iom-york vrf.pdf

Upload: tonylyf

Post on 25-Feb-2018

782 views

Category:

Documents


182 download

TRANSCRIPT

  • 7/25/2019 IOM-YORK VRF.pdf

    1/106

    YDOH(C)-0C IOM

    FORM NO.:Y (YGF)()

    V

    F (RF) S

    Installation, Operation & Maintenance anual

  • 7/25/2019 IOM-YORK VRF.pdf

    2/106

    Digital Scroll VRF Systems

    Part 1.

    Part 5

    Part 2

    Part 6.

    Part 3

    Part 7

    Part 8

    Part 4

  • 7/25/2019 IOM-YORK VRF.pdf

    3/106

    Part 9

    Part 10

    Part 12

    Part 11

    All the illustrations and information in this manual are only for reference. The manufacturer has the right to change,

    without prior notice, necessarily at any time due to reasons in relation to sale or production.

    Amicable tips:

    Units using environment friendly R410a has no harm to the ozonosphere.

    The manual is an integral part of the unit and should be properly kept for reference at any time after reading. At the same time, please hand themanual over to other operators for reference.

  • 7/25/2019 IOM-YORK VRF.pdf

    4/106

    Foreword

    This manual covers the necessary information for correct installation, commissioning, startup and maintenance of the unit.Please read this manual thoroughly before installing, starting or overhauling the unit so that it can be operated optimally.

    Dont operate the unit for fear of personal risk and unit failure, if you have not completely understood the working principle

    of the unit, or dont have sufficient general safety knowledge or adopt relevant safeguard measures.

    So, we suggest that the installation, starting and debugging of the unit should be done by specially trained personnel.

    Warranty only applies on the basis of the following prerequisites:

    Warranty only applies on the basis of the following prerequisites:

    The installation work must be carried on by specially trained personnel and the startup of the unit must be

    carried out by the professional technicians of YORK Repair Service Center or personnel of a service agent

    designated by YORK.

    Only those genuine spare parts supplied by YORK should be used.As for all the operation and maintenance specified in this manual, please strictly abide by the requirements

    in terms of the time and frequency.

    Any violation of the above mentioned prerequisites would automatically void the warranty.

    Personnel responsible for the installation of the units should ensure the security of the installation process and take

    responsibility for all the installation work of refrigerant piping, water circulation, electric and other necessary ancillary

    equipments.

    YORK shall not be liable for any personal injury or damage due to improper installation and

    commissioning, unnecessary repair, and failure to observe the provisions and instructions in this manual.

    In case of any doubt during the installation process, please contact YORK Company or its regional offices.

    Other notices

    Checkout

    Upon receiving the unit, damages that may occur in the transport process should be immediately checked. Any significant

    damage, if there is, should be written in the carrier transport documents, and claims should be pursued according to the

    notice instructions. If the parts other than the surface were damaged, please immediately notify the local maintenance

    personnel of York Company.

    Storage

    If the unit is to be stored for a period of time until the installation, protective measures should be taken to prevent the

    damage, corrosion or wear;

    The storage temperature should not exceed 45. Direct sunlight shall be avoided.

    The air-cooled coil heat exchanger on the unit should be covered. Especially, it shall not be stored in the open region of

    construction, lest the fin will be blocked and stained.

    To reduce the possibility of accidental damage (e.g. damaged by the collision, etc.), the unit should be kept in zones

    where the least activities occur.

    Periodical visual inspection should be carried during the storage period.

    During the production of the digital scroll air-condition unit, the design and production

    standards have been strictly observed, to ensure that the un is provided with high-quality operating stat high reliability

    and excellent adaptability.

  • 7/25/2019 IOM-YORK VRF.pdf

    5/106

    Johnson Controls YORK series digital scroll VRF (Variable Refrigerant Flow) systems aim to provide you with a

    comfortable indoor environment. Using the advanced digital scroll technology, it can accurately maintain the ideal room

    temperature while still saving energy. YORKVRF systems smart choice for better living.

    This range of VRF products from Johnson Controls offers the perfect combination of superior product quality, operating

    efficiency and value for money. All units are manufactured under strict quality control with full conformance to ISO 9001 and

    ISO 14001. The Johnson Controls YORKdigital scroll VRF air conditioners consist of ceiling concealed / cassette/

    wall mount indoor units and digital scroll outdoor condensing units.

    The outdoor units are available in vertical air discharge configurations. The cooling capacity ranges from 25.5 to 138kW

    with up to 3 modular units in combination. One outdoor unit can drive up to 48 indoor units (model 340 and above), and no

    matter what the room size or structure, there is always a flexible combination. Ceiling concealed indoor units range from 1.8

    to 17.5kW available in a range of 12 sizes. Ceiling cassette indoor units range from 2.8 to 13kW in 8 sizes, wall mounted

    indoor units are available in 3 sizes with 3.2, 5.3 and 7kW cooling capacities, while ceiling package indoor units range from

    1.8 to

    YORK digital scroll VRF systems are suitable for a variety of applications such as high rise apartment buildings,

    condominiums, houses, offices, schools, shops, mosques, indoor play areas and other similar applications. All units are

    designed with the convenience of the customer and the end user in mind and are factory assembled, tested, and supplied

    internally wired and with refrigerant charge.

    Y D CC 034 H O F L E A 0 C 3

    -- -- -- -- -- -- -- -- -- -- -- -- --

    1 2 3 4 5 6 7 8 9 10 11 12 13

    CP: Ceiling package

  • 7/25/2019 IOM-YORK VRF.pdf

    6/106

    Y D O H 80 E V V -0 C 1 E

    -- -- -- -- -- -- -- -- -- -- -- --

    1 2 3 4 5 6 7 8 9 10 11 12

  • 7/25/2019 IOM-YORK VRF.pdf

    7/106

    Note:

    80 100 120 140 160

    Basic Model YDOH(C)xxEVV-0C1

    YDOH180 32

    YDOH200 32

    YDOH220 32

    YDOH240

    32

    YDOH260 32

    YDOH280 32

    YDOH300 32

    YDOH320 32

    YDOH340 48

    YDOH360 48

    YDOH380 48

    YDOH400 48

    YDOH420 48

    YDOH440

    48

    YDOH460 48

    YDOH480 48

    Max # of

    indoor units

    Variable UnitModular Units

    Outdoor Model Type of UnitCapacity and Combination

  • 7/25/2019 IOM-YORK VRF.pdf

    8/106

    1.2. Physical data

    BASIC MODELS

    Following data table includes Cooling only model and heat pump model. YDOC refer to cooling only model and YDOH refer to heat pump

    model. The data remarks * is only available to heat pump.

    ModelYDOH80

    EVV-0C1

    YDOH100

    EVV-0C1

    YDOH120

    EVV-0C1

    YDOH140

    EVV-0C1

    YDOH160

    EVV-0C1

    Cooling Capacity kW 25.5 28.5 32 41 46

    Heating Capacity kW 29 31.5 35 43 47

    Power Supply 380V 3N ~50Hz

    Compres

    sorskW 7.69 9.07 9.37 11.52 15.10Cooling Power

    InputFan kW 0.45 0.45 0.72 1.14 1.14

    Cooling Current Input A 16 18 20 25 31Compres

    sorskW 7.51 8.08 8.09 9.57 12.30Heating Power

    InputFan kW 0.45 0.45 0.72 1.14 1.14

    Heating Current A 15 16 18 23 27

    Maximum Power Input kW 11.5 13 14 18 21

    Maximum Current Input A 22.2 23.8 29.1 34.1 40.1

    Air Flow m3/min 185 185 235 250 250

    H mm 1650

    W mm 1000 1300Dimension

    T mm 770

    Type - R410ARefrigerant

    Charge kg 9 10 1

    Machine Weight kg 270 270 320 380 380

    Gas mm 19.05 22.23 25.4 28.58

    Liquid mm 9.52 12.7Connecting

    PipesOil mm 6.35

    Maximum number of indoor units 16

    Note:1. Oil balance pipe is only used in module system

    2. Cooling test condition: outdoor dry bulb temperature: 35C; indoor dry bulb temperature/wet bulb temperature: 27C/19C.Heating test condition: outdoor dry bulb temperature/wet bulb temperature: 7C/6C; indoor dry bulb temperature/wet bulb temperature:20C/15C. Tubing length: 10m and height difference: 0m.

    3. Outdoor ambient temperature for air conditioning (recommended): 18~46C(cooling operation), -724 (heating operation).

    4. The indoor unit and outdoor unit must be matched as both C-types.5. The power supply voltage allowed scope

    Outdoor unit: minimum voltage allowed is 342V, maximum voltage allowed is 420VIndoor unit: minimum voltage allowed is 198V, maximum voltage allowed is 242V

    6. Power supply wiring, please refer to relevant regulations of the second part of electrical connections.

  • 7/25/2019 IOM-YORK VRF.pdf

    9/106

    Modular Units

  • 7/25/2019 IOM-YORK VRF.pdf

    10/106

  • 7/25/2019 IOM-YORK VRF.pdf

    11/106

    1.3. Outdoor Unit Dimension

    YDOH80/100EVseries outdoor unit

    Mounting hole spacing

    YDOH120/140/160EVV series outdoor unit

    Mounting hole spacing

    1

  • 7/25/2019 IOM-YORK VRF.pdf

    12/106

    YDOH80/100/120/140/160 outdoor dimension (Unit: mm)

    1.4. Installation Requirements

    The installation space requirement shown in the figure is a reference for cooling operation when the outdoor temperature is 35 .If the

    design outdoor temperature exceeds 35 or the heat load exceeds maximum capacity in all the outside unit, take a even large space on the

    intake shown in below figure.

    When installed as a single unit:

    SizemmModel

    A B C D

    YDOH80160 200 100 500 100

    When installed in serial

    Models A B C D E F

    First 200 500 100 100 200 200YDO180~480EVN

    Second 300 --- 200 --- 400 400

    1

  • 7/25/2019 IOM-YORK VRF.pdf

    13/106

    Note: 1. For First.

    a. Front wall or adjacent unit height should be lower than 1500mm. Backside wall or adjacent unit height should be lower that500mm. No height limitation for the side wall.

    b. If the wall or adjacent unit height beyond the maximum, expand 1/2 h1 and 1/2 h2 distance on the A and B clearance2. For Second no height limitation

    1.5. Location selection

    Select a location for installation that meets the following conditions and get the customers permission.

    Select the location of the unit in such a way that neither the discharged air nor the sound generated by the unit disturbs anyone.

    In places where air short-circuiting will not happen, it should ensure a sufficient space to prevent short c ircuiting cycle when installing

    several units.

    Places where there is no barrier at the air inlet and outlet.

    The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation.

    The piping length between the outside unit and the indoor unit may not exceed the allowable piping length.

