENTIFIER

Y = 1 SEER Gas Heat/Electric

NOMINAL COOLINGCAPACITY (MBH)

NOMINAL GAS HEATINGOUTPUT CAPACITY

045=45,000 BTUH070=70,000 BTUH080=80,000 BTUH090=90,000 BTUH110=110,000 BTUH135=135,000 BTUH

FACTORYINSTALLED GAS HEAT

N = Natural Gas Heat Installed

VOLTAGE CODE

= 208/230-1-60= 208/230-3-60= 460-3 -60

N

F

T

W

P 3

Y PA 3 6

024=24,000 BTUH

030=30,000 BTUH

036=36,000 BTUH

042=42,000 BTUH

048=48,000 BTUH

TABLE 1: UNIT APPLICATION DATA

Voltage Variation

Min. / Max.1

1. Rated in accordance with ARI Standard 110, utilizationrange “A”.

208/230V2

2. “T1” transformer primary tap must be moved from the230 volt connection to the 208 volt connection for lowvoltage applications of 208 volt and below

187 / 253

460V 414 / 504

Wet Bulb Temperature (°F) of Air onEvaporator Coil, Min. / Max.

57 / 72

Dry Bulb Temperature (°F) of Air on

Condenser Coil, Min.3 / Max.

3. A low ambient accessory is available for operationdown to 0 °F.

45 / 120

EXCESSIVE EXPOSURE OF THIS FURNACETO CONTAMINATED COMBUSTION AIR MAYRESULT IN EQUIPMENT DAMAGE OR PER-SONAL INJURY. TYPICAL CONTAMINATESINCLUDE: PERMANENT WAVE SOLUTION,CHLORINATED WASHES AND CLEANERS,CHLORINE BASED SWIMMING POOL CHEMI-CALS, WATER SOFTENING CHEMICALS, CAR-BON TETRACHLORIDE, HALOGEN TYPEREFRIGERANTS, CLEANING SOLVENTS (e.g.PERCHLOROETHYLENE), PRINTING INKS,PAINT REMOVERS, VARNISHES, HYDRO-CHLORIC ACID, CEMENTS AND GLUES, ANTI-STATIC FABRIC SOFTENERS FOR CLOTHESDRYERS, MASONRY ACID WASHING MATERI-ALS.

035-18868-001-A-0702

Unitary Products Group 5

should meet local codes and unit weight. Do not tie theslab to the building foundation.

4. For roof top installation, be sure the structure will supportthe weight of the unit plus any field installed components.Unit must be installed on a level roof curb or appropriateangle iron frame providing adequate support under thecompressor/condenser section.

5. Maintain level tolerance of unit to 1/8" maximum.

CLEARANCES

All units require certain clearances for proper operation andservice. Refer to Table 10 for the clearances required forcombustion, construction, servicing and proper unit opera-tion.

RIGGING OR HANDLING

Care must be exercised when moving the unit. Do notremove any packaging until the unit is near the place ofinstallation. Rig unit with slings placed under the unit.Spreader bars of sufficient length should be used across thetop of the unit.

Units may also be moved or lifted with a fork-lift. Slottedopenings in the skid are provided for this purpose. Forksmust pass completely through the base.

Refer to Table 2 for unit weights and to Figure 2 for approxi-mate center of gravity.

DUCT WORK

These units are adaptable to downflow use as well as rearsupply and return air duct openings. To convert to downflow,use the following steps:

1. Remove the duct covers found in the bottom return andsupply air duct openings. There are four (4) screwssecuring each duct cover (save these screws to use inStep 2).

2. Install the duct covers (removed in step one) to the rearsupply and return air duct openings. Secure with the four(4) screws used in step one.

DO NOT PERMIT OVERHANGING STRUC-TURES OR SHRUBS TO OBSTRUCT THE CON-DENSER AIR DISCHARGE, COMBUSTION AIRINLET OR VENT OUTLET.

BEFORE LIFTING A UNIT, MAKE SURE THATITS WEIGHT IS DISTRIBUTED EQUALLY ONTHE CABLES SO THAT IT WILL LIFT EVENLY.

TABLE 2: UNIT WEIGHTS AND CENTER OFGRAVITY

UNITSIZE

SHIPPINGWEIGHT

(LBS.)

OPERATINGWEIGHT

(LBS.)

CORNER WEIGHTS(LOCATION, LBS.)

“A” “B” “C” “D”

024 365 360 91 88 89 92

030 395 390 98 95 96 99

036 400 395 100 96 98 101

042 470 465 131 129 101 103

048 475 470 133 130 102 104

FIGURE 2 : UNIT CENTER OF GRAVITY

"A"

"B"

"C"

"D"

49-1/825 25

47-1/4

FRONT

OF

UNIT

CENTER OF

GRAVITY

035-18868-001-A-0702

6 Unitary Products Group

Duct work should be designed and sized according to themethods of the Air Conditioning Contractors of America(ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not pre-clude use of economizers or ventilation air intake. Flexiblejoints may be used in the supply and return duct work to min-imize the transmission of noise.

NOTE: Be sure to note supply and return openings.

Refer to Figure 8 and 9 for information concerning rear andbottom supply and return air duct openings.

ROOF CURB

On applications when a roof curb is used, the unit must bepositioned on the curb so the front of the unit is tight againstthe curb.

FILTERS

Single phase units are shipped without a filter or filter racks. Itis the responsibility of the installer to secure a filter in thereturn air ductwork or install a Filter/Frame Kit (1FF0110).

A filter rack and high velocity filters are standard on threephase units.

Filters must always be used and must be kept clean. Whenfilters become dirt laden, insufficient air will be delivered bythe blower, decreasing your units efficiency and increasingoperating costs and wear-and-tear on the unit and controls.

Filters should be checked monthly; this is especially impor-tant since this unit is used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is recommended to be installed in the con-densate drain. The plumbing must conform to local codes.

Use a sealing compound on male pipe threads. Install thecondensate drain line (NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the fol-lowing removable panels:

• Blower compartment• Gas control/electrical service access

Refer to Figure 7 for location of these access panels and min-imum clearances in Table 10.

THERMOSTAT

The room thermostat should be located on an inside wallapproximately 56" above the floor where it will not be subjectto drafts, sun exposure or heat from electrical fixtures orappliances. Follow manufacturer's instructions enclosed withthe thermostat for general installation procedure. Four colorcoded insulated wires (minimum #18 AWG) should be usedto connect thermostat to unit. See Figure 3.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the cur-rent N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordi-nances. The unit must be electrically grounded in accordancewith local codes or, in their absence, with the N.E.C./C.E.C.Voltage tolerances which must be maintained at the com-pressor terminals during starting and running conditions areindicated on the unit Rating Plate and Table 8.

The wiring entering the cabinet must be provided withmechanical strain relief.

A fused disconnect switch should be field provided for theunit. If any of the wire supplied with the unit must be replaced,replacement wire must be of the type shown on the wiringdiagram.

Electrical line must be sized properly to carry the load. Eachunit must be wired with a separate branch circuit fed directlyfrom the meter panel and properly fused.

Refer to Figure 4 for typical field wiring and to the appropriateunit wiring diagram for control circuit and power wiring infor-mation.

WHEN FASTENING DUCT WORK TO THE SIDEDUCT FLANGES ON THE UNIT, INSERT THESCREWS THROUGH THE DUCT FLANGESONLY. DO NOT INSERT THE SCREWSTHROUGH THE CASING. OUTDOOR DUCT-WORK MUST BE INSULATED AND WATER-PROOFED.

035-18868-001-A-0702

Unitary Products Group 7

COMPRESSORS

Units are shipped with compressor mountings which arefactory-adjusted and ready for operation.

