jalthotage dewadasa thesis.bak
TRANSCRIPT
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
1/179
Protection of distributed generation
interfaced networks
Manjula Dewadasa
B.Sc (Hons) in Electrical Engineering
A Thesis submitted in partial fulfilment of the requirements for
the degree of
Doctor of Philosophy
F lt f B ilt E i t d E i i
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
2/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
3/179
Keywords
Distributed generation, Microgrids, Distributed generator protection, Converter
interfaced distributed generators, Protective relays, Inverse time admittance relay,
Relay coordination, Relay Grading, Islanded operation, Re-synchronisation,
Reclosing, Fold back current control, Fault detection, Fault isolation, Arc extinction,
System restoration.
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
4/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
5/179
Abstract
With the rapid increase in electrical energy demand, power generation in the
form of distributed generation is becoming more important. However, the
connections of distributed generators (DGs) to a distribution network or a microgrid
can create several protection issues. The protection of these networks using
protective devices based only on current is a challenging task due to the change in
fault current levels and fault current direction. The isolation of a faulted segment
from such networks will be difficult if converter interfaced DGs are connected as
these DGs limit their output currents during the fault. Furthermore, if DG sources are
intermittent, the current sensing protective relays are difficult to set since fault
current changes with time depending on the availability of DG sources. The system
restoration after a fault occurs is also a challenging protection issue in a converter
interfaced DG connected distribution network or a microgrid. Usually, all the DGs
will be disconnected immediately after a fault in the network. The safety of
personnel and equipment of the distribution network, reclosing with DGs and arc
extinction are the major reasons for these DG disconnections.
In this thesis, an inverse time admittance (ITA) relay is proposed to protect a
distribution network or a microgrid which has several converter interfaced DG
connections. The ITA relay is capable of detecting faults and isolating a faulted
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
6/179
to some of the existing protection schemes. The relay performance is evaluated in
different types of distribution networks: radial, the IEEE 34 node test feeder and a
mesh network. The results are validated through PSCAD simulations and MATLAB
calculations. Several experimental tests are carried out to validate the numerical
results in a laboratory test feeder by implementing the ITA relay in LabVIEW.
Furthermore, a novel control strategy based on fold back current control is
proposed for a converter interfaced DG to overcome the problems associated with
the system restoration. The control strategy enables the self extinction of arc if the
fault is a temporary arc fault. This also helps in self system restoration if DG
capacity is sufficient to supply the load. The coordination with reclosers without
disconnecting the DGs from the network is discussed. This results in increased
reliability in the network by reduction of customer outages.
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
7/179
Table of Contents
List of figures ix
List of tables xiii
List of appendices xv
List of symbols and abbreviations xvii
Chapter 1: Introduction ............................................. 1
1.1 Background .............................................................................................. 1
1.2 Aims and objectives of the thesis ............................................................. 3
1.3 Significance of research ........................................................................... 3
1.4 The original contributions of the research ............................................... 4
1.4.1 A novel relay characteristic for DG connected networks ................. 4
1.4.2 A new DG control strategy for fast system restoration ..................... 4
1.5 Structure of the thesis ............................................................................... 5
Chapter 2: Literature review ..................................... 7
2.1 Introduction .............................................................................................. 7
2.2 Protection issues and solutions ................................................................ 8
2.2.1 Islanding operation and anti-islanding protection ............................. 9
2.2.2 Coordination between protective devices ....................................... 12
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
8/179
Chapter 3: Protective relay for DG connected
networks ................................................. 27
3.1 Introduction ............................................................................................ 27
3.2 ITA relay characteristics ........................................................................ 28
3.3 ITA relay reach settings ......................................................................... 30
3.4 Different ITA relay elements ................................................................. 34
3.4.1 Earth elements ................................................................................. 34
3.4.2 Phase elements ................................................................................. 34
3.4.3 Directional elements ........................................................................ 35
3.5 Connection of ITA relays to a network .................................................. 35
3.6 Settings of ITA relays to detect resistive faults ..................................... 37
3.6.1 Zone-1 settings ................................................................................ 38
3.6.2 Zone-2 settings ................................................................................ 39
3.6.3 Zone-3 settings ................................................................................ 39
3.7 Practical issues for admittance calculation ............................................ 41
3.8 Summary ................................................................................................ 43
Chapter 4: Evaluation of ITA relay performance . 45
4.1 Introduction ............................................................................................ 45
4.2 Inverse time overcurrent relays .............................................................. 46
4.3 Distance relays ....................................................................................... 48
4.4 ITA relays ............................................................................................... 51
4.5 ITA relay performance ........................................................................... 54
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
9/179
Chapter 5: Fold back current control and system
restoration .............................................. 79
5.1 Introduction ............................................................................................ 79
5.2 Fold back current control characteristics ............................................... 80
5.2.1 Fold back during contingency ......................................................... 80
5.2.2 Restoration process .......................................................................... 835.2.3 Coordination with reclosers ............................................................ 86
5.2.4 DG protection .................................................................................. 87
5.3 Arc fault model selection for simulation ............................................... 88
5.3.1 Primary arc fault .............................................................................. 89
5.3.2 Secondary arc fault .......................................................................... 90
5.3.3 Arc extinction .................................................................................. 91
5.4 Simulation studies .................................................................................. 91
5.4.1 Results for permanent faults ............................................................ 93
5.4.2 Results for Arc Faults ...................................................................... 97
5.4.3 Auto reclosing ............................................................................... 100
5.5 Summary .............................................................................................. 104
Chapter 6: Experimental results ........................... 105
6.1 Introduction .......................................................................................... 105
6.2 Test feeder arrangement ....................................................................... 105
6.3 Relay performance evaluation ............................................................. 109
6.4 Relay response for different fault locations ......................................... 111
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
10/179
6.5.2 The effect of fundamental extraction ............................................ 124
6.6 Summary .............................................................................................. 130
Chapter 7: Conclusions and recommendations ... 131
7.1 Conclusions .......................................................................................... 131
7.2 Recommendations for future research ................................................. 134
7.2.1 Consideration of rotary type DGs for protection........................... 134
7.2.2 Fold back type current control for rotary type DGs ...................... 134
7.2.3 The effect of single phase converters ............................................ 134
References 135
Publications arising from the thesis 143
Appendix-A 145
Appendix-B 147Appendix-C 153
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
11/179
List of Figures
Fig. 2.1 Different types of communication networks (Adapted from [55]) .... 24
Fig. 3.1 A radial distribution feeder ................................................................. 28
Fig. 3.2 The variation of normalised admittance ............................................. 29
Fig. 3.3 Relay tripping characteristic curve ..................................................... 30
Fig. 3.4 A radial distribution feeder with relays .............................................. 31Fig. 3.5 Relay protection zones and relay coordination .................................. 32
Fig. 3.6 Relay settings based on different forward and reverse reach ............. 33
Fig. 3.7 Relay connection diagram to the system ............................................ 36
Fig. 3.8 Process of relay tripping decision making ......................................... 36