    Locations where the units suction vent and outlet vent do not generally face the wind. Wind blowing directly into the suction or outlet

    vents will interfere with the units operation. If necessary, install some kind of obstruction to block the wind.

    The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available

    1.6. Outdoor Installation Base and Placing the Unit

    The Outdoor should be installed on a strong base to avoid the noise. The base could be solid concrete and height should be more than

    150mm.

    Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise. (Refer to below figure)

    The height of the base should be at least 150mm from the floor.

    Secure the unit to its base using foundation bolts. (Use four commercially available M12-type foundation bolts, nuts, and washers)

    The foundation bolts should be inserted 21mm.

    After the outdoor unit has been installed, please

    check whether the outdoor unit is horizontal and the tilt angle

    should be less than 10; if a shock absorber is equipped, please

    inspect whether it is horizontal after the shock absorber has

    been installed.

    We propose to place a shock isolator between the foundation

    and the outdoor unit base (such as the installation of rubber

    isolation pads and damp spring isolators, etc. when rubber

    isolation is selected, the thickness should be above 20mm;

    while select spring damper isolation, the selection criteria

    should be according to unit weight and vibration and noise

    source.) Isolation devices should be correctly selected and

    installed according to design requirements to meet the shock

    isolating requirements and avoid the solid sound transmission

    and the resonance phenomena; Models should normally be

    provided by professional engineers and constructed by

    professional personnel.

    YDOH(C) 80/100/120/140/160 Outdoor unit mounting hole bit

    size (Units :mm)

    Model

    A

    (unit width)mm

    B(mountinghole width)

    mm

    Mountingholequantity

    80/100 1000 798 4120/140/160 1300 1098 6

    Warning:

    When the outdoor unit is higher than the lightning protection

    device of a building, the original lightning protection device

    should be adjusted or a new lightning protector should be

    provided additionally, so that the protection device is higher

    than the unit and meets relevant national requirements.

    1

  • 7/25/2019 IOM-YORK VRF.pdf

    14/106

    1.7. Wiring Diagrams - Outdoor Units

    ELECTRICAL WIRING DIAGRAMS OUTDOOR UNITS

  • 7/25/2019 IOM-YORK VRF.pdf

    15/106

    1

  • 7/25/2019 IOM-YORK VRF.pdf

    16/106

    Part 2: Ceiling Concealed Indoor Units2.1 DATA SHEET CEILING CONCEALED INDOOR UNITS

    1

  • 7/25/2019 IOM-YORK VRF.pdf

    17/106

    DATA SHEET CEILING CONCEALED UNITS (ELECTRIC HEATER MODELS)

    1

  • 7/25/2019 IOM-YORK VRF.pdf

    18/106

    Notes: Standard setting of the ESP is 15Pa, and extra 5Pa (YDCC018-053, Nylon filter) or 12Pa (YDCC066-175, Aluminum filter) pressure

    drop will be caused by the filter, EXV.

    The standard offer is without electric heater. An option exists for auxiliary electric heater for heat pump.

    * Data applicable to heat pump models only.

    2.2. Dimension Data & Piping System

    LAYOUT & DIMENSIONS CEILING CONCEALED UNITS

    Models A B C D E

    YDCC066/078

    1205 1235 1450 1213 222

    YDCC095/115

    1505 1535 1780 1513 237

    Models A B C D E

    YDCC018/

    020/025605 630 830 609 681

    YDCC034 805 830 1030 809 881

    YDCC045/

    053910 935 1150 914 986

    Note: At the delivery, the direction of the air return box lifting lug

    of the electric cabinet is opposite to the direction of the location

    indicated in the figure. When the unit is hoisted, please adjust

    the lifting lug to the indicated direction.

    2.3. Indoor External Pressure Setting

    Ceiling concealed type indoor unit has 5 speed setting point on

    indoor control board. You can adjust and select the 3 speeds for

    High/Middle/Low fan speed according to the external static

    pressure.

    Out factory state, YDCC indoor unit ESP (External static

    pressure) default setting is 15Pa. Please adjust the wring to set

    the ESP as per demand. You can select three speeds

    (High/Mid/Low) from five.

    Three cable colors Red, Brown, Black connected with the

    control board, stand for motor speed for Low, Mid and High

    speed.)

    Following table is just for recommendation.

  • 7/25/2019 IOM-YORK VRF.pdf

    19/106

    Fan wiring board post codeIndoor Models

    5 4 3 2 1

    0Pa Red Brown Black

    15Pa Red Brown BlackYDCC018-053

    30Pa Red Brown Black

    15Pa Red Brown Black

    40Pa Red Brown BlackYDCC066-115

    80Pa Red Brown Black

    15Pa Red Brown Black

    50Pa Red Brown BlackYDCC140-175

    100Pa Red Brown Black

    The illustration shows fan wiring under the board

    2.4. Wiring Diagram Ducted Indoor Unit

    CEILING CONCEALED INDOOR UNITS

  • 7/25/2019 IOM-YORK VRF.pdf

    20/106

    CEILING CONCEALED INDOOR UNITS

    CEILING CONCEALED INDOOR UNITS

  • 7/25/2019 IOM-YORK VRF.pdf

    21/106

    2.5. INSTALLATION OF CEILING CONCEALED INDOOR UNITS

    2.5.1. Required spacing of Ceiling Concealed Indoor

    Units

    Note: at the top of indoor unit should be more than 5mm away

    from the roof; indoor unit at the bottom of water pan should be

    more than 5mm away from the ceiling.Necessary spacing is required around the unit to ensure air

    circulation and to be convenient for maintenance and repair.

    2.5.2. Fixing the Indoor Unit

    The indoor unit is hung on the screw suspender and leveled by the nut. In order to reduce noise and vibration, a shock isolator should be

    provided between the unit and the screw suspender. Check whether the unit is level, so that the condensed water can flow away smoothly.

    1 Hanger

    2 Air return tube

    3 Canvas air duct

    4 Air return port

    5 Drainpipe

    6 Transition joint

    7 Air outlet duct

    8 Diffuser

    9 Diffuser adapter

    Note:

    1. Please note that the pressure drop of YDCC018/020/025/034/053 return air and air outlet should not be higher than 30Pa, and

    should not be higher than 80Pa;

    2. Air return, air outlet, diffuser and air return port should have proper forms and dimensions, or otherwise air delivery may be influenced;

    3. The air outlet cannot be too high from the ground;

    4. The air outlet cannot be positioned at the place where it directly blows the people for a long period;

    5. The air speed at the air outlet is generally about 3m/s; and the air speed at the air return port is commonly about 2m/s;

    6. Use thermal insulation at the connections of air outlet or diffuser with the unit air outlet flange to avoid condensation;

    7. The connection between air outlet duct, air return duct and the unit should be flexible connections to reduce vibration and noise;

    8. Use thermal insulation at the outside of air outlet duct to avoid condensation.

    2

  • 7/25/2019 IOM-YORK VRF.pdf

    22/106

    2.5.3. DRAIN PIPE INSTALLATION

    The condensed water exhaust outlet of the unit is 19mm, See

    the attachment.

    In order to ensure smooth drainage, the drainpipe should have

    2% (20mm for every meter) downward gradient.

    The main drainpipe is determined as per the numbers of the

    indoor units and is required to be larger than or equal to 35mm.

    Thermal insulation should be done for the drainpipe, and the

    thickness of the insulating tube must meet the requirement.

    Please try best to drain water into the floor drains or toilet and

    other places where the water can be easily drained out.

    After the drainpipe has been installed, the water test must be

    carried on, so inspect whether water can be drained out

    smoothly.

    Water can be drained out the exhaust outlet and there is no

    water leak at other places.

    Attention: When the regular grade of the drainpipe cannot be

    guaranteed, an assistant drain pump may be installed.

    2.6. MAINTENANCE FOR FILTER

    We suggest clean the filter for each 1000 running hours. Following figure illustrate the process of remove filer from the unit.

    2

  • 7/25/2019 IOM-YORK VRF.pdf

    23/106

    2

    Part 3. Cassette Type Indoor Units3.1. PHYSTICAL DATA CASSETTE TYPE INDOOR UNITS

    DATA SHEET CASSETTE INDOOR UNITS

  • 7/25/2019 IOM-YORK VRF.pdf

    24/106

    3.2. DIMENSIONAL DATA CASSETTE TYPE INDOOR UNIT

    LAYOUT & DIMENSIONS CASSTEET INDOOR UNITS

    Models A B C D L S H H1 H2 H3 H4 H5

    YDCK028/036 650 650 616 280 570 570 278 250 125 148 183 205

    YDCK046 650 650 616 280 570 570 318 290 145 188 223 245

    YDCK056/072/090 850 850 776 440 730 730 318 290 145 188 223 245

    YDCK110/130 1050 1050 976 640 930 930 318 290 145 188 223 245

    3.3. INSTALLATION SPACE

    Model A(mm) B(mm)

    YDCK028/036 250 10

    YDCK046/056

    /072/090/110/130290 10

    2

  • 7/25/2019 IOM-YORK VRF.pdf

    25/106

    Opening Dimensions and Positions for Suspension Bolts

    Attach is the hanger bracket to the suspension bolt. Be

    sure to fix it securely by using a nut and washer from the

    upper and lower sides of the hanger bracket.

    Dimensions for

    OpeningSuspension Bolt

    Models

    A(mm) B(mm) C(mm) D(mm)

    YDCK028/036/046 590 590 616 280

    YDCK056/072/090 750 750 776 440

    YDCK110/130 950 950 976 640

    3.4. WIRING DIAGRAM OF CASSETTE INDOOR UNITS

    2

  • 7/25/2019 IOM-YORK VRF.pdf

    26/106

    3.5. INSTALLATION CASSETTE INDOOR UNIT

    3.5.1. SELECT LOCATION

    Select an installation site where the following conditions

    are fulfilled and that meets with your customers

    approval.

    Do not install the unit in rooms where flammable gas or

    alkaline acid substances are present.

    Aluminum/copper coils and/or internal plastic

    components can be damaged irreparably.

    Do not install in workshops or kitchens; oil vapors

    drawn in by treated air might deposit on the coils and

    alter their performance or damage the internal plastic

    parts of the unit.

    Having sufficient strength to carry the weight of the unit

    From where condensate can be easily run to drain

    Where optimum air distribution can be ensured.

    Where nothing blocks the air passage.

    Where the false ceiling is not noticeably on an incline.

    Where sufficient clearance for maintenance and service

    can be ensured.

    Where piping between indoor and outdoor units is

    possible within the allowable limit.

    3.5.2. FIXING THE SUSPENDING BRACKET AND UNIT

    Mark position of suspension rods, water lines and

    condensate drain pipe, power supply cables and

    remote control cable.

    Supporting rods can be fixed, depending on the type of

    ceiling.

    Fit suspension brackets supplied with the unit to the

    threaded rods.