FIGURE 3 : FIELD WIRING DIAGRAM CONTROL WIRING

��

� � � � � � � � �

� � � � � � � � � � �

� �� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � � � � � � ! � � " # � $ � � � � � # � � � � � % " "

� � � � � � � � � " # � � � � & % " " � # � ' ( � ) � " & � � � � � *

� � � � � � + � , � � � , � � � � � � , �

� � � -

� � � � � � , � , � � � �

� � � + � . � � � � � � � � / * 0 1

� � � � 2 � � � � � � � � . � � � *

' ( � 3 � �

� � � � 2 � � � �

FIGURE 4 : POWER WIRING FIELD DIAGRAM

� � � � � �

� � �

� � � � � � � � � � � � � � �

� � � � � � � � � � � � � � �

� � � � � � � � � � � �

� � � � � � � � � � �

� � � � � � � � �

� � � � � � � � �

� � � � � � � � � � �

� � � � � � � � �

� � � � � � � � �

� � � � � �

� � � � � � � � � � � � � � � � � �

� � � � � � � � � � � � � � �

� � � � � � � � � � � �

� � � � �

� � � � �

� � � � �

� � � � � �

� � � � �

� � � � �

� � � � �

� � � � � �

DO NOT LOOSEN COMPRESSOR MOUNTINGBOLTS.

035-18868-001-A-0702

8 Unitary Products Group

TABLE 3: NATURAL GAS APPLICATION DATA

AVAILABLE ON MODELSINPUT CAPACITY

(MBH)1OUTPUT CAPACITY

(MBH)GAS RATE2

FT.3/HR.

NUMBER OF

BURNERS

TEMP. RISE ºF A FULL

INPUT3

MIN. MAX.

2, 2-1/2, 3 TON 45 36 42 2 25 55

2, 2-1/2, 3 TON 70 56 65 3 25 55

3-1/2, 4 TON 80 64 74 3 25 55

3 TON 90 72 84 4 30 60

3-1/2, 4 TON 108 87 43 4 30 60

4 TON 135 108 126 5 35 65

1. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should bereduced by 4% for each 1,000 feet above sea level.

2. Based on 1075 BTU/Ft.3.3. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not

be below 55°F.

TABLE 4: PROPANE1 (LP) GAS APPLICATION DATA

AVAILABLE ON

MODELS

INPUT CAPACITY

(MBH)2OUTPUT CAPACITY

(MBH)GAS RATE3

FT.3/HR.

NUMBER OF

BURNERS

TEMP. RISE ºF A FULL

INPUT4

MIN. MAX.

2, 2-1/2, 3 TON 45 36 18 2 25 55

2, 2-1/2, 3 TON 70 56 28 3 25 55

3-1/2, 4 TON 80 64 32 3 25 55

3 TON 90 72 36 4 30 60

3-1/2, 4 TON 108 87 43 4 30 60

4 TON 135 108 54 5 35 65

1. Propane applications are accomplished by field installation of a Propane Conversion Accessory, Model 1NP0805.2. Heating capacity valid for elevations up to 2,000 feet above sea level. For elevations above 2,000 feet, rated capacity should be

reduced by 4% for each 1,000 feet above sea level.3. Based on 2500 BTU/Ft.3.4. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperatures should not

be below 55°F.

035-18868-001-A-0702

Unitary Products Group 9

GAS PIPING

Proper sizing of gas piping depends on the cubic feet perhour of gas flow required, specific gravity of the gas and thelength of run. National Fuel Gas Code Z223.1 or CSA B149.1should be followed in all cases unless superseded by localcodes or gas company requirements. Refer to Tables 5 & 6.

The heating value of the gas may differ with locality. Thevalue should be checked with the local gas utility.

NOTE: There may be a local gas utility requirement specify-ing a minimum diameter for gas piping. All units require a 1/2inch pipe connection at the gas valve.

GAS CONNECTION

The gas supply line can be routed through the hole locatedon the left side of the unit. Refer to Figure 7 to locate theseaccess openings. Typical supply piping arrangements areshown in Figure 5.

Gas piping requirements:

1. A drip leg and a ground joint union must be installed inthe gas piping.

2. When required by local codes, a manual shut-off valvemay have to be installed outside of the unit.

3. Use wrought iron or steel pipe for all gas lines. Pipe dopeshould be applied sparingly to male threads only.

FIGURE 5 : EXTERNAL SUPPLY CONNECTIONEXTERNAL SHUT-OFF

� � � � � � � � � � � � � � �

� � � � � � � � � � � �

� � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � �

TABLE 5: NATURAL GAS PIPE SIZING CHART1

LENGTH

IN FEET

NOMINAL INCHES IRON PIPE SIZE

1/2” 3/4” 1” 1-1/4”

10 132 278 520 1,050

20 92 190 350 730

30 73 152 285 590

40 63 130 245 500

50 56 115 215 440

60 50 105 195 400

70 46 96 180 370

80 43 90 170 350

90 40 84 160 320

100 38 79 150 305

1. Maximum capacity of pipe in cubic feet of gas per hour(based upon a pressure drop of 0.3 inch water columnand 0.6 specific gravity gas).

TABLE 6: PROPANE (LP) GAS PIPE SIZINGCHART1

1. Maximum capacity of pipe in thousands of BTU perhour (based upon a pressure drop of 0.5 inch water col-umn).

LENGTH

IN FEET

NOMINAL INCHES IRON PIPE SIZE

1/2” 3/4” 1” 1-1/4”

10 275 567 1,071 2,205

20 189 393 732 1,496

30 152 315 590 1,212

40 129 267 504 1,039

50 114 237 448 913

60 103 217 409 834

70 96 196 378 771

80 89 185 346 724

90 83 173 322 677

100 78 162 307 630

035-18868-001-A-0702

10 Unitary Products Group

4. All piping should be cleaned of dirt and scale by ham-mering on the outside of the pipe and blowing out theloose dirt and scale. Before initial start-up, be sure thatall of the gas lines external to the unit have been purgedof air.

5. The gas supply should be a separate line and installed inaccordance with all safety codes as prescribed underLimitations, shown on Page 4. After the gas connectionshave been completed, open the main shut-off valveadmitting normal gas pressure to the mains. Check alljoints for leaks with soap solution or other material suit-able for the purpose. NEVER USE A FLAME.

6. The furnace must be isolated from the gas supply pipingsystem by closing its individual manual shut-off valvebefore conducting any pressure testing of the gas supplypiping system at test pressures equal to or less than 1/2psig (3.48 kPa).

FLUE VENT HOOD

The flue vent hood with screen is shipped loose. This hoodmust be installed to assure proper unit operation. The hoodmust be fastened to the outside of the side gas control/electri-cal compartment with the screws provided in the bagattached to the inside of the gas control/electrical compart-ment, see Figure 6.

IF FLEXIBLE STAINLESS STEEL TUBING ISALLOWED BY THE AUTHORITY HAVING JURIS-DICTION, WROUGHT IRON OR STEEL PIPEMUST BE INSTALLED AT THE GAS VALVE ANDEXTEND A MINIMUM OF TWO (2) INCHES OUT-SIDE OF THE UNIT CASING.

NATURAL GAS MAY CONTAIN SOME PRO-PANE. PROPANE BEING A EXCELLENT SOL-VENT, WILL QUICKLY DISSOLVE WHITE LEADOR MOST STANDARD COMMERCIAL COM-POUNDS. THEREFORE, A SPECIAL PIPEDOPE MUST BE APPLIED WHEN WROUGHTIRON OR STEEL PIPE IS USED. SHELLACBASE COMPOUNDS SUCH AS GASKOLOC ORSTALASTIC, AND COMPOUNDS SUCH AS REC-TORSEAL # 5, CLYDE’S OR JOHN CRANE MAYBE USED.

FLUE HOOD SURFACES MAY BE HOT.

FIGURE 6 : FLUE VENT OUTLET AIR HOOD

THE FLUE EXHAUST HOOD MUST BE PROP-ERLY INSTALLED AND WITHIN THE RECOM-MENDED CLEARANCES. FURTHERCOMMUNICATIONS AND ACTION MUST BEGIVEN TO THE HOME OR BUILDINGOWNER(S) TO ELIMINATE ANY UNAUTHO-RIZED HUMAN CONTACT AROUND THIS AREADURING THE HEATING CYCLE. FLUE HOODSURFACE AND THE IMMEDIATE AREA REACHHIGH TEMPERATURES DURING THE HEATINGCYCLE.