Fig. 3.9 Relay tripping characteristics of different zones ................................ 41
Fig. 4.1 A radial distribution feeder with relays .............................................. 47
Fig. 4.2 Inverse time overcurrent relay grading .............................................. 47
Fig. 4.3 MHO relay characteristic ................................................................... 50
Fig. 4.4 MHO relay zone settings and timing diagram ................................... 50
Fig. 4.5 ITA relay grading ............................................................................... 52
Fig. 4.6 Faulted line with a relay ..................................................................... 52
Fig. 4.7 ITA relay characteristic in R-X diagram ............................................ 54
Fig. 4.8 Radial distribution feeder with DGs ................................................... 55
Fig. 4.9 OC and ITA relay grading .................................................................. 57Fig. 4.10 OC and ITA relay response when DG1 is connected ....................... 58
Fig. 4.11 Distance and ITA relay response when DG1 is connected .............. 58
Fig. 4.12 OC and ITA relay time-current characteristic .................................. 59
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
12/179
Fig. 4.20 Fault current seen by each ITA relay along the feeder ..................... 65
Fig. 4.21 Random load and DG distribution profiles along the feeder............ 66Fig. 4.22 ITA relay response for random load and DG distribution profiles .. 66
Fig. 4.23 IEEE 34 node test feeder with ITA relays ........................................ 67
Fig. 4.24 ITA relay response for SLG fault at node 858 ................................. 69
Fig. 4.25 ITA relay response for SLG fault at node 842 ................................. 69
Fig. 4.26 ITA relay response for SLG fault at node 862 ................................. 70
Fig. 4.27 Mesh network under study ............................................................... 71
Fig. 4.28 Equivalent representation of the faulted network ............................. 74
Fig. 4.29 ITA relay response for different values of fault resistances and DG
currents ............................................................................................ 76
Fig. 5.1 Proposed fold back characteristics ..................................................... 82
Fig. 5.2 System restoration .............................................................................. 85
Fig. 5.3 Simulated radial feeder with DGs ...................................................... 92
Fig. 5.4 Calculated ITA relay response for a three phase fault ....................... 94
Fig. 5.5 DG1 response (a) output voltage (b) output current (c) real poweroutput ................................................................................................. 95
Fig. 5.6 DG1 response (a) output voltage (b) output current (c) real power
output ................................................................................................. 97
Fig. 5.7 System behaviour for an arc fault (a) arc voltage (b) arc current (c) arc
resistance (d) relay response ............................................................... 99
Fig. 5.8 DG1 behaviour for an arc fault (a) output voltage (b) output current 99
Fig. 5.9 DG1 behaviour when downstream relay fails (a) output voltage (b)
output current 100
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
13/179
Fig. 6.6 Calculated relay response in different zones for bolted faults ......... 111
Fig. 6.7 The variation of voltage and current for SLG faults at BUS-2 ........ 113Fig. 6.8 The variation of voltage and current for SLG faults at BUS-3 ........ 114
Fig. 6.9 The variation of voltage and current for SLG faults at BUS-4 ........ 116
Fig. 6.10 The variation of voltage and current for SLG faults at BUS-5 ...... 117
Fig. 6.11 Voltage and current for a fault at BUS-2 ....................................... 118
Fig. 6.12 Voltage and current for a fault at BUS-3 ....................................... 119
Fig. 6.13 Voltage and current for a fault at BUS-4 ....................................... 119
Fig. 6.14 Voltage and current for a fault at BUS-5 ....................................... 119
Fig. 6.15 Change of parameters during a resistive fault at BUS-2 ................ 122
Fig. 6.16 Test feeder with an infeed .............................................................. 123
Fig. 6.17 Change of parameters for a fault at BUS-2 with fault resistance and
infeed ............................................................................................. 124
Fig. 6.18 A SLG fault at synchronous generator connected feeder ............... 125
Fig. 6.19 Current and voltage during a SLG fault ......................................... 126
Fig. 6.20 Values of relay parameters during a SLG fault .............................. 127Fig. 6.21 Faulted current and voltage during a SLG fault ............................. 128
Fig. 6.22 Values of calculated relay parameters during a SLG fault ............. 129
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
14/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
15/179
List of Tables
Table 3.1 Selection criterion of a directional element ..................................... 35
Table 4.1 System parameters ........................................................................... 55
Table 4.2 OC relay settings ............................................................................. 56
Table 4.3 Zone characteristics of ITA relay .................................................... 56
Table 4.4 System parameters ........................................................................... 64
Table 4.5 ITA relay forward and reverse reach settings .................................. 68
Table 4.6 System parameters ........................................................................... 71
Table 4.7 Zone-3 grading of ITA relays .......................................................... 72
Table 4.8 Fault clearing time of ITA relays .................................................... 73
Table 5.1 Simulated system data ..................................................................... 92
Table 5.2 Arc model parameters ...................................................................... 97
Table 6.1 System parameters of the experimental setup ............................... 108
Table 6.2 Relay reach setting and tripping characteristic in each zone ......... 110
Table 6.3 ITA relay response for faults at BUS-2 ......................................... 113
Table 6.4 ITA relay response for faults at BUS-3 ......................................... 114
Table 6.5 ITA relay response for faults at BUS-4 ......................................... 115
Table 6.6 ITA relay response for faults at BUS-5 ......................................... 116
Table 6.7 ITA relay response for SLG faults with higher source impedance 118
Table 6.8 Relay parameters during a resistive fault ...................................... 121Table 6.9 Change of relay parameters due to fault resistance and infeed ..... 123
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
16/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
17/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
18/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
19/179
List of principle symbols and abbreviations
A, , k Relay tripping constants
CB Circuit breaker
CT Current transformer
DFT Discrete Fourier transform
DG Distributed generator
FFT Fast Fourier transform
IDG Distributed generator current
Ip Pickup current
IRa, IRb Current in faulted phases A and B
Ir Rated current of converter
ITA Inverse time admittance
lp Primary arc length
ls Secondary arc length
MI Multiple of pickup current
OC Overcurrent
PCC Point of common coupling
R1, R2, R3 Protective relays
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
20/179
VT Voltage transformer
Ym Measured admittance
Yr Normalised admittance
YRK1 Positive sequence measured admittance
Yt Total admittance
Zdg Source impedance of distributed generator
ZLG Apparent impedance
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
21/179
Statement of original authorship
The work contained in this thesis has not been previously submitted to meet
requirements for an award at this or any other higher education institution. To the
best of my knowledge and belief, this thesis contains no material previously
published or written by another person except where due reference is made.
Signature:.
Date:.
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
22/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
23/179
Acknowledgements
First and foremost, I would like to convey my sincerest and deepest thanks to
my supervisors, Prof. Gerard Ledwich and Prof. Arindam Ghosh, for their
incomparable guidance and endless encouragement throughout my doctoral research.
It has been a great privilege for me to work under this supervision.
I wish to express my thanks to the Faculty of Built Environment and
Engineering, Queensland University of Technology (QUT) for providing me with
financial support during my research candidature.
I would also like to thank staff in the research portfolio office in QUT for their
generous support and assistance throughout the candidature, and the staff in the
School of Engineering Systems for providing such a helpful environment. Further, I
am thankful to staff in the Power Engineering Group for their valuable advice.
I would like to extend my appreciation to all the technical staff who supported
me during the laboratory experiments. Without this support, experimental work
would not have been successful.
I would further like to thank to all of my friends for sharing valuables ideas, for
supporting me during the experimental work, and for making the research period an
enjoyable one. Also, I am grateful to my parents for encouraging me to pursue higher
studies, and I thank them and my relatives for their constant support.
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
24/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
25/179
Chapter 1: Introduction1.1Background
With the rapid increase in electrical energy demand, power utilities are seeking
for more power generation capacity. However, environmental and right-of-way
concerns make the addition of central generating stations and the erection of power
transmission lines more difficult. Thus, newer technologies based on renewable
energy are becoming more acceptable as alternative energy generators. This
renewable energy push is starting to spread power generation over distribution
networks in the form of distributed generation and will lead to a significant increase
in the penetration level of distributed generation in the near future. It is expected that
20% of power generation will be through renewable sources by the year 2020 [1].
