  • 7/26/2019 Isolation Panels

    1/32

    Medical Isolated Power Panels

    Catalog

    4800CT1201R01/14

    2014Class 4800

    CONTENTS

    Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page

    Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Standard Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Duplex Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Dual Voltage Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Controlled Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    X-Ray/Power Receptacle Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Power Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

    Master Grounding Stations Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

    Hospital-Grade Ground Cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

    IG2000 Series Remote Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

    Main Disconnect Circuit Breaker Size . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

  • 7/26/2019 Isolation Panels

    2/32

    Medical Isolated Power PanelsOverview

    20122014 Schneider Electric

    All Rights Reserved

    2

    01/2014

    Isolated Power Systems

    Isolated power systems offer an invaluable advantage in medical settings

    early detection allows critical systems to remain online when hazardous

    current is present. The system gives a visual indication of the level of

    current in milliamperes (mA). If the system reaches a threshold of 3.7 mA,

    the visual and audible alarm indicates the presence of an excessiveamperage level instead of disconnecting the circuit. These systems provide

    isolated power in operating rooms and other critical areas.

    An isolation transformer serves a single operating room, except when

    supplying equipment requiring 150 V or higher (example: receptacles for

    laser/X-ray machines).

    A line isolation monitor Indicates possible leakage or fault currents from all

    isolated conductors to ground.

    A green LED remains lit when the system is adequately isolated from

    ground

    Under normal voltage conditions, a red LED lamp and audible warning

    signal activate when a fault hazard current (fault leakage current only)

    reaches a threshold value of 3.7 mA, or when the total hazard current

    reaches a threshold value of 5.0 mA

    A digital display indicates the total hazard current of the system

    Controlled Isolated Power Panel

    Incoming power

    (customer connection)

    Line

    Isolation

    Monitor

    To system ground

    (customer connection)

    Main

    circuit

    breaker

    To panel

    ground

    bus

    Panel

    ground

    bus

    Electrostatic shield

    connected to panel

    ground bus

    Ordering Information

    The products offered in this catalog can be

    ordered using the Schneider Electric

    Product Selector:

    MEDICAL PRODUCTS

    ISO GARD

  • 7/26/2019 Isolation Panels

    3/32

    Medical Isolated Power PanelsOverview

    301/2014 20122014 Schneider Electric

    All Rights Reserved

    Panel Types

    Standard Panels

    Standard panels offer the most compact solution for a single isolated power system.

    Available in four options: 3, 5, 7.5, or 10 kVA Up to 16 circuits

    Duplex Panels

    Duplex panels offer two isolated power systems in a single panel. The systems are separated from

    each other by a barrier. For example, they can be used to enclose a standard and an emergency

    isolated power system in a single back box with common trim.

    Each panel supplies both 120 V and 208 V

    120 V system has up to 16 circuits

    208 V options include:

    5 kVA system with a 30 A secondary main in a 16-circuit panelboard

    7.5 kVA system with a 40 A secondary main in a 16-circuit panelboard 10 kVA system with a 50 A secondary main in a 16-circuit panelboard

    Used when multiple panels are required in an operating room, and/or more than 16 circuits are

    required

    Dual Voltage Panels

    Dual voltage panels supply both 120 V and 208 V isolated power to an operating room.

    Back box requires a 14 in, deep wall

    Each panel supplies up to 16, 120 V circuits, plus

    One 30 A, 208 V circuit for equipment such as a laser receptacle

    One 50 A, 208 V circuit for equipment such as an X-ray receptacle

    Controlled Panels

    Controlled panels are designed to provide 208 V of isolated power to multiple areas from one central

    location. They can be used to add 208 V to existing rooms.

  • 7/26/2019 Isolation Panels

    4/32

    Medical Isolated Power PanelsComponents

    20122014 Schneider Electric

    All Rights Reserved

    4

    01/2014

    Isolated Power Panel Components(Feeding 120, 208, or 240 V power circuits)

    Isolation Transformer

    Hospital-grade isolation transformers from Schneider Electric provide

    isolation between system voltage and load requirements.

    Single-phase

    kVA range: 3, 5, 7.5, 10, 15, 25 A

    Primary voltages: 120, 208, 240, 277, or 480 V

    Secondary voltages: 120, 208, or 240 V

    Class 180 insulation

    Electrostatic shield

    Maximum sound level of 35dB

    Low leakage

    Compliance with UL 1047 (tables 30.1 and 30.2) and CSA Z32.2

    NQ Panelboard Interiors

    Schneider Electric has

    designed a single-phase,

    NQ panelboard interior for use

    in isolated power panels.

    Accepts plug-on or bolt-on

    branch circuit breakers

    100 A interiors

  • 7/26/2019 Isolation Panels

    5/32

    Medical Isolated Power PanelsComponents

    501/2014 20122014 Schneider Electric

    All Rights Reserved

    QO Branch Circuit Breakers

    10k AIR

    QO (plug on) or QOB (bolt on)

    20 A; 2-pole (120 V)

    20, 30, 50 or 60 A; 2-pole (208 or 240 V)

    Primary Circuit Breakers

    QO circuit breakers for 120, 208, and 240 V systems

    PowerPact H-frame circuit breakers for 277 and 480 V systems

    2-pole; size is based on transformer kVA and chosen primary voltage

    Iso-Gard Series 6 Line Isolation Monitor (LIM)

    Automatic operating voltage selection reduces repairs

    and technical calls and increases customer satisfaction

    Automatic self test with data logging reduces timerequired to perform periodic testing

    Communications bus provides centralized monitoringof LIM installations to improve predictive maintenance

    Built-in ground fault location system reduces the timerequired to locate detected fault(s)

    Plain text menu interface makes setting easier andalarms clearer

    Electrical system measurements help determine rootcause of detected fault

    Feature Value Feature Value

    Measuring range ZISO 10999 kW Load current monitoring Yes

    Measuring range RISO 20999 kW Transformer temperature monitor Yes

    Measuring range CLEAK 10200 nF Automatic operating voltage selection Yes

    Trip time (0 - > 5 mA) 3.5 sec. Automatic self test Yes (selectable time)

    Trip tolerance (THC) 4.55 mA Line to line voltage measurement 70276 V

    Detected fault location Yes Line to ground voltage measurement > 0276 V

    Event memory with time stamp Yes Detected faulty line indication Yes

    Communication bus compatibility Full Select different measuring frequencies Yes

    Device settings Plain text Split core measuring current Yes

    QO

    QOB

    PowerPact H-frame

  • 7/26/2019 Isolation Panels

    6/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsStandard Panels Features and Options

    6

    01/2014

    Efficient solutions designed to meet multiple needs

    Standard Isolated Power Panel

    Iso-Gard Series 6 line isolation monitor

    Primary circuit breaker

    (8) 20 A, 2-pole, Square D brand branch

    circuit breakers

    Mounting provisions for (8) additional 20 A,

    2-pole circuit breakers

    Reference ground bar with 20 terminals

    Designed for 120 V applications

    Available in 3, 5, 7.5, and 10 kVA

    Ideal for operating rooms or critical areas

    Standard Panel Enhancements

    Field convertible up to (16) 20 A, 2-pole,

    Square D brand branch circuit breakers

    Receptacles

    Red or ivory

    Duplex or single

    Twist-lock

    Power and ground modules

    Optional bolt-on circuit breakers

    Allows for centralized location of receptacles and

    ground jacks

    Accessories

    Power and ground modules

    Hospital-grade ground cords

    Remote indicator

    Remote annunciator stations

    Options

    Standard Isolated Power Panel Enhancements

    kVAPrimary

    Voltage

    Secondary

    VoltageMounting

    Circuit

    Breakers

    No. of 20 A,

    2-pole

    Circuits

    Ground

    Bar

    Remote

    Indicator

    120 V

    Receptacles

    Ground

    Jacks

    3

    5

    7.5

    10

    120

    208

    240

    277

    480

    120

    208

    240

    Flush

    Surface

    Plug-on

    Bolt-on

    8 field-installed

    916 shippedseparately

    Standard IG2000P

    08

    Red or Ivory,Duplex or Single

    L5L20twist lock

    08

  • 7/26/2019 Isolation Panels

    7/32

    Medical Isolated Power PanelsOrdering Information Standard Panels

    701/2014 20122014 Schneider Electric

    All Rights Reserved

    120 V Distribution

    Transformer Interior Trim

    Catalog No.