� � � � � � � � � � � � � �

� � � � � � � � � � � � � �� � � � � �

035-18868-001-A-0702

Unitary Products Group 11

TABLE 7: PHYSICAL DATA

MODELD*YP

024 030 036 042 048

EVAPORATOR BLOWERCENTRIFUGAL BLOWER (Dia. x Wd. in.) 10x8 10x8 11 x 10 12x11 12 x 11

FAN MOTOR HP 1/2 3/4 3/4 1 1

EVAPORATOR COIL

ROWS DEEP 2 3 3 3 3

FINS PER INCH 15 13 13 13 16

FACE AREA (Sq. Ft.) 3.5 3.5 3.5 4.5 4.5

CONDENSER FAN

PROPELLER DIA. (in.) 22 22 22 22 22

FAN MOTOR HP 1/4 1/4 1/4 1/4 1/3

NOM. CFM TOTAL 2,200 2,400 2,400 2,400 3,000

CONDENSER COIL

ROWS DEEP 1 1 2 2 2

FINS PER INCH 20 20 20 20 20

FACE AREA (Sq. Ft.) 11.7 11.7 11.7 14.7 14.7

CHARGE REFRIGERANT 22 (lbs./oz.) 4/10 4/9 6 / 12 9/6 8 / 4

FILTER FACE AREA (Sq. Ft.) Size (Nominal) 2.6/20x20 2.6/20x20 2.6/20x20 3.3/20x12(2 Reqd.)

3.3/20x12(2 Reqd.)

FURNACE SECTION

NATURAL GAS BURNER ORIFICE NO.(Drill Size) 43 43 43 40 40

PROPANE BURNER ORIFICE NO.(Drill Size) 55 55 55 53 53

GAS CONNECTION SIZE 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI

COMPRESSOR HERMETIC TYPE, (Qty. = 1) Recip Scroll Scroll Scroll Scroll

TABLE 8: ELECTRICAL DATA

MODELD*YP POWER SUPPLY

VOLTAGELIMITATIONS1 COMPRESSOR COND.

FANMOTOR,

FLA

SUPPLYAIR

BLOWERMOTOR

FLA

MINIMUMCIRCUIT

AMPACITY

MAX.FUSESIZE,

AMPS2

MAX.HACR

BREAKERSIZE,AMPS

UNITPOWERFACTOR

TRANSFORMERSIZE (VA)

MIN. MAX. RLA LRA

024 208/230-1-60 187 253 8.1 57 1.1 2.6 15.7 25 25 0.96 40

030 208/230-1-60 187 253 13.6 67 1.1 6.8 24.9 35 35 0.96 40

030 208/230-3-60 187 253 8.6 55 1.1 6.8 18.7 25 25 0.96 75

030 460-3-60 414 504 4.3 27 0.6 6.8 13.4 20 20 0.96 75

036 208/230-1-60 187 253 17.2 88 1.1 6.8 29.4 45 45 0.96 40

036 208/230-3-60 187 253 11.4 77 1.1 6.8 22.2 30 30 0.96 75

036 460-3-60 414 504 5.7 39 0.6 6.8 14.8 20 20 0.96 75

042 208/230-1-60 187 253 20 104 1.3 9.1 35.4 50 50 0.96 40

042 208/230-3-60 187 253 13.9 88 1.3 9.1 27.8 40 40 0.96 75

042 460-3-60 414 504 6.4 44 0.7 9.1 18.5 25 25 0.96 75

048 208/230-1-60 187 253 23.4 126 1.9 9.1 39.5 60 60 0.96 40

048 208/230-3-60 187 253 13 93 1.9 9.1 26.5 35 35 0.96 75

048 460-3-60 414 504 6.4 46.5 1.0 9.1 18.4 25 25 0.96 75

1. Rated in accordance with ARI Standard 110, utilization range “A”.2. Dual element, time delay type.

035-18868-001-A-0702

12 Unitary Products Group

FIGURE 7 : UNIT DIMENSIONS - FRONT

� � � � �

� � � � �

� � � � � �

� � � � �

� � � � �� � � � �

� � � � �

� �� � � � � � � � � � � �

� � � � �

� � � � � � � � � � � � � � � �

� ! � � � � � � � � �� � � � � � � � � � � � � �� � � � �

� � � � � � � � � " � � � � � � # � � � � $� � � � % � � � # � � � � � � � � &

� � � � � � � � � � � � � � � � � # � � � �% � � � � � � � � � � � � � &

� � � � � � � � � � � $ � � � � � � # � � � � $� � � �

� � � � � � � � � � � $ � � � � # � � � � $� � � �

� � � � � � � � � " � � � � � � # � � � � $� � � � � % � � � # � � � � � � � &

� ! � � � � � � � � $� � � � � # � � � � $ � � � � �' � � � � # � � � �

� � � � � � � �

� � � � � � � � � � � � � �

� � � � � � � � �� � � � � � � � � � �

� � �

� � � � � � � � � � � � � �� � � � � � � � � � �

� � � � � � � � � � � � �

% � � � � � � &

% � � � � � � &

All dimensions are in inches.They are subject to change with-out notice. Certified dimensionswill be provided upon request.

TABLE 9: UNIT DIMENSIONS FRONT

UNIT SIZEDIMENSION

“A” “B”

024, 030, 036 33-1/2 18-1/4042, 048 41-1/2 23-1/8

TABLE 10: UNIT MINIMUM CLEARANCES1 2

1. A 1” clearance must be provided between any combus-tible material and the supply air ductwork.

2. The products of combustion must not be allowed toaccumulate within a confined space and recirculate.

CLEARANCES

FRONT 36”BACK 0”

LEFT SIDE (Filter-Access) 24”

RIGHT SIDE 12”

BELOW UNIT3

3. Units may be installed on combustible floors made fromwood or class A, B, or C roof covering material.

0”

ABOVE UNIT 4

4. Units must be installed outdoors. Overhanging struc-tures or shrubs should not obstruct condenser air dis-charge outlet.

36” (For Condenser Air Discharge

035-18868-001-A-0702

Unitary Products Group 13

FIGURE 8 : UNIT DIMENSIONS - FRONT & BOTTOM

26-3/4

6

4-5/8

8-7/811-7/8 19-1/4

HIGH VOLTAGE

CONN. 1-3/32" DIA.

KNOCKOUT FRONT

CONDENSATE

DRAIN 3/4"' NPTI

GAS SUPPLY 1-5/8" DIA.

KNOCKOUT (1/2" NPTI

CONNECTION)

LOW VOLTAGE CONN.

" DIA. KNOCKOUT/87

FIGURE 9 : UNIT DIMENSIONS - BACK & BOTTOM

� � � � �

� �

� � � � � � (

� �

� � � � �

� � � � �

� � � � �

� �

� � � � � �

� � � � �

� � � � �

� � � � � �

� � � � � �

� � � � � �

� � � � � � �

� � � � � � � � � "� � � � � � � �

� � � � � � � � � � � � � � � � �

� � � � � � � � � � � � � � � � � �

� � � � � � � � � � "� � � � � � � �

� �

035-18868-001-A-0702

14 Unitary Products Group

SEQUENCE OF OPERATION

The unit is controlled by a conventional four wire heating/cooling thermostat common to this class of equipment.

HEATING

When the thermostat calls for HEAT, the thermostat terminalW is energized, energizing the combustion air blower.

After airflow is established, the air proving switch closes, thehot surface ignitor is energized and the pilot valve opensigniting the pilot flame.

The flame rod senses a flame and de-energizes the ignitoropening the main gas valve and the main burners light.

30 seconds after the main burners light the circulating fan isenergized at the heating speed.

When the thermostat is satisfied, terminal W is de-energized,which de-energizes the ignition system and closes the gasvalve.

After a 5 second postpurge timing period, the combustion airblower is de-energized and the heat fan off timing begins.

When this field selected heat fan off timing is completed, thecirculating fan is de-energized.

If the primary, rollout and auxiliary limit switches open, thethermostat and ignition system is de-energized and the gasvalve closes. The combustion blower and the circulating fan,at heat speed, are energized.

The combustion blower remains energized for the 5 secondpostpurge timing period if the primary, rollout and auxiliarylimit switches remake the contact (the rollout and auxiliarylimit switches must be manually reset). The circulating fanremains energized for the selected heat delay off timing.

Normal operation of the system resumes.

COOLING

When the thermostat calls for COOL, the thermostat termi-nals G and Y are energized, which signals the compressorand outdoor fan to run.

After a cool fan on delay timing of 2 seconds, the circulatingfan is energized at cooling speed.

When the thermostat is satisfied, terminals G and Y are de-energized, de-energizing the compressor and outdoor fan.