However, by that time, the penetration level of DGs is expected to be higher in many
countries which are seeking accelerated deployment of renewable technologies. The
DGs based on renewable energy sources will help in reducing greenhouse gas
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
26/179
Chapter 1: Introduction
fully controllable load which at peak hours can even supply power back to the utility
grid. A microgrid can operate in either (utility) grid connected mode or islanded
mode and can seamlessly change between these modes. In an islanded mode, the
DGs connected to the microgrid supply its loads, where a provision for load shedding
exists if the load demand is higher than the total DG generation.
Most of the existing distribution systems are radial where power flows from
substation to the customers in a unidirectional manner. Overcurrent protection is
used for such systems because of its simplicity and low cost [1, 4]. However, once a
DG or a microgrid is connected within the main utility system, this pure radial nature
is lost [2, 5, 6] and the existing protection devices may not respond in the fashion for
which they were initially designed [4]. This change in response may be due to the
change in parameters, such as source impedance, short circuit capacity level and
change of fault currents and fault current directions at various locations.
Solar photovoltaic cells produce power at dc voltage. Similarly, fuel cells and
batteries also produce dc output power. These are then converted into ac voltage
through dc-ac converters. Also, other sources such as wind and microturbines use a
converter stage for grid interconnection. All the converters try to protect themselves
by limiting their output currents. This becomes more crucial during faults. In general,
fault current is usually limited to a value that is twice the converter rated current [7,
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
27/179
Chapter 1: Introduction
1.2Aims and objectives of the thesisThe main objective of this thesis was to design and develop efficient protection
strategies to achieve the fault detection, faulted segment isolation, system restoration
and reclosing for both grid connected and islanded operations of a microgrid or a
distribution network which mainly consists of current limited DGs. To achieve this
goal, the aims of the research project were identified as:
analysing the protection issues related to a microgrid and a distribution networkin the presence of DGs
determining the applicability of the existing protection strategies determining the new protection strategies that are required to achieve
appropriate fault detection and protection of a network
addressing the protection issues associated with system restoration, arcextinction and reclosing in the presence of converter interfaced DGs in a
network
While the main objective of the thesis was to propose a generic protection
solution for DG connected distribution networks, the focus was limited to converter
interfaced DGs. Moreover, the protection of DG connected distribution networks
without communication was considered for a simple and cost effective solution.
Ch 1 I d i
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
28/179
Chapter 1: Introduction
minimize the protection issues in implementation with the use of the proposed
strategies.
1.4The original contributions of the researchThe main objective of this research was to propose protection strategies to
incorporate DGs into a micro grid or a distribution network by overcoming the
identified protection issues. The main contributions of this research can be listed as
follows.
1.4.1A novel relay characteristic for DG connected networksAn inverse time admittance (ITA) relay characteristic is proposed to overcome
the deficiencies of the existing overcurrent relays. The ITA relay has the capability
of detecting faults under different fault current levels which is the usual scenario that
can be seen in a distribution network when several DGs are present. These relays can
isolate the faulted segments and allow the unfaulted segments to operate either in
grid connected or islanded mode. Moreover, the relay is capable of providing
adequate protection for the islanded system which has several converter interfaced
DGs.
1.4.2A new DG control strategy for fast system restoration
Ch t 1 I t d ti
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
29/179
Chapter 1: Introduction
extinction of arc is achieved by reducing the output current of DGs. Furthermore, an
effective method is proposed to coordinate the operations of reclosers and converter
interfaced DGs in a network. The fold back control provides maximum benefits to
customers by reducing outages since the DGs are not disconnected immediately
when there is a fault in the system.
The proposed ITA relay and fold back current control strategy for a converter
interfaced DG provide a complete protection solution for a DG connected network.
The relays detect and isolate faults effectively while the fold back current control
helps in arc extinction, system restoration and recloser coordination with DGs.
1.5Structure of the thesisThis thesis is organised in seven chapters and three appendices. The research
aims and objectives are outlined in Chapter 1. The need and justification for the
research in this field are identified in Chapter 2. In this chapter, a literature review is
carried out to identify the protection issues related to DG connected distribution
networks and microgrids. Moreover, the deficiencies of the existing protection
schemes are identified and some of the already proposed solutions to overcome these
protection issues are analysed.
As a result of identification of the protection issues and the deficiencies of the
Chapter 1: Introduction
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
30/179
Chapter 1: Introduction
features are then compared with the ITA relays. Different case studies are carried out
to show the efficacy of the ITA relays. Moreover, simulation studies related to the
ITA relays are also presented in this chapter. Applications of ITA relays for both
radial and mesh networks are examined and their limitations are identified.
A fold back current control characteristic for a converter interfaced DG is
proposed in Chapter 5. The protection issues related to the system restoration, arc
extinction and reclosing are also addressed in this chapter. Different case studies of
both permanent and temporary faults were carried out and are presented here to show
the efficacy of proposed fold back converter control.
Chapter 6 presents the hardware results obtained through the experimental
laboratory tests. The ITA relay characteristic is modelled using LabVIEW software
and the relay performance is investigated for different fault locations and different
system configurations.
Conclusions drawn from this research and recommendations for future research
are given in Chapter 7. The list of references and a list of publications arsing from
the thesis are provided at the end of the last chapter. In Appendix-A, different types
of relay elements are discussed, while Appendix-B give a detailed description of the
converter structure and control used in simulation studies. The LabVIEW program
used in ITA relay implementation is presented in Appendix-C.
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
31/179
Chapter 2: Literature review2.1Introduction
The cost of transmission and distribution is rising with the rapid increases in
the load demand. However, the costs of distribution generation technologies are
falling [2]. So from a costing point of view, it is becoming more worthwhile to
increase the generation at the distribution level by connecting a distributed generator
(DG) to meet the load requirement without expanding the transmission and
distribution infrastructure. In addition, there are several advantages of having DGs;
short construction time, lower capital costs, reduction in gaseous emissions, reduced
transmission power loss since generation is now closer to the load, improving voltage
profile, enhancing reliability and diversification of energy sources [9-11].
A microgrid can be considered as a small grid based on DGs. Generally, the
microgrid consists of renewable energy based DGs and combined heat and power
plants. It can operate either grid connected or islanded mode. Most of the DGs are
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
32/179
Chapter 2: Literature review
the smallest possible set of faulted lines of the microgrid must be isolated for a fault
within this grid.
However, protection of a distribution network becomes more complicated and
challenging once several DGs are connected (as in a microgrid). In this chapter, the
complications in system protection arising due to the connection of DGs to a
distribution network are discussed. Also some of the already proposed solutions are
mentioned.
2.2Protection issues and solutionsThe present practice is to disconnect the DGs from the network using an
islanding detection method when there is a fault in the system [13, 14]. This is as per
the IEEE recommended practice, standard 1547 [15]. This may work satisfactorily
when the penetration of DGs in a distribution system is low. However, as the
penetration levels increase or in the case of micro or mini-grid, the DGs will be
expected to supply power even when the supply from the utility is lost and the DGs
form a small island. This will prevent unnecessary customer power interruption.
Thus, the benefits of DG installations can be maximized allowing the DGs to operate
in both grid connected and islanded modes of operation, especially when the DG
penetration level is high.
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
33/179
p w
2.2.1Islanding operation and anti-islanding protectionIslanding occurs when the main supply is disconnected and at least one
generator in the disconnected system continues to operate. If a DG is allowed to
operate in this islanding condition, it will bring benefits to customers by reducing
outages [16]. However, if DGs are not designed to operate in islanded operation, this
can cause a number of safety issues [17]. The point where the islanded system is
created after the disconnection of the utility for a fault cannot be identified exactly.