    Do not tighten nuts and counter nuts; this operation has

    to be done only after final leveling of the unit, when all

    the connections have been completed.

    Ensure the ceiling is horizontally level, otherwise

    condensate water cannot drain.

    The casing is fixed to the slab with 4 drop rods. The

    rods should have two nuts and washers to lock the unit

    in position. The Cassette brackets will be fixed. When

    lifting the Cassette into position care should be taken

    not to lift the unit by the drip tray, which could be

    damaged.

    Lift unit (without the air panel) with care by its four

    corners only. Do not lift unit by the condensate drain

    discharge pipe or by the piping connections.

    Incline unit and insert it into the false ceiling. Insert the

    rods into the bracket slot.

    With minimum height (see table) false ceilings, it might

    be necessary to remove some T brackets of the false

    ceiling temporarily.

    Using a level guide, line up the unit with a spirit level,

    and keep dimension between the body and the lower

    part of the false ceiling.

    Line up the unit to the supporting bars of the false

    ceiling tightening the nuts and counter nuts of the

    threaded rods.

    2

  • 7/25/2019 IOM-YORK VRF.pdf

    27/106

    After connection of the condensate drain piping and

    piping connections, check again that the unit is level.

    The spaces between the unit and ceiling can now be

    adjusted. Use the drop rods to make the adjustment. Check to ensure the unit is level. The drain will then

    automatically be lower than the rest of the drip tray.

    Tighten the nuts on the suspended rods.

    3.5.3. DRAIN PIPE WORK

    The unit is fitted with a condensate pump with a 500

    mm lift

    The unit is provided with 22mm bore flexible hose 300

    mm long.

    The flexible hose should be fitted into a 22 mm O/S

    polyvinyl tube and sealed. The drain must be installed

    with a downward slope.

    On completion the drain line should be insulated.

    3.5.4. FRESH AIR RENEWAL AND BRANCH DUCT

    The side opening allows separate ductwork to be

    installed for outside air intake and branch ducting.

    Cut and remove anti-condensate insulating material.

    Install your flanges and conduits to casing. Conduit can

    be flexible polyester with spring core or corrugated

    aluminum externally coated (dia.4 in.) with

    anti-condensate material (fiberglass 12-25 mm

    thickness).

    Fresh air There is one (1) opening for connecting a

    fresh air duct for YDCK028/036/046, and for

    YDCK056/072/090/110/130. Order flanges (spigots)

    and blanking plates as accessories separately.

    NOTE:

    1. Branch duct flange (Optional part)

    2. Fresh air duct flange (Optional part)

    3. Blanking plate (Optional part)

    3.5.5. BRANCH DUCT AND FRESH AIR DUCT

    INSTALLATION

    YDCK028/036/046

    YDCK056/072/090/110/130

    2

  • 7/25/2019 IOM-YORK VRF.pdf

    28/106

    BRANCH DUCT FRESH AIRMODEL

    Dia(mm) QTY Dia(mm) QTY

    YDCK028/

    036/046

    100 2 100 1

    YDCK056/072/

    090/110/130100 2 100 1

    3.5.6. BRANCH DUCT AND FRESH AIR DUCT

    POSITIONS

    1. Look for the yellow sticker on the casing for location of

    branch duct or fresh air intake connections.

    2. The sticker is at the center of a knock out hole underneath

    the casing insulation. Use a cutter and follow along the pre-cut

    circular marking as shown and trim off the insulation.

    3. Knock out the pre-cut hole.

    4. Connect the flange on to the opening with 3 mm 12

    mm tapping screws.

    3.5.7. INTER CONNECTING WIRING

    We recommend that shielded cable be used in electrically

    noisy areas.

    Always separate low voltage (5VDC) signal wires from power

    line (230 VAC) to avoid electro-magnetic disturbance of

    control system.

    Do not install the unit where electromagnetic waves are

    directly radiated at the infra red receiver on the unit.

    Install the unit and components as far away as is practical (at

    least 5 meters) from the electromagnetic wave source.

    Where electromagnetic waves exist use shielded sensor

    cable.

    Install a noise filter if any harmful noise exists in the power

    supply.

    3.5.8. MOUNTING FRONT PANEL ASSEMBLY

    Remove return grille from front panel.

    Move the front panel to casing.

    Tighten 4 screws.

    3.6. FILTER REMOVAL FOR MAINTENANCE

    Unlock the two fasteners on the front panel.

    Open the grill downward with care.

    Pull the filter out along the slot.

    Clean the filter and reassemble

    .

  • 7/25/2019 IOM-YORK VRF.pdf

    29/106

    3.7. FAN BLOWER REMOVAL FOR SERVICE

    3.8. CONDENSATE DRAIN PAN REMOVAL FOR

    SERVICE

    4.1. DATA SHEET OF HIGH-WALL INDOOR UNITS

    ModelYDHW032H0NNOA-0C3 YDHW053H0NNOA-0C3 YDHW070H0NNOA-0C3

    Cooling Capacity kW 3.2 5.3 7.0

    Heating Capacity kW 3.7 5.7 7.5

    Power supply V/Ph/Hz 220V/~/50Hz

    Air Flow Rate** m3/h 600 800 1100

    Number of

    Blade

    - 1

    Number of

    Motor

    - 1

    Power

    consumption

    W 60 60 70Fan

    Operating

    Current

    A 0.3 0.3 0.35

    External Static Pressure Pa 0

    Control method - remote control

    Width mm 1080

    Height mm 330Dimension

    Depth mm 220

    Machine Weight kg 15

    Liquid Pipe mm 6.35ConnectingPipes Gas Pipe mm 12.7

  • 7/25/2019 IOM-YORK VRF.pdf

    30/106

    4.2. LAYOUT & DIMENSION

    Model W (mm) H (mm) D (mm)

    YDHW032 1080 330 220

    YDHW053 1080 330 220

    YDHW070 1080 330 220

    4.3. HIGH-WALL INDOOR UNIT INSTALLATION

    4.3.1. PREPARATION BEFORE INSTALLATION

    Before doing any work, check the interior power supply

    cord and the main breaker capacity are sufficient and

    the installation area is sufficient and complies with the

    requirements.

    Check that the power supply available match the name

    plate voltage.

    Electrical work, wiring and cables must be in

    compliance with national and local wiring codes and

    standard.

    Do not use the extension cables. In the case extended

    cables are needed, use the terminal block.

  • 7/25/2019 IOM-YORK VRF.pdf

    31/106

    4.3.2. SELECTION OF THE LOCATION

    Models YDHW032 YDHW053 YDHW070

    A 12cm 12cm 12cm

    B 70cm 70cm 70cm

    C 12cm 12cm 12cm

    D 15cm 15cm 15cm

    Caution: Do not install in a place that cannot bear the

    weight of the unit.

    4.3.3. FIXING THE BRACKET

    1. Place the installation guide pattern on the designated

    installation place and mark the hole position.

    2. Drill a hole and mount installation plate.

    3. After determining the pipe hole position. Drill the hole

    at a slight downward slant towards the outdoor side.

    4. Make 6 mm 4-6 holes, in the wall at the four corners of

    mounting plate (bracket) then insert appropriate

    mounting devices.

    5. Install the mounting plate using 4-6 pieces of mounting

    screw securely at four corners and tighten the screw

    completely. Do not over tighten the screws and deform

    the back plate.

    MODEL 032/053 MODEL 070

    4.3.4. WIRING

    This indoor unit is ready for connection to the outdoor

    unit.

    Open the front grill.

    Remove the screw from electrical box cover, pull the

    electrical box cover away from the unit and set aside.

    Remove the screw from fastener, pull the fastener

    away from the unit and set aside.

    Connect the cable.

    Replace the fastener and electrical box cover

    .

    Or

  • 7/25/2019 IOM-YORK VRF.pdf

    32/106

    CAUTION:

    Never modify the unit by removing any of the safety guards or

    by passing any of the safety interlock switches.

    Connect the interconnecting cable correctly and connect the

    connecting cable to terminal as identified with their respective

    marking.

    Do not damage the conductor core or inner insulation of power

    supply cables and do not deform or crush the cables.

    4.3.5. PIPING

    The auxiliary piping can be connected in the directions shown

    the above diagram. To connect the D, E and F direction, pipes

    will be need to be extended

    CAUTION:

    Bend pipes carefully to avoid flattening or obstructing them if

    the pipes are bent incorrectly, the indoor unit may be unstable

    on the wall.

    Carefully arrange pipes so that pipes do not stick out of the

    rear plate of the indoor unit.

    4.3.6. DRAIN HOSE

    Drain hose is flexible and can be routed to suit various piping

    arrangements. The drain line must include elbow trap (U

    bend).

    Connect a plastic condensate pipe with an internal diameter of

    12 mm.

    NOTE: The drain hose can be connected to the left or

    the right side. For left and left rear piping (Factory

    Standard)

    3

  • 7/25/2019 IOM-YORK VRF.pdf

    33/106

    4.3.7. INDOOR UNIT FIXING

    Thread the indoor unit piping and cable through the hole.

    Hang the top of the unit onto the upper ridge of them in mounting plate.

    Make sure that the unit is correctly hung in place by sliding it to the left, then to the right.

    Press the bottom left and bottom right hand corners of the unit against the mounting plate until the fixing prongs click into place in the

    retainers provided to that effect.

    4.4. OPTIMAL OPERATION

    To achieve optimal performance, please note the following:

    Adjust the air flow direction correctly so that it is not directed on people.

    Adjust the temperature to achieve the highest comfort level. Do not adjust the unit to excessive temperature levels.

    Close doors and windows on COOL or HEAT modes, or performance may be reduced.

    Use TIMER ON button on the remote controller to select a time you want to start the air conditioner.

    Do not put any object near air inlet or air outlet, as the efficiency of the air conditioner may be reduced and the air conditioner may stop

    running.

    Clean the air fitter periodically, otherwise cooling or heating performance may be reduced.

    Do not operate unit with horizontal louver in closed position

  • 7/25/2019 IOM-YORK VRF.pdf

    34/106

    4.4. MAINTENANCE

    3

  • 7/25/2019 IOM-YORK VRF.pdf

    35/106

    3

    Part 5: Ceiling Package Indoor Units5.1 DATA SHEET CEILING PACKAGE INDOOR UNITS

  • 7/25/2019 IOM-YORK VRF.pdf

    36/106

  • 7/25/2019 IOM-YORK VRF.pdf

    37/106

  • 7/25/2019 IOM-YORK VRF.pdf

    38/106

    5.2. Dimension Data & Piping System

    LAYOUT & DIMENSIONS CEILING PACKAGE UNIT

    YDCP018~112 (mm)

    Models A B C D E F G H

    YDCP018/022/028/032/036/040/045 782 620 200 738 705 504 527 162

    YDCP050 982 620 200 938 905 504 727 162

    YDCP056/063/071 1182 620 200 1138 1105 504 927 162

    YDCP080 1182 620 220 1138 1105 504 927 182

    YDCP090/112 1532 620 220 1488 1455 504 1277 182

    5.3. Indoor External Pressure Setting

    Out factory state, YDCP indoor unit ESP(External static pressure)default setting is 15Pa.Please adjust the wring to set

    the ESP as per demand. You can select three speeds (High/Mid/Low) from five.