After a cool fan off delay timing of 30 seconds, the circulatingfan is de-energized.

CIRCULATING FAN

When the thermostat calls for FAN, the thermostat terminal Gis energized signaling the circulating fan to run at the heatspeed 2 seconds after the G terminal is energized.

If a call for HEAT occurs, the circulating fan continues to runat the heat speed.

If a call for COOL occurs, the circulating fan switches to coolspeed after a 4 second delay.

When the thermostat ends the call for FAN, the thermostatterminal G is de-energized, de-energizing the circulating fan.

START-UP

PRE-START CHECK LIST

Complete the following checks before starting the unit.

1. Check the type of gas being supplied. Be sure that it isthe same as listed on the unit nameplate.

2. Make sure that the vent outlet air hood has been prop-erly installed.

OPERATING INSTRUCTIONS

1. STOP! Read the information on the unit safety label.

2. Set the thermostat to the OFF position.

3. Turn off all electrical power to the unit.

4. DO NOT try to light the burners by hand. This applianceis equipped with an ignition device which automaticallylights the burners.

5. Remove the access panel.

6. Turn the gas valve switch to the OFF position.

7. Wait five (5) minutes to clear out any gas. If you thensmell gas, STOP! Follow B in the information on the unitsafety label. If you don't smell gas, go to the next step.

8. Turn the gas valve switch to the ON position.

9. Replace the control access panel.

10. Turn on all electric power to the unit.

11. Set the thermostat to the desired setting.

12. If the unit will not operate, follow the instructions To TurnOff Gas To Appliance and call your service technician orgas supplier.

035-18868-001-A-0702

Unitary Products Group 15

TO TURN OFF GAS TO UNIT

1. Set the thermostat to the OFF position.

2. Turn off all electric power to the appliance if service is tobe performed.

3. Remove the control access panel.

4. Turn the gas valve switch to the OFF position. DO NOTFORCE.

5. Replace the control access panel.

POST-START CHECK LIST (GAS)

After the entire control circuit has been energized and theheating section is operating, make the following checks:

1. Check for gas leaks in the unit piping as well as the sup-ply piping.

2. Check for correct manifold gas pressures. See CheckingGas Input.

3. Check the supply gas pressure. It must be within the lim-its shown on rating nameplate. Supply pressure shouldbe checked with all gas appliances in the building at fullfire. At no time should the standby gas line pressureexceed 10.5", nor the operating pressure drop below4.5" for natural gas units. If gas pressure is outside theselimits, contact the local gas utility for corrective action.

MANIFOLD GAS PRESSURE ADJUSTMENT

Small adjustments to the gas flow may be made by turningthe pressure regulator adjusting screw on the automatic gasvalve. Refer to Figure 10.

Adjust as follows:

1. Remove the cap from the valve body. See Figure 11 forlocation.

2. To decrease the gas pressure, turn the adjusting screwcounterclockwise.

3. To increase the gas pressure, turn the adjusting screwclockwise.

NOTE: The correct manifold pressure for natural gas fur-naces is 3.5 IWG. The correct manifold pressure forpropane (LP) is 10.0 IWG.

BURNER INSTRUCTIONS

To check or change the burners, CLOSE THE MAIN MAN-UAL SHUT-OFF VALVE AND SHUT OFF ALL POWER TOTHE UNIT.

1. Remove the two (2) #8 screws holding each burner inplace.

2. Remove the burner assembly from the manifold assem-bly by moving the burner assembly forward, turn at anangle and pull back.

3. Burners are now accessible for service.

FIGURE 10 : GAS VALVE - FRONT

� � � � � � � � �� ! � � �% � � ! � � � # � �� � � � � &

� � �� � � � � � � � � � �

� � � � � � � � � � � � � � � � �

� � � � � �� � � � � � � �� � �

� � � �� � � � � � �

� � � � � � � � �% � � � � � &

� � � � � � � � � � �

� � � �� � ) � � � � � �

FIGURE 11 : GAS VALVE - REAR

� � � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �% � � � � &

� � � � � � � � � � � � � � � �

� � � � � � � � � � � � � � �� � ) � � � � � �% � � � � � � � � &

035-18868-001-A-0702

16 Unitary Products Group

HOT SURFACE PILOT INSTRUCTIONS

To adjust the pilot flame:

1. Remove the pilot adjustment cover screw.

2. Adjust the pilot adjustment screw to achieve the properpilot flame.

3. The pilot flame should envelope 3/8” of the end of theflame sensor and not contain any yellow color, see Fig-ure 12.

4. Replace the pilot adjustment cover screw after the pilotflame is set.

To check, adjust or remove the hot surface pilot assembly,CLOSE THE MAIN MANUAL SHUT-OFF VALVE AND SHUTOFF ALL POWER TO THE UNIT.

1. Disconnect the wiring from the gas valve to the hot sur-face pilot assembly.

2. Remove the two (2) #8 screws holding the hot surfacepilot assembly in place.

3. Remove the hot surface pilot assembly.

To remove the hot surface ignitor and flame sensor assem-bly:

1. Remove the clip attaching the ignitor and sensor assem-bly as shown in Figure 13.

2. Lift the pilot and sensor from the assembly. Care must betaken not to damage the pilot or sensor when removingthis assembly.

ADJUSTMENT OF TEMPERATURE RISE

After about 20 minutes of operation, determine the furnacetemperature rise. Take readings of both the return air and theheated air in the ducts about six feet from the furnace wherethey will not be affected by radiant heat.

The temperature rise (or temperature difference between thereturn air and the heated air from the furnace) must lie within

the range shown on the rating plate and the data in Tables 3and 4.

After the temperature rise has been determined, the CFM canbe calculated as follows:

DIRECT DRIVE BLOWER

All units, with the exception of the 2 Ton, have direct drive,constant CFM blower motors. Refer to the unit wiring dia-gram, Table 1 for the desired cooling CFM. Heating CFM ispreset at the factory. For the 2 Ton unit, refer to the wiring dia-gram to connect the blower motor for the desired CFM.

CHECKING GAS INPUT

NATURAL GAS

1. Turn off all other gas appliances connected to the gasmeter.

2. With the furnace turned on, measure the time needed forone revolution of the hand on the smallest dial on themeter. A typical gas meter usually has a 1/2 or a 1 cubicfoot test dial.

3. Using the number of seconds for each revolution and thesize of the test dial increment, find the cubic feet of gasconsumed per hour from Table 11.

FIGURE 12 : PROPER FLAME ADJUSTMENT

� � �

FIGURE 13 : IGNITOR AND FLAME SENSORASSEMBLY

D e g r e e s F T e m p R i s eB T U H O u t p u t

1.08 C F M×------------------------------------=

OR

C F MB T U H O u t p u t

1.08 D e g r e e s F T e m p R i s e×-------------------------------------------------------------------------=

035-18868-001-A-0702

Unitary Products Group 17

If the actual input is not within 5% of the furnace rating withallowance being made for the permissible range of the regu-lator setting, replace the orifice spuds with spuds of theproper size.

NOTE: To find the BTU input, multiply the number of cubicfeet of gas consumed per hour by the BTU contentof the gas in your particular locality. (Contact yourgas company for this information since it varieswidely from city to city.)

TABLE 11: GASE RATE - CUBIC FEET PER HOUR1

SECONDSFOR ONE

REV.

SIZE OF TEST DIAL

1/2 CU. FT. 1 CU. FT.

10 180 360

12 150 300

14 129 257

16 113 225

18 100 200

20 90 180

22 82 164

24 75 150

26 69 138

28 64 129

30 60 120

32 56 113

34 53 106

36 50 100

38 47 95

40 45 90

42 43 86

44 41 82

46 39 78

48 37 75

50 36 72

52 35 69

54 34 67

56 32 64

58 31 62

60 30 60

1. EXAMPLE: By actual measurement, it takes 38 seconds for the hand on the 1-cubic foot dial to make a revolution with just a100,000 BTUH furnace running. Using this information, locate 28 seconds in the first column of Table 11. Read across to the col-umn headed “1 Cubic Foot,” where you will see that 95 cubic feet of gas per hour are consumed by the furnace at that rate. Multi-ply 95 x 1050 (the BTU rating of the gas obtained from the local gas company). The result is 99,750 BTUH, which is close to the100,000 BTUH rating of the furnace.