Therefore at the moment of islanding, the generation and load capacity may not be
equal.
When synchronous generators are present in the islanded region and if loads
are larger than the generation then the generators tend to slow down which can lead
to under frequency tripping of generators. In this case, a load shedding scheme
should be implemented to maintain the stability in the islanded system. On the other
hand if load capacity is less than the generation, generators could experience over
frequency tripping and require a fast governor controller to respond and balance the
power [18]. Thus there is a need to identify the islanding condition in an expanded
islanded system which has the loads beyond the PCC. The type of prime mover and
controller mode (i.e. droop control, constant power, etc) affect the response of the
system at the event of the islanding. These responses have been described according
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
34/179
p
Power quality may not be guaranteed within the island and there could be abnormal
conditions in voltage and frequency [19, 20]. In the islanded mode, short circuit
levels may drop significantly upon disconnection from the utility [1, 4, 19]. These
factors are the reason why anti-islanding protection is traditionally applied to achieve
the safety of personnel and equipment of the distribution system. Under and over
voltage relays, under and over frequency relays, vector shift and relays for detecting
rate of change of frequency (ROCOF) can be used as devices to detect islanding [10,
19, 21]. The common practice is to disconnect the DGs before the first reclosing
occurs after a fault in the system. Therefore anti-islanding protection devices should
be appropriately coordinated with other protective devices such as reclosers in the
system. From the reliability point of view, applying the anti-islanding protection to a
microgrid is disadvantageous.
An anti-islanding protection relay should detect the islanding condition within
the required time (typically 200 to 400 ms) and should trip all the generators. On the
other hand, it should not trip for small frequency variations in the system. A micro-
processor based line tracking system is suggested for detecting islanding condition of
a hydro power distributed generator (HPDG) using the changes of voltage,
frequency, active power and reactive power [10]. This method can be used to detect
the islanding condition of HPDG quickly and to isolate it from the main grid.
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
35/179
detection. However, these two relays are operated based on the system frequency.
Reference [21] has proposed a graphical method based on application region of the
frequency relay to determine the islanding requirements without disturbing the
frequency tripping requirements. Further this paper outlines how to coordinate the
operation of the islanding detection relay and standard frequency tripping relay.
Reference [20] also provides a mathematical development to determine the
application region of a frequency relay which satisfies both the islanding detection
and frequency tripping requirements. It has been shown that the frequency relay can
be replaced by an islanding detection vector shift relay if the proper settings are
selected. Similarly, a method is suggested to find out the application region of a
voltage relay to satisfy both the anti-islanding and voltage variation protection in
[22]. After disconnecting the main utility, the loading effect on DG is suddenly
changed. As a result, balance condition of loads and harmonic currents will change.
Therefore Total Harmonic Distortion (THD) of current and voltage unbalance at the
DG terminal have been introduced as two new monitoring parameters to detect the
islanding condition with voltage magnitude in [23]. Test results have shown that this
method can be used efficiently for improved performance.
The DGs are expected to supply either an increase of load at grid connected
operation or emergency loads at the islanding operation. Thus the islanding operation
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
36/179
from the faulted feeder after the fault occurs and a micro-processor based line
protection relay is used to implement the scheme. However this scheme may increase
the fault clearing time which can affect the dynamic condition of the system. Voltage
and frequency should be maintained in the desired range, in the presence of
disturbances in the islanding system. Control strategies should be implemented
considering over-generated and under-generated islanding conditions [10].
It has been mentioned that the only way to maintain the existing coordination
system in the presence of arbitrary DG penetration level is to disconnect all DGs
instantly in the case of a fault [2]. It would result in the DG disconnection for a
temporary fault as well. Therefore it is clear that new protection strategies are
required to investigate with the DG penetration to the utility. In addition, if the DG is
not disconnected from the system at the event of a fault, the fault arc would not
extinguish during an automatic recloser open time, since the source feeding the fault
still remains. Thus a compromise solution between islanding operation and anti-
islanding protection needs to evolve.
2.2.2Coordination between protective devicesThe coordination of protective devices based on current is relatively easy when
the distribution network is radial. However, with the connection of microgrids or
DGs to the utility the radial nature no longer exists and it permits the power flow to
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
37/179
implemented fast enough to prevent personal hazards and equipment damage [25].
Generally, the protection of the distribution network is done using the current
measurement based on the coordination of fuses, overcurrent relays, reclosers and
sectionalisers [26]. It should consist of a primary and backup protection system
which has proper time grading between each devices. As an example, tripping time
increases towards the main utility source from the fault location and operation device
sequences for a fault in a DG may be the first low voltage breaker, then the fuse,
after that the line recloser, finally if fault still exits it should be cleared by the
substation circuit breaker.
The coordination based on the current is relatively easy in the unidirectional
power flow networks, because the fault current reduces along the feeder [26].
However, with the growth of distributed generators, the system permits the power
flow to be bi-directional rather than uni-directional [5, 27]. This may create a number
of feeder protection issues. It causes relays to under-reach or over-reach [28]. The
DG location in the distribution network influences the relay reach to reduce or
increase. It has been shown that the reach of an overcurrent relay will reduce in the
presence of a DG [29]. Among the protective devices currently used, reclosers and
fuses usually do not have the directional sensing feature but a relay can easily be
made to have that feature [2]. In addition to that, the DG can contribute by suppling
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
38/179
An adaptive protection method is proposed for the distribution system with
high DG penetration level in [2]. In this approach, several zones are formed with a
reasonable balance of loads and DGs. Each breaker and recloser should have
communication capability and each individual zone breaker should be available to
check the synchronization function. At the beginning, load flow and short circuit
analysis for all types of faults need to be carried out. After the changes of system
configuration due to the loads or DGs , the load flow and short circuit analysis again
have to be repeated. This will not be feasible when a larger number of plug and play
DGs is connected /disconnected. Moreover, this adaptive method is complex as it is
not easy to define zones with the fluctuation of loads and DG generation. However,
protection is independent of DG size and location. The impact of DG capacity on
relay operation and coordination in a radial distribution system has been studied in
[31]. It has been shown that for a downstream fault from the connection point of a
DG, the relay selectivity remains unchanged and sensitivity improves due to the
increase in fault current. But there is a maximum capacity for the DG to keep the
relay coordination. Further a method was suggested to find out the maximum value
for the DG capacity. On the other hand for an upstream fault from the DG connection
point, it has been shown that the misoperation can occur for a low capacity DG.
Problems of protective devices coordination in a distribution network have
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
39/179
around 80% of the total faults in the distribution system, are temporary. Therefore
protective devices coordination should be done in an appropriate way when recloser
and fuse are present in a distribution system. Moreover the recloser should operate
fast enough to give a chance to clear the fault before the fuse [2, 5]. To achieve this
fast characteristic, the recloser should lie below the MM curve of the fuse. The fuse
should only operate for a permanent fault. This operation is obtained if the slow
characteristic of recloser lies above the TC curve of the fuse within the considered
minimum and maximum fault currents region. If DG is connected upstream to a
recloser, the fault current seen by the recloser and further downstream fuses will
increase. As a result the required margin between the fast characteristic of recloser
and minimum melting curve will tend to reduce. Thus there is a probability of losing
the coordination with any fuse further down to the recloser [32]. On the other hand, if
a DG is connected between a recloser and a fuse, the fault current seen by a fuse
increases and this may cause it to lose coordination. Before the DG connection, the
recloser and fuse see the same fault current. However, after the connection, the fuse
will see more current than the recloser and it responds before the recloser in the event
of a fault downstream to the fuse location. The effect on coordination increases with
DG capacity. Studies in [33] have shown that traditional reclosers are unable to keep
the coordination with fuses in the presence of high DG penetration. Further this
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
40/179
protection and in transmission as backup protection [34]. There are several types of
overcurrent relays available to select from depending on the application.
