Malaysia End-User Seminar11 November 20091
Device Management
Jonas BergeEmerson Process Management
Malaysia End-User Seminar11 November 20092
Topics
• What is intelligent device management?• Integrated device management• Why do I need a handheld field communicator?
– With fieldbus, I can do everything remotely from the control room, right?
• Handheld and workstation, are they the same?
3Malaysia End-User Seminar
11 November 2009
Intelligent Device Management
Malaysia End-User Seminar11 November 20094
The Promise of Bus Technologies:- Intelligent Device Management
Live Device Data• Monitoring
– Identification– Information
• Diagnostics• Configuration/Setup
– Parameterization– Range– Calibration Trim– Simulation & Override– Device Security
Database• Service Notes• Audit Trail and Reporting
– Configuration changes– Maintenance
• Device List• Calibration Scheduling• Documentation• Calibration Log Entry
Malaysia End-User Seminar11 November 20095
Sophisticated Workstation Graphics
Waveform Graph
Image
Trend Chart
Bar/Histogram
Gauge
Frame
Tabbed Card
Navigation
Table
Pop-Up Window
Malaysia End-User Seminar11 November 20096
Same Graphics in Handheld
Waveform GraphImage
Trend ChartBar/Histogram
Gauge
Table
Malaysia End-User Seminar11 November 20097
“Wizards”• Device Management
System• Handheld Field
Communicator
Malaysia End-User Seminar11 November 20098
Manufacturer Know How
• Device Management System
• Device Management System
Malaysia End-User Seminar11 November 20099
Identification
• Tag• Device ID• Manufacturer• Model number• Serial numbers• Versions
– Hardware– Firmware
• etc.
Malaysia End-User Seminar11 November 200910
Information
• Materials of constructions– Wetted parts
• Primary element data– Orifice plate
• Final element data– Actuator
• Manufacturer• Model number• Serial number
– Valve• Manufacturer• Model number• Serial number
Malaysia End-User Seminar11 November 200911
Diagnostics
• Sensor failures• Plugged impulse line• Loss of supply air• Memory failures• etc.
Fix problems sooner
Malaysia End-User Seminar11 November 200912
Smart Diagnostics- Integrated Device Management
• Normal operation...
• Device failure...• Faceplate...• Diagnostics
– No device configuration
Malaysia End-User Seminar11 November 200913
Performance Analysis
• Vibration spectrum• Valve signature• Step response• Hysteresis• etc.
Reduce Process
Variability
Malaysia End-User Seminar11 November 200914
Operational Statistics
• Reversals• Total travel• Power cycles• etc.
Predict and avoid problems
before they occur
Malaysia End-User Seminar11 November 200915
Parameterization
• Ranging• Advanced setup
– Radar echo curve• Reconciliation
– Compare• etc.
Faster commissioning
and replacement
Malaysia End-User Seminar11 November 200916
Device Security
• Write protection
Malaysia End-User Seminar11 November 200917
Document Access
• Device Type Documents– Product Data Sheet– Manuals– Procedures
• Plant Location Documents– P&ID– Loop diagram
Malaysia End-User Seminar11 November 200918
Monitoring
• Dynamic monitoring of device internal parameters and logic
Malaysia End-User Seminar11 November 200919
Maintenance
• Log– Calibration– Inspection– Service– etc.
Malaysia End-User Seminar11 November 200920
Service Notes
• Permanent record of technician's observation
Malaysia End-User Seminar11 November 200921
Audit Trail and Report• Reporting on all activities of activities for
traceability
Easier regulatory
compliance
Malaysia End-User Seminar11 November 200922
Scheduling
• Schedule– Calibration Trim
Better utilization of resources
23Malaysia End-User Seminar
11 November 2009
Calibration
What is calibration?Calibration CheckCalibration Trim
Malaysia End-User Seminar11 November 200924
CalibrateANSI/ISA–S51.1–1979 (R1993)
Calibrate: To ascertain outputs of a device corresponding to a series of values of the quantity which the device is to measure, receive, or transmit. Data so obtained are used to:
1) determine the locations at which scale graduations are to be placed;
2) adjust the output, to bring it to the desired value, within a specified tolerance;
3) ascertain the error by comparing the device output reading against a standard.
Malaysia End-User Seminar11 November 200925
Calibration- What does it mean?
1. Determine the locations at which scale graduations are to be placed;
– Set the 4 mA and 20 mA points (range)– Scaling/ranging can be done remotely without applying input– Scale/range not applicable to most fieldbus transmitters
2. Adjust the output, to bring it to the desired value, within a specified tolerance;
– Trim the output current– Need to connect a multimeter– Not applicable to fieldbus
3. Ascertain the error by comparing the device output reading against a standard.
– Trim the sensor reading– Need to apply input (e.g. equalize and vent manifold to zero)– Is applicable to fieldbus
Malaysia End-User Seminar11 November 200926
Calibration for Fieldbus
•Sensor Trim– If measurement reading is
wrong it must be corrected• E.g. correct for mounting position
– From transducer block– Need to apply input
• Done in the field
• Configure Range/Scale Setting
–Zero and Span• In PID block (valve or
controller)• In AI block for inferential
measurements such as DP flow and DP level
• Some transmitters may need range to operate
• Cancel wet-leg etc.–Set the portion (range/scale) between sensor limits which is of interest for application
–In function block–Just setting a value
•Done remotely from control room
Malaysia End-User Seminar11 November 200927
Calibration Trim
• Methods simplify complex tasks
• Ensure correct procedure
• Eliminates mistakes
Malaysia End-User Seminar11 November 200928
Field Calibration Trim Tools
• Field Communicator– Plus calibrator– Clipboard for notes
• Documenting calibrator– With Fieldbus interface– Mainly pressure and
temperature
Reduce Paper Work
29Malaysia End-User Seminar
11 November 2009
Handheld Communicator
Field Work
Malaysia End-User Seminar11 November 200930
Why do I need a handheld field communicator?
• Field tasks– Sensor trim
• Turn manifold– Cancel wet-leg
• Verify empty– Valve stroking
• See it move– Repair
• If it indeed failed
• Laptop/tablet– Heavy– Moving parts– Usually not rugged– Not hazardous area
certified– Limited battery life
Malaysia End-User Seminar11 November 200931
Are Handhelds and Device Management Software The Same?
• Information content & structure– Same, because determined by the device
manufacturer, not the system/handheld• Look & feel
– Slightly different, because dependent on the platform• Screen size, color, keyboard, mouse...
• Features– Different
• Device management software is permanently connected• Device management software has a database
– Audit trail, scheduling, persistent data storage, manuals, other documents etc.
Malaysia End-User Seminar11 November 200932
Conclusion
• You don’t have to go to the field as often– Diagnostics and configuration done remotely
• You still need to go to the field sometimes• Working in the field is easier than in the past• Specialized tools and solutions for fieldbus are
available• Fieldbus is not difficult
Malaysia End-User Seminar11 November 200933
www.fieldbus.org