jalthotage dewadasa thesis.bak

Upload: abhishek-kumar

Post on 03-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    1/179

    Protection of distributed generation

    interfaced networks

    Manjula Dewadasa

    B.Sc (Hons) in Electrical Engineering

    A Thesis submitted in partial fulfilment of the requirements for

    the degree of

    Doctor of Philosophy

    F lt f B ilt E i t d E i i

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    2/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    3/179

    Keywords

    Distributed generation, Microgrids, Distributed generator protection, Converter

    interfaced distributed generators, Protective relays, Inverse time admittance relay,

    Relay coordination, Relay Grading, Islanded operation, Re-synchronisation,

    Reclosing, Fold back current control, Fault detection, Fault isolation, Arc extinction,

    System restoration.

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    4/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    5/179

    Abstract

    With the rapid increase in electrical energy demand, power generation in the

    form of distributed generation is becoming more important. However, the

    connections of distributed generators (DGs) to a distribution network or a microgrid

    can create several protection issues. The protection of these networks using

    protective devices based only on current is a challenging task due to the change in

    fault current levels and fault current direction. The isolation of a faulted segment

    from such networks will be difficult if converter interfaced DGs are connected as

    these DGs limit their output currents during the fault. Furthermore, if DG sources are

    intermittent, the current sensing protective relays are difficult to set since fault

    current changes with time depending on the availability of DG sources. The system

    restoration after a fault occurs is also a challenging protection issue in a converter

    interfaced DG connected distribution network or a microgrid. Usually, all the DGs

    will be disconnected immediately after a fault in the network. The safety of

    personnel and equipment of the distribution network, reclosing with DGs and arc

    extinction are the major reasons for these DG disconnections.

    In this thesis, an inverse time admittance (ITA) relay is proposed to protect a

    distribution network or a microgrid which has several converter interfaced DG

    connections. The ITA relay is capable of detecting faults and isolating a faulted

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    6/179

    to some of the existing protection schemes. The relay performance is evaluated in

    different types of distribution networks: radial, the IEEE 34 node test feeder and a

    mesh network. The results are validated through PSCAD simulations and MATLAB

    calculations. Several experimental tests are carried out to validate the numerical

    results in a laboratory test feeder by implementing the ITA relay in LabVIEW.

    Furthermore, a novel control strategy based on fold back current control is

    proposed for a converter interfaced DG to overcome the problems associated with

    the system restoration. The control strategy enables the self extinction of arc if the

    fault is a temporary arc fault. This also helps in self system restoration if DG

    capacity is sufficient to supply the load. The coordination with reclosers without

    disconnecting the DGs from the network is discussed. This results in increased

    reliability in the network by reduction of customer outages.

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    7/179

    Table of Contents

    List of figures ix

    List of tables xiii

    List of appendices xv

    List of symbols and abbreviations xvii

    Chapter 1: Introduction ............................................. 1

    1.1 Background .............................................................................................. 1

    1.2 Aims and objectives of the thesis ............................................................. 3

    1.3 Significance of research ........................................................................... 3

    1.4 The original contributions of the research ............................................... 4

    1.4.1 A novel relay characteristic for DG connected networks ................. 4

    1.4.2 A new DG control strategy for fast system restoration ..................... 4

    1.5 Structure of the thesis ............................................................................... 5

    Chapter 2: Literature review ..................................... 7

    2.1 Introduction .............................................................................................. 7

    2.2 Protection issues and solutions ................................................................ 8

    2.2.1 Islanding operation and anti-islanding protection ............................. 9

    2.2.2 Coordination between protective devices ....................................... 12

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    8/179

    Chapter 3: Protective relay for DG connected

    networks ................................................. 27

    3.1 Introduction ............................................................................................ 27

    3.2 ITA relay characteristics ........................................................................ 28

    3.3 ITA relay reach settings ......................................................................... 30

    3.4 Different ITA relay elements ................................................................. 34

    3.4.1 Earth elements ................................................................................. 34

    3.4.2 Phase elements ................................................................................. 34

    3.4.3 Directional elements ........................................................................ 35

    3.5 Connection of ITA relays to a network .................................................. 35

    3.6 Settings of ITA relays to detect resistive faults ..................................... 37

    3.6.1 Zone-1 settings ................................................................................ 38

    3.6.2 Zone-2 settings ................................................................................ 39

    3.6.3 Zone-3 settings ................................................................................ 39

    3.7 Practical issues for admittance calculation ............................................ 41

    3.8 Summary ................................................................................................ 43

    Chapter 4: Evaluation of ITA relay performance . 45

    4.1 Introduction ............................................................................................ 45

    4.2 Inverse time overcurrent relays .............................................................. 46

    4.3 Distance relays ....................................................................................... 48

    4.4 ITA relays ............................................................................................... 51

    4.5 ITA relay performance ........................................................................... 54

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    9/179

    Chapter 5: Fold back current control and system

    restoration .............................................. 79

    5.1 Introduction ............................................................................................ 79

    5.2 Fold back current control characteristics ............................................... 80

    5.2.1 Fold back during contingency ......................................................... 80

    5.2.2 Restoration process .......................................................................... 835.2.3 Coordination with reclosers ............................................................ 86

    5.2.4 DG protection .................................................................................. 87

    5.3 Arc fault model selection for simulation ............................................... 88

    5.3.1 Primary arc fault .............................................................................. 89

    5.3.2 Secondary arc fault .......................................................................... 90

    5.3.3 Arc extinction .................................................................................. 91

    5.4 Simulation studies .................................................................................. 91

    5.4.1 Results for permanent faults ............................................................ 93

    5.4.2 Results for Arc Faults ...................................................................... 97

    5.4.3 Auto reclosing ............................................................................... 100

    5.5 Summary .............................................................................................. 104

    Chapter 6: Experimental results ........................... 105

    6.1 Introduction .......................................................................................... 105

    6.2 Test feeder arrangement ....................................................................... 105

    6.3 Relay performance evaluation ............................................................. 109

    6.4 Relay response for different fault locations ......................................... 111

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    10/179

    6.5.2 The effect of fundamental extraction ............................................ 124

    6.6 Summary .............................................................................................. 130

    Chapter 7: Conclusions and recommendations ... 131

    7.1 Conclusions .......................................................................................... 131

    7.2 Recommendations for future research ................................................. 134

    7.2.1 Consideration of rotary type DGs for protection........................... 134

    7.2.2 Fold back type current control for rotary type DGs ...................... 134

    7.2.3 The effect of single phase converters ............................................ 134

    References 135

    Publications arising from the thesis 143

    Appendix-A 145

    Appendix-B 147Appendix-C 153

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    11/179

    List of Figures

    Fig. 2.1 Different types of communication networks (Adapted from [55]) .... 24

    Fig. 3.1 A radial distribution feeder ................................................................. 28

    Fig. 3.2 The variation of normalised admittance ............................................. 29

    Fig. 3.3 Relay tripping characteristic curve ..................................................... 30

    Fig. 3.4 A radial distribution feeder with relays .............................................. 31Fig. 3.5 Relay protection zones and relay coordination .................................. 32

    Fig. 3.6 Relay settings based on different forward and reverse reach ............. 33

    Fig. 3.7 Relay connection diagram to the system ............................................ 36

    Fig. 3.8 Process of relay tripping decision making ......................................... 36

    Fig. 3.9 Relay tripping characteristics of different zones ................................ 41

    Fig. 4.1 A radial distribution feeder with relays .............................................. 47

    Fig. 4.2 Inverse time overcurrent relay grading .............................................. 47

    Fig. 4.3 MHO relay characteristic ................................................................... 50

    Fig. 4.4 MHO relay zone settings and timing diagram ................................... 50

    Fig. 4.5 ITA relay grading ............................................................................... 52

    Fig. 4.6 Faulted line with a relay ..................................................................... 52

    Fig. 4.7 ITA relay characteristic in R-X diagram ............................................ 54