Instantaneous overcurrent relays are mostly used to protect sub-transmission lines
while definite time relays are used in ungrounded or high impedance grounded
systems. Moreover inverse time relays can easily coordinate with other protective
devices and they are usually employed to protect distribution networks. A software
model of a inverse time overcurrent relay has been developed to simulate in PSCAD
[34].
High backup time for the minimum fault currents is a disadvantage of
overcurrent relays. A method which proposes to find the time element function for an
overcurrent relay to reduce the back-up time to a constant value independent of the
fault current magnitude rather than in the conventional overcurrent relay is given in
[35]. References [36] and [37] present the IEEE standard analytical equation for the
different types of overcurrent relays (i.e. moderately inverse, very inverse, and
extremely inverse) and operating and reset characteristics that can be taken for
coordination purposes. Relays employed in the radial networks have both inverse
time and instantaneous elements to achieve a quick response for the severe faults as
well as the coordination among relays [26].
Also in the case of the islanded microgrid, the ratio between the source
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
41/179
elements to achieve high speed fault clearing [38]. Reference [39] shows a method
to calculate directional overcurrent relays setting for both grid connected and
microgrid which consists of synchronous generator based DGs. In this method, the
Particle Swarm Optimization algorithm is used in the relay coordination problem to
obtain the optimal settings for the directional overcurrent relays while maintaining
the minimum operating time and coordination among relays. It has been shown that
it is not possible to calculate a setting time for the relays in both the grid connected
and islanded modes of operation. Hence a central control protection unit is required
to change the setting according to the system configuration. However fault current
seen by each device may change according to the location of microgrid connected to
the utility and fault location. Hence attention to coordinate protective devices is
essential.
There are numerous papers which address the coordination issues with the
presence of DGs in the distribution network. However, so far there is little attention
to the coordination analysis of the current limited converter interfaced DGs.
2.2.3Protection in the presence of current limited convertersThe fault current may change due to the presence of DGs in the network [2, 16,
19, 39, 40]. Its impact depends on the size, type, number of the DG, location of the
DG [5 31] Basically three types of DGs exist with different properties; synchronous
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
42/179
are studied in [40] considering the sensitive equipment response. Fault current
behaviour and fault detection in a distribution network for different types of faults in
the presence of an induction generator has been studied in [4]. The system which is
not designed with DGs may not work properly with existing protective devices once
several DGs are connected to the system [6]. In the presence of a generator within
the network, the fault current detected by a protective device located at the beginning
of the feeder can be reduced due to the rise of voltage drop over the feeder section
between the generator and the fault [4]. Therefore the faults previously cleared in a
very short time may now require a significant time to clear.
Most of the distribution resources in the microgrid are connected through the
power electronic converters [12]. For example, the dc power is generated by using
the sources such as fuel cell, micro turbine, or a photovoltaic and converters are
utilised to alter the dc power into ac power. These converter interface generators
supplies the currents not much greater than the nominal load currents [26]. Basically
the controller of the converter mainly consists of two control schemes named voltage
control and current control and it regulates the output active and reactive power [42].
In the voltage control mode, the converter produces a three phase balanced ac
voltage at the terminal. The current control scheme, which is explained in [42], uses
two control loops, an inner loop for the current output and outer loop for the power
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
43/179
protecting a converter dominated microgrid is a challenging technical issue under the
current limited environment [25]. Moreover there is a requirement to find other
protection techniques to solve this problem [7, 26, 27]. One possible approach which
facilitates using the existing overcurrent protection is up-rating of converters to
supply the required fault current. However this will be a costly process. Another
approach that is proposed to overcome this problem is to use a flywheel energy
storage system to obtain the necessary fault current in the event of a fault [44]. The
flywheel supplies the required fault current to operate the overcurrent protective
devices in the islanding operation.
A stand-alone three phase four leg voltage source converter model has been
studied to observe the fault behaviour of an islanded microgrid for different types of
faults in [7]. During a fault, the converter works as a constant current source
supplying the positive sequence current to the system. There are no active sources in
the negative or zero sequence networks. So it has been shown that the microgrid is
equivalent to a current source with parallel impedance which depends on the fault
type. In this converter topology, large voltages can be seen in healthy phases for
unbalanced faults. In [25], fault behaviour in a converter supplied microgrid has been
presented considering different types of converter topologies and microgrid earthing
systems. The paper concludes that the fault response strongly depends on the
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
44/179
proposes an adaptive overcurrent scheme which selects the lower current threshold to
operate the overcurrent device based on the value of voltage detection. In reference
[45], abc-dq transformation of the voltage waveforms is used to identify if the short
circuit condition is inside or outside a set zone in a microgrid. Voltage disturbance at
each relay location is calculated by comparing the reference value with the obtained
dc values in the d-q synchronous rotating frame. The tripping decision is made by
selecting the location which has the highest mean average disturbance value with the
help of a communication link among relays.
A differential relay based protection scheme is proposed to protect a microgrid
in either grid connected or islanded mode in [16]. In this, a central control unit is
used to make decisions on control and protection devices. Line parameters of the two
ends of a protected line have to be monitored by means of a wire connection if the
line is short or by a pilot wire communication if the line is long. The need for
communication channel is a disadvantage of the differential protection scheme.
Moreover, the response of DGs places between two relays will affect their
performance. Another approach for the protection of microgrid with converters in
both islanded and grid connected operation is presented in [8]. A static switch has
been designed to open the microgrid for all types of faults and faults should be
cleared using techniques which do not rely on high fault currents within the
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
45/179
minimum pickup current of the relay is update depending on the fault type and
location. Further, the response of an converter interfaced fuel cell under a fault
conditions has been investigated and it has been shown that the fault will cause the
voltage to drop below to a value such that the undervoltage relay would operate to
trip the DG if the fault occurs near the DG. Therefore undervoltage relay can be used
under a fault condition to determine the status of the DG. Furthermore, IEEE
standard 929-2000 states that converters will sense a short circuit by voltage drop
rather than sensing the short circuit current. Another option is to design the
protective devices to operate for small fault currents. However, this may cause
nuisance tripping [16, 19, 46]. Thus there is a need to assure that for both the
microgrid itself and for the grid connected modes, the protection system is operating
in an adequate fast, selective and reliable way to clear the faults [39].
2.2.4Reclosing, re-synchronization and arc faultsMost of the faults (around 90%) in the power system are temporary arc faults
(such as insulator failures, conductors clashing due to strong wind, animal contacts,
lightning strikes, etc). These faults can be successfully cleared by de-energizing the
line long enough such that the arc self extinguishes. Usually reclosers which open
and close a few times successively are used to clear such faults without any large
scale power interruption [47] Maximum dead time of single phase reclosing in
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
46/179
based on artificial neural network algorithms to solve this problem by analysing the
voltage of the open phase conductor during the recloser dead time interval [47].