035-18868-001-A-0702

18 Unitary Products Group

TROUBLE SHOOTING

NOTE: Before troubleshooting, familiarize yourself with theSTART-UP and CHECKOUT procedures.

TROUBLESHOOTING OF COMPONENTSNECESSITATES OPENING THE ELECTRICALCONTROL BOX WITH THE POWER CON-NECTED TO THE UNIT. USE EXTREME CAREWHEN WORKING WITH THE LIVE CIRCUITS!CHECK THE UNIT NAMEPLATE FOR THE COR-RECT LINE VOLTAGE AND SET THE VOLTMETER TO THE CORRECT RANGE BEFOREMAKING ANY CONTACT WITH LINE TERMI-NALS.

035-18868-001-A-0702

Unitary Products Group 19

FIGURE 14 : TYPICAL WIRING DIAGRAM D*YP 024 (208/230-1-60)

035-18868-001-A-0702

20U

nitaryP

roductsG

roup

FIG

UR

E15

:T

YP

ICA

LW

IRIN

GD

IAG

RA

MD

*YP

030,036,042,048(208/230-1-60

PO

WE

RS

UP

PLY

)

7

DETAIL "A"

T2L2M1-2

COOL/BLU

HEAT/BK

R/RED

224/R

240V/BLK

240V/PRP

GND/GRN

G/GRA

224/R

"SPEED" CONNECTIONS COOLING BLOWER FOR HEATING AND SEE TABLES 1 AND 2

R/RED

213/R 224/R 214/BR

110/BK

PRP

BLK

108/PR

240V/PRP

C2/BRN

108/PR

110/BK

220/O

213/R

221/BR

214/BR

224/R

M1

L1

L2

T1

T2

A

B

203/BR

(SEE NOTE 5) 202/Y

100/BK

107/PR

108/PR

BLK

101/BK

104/R

C

FAN

HERMRC1/RC2

BRN103/BR

PRP

104/R

RC1

7. SHUNT CONTACT ALSO USED WITH CRANKCASE HEATER. (OPTIONAL)

MOVE '108/PR' WIRE FROM 230V TO 208V ON TRANFORMER T1.6. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION

208

208V

R/RED/BLKHEAT

MOTOR

ID FAN

5

4

3

2

1

S5

S4ID MOTOR CONTROLLER

YELY1/

/BLUCOOL

BRNC2/

WHTW1/

BRNC1/

1514131211109

87654321

16

MOTOR "SPEED" CONNECTIONSTB2 TERMINAL BLOCK, 24V, ID

B

A

TB2

ID MOTOR CONTROLLER

S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL

* BLACK SQUARE INDICATES SWITCH POSITION

SETTINGFACTORY

180 SEC120 SEC

90 SEC60 SEC

INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*

INDOOR BLOWER HEAT ON DELAY: 30 SEC

INDOOR BLOWER COOL OFF DELAY: 30 SEC

INDOOR BLOWER COOL ON DELAY: 3 SEC

CONTROL BOARD SETTINGS:

COMBUSTION BLOWER POSTPURGE: 5 SEC

S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROLS3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE

S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVECN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD

S5/P5

P4/S4

B

A

TB2

FOR COOLING AIRFLOWBLOWER CONNECTIONSTABLE 1

"SPEED" CONNECTIONSFOR COOLING BLOWERSEE TABLE 1

COOL/BLU

HEAT/BLK

C1/BRN

BLK

PRP

11

5

3

5

4

3

12

2

6

1

R/RED

C2/BRN

W1/WHT

Y1/YEL

240V/BK

240V/PR

GRN

ROOM THERMOSTAT 24V CONNECTIONS

TB1 ON CONTROL BOARD

FIELD WIRING OPTIONAL WIRING AND DEVICES

FACTORY WIRING AND DEVICES

OUTDOORFAN

MOTOR

BLK BRN PRP

230-1-60MOTORDRAFT

1

230-1-60

1

MOTORID FAN

L2

L1

T2

T1

M2-2

M2-1

M2

ON CONTROL BOARD, 24-1-60, 18VA MAXEAC ELECTRONIC AIR CLEANER RELAY OUTPUT

BOARD, 24-1-60, 18VA MAXHUM HUMIDIFIER RELAY OUTPUT ON CONTROL

N

N

EAC

HUM

N

N

EAC

HUM

GRN

VALVE

GAS

P3

4

3

2

1P2

1

3

4

2

230-1-60

230-1-60

GAS VALVE

207/Y

211/PR

210/BL

209/BK

CLEAR

BLU

BLU

S3

4

3

2

1

S2

4

3

2

1

AFTER SERVICING. CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED, CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING

15H

220/O

221/BR

110/BK

240V/BLK

B

A

T2

T1

L2

L1

M2

110/BK

M2 CONTACTOR, DRAFT INDUCER MOTOR

107/PR

100/BK

108/PR

100/BK107/PR

201/BR200/R

211/PR

208/PR

206/R

205/R

204/O

213/R

CLEAR

BLU

BLUBLK

PRP

102/Y

103/BR101/BK

206/R

210/BL

209/BK

208/PR

207/Y

204/O

200/R

201/BR

C1/BRN

214/BR

221/BR

220/O

213/R

W1/WHT

Y1/YEL

203/BR

202/Y

HEAT

COOL

HSP

GAS HEAT SECTION

PS

LS

RS

MOTOR

DRAFT

R

SC

CONTROL BOX

T1

CONTROL BOARD

1

2S

DI

LEADS

MOTOR

UNUSED

4

3

2

1

C

X

XFMR

CN1

6 5 4

3 2 1

OF

F

DE

LA

Y

TB1

Y

C

R

W

Y

G

C

SEC

C230

LUGGND

LUGGND

NOTES:

4. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM CIRCUIT AMPACITY.

3. MOTORS ARE INHERENTLY PROTECTED.

CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL

LEGEND:

M1 CONTACTOR, COMPR & OD FAN

T1 TRANSFORMER, 24V, 40 VA

RC1/RC2 COMP. START & OUTDOOR FAN RUN CAPACITOR

COMPR COMPRESSOR

HSP HOT SURFACE TO PILOT

LS LIMIT SWITCH

.193 IWC NOM (.33 IWC MAX)PS PRESSURE SWITCH - MAKES @

RS ROLLOUT SWITCH

IDENTIFIED TERMINAL ON CAPACITOR

035-18578D000 REV. CBEFORE SERVICING THIS UNITCAUTION - OPEN ALL DISCONNECTS

3H,5H

LKJHGFEDCBA

CONNECTION DIAGRAM ELEMENTARY DIAGRAMCOOLING UNIT WITH GAS HEAT

RC2

202/Y

203/BR

208/230-1-60POWER SUPPLY

102/Y

103/BR

101/BK

R

S

C

COMPR

1

104/R

PRP

BRN

BLK

T2

T1

L2

L1

M1-2

M1-1

1

MOTOROD FAN

230VPRI

T1

C

75 VASEC 24V

201/BR

200/R

BLU

BLU

HSP

S3S2

211/PRPS

207/Y

208/PR

209/BK

210/BL

206/R

204/O RS

BOARDCONTROL

Y

C

1

2

S

DI

LEADS

MOTOR

UNUSED

NE

UT

RA

L

4

3

2

1

XFMR

X

C

HEAT

COOL

P1

CN1

653214

ALS205/R

213/R

ALS AUXILARY LIMIT SWITCH

LS213/R

ALS205/R

M1

FSHP LP

ASCT3 1

2

7 2802/BK 803/BK 804/BK

807/BL

800/Y

LR

801/BL (SEE NOTE 5)

(SEE NOTE 5)805/BL

BLRA

806/BR

(OPTIONAL ACCESSORIES - SEE NOTE 5)

ACCESSORY) OPENS @ 380 PSIGHP HIGH PRESSURE SWITCH (OPTIONAL OPEN @ 26 DEGREE FFS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)

OPEN @ 7 PSIGLP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)

LR LOCK OUT RELAY (OPTIONAL ACCESSORY)

(OPTIONAL ACCESSORY)ASCT ANTI-SHORT CYCLE TIMER

PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL. ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT 5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.

