Rf-Technologies nv - Lange Ambachtstraat 40 - 9860 Oosterzele - Belgium - Tel +32 9 362 31 71 - Fax +32 9 362 33 07 - www.rft.be - [email protected] Distributed in the UK and Ireland by: Smoke Control Dampers Limited - 6 Avon Gorge Industrial Estate - Portview Road, Avonmouth - Bristol, BS11 9LQ T:+44 (0) 117 938 1666 EN 12101-8 Tested & Certified Smoke Control Damper Kamouflage V12-A 11/2012 Clapets coupe-feu et Volets de désenfumage D.A.S. Organisme Certificateur AFNOR Certification - www.marque-nf.com Janus 2012 de l'Industrie 1812 P ATENT PENDING

Upload: others

Post on 05-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

Rf-Technologies nv - Lange Ambachtstraat 40 - 9860 Oosterzele - Belgium - Tel +32 9 362 31 71 - Fax +32 9 362 33 07 - www.rft.be - [email protected] in the UK and Ireland by: Smoke Control Dampers Limited - 6 Avon Gorge Industrial Estate - Portview Road, Avonmouth - Bristol, BS11 9LQ T:+44 (0) 117 938 1666

EN 12101-8 Tested & Certified Smoke Control Damper

Kamouflage

V1

2-A

11

/20

12

Clapets coupe-feu etVolets de désenfumage D.A.S.

Organisme CertificateurAFNOR Certification - www.marque-nf.com

Janus 2012de l'Industrie

1812

Patent Pending

Page 2: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

Kamouflage EN 12101-8 Smoke Control DamperV12-A

11/2012

2

Content

Content• ProduCt Presentation•r a n g e . . . . ..................................................................................................................2 Fire resistanCe • aPProvals and test rePorts •oPtions.................................................................................................3 Finishing • storage and handling • dimensions and installation...................................................................................4 eleCtriCal ConneCtions...........................................................................................................................................................6 oPerating..................................................................................................................................................................................7 maintenanCe • evolution - kits............................................................................................................................................8 teChniCal data........................................................................................................................................................................9 Free air Passage.....................................................................................................................................................................10 samPle order.........................................................................................................................................................................11

ProduCt Presentation

What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall. Its outer face consists of a plasterboard panel enabling decorative finishes to be applied to match or contrast with the adjacent wall finish. kamouflage is available as a 1 or 2 hour fire resistant smoke control damper for 24 volt DC activation with a manual reset only. In addition to single and double shutter units for vertical wall installation, the kamouflage P model is suitable for ceiling mounting into the bottom of smoke shafts. • Tested according to EN 1366-10, EN 12101-8 standard and NF S 61937• Aesthetic version without grille 2• Superior air tightness• Minimal pressure drop 6• Suitable for mounting in Fire board ducts 5• Increasedenergyandacousticefficiency• Easy to install• Maintenance free• For indoor applications • Winner of the "Janus de l'Industrie" Award

range

Minimal dimensions W x H [mm] Maximal dimensions W x H [mm]1V 60 1V 120 300 x 385 700 x 1075

2V 60 2V 120 350 x 385 1100 x 1105

W= WidthH= HeightSee complete range p. 10-11

6

5

4 213

7

1. 1 shutter (1V) / 2 shutters (2V) 2. Anodised aluminium frame 3. Electro release & manual key4. Terminal connection box5. Stand open device6. Central support 7. CE marked product

Page 3: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

V12-A11/2012

3

Kamouflage EN 12101-8 Smoke Control Damper

Fire resistanCe aCCording to en 13501-4

Fire board thickness

Kamouflage 1V/2V 60 Kamouflage 1V/2V 120

Mounting in calcium-silicate duct30 mm EI 60 (ved-i↔o)

S1500AAmulti -

50 mm EI 60 (ved-i↔o) S1500AAmulti

EI 120 (ved-i↔o) S1500AAmulti

Mounting in Fibrous plaster Geo-staff duct

30 mm EI 60 (ved-i↔o) S1500AAmulti -

45 mm EI 60 (ved-i↔o) S1500AAmulti

EI 120 (ved-i↔o) S1500AAmulti

E = integrity 60/120 = fire resistance i↔o = fire side randomly I = thermal insulation ved = vertical duct AA = automatic activation S = smoke leakage 1500 = pressure level 3 multi = multiple compartiment

aPProvals and test rePorts

Allourshuttersaresubmittedtotestsbyofficialtestinstitutes.Reportsofthesetestsformthebasisfortheapprovalsofour dampers

