irp-cdn.multiscreensite.com · 2017. 8. 31. · cbs solar series 1 s 260 0 2 2 7 4 2 25 4 2 neg od...
TRANSCRIPT
CBS Solar Series
260
2
274
2
254
2
NEG
SOd
199.5
2
18 0
-1
19.5 0-0.3
18 0
-1
17.9 0-0.3
180
2
1:9
1:9
3/8 "
17
90
2
Industry Type No.
Length(mm/inch)
Width(mm/inch)
Height(mm/inch)
Total Height(mm/inch)
Approx.Weight (kg/Ibs)
Terninal
Container material
Cells
Nominal Voltage
GC6
260/10.2
180/7.1
254/10.0
274/10.8
30/66.1
AM
PP
3 cell
6 V
Nominal Capacity
Internal Resistance(Approx.)
Self Discharge
Cranking Amps
Max.Discharge
Reserve Capacity
(80°F/27℃)
Charging(25℃)
(Constant Voltage)
240Ah@100 hour rate F.V.(1.75V/Cell)
≤Fully Charged battery(25℃):1.9mOhms
3% of capacity per month@68°F/20℃
1430A@32°F/0℃ 1100A@0°F/-18℃
1650A(5s)
@25A F.V.(1.75V/Cell) 460Min
120Min@75A F.V.(1.75V/Cell)
Initial Charging Current: 66A,2.40-2.45VPC
2.20-2.30VPC
Cycle use
Float use
Mechanical Characteristics Electrical Characteristics
Electrical Characteristics
1.75V/Cell 20HR 10HR 5HR 3HR 2HR 1HR @25A @75AFinal voltage
Amp Hours(AH)@77 F(25 C) o oMinutes of Discharge@80 F(27 C)o o
460 120220 210 190 175 155 130
± ±
±
CBS6V240AH
Features and BenefitsHigh density lead paste and specialized paste formula for deep cycle application.High strength ABS or PP case & cover and valve-regulated construction.Maintenance-free.High capacities.Environmentally friendly, Classified as “ Non-Spillable Battery” for transportation.High tin alloy grids offer: Less gassing, High corrosion-resistant, Low self discharge, Alloy sheeting material for deep cycle applications.Exceptional adaptability to operate at high and low temperature environments.Durable copper and stainless steel terminals for high electric conductivity.Excellent cycle life: 80% DOD 800 cycles.Exclusive electrolyte formula and separator, For protecting the electrolyte density from stratification.Superior design allows for fast charge acceptance and resistance to over-discharge.
Fusion 6V CBS Solar Series provide superior performance, capacities and reliability. Using state of art dry cell technology the CBS series is designed for environmentally sensitive areas that require enhanced cycle life capabilities in commercial, industrial, residential, and private applications. The maintenance-free(VRLA) construction and advanced design features makes the CBS Series the definitive choice for a wide variety of markets; Solar and Renewable Energy Storage; Electric Vehicle and Golf cart; Industrial equipment, Floor Machines, Forklifts, Aerial lifts, and Robotics; Marine, RV, and no-idle solutions; Mobility and Medical Equipment; Telecom, Broadband and Cable TV; UPS systems.
1
100HR240
Number of cyc les(cycles)C
apa
city
(%)
80% D.O.D .
120
100
80
60
40
20
0600 1200 1800 2400 3000 3600 4200
20%D.O.D . 50%D.O.D .
Relative state of charge (%)
Bat
tery
vol
tage
(V) 13. 5
13
12. 5
12
11. 5
110 10 20 30 40 50 60 70 80 90 100
120
100
80
60
40
20
0-20 -10 0 10 20 30 40 50
Cap
acit
y (%
)
oTemperature ( C)
0.1 C0.2 C
1.0 C
2.0 C
110
100
90
80
70
60
50
400 2 4 6 8 10 12 14 1 6 18 20
Storage time: months
Cap
acity
(%)
o40 C o30 C o20 C
-10 0 10 20 30 40 50 60oAmbient temperature ( C)
(V/1
2V)
15.6
15.0
14.4
13.8
13.2
(V/8
V)
(V/6
V)
(V/4
V)
(V/C
ELL
)
10.4
10.0
9.6
9.2
8.8
7.8
7.5
7.2
6.9
6.6
5.2
5.0
4.8
4.6
4.4
2.6
2.5
2.4
2.3
2.2
STAN D BY USE
CYC LE USE
CYCLE SERVICE LIFE IN RELATION TODEPTH OF DISCHARGE
Charging time (hours)
Cha
rged
Vol
ume
(%)
Cur
rent
(XCA )
Vol
tage
(V)
15.0
14.0
13.0
12.0
11.0
0.25
0.20
0.15
0.10
0.05
00 2 4 6 8 10 12 14 16 18 2 0
Constant voltage charge characteristico (0.25CA,25 C)
CHARGED VOLUME
140
120
100
80
60
40
20
0
CHARGE VOL TAGE
CHARG ING CURRENT
CHARGE CHARACTERISTIC CURVE
RELATIONSHIP OF OCV AND STATE OF CHARGE (25℃) SELF-DISCHARGE CHARACTERISTIC
RELATIONSHIP BETWEENCHARGING VOLTAGE AND TEMPERATURE
TEMPERATURE EFFECTS ON CAPACITY
THE
INTERNATIONAL
CERTIFICATION
NETWORKTHE
INTERNATIONAL
CERTIFICATION
NETWORK
testedGermany
Charge / Discharge Tables & Graphs
CBS6V240AH
2
Head OfficeUnit 3076 Hume HighwayLANSVALE NSW 2166Tel: (02) 9755 7851 Fax: (02) 9755 7852www.fusionagmbatteries.com.au
Features and BenefitsHigh density lead paste and specialized paste formula for deep cycle application.High strength ABS or PP case & cover and valve-regulated construction.Maintenance-free.High capacities.Environmentally friendly, Classified as “ Non-Spillable Battery” for transportation.High tin alloy grids offer: Less gassing, High corrosion-resistant, Low self discharge, Alloy sheeting material for deep cycle applications.Exceptional adaptability to operate at high and low temperature environments.Durable copper and stainless steel terminals for high electric conductivity.Excellent cycle life: 80% DOD 800 cycles.Exclusive electrolyte formula and separator, For protecting the electrolyte density from stratification.Superior design allows for fast charge acceptance and resistance to over-discharge.
