KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD
PUR20-044-ITT
Prince of Wales Public School New Elevator & Renovation
ADDENDUM NO. 3 This addendum shall form an integral part of the bid documents for the above noted Tender and shall be read in conjunction therewith. This addendum shall, however, take precedence over all requirements as it pertains to the particular and specific items noted below.
Part 1 – Answers to Questions Question 1: New Roller shades are noted on the drawings; however, they are not in the
specifications. Please confirm if they are required. Answer 1: See specification 12 24 00 “Window Shades” in Addendum No 1, prepared by AECOM
Canada Architects Ltd, attached. Question 2: Coat and Hat Racks are in the specifications; however, the drawings show individual
hooks. Please confirm which option to use. Answer 2: Use coat hooks as specified. Delete specification section 10 91 13 “Miscellaneous
Specialties”. Question 3: Detail 13/A601 shows 3 custom cushions. Can an allowance be added as there are no
specifications on the cushions? Answer 3: The Cash Allowance value in the Bidding System has been increased from $3,000.00 to
$4,500.00 to allow for the cushions. Question 4: Detail 1/A206 shows a painted detail on the floor. Our paint contractor is suggesting an
epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete &
Garage, self-priming, 1-part Epoxy, Statin finish, or approved equal. Install as per manufacturers recommendations. Allow for 2 colours.
Question 5: For LULA elevator, it appears there is an intermediate stop but I am not sure what you
would call the level. The drawings show ground level, first floor, and second floor but there is an intermediate stop between the ground level and the first floor on the opposite side of the cab. Is there a basement level, ground level, 1st and 2nd floor? Could you clarify as the specification just shows the maximum number of stops and it doesn’t tell you the number of stops and the drawings do not identify the intermediate stop.
Answer 5: There are 3 stops (floors) at the front door and 1 stop (exterior grade) at the rear door.
Total 4 stops. See Elevator Section 1/A205. Question 6: If the tender closing is going to proceed without a site meeting, can you make a cash
allowance for refinishing of millwork and hardwood floors? Answer 6: The cash allowance will not be increased to include the work described above. Review
Room Finish Schedule and notes #1 thru #9 below the schedule.
Page 2 of 2
Question 7: DWG E301 Detail 1 Luminaire Schedule: Can we please provide equals to manufacturers listed here? As not all the manufacturers are the same.
Answer 7: Equivalent products will be subject to consultant review and approval. Question 8: DWG E204 Detail 3: Please provide manufacturer and part number for exit signs. Answer 8: T&B Emergilite ES series, ES-2-W-U-VR (for double face) or ES-1-W-U-VR (for single
face) or approved equals. Question 9: Detail 1/A202 RCP- In the classrooms can you clarify how the outside of C1 are being
terminated, as they are being dropped below the plaster ceilings. Answer 9: Install extruded aluminum trim around perimeter of suspended ceilings in the four
classrooms. 4” high Compasso Standard, colour ‘white’ by USG-CGC. Question 10: Please provide a floor tile for pricing. Answer 10: Floor tile to be equal to Olympia Spectra series. Allow for two colours. Question 11: The following elevator company is asking to be added to the tender specification:
[email protected] Joe Leone EDM-A B&L Elevator Services Inc. O - 705-325-0330 or 833-325-0330 C - 705-817-7022 www.bl-elevator.ca
Answer 11: See Addendum No 1, prepared by AECOM Canada Architects Ltd, attached. Question 12: Please clarify door and drawer front style and finish. Elevations show shaker style. Spec
2.2.4.8 notes doors to be veneer faced 19mm MDF. Typically, one-piece MDF Shaker doors have a paint finish, but photos of existing cabinets show wood finish with solid wood stile and rails.
Answer 12: Cabinet doors to be MDF, Shaker style, painted. Question 13: Typical elevation notes are to “sand and paint wood base.” Should this be “sand and
lacquer” as per existing? Answer 13: See Room Finish Schedule Notes: Note #4 for Classrooms, Note #7 for Resource Room
#110. See detail 16, 17, 18, 19 & 20/A601 for finishing existing trim in the Classrooms. See detail 21/A610 for new stained baseboard in Resource Room #110.
Part 2 – Additional Information
Add: Addendum No. 1, prepared by AECOM Canada Architects Ltd, (9 pages)
END OF ADDENDUM NO. 3
AECOM Canada Architects Ltd.