Usually three phase reclosers are used in distribution networks. In a DG or
microgrid connected distribution network, the reclosing should be done with proper
synchronization since this will join two live systems. The maximum time available
for automatic reclosing without losing synchronism should be considered. During the
auto recloser open time, if the island and main grid undergo a phase mismatch, then
it may lead to damage to the equipment and DGs in the microgrid [5]. However, if
the DG is connected using a converter, the risk of damage to the DG is low as it has
its own protection [49]. Dead line voltage relay and sync-check relay can be used to
prevent out of phase reclosing [19]. In general, a DG is disconnected before the first
reclosing occurs in the system. This requires that any anti-islanding protection should
operate very quickly. As a result, the recloser should coordinate with the anti-
islanding protection, which is a challenging task [19]. A communication link can be
established between the line recloser and the DG to transfer trip signal to disconnect
the DG quickly [50]. An automatic synchronizing or synchronism check relay should
be used at the PCC breaker when restoring the system after disconnection [18]. Re-
synchronizing can be done manually or automatically using synchronism check relay
with a synchronous generator based DG. However for a converter interfaced DG,
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
47/179
rate after successful arc extinction at the current zero crossing [51]. Also the arc
extinction time is proportional to the arc time constant [52]. On the other hand, the
fault current magnitude of an arc fault is limited by the arc resistance. Sometimes it
results in difficulties of detecting the fault [53]. Moreover, the arc voltage at the fault
point is a source of errors in the fault locating process [54]. Therefore protection of
distribution network and restoration under arc fault is a challenging task.
2.2.5Communication based protectionThe distribution system protection will be complicated when the DGs are
spread throughout the network. As a result new protection issues will arise for the
traditional distribution networks. To address some of the issues, a protection based
on a communication medium has been developed. Communication media including
power line carrier (PLC), microwave and optical fibre have long been used for the
transmission line applications. However, in nature, the distribution lines are different
from transmission lines. These lines are shorter and they have numerous tapped
loads. Therefore a particular communication method for a distribution system
protection should be fast and reliable. Basically three types of communication
networks can be identified as shown in the Fig. 2.1 [55]. In centralised networks, all
nodes are connected to a central point, which is the acting agent for all
communications A network distributed across many nodes rather than centralized
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
48/179
Fig. 2.1 Different types of communication networks (Adapted from [55])
The installation of a larger number of DGs can cause the loss of protection
selectivity. Communication media may be the internet, PLC, wireless
communication, etc. In [56], PLC based methods are proposed for the coordination
of voltage control, islanding detection for a DG and controlling the interface devices
at the PCC. The Islanding detection method is introduced to minimize the problems
of traditional methods based on frequency and voltage measurements. High
attenuation levels can be expected in distribution lines when their structure is
complex and lines are long. To avoid such problems, repeaters need to be installed in
this implementation. Application considerations of internet as the real time
communication medium for providing the loss of mains protection of a DG has been
studied in [55].
The distribution system becomes a multi-source when one after another DG
gets connected at different locations. This change in system configuration will cause
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
49/179
agent approach based on communication is proposed in [17] to provide protection of
the power system and coordination between the protective devices in the presence of
DGs. A new method is proposed in [13] based on analysing the sign of wavelet
coefficients of the fault current transient to locate and isolate a faulted segment. In
this, relay agents are proposed to implant the proposed protection scheme. A fault
location and fault isolation technique of a DG connected distribution network using
neural networks is presented in [59]. In this, the system has different zones and the
relay at substation communicates with zone breakers to take appropriate actions.
With the use of communication, relay coordination has the ability to rapidly
select the faulted region. However, installation of extensive communication will
require time. Once the power system is smart grid ready, various smart relays can be
installed. Till that time, protection without any or low levels of communication will
be the most cost effective solution.
2.3SummaryIn this chapter, a brief summary is presented based on the review of the
previous published research work on the protection issues which arise after the
connections of DGs and microgrids to distribution networks. There are several
benefits available for both the network operator and customer by utilising DGs or
Chapter 2: Literature review
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
50/179
The proposed protection scheme should isolate the faulted segment as quickly
as possible from the network. The DGs can then supply the power to unfaulted
segments in the network if they have been designed to operate in islanded mode. To
achieve that solution, several protection solutions have been proposed based on
communication for DG connected networks. However, most of them need reliable
communication medium for fast operation.
Most of the time, current sensing protective devices have been used to detect
the faults in the network. However, with the high penetration level of converter based
DGs, protection of the system has been identified as a key challenging issue.
Although different solutions have been proposed to solve this problem, further
studies are still required to identify and improve the efficient fault detection methods.
In the near future, when more DGs come into operation, protection will be a
challenging task due to the network complexity.
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
51/179
Chapter 3: Protective relay for DG connectednetworks
3.1IntroductionIn a high penetrative DG network, a small possible portion should be isolated
during a fault allowing unfaulted segments to operate in either grid connected or
islanded mode to increase the system reliability by maximizing the DG benefits. To
achieve the faulted segment isolation, both upstream and downstream protective
devices should detect and isolate the fault. However, with the connection of DGs to a
distribution network or within a microgrid, fault current level can vary depending on
the DG connectivity, DG type and DG location. It results in difficulty of coordinating
existing overcurrent protective devices since network configuration changes.
Moreover, settings of these overcurrent relays to incorporate DGs are not possible if
DG power output changes with time or their connectivity is not consistent.
Furthermore, protection will be a challenging task when using converter
Chapter 3: Protective relay for DG connected networks
l I Ti Ad itt (ITA) t ti l i d b d th
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
52/179
novel Inverse Time Admittance (ITA) protective relay is proposed based on the
measured admittance of the protected line to avoid deficiencies of existing protection
schemes. The fundamentals of ITA relays are explained in this chapter.
3.2ITA relay characteristicsA radial distribution feeder as shown in Fig. 3.1 is considered to explain the
ITA relay characteristics. It is assumed that the relay is located at nodeRand node K
is an arbitrary point on the feeder. The total admittance of the protected line segment
is denoted by Yt while the measured admittance between the nodes R and K is
denoted by Ym. Then the normalised admittance (Yr) can be defined in terms of Ytand
Ymas
t
mr
Y
YY = (3.1)
Fig. 3.1 A radial distribution feeder
The variation of normalised admittance along a radial feeder is shown in Fig.
3.2 by assuming the feeder has a length of 3000m while the total feeder impedance is
Chapter 3: Protective relay for DG connected networks
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
53/179
Fig. 3.2 The variation of normalised admittance
The change of normalised admittance along the feeder is used to obtain an
inverse time tripping characteristic for the relay. The general form for the inverse
time characteristic of the relay can be expressed as
k
Y
At
r
p +
=
1
(3.2)
whereA, and kare constants, while the tripping time is denoted by tp. The values
for these constants can be selected based on the relay location in a feeder and the
protection requirements. The shape of the proposed inverse time tripping
characteristic can be changed by varying the constants to obtain the required fault
clearing time. When a network consists of different types of protective devices, these
Chapter 3: Protective relay for DG connected networks
tripping time for a fault near to the relay On the other hand higher fault clearing
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
54/179
tripping time for a fault near to the relay. On the other hand, higher fault clearing
time can be obtained when the fault is further away from the relay location.
Fig. 3.3 Relay tripping characteristic curve
It is to be noted that the normalized admittance in (3.2) should be greater than
1.0 for relay tripping. This implies that the measured admittance is greater than the
total admittance as shown in (3.3). This constraint is used by the relay algorithm to
detect a faulted condition in the network. Moreover, the relay algorithm checks this
constraint continuously during the faulted condition until relay issues the trip
command to avoid any unnecessary tripping due to the effect of transients. The
tripping time is decided depending on the calculated value of measured admittance.
Y
Chapter 3: Protective relay for DG connected networks
to generate a number of required zones of protection In each zone the relay has a
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
55/179
to generate a number of required zones of protection. In each zone, the relay has a
unique tripping characteristic. It checks whether the measured admittance is greater
than the total admittance of that particular zone before starting the relay tripping time
calculation. A large coverage and minimum tripping time can be achieved by
increasing the number of zones. It also leads to a good coordination amongst the
relays in a feeder. Any upstream relay always provides the back up protection for the
immediate downstream relay in the feeder.
