Diagnostic Techniques of Power
Transformers
ISEI 2010 –Short Course San Diego – June 6th 2010
Ali Naderian, P.Eng., PhD.Kinectrics Inc.
Toronto, [email protected]
+1-416-797-3724
1
![Page 2: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/2.jpg)
Introduction• Myself:
ITC ( Siemens Power Transformer) 1998-2000 Designed a 3-step cascade Testing Transformer
(2000) Rebuilding High voltage Lab of the University of
Waterloo (2005) Kinectrics (Ontario Hydro Research) since 2007
working at the HV Lab, as well as Testing on Transformers/Cables
2
![Page 3: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/3.jpg)
Objectives
• Identify the diagnostic and condition assessment methods
• Explain the selected conventional testing methods
• Identify innovative techniques of transformer diagnostics
• Interpret the test results of case studies3
![Page 4: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/4.jpg)
Contents• Routine (conventional)
Winding/Insulation Diagnostics Tests:Polarization Index (insulation resistance)Turn ratioDC resistanceShort circuit ImpedanceExcitation CurrentPower Factor, capacitance
• Oil Tests:DGAOil quality tests (Dielectric, Power factor, …)
4
![Page 5: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/5.jpg)
Contents• Advanced Condition Assessment
Techniques:
Partial Discharge (PD) :Electrical/Acoustic
Dielectric Frequency Response (DFR)
Frequency Response Analysis (FRA)
5
![Page 6: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/6.jpg)
Polarization Index
• Propose: Tests : Winding Insulation + Oil Overall integrity of the winding insulation Verify that the state of dryness of insulation
• Definition:Polarization Index : PI=R10-min /R1-min
Trend Measure of dielectric deterioration
Absorption ratio : AR=R60s /R15s
• Test Method: H-LG, L-HG, HL-G Utest=5 kV-DCTime= 15 s, 60 s, 10 min
6
![Page 7: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/7.jpg)
7
Insulation Resistance Model
iL iC
ReqRA is not a fix resistance:
![Page 8: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/8.jpg)
8
Test Arrangement
kV 20 °C 30 °C 40 °C 50 °C 60 °C
6.6 400 200 100 50 25
6.6-19 800 400 200 100 50
22-45 1000 500 250 125 65
≥ 66 1200 600 300 100 75
Typical Insulation Resistance MΩ
When to use Guard?
![Page 9: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/9.jpg)
9
Interpretation• R Needs temp correction
k=1.5 for oil-filled transformer
k=30 for untanked or dry-type transformers
• 1.3≤AR≤3.0: Dry Transformer
• PI (Large Power transformers)
1- Make sure transformer is grounded before and after test.
2- The energy stored must be discharged safely by short-circuiting at least x4 of the test period.
Winding
Winding
KVA
kUR 60
PI ConditionLess than 1 Dangerous
1.0 - 1.1 Poor (wet or poor dielectric)
1.1 - 1.25 Questionable1.25 - 2.0 AcceptableAbove 2.0 Very Good
![Page 10: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/10.jpg)
Turn Ratio (TTR)
• r= Np/Ns=Ep/Es
• Deviation indicates problem in either of windings High-resistance connections in the lead circuitry or
high contact resistance in tap changers, open circuits Low resistance: shorted turn-to-turn
• Minimum accuracy : 0.1%
10
IEEE 62, IEEE C57.12.00 IEC 60076-1
+/-0.5% nameplate ratio The lesser of +/-0.5% of declared voltage ratio or 0.1*Uk%
![Page 11: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/11.jpg)
Test Arrangement
11
![Page 12: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/12.jpg)
• Auxiliary Transformer 230kV/13.8kV
12
Test Case
Nothing wrong with transformer!Tap changer index is off by one position. Position 1 is 2, position 2 is 3, …, position 5 is 1.