300 Water Street 905 215 1400 tel
Whitby, ON, Canada L1N 9J2 905 668 0221 fax
www.aecom.com
AECOM Addendum No. 1
Project Name: Prince of Wales Public School - New Elevator & Renovation_______________________________________________________
Project No.: KPRDSB Tender No. PUR20-044-ITT (AECOM #60624140)_______________________________________________________
Date: March 24, 2020_______________________________________________________
The following information supplements and/or supersedes the bid documents issued on:
The addendum forms part of the contract documents and is to be read, interpreted and coordinated withall other parts. The cost of all contained herein is to be included in the contract sum. The followingrevisions supersede the information contained in the original drawings and specifications issued for theabove – named project to the extent referenced and shall become part thereof. Acknowledge receipt ofthis addendum by inserting its number and date on the Tender Form. Failure to do so may subject thebidder to disqualification.
General:
1-Operations and Maintenance Manuals: Contractor(s) shall include a dollar value in each progress drawfor manuals and as-built drawings. (General - $3,000) (Mechanical - $2,500) (Electrical - $2,500)
Drawings:
Drawing A201, “DEMOLITION FLOOR PLANS”Demolition note D10, turn salvaged coat hooks over to the school board.
Drawing A203 “NEW LAYOUT FLOOR PLANS”Add construction note #C26. Remove existing tackboard and make good existing plaster wall inHall #15A. Paint existing wall from Resource Room #110 window and over to new opening at Hall#110A (6.5m wide by 4.0m high). Install existing salvaged lockers. See image below.
AECOM Canada Architects Ltd.
300 Water Street 905 215 1400 tel
Whitby, ON, Canada L1N 9J2 905 668 0221 fax
www.aecom.com
AECOM Addendum No. 1
Drawing A205, “ELEVATOR – PLANS and SECTIONS” 4/A205.Install wall type W5 at infill location next to Classroom No.11. Install baseboard on ClassroomNo11 side of wall similar to detail 21/A601. Paint wall infill in Classroom No.11.
Drawing A604, “ROOM ELEVATIONS” Detail 5/A604. “GUARDRAIL ELEVATION”.Tempered glazing to be 13mm thick. Install stainless steel U-channels to support glazing.
Drawing M-103, “NEW LAYOUT – HVAC”.Provide access doors for control valves of the wall fins installed behind the bookshelves inResource Room #110 (4 required). The access door shall be equivalent to ACUDOR universalFlush model # UF-5000, size 24 X 24. Provide all necessary hardware to install the access doors.Co-ordinate the exact locations of control valves on site.
Drawing S104, “CANOPY PLANS AND DETAILS”New drawing issued.
Drawings E102, E203, & E304.Drawings re-issued.
Specifications:
12 24 00 “Window Shades”.New specification section issued.
14 20 00 “LULA Elevator”, 1.2.1.2, Alternate Manufacturers.Include manufacturer(s) Cambridge Elevating and Niagara Belco.
End of AECOM Addendum No.1
New Elevator & Renovation at Prince of Wales Public School Section 12 24 00Kawartha Pine Ridge District School Board WINDOW SHADESProject No. 60624140 PAGE 1
AECOM 2020-03-04
General
1.1 RELATED WORK SPECIFIED ELSEWHERE
.1 Steel stud framing.
.2 Acoustic Ceilings
1.2 WORK INCLUDED
.1 Supply and install manually operated roller shades at all windows, except as noted on drawings.Provide all components as needed for a complete and proper installation.
.2 Remove and dispose of all existing window coverings and hardware.
1.3 QUALITY ASSURANCE
.1 Use adequate numbers of skilled workers who are thoroughly trained and experienced in thenecessary crafts and who are completely familiar with the specific requirements and methodsneeded for proper performance of the work in this Section.
1.4 SUBMITTALS
.1 Submit list of proposed materials.
.2 Submit manufacturer=s specifications, product data, and other data needed to prove compliance
with the specified requirements.
.3 Shop drawings shall include sufficient detail to show fabrication, installation, anchorage, electricaland control wiring, and interface of work of this section with the work of adjacent trades. Indicatefield measurements on shop drawings.
.4 Manufacturer=s recommended installation procedure. Construct one complete light proof window
shade with attachments and accessories for approval by Owner which, when approved by theOwner will become the basis for accepting or rejecting actual installation procedures used on thework.
