J-series Chillers KITS and ACCESSORIES
Product Presentation
2Apr 19, 2023
Public
New Chiller Accessories
Daikin Name EWAD..AJ EWYD..AJ EWAD..BJ EWAP..AJ EWWD..DJ EWWD..CJ EWWD..BJEKAC200J o o o o o o oEKACBAC o o o o o o oEKACLON o o o o o o oEKCON o o o o o o oEKCONUSB o o o o o o oEKMODEM o o o o o o oEKGSMOD o o o o o o oEKBMSBNJ - - o o o o oEKRUPCJ o o - - - - -EKRUPCK - - o o o o oEKCSCII o o o o o o oEKPV2J o o o o o o oEKBT500N o o o o o o oEKBTC10N o o o o o o oEKBT500C o o o o o o oEKBTC10C o o o o o o o
o = available option
3Apr 19, 2023
Public
EKAC200J: RS485 Serial Address CardThree different connection possibilities exist: BMS: MODBUS needs an EKAC200J per connected chiller. No gateway. BMS: BACnet PTP (Point to Point) protocol requires an EKAC200J per connected
chiller and an EKBMSBNJ gateway. BACnet PTP is a low level Class 2 BACnet. RS485: All other communication or plant management accessories requiring RS485
or RS232 communication require an EKAC200J per connected chiller.
Unit 1
RS485 Supervisory Network
Unit 2 Unit 3 Unit ..
BACnet PTP (Class 2)
GatewayEKBMSBNJ
Supervisory systemEg: Chiller Sequencing Control EKCSCII
RS485: MODBUS Protocol
EKAC EKAC EKAC
EKAC
KEY
RS485 Serial Address Card EKAC200J
Unit 1
RS485 Supervisory Network
Unit 2 Unit 3 Unit ..
BACnet PTP (Class 2)
GatewayEKBMSBNJ
Supervisory systemEg: Chiller Sequencing Control EKCSCII
RS485: MODBUS Protocol
EKAC EKAC EKAC
EKAC
KEY
RS485 Serial Address Card EKAC200J
4Apr 19, 2023
Public
EKACBAC
Ethernet Address Card for Class 4 BACnet communication with a BMS system. Each connected chiller requires an Ethernet card. No gateway is needed.
Unit 1 Unit 2 Unit 3 Unit ..
BACnet (Class 4)
EKAC EKAC EKAC
EKAC
KEY
Ethernet Address CardEKACBAC
Unit 1 Unit 2 Unit 3 Unit ..
BACnet (Class 4)
EKAC EKAC EKAC
EKAC
KEY
Ethernet Address CardEKACBAC
5Apr 19, 2023
Public
EKACLON
LON FTT Address Card for LON communication with a BMS system. The card is supplied preloaded with the respective LON xif chiller profile.
Unit 1 Unit 2 Unit 3 Unit ..
LON Protocol
EKAC EKAC EKAC
EKAC
KEY
LON FTT Address CardEKACLON
Unit 1 Unit 2 Unit 3 Unit ..
LON Protocol
EKAC EKAC EKAC
EKAC
KEY
LON FTT Address CardEKACLON
6Apr 19, 2023
Public
EKMODEM: Fixed Line Modem for remote monitoring of the chiller plant. A maximum of 32 chillers can be connected to a single modem. The modem communication protocol is RS232 and an EKAC200J and EKCON are necessary.
EKGSMOD: GSM Modem for remote monitoring of the chiller plant. A maximum of 32 chillers can be connected to a single modem. The modem communication protocol is RS232 and an EKAC200J and EKCON are necessary.
Tele-communication
Unit 1
RS232 Supervisory Network
Unit 2 Unit 3 Unit ..
GSM ModemEKGSMOD
Supervisory systemEg: Plant Visor EKPV2J
EKAC EKAC EKAC
EKAC
KEY
RS485 Serial Address Card EKAC200J
EKCON EKCON EKCON
Fixed ModemEKMODEM
EKCON RS485 to RS232 Converter EKCON
Unit 1
RS232 Supervisory Network
Unit 2 Unit 3 Unit ..
GSM ModemEKGSMOD
Supervisory systemEg: Plant Visor EKPV2J
EKAC EKAC EKAC
EKAC
KEY
RS485 Serial Address Card EKAC200J
EKCON EKCON EKCON
Fixed ModemEKMODEM
EKCON RS485 to RS232 Converter EKCON
7Apr 19, 2023
Public
Remote User Interfaces EKRUPCJ: Remote control interface for EWAD~AJYNN. This interface can be
located upto 500m from the unit.
EKRUPCK: Remote control interface for other ranges. This interface can be located upto 500m from the unit.
Unit 1
pLAN
EKRUPCJ orEKRUPCK
Unit 1
pLAN
EKRUPCJ orEKRUPCK
8Apr 19, 2023
Public
EKCSCII: Chiller Sequencing Control
Chiller sequencing (Max chillers = 5) Cooling towers sequencing control (Max Towers = 5 each with 2 steps) Chiller sequencing Primary pump control (Max Primary pumps = 1) Secondary pumps control (Max Secondary Pumps = 5, with upto 2 inverter driven) Secondary circuit bypass valve control Chilled water circuit bypass valve control Set point override Demand limit Double set point Unit turnover BMS connectivity (Carel, Modbus, LonWork, BACnet) Remote On/Off
Separate control panel to allow the sequencing of a group of chillers (max 5) as a single plant for optimised power management and energy flow balancing.
Note: See separate EKCSCII presentation
9Apr 19, 2023
Public
EKPV2J: Plant Visor 2 For local monitoring (PC) of each chiller or remote monitoring via modem (EKMODEM or EKGSMOD) with the PlantVisorTM supervision program.
Compatible with Windows 2000 2nd Edition and Windows XP. Both local and remote monitoring is by RS232 communication.
The main monitoring and control features are: Unit status monitoring Circuit status monitoring Modification of setpoints Display of Alarms
10Apr 19, 2023
Public
Hydraulic Kits: Buffer Tanks EKBT500N: 500l naked buffer tank on metal base frame. EKBTC10N: 1000l naked buffer tank on metal base frame. EKBT500C: 500l buffer tank with cabinet on metal base frame. EKBTC10C: 1000l buffer tank with cabinet on metal base frame.
Naked Buffer Tank on Base Frame
Plan View
EKBT***C
Buffer Tank with cabinet in RAL7032
EKBT***N
11Apr 19, 2023
Public