    Fan wiring board

    Post code

    Indoor Models

    5 4 3 2 1

    0Pa Red Brown Black

    15 Pa Red Brown BlackYDCP018/022/028/032/

    040/045/05/05630 Pa Red Brown Black

    0Pa Red Brown Black

    15 Pa Red Brown BlackYDCP 080

    40 Pa Red Brown Black

    15 Pa Red Brown Black

    30Pa Red Brown BlackYDCP 090/112

    40 Pa Red Brown Black

  • 7/25/2019 IOM-YORK VRF.pdf

    39/106

    The illustration shows fan wiring under the board

  • 7/25/2019 IOM-YORK VRF.pdf

    40/106

    39

    5.4. Wiring Diagram Ducted Indoor Unit

    YDCP018-112 INDOOR UNITS

  • 7/25/2019 IOM-YORK VRF.pdf

    41/106

    NOTE:

    1. Pump application: the power wire of pump should be inserted in the motherboards CN_PUMP port, the float switch (water-lever switch)

    should be inserted in the motherboards water-lever switch port;

    2. TiO2 application: the power wire of TiO2 should be inserted in the motherboards CN_PUMP port, resistance should be inserted in the

    motherboards CN4 port;

    3. Water pump and TiO2 cannot be used at the same time;

    4. Air outlet temperature sensor will be installed when Billing System is required;

    5. Billing System and TiO2 cannot be used at the same time.

    5.5. INSTALLATION OF CEILING CONCEALED INDOOR UNITS

    5.5.1. Required spacing of Ceiling Concealed Indoor Units

    Necessary spacing is required around the unit to ensure air circulation and to be convenient or maintenance an repair.

    YDCP080/090/112

    4

    Noteat the top of indoor unit sh n 20mm away from the roof; indoor unit at the bottom of water pan should be more thanould be more tha

    20mm away from the ceiling.

    YDCP018/022/032/036/040/045/050/056/063/071

  • 7/25/2019 IOM-YORK VRF.pdf

    42/106

    .5.2. Fixing the Indoor Unit

    rew suspender and leveled by the nut. In order to reduce noise and vibration, a shock isolator should be

    5

    The indoor unit is hung on the sc

    provided between the unit and the screw suspender. Check whether the unit is level, so that the condensed water can flow away smoothly.

    Note:

    e note that the pressure drop of YDCP018/022/028/032/036/040/045/050/056 /063/071return air and air outlet should not be

    2 nfluenced;

    y blows the people for a long period;

    monly about 2m/s;

    and noise;

    5.5.3. DRAIN PIPE INSTALLATION

    attachment.

    very meter) downward gradient.

    al to 35mm.

    1. Pleas

    higher than 30Pa, and YDCC080/090/112 should not be higher than 40Pa;

    . Air return, air outlet, diffuser and air return port should have proper forms and dimensions, or otherwise air delivery may be i

    3. The air outlet cannot be too high from the ground;

    4. The air outlet cannot be positioned at the place where it directl

    5. The air speed at the air outlet is generally about 3m/s; and the air speed at the air return port is com

    6. Use thermal insulation at the connections of air outlet or diffuser with the unit air outlet flange to avoid condensation;

    7. The connection between air outlet duct, air return duct and the unit should be flexible connections to reduce vibration

    8. Use thermal insulation at the outside of air outlet duct to avoid condensation.

    The condensed water exhaust outlet of the unit is 19mm, See the

    In order to ensure smooth drainage, the drainpipe should have 2% (20mm for e

    The main drainpipe is determined as per the numbers of the indoor units and is required to be larger than or equ

    Thermal insulation should be done for the drainpipe, and the thickness of the insulating tube must meet the requirement.

    moothly.

    rain pump may be installed.

    1 Hanger

    2 Air return tube

    3 Canvas air duct

    4 Air return port

    5 Drainpipe

    6 Transition joint

    7 Air outlet duct

    8 Diffuser

    9 Diffuser adapter

    Please try best to drain water into the floor drains or toilet and other places where the water can be easily drained out.

    After the drainpipe has been installed, the water test must be carried on, so inspect whether water can be drained out s

    Water can be drained out the exhaust outlet and there is no water leak at other places.

    Attention: When the regular grade of the drainpipe cannot be guaranteed, an assistant d

    4

  • 7/25/2019 IOM-YORK VRF.pdf

    43/106

    In the Johnson Controls YORK VRF System, the combination ratio should comply with the following condition

    50% 130%

    factor at the same time) Rated cooling capacity of

    Note: actor at the same time of indoor units, its the ratio that the max. Total cooling capacity of

    s mentioned above are not met, then another effort at unit selection is necessary.

    .2. PERMITTED TUBING LENGTH AND HEIGHT DIFFERENCE

    Ratedcooling capacity of Indoor Units

    Rated cooling capacity of Outdoor Units

    and Rated cooling capacity of Indoor Units (using

    Outdoor Units.

    is the using f

    indoor units could start at the same time and Rated cooling capacity of Indoor units on the premise of units

    normal operation.

    If the two condition

    6

    OUTDOOR UNIT

    Outdoor unit capacity (kW) 25.5138 kW

    Actual pipe length (m) = a + b150

    + c + d + e + fMaximum permitted pipe lengthMaximum pipe length

    bet itsEquivalent pipe length (m) 175

    ween outdoor/indoor un

    Outdoor above (m) 50Elevation difference between

    outdoor/indoor units = H1 Outdoor below (m) 40Max. Elevation difference

    tween indElevation difference be oor units = H2 (m) 15

    Permitted pipe length for final Equiv r unit

    40branch

    alent pipe length between first branch and last indoo

    (m)

    .3. EQUIVALENT PIPE LENGTH

    ipe length after

    tity of elbow x (equivalent length of

    converging pipe accounts for 1.0 meter equivalent length. When

    mum

    the size for gas pipe should be changed

    in

    6

    Equivalent pipe length is the converted p

    considering the pressure loss caused by elbow etc.

    Equivalent pipe length =

    Actual pipe length + Quan

    elbow) + Quantity of Oil bending x (equivalent length of Oil

    bending)+ Equivalent length of branch. Each branch junction

    accounts for 0.5 meter equivalent length, each branch

    the Y-type equivalent pipe length exceeds 90% of maxi

    permitted pipe length, the size for gas side main pipe should be

    increased by 1-size.

    Example: For 16kW outdoor unit, when the equivalent pipe

    length exceeds 65 m,

    from 22.23 mm to 25.40 mm. When the size for gas side ma

    4

    pipe is increased by 1-size, the derating factor for capacity drop

    will be reduced.

    6.1. COMBINATION RATIO OF CAPACITY

  • 7/25/2019 IOM-YORK VRF.pdf

    44/106

    Equivalent length conversion table of elbows and oil storage elbows

    Tube d orageiameter Equivalent length of Equivalent length of oil st

    mm elbowm elbowm

    9.52 0.18 1.3

    12.70 0.20 1.5

    15.88 0.25 2.019.05 0.35 2.4

    22.23 0.40 3.0

    25.40 0.45 3.4

    28.58 0.50 3.7

    31.75 0.55 4.0

    34.90 0.60 4.4

    38.10 0.65 5.0

    41.30 0.75 5.4

    54.10 0.95 7.0

    .4. PIPE SIZE SELECTION

    6

    Pipe size data sheet:

    4

    Outdoor unit capacity YDOH(C)80 YDOH(C)100 YDOH(C)120 YDOH(C)140 YDOH(C)160 YDOH(C)180

    Between outdoor unit and the first branch tube

    Liquid tube 9.52*0.8 12.7*0.8 15.88*1.0

    Gas tube 19.05*1.0 22.23*1.0 25.4*1.0 28.58*1.0

    Between branch tube and branch tube

  • 7/25/2019 IOM-YORK VRF.pdf

    45/106

    Note:

    When the equivalent pipe length between outdoor units and indoor units is 90m or more, the size of main pipes (both gas side and liquid side)

    must be increased according to the following table.

    Normal Installation 90m or moreOutdoor Unit

    Capacit y Type Liquid Pipe Gas Pipe Liquid Pipe Gas Pipe

    8 HP 9.52 19.05 12.7 22.23

    10 HP 9.52 22.23 12.7 25.4

    12 HP

    14 HP12.7 25.4 15.88 28.58

    16 HP 12.7 28.58 15.88 31.75

    18HP

    20HP

    22HP

    24HP

    15.88 28.58 19.05 31.75

    26HP

    28HP

    30HP

    32HP

    19.05 34.9 22.23 38.1

    4

    Outdoor unit capacityYDOH(C)

    200

    YDOH(C )

    220

    YDOH(C)

    240

    YDOH(C)

    260-300

    YDOH(C)

    320-340

    YDOH(C)

    360-420

    Between parallel outdoor unit and the first branch tube

    Liquid tube 15.88*1.0 19.05*1.0

    Gas tube 28.58*1.0 34.9*1.3 38.1*1.4

    Between branch tube and branch tube

  • 7/25/2019 IOM-YORK VRF.pdf

    46/106

    34HP

    36HP

    38HP

    40HP

    42HP

    44HP

    46HP

    48HP

    19.05 38.1 22.23 41.3

    6.5. SELECTION OF REFRIGERANT PIPE MATERIAL

    1). Refrigerant Pipe

    Use the long straight pipe as much as possible to avoid frequent soldering.

    Copper pipe to be used must comply with the SPEC (size, material, thickness, etc.) proposed by the manufacturer. It must be seamless

    copper pipe.

    Never use the copper which are for plumbing usage (internal surface is not clean enough).

    2). Branch joint, elbow, header

    L type elbow is usually used.

    For branch joint, please use the products recommended by the manufacturer.