.5 Fabric to be flame retardant. Provide proof of compliance with CAN/ULC S109, Flame Tests ofFlame-Resistant Fabrics and Films, small scale vertical burn requirements test.
.6 Submit fabric samples for colour selection by the Owner.
.7 Provide printed operation and maintenance instructions to Owner.
1.5 WARRANTY
.1 Provide a warranty for an extended period of three (3) years from date of completion againstmechanical and fabric failure (including fabric fading) under normal conditions.
Products
2.1 WINDOW SHADES
.1 Manual shades shall be roller blind system with smooth operation chain and sprocket roller asmanufactured by Shade-O-Matic Products Ltd., or pre tender approved equivalent.
.2 Provide system with easy lift (chain operated) action with infinite positioning. Left or right handoperation to be determined on site.
.3 Provide fully factory assembled shade unit consisting of two end brackets, shade tube, fascia(where specified), hem bar, drive chain and specified fabric.
.1 Mounting type: Wall mounted above frame opening, or on block opening inside butnever on window frame.
.2 Removal must not require the disassembly of the shade units.
New Elevator & Renovation at Prince of Wales Public School Section 12 24 00Kawartha Pine Ridge District School Board WINDOW SHADESProject No. 60624140 PAGE 2
AECOM 2020-03-04
.4 End Brackets
.1 70 x 83mm end bracket shall be made of 16 gauge enameled galvanized steel capable ofbeing mounted in any position.
.2 Clutch and bracket shall have multi-channel chain control and guide insert.
.3 The idle-end bracket shall have a means of leveling the shade after installation, the screwshall provide infinite leveling degrees.
.4 Bracket colour shall coordinate with fabric colour.
.5 Shade Tube
.1 38mm extruded anodized aluminum shade tube shall be 1.52mm thick with three internalcontinuous fins 4.82mm high, for strength and drive capabilities when attached to thenylon sprocket.
.2 The fins shall be spaced 120 degrees apart.
.3 The tube shall incorporate an integral channel for affixing the shade band to the tube viaa spine.
.6 Fascia (Optional as noted on Drawings)
.1 Extruded anodized aluminum fascia shall be 1.7mm thick, squared design, to coverunderside of assembly.
.2 Finish shall be anodized aluminum or painted baked enamel.
.7 Drive Assembly
.1 Shall be factory set for size and travel of shades.
.2 Capable of being field adjusted from the exterior of the shade unit without having todisassemble the hardware.
.3 Provide with built-in shock absorber system to prevent chain breakage, under normalusage conditions.
.8 Drive Chain
.1 No. 10 stainless steel bead chain formed in a continuous loop. Chain shall have a 90#test strength.
.9 Exterior Hembar
.1 Extruded aluminum, clear anodized, with plastic end finials. Hembar to be fully enclosedin hem and non removable.
2.2 OPAQUE FABRIC (CLASSROOMS)
.1 Sun block / duplex room darkening 12 oz fibreglass
.2 Seams, if required, shall be equally spaced vertically to form material in equal widths. Location asper drawings.
.3 Fabric shall hang flat, without buckling or distortion. Edge, when trimmed, shall hang straight,without raveling. An unguided shade cloth shall roll true and straight, without shifting sidewaysmore than 3mm in either direction due to warp distortion or weave design.
.4 Fabric shall be woven vinyl coated polyester, dimensionally stable and flame retardant, inaccordance with CAN/ULC S-109 small scale vertical burn test.
.5 Owner to choose colour when shop drawings are submitted. Colours will be selected by theOwner from the manufacturers standard collection. A minimum of 9 colour choices must beoffered.
New Elevator & Renovation at Prince of Wales Public School Section 12 24 00Kawartha Pine Ridge District School Board WINDOW SHADESProject No. 60624140 PAGE 3
AECOM 2020-03-04
2.3 SUN SHADING FABRIC (OFFICES AND STAFF ROOMS)
.1 5% open weave flame retardant, 25% polyester / 75% vinyl on polyester.
.2 Seams, if required, shall be equally spaced vertically to form material in equal widths. Location asper drawings.
.3 Fabric shall hang flat, without buckling or distortion. Edge, when trimmed, shall hang straight,without raveling. An unguided shade cloth shall roll true and straight, without shifting sidewaysmore than 3mm in either direction due to warp distortion or weave design.