The radial feeder shown in Fig. 3.4 is considered to explain the relay reach
settings. The relays are located at BUS-1, BUS-2 and BUS-3. It is assumed that each
relay has two zones of protection. Zone-1 of each relay is selected to cover the whole
line segment between two adjacent relays, while Zone-2 is selected to cover twice
the length of the first line segment. The reach setting is set based on the positive
sequence admittance of the considered line segments. Zone-1 and Zone-2 tripping
characteristics are the same for all the relays. For example, relay tripping
characteristic curves for two adjacent relays R1and R2are illustrated in Fig. 3.5. The
locations of relays R1and R2and the tripping time of these relays against the distance
to the fault from the relay locations are shown in the figure. Each zone has different
values for the constants in (3.2) resulting different relay tripping characteristic
curves. It can be seen from Fig. 3.5, Zone-2 of R1will provide a backup for the relay
Chapter 3: Protective relay for DG connected networks
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
56/179
Fig. 3.5 Relay protection zones and relay coordination
The proposed new relay does have the ability to isolate the faults occurring at
either side of the relay in a radial feeder. This is because the absolute value is taken
into consideration in admittance normalizing process. However, for the relay to
operate for reverse faults there must be an infeed that is located downstream from the
relay. If the distribution network consists of these relays located at equal distances,
the same forward and reverse reach can be used to isolate forward and reverse faults.
The value for the reach of a particular zone should be selected according to the
requirement.
However, the reach setting should be different for forward and reverse faults,
when the relays are not placed equidistant from one another. In this case, each relay
Chapter 3: Protective relay for DG connected networks
relays are not equal. To accomplish forward and reverse reach in relays, the relay
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
57/179
y q p y , y
should sense the fault direction. Moreover, the relay has the capability to identify
whether the fault is in the forward or reverse direction. Any method which will
determine the fault direction can be used for this purpose.
One possibility is to measure the relative difference of angle between the
current and bus voltage. The fault current lags the bus voltage for a forward fault
while for a reverse fault the fault current leads the bus voltage. In [60], relative phase
angle between fault current and pre-fault voltage is used to determine the fault
direction. Another possibility is to calculate the negative sequence impedance seen
by the relay. Based on the calculated value, the relay identifies the fault direction to
select the appropriate reach setting. This approach is only valid if the fault is
unsymmetrical since negative sequence will not be present for symmetrical faults.
The negative sequence impedance is always positive for the reverse faults and it is
negative for the forward faults [61]. The positive sequence directional element
proposed in [62] can be also used to identify the fault direction. After identifying the
fault direction, the process of tripping time calculation can be implemented as shown
in Fig. 3.6.
Chapter 3: Protective relay for DG connected networks
3.4Different ITA relay elements
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
58/179
y
The ITA relay has different types of protection elements to detect different
faults. All elements are designed to operate based on measured admittance of the
protected line. These elements are explained below.
3.4.1Earth elementsThese elements will respond for the line to ground faults. The number of
elements varies depending on whether protection has been configured as directional
or non-directional. If protection is directional, then there are two independent earth
elements per phase. The positive sequence measured admittance; YRK1 seen by this
relay element is given by (3.4). The derivation of this formula is given in Appendix-
A.
Ra
RK
RK
RaR
RKV
Y
YI
aI
Y
+
=
10
1
01
(3.4)
where IRa is the rms line fault current through the relay while IRa0 is the zero
sequence fault current seen by relay and VRa is the faulted phase rms voltage. The
line parameters are used to calculate the ratio of YRK1/ YRK0. The relay reach is set
based on the positive sequence admittance of the protected line segment. This relay
Chapter 3: Protective relay for DG connected networks
example, for phase A, two phase elements are employed, if protection is non-
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
59/179
directional, one for the faults between phase A and phase B and another for the faults
between phase A and phase C. Measured admittance seen by a phase element for a
line to line fault, between phase A and phase B, can be expressed as,
RbRa
RbRRK
VV
IaIY
=1 (3.5)
whereIRaandIRbare rms phase currents in faulted phases and VRaand VRbare faulted
phase rms voltages. This measured admittance in (3.5) is used by relay logic to detect
a line to line fault in the network.
3.4.3Directional elementsThe directional elements can be used to identify whether the fault is in forward
or reverse direction from the relay. This will help to implement separate reach
settings for each direction especially when a relay protects non-equidistant zones.
The user has been given the facility to select the preference as listed in Table 3.1.
Table 3.1 Selection criterion of a directional element
Setting Operation
Directional Each element has two settings to cover both forward
and reverse direction faults
Non-directional Each element operates regardless of the fault direction
Chapter 3: Protective relay for DG connected networks
current transformer (CT) respectively. The relay output is linked to the tripping coil
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
60/179
of the circuit breaker (CB). The relay continuously monitors the input parameters and
executes the relay logic to identify a faulted condition in the network. The process of
making the tripping decision is shown in the Fig. 3.8. Based on the fundamental
voltage and current, the admittance is calculated, which is the measured admittance
of the relay point at a given time. The measured admittance and values for the relay
reach settings are the inputs to the relay logic. This logic consists of normalized
admittance calculation, relay characteristic equations, relay tripping time
calculations, identification of fault direction and defined relay constraints. The
faulted condition is detected by using the constraint in (3.3). Once fault is detected,
the calculated tripping time based on measured admittance is fed through an
integrator to obtain the tripping signal for the CB. Also relay checks whether the
fault detection signal exists until relay issues the tripping command to avoid any
nuisance tripping.
Fi 3 7 R l i di h
Chapter 3: Protective relay for DG connected networks
3.6Settings of ITA relays to detect resistive faults
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
61/179
Higher fault resistance can affect the operation of ITA relays. Therefore a
method of relay settings is described to achieve successful relay operation in the
presence of fault resistance. The relay carefully checks the constraint in (3.3)
continuously, which is the comparison between the measured admittance (Ym) and
the total admittance (Yt) setting of a particular zone. The relay detects a fault in the
network when Ymbecomes higher than Yt. For a fault within a particular zone, Ymis
always greater than Yt, if fault resistance is zero. However, with the increase of .fault
resistance, Ym can become less than Yt. Also the maximum fault resistance which
allows the relay to operate depends on the fault location of the line. For example, the
relay can operate for a higher resistive fault, if the fault is near the relay than when it
is further away from the relay since a higher value of fault resistance can be
compensated by each zone for near faults.
Another protective zone is introduced to achieve the tripping operation of the
relays under resistive faults. The maximum fault resistance which can be tolerated by
the relay is decided based on the loads of the feeder. In this case, the relay operation
can be obtained up to a pre-defined value of fault resistance. This method will not
work for higher resistive faults, where fault currents are in same levels as load
currents. The minimum equivalent impedance of loads (i.e. the maximum load
Chapter 3: Protective relay for DG connected networks
effect of cold load inrush can be considered. Therefore, it is proposed to select one
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
62/179
third of minimum equivalent impedance of loads as the fault resistance setting.
A relay, if it has two zones, has two tripping characteristic curves. In this case,
total admittance, Ytshould be set separately for each zone depending on protection
requirements. Instead of these two zone characteristics, another characteristic will be
introduced to discriminate the high resistive faults as mentioned above. Hereinafter,
this zone is denoted by Zone-3. In this case Yt consists of corresponding line
impedance and the maximum fault resistance which is determined based on loading
condition. A coordination time interval should be kept between adjacent two Zone-3s
of relays to obtain the correct relay grading. Otherwise relay characteristic of Zone-3
in each relay will not show a considerable time difference for the faults with low
fault resistance. Also the tripping time is set to a little higher value than the settings
in the normal zone operations, since there is no requirement to isolate the faults with
lower fault currents faster than the faults with higher fault currents. The radial
network shown in Fig. 3.4 is considered again to illustrate the relay settings for all
the zones.