COMPR

2A

7B

800/Y

801/BL

(SEE NOTE 5) LR

802/BK

800/Y202/Y

FS803/BK

804/BK

LP805/BL

804/BK

HP803/BK

802/BK

3

21

807/BL

(SEE NOTE 5)ASCT

801/BL805/BL

806/BR

10G

100/BK

107/PR

201/BR

30

29

28

OF

F

ON

DE

LA

Y

27

26

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

THERMOSTATROOM

R

G

Y

WHEAT

COOL

OFF

ON

AUTO

TB1

C

G

Y

W

R

17H

102/Y

CCH CRANKASE HEATER (OPTIONAL)

CCHBLK

BLK

L1

T1

BLKCCH

BLK

L1

L2

BLKCCH

BLK

OPTIONAL CCH

D/P CONFIGURATION

S/P CONFIGURATION

SEE DETAIL "A"

COOL/BLU TO:WIRECONNECT

(CFM) AIRFLOWFOR COOLING

1400 (ARI RATING) TB2-A

1350 TB2-B

1200 (ARI RATING) TB2-A

1600 TB2-B

UNIT SIZE

-036

-036

-048

-048

------

------

12

12160

270

ALS

RS

0364 TUBE

LS 160 1306 9

------

------

12

12160

270

ALS

RS

LS 160 1306 9

------

------

12

12160

200

ALS

RS

0362 TUBE

LS 140 1106 9

+/-CLOSE+/-OPEN

CONTROL SETPOINT (DEG F)UNIT SIZE DEVICE

TEMPERATURE CONTROLS

------

------

12

12160

270

ALS

RS

0485 TUBE

LS 160 1306 9

------

------

12

12160

270

ALS

RS

0484 TUBE

LS 175 1456 9

------

------

12

12160

200

ALS

RS

0483 TUBE

LS 150 1206 9

0363 TUBE

------

------

12

12160

200

ALS

RS

0302 TUBE

LS 140 1106 9

------

------

12

12160

270

ALS

RS

0303 TUBE

LS 160 1306 9

------

------

12

12160

200

ALS

RS

0423 TUBE

LS 140 1106 9

------

------

12

12160

270

ALS

RS

0424 TUBE

LS 140 1106 9

1250 TB2-B

1000 (ARI RATING) TB2-A-030

-030

1500 TB2-B

1350 (ARI RATING) TB2-A-042

-042

035-18868-001-A-0702

Unitary

Products

Group

21

FIG

UR

E16

:T

YP

ICA

LW

IRIN

GD

IAG

RA

MD

*YP

030,036,042,048(208/230-3-60

PO

WE

RS

UP

PL

Y)

17H

15H

3H,5H

10G

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

G/GRA

COOL/BLU

HEAT/BK

R/RED

108/PR

224/R

213/R

224/R

224/R

"SPEED" CONNECTIONS COOLING BLOWER FOR HEATING AND SEE TABLES 1 AND 2

R/RED

213/R 214/BR

BLK

PRP

108/PR

240V/PRP

C2/BRN

240V/BLK

240V/PRP

GND/GRN

220/O

221/BR

224/R

214/BR

110/BK

MOVE '108/PR' WIRE FROM 230V TO 208V ON TRANFORMER T1.6. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION

208

208V

R/RED/BLKHEAT

MOTOR

ID FAN

5

4

3

2

1

S5

S4ID MOTOR CONTROLLER

YELY1/

/BLUCOOL

BRNC2/

WHTW1/

BRNC1/

1514131211109

87654321

16

MOTOR "SPEED" CONNECTIONSTB2 TERMINAL BLOCK, 24V, ID

B

A

TB2

ID MOTOR CONTROLLER

S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL

* BLACK SQUARE INDICATES SWITCH POSITION

SETTINGFACTORY

180 SEC120 SEC

90 SEC60 SEC

INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*

INDOOR BLOWER HEAT ON DELAY: 30 SEC

INDOOR BLOWER COOL OFF DELAY: 30 SEC

INDOOR BLOWER COOL ON DELAY: 3 SEC

CONTROL BOARD SETTINGS:

COMBUSTION BLOWER POSTPURGE: 5 SEC

S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROLS3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE

S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVECN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD

B

A

TB2

FOR COOLING AIRFLOWBLOWER CONNECTIONSTABLE 1

"SPEED" CONNECTIONSFOR COOLING BLOWERSEE TABLE 1

BLK

PRP

5

4

3

240V/BLK

240V/PRP

GRN

ROOM THERMOSTAT 24V CONNECTIONS

TB1 ON CONTROL BOARD

FIELD WIRING

OPTIONAL WIRING AND DEVICES

FACTORY WIRING AND DEVICES

OUTDOORFAN

MOTOR

BLK BRN PRP

230-1-60MOTORDRAFT

1

230-1-60

1

MOTORID FAN

L2

L1

T2

T1

M2-2

M2-1

M2

ON CONTROL BOARD, 24-1-60, 18VA MAXEAC ELECTRONIC AIR CLEANER RELAY OUTPUT

BOARD, 24-1-60, 18VA MAXHUM HUMIDIFIER RELAY OUTPUT ON CONTROL

N

N

EAC

HUM

N

N

EAC

HUM

GRN

VALVE

GAS

P3

4

3

2

1P2

1

3

4

2

230-1-60

230-3-60

GAS VALVE

207/Y

211/PR

210/BL

209/BK

CLEAR

BLU

BLU

S3

4

3

2

1

S2

4

3

2

1

AFTER SERVICING. CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED, CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING

220/O

221/BR

110/BK

240V/BLK

110/BK

100/BK

B

A

T2

T1

L2

L1

M2

110/BK

M2 CONTACTOR, DRAFT INDUCER MOTOR

107/PR

100/BK

108/PR

203/BR

(SEE NOTE 5) 202/Y

107/PR

108/PR

100/BK107/PR

201/BR200/R

BRN

PRP

105/BL

212/R

200/R

121/BK

BK

123/BL

105/BL

126/Y

211/PR

208/PR

206/R

205/R

204/O

213/R

CLEAR

BLU

BLUBLK

PRP

126/Y

123/BL121/BK

206/R

210/BL

209/BK

208/PR

207/Y

204/O

212/R

201/BR

C1/BRN

214/BR

221/BR

220/O

213/R

W1/WHT

Y1/YEL

203/BR

202/Y

HEAT

COOL

HSP

GAS HEAT SECTION

PS

LS

RS

MOTOR

DRAFT

L3

L2L1

CONTROL BOX

T1

CONTROL BOARD

CB

1

2S

DI

LEADS

MOTOR

UNUSED

4

3

2

1

C

X

XFMR

CN1

6 5 4

3 2 1

OF

F

DE

LAY

TB1

Y

C

R

W

Y

G

C

SEC

C230

RC2

LUGGND

T3

T2

T1

L3

L2

L1

B

A

M1

LUGGND

NOTES:

4. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM CIRCUIT AMPACITY.

3. MOTORS ARE INHERENTLY PROTECTED.

CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL

3.2 AMP

LEGEND:

M1 CONTACTOR, COMPR & OD FAN

T1 TRANSFORMER, 24V, 75 VA

RC2 OUTDOOR FAN RUN CAPACITOR

CB CIRCUIT BREAKER

COMPR COMPRESSOR

HSP HOT SURFACE TO PILOT

LS LIMIT SWITCH

.193 IWC NOM (.33 IWC MAX)PS PRESSURE SWITCH - MAKES @

RS ROLLOUT SWITCH

IDENTIFIED TERMINAL ON CAPACITOR

035-18845D000 REV.CBEFORE SERVICING THIS UNITCAUTION - OPEN ALL DISCONNECTS

LKJHGFEDCBA

CONNECTION DIAGRAM ELEMENTARY DIAGRAMCOOLING UNIT WITH GAS HEAT

RC2

202/Y

203/BR

208/230-3-60POWER SUPPLY

126/Y

123/BL

121/BK

L3

L2

L1

COMPR

3

105/BL

PRP

BRN

BLK

T3

T2

T1

L3

L2

L1

M1-3

M1-2

M1-1

1

MOTOROD FAN

230VPRI

T1

C

CB 75 VASEC 24V

200/R

201/BR

212/R

BLU

BLU

HSP

S3S2

211/PRPS

207/Y

208/PR

209/BK

210/BL

206/R

204/O RS

BOARDCONTROL

Y

C

1

2

S

DI

LEADS

MOTOR

UNUSED

NE

UT

RA

L

4

3

2

1

XFMR

X

C

HEAT

COOL

P1

CN1

653214

ALS205/R

213/R

ALS AUXILARY LIMIT SWITCH

LS213/R

ALS205/R

M1

FSHP LP

ASCT3 1

2

7 2802/BK 803/BK 804/BK

807/BL

800/Y

LR

801/BL (SEE NOTE 5)

(SEE NOTE 5)805/BL

BLRA

806/BR

(OPTIONAL ACCESSORIES - SEE NOTE 5)

ACCESSORY) OPENS @ 380 PSIGHP HIGH PRESSURE SWITCH (OPTIONAL OPEN @ 26 DEGREE FFS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)

OPEN @ 7 PSIGLP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)

LR LOCK OUT RELAY (OPTIONAL ACCESSORY)

(OPTIONAL ACCESSORY)ASCT ANTI-SHORT CYCLE TIMER

PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL. ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT 5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.