1812 Europe :ClassificationfollowingEN12101-8(Approval1812-CPD-1043) France :NFcertificate:pending

ISO :Certification:ISO9001

oPtions

1. 2 sets of volt free contacts for remote signalling of damper position. 2 x Open and 2 x Closed

FDCB (FDCU standard included)

2. Mounting frame KAP 3. Drop guard grid KGC 4. Protection bars KGD

Build in mounting frame for all wall types (delivered separately)

Mounting frame with hinged drop guard grid. The grid is easily deployed in the duct and provides an invisible solution for anti-fall prevention grille when low mounted shutters. (delivered separately)

Horizontal anti-fall protection bars(fixedintheshutterprofile),alternative option for the lower shutters.(Suppliedfixedtofrontofdamper)

iCaution:• Using a mounting frame has an impact on the dimensions of the opening.• These options cannot all be combined. In order to secure lower shutters, select either

KGC (frame + invisible grid), or KAP + KGD.

Page 4: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

Kamouflage EN 12101-8 Smoke Control DamperV12-A

11/2012

4

storage and handling

TheKamouflagesmokecontroldamperisafiresafetyproduct,itneedstobestoredandhandledwithcautionandkeptingood working order. Comprehensive safety, installation and maintenance instructions are available and despatched with each product but general requirements as follows: iCaution:

• Handle with extreme care when transporting and transferring the damper to avoid any damage. Do not drop.• Keep storage period to a minimum.• Do not store in the open but in a dry place well protected from rain.• Keep clear of the ground by the use of pallets. Do not stack.• Store away from cement, plaster and lime keep covered but allow air to circulate.

dimensions and installation

iCaution :

•Whenfitting,theshuttershouldbeprotectedfromanysealingproductsandhandledwithcare. • Before putting the installation into operation, clean off all the dust and dirt. •Iffittinginasmokeevacuationduct,bearinmindtheshutter'sclearance.

Legend :

1.Refractorymaterialforfirecompartmentpenetrationsleeve(calcium-silicatefireboard)

2. Penetration seal (ex. plaster) if mounting frame is used3. KAP mounting frame (option)4. KGC drop guard grid (option)

Wn Wn + 10mm

Wn + 54mm

(1V

) W

n +

52

mm

(2V

) W

n/2

+ 6

6m

m

(1V

) W

n +

62

mm

min

.10

5m

m1

0m

m

(2V

) W

n/2

+ 7

2m

m

Wn + 20mm

4

2

1

3

92

mm

Page 5: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

5

Kamouflage V12-A11/2012EN 12101-8 Smoke Control Damper

Application to other duct constructions than those used during the test:

Multi- compartment smoke control dampers may be applied to ducts that have been tested to EN 1366-9 and EN 1366-8 as appropriate, constructed from materials of the same density as those tested or of the same material with a greater density or thickness. Theductshouldbebuiltaccordingtothemanufacturer'sclassificationreport.

Installation in calcium-silicate or staff duct

Fixation with mounting frame Fixation by direct sealing

Reference / RéférencePlate / Planche

Plan Title / Titre du planD

ate / Date:

23/08/2011

3/3Subject / Sujet

Notice V

A-1V

NT-V

A-1V

-2-Montage

(L +

A) x

(H+

A) m

m

e

e

Reference / RéférencePlate / Planche

Plan Title / Titre du planD

ate / Date:

23/08/2011

2/2Subject / Sujet

Notice V

A-1V

NT-V

A-1V

-3-Montage

(L +

A) x

(H+

A) m

m

e

e

1. Make an opening of (W + A) x (H + A)mm (A = 2x(thickness of sleeve e)+20).

2. Fit a sleeve (thickness e) of 105mm deep in the opening.3. Fix the sleeve to the partition wall.4. Seal the mounting frame taking care not to misshape it. 2 sealinglugsareprovidedoneachfitting,whichmustbeopenedoutwhensealing.Thefinishedopeningmustbethesame size as the mounting frame (W + 10) x (H + 10)mm.