![Page 13: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/13.jpg)
DC Resistance
13
• Measure of winding resistance • For temp-rise=55°C corrected to 75°C• For temp-rise=65°C corrected to 85°C• Before test:
(IEEE)different between top and bottom temp ≤5°C
(IEC) 3hours rest time
• Test current ≤10% of rated current• DC resistance should be ≤ 2% factory
test
![Page 14: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/14.jpg)
DC ResistanceCan detect:• Shorted-turns• Loose connection on bushing• Loose connections or high-contact
resistance on tap changers• Broken winding strands• The above issues leads to hot-
spots, generates gases DGA
14
![Page 15: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/15.jpg)
Short circuit impedance• Applications:
Investigate winding deformation confirm the name plate values To check shipping as a receiving
(pre- commissioning test) • If possible run three-phase if not
feasible it can be done single-phase , then average the results
15
![Page 16: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/16.jpg)
Short circuit impedance
16
Apply voltage and measure current in HV side while shorting out the dual leg of the LV side.
Applied voltage is 100 V-500 V Watch the current in LV side LTC is in neutral position
3-phase Single phase
![Page 17: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/17.jpg)
Short circuit impedance• If deviation exists it could be due to:
Type of excitation (1-phase versus 3-phase) Different instrumentation Winding deformation
17
• Deviations of over ± 3% from the benchmark Per Phase Tests could be related to winding deformations.
• Even 3-phase test result may be different from nameplate because of the Vtest.
![Page 18: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/18.jpg)
Excitation Current • Can possibly detect: Core problems such as:
Shorted core laminations poor joints
Winding problems such as: short circuit (turn to turn) open circuit poor connections
LTC problems such as: high hesitance connection open circuitCoking and wear of LTC and DETC contacts
18
![Page 19: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/19.jpg)
Excitation Current Test
• Factory tested at rated voltage (no-load)
• If possible run three-phase if not ,can be done single-phase.
• Perform Excitation Test before any DC test: DC test leaves residual magnetism in the core.
• Voltage is applied to HV :5kV or 10 kV• LTC set to: 1- Neutral , 2- 1 step up, 3- 1 step down
4- Full raise , 5- Full lower
19
![Page 20: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/20.jpg)
Excitation Current Setup
20
![Page 21: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/21.jpg)
Excitation Current Pattern
21
H1 H2 H3
ExcitationH1-H0
Similar to H3-H0
H2-H0
Higher R results higher
excitation
current
![Page 22: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/22.jpg)
Excitation Current Results
22
Possible patterns
Characteristics of
H-L-H • 3 leg core-type (Most common)• 5 leg core or shell type with a delta secondary
L-H-L • 3 leg core-type ,Y secondary, inaccessible neutral
All equal
• 5 leg with Y secondary• 3 single phase connected as 3- phase• Shell-type with Y-connected secondary
All different
• Can be due to magnetized core• Defects, Faults
Excitation current
Criteria to detect defect
Iext<50 mA The difference between 2 higher current >10%
Iext >50 mA The difference between 2 higher current >5%
![Page 23: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/23.jpg)
Excitation Current with LTC
23
When the Autotransformer is in the bridging position the excitation current goes up.
![Page 24: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/24.jpg)
I
IC IR
Power Factor TestingDissipation Factor or is
the ratio of the resistive current to capacitive current
24
Dissipation factor : tan=IR/IC
I=IC+IR
Power Factor : P.F.= IR/I
To check the condition of the capacitive insulation: Between windingsBetween winding and coreBetween winding and tank
![Page 25: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/25.jpg)
Capacitances
2-Winding Transformer
1 phase of 3 phases shown
25
• CH: HV bushing + HV winding +Oil• CL: LV bushing + LV winding + Oil• CHL: Both windings+ barriers + Oil
![Page 26: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/26.jpg)
Test Arrangement3 test modes: Ungrounded Specimen Test (UST)
Grounded Specimen Test (GST)
Grounded Specimen with Guard (GST-g)
26
![Page 27: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/27.jpg)
Test Arrangement
One of the most common source of measurement error: Neutral is not properly connected.