    Back Box

    Catalog No.

    kVA Primary SecondaryCatalog

    No.

    LIM

    Included

    (field-installed)

    Main Disconnect

    Circuit

    Breakers

    (factory-installed)

    SpacesCatalog

    No.

    Flush Surface Flush Surface

    Plug-on Circuit Breakers

    3 208 V

    120 V

    SXM03BA

    Iso-GardSeries 6

    QO 20 A, 2-pole EightQO 20 A,

    2-pole

    Eight2-pole

    SIP03BA

    ST4526 ST4324 SB432406 SB432406S3 240 V SXM03CA SIP03CA

    3 277 V SXM03DAPowerPact H-frame

    15 A, 1-poleSIP03DA

    5 208 V

    120 V

    SXM05BA

    Iso-GardSeries 6

    QO 30 A, 2-poleEight

    QO 20 A,2-pole

    Eight2-pole

    SIP05BA

    ST4526 ST4324 SB432406 SB432406S5 240 V SXM05CA SIP05CA

    5 277 V SXM05DAPowerPact H-frame

    25 A, 1-poleSIP05DA

    5 480 V SXM05EAPowerPact H-frame

    15 A, 2-poleSIP05EA

    7.5 208 V

    120 V

    SXM07BA

    Iso-GardSeries 6

    QO 45 A, 2-poleEight

    QO 20 A,2-pole

    Eight2-pole

    SIP07BA

    ST4526 ST4324 SB432408 SB432408S7.5 240 V SXM07CA SIP07CA

    7.5 277 V SXM07DAPowerPact H-frame

    35 A, 1-poleSIP07DA

    7.5 480 V SXM07EAPowerPact H-frame

    20 A, 2-poleSIP07EA

    10 208 V

    120 V

    SXM10BA

    Iso-GardSeries 6

    QO 60 A, 2-poleEight

    QO 20 A,2-pole

    Eight2-pole

    SIP10BA

    ST4526 ST4324 SB432408 SB432408S10 240 V SXM10CA SIP10CA

    10 277 V SXM10DAPowerPact H-frame

    45 A, 1-poleSIP10DA

    10 480 V SXM10EAPowerPact H-frame

    30 A, 2-poleSIP10EA

    Bolt-on Circuit Breakers

    3 208 V

    120 V

    SXM03BAIso-GardSeries 6

    QOB 20 A, 2-pole EightQOB 20 A,

    2-pole

    Eight2-pole

    SIP03BAB

    ST4526 ST4324 SB432406 SB432406S3 240 V SXM03CA SIP03CAB

    3 277 V SXM03DA PowerPact H-frame15 A, 1-pole

    SIP03DAB

    5 208 V

    120 V

    SXM05BA

    Iso-GardSeries 6

    QOB 30 A, 2-poleEight

    QOB 20 A,2-pole

    Eight2-pole

    SIP05BAB

    ST4526 ST4324 SB432406 SB432406S5 240 V SXM05CA SIP05CAB

    5 277 V SXM05DAPowerPact H-frame

    25 A, 1-poleSIP05DAB

    5 480 V SXM05EAPowerPact H-frame

    15 A, 2-poleSIP05EAB

    7.5 208 V

    120 V

    SXM07BA

    Iso-GardSeries 6

    QOB 45 A, 2-poleEight

    QOB 20 A,2-pole

    Eight2-pole

    SIP07BAB

    ST4526 ST4324 SB432408 SB432408S7.5 240 V SXM07CA SIP07CAB

    7.5 277 V SXM07DAPowerPact H-frame

    35 A, 1-poleSIP07DAB

    7.5 480 V SXM07EAPowerPact H-frame

    20 A, 2-poleSIP07EAB

    10 208 V

    120 V

    SXM10BA

    Iso-GardSeries 6

    QOB 60 A, 2-poleEight

    QOB 20 A,2-pole

    Eight2-pole

    SIP10BAB

    ST4526 ST4324 SB432408 SB432408S10 240 V SXM10CA SIP10CAB

    10 277 V SXM10DAPowerPact H-frame

    45 A, 1-poleSIP10DAB

    10 480 V SXM10EAPowerPact H-frame

    30 A, 2-poleSIP10EAB

    Also available with factory-installed power modules. Options are:

    18 receptacles: Red Duplex, Ivory Duplex, Red Single, Ivory Single, Black Twist Lock 18 ground modules

  • 7/26/2019 Isolation Panels

    8/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsStandard Panels Technical Data

    8

    01/2014

    Wiring Diagram

    L1

    L2

    12 Vdc Com

    A

    B

    RI1

    K1/NC

    K1/COM

    K1/NO

    SAFE

    HAZARD

    RI2

    GND2

    LIM GND

    TEST

    1S1

    Z1/M +

    1S2

    Z2/M -

    K2/COM

    K2/NO

    K2/NC

    To remote indicator

    and accessories

    (if required)

    Panel

    ground

    Panel

    ground

    Panel

    ground

    Incoming

    power

    H2

    H1 X2

    X1

    L2L1 To system

    ground

    Receptacles and

    ground jacks

    are options.

    16

    14

    12

    10

    8

    6

    4

    2

    15

    13

    11

    9

    7

    5

    3

    1

  • 7/26/2019 Isolation Panels

    9/32

    Medical Isolated Power PanelsTechnical Data Standard Panels

    901/2014 20122014 Schneider Electric

    All Rights Reserved

    OutlineStandard Isolated Power Panel

    OutlineStandard Isolated Power Panel with Enhancements

    24(610)

    6(152)Flush 1(25)

    Surface 0(0)Top View

    Flush 26(660)Surface 24(610)

    6(152)

    Flush 1 (25)

    Surface 0 (0)

    43(1092)

    Flush 45(1143)

    Surface 43(1092)

    24(610)

    Flush 1(25)

    Surface 0(0)Top View

    Flush 26(660)Surface 24(610)

    8(203)

    Flush 1 (25)

    Surface 0 (0)

    43(1092)

    Flush 45(1143)

    Surface 43(1092)

    Side ViewFront View Side ViewFront View

    8(203)

    3 and 5 kVA 7.5 and 10 kVA

    Dual dimensions: Inches(mm)

    24(610)

    8(203)Flush 1(25)

    Surface 0(0)Top View

    Flush 26(660)

    Surface 24(610)Flush 1 (25)

    Surface 0 (0)

    48(1220)

    Flush 50 (1270)

    Surface 48(1220)

    Side ViewFront View

    8(203)

    3, 5, 7.5, and 10 kVA

    Dual dimensions: Inches(mm)

  • 7/26/2019 Isolation Panels

    10/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsDuplex Panels Features and Options

    10

    01/2014

    Duplex Operating Room Panels

    Ideal for locations where space is limited, for renovations, or for minimizing leakage current on the

    individual panel and transformer.