5. Positiontheshutterinthemountingframeandfixtheshutter to the frame using 4 screws M6, supplied with the frame.

iCaution : make sure that the screws don't exceed the thickness of the sleeve !

1. Make an opening of (W + A) x (H + A)mm (A = 2x(thickness of sleeve e)+10).

2. Fit a sleeve (thickness e) of 105mm deep in the opening.3. Fix the sleeve to the partition wall.4. Positiontheshutterinthemountingframeandfixthe

shutter to the frame using 4 screws M6, supplied with the frame.

iCaution : make sure that the screws don't exceed the thickness of the sleeve !

Page 6: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

6

Kamouflage V12-A11/2012EN 12101-8 Smoke Control Damper

eleCtriCal ConneCtions

Wiring diagram

FCU

121110

DCB

NONFC

15 161413

FCB

NONFC

9875 6

DCU

NONFCNONFC

1

-+

2

24/48 V DC +/- 10%24/48 V AC +/- 10%

24 V DC 48 V DC

Technical data

Power supply Position switches

Magnet: 24VDC/48VDC Standard: 1mA...6A, DC 5V...AC 250V

Power consumption Degree of protection

Magnet VD: Pmax = 3,5W IP 42

VM: Pnom = 1,5W

Explanation of the abbreviations

VAC= Alternative current V= Volt PMAx

= Maximal capacity MOD= ModuleVCC= Direct current W= Watt P

NOM= Nominal capacity DAS MOD=Modular product

E.ALIM= Power input TELE=Remotecontrolled S.L.= Free surface E.TELE= Entry control

Electrical supplyDETAIL A

SCALE 1 : 5

Reference / Référence Plate / Planche

Plan Title / Titre du plan Date / Date:

24/08/2011

1/1Subject / Sujet

Notice VA-1V

NT-VA-1V-Arrivée électrique

The electrical supply can be done at the 4 corners of the shutter.

It is enough to drill a hole in the refractory at the side needed, the galvanised part is already indented.

Connectioncablescanbefixedwithfixationclips,presentintheconnectionbox.

Finally, install, between the electrical supply and the connection box, the cable-tie that prevents from unintentionally pulling the cables (included in the connection box). Comply with the installation rules according to article 6.1 of NF S 61-932

Page 7: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

7

Kamouflage V12-A11/2012EN 12101-8 Smoke Control Damper

oPerating kamouFlage

iViewthevideoonourwebsite:www.rft.be(product:Kamouflage,menu:Installation)

iCaution : Please note that the shutters are not allowed to open when the ventilators are working.

1V

Manual /remote control (opening) Manual rearmation (closing)

20°

20°35°

Manual1. Insert the key in the lock2. Turn the key 20° counter clock wise: the shutter opens3. Withdraw the key

RemoteBy sending an electrical impulse (VD) or by interrupting (VM) the power supply to the magnet

1. Insert the key in the lock2. Turn the key 35° clock wise, the key gets blocked in the lock3. Push the blocking mechanism4. Close the shutter by pulling at the key5. Turn the key 15° counter clock wise, the key unblocks from

the lock6. Withdraw the key

2V

Manual/ remote control (opening) Manual rearmation (closing)

20°20°

35°

12

A

B

12

Manual1. Insert the key in the lock2. Turn the key 20° counter clock wise: the shutter opens3. Withdraw the key

RemoteBy sending an electrical impulse (VD) or by interrupting (VM) the power supply to the magnet

1. Insert the key in the lock2. Turn the key 35° clock wise, the key gets blocked in the lock3. Push the blocking mechanism4. Closethefirstshutterbypullingatthekey5. Turn the key 15° counter clock wise, the key unblocks from

the lock6. Push the blocking mechanism of the 2nd shutter7. Close the 2nd shutter by pulling the buckle and

hold the door in your hand (A)8.Openthefirstshutterwiththekeyuntil

position B9. Close both shutters together10. Withdraw the key

eleCtriCal ConneCtions

Wiring diagram

FCU

121110

DCB

NONFC

15 161413

FCB

NONFC

9875 6

DCU

NONFCNONFC

1

-+

2

24/48 V DC +/- 10%24/48 V AC +/- 10%

24 V DC 48 V DC

Technical data

Power supply Position switches

Magnet: 24VDC/48VDC Standard: 1mA...6A, DC 5V...AC 250V

Power consumption Degree of protection

Magnet VD: Pmax = 3,5W IP 42

VM: Pnom = 1,5W

Explanation of the abbreviations

VAC= Alternative current V= Volt PMAx

= Maximal capacity MOD= ModuleVCC= Direct current W= Watt P

NOM= Nominal capacity DAS MOD=Modular product

E.ALIM= Power input TELE=Remotecontrolled S.L.= Free surface E.TELE= Entry control