3.6.1Zone-1 settingsZone-1 reach setting is similar for all the relays if they are located equidistant.
Therefore Yt is set by assuming the Zone-1 will protect 120% of the first line Z12
Chapter 3: Protective relay for DG connected networks
3.6.2Zone-2 settings
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
63/179
Ytis set by assuming Zone-2 will protect 200% of the first line. This setting is
also similar for all the relays. The reach setting and tripping characteristic can be
given by
)2(
1
122_
ZY Zonet
= (3.8)
15.01
0037.01.0 +
=
r
pY
t (3.9)
3.6.3Zone-3 settingsThis zone represents a broader coverage of the protected line including the
compensation for fault resistance. The value of Yt can be set using the allowable
maximum fault resistance. The allowable maximum fault resistance is denoted by Zf
after calculating the maximum load and adjusting it using the safety margin. It
should be noted that Zfis the maximum fault resistance that can be handled by the
relay when fault occurs in the far end of the protected zone. It is not the fault
resistance in a particular fault condition. In this case, Ytfor the Zone-3 can be set as,
)(1
123_
fZonet
ZZY
+= (3.10)
Zone-1 and Zone-2 tripping characteristics are same for all the relays.
Chapter 3: Protective relay for DG connected networks
reverse faults. If the relay detects the fault as forward, then forward tripping
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
64/179
characteristic, t_Zone3Fis activated. On the other hand, reverse tripping characteristics,
t_Zone3Ris activated if fault is detected by the relay as reverse.
The Zone-3 tripping characteristic of each relay can be modified by assigning
different constant values. A minimum tripping time characteristic should be selected
for the furthest downstream relay to discriminate the forward faults. It can be then
increased according to the coordination time interval between two adjacent relays.
This Zone-3 grading is similar to the TDS setting of an overcurrent relay in a radial
feeder. On the other hand, the minimum tripping time characteristic for reverse fault
is selected to the furthest upstream relay. The settings of Zone-3 for the relays R1, R2,
and R3 in the radial feeder of Fig. 3.4 can be given as shown in (3.11)-(3.13)
respectively. These settings can be changed according to the protection requirements.
15.1
1
0037.0
1.01_3 +
=
r
RFZone
Y
t
45.01
0037.01.01_3
+
=
r
RRZoneY
t
(3.11)
85.01
0037.01.02_3
+
=
r
RFZoneY
t
75.01
0037.01.02_3
+
=
r
RRZoneY
t (3.12)
5500037.0
3 +=t
Chapter 3: Protective relay for DG connected networks
tripping characteristics of R2 and R3 are calculated using (3.12) and (3.13)
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
65/179
respectively. The figure also shows the combined forward relay characteristics of
Zone-1 and Zone-2. It can be seen that forward Zone-3 as well as reverse Zone-3
characteristics of each relay have been graded appropriately to achieve the backup
protection. For example, it is assumed that a fault between BUS-1 and BUS-2 in the
system cannot be detected by the primary zones (i.e., Zone-1 and Zone-2) of R 1and
R2. Then, in this case, R2detects the fault in reverse Zone-3 to isolate the fault from
downstream side while R3provides the backup protection as shown in Fig. 3.9.
Fig. 3.9 Relay tripping characteristics of different zones
3.7Practical issues for admittance calculation
Chapter 3: Protective relay for DG connected networks
usually appear in current signal. However, the decaying dc magnitude and time
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
66/179
constant cannot be calculated before a fault occurs since it depends on the system
configuration (X/R ratio), fault location and the value of fault resistance.
Fast Fourier Transform (FFT) or Discrete Fourier Transform (DFT) can be
used to extract the fundamental component from a sampled waveform. FFT is a fast
way of calculating the DFT. FFT can accurately calculate the fundamental in the
presence of harmonics and signal noises. However, it is not immune to decaying dc
component.
DFT is widely used in digital protective relays. DFT can extract the
fundamental in the presence of harmonics, however it is also not immune to decaying
dc component [63]. Some previous studies propose some interesting techniques to
calculate the fundamental component accurately in the presence of decaying dc
component. A method is proposed in [63] to eliminate the effect of decaying dc
component by calculating the time constant of the faulted current waveform. In this
algorithm, the dc magnitude is then calculated based on the calculated time constant
for a cycle and subtract the dc magnitude from samples to obtain the DFT without
decaying dc component. A DFT based filter algorithm is presented in [64] for digital
distance relays to extract the fundamental accurately. In [65], a method is described
to remove the decaying dc component for an application of protective relays. It can
Chapter 3: Protective relay for DG connected networks
tripping time calculation. However, the speed of the calculation and burden on the
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
67/179
processor should be carefully considered when selecting a particular algorithm to
avoid the errors coming form decaying dc component on tripping time calculations.
3.8SummaryIn this chapter, the basic features of the proposed ITA relay to protect a
distribution network or a microgrid which has several DGs are discussed. The relay
inverse time characteristic and relay reach setting have been explained. Furthermore,
different relay elements and a method of relay setting to achieve fault detection under
higher resistive faults have been explained. Finally, the challenges of implementing
ITA relays and possible solutions to avoid them are identified.
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
68/179
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
69/179
Chapter 4: Evaluation of ITA relayperformance
4.1IntroductionFaults can be usually identified by sensing the current level in an electrical
power system since high currents can be seen during the faults. Overcurrent (OC)
relays, fuses and moulded case circuit breakers (MCCBs) are the common type of
current sensing protective devices used in distribution networks. The OC relays can
be classified as definite current or instantaneous, definite time and inverse time based
on the operating characteristics. In this chapter, features of inverse time OC relays
are briefly considered since they are commonly used in distribution networks. On the
other hand, distance type relays are commonly used to protect the transmission
networks where speed of operation and reliability are very important. Fundamentally,
MHO type distance relay are considered in this chapter. These existing OC and
distance relay protection schemes are compared with the proposed ITA relay to
demonstrate the performance of the ITA relay. The grading and coordination of
Chapter 4: Evaluation of ITA relay performance
4.2Inverse time overcurrent relays
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
70/179
Most of the existing distribution networks are radial and they are employed
with OC protective devices because of their simplicity and low cost [4, 30].
Coordination of such protective devices based on current is relatively easy in the
radial networks. The IEEE Standard inverse time relay tripping characteristic is
given by [37]
TDSBM
At
pp
+
=
1 (4.1)
where the constants A, Band pare used to select the relay characteristic curve and
time dial setting (i.e. TDS) is used for the coordination between several OC relays.M
is the multiple of pickup current and it is defined by
=
p
f
I
IM (4.2)
whereIfis the fault current seen by the relay andIpis the relay set current (i.e. pickup
current). Three inverse time OC relay characteristic equations are given in the IEEE
report [37]. They are moderately inverse, very inverse and extremely inverse. Each
relay curve has different constants values in (4.1).
To illustrate the grading of inverse time OC relays, a four bus bar radial feeder
Chapter 4: Evaluation of ITA relay performance
4.2. The relay tripping time tp is shown with the fault location. Coordination time
i t l f R R d R R d t d b t d t ti l L t TDS
-
8/12/2019 Jalthotage Dewadasa Thesis.bak
71/179
intervals for R1-R2 and R2-R3are