    Each panel features the following items:

    Iso-Gard Series 6 line isolation monitor Primary circuit breaker

    Eight Square D brand, 20 A, 2-pole, branch circuit breakers

    Mounting provisions for eight additional 20 A, 2-pole circuit breakers

    Reference ground bar with 20 terminals

    Designed for 120 V applications

    Available in 3, 5, 7.5, and 10 kVA

    Duplex Panelsonly one back box and trim piece required for two Isolated Power Systems

    Transformertwo required (one for each system)

    Interiortwo mains, two LIMs, two panelboards, two ground bars mounted on one common

    back plate

    Single trim Single back box

    All items must be ordered as separate line items.

    Back box for all duplex panels: Flush-mountSB713408; Surface-mountSB713408S

    Trim for all duplex panels: Flush-mountST7336; Surface-mountST7134

    Units are available in any combination of primary voltages and kVA ratings. Please use the

    Product Selector to meet the requirements of a specific customer.

    Options a

    Duplex Operating Room Panel

    kVA Primary VoltageSecondary

    VoltageMounting

    Circuit

    Breakers

    No. of 20 A,

    2-pole CircuitsGround Bar

    3

    5

    7.5

    10

    120

    208

    240

    277

    480

    120

    208

    240

    Flush

    Surface

    Plug-on

    Bolt-on

    8 field installed

    916 shippedseparately

    Standard

    a Options are for both the left and right side; selection is required for each side.

  • 7/26/2019 Isolation Panels

    11/32

    Medical Isolated Power PanelsOrdering Information Duplex Panels

    1101/2014 20122014 Schneider Electric

    All Rights Reserved

    NOTE: To complete the system, you must order the appropriate back box and trim from page 10.

    120 V Distribution on Both Sides of the Panel

    Transformer Interior

    kVA

    Prim

    ary

    Secon

    dary

    Catalog No. Left Right

    Catalog No.Left

    Right

    LIM

    Inclu

    ded

    (field-installed)

    MainDisco

    nnect

    CircuitBre

    akers

    (factory-ins

    talled)

    Space

    s

    LIM

    Inclu

    ded

    (field-installed)

    MainDisco

    nnect

    CircuitBre

    akers

    (factory-ins

    talled)

    Space

    s

    Plug-on Circuit Breakers

    3 208 V

    120 V

    SXM03BA SXM03BA

    Iso-GardSeries 6

    QO 20 A, 2-pole EightQO 20

    A, 2-pole

    Eight2-pole

    Iso-GardSeries 6

    QO 20 A, 2-pole EightQO 20

    A, 2-pole

    Eight2-pole

    SIX03BA03BA

    3 240 V SXM03CA SXM03CA SIX03CA03CA

    3 277 V SXM03DA SXM03DAPowerPact H-frame

    15 A, 1-polePowerPact H-frame

    15 A, 1-poleSIX03DA03DA

    5 208 V

    120 V

    SXM05BA SXM05BA

    Iso-GardSeries 6

    QO 30 A, 2-pole

    EightQO 20

    A, 2-pole

    Eight2-pole

    Iso-GardSeries 6

    QO 30 A, 2-pole

    EightQO 20

    A, 2-pole

    Eight2-pole

    SIX05BA05BA

    5 240 V SXM05CA SXM05CA SIX05CA05CA

    5 277 V SXM05DA SXM05DAPowerPact H-frame

    25 A, 1-pole

    PowerPact H-frame

    25 A, 1-pole

    SIX05DA05DA

    5 480 V SXM05EA SXM05EAPowerPact H-frame

    15 A, 2-polePowerPact H-frame

    15 A, 2-poleSIX05EA05EA

    7.5 208 V

    120 V

    SXM07BA SXM07BA

    Iso-GardSeries 6

    QO 45 A, 2-poleEight

    QO 20A, 2-pole

    Eight2-pole

    Iso-GardSeries 6

    QO 45 A, 2-poleEight

    QO 20A, 2-pole

    Eight2-pole

    SIX07BA07BA

    7.5 240 V SXM07CA SXM07CA SIX07CA07CA

    7.5 277 V SXM07DA SXM07DAPowerPact H-frame

    35 A, 1-polePowerPact H-frame

    35 A, 1-poleSIX07DA07DA

    7.5 480 V SXM07EA SXM07EAPowerPact H-frame

    20 A, 2-polePowerPact H-frame

    20 A, 2-poleSIX07EA07EA

    10 208 V

    120 V

    SXM10BA SXM10BA

    Iso-GardSeries 6

    QO 60 A, 2-poleEight

    QO 20A, 2-pole

    Eight2-pole

    Iso-GardSeries 6

    QO 60 A, 2-poleEight

    QO 20A, 2-pole

    Eight2-pole

    SIX10BA10BA

    10 240 V SXM10CA SXM10CA SIX10CA10CA

    10 277 V SXM10DA SXM10DAPowerPact H-frame

    45 A, 1-polePowerPact H-frame

    45 A, 1-poleSIX10DA10DA

    10 480 V SXM10EA SXM10EAPowerPact H-frame

    30 A, 2-polePowerPact H-frame

    30 A, 2-poleSIX10EA10EA

    Bolt-on Circuit Breakers

    3 208 V

    120 V

    SXM03BA SXM03BA

    Iso-GardSeries 6

    QOB 20 A, 2-pole EightQOB 20

    A, 2-pole

    Eight2-pole

    Iso-GardSeries 6

    QOB 20 A, 2-pole EightQOB 20

    A, 2-pole

    Eight2-pole

    SIX03BA03BAB

    3 240 V SXM03CA SXM03CA SIX03CA03CAB

    3 277 V SXM03DA SXM03DA PowerPact H-frame15 A, 1-pole

    PowerPact H-frame15 A, 1-pole

    SIX03DA03DAB

    5 208 V

    120 V

    SXM05BA SXM05BA

    Iso-GardSeries 6

    QOB 30 A, 2-pole

    EightQOB 20

    A, 2-pole

    Eight2-pole

    Iso-GardSeries 6

    QOB 30 A, 2-pole

    EightQOB 20

    A, 2-pole

    Eight2-pole

    SIX05BA05BAB

    5 240 V SXM05CA SXM05CA SIX05CA05CAB

    5 277 V SXM05DA SXM05DAPowerPact H-frame

    25 A, 1-polePowerPact H-frame

    25 A, 1-poleSIX05DA05DAB

    5 480 V SXM05EA SXM05EAPowerPact H-frame

    15 A, 2-polePowerPact H-frame

    15 A, 2-poleSIX05EA05EAB

    7.5 208 V

    120 V

    SXM07BA SXM07BA

    Iso-GardSeries 6

    QOB 45 A, 2-poleEight

    QOB 20A, 2-pole

    Eight2-pole

    Iso-GardSeries 6

    QOB 45 A, 2-poleEight

    QOB 20A, 2-pole

    Eight2-pole

    SIX07BA07BAB

    7.5 240 V SXM07CA SXM07CA SIX07CA07CAB

    7.5 277 V SXM07DA SXM07DAPowerPact H-frame

    35 A, 1-polePowerPact H-frame

    35 A, 1-poleSIX07DA07DAB

    7.5 480 V SXM07EA SXM07EAPowerPact H-frame

    20 A, 2-polePowerPact H-frame

    20 A, 2-poleSIX07EA07EAB

    10 208 V

    120 V

    SXM10BA SXM10BA

    Iso-GardSeries 6

    QOB 60 A, 2-poleEight

    QOB 20A, 2-pole

    Eight2-pole

    Iso-GardSeries 6

    QOB 60 A, 2-poleEight

    QOB 20A, 2-pole

    Eight2-pole

    SIX10BA10BAB

    10 240 V SXM10CA SXM10CA SIX10CA10CAB

    10 277 V SXM10DA SXM10DAPowerPact H-frame

    45 A, 1-polePowerPact H-frame

    45 A, 1-poleSIX10DA10DAB

    10 480 V SXM10EA SXM10EAPowerPact H-frame

    30 A, 2-polePowerPact H-frame

    30 A, 2-poleSIX10EA10EAB

  • 7/26/2019 Isolation Panels

    12/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsDuplex Panels Technical Data