Electrical supplyDETAIL A

SCALE 1 : 5

Reference / Référence Plate / Planche

Plan Title / Titre du plan Date / Date:

24/08/2011

1/1Subject / Sujet

Notice VA-1V

NT-VA-1V-Arrivée électrique

The electrical supply can be done at the 4 corners of the shutter.

It is enough to drill a hole in the refractory at the side needed, the galvanised part is already indented.

Connectioncablescanbefixedwithfixationclips,presentintheconnectionbox.

Finally, install, between the electrical supply and the connection box, the cable-tie that prevents from unintentionally pulling the cables (included in the connection box). Comply with the installation rules according to article 6.1 of NF S 61-932

Page 8: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

8

Kamouflage V12-A11/2012EN 12101-8 Smoke Control Damper

Finishing

The upper face of the shutter consists of a sheet of plasterboard, which you can decorate to match the wall in which the shutter is installed (paint or wallpaper).

• Coveringplateofplasterboard:filltheholesofthescrewswithasuitablefiller.Letitdryandsand.Applyaprimerpaint suitable for plasterboard.

• Profileofanodisedaluminium:theframeisalreadypreparedtobecovered.Applyaprimersuitableformetal.

Oncetheprimerisdry,proceedwiththefinishing(paintorwallpaper).

maintenanCe

• Nospecificmaintenancerequired• Schedule at least two running checks each year• Removedustandallotherparticlesbeforestart-up• RespectthemaintenanceregulationsaccordingtoNFS61-933

evolution kits

KIT VD24 VA (MOD) KIT VD48 VA (MOD)

Magnet VD24/48

KIT VM24 VA (MOD) KIT VM48 VA (MOD)

Magnet VM24/48

KIT FDC VA (MOD)

2 beginning and end of range switches FDCB

Page 9: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

9

Kamouflage V12-A11/2012EN 12101-8 Smoke Control Damper

teChniCal data

Collective duct Shunt or single duct

Product Smoke evacuation shutter Smoke evacuation shutter

Certification

1812 1812

Obligation Rearmation possible after cold unlocking Beginning of range position switch (DCU) End of range position switch (FCU)

Rearmation possible after cold unlocking Manual control integrated on level 0 or 1 on opening

Security options Manual control integrated on level 1 for opening and closing

Beginning of range position switch (DCU) End of range position switch (FCU)

Interdiction Change of state prohibited after interrupting of power supply to the magnet

Functioning Without external energy Without external energy

Operation Remotecontrolled:Bysendinganelectricalimpulse(VD)orbyinterrupting(VM)thepowersupplyto the magnet

Power supply 24 or 48 Vdc 24 or 48 Vdc

Power consumption 3.5W by electrical impulse (VD) 3.5W by electrical impulse (VD) 1.5W by interrupting (VM) the power supply

Installation direction Axis of the damper blade vertical Axis of the damper blade vertical

Direction of air circulation

Random Random

Position indication Option : bipolar beginning and end of range switches FCB/DCB

Free air passage 1V: [((L-73)x(H-73))-3000]/100002V: [((L-73)x(H-73))-3000-(56.2x(H-73))]/10000

Dimensions WxH See pages 10-11

Durability test After 300 cycles the characteristics stay within declared limit values.