.4 Fabric shall be woven vinyl coated polyester, dimensionally stable and flame retardant, inaccordance with CAN/ULC S-109 small scale vertical burn test.
.5 Owner to choose colour when shop drawings are submitted. Colours will be selected by theOwner from the manufacturers standard collection. A minimum of 9 colour choices must beoffered. (Colour to match Jackson shear weave Pebblestone)
2.4 BLACK OUT SHADES (DRAMA ROOMS AND THEATERS OR AS NOTED)
.1 Light proof shades to be 100% opaque blackout flame retardant.
.2 Seams, if required, shall be equally spaced vertically to form material in equal widths. Location asper drawings.
.3 Fabric shall hang flat, without buckling or distortion. Edge, when trimmed, shall hang straight,without raveling. An unguided shade cloth shall roll true and straight, without shifting sidewaysmore than 3mm in either direction due to warp distortion or weave design.
.4 Fabric shall be woven vinyl coated polyester, dimensionally stable and flame retardant, inaccordance with CAN/ULC S-109 small scale vertical burn test.
.5 Owner to choose colour when shop drawings are submitted. 2 Colours will be selected by theOwner from the manufacturer=s standard collection. A minimum of 9 colour choices must be
offered.
Execution
3.1 EXISTING CONDITIONS
.1 Examine the areas and conditions under which the work of this section will be performed. Correctconditions detrimental to timely and proper completion of the work.
.2 Remove and dispose of all existing window coverings and hardware.
3.2 INSTALLATION
.1 Co-ordinate as required with the Owner as to hours of work.
.2 Install the work of this section in strict accordance with approved Shop Drawings, pertinentrequirements of Government Agencies having jurisdiction, and the manufacturer=s recommended
installation procedures as approved by the Owner, anchoring all components firmly into positionfor long life.
.3 Install the work plumb, level and in proper operating condition.
.4 Upon completion of the installation, put each operating component through at least five completecycles, adjust as required to achieve optimum operation.
.5 Touch up scratches and blemishes to any damaged existing finishes.
END OF SECTION
HSS102x76x4.8
HSS102x76x4.8
HS
S8
9x8
9x4.8
HS
S8
9x8
9x4.8
HS
S8
9x8
9x4.8
4
S104
2
S104
3
S104
38 DP x 0.91 THK
PREFINISHED ROOFING
950 950 150
19
00
30
51
50
HSS102x102x6.4
HSS102x102x6.4
Mr = 15 kN MIN.
Mr = 15 kN MIN.
HS
S8
9x8
9x4.8
HS
S8
9x8
9x4.8
4
S104
5
S104
Mr = 15 kN MIN.
HSS102x76x4.8
5
S104
20
02
20
01
20
0
MIN
.
90
0
950 150950
38 DP x 0.91 THK
GALVANIZED STEEL DECK
HSS102x76x4.8
HSS89x89x4.8
HSS102x102x6.4
EXIST. MULTI-WYTHE
BRICK WALL
150 GRANULAR 'A'
COMPACTED TO 98%
S.P.M.D.D., OR AS
REQUIRED BY
GEOTECHNICAL ENGINEER
PROVIDE 25 THK GROUT BASE
(TYP.)
300 DIA. 25 MPa CONCRETE
PIER IN SONOTUBE
POUR 300x300 BOX ABOVE
GRADE
6
S104TYP.
20
02
20
09
00
4501900
12
00
MIN
.
EXIST. MULTI-WYTHE
BRICK WALL
38 DP x 0.91 THK
PREFINISHED ROOFING
HSS102x76x4.8
PROVIDE CLOSURE TRIM
AT PERIMETER PER
ARCHITECTURAL
DRAWINGS
HSS102x102x6.4
300 DIA. 25 MPa CONCRETE
PIER IN SONOTUBE
150 GRANULAR 'A'
COMPACTED TO 98%
S.P.M.D.D., OR AS
REQUIRED BY
GEOTECHNICAL ENGINEER
PROVIDE 25 THK GROUT BASE
(TYP.)
POUR 300x300 BOX ABOVE
GRADE
20320335 35
75
75
19Ø THREADED ROD C/W
HILTI HY-70 EPOXY AND
SLEEVE, MIN EMBED = 330
(TYP. FOR 2)
PL12x475X150
HSS102x76x4.8
6
70
70
30
30
70 70 3030
16Ø ANCHOR RODS, MIN.