    12

    01/2014

    Wiring Diagram

    L1

    L2

    12 Vdc Com

    A

    B

    RI1

    K1/NC

    K1/COM

    K1/NO

    SAFE

    HAZARD

    RI2

    GND2

    LIM GND

    TEST

    1S1

    Z1/M +

    1S2

    Z2/M -

    K2/COM

    K2/NOK2/NC

    To remote indicator

    and accessories

    (if required)

    Panel

    ground

    Panel

    ground

    Panel

    ground

    Incoming

    power

    H2

    H1 X2

    X1

    L2L1

    To system

    ground

    16

    14

    12

    10

    8

    6

    4

    2

    15

    13

    11

    9

    7

    5

    3

    1

    System A

    L1

    L2

    12 Vdc Com

    A

    B

    RI1

    K1/NC

    K1/COM

    K1/NO

    SAFE

    HAZARD

    RI2

    GND2

    LIM GND

    TEST

    1S1

    Z1/M +

    1S2

    Z2/M -

    K2/COM

    K2/NOK2/NC

    To remote indicator

    and accessories

    (if required)

    Panel

    ground

    Panel

    ground

    Panel

    ground

    Incoming

    power

    H2

    H1 X2

    X1

    L2L1

    To system

    ground

    16

    14

    12

    10

    8

    6

    4

    2

    15

    13

    11

    9

    7

    5

    3

    1

    System B

  • 7/26/2019 Isolation Panels

    13/32

    Medical Isolated Power PanelsTechnical Data Duplex Panels

    1301/2014 20122014 Schneider Electric

    All Rights Reserved

    Outline

    34(864)

    8(203)

    Flush 1(25)Surface 0(0)

    Top View

    Flush 36(914)

    Surface 34(864)

    Flush 1 (25)

    Surface 0 (0)

    71(1803)

    Flush 73 (1854)

    Surface 71 (1803)

    Side ViewFront View

    8(203)

    System A System B

    Flush 36.5 (927)

    Surface 35.5 (902)

    Flush 36.5 (927)

    Surface 35.5 (902)

    Dual dimensions: Inches(mm)

  • 7/26/2019 Isolation Panels

    14/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsDual Voltage Panels Features and Options

    14

    01/2014

    Dual Voltage Isolated Power Panels

    Combines standard (120 V) and controlled (208 or 240 V) panels into one space-saving solution.

    Primary circuit breaker

    120 V output

    Iso-Gard Series 6 line isolation monitor (8) Square D brand, 20 A, 2-pole, branch circuit breakers

    Mounting provisions for (8) additional 20 A, 2-pole circuit breakers

    Reference ground bar with 20 terminals

    Available in 3, 5, 7.5, and 10 kVA

    Up to 8 receptacles

    Up to 8 ground jacks

    208 or 240 V output

    Iso-Gard Series 6 line isolation monitor

    (2) Square D brand, 20 A, 2-pole, branch circuit breakers

    Reference ground bar with 20 terminals

    Customized control to meet customer requirements

    Available in 15 kVA

    12 laser outlets

    Dual Voltage Panels120 V distribution plus two circuits of 208V or 240V

    kVA Ratings

    5/15 kVA20 kVA Primary, 5 kVA 120 V Secondary, 15 kVA 208 or 240 V Secondary

    7.5/15 kVA22.5 kVA Primary,7.5 kVA 120 V Secondary, 15 kVA 208 or 240 V Secondary

    10/15 kVA25 kVA Primary, 10 kVA 120 V Secondary, 15 kVA 208 or 240 V Secondary

    Options

    208/240 branch circuits can be changed to any combination of 20, 30, 50, or 60 A circuit breakers.

    Please use the Product Selector to obtain the combination required.

    Available with factory-installed power modules via the Product Selector.

    Receptacle 0 to 8Red Duplex, Ivory Duplex, Red Single, Ivory Single, Black Twist Lock

    Ground modules 0 to 8

    208 V and 240 V receptacles

    NEMA 6-15R, NEMA 6-20R, NEMA 6-30R, NEMA 6-50R

    NEMA L6-15R, NEMA L6-20R, NEMA L6-30R

    Hubbell CS8269, Hubbell IN16494

  • 7/26/2019 Isolation Panels

    15/32

    Medical Isolated Power PanelsOrdering Information Dual Voltage Panels

    1501/2014 20122014 Schneider Electric

    All Rights Reserved

    Transformer Interior Trim

    Catalog No.Back Box

    Catalog No.

    kVA

    Primary

    S

    econdary

    CatalogNo.

    LIMIncluded

    (field-installed)

    Main

    Disconnect

    120VPanelMain

    Circ

    uitBreakers

    Circ

    uitBreakers

    (factory-installed)

    Spaces

    208

    /240VMain

    Circ

    uitBreakers

    208/240VBranch

    Circ

    uitBreakers

    CatalogNo.

    Flush

    Surface

    Flush

    Surface

    Plug-on Circuit Breakers

    5/15

    208

    208/120

    SXM25BB10

    Iso-GardSeries 6

    QO 125 A2-pole

    QO250Eight

    QO 20 A2-pole

    Eight2-pole

    QOU80 A

    SID20BB05A31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CB10QO 100 A

    2-pole(1) QOU

    30 A 2-poleSID20CB05A31A51

    277 SXM25DB10H-frame

    90 A 1-pole(1) QOU

    50 A 2-poleSID20DB05A31A51

    480 SXM25EB10H-frame

    50 A 2-poleSID20EB05A31A51

    7.5/15

    208

    208/120

    SXM25BB10

    Iso-GardSeries 6

    QO ( ) A2-pole

    QO270Eight

    QO 20 A2-pole

    Eight2-pole

    QOU80 A

    SID22BB07A31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CB10QO ( ) A2-pole

    (1) QOU30 A 2-pole

    SID22CB07A31A51

    277 SXM25DB10H-frame

    ( ) A 1-pole(1) QOU

    50 A 2-poleSID22DB07A31A51

    480 SXM25EB10 H-frame( ) A 2-pole

    SID22EB07A31A51

    10/15

    208

    208/120

    SXM25BB10

    Iso-GardSeries 6

    QO 150 A2-pole

    QO2100Eight

    QO 20 A2-pole

    Eight2-pole

    QOU80 A

    SID25BB10A31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CB10QO 150 A

    2-pole(1) QOU

    30 A 2-poleSID25CB10A31A51

    277 SXM25DB10H-frame125 A 1-

    (1) QOU50 A 2-pole

    SID25DB10A31A51

    480 SXM25EB10H-frame

    70 A 2-poleSID25EB10A31A51

    5/15

    208

    240/120

    SXM25BC10

    Iso-GardSeries 6

    QO 125 A2-pole

    QO250Eight

    QO 20 A2-pole

    Eight2-pole

    QOU70 A

    SID20BC05A31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CC10QO 100 A

    2-pole(1) QOU

    30 A 2-poleSID20CC05A31A51

    277 SXM25DC10H-frame

    90 A 2-pole(1) QOU

    50 A 2-poleSID20DC05A31A51

    480 SXM25EC10H-frame

    50 A 2-poleSID20EC05A31A51

    7.5/15

    208

    240/120

    SXM25BC10

    Iso-GardSeries 6

    QO ( ) A2-pole

    QO270Eight

    QO 20 A2-pole

    Eight2-pole

    QOU70 A

    SID22BC07A31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CC10QO ( ) A2-pole