Fire resistance classification

Classification Fire resistance (1500 AA multi):- EI 120 (ved-i o) S 1500 AA multi : range 1V/2V 120: Installation in staff duct 45mm - EI 120 (ved-i o) S 1500 AA multi : range 1V/2V 120: Installation in calcium-silicate duct 50mm - EI 60 (ved-i o) S 1500 AA multi : range 1V/2V 60: Installation in staff duct 30mm - EI 60 (ved-i o) S 1500 AA multi : range 1V/2V 60: Installation in calcium-silicate duct 30mm

Fire side Random Random

Mounting In wall Fixation with or without mounting frame

In wall Fixation with or without mounting frame

Grill Withfinishinggrill Withfinishinggrill

Kits Yes Yes

List of kits See page 8 See page 8

Certifyingorganization:AFNORCertification 11RueFrancisdePressensé F93571 La Plaine Saint-Denis Cedex

The NF-label guarantees: - The conformity with the standard NF S 61-937: “SystèmesdeSécuritéIncendieDispositifsActionnésdeSécurité” - The conformity with the national decree of march 22, 2004 - The values of the characteristics mentioned in this document

Page 10: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

10

Kamouflage V12-A11/2012EN 12101-8 Smoke Control Damper

Free air Passage

iFind the complete selection data and select the ideal product on www.logi-k.fr

Free air passage Kamouflage 1V

H/W [mm] 300 350 400 450 500 550 600 650 700

385 6,8 8,3 9,9 11,5 13,0 14,6 16,1 17,7 19,3

415 7,5 9,2 10,9 12,6 14,3 16,0 17,7 19,4 21,1

445 8,1 10,0 11,9 13,7 15,6 17,4 19,3 21,2 23,0

475 8,8 10,8 12,8 14,9 16,9 18,9 20,9 22,9 24,9

505 9,5 11,7 13,8 16,0 18,1 20,3 22,5 24,6 26,8

535 10,2 12,5 14,8 17,1 19,4 21,7 24,0 26,4 28,7

565 10,9 13,3 15,8 18,2 20,7 23,2 25,6 28,1 30,5

595 11,5 14,2 16,8 19,4 22,0 24,6 27,2 29,8 32,4

625 12,2 15,0 17,8 20,5 23,3 26,0 28,8 31,6 34,3

655 12,9 15,8 18,7 21,6 24,6 27,5 30,4 33,3 36,2

685 13,6 16,7 19,7 22,8 25,8 28,9 32,0 35,0 38,1

715 14,3 17,5 20,7 23,9 27,1 30,3 33,5 36,7 40,0

745 15,0 18,3 21,7 25,0 28,4 31,8 35,1 38,5 41,8

775 15,6 19,1 22,7 26,2 29,7 33,2 36,7 40,2 43,7

805 16,3 20,0 23,6 27,3 31,0 34,6 38,3 41,9 45,6

835 17,0 20,8 24,6 28,4 32,2 36,0 39,9 43,7 47,5

865 17,7 21,6 25,6 29,6 33,5 37,5 41,4 45,4 49,4

895 18,4 22,5 26,6 30,7 34,8 38,9 43,0 47,1 51,2

925 19,0 23,3 27,6 31,8 36,1 40,3 44,6 48,9 53,1

955 19,7 24,1 28,5 33,0 37,4 41,8 46,2 50,6 55,0

985 20,4 25,0 29,5 34,1 38,6 43,2 47,8 52,3 56,9

1015 21,1 25,8 30,5 35,2 39,9 44,6 49,3 54,1 58,8

1045 21,8 26,6 31,5 36,3 41,2 46,1 50,9 55,8 60,6

1075 22,4 27,5 32,5 37,5 42,5 47,5 52,5 57,5 62,5

Page 11: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

11

Kamouflage V12-A11/2012EN 12101-8 Smoke Control Damper

Free air passage Kamouflage 2V

H/W[mm] 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100

385 6,6 8,1 9,7 11,3 12,8 14,4 15,9 17,5 19,1 20,6 22,2 23,7 25,3 26,9 28,4 30,0

415 7,3 9,0 10,7 12,4 14,1 15,8 17,5 19,2 20,9 22,6 24,4 26,1 27,8 29,5 31,2 32,9

445 7,9 9,8 11,6 13,5 15,4 17,2 19,1 20,9 22,8 24,7 26,5 28,4 30,2 32,1 34,0 35,8

475 8,6 10,6 12,6 14,6 16,6 18,6 20,6 22,6 24,7 26,7 28,7 30,7 32,7 34,7 36,7 38,7

505 9,2 11,4 13,6 15,7 17,9 20,0 22,2 24,4 26,5 28,7 30,8 33,0 35,2 37,3 39,5 41,6

535 9,9 12,2 14,5 16,8 19,1 21,5 23,8 26,1 28,4 30,7 33,0 35,3 37,6 39,9 42,2 44,6