    Fig. 4.8 Radial distribution feeder with DGs ................................................... 55

    Fig. 4.9 OC and ITA relay grading .................................................................. 57Fig. 4.10 OC and ITA relay response when DG1 is connected ....................... 58

    Fig. 4.11 Distance and ITA relay response when DG1 is connected .............. 58

    Fig. 4.12 OC and ITA relay time-current characteristic .................................. 59

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    12/179

    Fig. 4.20 Fault current seen by each ITA relay along the feeder ..................... 65

    Fig. 4.21 Random load and DG distribution profiles along the feeder............ 66Fig. 4.22 ITA relay response for random load and DG distribution profiles .. 66

    Fig. 4.23 IEEE 34 node test feeder with ITA relays ........................................ 67

    Fig. 4.24 ITA relay response for SLG fault at node 858 ................................. 69

    Fig. 4.25 ITA relay response for SLG fault at node 842 ................................. 69

    Fig. 4.26 ITA relay response for SLG fault at node 862 ................................. 70

    Fig. 4.27 Mesh network under study ............................................................... 71

    Fig. 4.28 Equivalent representation of the faulted network ............................. 74

    Fig. 4.29 ITA relay response for different values of fault resistances and DG

    currents ............................................................................................ 76

    Fig. 5.1 Proposed fold back characteristics ..................................................... 82

    Fig. 5.2 System restoration .............................................................................. 85

    Fig. 5.3 Simulated radial feeder with DGs ...................................................... 92

    Fig. 5.4 Calculated ITA relay response for a three phase fault ....................... 94

    Fig. 5.5 DG1 response (a) output voltage (b) output current (c) real poweroutput ................................................................................................. 95

    Fig. 5.6 DG1 response (a) output voltage (b) output current (c) real power

    output ................................................................................................. 97

    Fig. 5.7 System behaviour for an arc fault (a) arc voltage (b) arc current (c) arc

    resistance (d) relay response ............................................................... 99

    Fig. 5.8 DG1 behaviour for an arc fault (a) output voltage (b) output current 99

    Fig. 5.9 DG1 behaviour when downstream relay fails (a) output voltage (b)

    output current 100

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    13/179

    Fig. 6.6 Calculated relay response in different zones for bolted faults ......... 111

    Fig. 6.7 The variation of voltage and current for SLG faults at BUS-2 ........ 113Fig. 6.8 The variation of voltage and current for SLG faults at BUS-3 ........ 114

    Fig. 6.9 The variation of voltage and current for SLG faults at BUS-4 ........ 116

    Fig. 6.10 The variation of voltage and current for SLG faults at BUS-5 ...... 117

    Fig. 6.11 Voltage and current for a fault at BUS-2 ....................................... 118

    Fig. 6.12 Voltage and current for a fault at BUS-3 ....................................... 119

    Fig. 6.13 Voltage and current for a fault at BUS-4 ....................................... 119

    Fig. 6.14 Voltage and current for a fault at BUS-5 ....................................... 119

    Fig. 6.15 Change of parameters during a resistive fault at BUS-2 ................ 122

    Fig. 6.16 Test feeder with an infeed .............................................................. 123

    Fig. 6.17 Change of parameters for a fault at BUS-2 with fault resistance and

    infeed ............................................................................................. 124

    Fig. 6.18 A SLG fault at synchronous generator connected feeder ............... 125

    Fig. 6.19 Current and voltage during a SLG fault ......................................... 126

    Fig. 6.20 Values of relay parameters during a SLG fault .............................. 127Fig. 6.21 Faulted current and voltage during a SLG fault ............................. 128

    Fig. 6.22 Values of calculated relay parameters during a SLG fault ............. 129

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    14/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    15/179

    List of Tables

    Table 3.1 Selection criterion of a directional element ..................................... 35

    Table 4.1 System parameters ........................................................................... 55

    Table 4.2 OC relay settings ............................................................................. 56

    Table 4.3 Zone characteristics of ITA relay .................................................... 56

    Table 4.4 System parameters ........................................................................... 64

    Table 4.5 ITA relay forward and reverse reach settings .................................. 68

    Table 4.6 System parameters ........................................................................... 71

    Table 4.7 Zone-3 grading of ITA relays .......................................................... 72

    Table 4.8 Fault clearing time of ITA relays .................................................... 73

    Table 5.1 Simulated system data ..................................................................... 92

    Table 5.2 Arc model parameters ...................................................................... 97

    Table 6.1 System parameters of the experimental setup ............................... 108

    Table 6.2 Relay reach setting and tripping characteristic in each zone ......... 110

    Table 6.3 ITA relay response for faults at BUS-2 ......................................... 113

    Table 6.4 ITA relay response for faults at BUS-3 ......................................... 114

    Table 6.5 ITA relay response for faults at BUS-4 ......................................... 115

    Table 6.6 ITA relay response for faults at BUS-5 ......................................... 116

    Table 6.7 ITA relay response for SLG faults with higher source impedance 118

    Table 6.8 Relay parameters during a resistive fault ...................................... 121Table 6.9 Change of relay parameters due to fault resistance and infeed ..... 123

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    16/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    17/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    18/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    19/179

    List of principle symbols and abbreviations

    A, , k Relay tripping constants

    CB Circuit breaker

    CT Current transformer

    DFT Discrete Fourier transform

    DG Distributed generator

    FFT Fast Fourier transform

    IDG Distributed generator current

    Ip Pickup current

    IRa, IRb Current in faulted phases A and B

    Ir Rated current of converter

    ITA Inverse time admittance

    lp Primary arc length

    ls Secondary arc length

    MI Multiple of pickup current

    OC Overcurrent

    PCC Point of common coupling

    R1, R2, R3 Protective relays

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    20/179

    VT Voltage transformer

    Ym Measured admittance

    Yr Normalised admittance

    YRK1 Positive sequence measured admittance

    Yt Total admittance

    Zdg Source impedance of distributed generator

    ZLG Apparent impedance

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    21/179

    Statement of original authorship

    The work contained in this thesis has not been previously submitted to meet

    requirements for an award at this or any other higher education institution. To the

    best of my knowledge and belief, this thesis contains no material previously

    published or written by another person except where due reference is made.

    Signature:.

    Date:.

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    22/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    23/179

    Acknowledgements

    First and foremost, I would like to convey my sincerest and deepest thanks to

    my supervisors, Prof. Gerard Ledwich and Prof. Arindam Ghosh, for their

    incomparable guidance and endless encouragement throughout my doctoral research.

    It has been a great privilege for me to work under this supervision.

    I wish to express my thanks to the Faculty of Built Environment and

    Engineering, Queensland University of Technology (QUT) for providing me with

    financial support during my research candidature.

    I would also like to thank staff in the research portfolio office in QUT for their

    generous support and assistance throughout the candidature, and the staff in the

    School of Engineering Systems for providing such a helpful environment. Further, I

    am thankful to staff in the Power Engineering Group for their valuable advice.

    I would like to extend my appreciation to all the technical staff who supported

    me during the laboratory experiments. Without this support, experimental work

    would not have been successful.

    I would further like to thank to all of my friends for sharing valuables ideas, for

    supporting me during the experimental work, and for making the research period an

    enjoyable one. Also, I am grateful to my parents for encouraging me to pursue higher

    studies, and I thank them and my relatives for their constant support.

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    24/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    25/179

    Chapter 1: Introduction1.1Background

    With the rapid increase in electrical energy demand, power utilities are seeking

    for more power generation capacity. However, environmental and right-of-way

    concerns make the addition of central generating stations and the erection of power

    transmission lines more difficult. Thus, newer technologies based on renewable

    energy are becoming more acceptable as alternative energy generators. This

    renewable energy push is starting to spread power generation over distribution

    networks in the form of distributed generation and will lead to a significant increase

    in the penetration level of distributed generation in the near future. It is expected that

    20% of power generation will be through renewable sources by the year 2020 [1].