    (1) QOU30 A 2-pole

    SID22CC07A31A51

    277 SXM25DC10H-frame

    ( ) A 1-pole(1) QOU

    50 A 2-poleSID22DC07A31A51

    480 SXM25EC10H-frame

    ( ) A 2-poleSID22EC07A31A51

    10/15

    208

    240/120

    SXM25BC10

    Iso-GardSeries 6

    QO 150 A2-pole

    QO2100Eight

    QO 20 A2-pole

    Eight2-pole

    QOU70 A

    SID25BC10A31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CC10QO 150 A

    2-pole(1) QOU

    30 A 2-poleSID25CC10A31A51

    277 SXM25DC10H-frame125 A 1-

    (1) QOU50 A 2-pole

    SID25DC10A31A51

    480 SXM25EC10H-frame

    70 A 2-poleSID25EC10A31A51

  • 7/26/2019 Isolation Panels

    16/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsDual Voltage Panels Ordering Information

    16

    01/2014

    Bolt-on Circuit Breakers

    5/15

    208

    208/120

    SXM25BB10

    Iso-GardSeries 6

    QO 125 A2-pole

    QO250Eight

    QO 20 A2-pole

    Eight2-pole

    QOU80 A

    SID20BB05BA31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CB10QO 100 A

    2-pole(1) QOU

    30 A 2-poleSID20CB05BA31A51

    277 SXM25DB10H-frame

    90 A 1-pole(1) QOU

    50 A 2-poleSID20DB05BA31A51

    480 SXM25EB10H-frame

    50 A 2-poleSID20EB05BA31A51

    7.5/15

    208

    208/120

    SXM25BB10

    Iso-GardSeries 6

    QO ( ) A2-pole

    QO270Eight

    QO 20 A2-pole

    Eight2-pole

    QOU80 A

    SID22BB07BA31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CB10QO ( ) A2-pole

    (1) QOU30 A 2-pole

    SID22CB07BA31A51

    277 SXM25DB10H-frame

    ( ) A 1-pole(1) QOU

    50 A 2-poleSID22DB07BA31A51

    480 SXM25EB10 H-frame( ) A 2-pole SID22EB07BA31A51

    10/15

    208

    208/120

    SXM25BB10

    Iso-GardSeries 6

    QO 150 A2-pole

    QO2100Eight

    QO 20 A2-pole

    Eight2-pole

    QOU80 A

    SID25BB10BA31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CB10QO 150 A

    2-pole(1) QOU

    30 A 2-poleSID25CB10BA31A51

    277 SXM25DB10H-frame125 A 1-

    (1) QOU50 A 2-pole

    SID25DB10BA31A51

    480 SXM25EB10H-frame

    70 A 2-poleSID25EB10BA31A51

    5/15

    208

    240/120

    SXM25BC10

    Iso-GardSeries 6

    QO 125 A2-pole

    QO250Eight

    QO 20 A2-pole

    Eight2-pole

    QOU70 A

    SID20BC05BA31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CC10QO 100 A

    2-pole(1) QOU

    30 A 2-poleSID20CC05BA31A51

    277 SXM25DC10H-frame

    90 A 2-pole(1) QOU

    50 A 2-poleSID20DC05BA31A51

    480 SXM25EC10H-frame

    50 A 2-poleSID20EC05BA31A51

    7.5/15

    208

    240/120

    SXM25BC10

    Iso-GardSeries 6

    QO ( ) A2-pole

    QO270Eight

    QO 20 A2-pole

    Eight2-pole

    QOU70 A

    SID22BC07BA31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CC10QO ( ) A2-pole

    (1) QOU30 A 2-pole

    SID22CC07BA31A51

    277 SXM25DC10H-frame

    ( ) A 1-pole(1) QOU

    50 A 2-poleSID22DC07BA31A51

    480 SXM25EC10H-frame

    ( ) A 2-poleSID22EC07BA31A51

    10/15

    208

    240/120

    SXM25BC10

    Iso-GardSeries 6

    QO 150 A2-pole

    QO2100Eight

    QO 20 A2-pole

    Eight2-pole

    QOU70 A

    SID25BC10BA31A51

    ST5836 ST5634 SB563414 SB563414S

    240 SXM25CC10QO 150 A

    2-pole(1) QOU

    30 A 2-poleSID25CC10BA31A51

    277 SXM25DC10H-frame125 A 1-

    (1) QOU50 A 2-pole

    SID25DC10BA31A51

    480 SXM25EC10H-frame

    70 A 2-poleSID25EC10BA31A51

    Transformer Interior Trim

    Catalog No.Back Box

    Catalog No.

    kVA

    Primary

    S

    econdary

    C

    atalogNo.

    LIMIncluded

    (fie

    ld-installed)

    MainDisconnect

    120

    VPanelMain

    CircuitBreakers

    CircuitBreakers

    (factory-installed)

    Spaces

    208/240VMain

    CircuitBreakers

    208/240VBranch

    CircuitBreakers

    C

    atalogNo.

    Flush

    Surface

    Flush

    Surface

  • 7/26/2019 Isolation Panels

    17/32

    Medical Isolated Power PanelsTechnical Data Dual Voltage Panels

    1701/2014 20122014 Schneider Electric

    All Rights Reserved

    Wiring Diagram

    Recep

    tac

    lesan

    d

    groun

    djac

    ks

    areop

    tions.

    Tosys

    tem

    groun

    d

    P

    ane

    l

    groun

    d

    Pane

    l

    groun

    d

    Toremo

    teindica

    tor

    an

    daccessories

    (ifrequ

    ired

    )

    L1

    L2

    12VdcCom

    A BRI1

    K1/NC

    K1/COM

    K1/NO

    SAFE

    HAZARD

    RI2

    GND2

    LIM

    GND

    TEST

    1S1

    Z1/M

    +

    1S2

    Z2/M

    -

    K2/COM

    K2/NO

    K2/NC

    HighVolta

    ge

    Sec

    tion

    Low

    Vo

    lta

    ge

    Sec

    tion

    Tosys

    tem

    groun

    d

    Pane

    l

    groun

    d

    Pane

    l

    groun

    d

    Toremo

    tein

    dica

    tor

    an

    daccessories

    (ifrequire

    d)

    L1

    L2

    12VdcCom

    A BRI1

    K1/NC

    K1/COM

    K1/NO

    SAFE

    HAZARD

    RI2

    GND2

    LIM

    GND

    TEST

    1S1

    Z1/M

    +

    1S2

    Z2/M

    -

    K2/COM

    K2/NO

    K2/NC

    L2

    L1

    L2

    L1

    Pane

    l

    grou

    nd

    16

    Incom

    ing

    power

    X2

    X1

    H2

    H1

    T1

    14

    12

    108642

    15

    13

    1197531

    X3

    X4

    op

    tiona

    l

  • 7/26/2019 Isolation Panels

    18/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsDual Voltage Panels Technical Data

    18

    01/2014

    Outline

    34(864)

    14

    (356)

    Flush 1(25)

    Surface 0(0)Top View

    Flush 36(914)

    Surface 34(864)

    Flush 1 (25)

    Surface 0 (0)

    56(1422)

    Flush 58 (1473)Surface 56 (1422)

    Side ViewFront View

    14(356)

    Dual dimensions: Inches(mm)