565 10,6 13,0 15,5 17,9 20,4 22,9 25,3 27,8 30,2 32,7 35,2 37,6 40,1 42,5 45,0 47,5

595 11,2 13,8 16,4 19,1 21,7 24,3 26,9 29,5 32,1 34,7 37,3 39,9 42,5 45,2 47,8 50,4

625 11,9 14,6 17,4 20,2 22,9 25,7 28,4 31,2 34,0 36,7 39,5 42,2 45,0 47,8 50,5 53,3

655 12,6 15,5 18,4 21,3 24,2 27,1 30,0 32,9 35,8 38,7 41,7 44,6 47,5 50,4 53,3 56,2

685 13,2 16,3 19,3 22,4 25,5 28,5 31,6 34,6 37,7 40,8 43,8 46,9 49,9 53,0 56,1 59,1

715 13,9 17,1 20,3 23,5 26,7 29,9 33,1 36,3 39,6 42,8 46,0 49,2 52,4 55,6 58,8 62,0

745 14,5 17,9 21,3 24,6 28,0 31,3 34,7 38,1 41,4 44,8 48,1 51,5 54,9 58,2 61,6 64,9

775 15,2 18,7 22,2 25,7 29,2 32,8 36,3 39,8 43,3 46,8 50,3 53,8 57,3 60,8 64,3 67,9

805 15,9 19,5 23,2 26,8 30,5 34,2 37,8 41,5 45,1 48,8 52,5 56,1 59,8 63,4 67,1 70,8

835 16,5 20,3 24,1 28,0 31,8 35,6 39,4 43,2 47,0 50,8 54,6 58,4 62,2 66,1 69,9 73,7

865 17,2 21,1 25,1 29,1 33,0 37,0 40,9 44,9 48,9 52,8 56,8 60,7 64,7 68,7 72,6 76,6

895 17,8 22,0 26,1 30,2 34,3 38,4 42,5 46,6 50,7 54,8 58,9 63,1 67,2 71,3 75,4 79,5

925 18,5 22,8 27,0 31,3 35,6 39,8 44,1 48,3 52,6 56,9 61,1 65,4 69,6 73,9 78,2 82,4

955 19,2 23,6 28,0 32,4 36,8 41,2 45,6 50,0 54,5 58,9 63,3 67,7 72,1 76,5 80,9 85,3

985 19,8 24,4 29,0 33,5 38,1 42,6 47,2 51,8 56,3 60,9 65,4 70,0 74,6 79,1 83,7 88,2

1015 20,5 25,2 29,9 34,6 39,3 44,0 48,8 53,5 58,2 62,9 67,6 72,3 77,0 81,7 86,4 91,1

1045 21,2 26,0 30,9 35,7 40,6 45,5 50,3 55,2 60,0 64,9 69,8 74,6 79,5 84,3 89,2 94,1

1075 21,8 26,8 31,8 36,9 41,9 46,9 51,9 56,9 61,9 66,9 71,9 76,9 81,9 87,0 92,0 97,0

1105 22,5 27,6 32,8 38,0 43,1 48,3 53,4 58,6 63,8 68,9 74,1 79,2 84,4 89,6 94,7 99,9

order samPle

Kamouflage 1V 60 600 385 VD48 FDCB KGD

61 2 3 4 5

1 Type of shutter

2 Width of damper

3 Height of damper

4 Type of magnet

5 Option:bipolarswitches

6 KGD: Protection bars

Iftheproductismanipulatedinanyotherwaythandescribedinthismanual,Rf-Technologieswilldeclineanyresponsibility and the guarantee will immediately expire

Page 12: Kamouflage - Smoke Control Dampers€¦ · ProduCt Presentation What makes the Kamouflage smoke control damper truly unique is its ability to be disguised within the compartment wall

12

Kamouflage V12-A11/2012EN 12101-8 Smoke Control Damper

DECLAR

ATION OF PERFORM

ANCE

 Ka

mou

flage

 CE

_DoP

_Rf‐t_V

12_EN

 B‐08

/201

3  

1. Uniqu

e iden

tification code

 of the

 produ

ct‐type: 

Smoke evacuatio

n shutter

2. Iden

tification of th

e constructio

n prod

uct:

Kamou

flage

3. Intend

ed use(s) o

f the

 con

struction prod

uct: 

Smoke evacuatio

n shutter to be

 used in sm

oke control systems, in

 multi‐compartmen

t app

lications at fire

 tempe

ratures, or in sin

gle‐compartmen

t app

lications. 