EMBED = 250
PL9.5x200x200
HSS102x102x6.4
6
14026635 35
65
65
19Ø THREADED ROD C/W
HILTI HY-70 EPOXY AND
SLEEVE, MIN EMBED = 330
(TYP. FOR 2)
PL12x475X150
HSS102x76x4.8
6
Printed on ___% Post-ConsumerRecycled Content Paper
KEY PLAN
REGISTRATION
CLIENT
Kawartha Pine Ridge
District School Board1994 Fisher Drive, Peterborough, Ontario
705.742.9773 tel 705.742.7801 fax
www.kprdsb.ca
PROJECT
New Elevator & Renovation
Prince of Wales
Public School1211 Monaghan Road. S. Peterborough, Ontario
PROJECT NUMBER
60624140
CONSULTANT
AECOM Canada Ltd.
300 Water Street
Whitby, Ontario, Canada L1N 9J2
905.215.1400 tel 905.668.0221 faxwww.aecom.com
NORTH
CO
NS
TRU
CTIO
NN
OR
TH
1
3
0.50
10 2
32
4 5 10'
4m
BARSCALE 1=50
I/R DATE DESCRIPTION
ISSUE/REVISION
1 2020-03-24 AECOM ADDENDUM #1
SHEET TITLE
CANOPY PLANS AND DETAILS
SHEET NUMBER
S10420
20
-03
-24
__
__
__
___
__
___
_W
AL
ES
EL
EV
AT
OR
SH
AF
T\C
AD
\60
624
14
0-S
.DW
G
Scale: 1:20
CANOPY PLAN1S104
Scale: 1:20
CANOPY SECTION2S104 Scale: 1:20
CANOPY ELEVATION3S104
Scale: 1:5
DETAIL4S104
Scale: 1:5
DETAIL6S104
CANOPY DESIGN LOADS
DEAD LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.10 kPa
SNOW LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.59 kPa
WIND UPLIFT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.26 kPa
1. REFER TO DRAWING S101 FOR STRUCTURAL NOTES.
2. VERIFY EXISTING WALL CONSTRUCTION PRIOR TO INSTALLING
ANCHORS. NOTIFY ENGINEER IF ANY DISCREPANCY EXISTS
BETWEEN DRAWINGS AND EXISTING CONSTRUCTION.
3. ALL EXTERIOR STEEL TO BE HOT DIP GALVANIZED TO CSA G164.
4. FIX DECK TO HSS MEMBERS WITH PUDDLE WELDS AT 300 O/C.
5. PROVIDE MOMENT CONNECTIONS WHERE INDICATED.
6. PROVIDE SHOP DRAWINGS FOR CONSULTANT REVIEW PRIOR TO
FABRICATION. SHOP DRAWINGS TO BE STAMPED BY ENGINEER
CERTIFIED IN THE PROVINCE OF ONTARIO.
7. DRAWING TO BE READ IN CONJUNCTION WITH ARCHITECTURAL
DRAWINGS. NOTIFY CONSULTANT IF ANY DISCREPANCY EXISTS.
NOTES:
Scale: 1:5
DETAIL5S104
B06H
HALL
B12
ELECT.
PANEL 'DP1'
'PANEL #13'
FIRE CONTROL
PANEL (EXISTING
PANEL TO BE
REMOVED)
Printed on ___% Post-Consumer
Recycled Content Paper
This draw
ing has been prepared for the use of A
EC
OM
's client and m
ay not be used, reproduced or relied upon by third parties, except as agreed by A
EC
OM
and its client, as required by law
or for use by governm
ental review
ing agencies. A
EC
OM
accepts no responsibility, and denies any liability w
hatsoever, to any party that m
odifies this draw
ing w
ithout A
EC
OM
's express w
ritten consent. D
o not scale this docum
ent. A
ll m
easurem
ents m
ust be obtained from
stated dim
ensions.
KEY PLAN
REGISTRATION
CLIENT
Kawartha Pine Ridge
District School Board
1994 Fisher Drive, Peterborough, Ontario
705.742.9773 tel 705.742.7801 fax
www.kprdsb.ca
PROJECT
New Elevator & Renovation
Prince of Wales
Public School
1211 Monaghan Road. S. Peterborough, Ontario
PROJECT NUMBER
60624140
AR
CH
D
2
4" x 3
6"
CONSULTANT
AECOM Canada Ltd.