  • 7/26/2019 Isolation Panels

    19/32

    Medical Isolated Power PanelsFeatures and Options Controlled Panels

    1901/2014 20122014 Schneider Electric

    All Rights Reserved

    Controlled Isolated Power Panels

    Panels with circuit control have a secondary circuit breaker that is connected to a maximum of eight

    branch circuits. The configuration of which circuits receive power is made at the factory to meet

    customer requirements. The selection of a secondary circuit is typically door-contact-controlled at the

    individual receptacle station or from a push button station built into the isolated power panel. No power

    will be delivered to a secondary circuit until the secondary breaker is closed. Iso-Gard Series 6 line isolation monitor

    Primary circuit breaker

    (8) Square D brand, 20 A, 2-pole, branch circuit breakers

    Mounting provisions for (8) additional 20 A, 2-pole circuit breakers

    Reference ground bar with 20 terminals

    Designed for 208 or 240 V applications

    Customized control to meet customer requirements

    Available in 7.5, 10, 15, or 25 kVA

    Ideal for X-ray and laser equipment; control option is available for supplying power to portable

    equipment

    Customized control optionprogrammable logic controller (PLC) to interface with the 208/240 V

    receptacle module accessory

    Units are available in other combinations of branch breakers, simultaneous circuits are limited to the

    number shown in the following table.

    NOTE:Also available with 240 V secondary. Please use the Product Selector to meet special

    requirements.

    Options

    Controlled Isolated Power Panel X-Ray Module

    kVAPrimary

    Voltage

    Secondary

    VoltageMounting

    Type of

    Control

    PLC

    No. of

    Laser

    Circuits

    No. of Hot

    Circuits

    Secondary

    BreakerQuantity Mounting

    Type of Power

    Receptacle

    7.5

    10

    15

    25

    208

    240

    277

    480

    208

    240

    Flush

    Surface

    Door contactwith lamp

    Door contactwithout lamp

    Push buttonpanel

    Remote pushbutton

    18 16

    20 A

    30 A

    50 A

    60 A

    Matchcircuits

    Recessed

    Surface

    NEMA #6-15R or#L6-15R

    NEMA #6-20R or#L6-20R

    NEMA #6-30R or#L6-30R

    NEMA #6-50RHubbel #IN16494

    kVASecondary

    Voltage

    Maximum Number of Branch Circuits

    20 A 30 A 50 A 60 A

    5208 1 1 0 0

    240 1 1 0 0

    7.5208 2 1 0 0

    240 1 1 0 0

    10208 2 1 1 0

    240 2 1 1 0

    15208 4 2 1 2

    240 3 2 1 2

    25208 6 4 2 2

    240 6 4 2 2

  • 7/26/2019 Isolation Panels

    20/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsControlled Panels Ordering Information

    20

    01/2014

    Transformer Interior Trim

    Catalog No.

    Back Box

    Catalog No.

    kV

    A

    Prim

    ary

    Secon

    dary

    Catalo

    gNo.

    LIMInc

    luded

    (field-installed)

    MainDisconnect

    CircuitB

    reakers

    (factory-installed)

    SimultaneousCircuits

    PLCCon

    trolled

    Catalo

    gNo.