    However, by that time, the penetration level of DGs is expected to be higher in many

    countries which are seeking accelerated deployment of renewable technologies. The

    DGs based on renewable energy sources will help in reducing greenhouse gas

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    26/179

    Chapter 1: Introduction

    fully controllable load which at peak hours can even supply power back to the utility

    grid. A microgrid can operate in either (utility) grid connected mode or islanded

    mode and can seamlessly change between these modes. In an islanded mode, the

    DGs connected to the microgrid supply its loads, where a provision for load shedding

    exists if the load demand is higher than the total DG generation.

    Most of the existing distribution systems are radial where power flows from

    substation to the customers in a unidirectional manner. Overcurrent protection is

    used for such systems because of its simplicity and low cost [1, 4]. However, once a

    DG or a microgrid is connected within the main utility system, this pure radial nature

    is lost [2, 5, 6] and the existing protection devices may not respond in the fashion for

    which they were initially designed [4]. This change in response may be due to the

    change in parameters, such as source impedance, short circuit capacity level and

    change of fault currents and fault current directions at various locations.

    Solar photovoltaic cells produce power at dc voltage. Similarly, fuel cells and

    batteries also produce dc output power. These are then converted into ac voltage

    through dc-ac converters. Also, other sources such as wind and microturbines use a

    converter stage for grid interconnection. All the converters try to protect themselves

    by limiting their output currents. This becomes more crucial during faults. In general,

    fault current is usually limited to a value that is twice the converter rated current [7,

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    27/179

    Chapter 1: Introduction

    1.2Aims and objectives of the thesisThe main objective of this thesis was to design and develop efficient protection

    strategies to achieve the fault detection, faulted segment isolation, system restoration

    and reclosing for both grid connected and islanded operations of a microgrid or a

    distribution network which mainly consists of current limited DGs. To achieve this

    goal, the aims of the research project were identified as:

    analysing the protection issues related to a microgrid and a distribution networkin the presence of DGs

    determining the applicability of the existing protection strategies determining the new protection strategies that are required to achieve

    appropriate fault detection and protection of a network

    addressing the protection issues associated with system restoration, arcextinction and reclosing in the presence of converter interfaced DGs in a

    network

    While the main objective of the thesis was to propose a generic protection

    solution for DG connected distribution networks, the focus was limited to converter

    interfaced DGs. Moreover, the protection of DG connected distribution networks

    without communication was considered for a simple and cost effective solution.

    Ch 1 I d i

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    28/179

    Chapter 1: Introduction

    minimize the protection issues in implementation with the use of the proposed

    strategies.

    1.4The original contributions of the researchThe main objective of this research was to propose protection strategies to

    incorporate DGs into a micro grid or a distribution network by overcoming the

    identified protection issues. The main contributions of this research can be listed as

    follows.

    1.4.1A novel relay characteristic for DG connected networksAn inverse time admittance (ITA) relay characteristic is proposed to overcome

    the deficiencies of the existing overcurrent relays. The ITA relay has the capability

    of detecting faults under different fault current levels which is the usual scenario that

    can be seen in a distribution network when several DGs are present. These relays can

    isolate the faulted segments and allow the unfaulted segments to operate either in

    grid connected or islanded mode. Moreover, the relay is capable of providing

    adequate protection for the islanded system which has several converter interfaced

    DGs.

    1.4.2A new DG control strategy for fast system restoration

    Ch t 1 I t d ti

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    29/179

    Chapter 1: Introduction

    extinction of arc is achieved by reducing the output current of DGs. Furthermore, an

    effective method is proposed to coordinate the operations of reclosers and converter

    interfaced DGs in a network. The fold back control provides maximum benefits to

    customers by reducing outages since the DGs are not disconnected immediately

    when there is a fault in the system.

    The proposed ITA relay and fold back current control strategy for a converter

    interfaced DG provide a complete protection solution for a DG connected network.

    The relays detect and isolate faults effectively while the fold back current control

    helps in arc extinction, system restoration and recloser coordination with DGs.

    1.5Structure of the thesisThis thesis is organised in seven chapters and three appendices. The research

    aims and objectives are outlined in Chapter 1. The need and justification for the

    research in this field are identified in Chapter 2. In this chapter, a literature review is

    carried out to identify the protection issues related to DG connected distribution

    networks and microgrids. Moreover, the deficiencies of the existing protection

    schemes are identified and some of the already proposed solutions to overcome these

    protection issues are analysed.

    As a result of identification of the protection issues and the deficiencies of the

    Chapter 1: Introduction

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    30/179

    Chapter 1: Introduction

    features are then compared with the ITA relays. Different case studies are carried out

    to show the efficacy of the ITA relays. Moreover, simulation studies related to the

    ITA relays are also presented in this chapter. Applications of ITA relays for both

    radial and mesh networks are examined and their limitations are identified.

    A fold back current control characteristic for a converter interfaced DG is

    proposed in Chapter 5. The protection issues related to the system restoration, arc

    extinction and reclosing are also addressed in this chapter. Different case studies of

    both permanent and temporary faults were carried out and are presented here to show

    the efficacy of proposed fold back converter control.

    Chapter 6 presents the hardware results obtained through the experimental

    laboratory tests. The ITA relay characteristic is modelled using LabVIEW software

    and the relay performance is investigated for different fault locations and different

    system configurations.

    Conclusions drawn from this research and recommendations for future research

    are given in Chapter 7. The list of references and a list of publications arsing from

    the thesis are provided at the end of the last chapter. In Appendix-A, different types

    of relay elements are discussed, while Appendix-B give a detailed description of the

    converter structure and control used in simulation studies. The LabVIEW program

    used in ITA relay implementation is presented in Appendix-C.

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    31/179

    Chapter 2: Literature review2.1Introduction

    The cost of transmission and distribution is rising with the rapid increases in

    the load demand. However, the costs of distribution generation technologies are

    falling [2]. So from a costing point of view, it is becoming more worthwhile to

    increase the generation at the distribution level by connecting a distributed generator

    (DG) to meet the load requirement without expanding the transmission and

    distribution infrastructure. In addition, there are several advantages of having DGs;

    short construction time, lower capital costs, reduction in gaseous emissions, reduced

    transmission power loss since generation is now closer to the load, improving voltage

    profile, enhancing reliability and diversification of energy sources [9-11].

    A microgrid can be considered as a small grid based on DGs. Generally, the

    microgrid consists of renewable energy based DGs and combined heat and power

    plants. It can operate either grid connected or islanded mode. Most of the DGs are

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    32/179

    Chapter 2: Literature review

    the smallest possible set of faulted lines of the microgrid must be isolated for a fault

    within this grid.

    However, protection of a distribution network becomes more complicated and

    challenging once several DGs are connected (as in a microgrid). In this chapter, the

    complications in system protection arising due to the connection of DGs to a

    distribution network are discussed. Also some of the already proposed solutions are

    mentioned.

    2.2Protection issues and solutionsThe present practice is to disconnect the DGs from the network using an

    islanding detection method when there is a fault in the system [13, 14]. This is as per

    the IEEE recommended practice, standard 1547 [15]. This may work satisfactorily

    when the penetration of DGs in a distribution system is low. However, as the

    penetration levels increase or in the case of micro or mini-grid, the DGs will be

    expected to supply power even when the supply from the utility is lost and the DGs

    form a small island. This will prevent unnecessary customer power interruption.

    Thus, the benefits of DG installations can be maximized allowing the DGs to operate

    in both grid connected and islanded modes of operation, especially when the DG

    penetration level is high.

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    33/179

    p w

    2.2.1Islanding operation and anti-islanding protectionIslanding occurs when the main supply is disconnected and at least one

    generator in the disconnected system continues to operate. If a DG is allowed to

    operate in this islanding condition, it will bring benefits to customers by reducing

    outages [16]. However, if DGs are not designed to operate in islanded operation, this

    can cause a number of safety issues [17]. The point where the islanded system is

    created after the disconnection of the utility for a fault cannot be identified exactly.