COMPR

2A

7B

800/Y

801/BL

(SEE NOTE 5) LR

802/BK

800/Y202/Y

FS803/BK

804/BK

LP805/BL

804/BK

HP803/BK

802/BK

3

21

807/BL

(SEE NOTE 5)ASCT

801/BL805/BL

806/BR

100/BK

107/PR

201/BR

OF

F

ON

DE

LAY

13

12

11

10

9

8

7

6

5

4

3

2

1

THERMOSTATROOM

R

G

Y

WHEAT

COOL

OFF

ON

AUTO

TB1

C

G

Y

W

R

W1/WHT

R/RED

Y1/YEL

C1/BRN

C2/BRN

COOL/BLU

HEAT/BLK

3

1

6

12

2

P4/S4

11

5

COOL/BLU TO:WIRECONNECT

(CFM) AIRFLOWFOR COOLING

1400 (ARI RATING) TB2-A

1350 TB2-B

1200 (ARI RATING) TB2-A

1600 TB2-B

UNIT SIZE

-036

-036

-048

-048

1250 TB2-B

1000 (ARI RATING) TB2-A-030

-030

1500 TB2-B

1350 (ARI RATING) TB2-A-042

-042

------

------

12

12160

270

ALS

RS

0364 TUBE

LS 160 1306 9

------

------

12

12160

270

ALS

RS

LS 160 1306 9

------

------

12

12160

200

ALS

RS

0362 TUBE

LS 140 1106 9

+/-CLOSE+/-OPEN

CONTROL SETPOINT (DEG F)UNIT SIZE DEVICE

TEMPERATURE CONTROLS

------

------

12

12160

270

ALS

RS

0485 TUBE

LS 160 1306 9

------

------

12

12160

270

ALS

RS

0484 TUBE

LS 175 1456 9

------

------

12

12160

200

ALS

RS

0483 TUBE

LS 150 1206 9

0363 TUBE

------

------

12

12160

200

ALS

RS

0302 TUBE

LS 140 1106 9

------

------

12

12160

270

ALS

RS

0303 TUBE

LS 160 1306 9

------

------

12

12160

200

ALS

RS

0423 TUBE

LS 140 1106 9

------

------

12

12160

270

ALS

RS

0424 TUBE

LS 140 1106 9

035-18868-001-A-0702

22U

nitaryP

roductsG

roup

FIG

UR

E17

:T

YP

ICA

LW

IRIN

GD

IAG

RA

MD

*YP

030,036,042,048(460-3-60

PO

WE

RS

UP

PLY

)

17H

15H

3H,5H

10G

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

G/GRA

COOL/BLU

HEAT/BK

R/RED

240V/BLK

240V/PRP

GND/GRN

R/RED/BLKHEAT

YELY1/

/BLUCOOL

BRNC2/

WHTW1/

BRNC1/

224/R

224/R

"SPEED" CONNECTIONS COOLING BLOWER FOR HEATING AND SEE TABLES 1 AND 2

213/R

R/RED214/BR

BLK

PRP

131/PR

240V/PRP

108/PR

C2/BRN

224/R

213/R

220/O

221/BR

224/R

214/BR

108/PR

125/BK

MOTOR

ID FAN

5

4

3

2

1

S5

S4ID MOTOR CONTROLLER

1514131211109

87654321

16

MOTOR "SPEED" CONNECTIONSTB2 TERMINAL BLOCK, 24V, ID

B

A

TB2

ID MOTOR CONTROLLER

S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL

* BLACK SQUARE INDICATES SWITCH POSITION

SETTINGFACTORY

180 SEC120 SEC

90 SEC60 SEC

INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*

INDOOR BLOWER HEAT ON DELAY: 30 SEC

INDOOR BLOWER COOL OFF DELAY: 30 SEC

INDOOR BLOWER COOL ON DELAY: 3 SEC

CONTROL BOARD SETTINGS:

COMBUSTION BLOWER POSTPURGE: 5 SEC

S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROLS3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE

S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVECN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD

S5/P5

B

A

TB2

FOR COOLING AIRFLOWBLOWER CONNECTIONSTABLE 1

"SPEED" CONNECTIONSFOR COOLING BLOWERSEE TABLE 1

BLK

PRP

5

4

3

240V/BK

240V/PR

GRN

ROOM THERMOSTAT 24V CONNECTIONS

TB1 ON CONTROL BOARD

FIELD WIRING

OPTIONAL WIRING AND DEVICES

FACTORY WIRING AND DEVICES

125/BK131/PR

H4H2H3H1

T2

120/BK

X1X3X2X4

OUTDOORFAN

MOTOR

BLK BRN PRP

230-1-60MOTORDRAFT

1

230-1-60

1

MOTORID FAN

L2

L1

T2

T1

M2-2

M2-1

M2

ON CONTROL BOARD, 24-1-60, 18VA MAXEAC ELECTRONIC AIR CLEANER RELAY OUTPUT

BOARD, 24-1-60, 18VA MAXHUM HUMIDIFIER RELAY OUTPUT ON CONTROL

N

N

EAC

HUM

N

N

EAC

HUM

GRN

VALVE

GAS

P3

4

3

2

1P2

1

3

4

2

460-1-60

460-3-60

GAS VALVE

207/Y

211/PR

210/BL

209/BK

CLEAR

BLU

BLU

S3

4

3

2

1

S2

4

3

2

1

AFTER SERVICING. CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED, CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING

220/O

221/BR

125/BK

240V/BLK

120/BK

100/BK

240 V

480 V

B

A

T2

T1

L2

L1

M2

120/BK

120/BK

131/PR

T2

X4X3X2X1

H4H3

H2H1

T2 TRANSFORMER, 480/240 VOLT

M2 CONTACTOR, DRAFT INDUCER MOTOR

107/PR

100/BK

108/PR

203/BR

(SEE NOTE 5) 202/Y

107/PR

108/PR

100/BK107/PR

201/BR200/R

BRN

PRP

105/BL

212/R

200/R

121/BK

BK

123/BL

105/BL

126/Y

211/PR

208/PR

206/R

205/R

204/O

213/R

CLEAR

BLU

BLUBLK

PRP

126/Y

123/BL121/BK

206/R

210/BL

209/BK

208/PR

207/Y

204/O

212/R

201/BR

C1/BRN

214/BR

221/BR

220/O

213/R

W1/WHT

Y1/YEL

203/BR

202/Y

HEAT

COOL

HSP

GAS HEAT SECTION

PS

LS

RS

MOTOR

DRAFT

L3

L2L1

CONTROL BOX

T1

CONTROL BOARD

CB

1

2S

DI

LEADS

MOTOR

UNUSED

4

3

2

1

C

X

XFMR

CN1

6 5 4

3 2 1

OF

F

DE

LA

Y

TB1

Y

C

R

W

Y

G

C

SEC

C480

RC2

LUGGND

T3

T2

T1

L3

L2

L1

B

A

M1

LUGGND

NOTES:

4. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM CIRCUIT AMPACITY.