27
Test Mode Energize Ground Guard Winding
1 UST HV - - CHL
2 UST LV - - CHL
3 GST HV LV - CH+CHL
4 GST-g HV - LV CH
5 GST LV HV - CL+CHL
6 GST-g LV - HV CL
Usually 6 tests are performed to confirm the values:
![Page 28: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/28.jpg)
P.F. Interpretation Power Factor Insulation ConditionAbove 1.0% Dangerous
wet transformer0.7 – 1.0 Investigate0.5 – 0.7 Deteriorated
Less than 0.5 Good
28
3 winding transformer
Shielding between LV/HV
IEEE Std 62: Service aged transformers : P.F.<2%
![Page 29: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/29.jpg)
Oil Test: DGA
• Rogers Ratio• Doernenburg Ratio• Duval Triangle • IEC1 - (1st Edition 1978)• IEC2 – (2nd Edition 1999)• ANSI/IEEE (C57.104-1991)•CIGRE Method• Laborelec• Japanese Method• Russian Method
29
![Page 30: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/30.jpg)
Key Gas Method
30
Key Gas
Secondary Gas Fault Pattern Possible Root cause
H2
CH4 and minor C2H6
and C2H4
Low energy Partial
Discharge
Aging of insulation, possible carbon particles in oil, poor grounding of metal objects, loosed lead, floating metal or contamination
C2H4
(ethylene)
CH4 and minor H2 and C2H6(ethane)
Oil overheatingPaper insulation destroyed. Metal discoloration. Oil heavily carbonized.
C2H2
H2 and minor CH4 and C2H4
High Energy Arcing
Poor contacts in leads, weakened insulation from aging, carbonized oil.
CO, CO2
If the fault involves and oil-impregnated
structure CH4 and C2H4
Conductor Overheating
Overloading or cooling problem, bad connection in leads, stray magnetic flux, discoloration of paper.
![Page 31: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/31.jpg)
Duval Triangle
31
%C2H2=100x/(x+y+z);
%C2H4 = 100y/(x+y+z);
%CH4 = 100z/(x+y+z),
T1: Low-range thermal fault (below 300 C)T2 :Medium-range thermal fault (300-700 C) T3 :High-range thermal fault (above 700 C) D1: Low-energy electrical dischargeD2 :High-energy electrical dischargeDT: Indeterminate - thermal fault or electrical discharge.
x = (C2H2); y = (C2H4); z = (CH4), in ppm
![Page 32: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/32.jpg)
IEEE Std C57.104
32
• Four-condition DGA guide to classify risks to transformers with no previous problems.
• Uses combinations of individual gases and total dissolved combustible gas concentration (TDCG).
The three-ratio version of Rogers
ratio Method uses the
following ratios: R1= C2H2/ C2H4 ,
R2= CH4/H2 , R3= C2H4/ C2H6
R2<0.1 0.1<R1<1 R3<1
1<R3<3
R1>1
R1<0.1 R3<1
1<R2<3
Gas Inputs R1,R2, R3
1<R3<3
R3>3
R3>30.1<R1<1
Case 0No fault or it cannot be detected
Case 3Low Temp Thermal Overloading
Case4Thermal <700 oC
Case5Thermal >700 oC
Case1PD low energy
Case2High energy arcing
Y
Y YY
Y Y
Y
Y
Y
Y
Y
Y
YN
N N
N
N
Rogers Fault Tree
![Page 33: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/33.jpg)
IEEE Std C57.104
33
• Not all techniques were applicable in all cases
•CIGRE: CO2/CO <3 Excessive paper degradation
• If most of Gas levels < 1 and one or two is high, the error of regular methods might be high. Call your judgment, do not forget Key Gas Table.