4. Nam

e and contact a

ddress of the

 manufacturer: 

Rf‐Techn

ologies N

V, Lange Ambachtstraat 4

0, B‐986

0 Oosterzele

5. System of assessm

ent a

nd verificatio

n of con

stancy of 

performance of the

 con

struction prod

uct: 

System

 1

6. In

 case of th

e de

claration of perform

ance con

cerning a 

constructio

n prod

uct covered

 by a harm

onised

 stand

ard: 

Notified

 factory prod

uctio

n control certification bo

dy Efectis with

 iden

tification nu

mbe

r 181

2 pe

rformed

 the de

term

ination of

the prod

uct type on

 the basis

 of type testing 

(includ

ing sampling), the

 initial inspectio

n of th

e manufacturin

g plant a

nd of factory produ

ction control and

 con

tinuo

us su

rveillance, assessm

ent a

nd evaluation of factory 

prod

uctio

n control und

er sy

stem

 1 and

 issued

 the certificate of con

stancy of p

erform

ance (1

812_CP

R_10

43) 

7. Declared pe

rformance according

 to EN 121

01‐8: 

(Fire

 resistance according to EN 136

6‐10

 and

 classificatio

ns according

 to EN 135

01‐4)

 

Essential cha

racteristic

s Pe

rforman

ce 

Harmonised standard EN 12101‐8 :2011 

Range 

Type

 Wall

Classification

300x38

5 mm 

≤ Kamou

flage 1V ≤ 

700x10

75 m

  350x38

5 mm 

≤ Kamou

flage 2V ≤ 

1100x110

5 mm 

Shaft 

Kamou

flage

 60

Prom

atect L50

0 ≥ 30

 mm 

EI 60 (v

ed i

o) S 150

0 AA

 multi 

Geo

flam ≥ 30 mm 

EI 60 (v

ed i

o) S 150

0 AA

 multi 

Kamou

flage

 120

Prom

atect L50

0 ≥ 50

 mm 

EI 120

 (ved i

o) S 150

0 AA

 multi 

Geo

flam ≥ 45 mm 

EI 120

 (ved i

o) S 150

0 AA

 multi 

Tecniver ≥ 55m

EI 120

 (ved i

o) S 150

0 AA

 multi 

Type

 of installatio

n: sh

aft‐mou

nted

Approv

ed accessorie

s: Acrylic paint on the leaf and

 synthe

tic paint on the fram

e on

 the sid

e no

t exposed

 to fire; G

lued

 wall paper on the sid

e no

t exposed

 to fire; K

AP or K

GC mou

nting fram

e with

 or w

ithou

t mastic

 seal; A

ntifa

ll de

vice ty

pe KGD 

Nom

inal activation cond

ition

s/sensitivity:

 Pass ‐ automatic activation 

Respon

se delay (respo

nse tim

e):

Pass ‐ automatic activation 

Ope

ratio

nal reliability: 

 30

0 cycles (n

o load

)  

Durab

ility of respo

nse de

lay: 

 Pass 

Durab

ility of o

peratio

nal reliability:

 Pass 

Free

 air pa

ssage (dm²): 

 1V

: [((W

‐73)*(H‐73

))‐30

00]/10

000; 2V: [((W

‐73)*(H‐73

))‐30

00‐(5

6.2*(H‐73))]/10

000 

(W=w

idth; H

=height) 

High op

erationa

l tem

perature (H

OT 40

0/30

): 

NPD

 (no pe

rforman

ce determined

8. The

 perform

ance of the

 produ

ct iden

tified in points 1

 and

 2 is in

 con

form

ity with

 the de

clared

 perform

ance in

 point 7. 

This de

claration of perform

ance is issued

 und

er th

e sole re

spon

sibility of the

 manufacturer ide

ntified

 in point 4. 

Signed

 for a

nd on be

half of th

e manufacturer b

y: 

 Oosterzele, 01/08

/201

3 To

m Van

 Leu

ven, Techn

ical M

anager