    6.6. BRANCH JOINT SELECTION AND DIMENSION

    1) Y-type branch selection and specificationFirst Y-type branch selection (according to outdoor unit capacity)

    Outdoor CapacityHP Y-type Branch

    8HP, 10HP Liquid: YBP-YL2B Gas: YBP-YG2B

    12HP 24HP Liquid: YBP-YL3B Gas: YBP-YG3B

    24HP 48HP Liquid: YBP-YL4B Gas: YBP-YG4B

    The other Y-type branch selection

    Y-type BranchTotal Outdoor unit Capacity (kW)

    Liquid Gas

    x 26 kW YBP-YL1B YBP-YG1B

    26 kW x 31.5 kW YBP-YL2B YBP-YG2B

    31.5 kW x 71 kW YBP-YL3B YBP-YG3B

    71 kW x 180 kW YBP-YL4B YBP-YG4B

    Y-type branch specification and dimension

  • 7/25/2019 IOM-YORK VRF.pdf

    47/106

    Type Import Diameter (mm)

    Converter Tube

    (Interior diameter *

    Exterior diameter)

    YBP-YL1B

    YBP-YG1B

    19.05*22.23 (1)

    15.88*19.05 (1)

    12.7*9.53 (1)

    YBP-YL2B

    YBP-YG2B

    22.23*25.4 (1)

    19.05*22.23 (1)

  • 7/25/2019 IOM-YORK VRF.pdf

    48/106

    YBP-YL3B

    15.88*19.05 (1)

    12.7*15.88 (1)

    YBP-YG3B

    28.58*31.75 (1)

    25.4*28.58 (1)

    19.05*22.23 (1)

    Y

    BP-YL4B

    19.05*22.23 (1)

    9.53*6.35 (1)

    YBP-YG4B

    38.1*41.3 (1)

    34.93*38.1 (1)

    28.58*35.1 (1)

    22.23*19.05 (1)

    22.23*15.88 (1)

  • 7/25/2019 IOM-YORK VRF.pdf

    49/106

    2) Comb-type Branch Selection and Specification

    Comb-type Branch Selection (according to outdoor unit capacity)

    Total Outdoor Unit Capacity (kW) Comb-type Branch

    x 26 kW YBP-CL1B YBP-CG1B

    26 kW x 41 kW YBP-CL2B YBP-CG2B

    41 kW x 71 kW YBP-CL3B YBP-CG3B

    Comb-type branch specification and dimension

    YBP-CG1B YBP-CL1B

    Note

    1. Each Y-type branch has a label of Only for R410A

    2. Definition of interior and exterior diameter of

    converter tube shown in right figure

  • 7/25/2019 IOM-YORK VRF.pdf

    50/106

    YBP-CG2B YBP-CL2B

    YBP-CG3B YBP-CL3B

  • 7/25/2019 IOM-YORK VRF.pdf

    51/106

    6.7. Y TYPE AND COMB TYPE BRANCH JOINT CONNECTION

    1. CONNECTING TYPE BY PURE Y TYPE BRANCH JOINT:

    Outdoor unit

    3. CONNECTING TYPE OF Y TYPE JOINT AND COMB

    TYPE JOINT:

    2. CONNECTING BY PURE COMB TYPE JOINT:

    :

    4. BRANCH JOINT INSTALLATION REQUIREMENTS:

    Y-type branch junction should be installed in horizontal mode or vertical mode.

    Comb-type branch junction should be installed in horizontal

    Wrong Connection

    5

  • 7/25/2019 IOM-YORK VRF.pdf

    52/106

    Caution:

    1. After the comb type distributor, the Y type distributor

    connection cannot be used again or the repeated application

    of the comb type distributor is not allowed.

    2. Branch converging pipe must be installed in horizontal

    direction.

    6.8. SELECTION OF PIPE BETWEEN OUTDOOR

    UNITS

    When multi outdoor units are connected in parallel, outdoor unit

    number should be set, the number should not be coincided.

    1) THE PIPING LENGTH AND DIAMETER BETWEEN

    OUTDOOR UNITS

    Caution:

    1. The length of liquid pipe and gas pipe :L1+ L2 5m,

    L2+ L3 5m, L3+ L4 5m.

    2. The diameter of liquid pipe and gas pipe :

    The size for L1, L3 and L4 will be selected based on the model

    of outdoor Unit.

    L2 = L3 + L4, L0 = L1 + L2

    Select from the following table:

    Capacity Liquid pipe(mm) Gas pipe(mm)

    8 HP 19.05

    10 HP9.52

    22.23

    12 HP 14HP 25.4

    16 HP

    12.7

    18HP 24HP 15.8828.58

    26HP 34HP 34.9

    36HP 48HP19.05

    38.1

    2) OIL BALANCE PIPE

    The size for oil balance pipe is 6.35mm.

    The total length of oil balance pipe between adjacent units is not more than 5m.

    If the distance between two outdoor units is more than two meters, then in the gas piping a 200 mm high vertical trap needs to be installed

    L1 200mm, L2 2m, L3 2m, L4 2m

    5

  • 7/25/2019 IOM-YORK VRF.pdf

    53/106

    3) Installation example - The location of Pipeline

    a) Installation error:

    b) Installation error

    :

    Correct installation method

    For high wall unit, external EXV is standard. No options are available.

    The model of EXV BOX must be consistent with the models of the indoor units.

    Indoor unit EXV BOX Connection Remarks

    YDHW032/053/070 YDEXB-18-4C Nuts Connection

    Refrigerant Pipe Design

    5

  • 7/25/2019 IOM-YORK VRF.pdf

    54/106

    5

    INSTALLATION

    When EXV BOX is installed in the liquid pipe of the indoor unit, the length between indoor unit and EXV box , should not

    exceed 5m. After the installation finished please connect the EXV control line into the indoor unit PCB. Note that the control

    cable connections must be reliable, and the clamp firmly fixed. External EXV box cannot be connected with units supplied

    with built-in EXV, otherwise the indoor unit will have no refrigerant flow.

    WIRE CONNECTION EXAMPLE:

    The EXV Box is supplied with a 3 mm core wire to connect indoor control board and EXV box. If the standard wire is not

    long enough, please connect as explained in below pictures.

    6.10. OIL TRAP DESIGN

    Please use the oil trap design in the piping system as shown below.

  • 7/25/2019 IOM-YORK VRF.pdf

    55/106

    Part 7. Refrigerant Pipe Connection

    7.1. PRECAUTION OF REFRIGERANT PIPE CONNECTING

    Refrigerant piping connections must be YORK corporate training by a professional installation or special designated

    company personnel.

    Tubing precautions:

    The refrigerant tube must be the tubing with designated diameter;

    Requirements of refrigerant pipe diameter and thickness (the minimum thickness) shown below

    Table Min Thickness and Stiffness of Different Tubes

    Exterior Diameter

    [mm (inch)]Min Thickness (mm) Stiffness Level

    6.35 (1/4) 0.8

    9.52 (3/8) 0.8

    12.7 (1/2) 0.8

    15.88 (5/8) 1.0

    O style (tube)

    19.05 (3/4) 1.0

    22.23 (7/8) 1.0

    25.4 (1) 1.0

    28.58 (1-1/8) 1.0

    31.75 (1-1/4) 1.1

    34.9 (1-3/8) 1.3

    38.10 (1-1/2) 1.4

    41.3 (1-5/8) 1.5

    44.5 (1-3/4) 1.7

    1/2H style (straight tube)

    5

    Note: While installing 19.05 tube, if it is O style, the min thickness should not be less than 1.2 mm.

    The distributor must be installed horizontally or vertically;

    The comb type distributor must be installed horizontally;

    The comb type distributor is directly connected with the indoor unit, and no branch connection is permitted;

    Electronic expansion valve (throttling box) must be installed vertically (as shown in the right figure).

  • 7/25/2019 IOM-YORK VRF.pdf

    56/106

    On the air tube, an oil return elbow must be provided for vertical ascending of every 10m.

    The Electronic expansion valve (throttling box) should be installed in the place that insensitive to noise and convenient for

    maintenance.

    Tube connection should comply with the symbol on the box. The box should be in vertical and the hug on top. (It is only for

    the unit with exterior EXV)Refrigerant tube must be fixed in reliable (Indoor refrigerant tube cannot be placed directly on the weak stiffness ceilings)

    It is recommended that a service valve should be installed on both main liquid tube and main gas tube for latter air tight test,

    vacuuming and refrigerant charging.

    7.2. CONNECTION OF REFRIGERANT TUBE

    Tube placing flow process:

    Installing indoor and outdoor units > cutting the tube to the required dimensions > temporarily installing the tubes >

    Nitrogen protection > Welding > blowing off > Airtight test > Vacuum drying > Filling refrigerant > Thermal insulating.

    Strictly observe three refrigerant tubing principles: Keep the tubes dry, clear and air-tight.

    Capping of refrigerant tube:

    During the construction, the pipe mouth should be packed or sealed in a good condition (as shown in the figure) to prevent

    external moisture and sundries from entering the pipe.

    Special attention should be paid when the following operations are carried out:

    1. Prevent the sundries from entering into the pipe when the copper tube is threaded through the hole.

    2. Prevent rainwater from entering into the pipe when the copper tube is threaded to the outside.

    7.3. NITROGEN PROTECTION FOR WELDING COPPER TUBE

    The nitrogen protection must be adopted during welding.

    The pipe should be filled with nitrogen and then welded,

    so as to prevent the formation of oxides in the pipe.

    Attention:

    1. Ensure that there is nitrogen in the pipe during

    welding.

    2. Nitrogen pressure should not be too high and little

    positive pressure is tolerable, or otherwise, the welding

    may not be firm enough.

    5

  • 7/25/2019 IOM-YORK VRF.pdf

    57/106

    7.4. REFFER TO THE RIGHT FIGURE FOR EXAMPLES:

    1. Install the pressure regulator onto the nitrogen bottle;

    2. Use an air-filled tube to connect the pressure regulator

    with the inlet at the side of the liquid tube of the

    outdoor unit.3. Use blind plugs to block all interfaces of the copper

    tubes (including Position B) except for those at the

    side of the indoor unit A.

    4. Open the nitrogen bottle valve and adjust the pressure

    regulator to 5kgf/cm2.

    5. Check whether nitrogen flows into the liquid tube from

    the side of indoor unit A.

    6. Blow wash

    Use the insulating material in hand to prop up the

    nozzle.

    When the pressure becomes too great and cannot be

    propped up, release the insulating material quickly (the

    1stblow wash).

    Then, use the insulating material to prop up the nozzle

    again (the 2nd blow wash).

    When the nitrogen is used to blow wash the inside of

    the tube, loose place a piece of rag or white paper at

    the nozzle for inspection, until no dampness and

    sundries appear.7. Close the main nitrogen valve.

    8. Repeat the above operation for other indoor units,

    including indoor unit B.

    9. After the operation of the liquid tube is completed, the

    above blow-wash operation should be carried out for

    air tubes.

    7.5. AIR TIGHT TEST

    After the refrigerant tubes for outdoor unit and indoor unit has been connected, the airtight test must be done for the

    connecting tube and the indoor unit, and the test pressure should be 4.15MPa. when the pressure slowly rises to the

    specified pressure, it should be maintained for 10min,, and then soapy water or other foaming agent are applied to the

    connection positions, such as welding seams, screwed joints and so on for leak detection. After it has been confirmed that

    the system does not leak, the dwelling test should be performed for the system. The system is charged with air up to the

    pressure of 4.15MPa, which is maintained for 6h and then the manometer readings should be recorded. After 24h, the

    manometer readings are recorded again. No pressure drop means that the air tightness is up to grade. If pressure drop

    occurs, the leaking source should be found out and mended, and then the airtight test is carried on again until it is up to

    grade.