Status H2 CH4 C2H2 C2H4 C2H6 CO CO2 TDCGCondition 1
100 120 35 50 65 350 2500 720
Condition 2
101-700 121-400 36-50 51-100 66-100 351-570
2500-4000
721-1920
Condition 3
701-1800
401-1000 51-80 101-200 101-150
571-1400
4001-10000
1921-4630
Condition 4
>1800 >1000 >80 >200 >150 >1400 >10000 >4630
![Page 34: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/34.jpg)
Case 1:750 MVA,500kV
34
Date H2 CH4 C2H2 C2H4 C2H6 CO2 CO TCGppm/day
April 2010
10 5 2 6 2 1398 277 47,800
May 2009
10 5 2 2 2 155 71 0.13
Key Gas IEC IEEE Roger’s ratio
IEEE Duval Method
Doernenb-urg Ratio
Suggestion
Conductor Overheating
Partial discharge or power discharge
Not conclusive
TCG levels indicate excessive decomposition
D1:Disch--arge of low energy
No diagnosis
DGA every day, On-line PD test (electric follow up with acoustic) , temporary removal from service for off-line tests
![Page 35: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/35.jpg)
Case 2:300 MVA, 420 kV
35
• The content of hydrogen detected by the on-line monitoring system increased continuously.• Concentration of hydrogen is only dependent on the oil temperature.
• Oil used was uninhibited oil considered as “moderately stray gassing”• Avoid misleading of DGA pattern (Stray Gassing) caused by catalytic effects of zinc surfaces and oil .
![Page 36: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/36.jpg)
Oil Quality TestsRecommended oil quality tests for insulating oil
[IEEE Std C57.106-2006]
36
Test Dielectric Strength
Dissipation Factor
Interfacial tension (IFT)
Neutralization number (acidity)
PCB
Standard ASTM D1816 -97 (1 mm gap)ASTM 877[min]
ASTM D924-99 @ 25 0C[max]
ASTM D-971-91[min]
ASTM D974-92[max]
ASTM 4059-91[max]
Limit (new oil)
1816:23kV877: 26 kV
0.1% 35 mN/m 0.03 mg KOH/g
2
Limit (service aged oil)
1mm gap:23kV
0.5% 24 mN/m 0.2 mg KOH/g
50
![Page 37: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/37.jpg)
Post Failure Test Interpretation
37
Suggested Problem Category
Test Data1st priority 2nd priority 3rd priority
Turn-to-turn fault Out of tolerance ratio
Low winding resistance
Excitation increase
Damage to major insulation
High power factor Low insulation resistance
Abnormal DGA
Lead and terminal issues
Abnormal DGA, trend inclines
DC resistance Excitation increases if load
increasesThrough fault mechanical
damage
FRA shows different pattern for faulty phase
Deviation of exciting current
Change in impulse
Core heating Abnormal DGA Low core ground resistance
Excitation increases
Moisture High insulation power factor
Low dielectric oil test
Low insulation resistance
![Page 38: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/38.jpg)
Time for Break!
38
![Page 39: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/39.jpg)
Selected Advanced Techniques
• Partial Discharge
• Dielectric Frequency Response (or Frequency Domain Spectroscopy)
• Frequency Response Analysis
39
![Page 40: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/40.jpg)
Partial Discharge
40
Draft IEEE PC57.113™
IEEE Std C57.127
![Page 41: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/41.jpg)
Partial Discharge-IEC 60270
41
• PD should be done along with induced voltage test• Background noise < 100 pC
max (pC)=100 at 110%Urated max (pC)=300 at 130%Urated max (pC)=500 at 150%Urated
Wide-Band PD measurement Narrow-band PD measurement
![Page 42: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/42.jpg)
Partial Discharge Measurement
42
• Signal from coupling capacitor or bushing tap
coupling device in series with the coupling capacitor frequently used circuit in test laboratories
Via Bushing Tap often applied in on-site offline /online PD investigations
![Page 43: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/43.jpg)
Bushing Tap Sensors
43
To get down the voltage to U, it is necessary to use capacitance (Cz)
Possible power that can be taken from the test tap:
To avoid bushing damage:
![Page 44: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/44.jpg)
Partial Discharge Patterns
44
Corona at HV electrode Corona at Ground
Floated metal object Creeping discharges
1 Cycle screenshot 1 Cycle screenshot
1 Cycle screenshot PD Resolved Pattern
![Page 45: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/45.jpg)
UHF Measurement Via Oil Valve
45
• PD-signals :UHF frequency range (300 MHz – 1 GHz)
• Sensor application at oil valves, which are available e.g. for oil filling or draining.
