ipe-etap case-0039.pdf
TRANSCRIPT
-
8/10/2019 IPE-ETAP CASE-0039.pdf
1/2
IndependentPowerEngineers NeverTrusttheMachine,trusttheengineer!
1
Whoarewe?IPE(IndependentPowerEngineers) isanonprofitorganizationpassionateaboutthe
powerengineering industry. Ourmainmandate is to testandexpose thedifferent
issuesanddysfunctionsofdifferentpowersystemsimulationsoftwares.Pleasenote
thatallofour testsaremadeavailablealsoonYouTube for transparency.Look for
IndependentPowerEngineersonYouTubetogetaccesstoourlatestvideos.
Product ETAP
Manufacturer OTI(OperationTechnologyInc)
Version 6, 7.1, 7.5, 11,12.0 and 12.5
Revision Allversions
Operatingsystem Windows7/64Bit
Systemproperties [email protected]:2.00GB
ETAPCASE
0039
Analysis All Load Flow Methods( Adaptive Newton Raphson, Newton Raphson, Fast Decoupled,
AcceleratedGaussSeidel)
Analysisdetail Precision=0.000000001,MaxNo.ofIteration=9999
Issue Wrong results, The incoming current to a node and outgoing current from node are not
equal?
Reason WrongCalculation/ConvergencewhenR(Resistance)isHigherthanInductanceR>2X
(LVCables)
Proposedsolution none
ETAPCASE0039Overview:
Wedecided
to
remodel
an
extremely
simple
real
network
to
test
the
Load
Flow
engine
for
load
flow
in
ETAP
12.5.
Themodelconsistsofasource, twocables (Selected fromETAP library),Twosimilar inductionsmotors (Selected
fromETAPDatabase).
Figure1:SimpleNetworkmodeling
-
8/10/2019 IPE-ETAP CASE-0039.pdf
2/2
IndependentPowerEngineers NeverTrusttheMachine,trusttheengineer!
2
Source(SCrating=40MVA,X/R=10,0.46KV,Isc=50KA)
Motor No.1& 2,: (0.415KV, 100 HP, PF=85.22%, Eff= 95.23%, LRC=625.4%, PF(Locked Rotor)=30.99%,
LRT=103.8%,MaxT=198.4%,Ns=1800,Nr=1782,Slip=1.02%,In=127.8A),ModelSingle2:Singlecagewithdeep
bar,H=1.44,LoadModel:TL=100w3
CableNo.1(CABLEC001):3X1C95mm2,ICEA,AL,1KV,Rubber,(R=0.37671ohm/1000m,
X=0.13884
ohm/1000
m,
Y=0.0),
Length=150m
CableNo.2(CABLEC002):3X1C35mm2,ICEA,AL,1KV,Rubber,(R=0.37671ohm/1000m,
X=0.13884ohm/1000m.Y=0.0),Length=200m
BusbarNo.1NominalVoltage:460V
BusbarNo.2and3NominalVoltages:415V
Observation
Werunloadflowinalltheloadflowmethodsandfollowingresultswillbeobtained.
Figure2:Loadflowresults,demonstratingbranchescurrents
Aboveresultswillbeobtainedwithoutanywarnings.
Doyouthinkresultsarecorrect?WejustwanttoanalysesresultsaboutBusbarsincoming/outgoingCurrents:
B002:incomingActivecurrentis259x0.869=225.07