ISOLATOR
![Page 2: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/2.jpg)
Standards Referred
IEC 62271-102 (High Voltage Switch gear and control
gear)
IEC 61128 (Alternating current disconnectors – Bus-
transfer current switching by disconnectors)
IEC 60060-1 (High-voltage test techniques)
IS: 9921 (Alternating current disconnectors)
IEC 60694 (Common Specifications For High-Voltage
Switchgear and Controlgear Standards)
![Page 3: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/3.jpg)
Purpose of Isolators
Used to isolate the circuit under no load
conditions.
Used for isolation of networks for small
switching currents (<0.5 A) and also for
commutation currents.
Cannot be used to make or break the
circuit.
It is used in addition to Circuit Breakers.
![Page 4: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/4.jpg)
Types of Isolators
Horizontal centre Break isolator (Two column Rotary Disconnector) (72.5KV – 765 KV)
Horizontal Double break Isolator( Three column rotary Disconnector) (12 KV – 765 KV)
Vertical Break Isolator( Two column Vertical Break Disconnector) (<25KV)
Knee Type Isolator (33KV – 765KV)Pantograph Isolator( Single column
Disconnector)(145KV – 765KV)
![Page 5: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/5.jpg)
Horizontal centre break Isolator
![Page 6: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/6.jpg)
![Page 7: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/7.jpg)
Horizontal Double break Isolator
![Page 8: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/8.jpg)
![Page 9: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/9.jpg)
Vertical Break Disconnector
![Page 10: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/10.jpg)
![Page 11: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/11.jpg)
Knee Type
![Page 12: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/12.jpg)
![Page 13: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/13.jpg)
Pantograph Insulator
![Page 14: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/14.jpg)
![Page 15: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/15.jpg)
![Page 16: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/16.jpg)
Operating Mechanism
Motor Operating MechanismSpur Gear followed by Worm Gear is installed for smooth operation and self locking
Manual with Gear MechanismHand operation with Worm Gear is used for self locking capability
Manual OperationHand operation using lever is
practiced
![Page 17: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/17.jpg)
Spur Gear Worm Gear
![Page 18: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/18.jpg)
Earth Switch
Connected between line conductor and
earth.
Usually mounted on frame of isolator.
Interlocked mechanically and electrically
with isolators
![Page 19: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/19.jpg)
Single Coloumn Earth Switch
![Page 20: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/20.jpg)
TerminologyParticulars Data for 400
KV
Rated Current under site conditions at 50ºC ambient
2000/3150Amp.
Rated Short Circuit current of Isolator and E/S for 1 sec.
50KA(rms)
Rated dynamic short circuit withstand current of Isolator and E/S.
125 KA(peak)
Rated Mechanical terminal Load
Dielectric Withstand Capacity 520 KVrms
One min. power freq. withstand voltagei. Against Groundii. Against Isolating Distance
520KVrms610KVrms
1.2/50 µsec. Impulse withstand voltagei. Against Groundii. Against Isolating Distance
1425KV(peak)1450(+240)KV(peak)
Corona Extinction Voltage 320 KVrms
Operating Time Less than 12 Sec.
![Page 21: Isolator by Anuj](https://reader038.vdocument.in/reader038/viewer/2022111016/5533ab90550346c3558b49d2/html5/thumbnails/21.jpg)