300 Water Street
Whitby, Ontario, Canada L1N 9J2
905.215.1400 tel 905.668.0221 fax
www.aecom.com
N
O
R
T
H
C
O
N
S
T
R
U
C
T
I
O
N
N
O
R
T
H
1
3
0.50
10 2
32
4 5 10
54
15
6 7 8m
20 25'
BARSCALE 1=100
I/R DATE DESCRIPTION
ISSUE/REVISION
1 MAR/04/2020 TENDER AND PERMIT
2 MAR/23/2020 AECOM ADDENDUM NO1
SHEET TITLE
ELECTRICAL
SINGLE LINE DIAGRAM
AND NEW PANEL DETAILS
SHEET NUMBER
E102
La
st sa
ve
d b
y: S
HA
RO
N.L
IN
(2
02
0-0
3-2
4) L
ast P
lo
tte
d: 2
02
0-0
3-2
4P
ro
je
ct M
an
ag
em
en
t In
itia
ls:
De
sig
ne
r:
Ch
ecke
d:
Ap
pro
ve
d:
__
__
__
__
__
__
__
_
File
na
me
: \\C
AW
BY
1F
P0
01
\D
AT
A\P
RO
JE
CT
S\6
06
24
14
0\9
00
-C
AD
_G
IS
\9
10
-C
AD
\2
0-S
HE
ET
S\E
\6
06
24
14
0-S
HT
-E
10
1-E
10
3.D
WG
1200A-3P FRAME C/W
1200A TRIP UNIT
SUPPLY AUTHORITY
METERING CABINET
800A-3P
800A TRIP
RM. B07B
208V, 3PH, 4W, 1200A, EX. SWITCHBOARD 'AA'
................
N.T.S
EX. SINGLE LINE DIAGRAM1
E102
RM. B12
208V, 3PH, 4W, 800A, EX. DISTRIBUTION PANEL 'DP-1'
NEW
PANEL
'13A'
100A-3P
RM. B12
Scale: 1:50
ELECT. RM. B12 LAYOUT2
E102
EX. LOAD
EX.
BREAKERS
N.T.S
NEW PANEL SCHEDULE - '13A'3
E102
PANEL
'13A'
ACCESS CONTROL PANEL
4#3 AWG + GND IN 41 mmC
1. PROVIDE 53mm CONDUIT STUBBED AND CAPPED IN CEILING SPACE FOR FUTURE LOAD.
CONFIRM AND COORDINATE FINAL LOCATION ON SITE WITH TRENT AND CLIENT.
NOTES:
EX
FROM UTILITY
EX
EX
NOT ALL BREAKERS ARE SHOWN.
NEW CIRCUIT BREAKER TYPE AND KAIC RATING TO MATCH EXISTING CIRCUIT BREAKER.
NOTES:
2
2
1.
MASTER CONTROL PANEL
FOR VIDEO INTERCOM
SYSTEM
2
2
2
2
2
T
110
RESOURCE
ROOM
110B
W.R.
110A
HALL
110C
EXISTING
SHAFT
AC-1
ERV-1
AC-5
CCT: 13A-13/15
CCT: 13A-1/3/5
CCT: 13A-13/15
AC-4
CCT: 13A-13/15
AC-3
CCT: 13A-13/15
AC-2
CCT: 13A-13/15
EDH-1
CCT: 13A-7/9/11
EX
EX
RL
RL
EX. 'PANEL
#2 - 38'
EX. 'PANEL
#2 - 38'
EX. 'PANEL
#2 - 38'
EX. 'PANEL
#2 - 36'
EX. 'PANEL
#2 - 36'
EX. 'PANEL
#2 - 39'
EX. 'PANEL
#2 - 42'
EX. 'PANEL
#2 - 40'
EX. 'PANEL
#2 - 41'
EX. 'PANEL
#2 - 37'
EX. 'PANEL
#2 - 37'
EX. 'PANEL
#2 - 37'
EX. 'PANEL
#2 - 39'
IWB
RL
EX. 'PANEL
#2 - 37'
T T T T T
RL RL RL RL
IWB
RL
26
CLASSROOM
25
CLASSROOM
23
STAFF
ROOM
21
CLASSROOM
22
CLASSROOM
30H CORRIDOR
23A
HALL
IWB IWB IWB
RL RL
RL
RL
RL
RL
TR TR
EX. 'PANEL
#1 - 22'
EX. 'PANEL
#1 - 22'
EX. 'PANEL
#1 - 22'
EX. 'PANEL
#1 - 22'
EX. 'PANEL
#1 - 22'
EX. 'PANEL
#1 - 22'
EX. 'PANEL
#1 - 20'