    Therefore at the moment of islanding, the generation and load capacity may not be

    equal.

    When synchronous generators are present in the islanded region and if loads

    are larger than the generation then the generators tend to slow down which can lead

    to under frequency tripping of generators. In this case, a load shedding scheme

    should be implemented to maintain the stability in the islanded system. On the other

    hand if load capacity is less than the generation, generators could experience over

    frequency tripping and require a fast governor controller to respond and balance the

    power [18]. Thus there is a need to identify the islanding condition in an expanded

    islanded system which has the loads beyond the PCC. The type of prime mover and

    controller mode (i.e. droop control, constant power, etc) affect the response of the

    system at the event of the islanding. These responses have been described according

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    34/179

    p

    Power quality may not be guaranteed within the island and there could be abnormal

    conditions in voltage and frequency [19, 20]. In the islanded mode, short circuit

    levels may drop significantly upon disconnection from the utility [1, 4, 19]. These

    factors are the reason why anti-islanding protection is traditionally applied to achieve

    the safety of personnel and equipment of the distribution system. Under and over

    voltage relays, under and over frequency relays, vector shift and relays for detecting

    rate of change of frequency (ROCOF) can be used as devices to detect islanding [10,

    19, 21]. The common practice is to disconnect the DGs before the first reclosing

    occurs after a fault in the system. Therefore anti-islanding protection devices should

    be appropriately coordinated with other protective devices such as reclosers in the

    system. From the reliability point of view, applying the anti-islanding protection to a

    microgrid is disadvantageous.

    An anti-islanding protection relay should detect the islanding condition within

    the required time (typically 200 to 400 ms) and should trip all the generators. On the

    other hand, it should not trip for small frequency variations in the system. A micro-

    processor based line tracking system is suggested for detecting islanding condition of

    a hydro power distributed generator (HPDG) using the changes of voltage,

    frequency, active power and reactive power [10]. This method can be used to detect

    the islanding condition of HPDG quickly and to isolate it from the main grid.

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    35/179

    detection. However, these two relays are operated based on the system frequency.

    Reference [21] has proposed a graphical method based on application region of the

    frequency relay to determine the islanding requirements without disturbing the

    frequency tripping requirements. Further this paper outlines how to coordinate the

    operation of the islanding detection relay and standard frequency tripping relay.

    Reference [20] also provides a mathematical development to determine the

    application region of a frequency relay which satisfies both the islanding detection

    and frequency tripping requirements. It has been shown that the frequency relay can

    be replaced by an islanding detection vector shift relay if the proper settings are

    selected. Similarly, a method is suggested to find out the application region of a

    voltage relay to satisfy both the anti-islanding and voltage variation protection in

    [22]. After disconnecting the main utility, the loading effect on DG is suddenly

    changed. As a result, balance condition of loads and harmonic currents will change.

    Therefore Total Harmonic Distortion (THD) of current and voltage unbalance at the

    DG terminal have been introduced as two new monitoring parameters to detect the

    islanding condition with voltage magnitude in [23]. Test results have shown that this

    method can be used efficiently for improved performance.

    The DGs are expected to supply either an increase of load at grid connected

    operation or emergency loads at the islanding operation. Thus the islanding operation

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    36/179

    from the faulted feeder after the fault occurs and a micro-processor based line

    protection relay is used to implement the scheme. However this scheme may increase

    the fault clearing time which can affect the dynamic condition of the system. Voltage

    and frequency should be maintained in the desired range, in the presence of

    disturbances in the islanding system. Control strategies should be implemented

    considering over-generated and under-generated islanding conditions [10].

    It has been mentioned that the only way to maintain the existing coordination

    system in the presence of arbitrary DG penetration level is to disconnect all DGs

    instantly in the case of a fault [2]. It would result in the DG disconnection for a

    temporary fault as well. Therefore it is clear that new protection strategies are

    required to investigate with the DG penetration to the utility. In addition, if the DG is

    not disconnected from the system at the event of a fault, the fault arc would not

    extinguish during an automatic recloser open time, since the source feeding the fault

    still remains. Thus a compromise solution between islanding operation and anti-

    islanding protection needs to evolve.

    2.2.2Coordination between protective devicesThe coordination of protective devices based on current is relatively easy when

    the distribution network is radial. However, with the connection of microgrids or

    DGs to the utility the radial nature no longer exists and it permits the power flow to

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    37/179

    implemented fast enough to prevent personal hazards and equipment damage [25].

    Generally, the protection of the distribution network is done using the current

    measurement based on the coordination of fuses, overcurrent relays, reclosers and

    sectionalisers [26]. It should consist of a primary and backup protection system

    which has proper time grading between each devices. As an example, tripping time

    increases towards the main utility source from the fault location and operation device

    sequences for a fault in a DG may be the first low voltage breaker, then the fuse,

    after that the line recloser, finally if fault still exits it should be cleared by the

    substation circuit breaker.

    The coordination based on the current is relatively easy in the unidirectional

    power flow networks, because the fault current reduces along the feeder [26].

    However, with the growth of distributed generators, the system permits the power

    flow to be bi-directional rather than uni-directional [5, 27]. This may create a number

    of feeder protection issues. It causes relays to under-reach or over-reach [28]. The

    DG location in the distribution network influences the relay reach to reduce or

    increase. It has been shown that the reach of an overcurrent relay will reduce in the

    presence of a DG [29]. Among the protective devices currently used, reclosers and

    fuses usually do not have the directional sensing feature but a relay can easily be

    made to have that feature [2]. In addition to that, the DG can contribute by suppling

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    38/179

    An adaptive protection method is proposed for the distribution system with

    high DG penetration level in [2]. In this approach, several zones are formed with a

    reasonable balance of loads and DGs. Each breaker and recloser should have

    communication capability and each individual zone breaker should be available to

    check the synchronization function. At the beginning, load flow and short circuit

    analysis for all types of faults need to be carried out. After the changes of system

    configuration due to the loads or DGs , the load flow and short circuit analysis again

    have to be repeated. This will not be feasible when a larger number of plug and play

    DGs is connected /disconnected. Moreover, this adaptive method is complex as it is

    not easy to define zones with the fluctuation of loads and DG generation. However,

    protection is independent of DG size and location. The impact of DG capacity on

    relay operation and coordination in a radial distribution system has been studied in

    [31]. It has been shown that for a downstream fault from the connection point of a

    DG, the relay selectivity remains unchanged and sensitivity improves due to the

    increase in fault current. But there is a maximum capacity for the DG to keep the

    relay coordination. Further a method was suggested to find out the maximum value

    for the DG capacity. On the other hand for an upstream fault from the DG connection

    point, it has been shown that the misoperation can occur for a low capacity DG.

    Problems of protective devices coordination in a distribution network have

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    39/179

    around 80% of the total faults in the distribution system, are temporary. Therefore

    protective devices coordination should be done in an appropriate way when recloser

    and fuse are present in a distribution system. Moreover the recloser should operate

    fast enough to give a chance to clear the fault before the fuse [2, 5]. To achieve this

    fast characteristic, the recloser should lie below the MM curve of the fuse. The fuse

    should only operate for a permanent fault. This operation is obtained if the slow

    characteristic of recloser lies above the TC curve of the fuse within the considered

    minimum and maximum fault currents region. If DG is connected upstream to a

    recloser, the fault current seen by the recloser and further downstream fuses will

    increase. As a result the required margin between the fast characteristic of recloser

    and minimum melting curve will tend to reduce. Thus there is a probability of losing

    the coordination with any fuse further down to the recloser [32]. On the other hand, if

    a DG is connected between a recloser and a fuse, the fault current seen by a fuse

    increases and this may cause it to lose coordination. Before the DG connection, the

    recloser and fuse see the same fault current. However, after the connection, the fuse

    will see more current than the recloser and it responds before the recloser in the event

    of a fault downstream to the fuse location. The effect on coordination increases with

    DG capacity. Studies in [33] have shown that traditional reclosers are unable to keep

    the coordination with fuses in the presence of high DG penetration. Further this

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    40/179

    protection and in transmission as backup protection [34]. There are several types of

    overcurrent relays available to select from depending on the application.