    However, when the temperature at the pressurization is different from the ambient temperature, the pressure change of 0.13kg/cm2

    may occur for every 1 and should be corrected.

    Corrected value = (temperature at pressurization temperature at observation) 0.13

  • 7/25/2019 IOM-YORK VRF.pdf

    58/106

    then conduct leak detection on the outdoor unit connecting pipe ports using halogen leak detection instrument, finally, if the air tight sound,

    then open all of the connected outdoor unit oil stop valve.

    Warning:

    1. When the pressure is applied for the airtight test, both air and liquid tubes are filled at the same time, for fear of pressure unbalance at air

    and liquid sides.

    2. Do not connect outdoor with indoor unit during the air tightness test; otherwise, it may result in nitrogen released into the outdoor unit.

    3. Do not check the R410A leakage using halogen detection instrument.

    Vacuum drying of refrigerant tube

    The so-called vacuum drying is to use a vacuum pump to turn the moisture (liquid) within the tube into the vapor (gas) and then to exhaust

    it out of the tube, so that the inside of the tube is dry.

    Operational sequence of vacuum drying method:

    1. Vacuum drying (the 1st time) Connect a universal meter at the filler openings of the liquid tube and the air tube, and operate the

    vacuum pump for more than 2h (The vacuum degree should be below -755mmHg). If 2h pumping cannot reach the level below -755mm

    Hg, it means that there is moisture within the piping system or exist leak points, and the pumping should be continued for 1h. If 3h

    pumping still cannot reach -755mmHg, please check whether there is an air leak port.

    2. When vacuum holding test is carried out for 1h after the pressure reaches -755mmHg, the pointer of the vacuum meter does not rise,

    indicating that it is up to grade, and the pointer rises, indicating there is moisture or a leak port inside.

    3. Connect the refrigerant tank and liquid pipe service valve for additional refrigerant charging.

    4. Fully open the stop valve, fully open all stop valves in liquid and gaseous pipe.

    ATTENTION:

    1. Vacuum pumping operation is performed from the liquid tube and the air tube at the same time (for various functional parts are attached

    inside the indoor unit and may block out halfway). When the vacuum pumping is carried out, the vacuum pump cannot lose power,

    otherwise the lubricating oil within the vacuum pump will be sucked into the system.

    2. The air displacement of the vacuum pump must not be smaller than 40L/M. before the operation, the vacuum meter must be checked

    out to ensure that its measurement range can reach -755mmHg.

    3. An electronic check valve is needed for the vacuum pump to avoid oil return to the pump.

    7.6. ADDITIOANL REFRIGERANT CHARGING

    The amount of the refrigerant supplemented to each system should be calculated while make engineering drawings. The construction unit

    should add the refrigerant as per the said amount. When there are several systems, please mark the individual refrigerant amount of each

    system, to avoid the confusion of the complemented refrigerant among all systems.

    Note:

    Do not connect outdoor with indoor unit during the air tightness test; otherwise, it may result in nitrogen released into the outdoor unit.

    After the indoor unit air tightness test, connect outdoor with indoor unit, and then filled into (not to be higher than the outdoor unit refrigerant

    pressure) refrigerant and nitrogen mixture at the pressure around 0.4MPa, and then conduct leak detection on the outdoor unit connecting

    pipe ports.

    Air tight inspection and related operations for oil balance pipe connection: module unit combination, evacuate the oil balance pipe between

    the outdoor unit (open the valve on the outdoor unit to use its filling of refrigerant or with an external refrigerant to evacuate the air), and

  • 7/25/2019 IOM-YORK VRF.pdf

    59/106

    into the system.

    4. When the refrigerant cannot be filled in completely, the operation of the compressor should be used during the trial operation to charge

    the liquid refrigerant from the air tube; the air valve and liquid valve should be opened before the startup.

    5. The filling amount of the refrigerant must be measured with an electronic scale and a person should be assigned to supervise the

    charging of the refrigerant, for fear of over charging

    Complement refrigerant calculation table:

    Diameter of liquid tube(mm)Standard refrigerant

    amount(kg/m)

    Total equivalent length of liquid

    tube(m)

    Added refrigerant amount for

    each tube(kg)

    6.35 0.02 L1= 0.02* L1

    9.52 0.06 L2= 0.06* L2

    12.70 0.125 L3= 0.125* L3

    15.88 0.18 L4= 0.18* L4

    19.05 0.27 L5= 0.27* L5

    22.23 0.35 L6= 0.35* L6

    Gross amount of added

    refrigerantM = 0.02* L1+0.06* L2+0.125* L3+0.18*L4+0.27*L5+0.35*L6- corrected value=

    Model of the

    unit

    YDOH

    80/100

    YDOH

    120/140/160

    YDOH

    180/200

    YDOH

    220/240/260

    YDOH

    280/300/320

    YDOH

    340/360

    YDOH

    380/400/420

    YDOH

    440/460/480

    corrected

    value0.6 kg 1.25 kg 1.2 kg 1.85 kg 2.5 kg 2.45 kg 3.1 kg 3.75 kg

    7.7. THERMATL INSUALTION OF REFRIGERANT TUBE

    Incorrect insulation workAll refrigerant tubes between all indoor and outdoor units are

    thermally insulated with thermal-insulating cotton, which must be

    pasted well, so that there shall be no condensate water during the

    operation and the external water must not enter the

    thermal-insulating cotton.

    At the places of wall crossing or corners, the markers should be

    made on the tubes, so that it is convenient for overhauling and

    installation to prevent the tubes between systems are installed

    wrongly.

    PRECAUTIONS:

    1. The calculated results must be recorded (work out a table).

    2. When the outdoor unit is delivered from the factory, the filled refrigerant amount should be 10m. When the distance between the indoor

    unit and the outdoor unit exceeds 10m, the complementary refrigerant should be filled as per the diameter and length of the liquid tube.

    3. After the drying operation of the liquid tube has been completed, fill the liquid refrigerant from the shutoff valve at the side of the liquid

    tube. After the vacuum pumping, the junction valve cannot be changed before the refrigerant is filled, for the replacement may bring air

  • 7/25/2019 IOM-YORK VRF.pdf

    60/106

    Correct insulation work

    Caution:1. If operation ambient temp. Lower than 10C, Liquid pipe must

    be insulated too.

    2. Insulation work must cover all the drainage pipe including joint

    place, otherwise, will cause condensate water collect.

    3. All welding and connection place should be insulated after

    installatio

    8.1. INSTALLATION PRECAUTIONS

    WARNING:

    The designated electric wire must be used to sully power for the unit. Never share the same power source with other electric appliances,

    for fear of resulting in overloading risk. The fuses or breakers matching the operating voltage of the unit must be used. Never use the

    electric wires or fuses exceeding Warning: The accessories specified by the company can only be used. The manufacturers or authorized

    dealers are required to provide installation and technical services. If the control accessories are installed improperly, it may result in such

    consequences as failure of the controller or electric shock, the appointed stages.

    Attention: The grounding line must be installed for the unit. Never connect the grounding line with the gas pipe, water pipe, lightning

    conductor or telephone lines connected to the ground. Improper grounding may cause an electric shock. Please regularly check whether

    the grounding line of the unit is connected firmly with grounding terminals of the unit and grounding electrodes.

    Attention: When the indoor and outdoor units are connected, the strong and weak current lines are distributed separately; for fear that the

    communication and operation of the unit may be affected.

    8.2. POWER SUPPLY AND COMMUNICATION WIRING OF THE WHOLE SYSTEM

    WIRING REQUIREMENTS:

    1. All work related to the electric appliances should be done by the professional electricians.

    2. The power sources of the indoor unit and the outdoor unit should come from the same distribution box. The power lines and control lines

    are provided with sleeves and kept in a certain distance.

    3. The control signal line must be 2-cored shielded cable (RVSP20.75) to prevent the weak current signal from being interfered.

    4. All electric wires and components are tested and conform to relevant national electrical requirements.

    5. Each device (indoor unit and outdoor unit) must be equipped with a breaker and a leak protector.6. The connecting line must be firm and the electric lines or

    other components must be covered with casings for fear of

    loosening, which may result in overheat, shorting or fire.

    7. If the signal cable and power cable are distributed in parallel,

    there exists the possibility of false operation due to

    electromagnetic coupling. The right table shows the

    recommended values of suitable spacing when the control

    cable is distributed in parallel to other cables

    Amperage of power sourceParallel

    spacing (D)

    Below 10A 300MM

    50A 500MM

    100A 1000MMAbove 100V

    Above 100A 1500MM

    8. When the communication line is distributed outdoor, the special trucking must be installed for fear that the communication lines are aged

    and damaged.

    Part 8. Field Wiring

  • 7/25/2019 IOM-YORK VRF.pdf

    61/106

    9. When the power line is provided with trucking, the waterproof treatment must be done to prevent the seeper in the trucking from flowing

    into the power source and resulting in danger. When there are several systems, the markers must be made on the communication lines

    for fear that the communication lines are connected incorrectly.

    8.3. WIRING SPECIFICATIONS

    8.3.1. OUTDOOR UNIT POWER SPECIFICAITON

    Outdoor Unit

    ModelPower Supply

    Maximum input

    current

    (A)

    Circuit Breaker

    (Recommend)

    (A)

    Wire specification ( Recommend )

    (mm2)

    Main power wiring less than 20m/over 20m

    YDOH80 380V 3N ~50Hz 22.2 32A 3P RVV 4mm2/6mm

    2

    YDOH100 380V 3N ~50Hz 23.8 32A 3P RVV 4mm2/6mm

    2

    YDOH120 380V 3N ~50Hz 29.1 32A 3P RVV 4mm2/6mm

    2

    YDOH140 380V 3N ~50Hz 34.1 40A 3P RVV 6mm2/10mm

    2

    YDOH160 380V 3N ~50Hz 40.1 50A 3P RVV 6mm2/10mm

    2

    YDOH180 380V 3N ~50Hz 46.0 63A 3P RVV 10mm2/16mm

    2

    YDOH200 380V 3N ~50Hz 47.6 63A 3P RVV 10mm2/16mm

    2

    YDOH220 380V 3N ~50Hz 52.9 80A 3P RVV 16mm2/25mm

    2

    YDOH240 380V 3N ~50Hz 57.9 80A 3P RVV 16mm2/25mm

    2

    YDOH260 380V 3N ~50Hz 63.9 80A 3P RVV 16mm2/25mm

    2

    YDOH280 380V 3N ~50Hz 69.2 100A 3P RVV 25mm2/35mm

    2

    YDOH300 380V 3N ~50Hz 74.2 100A 3P RVV 25mm2/35mm2

    YDOH320 380V 3N ~50Hz 80.2 100A 3P RVV 25mm2/35mm

    2

    YDOH340 380V 3N ~50Hz 81.7 100A 3P RVV 25mm2/35mm

    2

    YDOH360 380V 3N ~50Hz 87.7 125A 3P RVV 35mm2/50mm

    2

    YDOH380 380V 3N ~50Hz 93.0 125A 3P RVV 35mm2/50mm

    2

    YDOH400 380V 3N ~50Hz 98.0 125A 3P RVV 35mm2/50mm

    2

    YDOH420 380V 3N ~50Hz 104.0 160A 3P RVV 35mm2/50mm

    2

    YDOH440 380V 3N ~50Hz 109.3 160A 3P RVV 35mm2

    /50mm2

    YDOH460 380V 3N ~50Hz 114.3 160A 3P RVV 35mm2/50mm

    2

    YDOH480 380V 3N ~50Hz 120.3 160A 3P RVV 35mm2/50mm

    2

    NOTE

    1. The above recommended cable and circuit breaker selection is based on the requirements of wire trough under 40 ambient condition.