    Flush

    Surface

    Flush

    Surface

    10

    208

    208

    SXM10BB

    Iso-GardSeries 6

    QO 60 A2-pole

    Four QO20 A

    2-pole1

    SIP10BBPNA34H1

    ST5332 ST5130 SB513014 SB513014S

    240 SXM10CBQO 60 A2-pole

    SIP10CBPNA34H1

    277 SXM10DBH-frame

    45 A 1-poleSIP10DBPNA34H1

    480 SXM10EBH-frame

    30 A 2-poleSIP10EBPNA34H1

    10

    208

    208

    SXM10BB

    Iso-Gard

    Series 6

    QO 60 A2-pole

    Eight QO20 A

    2-pole

    1

    SIP10BBPNA38H1

    ST5332 ST5130 SB513014 SB513014S

    240 SXM10CBQO 60 A2-pole

    SIP10CBPNA38H1

    277 SXM10DB H-frame45 A 1-pole SIP10DBPNA38H1

    480 SXM10EBH-frame

    30 A 2-poleSIP10EBPNA38H1

    10

    208

    208

    SXM10BB

    Iso-GardSeries 6

    QO 60 A2-pole

    Two QO520 A2-pole

    1

    SIP10BBPNA52H1

    ST5332 ST5130 SB513014 SB513014S

    240 SXM10CBQO 60 A2-pole

    SIP10CBPNA52H1

    277 SXM10DBH-frame

    45 A 1-poleSIP10DBPNA52H1

    480 SXM10EBH-frame

    30 A 2-poleSIP10EBPNA52H1

    10

    208

    208

    SXM10BB

    Iso-GardSeries 6

    QO 60 A2-pole

    Four QO50 A

    2-pole1

    SIP10BBPNA54H1

    ST5332 ST5130 SB513014 SB513014S

    240 SXM10CBQO 60 A2-pole

    SIP10CBPNA54H1

    277 SXM10DBH-frame

    45 A 1-poleSIP10DBPNA54H1

    480 SXM10EB H-frame30 A 2-pole

    SIP10EBPNA54H1

    15

    208

    208

    SXM15BB

    Iso-GardSeries 6

    QO 90 A2-pole

    Two QO520 A2-pole

    1

    SIP15BBPNA52H1

    ST5332 ST5130 SB513014 SB513014S

    240 SXM15CBQO 80 A2-pole

    SIP15CBPNA52H1

    277 SXM15DBH-frame

    70 A 1-poleSIP15DBPNA52H1

    480 SXM15EBH-frame

    40 A 2-poleSIP15EBPNA52H1

    15

    208

    208

    SXM15BB

    Iso-GardSeries 6

    QO 90 A2-pole

    Four QO50 A

    2-pole1

    SIP15BBPNA54H1

    ST5332 ST5130 SB513014 SB513014S

    240 SXM15CBQO 80 A2-pole

    SIP15CBPNA54H1

    277 SXM15DBH-frame

    70 A 1-poleSIP15DBPNA54H1

    480 SXM15EBH-frame

    40 A 2-poleSIP15EBPNA54H1

    15

    208

    208

    SXM15BB

    Iso-GardSeries 6

    QO 90 A2-pole One QO

    50 A2-pole

    One QO30 30 A2-pole

    1

    SIP15BBPNA31A51H1

    ST5332 ST5130 SB513014 SB513014S

    240 SXM15CBQO 80 A2-pole

    SIP15CBPNA31A51H1

    277 SXM15DBH-frame

    70 A 1-poleSIP15DBPNA31A51H1

    480 SXM15EBH-frame

    40 A 2-poleSIP15EBPNA31A51H1

  • 7/26/2019 Isolation Panels

    21/32

    Medical Isolated Power PanelsTechnical Data Controlled Panels

    2101/2014 20122014 Schneider Electric

    All Rights Reserved

    Wiring Diagram

    16

    Recep

    tac

    le

    Mo

    du

    le#1

    Recep

    tac

    le

    Mo

    du

    le#5

    Recep

    tac

    le

    Mo

    du

    le#4

    Recep

    tac

    le

    Mo

    du

    le#3

    Recep

    tac

    le

    Mo

    du

    le#2

    L1

    L2

    12V

    dc

    Com

    A BRI1

    K

    1/NC

    K1

    /COM

    K1/NO

    S

    AFE

    HA

    ZARD

    RI2

    G

    ND2

    LIM

    GND

    T

    EST

    1S1

    Z1/M

    +

    1S2

    Z2/M

    -

    K2

    /COM

    K2/NO

    K

    2/NC

    Pane

    l

    groun

    d

    Tosys

    tem

    groun

    d

    Pane

    l

    groun

    d

    Pane

    l

    groun

    d

    To

    recep

    tac

    les

    Pane

    l

    groun

    d

    Incom

    ing

    power

    X2

    X1

    H2

    H1

    L2

    L1

    T1

    X2

    X1

    H2

    H1

    T1

    F1

    F3

    F2

    12V

    dc

    Com

    Safe

    Haza

    rd

    Doorcon

    tac

    t

    Doorcon

    tac

    t

    12V

    dc

    Com

    Safe

    Haza

    rd

    Doorcon

    tac

    t

    Doorcon

    tac

    t

    12V

    dc

    Com

    Safe

    Haza

    rd

    Doorcon

    tac

    t

    Doorcon

    tac

    t

    12V

    dc

    Com

    Safe

    Haza

    rd

    Doorcon

    tac

    t

    Doorcon

    tac

    t

    12V

    dc

    Com

    Safe

    Haza

    rd

    Doorcon

    tac

    t

    Doorcon

    tac

    t

    TB1

    M4

    M2

    M5

    M3

    M1

    14

    12

    108642

    15

    13

    1197531

    M1

    M2 M

    3M4 M

    5

    FX1s-1

    4MR

    -ES/UL

    0V

    Y0

    Y3

    Y5

    Y4

    Y2

    Y1

    24V

    COM

    0

    COM2

    COM

    1

    N

    L

    S/S

    X1

    X5

    X7

    X6

    X4

    X2

    X0

    X3

    12

    0V

    AC1

    M1

    AC5

    M5

    AC4

    M4

    AC3

    M3

    AC2

    M2

    1 32 14

    13 1 32 1

    413 1 32 1

    413 1 32 1

    413 1 32 1

    413

    1 32 54 6 87 109 1

    113

    12

    15

    14

    16

    18

    17

    20

    19

    21

    23

    22

    25

    24

  • 7/26/2019 Isolation Panels

    22/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsControlled Panels Technical Data

    22

    01/2014

    Outline

    30(762)

    5(127)

    32(819)

    14(356)

    53(1346)

    51(1295)

    14(356)

    Top View

    Side ViewFront View

    Dual dimensions: Inches(mm)

  • 7/26/2019 Isolation Panels

    23/32

    Medical Isolated Power PanelsFeatures and Options X-Ray/Power Receptacle Modules

    2301/2014 20122014 Schneider Electric

    All Rights Reserved

    X-ray/laser power receptacle modules from Schneider Electric provide a convenient source of power

    for portable X-ray and laser equipment. The hospital-grade receptacle provided in each module is

    matched to the NEMA plug configuration of the equipment with which it will be used. The recessed

    power receptacle is mounted behind the door on the stainless steel faceplate. The door features a

    concealed hinge and a touch latch.

    Designed for flush- or surface-mounted applications

    Available options:

    Iso-Gard IG2000P remote indicator

    In-use lamp; when illuminated, indicates the receptacle cannot be used

    Door contact (limit switch)

    UL Listed (UL1047)

    Five-year limited warranty

    For questions, further assistance, or additional equipment or custom requirements, please contact

    your local Schneider Electric representative.

    TEST

    PRUEBA

    IG2000P

    Customer-specifiedreceptacle

    IG2000P

    In-use light (optional)

    Door interlock (remotely operated)

  • 7/26/2019 Isolation Panels

    24/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsX-Ray/Power Receptacle Modules Ordering Information

    24

    01/2014

    Customer-Specified Receptacles

    250 V Grounding Devices

    Ampere RatingsReceptacle Configuration

    Straight Blade Locking Hubbell

    15

    20

    30

    50

    60

    Catalog No. Description Back Box

    SXRM1A1F Flush-mounted, IG2000P installed, receptacle Hubbell IN16494

    SB120804

    SXRM2A1F Flush-mounted, IG2000P installed, receptacle NEMA 6-15R

    SXRM3A1F Flush-mounted, IG2000P installed, receptacle NEMA 6-20R

    SXRM4A1F Flush-mounted, IG2000P installed, receptacle NEMA 6-30R

    SXRM5A1F Flush-mounted, IG2000P installed, receptacle NEMA 6-50R

    SXRM6A1F Flush-mounted, IG2000P installed, receptacle NEMA L6-15R

    SXRM7A1F Flush-mounted, IG2000P installed, receptacle NEMA L6-20R

    SXRM8A1F Flush-mounted, IG2000P installed, receptacle NEMA L6-30R

    SXRM9A1F Flush-mounted, IG2000P installed, receptacle Hubbell CS8269

    SXRM1A2F Flush-mounted, IG2000P installed, receptacle Hubbell IN16494, in-use light

    SXRM2A2F Flush-mounted, IG2000P installed, receptacle NEMA 6-15R, in-use light

    SXRM3A2F Flush-mounted, IG2000P installed, receptacle NEMA 6-20R, in-use light

    SXRM4A2F Flush-mounted, IG2000P installed, receptacle NEMA 6-30R, in-use light

    SXRM5A2F Flush-mounted, IG2000P installed, receptacle NEMA 6-50R, in-use light

    SXRM6A2F Flush-mounted, IG2000P installed, receptacle NEMA L6-15R, in-use light

    SXRM7A2F Flush-mounted, IG2000P installed, receptacle NEMA L6-20R, in-use light

    SXRM8A2F Flush-mounted, IG2000P installed, receptacle NEMA L6-30R, in-use light

    SXRM9A2F Flush-mounted, IG2000P installed, receptacle Hubbell CS8269 , in-use light

    NEMA 6-15R NEMA L6-15R

    NEMA 6-20R NEMA L6-20R

    NEMA 6-30R NEMA L6-30R

    NEMA 6-50R CS8269

    IN16494

  • 7/26/2019 Isolation Panels

    25/32

    Medical Isolated Power PanelsOverview and Ordering Information Power and Master Grounding Station Modules

    2501/2014 20122014 Schneider Electric

    All Rights Reserved

    Power Modules

    Where room ground extensions and power receptacles are both required,

    these modules offer convenience and save labor in field wiring. Each unit

    includes four power receptacles, four twist-to-lock ground jacks, and a

    ground bus, along with a generous number of lugs for external ground

    connections.The main ground connection in the module accommodates up to a #1/0

    cable. The unit is completely factory wiredonly field power connections

    and ground connections are necessary. The front trim is #304 stainless

    steel with a #4 brushed finish.

    Master Grounding Station Module120 Series

    These modules can be used as a collection point for grounds in a large area

    such as a coronary care unit or intensive care ward. The primary application

    is where the equipment ground bus in the emergency distribution panel is

    not conveniently located or cannot accept the large number of connections

    required for the area.

    This unit can be connected to the ground point by a single conductor and

    located in a more convenient area. The module contains a bus bar with 18

    lugs for field connections and has a Type #304 brushed stainless steel

    cover plate. It is designed for installation into a 12 in. x 8 in. x 4 in. back box.

    Any combination of eight receptacles or ground connectors is allowed via

    the Product Selector.

    Back Boxes

    The back box required is based on the quantity of devices chosen.