    Instantaneous overcurrent relays are mostly used to protect sub-transmission lines

    while definite time relays are used in ungrounded or high impedance grounded

    systems. Moreover inverse time relays can easily coordinate with other protective

    devices and they are usually employed to protect distribution networks. A software

    model of a inverse time overcurrent relay has been developed to simulate in PSCAD

    [34].

    High backup time for the minimum fault currents is a disadvantage of

    overcurrent relays. A method which proposes to find the time element function for an

    overcurrent relay to reduce the back-up time to a constant value independent of the

    fault current magnitude rather than in the conventional overcurrent relay is given in

    [35]. References [36] and [37] present the IEEE standard analytical equation for the

    different types of overcurrent relays (i.e. moderately inverse, very inverse, and

    extremely inverse) and operating and reset characteristics that can be taken for

    coordination purposes. Relays employed in the radial networks have both inverse

    time and instantaneous elements to achieve a quick response for the severe faults as

    well as the coordination among relays [26].

    Also in the case of the islanded microgrid, the ratio between the source

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    41/179

    elements to achieve high speed fault clearing [38]. Reference [39] shows a method

    to calculate directional overcurrent relays setting for both grid connected and

    microgrid which consists of synchronous generator based DGs. In this method, the

    Particle Swarm Optimization algorithm is used in the relay coordination problem to

    obtain the optimal settings for the directional overcurrent relays while maintaining

    the minimum operating time and coordination among relays. It has been shown that

    it is not possible to calculate a setting time for the relays in both the grid connected

    and islanded modes of operation. Hence a central control protection unit is required

    to change the setting according to the system configuration. However fault current

    seen by each device may change according to the location of microgrid connected to

    the utility and fault location. Hence attention to coordinate protective devices is

    essential.

    There are numerous papers which address the coordination issues with the

    presence of DGs in the distribution network. However, so far there is little attention

    to the coordination analysis of the current limited converter interfaced DGs.

    2.2.3Protection in the presence of current limited convertersThe fault current may change due to the presence of DGs in the network [2, 16,

    19, 39, 40]. Its impact depends on the size, type, number of the DG, location of the

    DG [5 31] Basically three types of DGs exist with different properties; synchronous

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    42/179

    are studied in [40] considering the sensitive equipment response. Fault current

    behaviour and fault detection in a distribution network for different types of faults in

    the presence of an induction generator has been studied in [4]. The system which is

    not designed with DGs may not work properly with existing protective devices once

    several DGs are connected to the system [6]. In the presence of a generator within

    the network, the fault current detected by a protective device located at the beginning

    of the feeder can be reduced due to the rise of voltage drop over the feeder section

    between the generator and the fault [4]. Therefore the faults previously cleared in a

    very short time may now require a significant time to clear.

    Most of the distribution resources in the microgrid are connected through the

    power electronic converters [12]. For example, the dc power is generated by using

    the sources such as fuel cell, micro turbine, or a photovoltaic and converters are

    utilised to alter the dc power into ac power. These converter interface generators

    supplies the currents not much greater than the nominal load currents [26]. Basically

    the controller of the converter mainly consists of two control schemes named voltage

    control and current control and it regulates the output active and reactive power [42].

    In the voltage control mode, the converter produces a three phase balanced ac

    voltage at the terminal. The current control scheme, which is explained in [42], uses

    two control loops, an inner loop for the current output and outer loop for the power

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    43/179

    protecting a converter dominated microgrid is a challenging technical issue under the

    current limited environment [25]. Moreover there is a requirement to find other

    protection techniques to solve this problem [7, 26, 27]. One possible approach which

    facilitates using the existing overcurrent protection is up-rating of converters to

    supply the required fault current. However this will be a costly process. Another

    approach that is proposed to overcome this problem is to use a flywheel energy

    storage system to obtain the necessary fault current in the event of a fault [44]. The

    flywheel supplies the required fault current to operate the overcurrent protective

    devices in the islanding operation.

    A stand-alone three phase four leg voltage source converter model has been

    studied to observe the fault behaviour of an islanded microgrid for different types of

    faults in [7]. During a fault, the converter works as a constant current source

    supplying the positive sequence current to the system. There are no active sources in

    the negative or zero sequence networks. So it has been shown that the microgrid is

    equivalent to a current source with parallel impedance which depends on the fault

    type. In this converter topology, large voltages can be seen in healthy phases for

    unbalanced faults. In [25], fault behaviour in a converter supplied microgrid has been

    presented considering different types of converter topologies and microgrid earthing

    systems. The paper concludes that the fault response strongly depends on the

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    44/179

    proposes an adaptive overcurrent scheme which selects the lower current threshold to

    operate the overcurrent device based on the value of voltage detection. In reference

    [45], abc-dq transformation of the voltage waveforms is used to identify if the short

    circuit condition is inside or outside a set zone in a microgrid. Voltage disturbance at

    each relay location is calculated by comparing the reference value with the obtained

    dc values in the d-q synchronous rotating frame. The tripping decision is made by

    selecting the location which has the highest mean average disturbance value with the

    help of a communication link among relays.

    A differential relay based protection scheme is proposed to protect a microgrid

    in either grid connected or islanded mode in [16]. In this, a central control unit is

    used to make decisions on control and protection devices. Line parameters of the two

    ends of a protected line have to be monitored by means of a wire connection if the

    line is short or by a pilot wire communication if the line is long. The need for

    communication channel is a disadvantage of the differential protection scheme.

    Moreover, the response of DGs places between two relays will affect their

    performance. Another approach for the protection of microgrid with converters in

    both islanded and grid connected operation is presented in [8]. A static switch has

    been designed to open the microgrid for all types of faults and faults should be

    cleared using techniques which do not rely on high fault currents within the

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    45/179

    minimum pickup current of the relay is update depending on the fault type and

    location. Further, the response of an converter interfaced fuel cell under a fault

    conditions has been investigated and it has been shown that the fault will cause the

    voltage to drop below to a value such that the undervoltage relay would operate to

    trip the DG if the fault occurs near the DG. Therefore undervoltage relay can be used

    under a fault condition to determine the status of the DG. Furthermore, IEEE

    standard 929-2000 states that converters will sense a short circuit by voltage drop

    rather than sensing the short circuit current. Another option is to design the

    protective devices to operate for small fault currents. However, this may cause

    nuisance tripping [16, 19, 46]. Thus there is a need to assure that for both the

    microgrid itself and for the grid connected modes, the protection system is operating

    in an adequate fast, selective and reliable way to clear the faults [39].

    2.2.4Reclosing, re-synchronization and arc faultsMost of the faults (around 90%) in the power system are temporary arc faults

    (such as insulator failures, conductors clashing due to strong wind, animal contacts,

    lightning strikes, etc). These faults can be successfully cleared by de-energizing the

    line long enough such that the arc self extinguishes. Usually reclosers which open

    and close a few times successively are used to clear such faults without any large

    scale power interruption [47] Maximum dead time of single phase reclosing in

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    46/179

    based on artificial neural network algorithms to solve this problem by analysing the

    voltage of the open phase conductor during the recloser dead time interval [47].