Case1 Case2
Courtesy of LDS GmbH (Lemke)
Drawback: High attenuation (high frequency); cannot determine which phase?; Hard to use for ball valves.
![Page 46: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/46.jpg)
How to distinguish PD?
46
• External noises appear often independent from the applied AC test voltage level.
• Pulse-shaped noises may appear unsynchronized with the applied AC test voltage, whereas PD pulses occur always phase-correlated.
• Rise-time of PD is different from noise signals are different from pulse.
• Pattern recognition techniques help a lot!
![Page 47: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/47.jpg)
T-F Classification Map
47
![Page 48: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/48.jpg)
Acoustic PD :Off-line/On-line
48
1. All-Acoustic (minimum 3 sensors)2. Acoustic with Electrical PD trigger
Velocity of sound in oil :1413 m/s at 20 °C
![Page 49: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/49.jpg)
Acoustic PD
49
• Vibration noises (core,fan,pump) <50kHZ• Band Pass filter: f1=50 kHz, f2=350 kHz• Propagation path: direct , indirect
Sensor locations when phase of PD source is not known
![Page 50: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/50.jpg)
Acoustic PD
50
• Before placing the AE transducer, wipe the area (dirt, oil, bugs,…).
• Acoustic couplant needed for enhancing the mechanical and acoustical coupling between the transducer and the tank surface.
• A sound transmitting epoxy to be used if the mounting location is non-magnetic.
• Magnetic tank shielding causes extra signal attenuation.
• LTC operation contains a high electromechanical energy that usually propagates through the entire transformer. To be distinguished in post-analysis.
• Initial place to start: one sensor in the bottom connection of each bushing.
![Page 51: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/51.jpg)
Application of Acoustic PD
51
• When electrical PD is detected, for confirmation and source location
• When DGA indicates the possible presence of PD
• For PD detection during factory impulse testing
• When static electrification is suspected
![Page 52: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/52.jpg)
Acoustic PD
52
• Electrical PD has a threshold 300 (500)pC. There is no similar threshold for acoustic systems.
• A strong signal buried deep within a winding may be very weak by the time it reaches the acoustic sensor.
• Sometimes longer monitoring period is necessary: weeks
• Only high PD levels can be detected.• The correlation is weak between measured and real
PD level due to attenuation.
Wall propagationDirect signal
![Page 53: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/53.jpg)
Test Case:
53
Single phase autotransformer: 500/230/13.8 kV,146/194/243 MVA
• After two years in operation started gassing.
• Acoustic monitoring for 5 days :significant activity
Load is minimumVoltage is maximum
![Page 54: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/54.jpg)
Test Case:3-D Plot
54
![Page 55: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/55.jpg)
Dielectric Frequency Response
55
• “Dielectric Frequency Response” also called “Frequency Domain Spectroscopy”
• DFR is Power factor measured in a wide range of frequency (mHZ-kHZ) unlike conventional 60Hz measurement.
Power Factor @60Hz DFR
![Page 56: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/56.jpg)
How to Measure DFR
• Measurement modes: UST, GST, GTS-g
56
![Page 57: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/57.jpg)
Application
• Originally to Estimate the Moisture Content
• Now extend to find out other problems : Insulation Contamination Degradation of overall insulation system High resistance contacts Bushings issues ….
57
![Page 58: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/58.jpg)
DFR to Estimate Moisture
58Using DFR curve, the Wt% can be estimated.
![Page 59: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/59.jpg)
How DFR Estimates Moisture?• X-Y Model of Insulation
59)(
1
)()(
1
)(
1
boardoilspacercomb CCCC
![Page 60: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/60.jpg)
How DFR Estimates Moisture? Oil
– Non-polar liquid; r = 2.2 Pressboard, oil impregnated cellulose
– More polar; r = 4.5
– Sensitive to moisture
60
![Page 61: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/61.jpg)
Why moisture is important?