3. MOTORS ARE INHERENTLY PROTECTED.

CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL

3.2 AMP

LEGEND:

M1 CONTACTOR, COMPR & OD FAN

T1 TRANSFORMER, 24V, 75 VA

RC2 OUTDOOR FAN RUN CAPACITOR

CB CIRCUIT BREAKER

COMPR COMPRESSOR

HSP HOT SURFACE TO PILOT

LS LIMIT SWITCH

.193 IWC NOM (.33 IWC MAX)PS PRESSURE SWITCH - MAKES @

RS ROLLOUT SWITCH

IDENTIFIED TERMINAL ON CAPACITOR

035-18846D000 REV.C

BEFORE SERVICING THIS UNITCAUTION - OPEN ALL DISCONNECTS

LKJHGFEDCBA

CONNECTION DIAGRAM ELEMENTARY DIAGRAMCOOLING UNIT WITH GAS HEAT

RC2

202/Y

203/BR

460-3-60POWER SUPPLY

126/Y

123/BL

121/BK

L3

L2

L1

COMPR

3

105/BL

PRP

BRN

BLK

T3

T2

T1

L3

L2

L1

M1-3

M1-2

M1-1

1

MOTOROD FAN

480VPRI

T1

C

CB 75 VASEC 24V

200/R

201/BR

212/R

BLU

BLU

HSP

S3S2

211/PRPS

207/Y

208/PR

209/BK

210/BL

206/R

204/O RS

BOARDCONTROL

Y

C

1

2

S

DI

LEADS

MOTOR

UNUSED

NE

UT

RA

L

4

3

2

1

XFMR

X

C

HEAT

COOL

P1

CN1

653214

ALS205/R

213/R

ALS AUXILARY LIMIT SWITCH

LS213/R

ALS205/R

M1

FSHP LP

ASCT3 1

2

7 2802/BK 803/BK 804/BK

807/BL

800/Y

LR

801/BL (SEE NOTE 5)

(SEE NOTE 5)805/BL

BLRA

806/BR

(OPTIONAL ACCESSORIES - SEE NOTE 5)

ACCESSORY) OPENS @ 380 PSIGHP HIGH PRESSURE SWITCH (OPTIONAL OPEN @ 26 DEGREE FFS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)

OPEN @ 7 PSIGLP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)

LR LOCK OUT RELAY (OPTIONAL ACCESSORY)

(OPTIONAL ACCESSORY)ASCT ANTI-SHORT CYCLE TIMER

PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL. ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT 5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.

COMPR

2A

7B

800/Y

801/BL

(SEE NOTE 5) LR

802/BK

800/Y202/Y

FS803/BK

804/BK

LP805/BL

804/BK

HP803/BK

802/BK

3

21

807/BL

(SEE NOTE 5)ASCT

801/BL805/BL

806/BR

100/BK

107/PR

OF

F

ON

DE

LA

Y

13

12

11

10

9

8

7

6

5

4

3

2

1

THERMOSTATROOM

R

G

Y

WHEAT

COOL

OFF

ON

AUTO

TB1

C

G

Y

W

R

W1/WHT

R/RED

Y1/YEL

C1/BRN

C2/BRN

COOL/BLU

HEAT/BLK

3

1

6

12

2

P4/S4

11

5

COOL/BLU TO:WIRECONNECT

(CFM) AIRFLOWFOR COOLING

1400 (ARI RATING) TB2-A

1350 TB2-B

1200 (ARI RATING) TB2-A

1600 TB2-B

UNIT SIZE

-036

-036

-048

-048

1250 TB2-B

1000 (ARI RATING) TB2-A-030

-030

1500 TB2-B

1350 (ARI RATING) TB2-A-042

-042

------

------

12

12160

270

ALS

RS

0364 TUBE

LS 160 1306 9

------

------

12

12160

270

ALS

RS

LS 160 1306 9

------

------

12

12160

200

ALS

RS

0362 TUBE

LS 140 1106 9

+/-CLOSE+/-OPEN

CONTROL SETPOINT (DEG F)UNIT SIZE DEVICE

TEMPERATURE CONTROLS

------

------

12

12160

270

ALS

RS

0485 TUBE

LS 160 1306 9

------

------

12

12160

270

ALS

RS

0484 TUBE

LS 175 1456 9

------

------

12

12160

200

ALS

RS

0483 TUBE

LS 150 1206 9

0363 TUBE

------

------

12

12160

200

ALS

RS

0302 TUBE

LS 140 1106 9

------

------

12

12160

270

ALS

RS

0303 TUBE

LS 160 1306 9

------

------

12

12160

200

ALS

RS

0423 TUBE

LS 140 1106 9

------

------

12

12160

270

ALS

RS

0424 TUBE

LS 140 1106 9

035-18868-001-A-0702

Unitary Products Group 23

TYPICAL WIRING DIAGRAM NOTES (SEE FIGURES14, 15, 16 AND 17)

1. All field wiring to be accomplished following city, localand/or national codes in effect at time of installation ofthis unit.

2. Caution: Label all wires prior to disconnection when ser-vicing controls. Wiring errors can cause improper anddangerous operation if any of the wire as supplied withthis unit must be removed it must be replaced with type105°C, 600V wire or equivalent clearly renumbered foridentification. Verify proper operation after servicing.

3. Motors are inherently protected.

4. See unit nameplate for maximum fuse size and minimumcircuit ampacity.

5. For the 030, 036, 042 and 048, select indoor blowercooling speed from the Unit Wiring Diagram Table 1.Heating speed is preset at the factory.

6. For 024, select indoor blower speed to remain within thetemperature rise range on the nameplate in heating andto obtain approximately 400 CFM/Ton in cooling.Unit is factory wired for low or medium speed indoorblower operation. To change motor speed, connectspeed tap wires from indoor blower motor per Detail B(Figure 20). Tape unused speed tap wires to preventshorting and secure near M2 contactor.

7. If both LR and ASCT are present, wire 801/BL and 805/BL are connected to ASCT-3 if LR only is present wire801/BL and 805/BL are connected to M1 coil. If ASCTonly is present wire 202/Y is connected to ASCT-3. Ifneither LR or ASCT are present, Wire 202/Y is connectto M1 coil.

OPEN ALL DISCONNECTS BEFORE SERVIC-ING THIS UNIT.

FIGURE 18 : TYPICAL WIRING DIAGRAMLEGEND1

1. See Figures 14, 15, 16 and 17.

ALS

ASCT

COMPR

EAC

FS

HP

HSP

HUM

LP

LR

LS

M1

M2

PS

RC1/RC2

RS

T1

T2

TB2

ELECTRIC AIR CLEANER RELAY OUTPUT

LEGEND :

AUXILARY LIMIT SWITCH

ANTI-SHORT CYCLE TIMER

(OPTIONAL ACCESSORY)

COMRESSOR

ON CONTROL BOARD, 24-1-60, 18VA MAX.

FREEZESTAT SWITCH (OPTIONAL ACCESSORY)

OPEN @ 250 F

HIGH PRESSURE SWITCH (OPTIONAL

ACCESSORY) OPENS @ 380 PSIG

HOT SURFACE TO PILOT

HUMIDIFER RELAY OUTPUT ON CONTROL

BOARD, 24-1-60, 18VA MAX.

LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)

OPEN @ 7 PSIG

LOCK OUT RELAY (OPTIOAL ACCESSORY)

LIMIT SWITCH

CONTACTOR, COMPR. & O.D.FAN

CONTACTOR, DRAFT INDUCER MOTOR

PRESSURE SWITCH MAKES @

.193 IWC NOM. (.33 IWC MAX.)

COMPR. START & OUTDOOR FAN RUN CAPACITOR

ROLL OUT SWITCH

TRANSFORMER, 24V, 40VA

TRANSFORMER, 480/240 VOLT

TERMINAL BLOCK, 24V, I.D.

MOTOR "SPEED" CONNECTION

IDENTIFIED TERMINAL ON CAPACITOR

FIELD WIRING

D*YP LEGEND WIRING DIA.

ROOM THERMOSTAT 24V CONNECTIONS

TB1 ON CONTROL BOARD

FACTORY WIRING AND DEVICES

OPITIONAL WIRING AND DEVICES

Subject to change without notice. Printed in U.S.A.Copyright © by Unitary Products Group 2002. All rights reserved. Supersedes: 035-18868-000-A-0302 035-18868-001-A-0702

Unitary 5005 NormanProducts York OKGroup Drive 73069