    Usually three phase reclosers are used in distribution networks. In a DG or

    microgrid connected distribution network, the reclosing should be done with proper

    synchronization since this will join two live systems. The maximum time available

    for automatic reclosing without losing synchronism should be considered. During the

    auto recloser open time, if the island and main grid undergo a phase mismatch, then

    it may lead to damage to the equipment and DGs in the microgrid [5]. However, if

    the DG is connected using a converter, the risk of damage to the DG is low as it has

    its own protection [49]. Dead line voltage relay and sync-check relay can be used to

    prevent out of phase reclosing [19]. In general, a DG is disconnected before the first

    reclosing occurs in the system. This requires that any anti-islanding protection should

    operate very quickly. As a result, the recloser should coordinate with the anti-

    islanding protection, which is a challenging task [19]. A communication link can be

    established between the line recloser and the DG to transfer trip signal to disconnect

    the DG quickly [50]. An automatic synchronizing or synchronism check relay should

    be used at the PCC breaker when restoring the system after disconnection [18]. Re-

    synchronizing can be done manually or automatically using synchronism check relay

    with a synchronous generator based DG. However for a converter interfaced DG,

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    47/179

    rate after successful arc extinction at the current zero crossing [51]. Also the arc

    extinction time is proportional to the arc time constant [52]. On the other hand, the

    fault current magnitude of an arc fault is limited by the arc resistance. Sometimes it

    results in difficulties of detecting the fault [53]. Moreover, the arc voltage at the fault

    point is a source of errors in the fault locating process [54]. Therefore protection of

    distribution network and restoration under arc fault is a challenging task.

    2.2.5Communication based protectionThe distribution system protection will be complicated when the DGs are

    spread throughout the network. As a result new protection issues will arise for the

    traditional distribution networks. To address some of the issues, a protection based

    on a communication medium has been developed. Communication media including

    power line carrier (PLC), microwave and optical fibre have long been used for the

    transmission line applications. However, in nature, the distribution lines are different

    from transmission lines. These lines are shorter and they have numerous tapped

    loads. Therefore a particular communication method for a distribution system

    protection should be fast and reliable. Basically three types of communication

    networks can be identified as shown in the Fig. 2.1 [55]. In centralised networks, all

    nodes are connected to a central point, which is the acting agent for all

    communications A network distributed across many nodes rather than centralized

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    48/179

    Fig. 2.1 Different types of communication networks (Adapted from [55])

    The installation of a larger number of DGs can cause the loss of protection

    selectivity. Communication media may be the internet, PLC, wireless

    communication, etc. In [56], PLC based methods are proposed for the coordination

    of voltage control, islanding detection for a DG and controlling the interface devices

    at the PCC. The Islanding detection method is introduced to minimize the problems

    of traditional methods based on frequency and voltage measurements. High

    attenuation levels can be expected in distribution lines when their structure is

    complex and lines are long. To avoid such problems, repeaters need to be installed in

    this implementation. Application considerations of internet as the real time

    communication medium for providing the loss of mains protection of a DG has been

    studied in [55].

    The distribution system becomes a multi-source when one after another DG

    gets connected at different locations. This change in system configuration will cause

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    49/179

    agent approach based on communication is proposed in [17] to provide protection of

    the power system and coordination between the protective devices in the presence of

    DGs. A new method is proposed in [13] based on analysing the sign of wavelet

    coefficients of the fault current transient to locate and isolate a faulted segment. In

    this, relay agents are proposed to implant the proposed protection scheme. A fault

    location and fault isolation technique of a DG connected distribution network using

    neural networks is presented in [59]. In this, the system has different zones and the

    relay at substation communicates with zone breakers to take appropriate actions.

    With the use of communication, relay coordination has the ability to rapidly

    select the faulted region. However, installation of extensive communication will

    require time. Once the power system is smart grid ready, various smart relays can be

    installed. Till that time, protection without any or low levels of communication will

    be the most cost effective solution.

    2.3SummaryIn this chapter, a brief summary is presented based on the review of the

    previous published research work on the protection issues which arise after the

    connections of DGs and microgrids to distribution networks. There are several

    benefits available for both the network operator and customer by utilising DGs or

    Chapter 2: Literature review

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    50/179

    The proposed protection scheme should isolate the faulted segment as quickly

    as possible from the network. The DGs can then supply the power to unfaulted

    segments in the network if they have been designed to operate in islanded mode. To

    achieve that solution, several protection solutions have been proposed based on

    communication for DG connected networks. However, most of them need reliable

    communication medium for fast operation.

    Most of the time, current sensing protective devices have been used to detect

    the faults in the network. However, with the high penetration level of converter based

    DGs, protection of the system has been identified as a key challenging issue.

    Although different solutions have been proposed to solve this problem, further

    studies are still required to identify and improve the efficient fault detection methods.

    In the near future, when more DGs come into operation, protection will be a

    challenging task due to the network complexity.

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    51/179

    Chapter 3: Protective relay for DG connectednetworks

    3.1IntroductionIn a high penetrative DG network, a small possible portion should be isolated

    during a fault allowing unfaulted segments to operate in either grid connected or

    islanded mode to increase the system reliability by maximizing the DG benefits. To

    achieve the faulted segment isolation, both upstream and downstream protective

    devices should detect and isolate the fault. However, with the connection of DGs to a

    distribution network or within a microgrid, fault current level can vary depending on

    the DG connectivity, DG type and DG location. It results in difficulty of coordinating

    existing overcurrent protective devices since network configuration changes.

    Moreover, settings of these overcurrent relays to incorporate DGs are not possible if

    DG power output changes with time or their connectivity is not consistent.

    Furthermore, protection will be a challenging task when using converter

    Chapter 3: Protective relay for DG connected networks

    l I Ti Ad itt (ITA) t ti l i d b d th

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    52/179

    novel Inverse Time Admittance (ITA) protective relay is proposed based on the

    measured admittance of the protected line to avoid deficiencies of existing protection

    schemes. The fundamentals of ITA relays are explained in this chapter.

    3.2ITA relay characteristicsA radial distribution feeder as shown in Fig. 3.1 is considered to explain the

    ITA relay characteristics. It is assumed that the relay is located at nodeRand node K

    is an arbitrary point on the feeder. The total admittance of the protected line segment

    is denoted by Yt while the measured admittance between the nodes R and K is

    denoted by Ym. Then the normalised admittance (Yr) can be defined in terms of Ytand

    Ymas

    t

    mr

    Y

    YY = (3.1)

    Fig. 3.1 A radial distribution feeder

    The variation of normalised admittance along a radial feeder is shown in Fig.

    3.2 by assuming the feeder has a length of 3000m while the total feeder impedance is

    Chapter 3: Protective relay for DG connected networks

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    53/179

    Fig. 3.2 The variation of normalised admittance

    The change of normalised admittance along the feeder is used to obtain an

    inverse time tripping characteristic for the relay. The general form for the inverse

    time characteristic of the relay can be expressed as

    k

    Y

    At

    r

    p +

    =

    1

    (3.2)

    whereA, and kare constants, while the tripping time is denoted by tp. The values

    for these constants can be selected based on the relay location in a feeder and the

    protection requirements. The shape of the proposed inverse time tripping

    characteristic can be changed by varying the constants to obtain the required fault

    clearing time. When a network consists of different types of protective devices, these

    Chapter 3: Protective relay for DG connected networks

    tripping time for a fault near to the relay On the other hand higher fault clearing

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    54/179

    tripping time for a fault near to the relay. On the other hand, higher fault clearing

    time can be obtained when the fault is further away from the relay location.

    Fig. 3.3 Relay tripping characteristic curve

    It is to be noted that the normalized admittance in (3.2) should be greater than

    1.0 for relay tripping. This implies that the measured admittance is greater than the

    total admittance as shown in (3.3). This constraint is used by the relay algorithm to

    detect a faulted condition in the network. Moreover, the relay algorithm checks this

    constraint continuously during the faulted condition until relay issues the trip

    command to avoid any unnecessary tripping due to the effect of transients. The

    tripping time is decided depending on the calculated value of measured admittance.

    Y

    Chapter 3: Protective relay for DG connected networks

    to generate a number of required zones of protection In each zone the relay has a

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    55/179

    to generate a number of required zones of protection. In each zone, the relay has a

    unique tripping characteristic. It checks whether the measured admittance is greater

    than the total admittance of that particular zone before starting the relay tripping time

    calculation. A large coverage and minimum tripping time can be achieved by

    increasing the number of zones. It also leads to a good coordination amongst the

    relays in a feeder. Any upstream relay always provides the back up protection for the

    immediate downstream relay in the feeder.