    For the on-site status, please refer to the local norm.

    2. If on-site difference appears (such as capacitor decreasing), please refer to IEC criteria and the requirements of the cable supplier.

    3. For the parallel connection system, circuit breaker should be installed not only in the main power circuit but also in the power circuit of

    each outdoor unit.

    4. Only copper cables can be used.

    5. The table above is for reference only wire specifications, concrete specifications, please wire the norms according to the local selection.

    6

  • 7/25/2019 IOM-YORK VRF.pdf

    62/106

    8.3.2. POWER WIRING SPECIFICATION FOR CEILING CONCEALED INDOOR UNIT

    With Electric HeaterWithout Electric Heater

    With 2# Electric Heater With 4# Electric Heater

    Indoor Unit Model Power Supply Max

    Current

    (A)

    Wire Spec

    (Recommend)

    (mm2)

    Max

    Current

    (A)

    Wire Spec

    (Recommend)

    (mm2)

    Max

    Current

    (A)

    Wire Spec

    (Recommend)

    (mm2)

    YDCC018 220V~50Hz 0.26 1.0 4.76 1.5 --- ---

    YDC 220V~50Hz 0.26 1.0 4.76 1.5 --- ---

    YDC 220V~50Hz 0.26 1.0 4.76 1.5 --- ---

    YDCC034 220V~50Hz 0.35 1.0 4.85 1.5 7.65 1.5

    YDCC045 220V~50Hz 0.46 1.0 4.96 1.5 7.76 1.5

    YDCC053 220V~50Hz 0.52 1.0 7.82 1.5 9.52 1.5

    YDCC066 220V~50Hz 0.85 1.0 8.15 1.5 9.85 1.5

    YDCC078 220V~50Hz 1.0 1.0 10.0 1.5 15.5 2.5

    YDCC095 220V~50Hz 1.29 1.0 10.29 1.5 15.79 2.5

    YDCC115 220V~50Hz 1.31 1.0 10.31 1.5 15.81 2.5

    YDC140 220V~50Hz 2.80 1.0 17.30 2.5 26.30 4.0

    YDCC175 220V~50Hz 3.18 1.0 17.68 2.5 26.68 4.0

    NOTE:

    The table above is for reference only wire specifications, concrete specifications, please wire the norms according to the local selection

    8.3.3. POWER WIRING SPECIFICATION FOR CASSETTE INDOOR UNIT

    Without electric heater With 2# electric heater

    Indoor Unit Model Power supply Maximum current

    (A)

    Wire

    spec(Recommend)

    (mm2)

    Maximum current

    (A)

    Wire

    spec(Recommend)

    (mm2)

    YDCK028 220V~50Hz 0.20 1.0 4.74 1.0

    YDCK036 220V~50Hz 0.32 1.0 4.86 1.0

    YDCK046 220V~50Hz 0.32 1.0 7.14 1.5

    YDCK056 220V~50Hz 0.41 1.0 7.23 1.5

    YDCK072 220V~50Hz 0.52 1.0 9.61 1.5

    YDCK090 220V~50Hz 0.85 1.0 9.94 1.5

    YDCK110 220V~50Hz 1.05 1.0 10.14 1.5

    YDCK130 220V~50Hz 1.09 1.0 10.18 1.5

    NOTE:1. The table above table is for reference only wire specifications, concrete specifications, please wire the norms according to the

    local selection.

    2. All on-site wiring and components must be installed by professionally qualified electrician and must comply with local andnational norms.

    6

  • 7/25/2019 IOM-YORK VRF.pdf

    63/106

    8.3.4. POWER WIRING SPECIFICATION FOR WALL MOUNTED INDOOR UNIT

    Indoor Unit Model

    Heater power

    input

    ()

    Current

    (A)

    Wire spec

    (Recommend)

    YDHW032 0.3 RVV21.5

    YDHW053 0.3 RVV21.5

    YDHW070 0.35 RVV21.5

    8.3.5. POWER WIRING SPECIFICATION FOR CEILING PACKAGE INDOOR UNIT

    Without Electric Heater With 2# Electric Heater With 4# Electric HeaterIndoor

    UnitModel

    Power

    Supply Max Current

    (A)

    Wire Spec

    (Recommend)

    (mm2)

    Max Current

    (A)

    Wire Spec

    (Recommend)

    (mm2)

    Max

    Current

    (A)

    Wire Spec

    (Recommend)

    (mm2)

    YDCP018 220V~50Hz 0.16 1.0 4.66 1.5

    YDCP022 220V~50Hz 0.16 1.0 4.66 1.5

    YDCP028 220V~50Hz 0.20 1.0 4.70 1.5

    YDCP032 220V~50Hz 0.21 1.0 4.71 1.5

    YDCP036 220V~50Hz 0.22 1.0 4.72 1.5

    YDCP040 220V~50Hz 0.30 1.0 4.80 1.5

    YDCP045 220V~50Hz 0.30 1.0 4.80 1.5

    YDCP050 220V~50Hz 0.33 1.0 7.63 1.5 9.43 1.5

    YDCP056 220V~50Hz 0.46 1.0 7.76 1.5 9.56 1.5

    YDCP063 220V~50Hz 0.48 1.0 7.78 1.5 9.58 1.5

    YDCP071 220V~50Hz 0.48 1.0 7.78 1.5 9.58 1.5

    YDCP080 220V~50Hz 0.60 1.0 9.70 1.5 15.10 2.5

    YDCP090 220V~50Hz 0.90 1.0 10.00 1.5 15.40 2.5

    YDCP112 220V~50Hz 1.25 1.0 10.35 1.5 15.75 2.5

    NOTE:

    The table above is for reference only wire specifications, concrete specifications, please wire the norms according to the local selection

    6

  • 7/25/2019 IOM-YORK VRF.pdf

    64/106

    8.3.6. COMMUNICATION WIRING SPECIFICATION:

    RECOMMENDED MODEL OF COMMUNICATION LINE: RVSP20.75

    8.4. FIELD WIRING DIAGRAM

    POWER DISTRIBUTION DIAGRAM OF THE UNIT

    Precautions:

    A system is controlled with an independent switch and several systems cannot be controlled with a switch, or an indoor unit in a system

    share a control switch with other system, while other indoor units are controlled with another switch

    8.5. POWER LINE CONNECTION OF OUTDOOR UNIT

    Note:

    The unit must be grounded reliably.

    6

  • 7/25/2019 IOM-YORK VRF.pdf

    65/106

    8.6. INDOOR UNIT POWER LINE WIRING

    220V, N~, PE, 50Hz

    8.7. COMMUNICATIONS NETWORK

    OUTDOOR UNIT COMMUNICATION LINE WIRING DIAGRAM:

    Multiple outdoor units in parallel, communication wirings are shown below. If there is only one outdoor unit, its no needs to connect.

    Attention:

    Outdoor unit and indoor unit communication line wiring diagram: A

    6

  • 7/25/2019 IOM-YORK VRF.pdf

    66/106

    Attention:

    or unit communication wire can only connect up to 16 indoor units. If the indoor units are more than 16, it needs to be

    or

    Each outdoor unit has a dip switch to set the quantity of indoor unit connected with this outdoor unit. If the setting quantity is not same as

    connection, otherwise it will have a failure.

    ROL OF THE WIRING DIAGRAM:

    . A wired control of one indoor unit.

    or unit

    Each outdo

    connected to another outdoor unit. For example, YDOH480 have three outdoor units, the whole system can connect up to 48 indo

    units.

    the actual unit that connected, the system will not run correctly.

    The indoor unit of TB2, TB3 (TB2 in, TB3out) should not converse

    INDOOR UNIT AND WIRED CONT

    1

    Indo

    . A wired control of a multi-indoor unit (MAX4)2

  • 7/25/2019 IOM-YORK VRF.pdf

    67/106

    3. Indoor unit and remote control receiver wiring diagram:

    9.1. CAUTION:

    Warning:Unit initial boot or reboot after a long power outages, it is important to power on for more than 8 hours before operate the

    unit.

    Warning:Do not attempt to repair the unit by user. If the controller repaired improperly, may cause electric shock or damage to the

    controller, such as the consequences. User if there is any need for repair, please contacts the manufacturer.

    Warning:To carry out the maintenance, please cut off power supply. Do not rinse units with water directly, so as not to lead to

    controllers failure or electric shock.

    Warning: Do not use sharp objects to press the button, which will damage the controller; do not distort or pull the controller wires, so

    as to avoid damages of controller; do not use benzene, diluents or chemical cloth to smear the controller, or else it may lead to bleeding or

    mechanical failures.

    Warning:Air-conditioner use in the season, all the indoor unit must be power, otherwise, may occur as a result of system detects the

    num

    .2. CONTROL SYSTEM INITIALIZATION AND ADDRESS ASSIGNMENT

    ring installation is completed, the system must be initialized before the operation;

    eed to conduct initial setting and address

    Each outdoor unit has a dip switch to set the quantity of indoor unit connected with this outdoor unit. If the setting quantity is not same as

    rk for connecting (X, Y), pay attention to distinguish them from that ofindoor units (A, B).

    ber of indoor unit cannot operate below normal phenomenon.

    9

    Notes:

    After wi

    After installation or any control board in the system are replaced, the unit control system n

    assignment

    the actual unit that connected, the system will not run correctly.

    Each outdoor unit has its own independent communication netwo

    Part 9. Control System Initialization Setting

  • 7/25/2019 IOM-YORK VRF.pdf

    68/106

    During address allocation, mandatory shutdown and test mode, can only be 1# unit to operate, other unit operation is invalid

    Allocated on the outdoor unit code switch settings, must each have a separate outdoor unit settings, including: an outdoor unit address,

    read the following specific operation.

    , to carry out the operation

    Remarks

    the connected indoor unit, quantity, etc.