Fusion 6V CBS Solar Series provide superior performance, capacities and reliability. Using state of art dry cell technology the CBS series is designed for environmentally sensitive areas that require enhanced cycle life capabilities in commercial, industrial, residential, and private applications. The maintenance-free(VRLA) construction and advanced design features makes the CBS Series the definitive choice for a wide variety of markets; Solar and Renewable Energy Storage; Electric Vehicle and Golf cart; Industrial equipment, Floor Machines, Forklifts, Aerial lifts, and Robotics; Marine, RV, and no-idle solutions; Mobility and Medical Equipment; Telecom, Broadband and Cable TV; UPS systems.
Industry Type No.
Length(mm/inch)
Width(mm/inch)
Height(mm/inch)
Total Height(mm/inch)
Approx.Weight (kg/Ibs)
Terninal
Container material
Cells
Nominal Voltage
L16
295/11.6
180/7.1
405/15.9
426/16.8
55.5/122.4
AM
PP
3 cell
6 V
Nominal Capacity
Internal Resistance(Approx.)
Self Discharge
Cranking Amps
Max.Discharge
Reserve Capacity
(80°F/27℃)
Charging(25℃)
(Constant Voltage)
440Ah@100 hour rate F.V.(1.75V/Cell)
≤Fully Charged battery(25℃):6.7mOhms
3% of capacity per month@68°F/20℃
2580A@32°F/0℃ 2010A@0°F/-18℃
3000A(5s)
@25A F.V.(1.75V/Cell) 920Min
270Min@75A F.V.(1.75V/Cell)
Initial Charging Current: 120A,2.40-2.45VPC
2.20-2.30VPC
Cycle use
Float use
Mechanical Characteristics Electrical Characteristics
Electrical Characteristics
295 2
405
2
426
2
180 2
67
105
NEG
50
POS
3/8"
19.5 0-0.3
1:9
18 0 -1
1:9
18 0 -1
1717.9 0-0.3
CBS6V440AH
CBS Solar Series
1
1.75V/Cell 20HR 10HR 5HR 3HR 2HR 1HR @25A @75AFinal voltage
Amp Hours(AH)@77 F(25 C) o oMinutes of Discharge@80 F(27 C)o o
460 120400 380 320 315 280 230100HR
440
Number of cyc les(cycles)C
apa
city
(%)
80% D.O.D .
120
100
80
60
40
20
0600 1200 1800 2400 3000 3600 4200
20%D.O.D . 50%D.O.D .
Relative state of charge (%)
Bat
tery
vol
tage
(V) 13. 5
13
12. 5
12
11. 5
110 10 20 30 40 50 60 70 80 90 100
120
100
80
60
40
20
0-20 -10 0 10 20 30 40 50
Cap
acit
y (%
)
oTemperature ( C)
0.1 C0.2 C
1.0 C
2.0 C
110
100
90
80
70
60
50
400 2 4 6 8 10 12 14 1 6 18 20
Storage time: months
Cap
acity
(%)
o40 C o30 C o20 C
-10 0 10 20 30 40 50 60oAmbient temperature ( C)
(V/1
2V)
15.6
15.0
14.4
13.8
13.2
(V/8
V)
(V/6
V)
(V/4
V)
(V/C
ELL
)
10.4
10.0
9.6
9.2
8.8
7.8
7.5
7.2
6.9
6.6
5.2
5.0
4.8
4.6
4.4
2.6
2.5
2.4
2.3
2.2
STAN D BY USE
CYC LE USE
CYCLE SERVICE LIFE IN RELATION TODEPTH OF DISCHARGE
Charging time (hours)
Cha
rged
Vol
ume
(%)
Cur
rent
(XCA )
Vol
tage
(V)
15.0
14.0
13.0
12.0
11.0
0.25
0.20
0.15
0.10
0.05
00 2 4 6 8 10 12 14 16 18 2 0
Constant voltage charge characteristico (0.25CA,25 C)
CHARGED VOLUME
140
120
100
80
60
40
20
0
CHARGE VOL TAGE
CHARG ING CURRENT
CHARGE CHARACTERISTIC CURVE
RELATIONSHIP OF OCV AND STATE OF CHARGE (25℃) SELF-DISCHARGE CHARACTERISTIC
RELATIONSHIP BETWEENCHARGING VOLTAGE AND TEMPERATURE
TEMPERATURE EFFECTS ON CAPACITY
THE
INTERNATIONAL
CERTIFICATION
NETWORKTHE
INTERNATIONAL
CERTIFICATION
NETWORK
testedGermany
Charge / Discharge Tables & Graphs
CBS6V440AH
2
Head OfficeUnit 3076 Hume HighwayLANSVALE NSW 2166Tel: (02) 9755 7851 Fax: (02) 9755 7852www.fusionagmbatteries.com.au