61
![Page 62: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/62.jpg)
Conventional Moisture Estimation
• Low accuracy at low temperatures because the water has migrated to the paper
62
MOISTURE EQUILIBRIUM BETWEEN OIL AND CELLULOSE
Uncertain area
![Page 63: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/63.jpg)
Conventional Method Cons
• Transformer needs to reach Thermal Equilibrium
• Oil Moisture changes with temperature
• Not accurate in lower temperatures
• Aged oil resolved higher Water% than New oil
63
DFR found to be the most accurate method to estimate the insulation moisture.
![Page 64: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/64.jpg)
DFR & Moisture %
64
![Page 65: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/65.jpg)
Test Case :500 MVA 230kV GSU,1976
• CH and CL increased 100%!
• DGA had gone up in the past but was constant lately.
• The unit was taken out.
• One reason for increasing P.F. is moisture. Should the unit be dry-out?
• Just shipping to the closest maintenance cost $500K.
• Kinectrics offered DFR to diagnose.65
Measurement Year 2000 Year 2009CHL 0.16 0.2CH 0.29 0.59CL 0.48 0.99
Conventional Power Factor :
![Page 66: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/66.jpg)
Test Case
• CHL is normal showing Water content 0.5-1%
• CL does not match with any moisture model curve, So it is not moisture.
• The whole curves shifted up. Insulation conductivity has changed.
• Conclusion: Contamination, no dry-out needed. Shipped out to replace the windings.
66
After opening tank: carbon deposit found on LV and HV winding due to
arcing of tank shipping bolt to the core.
DFR Result
CHCL
CHL
![Page 67: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/67.jpg)
DFR Is Able to:Estimate the moisture content of power
transformers accurately. Identify unsatisfactory conditions during routine
testing. Detect contamination on insulating system. Characterize transformers to avoid potential
catastrophic failures.
67
Drawbacks:
Needs basic transformer design data Needs expertise to interpret results
![Page 68: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/68.jpg)
FRA (SFRA)
Two methods:- Applying LV Impulse (Obsolete) :Time domain- AC , Sweep Frequency (SFRA)
68
![Page 69: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/69.jpg)
Test techniques
Freq response analysis (FRA)• Impedance/admittance/transfer
measurements• Typically 1kHz – 1MHz• Network analyzer or equivalent• Detects deformations/displacements• Compare against other phases , previous
measurement, or sister unit• The lead lengths need to be as short as
possible, and the test configuration must remain constant for repeated tests.
69
![Page 70: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/70.jpg)
Application
70
• Detecting Faults which involves:Winding deformations Core movementsFaulty core groundsPartial winding collapseHoop bucklingBroken clamping structuresShorted turns and open windings
• Generate a base-line data for future comparison
• To Confirm Smooth Transportation
![Page 71: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/71.jpg)
FRA
71
![Page 72: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/72.jpg)
FRA
72
![Page 73: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/73.jpg)
FRA
Repeatability is Key in FRA Measurement
73
Core NOT grounded
Core grounded
![Page 74: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/74.jpg)
FRA-Typical Curves
74
![Page 75: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/75.jpg)
FRA-Interpretation
• Low frequencies
– Core problems
– shorted/open windings
• Medium frequencies
– Winding deformations
• High frequencies
– Tap connections
– Other winding connection problems
75
![Page 76: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/76.jpg)
FRA-Applied voltage
It is usually 10V.
76
2.8 VOmicron
10 VFRAX, Doble and others
![Page 77: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/77.jpg)
FRA-Proper Grounding
77
Good grounding practice
Poor grounding practice
![Page 78: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/78.jpg)
FRA-Test Case -180 MVA off-shore• Acetylene up
• Change in winding resistance
• LV distorted at 5 kHz – 500 kHz 78
![Page 79: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/79.jpg)
Shipped for repair
79
![Page 80: ISEI 2010-Diagnostics Techniques of Power Transformers](https://reader035.vdocument.in/reader035/viewer/2022081413/547822c6b4af9f921f8b467d/html5/thumbnails/80.jpg)
Time for More Questions!