    Outdoor fan low-noise operation of only 1# set up unit in place effective.

    THE INITIALIZATION STEPS:

    To initialize operation, please carefully

    Attachment: outdoor unit, respectively

    Operation 1#outdoor unit 2#3#outdoor unit

    Unit Model ok ok Factory settings

    This unit to connect the number of

    indoor unitok ok Initialization settings

    The compressor unit switch ok ok Factory settings, the compressor fails, can be re-instated

    Address allocated to the unit code ok ok Initialization settings

    System No. ok The use of DVRF individual charging system need to set up

    Low-noise operation ok When its necessary

    Automatic Address Assignment ok Initialization settings

    Reset procedure ok ok rationsDebugging and maintenance ope

    Test operation ok Debugging unit operation

    9.2.1. INDOOR CONTROL BOARD DIP SWITCH SETTING

    re two dip switches on the indoor control board, DIP1 and DIP2, which is illustrated in following pictureThere a

  • 7/25/2019 IOM-YORK VRF.pdf

    69/106

    IP1 switch setting:

    IP1 switch is for setting the special features of indoor unit.

    Function definition Code position Remarks

    D

    D

    No. DIP 1 Switch

    1 S1 Undefined Back up

    S2=0 Heat pump2 S2 Cooling only / Heat pump settingS2=1 Cooling yonl

    S3=0 Without unctionauto restart f3 S3 Auto restart

    S3=1 With a ctionuto restart fun

    S4=0 Room card control without auto restart4 S4 Room c control

    Roo tartard / Remote

    S4=1 m card control with auto res

    Note

    2 Cooling only / Heat pump

    g of S2 must be consistent with outdoor unit. If the outdoor unit is cooling only the indoor unit should set as cooling only too

    en Dip1 S3=1, the indoor unit has the restart function. The indoor control board will record the setting mode before power off. It will

    estart when power on again, the default setting temperature of cooling is 26and heating 24.

    n the control board, there a room card connection as showed in the picture. If you need this function, please order an accessory from the

    able when it is connected.

    Whatever S4=0 OR S4=1, when the switch signal is from 0 change to 1

    rd

    to on or from open to close), but it can be

    to on or

    S

    The settin

    otherwise it may cause failure.

    S3 for Auto Restart Function

    H

    remember the operation mode and r

    S4 for Room Card Function / Remote control function setting

    O

    factory to connect with the control board and room card. This function will be avail

    It also can be used as a remote controller as same as the room card.

    (from on to off or from close to open), indoor will stop running and reco

    indoor operation mode.

    If S4=0, It will not Auto restart when the switch signal is from 1

    change to 0 ( from off

    controlled by the wire controller or wireless controller.

    If S4=1, It will remember the last operation mode and auto restart

    when the switch signal is from 1 change to 0 ( from off

    from open to close), the default setting temperature of cooling is

    26C and heating 24C.

    N

    his function only detect the status change signal to control the indoor unit, but whatever i t is in open or close status, the indoor unit can

    controlled by local wire or wireless controller.

    .

    ote:

    T

    also be

    Power-down memory function: when abnormal power-down the operation mode will be stored in the indoor unit and then after the

    power-up indoor unit will return the mode automatically

    DVRF_ID V2.00K Indoor control motherboard DIP2 switch setting determines the type of indoor unit, the specific location of the

    corresponding control panel as follows:

  • 7/25/2019 IOM-YORK VRF.pdf

    70/106

    DIP2 switch setting

    DIP2 switch is for setting the indoor model definition. Detailed refer to following figures.

    OOR CONTROL BOARD DIP SWITCH

    ETTING

    8.2.2. OUTD

    S

    Outdoor has 4 Dip-switches for function setting.

    Note:

    DIP 1 is for PC centralization control definition, not available

    1. DIP 2 Setting:

    DIP2 dial code used to set the outdoor unit of some basic

    formation

    here.

    configuration in

    DIP2-6 to DIP2-8 is used for outdoor unit model set table

    DIP2-6 DIP2-7 DIP2- 8 Outdoor unit model

    OFF OFF OFF 8HP

    OFF OFF ON 10PH

    OFF ON OFF 12PH

    OFF ON ON 14PH

    ON OFF OFF 16PH

    ON OFF ON Back up

    ON ON OFF Back up

    ON ON ON Back up

    lid settings

    DIP2-3 DIP2-4 DIP2-5 Outdoor unit compressor whether to allow work

    DIP2-3 to DIP2-5 is used for outdoor compressor unit is va

    OFF OFF OFF Outdoor modules prohibit all compressors running

    OFF OFF ON Outdoor modules with prohibit runningin the permit to run the compressor 3#, 1# and 2#

    OFF ON OFF Outdoor modules of 2# permit compressor operation, and 1# 3# prohibit running

    OFF ON ON Outdoor modules of 2# and 3# compressor operation permit, 1# prohibit running

    ON OFF OFF Outdoor modules within the permit to run the compressor 1#, 2# and 3# prohibit running

    ON OFF ON Outdoor modules within the 1# and 3# permit the compressor to run 2# prohibit running

    ON ON OFF Outdoor modules within the 1# and 2# compressor operation permit, to prohibit operation 3#

    ON ON ON Outdoor all modules are allowed to run the compressor

  • 7/25/2019 IOM-YORK VRF.pdf

    71/106

    Note:

    . The factory default permit all compressors are running, that is 3, 4, 5 are in ON state even though the outdoor only has 2 compressor.

    ctory default setting is all the compressors can run normally, that means 3, 4, 5 all in the status of ON.

    . DIP 3 Setting: DIP3-2 to DIP3-6 is used to set the quantity of indoor units that connected with this outdoor unit. If the setting quantity is

    n

    1

    2. The fa

    3. For the parallel connection system, the whole system cannot run unless at least one digital compressor runs normally. But the module

    that digital compressor is locked will not startup.

    4. In parallel connection system, the whole system cannot run heating mode, unless both at least one digital compressor and normal

    compressor in each module unit are available. But for the unit that digital compressor is locked, it only runs in the startup process, then

    shuts down and exits normal heating operation.

    DIP2-1 to DIP2-2 is used for PC centralization control definition, not available here.

    2

    ot same as the actual unit that connected, the system will not run correctly.

    DIP3-2 DIP3-3 DIP3-4 DIP3-5 DIP3-6

    The module by

    Connecting the number

    Of indoor unit

    OFF OFF OFF OFF OFF 0

    OFF OFF OFF OFF ON 1

    OFF OFF OFF ON OFF 2

    OFF OFF OFF ON ON 3

    OFF OFF ON OFF OFF 4

    OFF OFF ON OFF ON 5

    OFF OFF ON ON OFF 6

    OFF OFF ON ON ON 7

    OFF ON OFF OFF OFF 8

    OFF ON OFF OFF ON 9

    OFF ON OFF ON OFF 10

    OFF ON OFF ON ON 11

    OFF ON ON OFF OFF 12

    OFF ON ON OFF ON 13

    OFF ON ON ON OFF 14

    OFF ON ON ON ON 15

    ON OFF OFF OFF OFF 16

    Note:

    Each outdoor unit can only conn to 16 ind its. If the i units are to another outdoor

    r example, YDOH480 has three outdoor units, the whole system can connect up to 48 indoor units.

    ect up oor un ndoor more than 16, it needs to be connected

    unit. Fo

    DIP3-2 is used to set Outdoor fan low-noise operation. Only master unit need to set if needed, salve unit dont need to set. Suggest you to

    use the default setting OFF, T3 unit are not allowed to set to ON.

    DIP3-1 Description

    OFF Default design

    ON Fan speed wil l be down to low speed appl ication between 21:00 to 8:00for low noise

    7

  • 7/25/2019 IOM-YORK VRF.pdf

    72/106

    7

    3. DIP 4 Setting: dial coDIP4 de modules used to set the address

    9.3. ADDRESS ASSIGNMENT

    nly effective on master unit.Address assignment operation can o

    Note: the procedure press the reset button is equivalent to

    -power control system, when re-change the settings, you can

    SET / VACUUM MODE

    he initial installation must be carried out this operation).

    d then the

    automatic address distribution can be operated. All the indoor

    and outdoor electronic expansion valves can be reset, and

    oller

    m

    n pressing down

    actory default system for only one outdoor unit modules, so

    initial power to detect the number of outdoor unit does

    re

    press the button to make settings effective. System

    power-debug to run:

    1. THE SYSTEM RE

    (t

    The mode can force the system to shut down, an

    opened to maximum 480 steps, which can be used for the

    vacuum pumping of the system, at the time, the indoor unit

    operation should be locked (the operation of the linear contr

    and the telecontroller is not effective). Under the normal alar

    free state, press down the reset/ vacuum Key and then

    release it, the system will operate in this mode for the automatic

    address distribution firstly. If the address is falsely distributed,

    the error address distribution information will be displayed; if the

    address is normally distributed, the indicator light of the reset/

    vacuum mode is shining, and the system will

    be forced to shut down at the same time, and the indoor and

    outdoor EXV will be opened to maximum. Whe

    Notes:

    the Key again, the system will be back out of the reset/

    vacuum mode. The flow diagram is as follows:

    F

    after the

    not match with the factory default, it will have a communication

    failure. System must do the address automatically assignment

    (in accordance with the above steps do the address assignment

    and no needs to care about whether the alarm appeared), and

    only after the success of the allocation, the system will be

    effective the current state of preservation of the outdoor unit,

    inter-unit communication failure automatic recovery

    2. The test operation mode

    According to the environmental temperature the mandatory refrigeration operation is running and locked indoor unit operations (wired

    perations are invalid), running 30 minutes later, collected in accordance with the system parameters tocontrol and remote control o

    determine whether the system is normal ; No alarm in the shutdown mode, press the 1# outdoor unit control panel button "test" more than 5

  • 7/25/2019 IOM-YORK VRF.pdf

    73/106

    seconds after release, the system will enter a test run, when the LED indicator light directed normal refrigeration, then after 30 minut

    there is no alarm, the system automatically exit test mode, while the implementation of the entire system shuts down the operation. When

    after 30 minutes, testing to failure, there are LED indicator light shows that the corresponding alarm information at this time after solve the

    fault, the system needs to reset. The test mode is running, if you press 1# outdoor unit control board "test" button, the system will be a

    mandatory exit test run.

    3. The system forced shut down

    System allows the user to

    es, if

    shutdown the entire system in the debug process.

    t / vacuum" key of 1# outdoor unit immediately, then the release the System will be forced to shut down.

    tween ON and OFF for each pressing.

    eration state will be displayed when starting

    g

    1

    It can be switched among all operation modes for each

    It can be switched between the automatic high middle

    ir speed for each pressing

    1

    System is running press the "rese

    10.1. REMOTES OPERATING INSTRUCTION

    1.1 Exterior d