    Catalog No. DescriptionBack

    Box

    SGPMF4DR4 Power module, 4 ground connectors, 4 duplex red, flush-mounted

    SB120804

    SGPMF4DI4 Power module, 4 ground connectors, 4 duplex ivory, flush-mounted

    SGPMF0DR2 Power module, 2 duplex red, flush-mountedSGPMF0DI2 Power module, 2 duplex ivory, flush-mounted

    SGPMF0NN0 Master grounding station, flush-mounted

    SGPMF4NN0 Master grounding station, 4 ground connectors, flush-mounted

    SGPMG4SR4 Power module, 4 ground connectors, 4 single red, trim

    Customer-supplied,four-gang

    SGPMG4SI4 Power module, 4 ground connectors, 4 single ivory, trim

    SGPMG4NN0 Master grounding station, 4 ground connectors, trim

    SGPMG2NN0 Master grounding station, 2 ground connectors, trim

    4.00(102)

    Red or ivory duplex receptacle:

    20 A, hospital grade

    12.00(305)

    12.00(305)

    14.00(356)

    14.00(356)

    4.00(102)

    8.00(283)

    12.00(305)

    10.00(254)

    14.00(356)

    Ground jack: 30 A, twist-to-lock

    Stainless steel faceplate

    Back box

    SB121204

    Back box

    SB120804 Dual dimensions: Inches(mm)

  • 7/26/2019 Isolation Panels

    26/32

    Medical Isolated Power PanelsHospital-Grade Ground Cords Ordering Information

    20122014 Schneider Electric

    All Rights Reserved

    26

    01/2014

    Hospital-Grade Ground Cords

    Shorter cables are available. Please contact your local Schneider Electric

    representative for the correct part number.Ground Cord with Lug End

    Ground Cord with Clip End

    Ground Jack

    Catalog No. DescriptionLegacy Catalog

    No.

    SHGC15L 15 ft., with plug and lug for #10 stud P751N

    SHGC15C 15 ft., with plug and heavy duty clip P753N

    SHGC12L 12 ft. , with plug and lug for #10 stud

    Not applicableSHGC12C 12 ft. , with plug and heavy duty clip

    SHGC10L 10 ft. , with plug and lug for #10 stud

    SHGC10C 10 ft. , with plug and heavy duty clip

    SHGJ1R Hospital grade ground jack, 30 A, 250 V, green 4319950007

  • 7/26/2019 Isolation Panels

    27/32

    Medical Isolated Power PanelsOverview IG2000 Series Remote Indicators

    2701/2014 20122014 Schneider Electric

    All Rights Reserved

    Schneider Electric offers two remote indicators for interfacing with line

    isolation monitors: the Iso-Gard IG2000P and IG2000CBM.

    IG2000P Remote Indicator

    The Iso-Gard IG2000P remote indicator from Schneider Electric provides

    remote indication of the visible and audible alarms from a line isolation

    monitor (LIM).

    Green LEDstays illuminated while the system is in normal condition

    Red hazard LEDilluminates when the Total Hazard Current exceeds

    the preset alarm level

    Audible hazard alarmsounds when the Total Hazard Current exceedsthe preset alarm level

    Mute button with yellow LEDsilences the audible alarm on the remote

    indicator (local muting), or silences all audible alarms in the system

    (system muting)

    Test buttonremotely performs a functional test of the LIM

    The IG2000P remote indicator is available mounted in a one- or two-gang

    stainless steel faceplate for flush mounting into a panel or wall box with a

    two-inch minimum depth. The basic electrical connection is made using

    three wires.

    Features

    Interfaces with all Iso-Gard LIMs from Schneider Electric (Series 1, A, B,

    C, D, and 6), as well as with LIMs from other manufacturers Does not interfere with medical equipment

    Uses low voltage wiring (12 Vdc or 12 Vac)

    Mounts to a standard, electrical gang box

    Connects by means of a screw terminal strip

    Uses long-life, LED displays

    Features an easy-to-clean, rugged, stainless steel and Lexan design

    Catalog No. Description Back Box

    IG2000PG1 Composite unit incorporating a displaypanel section with alarm and test

    functions

    Customer-supplied, single-gang box

    IG2000PG2 Customer-supplied, two-gang box

    IG2000CBM

    Composite unit incorporating a displaypanel section with alarm and testfunction. Also includes a digital TotalHazard Current (THC) display area

    Customer-supplied, two-gang box

    Redhazard

    LED

    Test

    button

    Mutebutton

    GreenLED

  • 7/26/2019 Isolation Panels

    28/32

    Medical Isolated Power PanelsIG2000 Series Remote Indicators Overview

    20122014 Schneider Electric

    All Rights Reserved

    28

    01/2014

    IG2000CBM Remote Indicator

    The Iso-Gard IG2000CBM remote indicator from Schneider Electric

    provides remote indication of the visible and audible alarms and digital mA

    reading from an Iso-Gard Series 6 (IG6) line isolation monitor (LIM).

    Green LEDstays illuminated while the system is in normal condition

    Red hazard LEDilluminates when the Total Hazard Current (THC)exceeds the preset alarm level

    Audible hazard alarmsounds when the THC exceeds the preset

    alarm level

    Mute button with yellow LEDsilences the audible alarm on the remote

    indicator (local muting), or silences all audible alarms in the system

    (system muting)

    Test buttonremotely performs a functional test of the LIM

    Digital displayshows the THC in real time

    The IG2000CBM remote indicator is available mounted in a two-gang

    stainless steel faceplate for flush mounting into a wall box with a two-inch

    minimum depth. The basic electrical connection is made using four wires.

    Features

    Interfaces with the Iso-Gard Series 6 LIM from Schneider Electric

    Does not interfere with medical equipment

    Uses low voltage wiring and RS-485 wiring

    Mounts to a standard, electrical two-gang box

    Connects by means of a screw terminal strip

    Uses long-life, LED displays

    Features an easy-to-clean, rugged, stainless steel and Lexan design

    Red hazard LED

    Test button

    Mute button

    Green LED

    THC display

  • 7/26/2019 Isolation Panels

    29/32

    Medical Isolated Power PanelsTechnical Data IG2000 Series Remote Indicators

    2901/2014 20122014 Schneider Electric

    All Rights Reserved

    Outline

    4.60(117)

    4.50(114)

    2.80(71)

    4.50(114)

    Dual dimensions: Inches(mm)

    4.60(117)

    4.50(114)

    IG2000PG1 IG2000PG2

    IG2000CBM

  • 7/26/2019 Isolation Panels

    30/32

    20122014 Schneider Electric

    All Rights Reserved

    Medical Isolated Power PanelsMiscellaneous Technical Data

    30

    01/2014

    Main Disconnect Circuit Breaker Size

    kVA Primary Voltage Actual Circuit Breaker Rating (A)

    3

    120 35

    208 20

    220 20

    240 20

    277 15

    5

    120 60

    208 30

    220 30

    240 30

    277 25

    480 15

    7.5

    120 80

    208 45

    220 45

    240 40

    277 35

    480 20

    10

    120 100

    208 60

    220 60

    240 60

    277 45

    480 30

    15

    120 150

    208 90

    220 90

    240 80

    277 70

    480 40

    20

    208 125

    220 125

    240 100

    277 90

    480 60

    22.5

    208 125

    220 125

    240 125

    277 100

    480 60

    25

    208 150

    220 150

    240 150

    277 125

    480 70

  • 7/26/2019 Isolation Panels

    31/32

    Medical Isolated Power Panels

    3101/2014 20122014 Schneider Electric

    All Rights Reserved

  • 7/26/2019 Isolation Panels

    32/32

    Schneider Electric USA, Inc.1415 S. Roselle RoadPalatine, IL 60067 USA1-888-778-2733

    20122014 Schneider Electric All Rights ReservedIso-Gard, PowerPact, QO, QOB, Schneider Electric, and Square D are trademarks owned bySchneider Electric Industries SAS or its affiliated companies. All other trademarks are the propertyof their respective owners.