    The radial feeder shown in Fig. 3.4 is considered to explain the relay reach

    settings. The relays are located at BUS-1, BUS-2 and BUS-3. It is assumed that each

    relay has two zones of protection. Zone-1 of each relay is selected to cover the whole

    line segment between two adjacent relays, while Zone-2 is selected to cover twice

    the length of the first line segment. The reach setting is set based on the positive

    sequence admittance of the considered line segments. Zone-1 and Zone-2 tripping

    characteristics are the same for all the relays. For example, relay tripping

    characteristic curves for two adjacent relays R1and R2are illustrated in Fig. 3.5. The

    locations of relays R1and R2and the tripping time of these relays against the distance

    to the fault from the relay locations are shown in the figure. Each zone has different

    values for the constants in (3.2) resulting different relay tripping characteristic

    curves. It can be seen from Fig. 3.5, Zone-2 of R1will provide a backup for the relay

    Chapter 3: Protective relay for DG connected networks

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    56/179

    Fig. 3.5 Relay protection zones and relay coordination

    The proposed new relay does have the ability to isolate the faults occurring at

    either side of the relay in a radial feeder. This is because the absolute value is taken

    into consideration in admittance normalizing process. However, for the relay to

    operate for reverse faults there must be an infeed that is located downstream from the

    relay. If the distribution network consists of these relays located at equal distances,

    the same forward and reverse reach can be used to isolate forward and reverse faults.

    The value for the reach of a particular zone should be selected according to the

    requirement.

    However, the reach setting should be different for forward and reverse faults,

    when the relays are not placed equidistant from one another. In this case, each relay

    Chapter 3: Protective relay for DG connected networks

    relays are not equal. To accomplish forward and reverse reach in relays, the relay

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    57/179

    y q p y , y

    should sense the fault direction. Moreover, the relay has the capability to identify

    whether the fault is in the forward or reverse direction. Any method which will

    determine the fault direction can be used for this purpose.

    One possibility is to measure the relative difference of angle between the

    current and bus voltage. The fault current lags the bus voltage for a forward fault

    while for a reverse fault the fault current leads the bus voltage. In [60], relative phase

    angle between fault current and pre-fault voltage is used to determine the fault

    direction. Another possibility is to calculate the negative sequence impedance seen

    by the relay. Based on the calculated value, the relay identifies the fault direction to

    select the appropriate reach setting. This approach is only valid if the fault is

    unsymmetrical since negative sequence will not be present for symmetrical faults.

    The negative sequence impedance is always positive for the reverse faults and it is

    negative for the forward faults [61]. The positive sequence directional element

    proposed in [62] can be also used to identify the fault direction. After identifying the

    fault direction, the process of tripping time calculation can be implemented as shown

    in Fig. 3.6.

    Chapter 3: Protective relay for DG connected networks

    3.4Different ITA relay elements

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    58/179

    y

    The ITA relay has different types of protection elements to detect different

    faults. All elements are designed to operate based on measured admittance of the

    protected line. These elements are explained below.

    3.4.1Earth elementsThese elements will respond for the line to ground faults. The number of

    elements varies depending on whether protection has been configured as directional

    or non-directional. If protection is directional, then there are two independent earth

    elements per phase. The positive sequence measured admittance; YRK1 seen by this

    relay element is given by (3.4). The derivation of this formula is given in Appendix-

    A.

    Ra

    RK

    RK

    RaR

    RKV

    Y

    YI

    aI

    Y

    +

    =

    10

    1

    01

    (3.4)

    where IRa is the rms line fault current through the relay while IRa0 is the zero

    sequence fault current seen by relay and VRa is the faulted phase rms voltage. The

    line parameters are used to calculate the ratio of YRK1/ YRK0. The relay reach is set

    based on the positive sequence admittance of the protected line segment. This relay

    Chapter 3: Protective relay for DG connected networks

    example, for phase A, two phase elements are employed, if protection is non-

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    59/179

    directional, one for the faults between phase A and phase B and another for the faults

    between phase A and phase C. Measured admittance seen by a phase element for a

    line to line fault, between phase A and phase B, can be expressed as,

    RbRa

    RbRRK

    VV

    IaIY

    =1 (3.5)

    whereIRaandIRbare rms phase currents in faulted phases and VRaand VRbare faulted

    phase rms voltages. This measured admittance in (3.5) is used by relay logic to detect

    a line to line fault in the network.

    3.4.3Directional elementsThe directional elements can be used to identify whether the fault is in forward

    or reverse direction from the relay. This will help to implement separate reach

    settings for each direction especially when a relay protects non-equidistant zones.

    The user has been given the facility to select the preference as listed in Table 3.1.

    Table 3.1 Selection criterion of a directional element

    Setting Operation

    Directional Each element has two settings to cover both forward

    and reverse direction faults

    Non-directional Each element operates regardless of the fault direction

    Chapter 3: Protective relay for DG connected networks

    current transformer (CT) respectively. The relay output is linked to the tripping coil

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    60/179

    of the circuit breaker (CB). The relay continuously monitors the input parameters and

    executes the relay logic to identify a faulted condition in the network. The process of

    making the tripping decision is shown in the Fig. 3.8. Based on the fundamental

    voltage and current, the admittance is calculated, which is the measured admittance

    of the relay point at a given time. The measured admittance and values for the relay

    reach settings are the inputs to the relay logic. This logic consists of normalized

    admittance calculation, relay characteristic equations, relay tripping time

    calculations, identification of fault direction and defined relay constraints. The

    faulted condition is detected by using the constraint in (3.3). Once fault is detected,

    the calculated tripping time based on measured admittance is fed through an

    integrator to obtain the tripping signal for the CB. Also relay checks whether the

    fault detection signal exists until relay issues the tripping command to avoid any

    nuisance tripping.

    Fi 3 7 R l i di h

    Chapter 3: Protective relay for DG connected networks

    3.6Settings of ITA relays to detect resistive faults

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    61/179

    Higher fault resistance can affect the operation of ITA relays. Therefore a

    method of relay settings is described to achieve successful relay operation in the

    presence of fault resistance. The relay carefully checks the constraint in (3.3)

    continuously, which is the comparison between the measured admittance (Ym) and

    the total admittance (Yt) setting of a particular zone. The relay detects a fault in the

    network when Ymbecomes higher than Yt. For a fault within a particular zone, Ymis

    always greater than Yt, if fault resistance is zero. However, with the increase of .fault

    resistance, Ym can become less than Yt. Also the maximum fault resistance which

    allows the relay to operate depends on the fault location of the line. For example, the

    relay can operate for a higher resistive fault, if the fault is near the relay than when it

    is further away from the relay since a higher value of fault resistance can be

    compensated by each zone for near faults.

    Another protective zone is introduced to achieve the tripping operation of the

    relays under resistive faults. The maximum fault resistance which can be tolerated by

    the relay is decided based on the loads of the feeder. In this case, the relay operation

    can be obtained up to a pre-defined value of fault resistance. This method will not

    work for higher resistive faults, where fault currents are in same levels as load

    currents. The minimum equivalent impedance of loads (i.e. the maximum load

    Chapter 3: Protective relay for DG connected networks

    effect of cold load inrush can be considered. Therefore, it is proposed to select one

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    62/179

    third of minimum equivalent impedance of loads as the fault resistance setting.

    A relay, if it has two zones, has two tripping characteristic curves. In this case,

    total admittance, Ytshould be set separately for each zone depending on protection

    requirements. Instead of these two zone characteristics, another characteristic will be

    introduced to discriminate the high resistive faults as mentioned above. Hereinafter,

    this zone is denoted by Zone-3. In this case Yt consists of corresponding line

    impedance and the maximum fault resistance which is determined based on loading

    condition. A coordination time interval should be kept between adjacent two Zone-3s

    of relays to obtain the correct relay grading. Otherwise relay characteristic of Zone-3

    in each relay will not show a considerable time difference for the faults with low

    fault resistance. Also the tripping time is set to a little higher value than the settings

    in the normal zone operations, since there is no requirement to isolate the faults with

    lower fault currents faster than the faults with higher fault currents. The radial

    network shown in Fig. 3.4 is considered again to illustrate the relay settings for all

    the zones.

    3.6.1Zone-1 settingsZone-1 reach setting is similar for all the relays if they are located equidistant.

    Therefore Yt is set by assuming the Zone-1 will protect 120% of the first line Z12

    Chapter 3: Protective relay for DG connected networks

    3.6.2Zone-2 settings

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    63/179

    Ytis set by assuming Zone-2 will protect 200% of the first line. This setting is

    also similar for all the relays. The reach setting and tripping characteristic can be

    given by

    )2(

    1

    122_

    ZY Zonet

    = (3.8)

    15.01

    0037.01.0 +

    =

    r

    pY

    t (3.9)

    3.6.3Zone-3 settingsThis zone represents a broader coverage of the protected line including the

    compensation for fault resistance. The value of Yt can be set using the allowable

    maximum fault resistance. The allowable maximum fault resistance is denoted by Zf

    after calculating the maximum load and adjusting it using the safety margin. It

    should be noted that Zfis the maximum fault resistance that can be handled by the

    relay when fault occurs in the far end of the protected zone. It is not the fault

    resistance in a particular fault condition. In this case, Ytfor the Zone-3 can be set as,

    )(1

    123_

    fZonet

    ZZY

    += (3.10)

    Zone-1 and Zone-2 tripping characteristics are same for all the relays.

    Chapter 3: Protective relay for DG connected networks

    reverse faults. If the relay detects the fault as forward, then forward tripping

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    64/179

    characteristic, t_Zone3Fis activated. On the other hand, reverse tripping characteristics,

    t_Zone3Ris activated if fault is detected by the relay as reverse.

    The Zone-3 tripping characteristic of each relay can be modified by assigning

    different constant values. A minimum tripping time characteristic should be selected

    for the furthest downstream relay to discriminate the forward faults. It can be then

    increased according to the coordination time interval between two adjacent relays.

    This Zone-3 grading is similar to the TDS setting of an overcurrent relay in a radial

    feeder. On the other hand, the minimum tripping time characteristic for reverse fault

    is selected to the furthest upstream relay. The settings of Zone-3 for the relays R1, R2,

    and R3 in the radial feeder of Fig. 3.4 can be given as shown in (3.11)-(3.13)

    respectively. These settings can be changed according to the protection requirements.

    15.1

    1

    0037.0

    1.01_3 +

    =

    r

    RFZone

    Y

    t

    45.01

    0037.01.01_3

    +

    =

    r

    RRZoneY

    t

    (3.11)

    85.01

    0037.01.02_3

    +

    =

    r

    RFZoneY

    t

    75.01

    0037.01.02_3

    +

    =

    r

    RRZoneY

    t (3.12)

    5500037.0

    3 +=t

    Chapter 3: Protective relay for DG connected networks

    tripping characteristics of R2 and R3 are calculated using (3.12) and (3.13)

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    65/179

    respectively. The figure also shows the combined forward relay characteristics of

    Zone-1 and Zone-2. It can be seen that forward Zone-3 as well as reverse Zone-3

    characteristics of each relay have been graded appropriately to achieve the backup

    protection. For example, it is assumed that a fault between BUS-1 and BUS-2 in the

    system cannot be detected by the primary zones (i.e., Zone-1 and Zone-2) of R 1and

    R2. Then, in this case, R2detects the fault in reverse Zone-3 to isolate the fault from

    downstream side while R3provides the backup protection as shown in Fig. 3.9.

    Fig. 3.9 Relay tripping characteristics of different zones

    3.7Practical issues for admittance calculation

    Chapter 3: Protective relay for DG connected networks

    usually appear in current signal. However, the decaying dc magnitude and time

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    66/179

    constant cannot be calculated before a fault occurs since it depends on the system

    configuration (X/R ratio), fault location and the value of fault resistance.

    Fast Fourier Transform (FFT) or Discrete Fourier Transform (DFT) can be

    used to extract the fundamental component from a sampled waveform. FFT is a fast

    way of calculating the DFT. FFT can accurately calculate the fundamental in the

    presence of harmonics and signal noises. However, it is not immune to decaying dc

    component.

    DFT is widely used in digital protective relays. DFT can extract the

    fundamental in the presence of harmonics, however it is also not immune to decaying

    dc component [63]. Some previous studies propose some interesting techniques to

    calculate the fundamental component accurately in the presence of decaying dc

    component. A method is proposed in [63] to eliminate the effect of decaying dc

    component by calculating the time constant of the faulted current waveform. In this

    algorithm, the dc magnitude is then calculated based on the calculated time constant

    for a cycle and subtract the dc magnitude from samples to obtain the DFT without

    decaying dc component. A DFT based filter algorithm is presented in [64] for digital

    distance relays to extract the fundamental accurately. In [65], a method is described

    to remove the decaying dc component for an application of protective relays. It can

    Chapter 3: Protective relay for DG connected networks

    tripping time calculation. However, the speed of the calculation and burden on the

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    67/179

    processor should be carefully considered when selecting a particular algorithm to

    avoid the errors coming form decaying dc component on tripping time calculations.

    3.8SummaryIn this chapter, the basic features of the proposed ITA relay to protect a

    distribution network or a microgrid which has several DGs are discussed. The relay

    inverse time characteristic and relay reach setting have been explained. Furthermore,

    different relay elements and a method of relay setting to achieve fault detection under

    higher resistive faults have been explained. Finally, the challenges of implementing

    ITA relays and possible solutions to avoid them are identified.

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    68/179

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    69/179

    Chapter 4: Evaluation of ITA relayperformance

    4.1IntroductionFaults can be usually identified by sensing the current level in an electrical

    power system since high currents can be seen during the faults. Overcurrent (OC)

    relays, fuses and moulded case circuit breakers (MCCBs) are the common type of

    current sensing protective devices used in distribution networks. The OC relays can

    be classified as definite current or instantaneous, definite time and inverse time based

    on the operating characteristics. In this chapter, features of inverse time OC relays

    are briefly considered since they are commonly used in distribution networks. On the

    other hand, distance type relays are commonly used to protect the transmission

    networks where speed of operation and reliability are very important. Fundamentally,

    MHO type distance relay are considered in this chapter. These existing OC and

    distance relay protection schemes are compared with the proposed ITA relay to

    demonstrate the performance of the ITA relay. The grading and coordination of

    Chapter 4: Evaluation of ITA relay performance

    4.2Inverse time overcurrent relays

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    70/179

    Most of the existing distribution networks are radial and they are employed

    with OC protective devices because of their simplicity and low cost [4, 30].

    Coordination of such protective devices based on current is relatively easy in the

    radial networks. The IEEE Standard inverse time relay tripping characteristic is

    given by [37]

    TDSBM

    At

    pp

    +

    =

    1 (4.1)

    where the constants A, Band pare used to select the relay characteristic curve and

    time dial setting (i.e. TDS) is used for the coordination between several OC relays.M

    is the multiple of pickup current and it is defined by

    =

    p

    f

    I

    IM (4.2)

    whereIfis the fault current seen by the relay andIpis the relay set current (i.e. pickup

    current). Three inverse time OC relay characteristic equations are given in the IEEE

    report [37]. They are moderately inverse, very inverse and extremely inverse. Each

    relay curve has different constants values in (4.1).

    To illustrate the grading of inverse time OC relays, a four bus bar radial feeder

    Chapter 4: Evaluation of ITA relay performance

    4.2. The relay tripping time tp is shown with the fault location. Coordination time

    i t l f R R d R R d t d b t d t ti l L t TDS

  • 8/12/2019 Jalthotage Dewadasa Thesis.bak

    71/179

    intervals for R1-R2 and R2-R3are