EX. 'PANEL
#1 - 20'
EX. 'PANEL
#1 - 20'
EX. 'PANEL
#1 - 20'
EX. 'PANEL
#1 - 20'
EX. 'PANEL
#1 - 20'
EX. 'PANEL
#1 - 22'
EX. 'PANEL
#1 - 11'
EX. 'PANEL
#1 - 11'
EX. 'PANEL
#1 - 22'
EX. 'PANEL
#1 - 22'
TR TR
EX. 'PANEL
#1 - 12'
EX. 'PANEL
#1 - 12'
TR TR
EX. 'PANEL
#1 - 18'
EX. 'PANEL
#1 - 18'
TR TR
EX. 'PANEL
#1 - 17'
EX. 'PANEL
#1 - 17'
EX. 'PANEL
#1 - 20'
EX. 'PANEL
#1 - 20'
EX. 'PANEL
#1 - 20'
T
TGFI
5-20R
CCT: 13A-8
GFI
5-20R
CCT: 13A-10
WP,GFI
5-15R
CCT: 13A-20
B05
CUST.
B06
HALL
B07
BOILER ROOM
B07B
ELECT. RM.
B07A
B01H CORRIDOR
B06H HALL
B12
ELECT.
STORAGE
B06C
HALL
B06D
STORAGE
B06B
MACHINE
ROOM
B06A
ELEV.
EF-1
CCT: 13A-12
FFH-1
CCT: 13A-14
CCT: 13A-16
FOR
SECURITY
CCT: 13A-18
CCT: 13A-18CCT:
13A-18
F
F
ACCU-1ACCU-1
CCT: 13A-2/4
WP,GFI
5-20R
CCT: 13A-6
Printed on ___% Post-Consumer
Recycled Content Paper
This draw
ing has been prepared for the use of A
EC
OM
's client and m
ay not be used, reproduced or relied upon by third parties, except as agreed by A
EC
OM
and its client, as required by law
or for use by governm
ental review
ing agencies. A
EC
OM
accepts no responsibility, and denies any liability w
hatsoever, to any party that m
odifies this draw
ing w
ithout A
EC
OM
's express w
ritten consent. D
o not scale this docum
ent. A
ll m
easurem
ents m
ust be obtained from
stated dim
ensions.
KEY PLAN
REGISTRATION
CLIENT
Kawartha Pine Ridge
District School Board
1994 Fisher Drive, Peterborough, Ontario
705.742.9773 tel 705.742.7801 fax
www.kprdsb.ca
PROJECT
New Elevator & Renovation
Prince of Wales
Public School
1211 Monaghan Road. S. Peterborough, Ontario
PROJECT NUMBER
60624140
AR
CH
D
2
4" x 3
6"
CONSULTANT
AECOM Canada Ltd.
300 Water Street
Whitby, Ontario, Canada L1N 9J2
905.215.1400 tel 905.668.0221 fax
www.aecom.com
I/R DATE DESCRIPTION
ISSUE/REVISION
1 MAR/04/2020 TENDER AND PERMIT
2 MAR/23/2020 AECOM ADDENDUM NO1
SHEET TITLE
ELECTRICAL
POWER AND SYSTEMS
NEW PLAN
SHEET NUMBER
E203
La
st sa
ve
d b
y: S
HA
RO
N.L
IN
(2
02
0-0
3-2
3) L
ast P
lo
tte
d: 2
02
0-0
3-2
4P
ro
je
ct M
an
ag
em
en
t In
itia
ls:
De
sig
ne
r:
Ch
ecke
d:
Ap
pro
ve
d:
__
__
__
__
__
__
__
_
File
na
me
: \\C
AW
BY
1F
P0
01
\D
AT
A\P
RO
JE
CT
S\6
06
24
14
0\9
00
-C
AD
_G
IS
\9
10
-C
AD
\2
0-S
HE
ET
S\E
\6
06
24
14
0-S
HT
-E
20
3-P
OW
ER
&
S
YS
TE
MS
- N
EW
.D
WG
N
O
R
T
H
C
O
N
S
T
R
U
C
T
I
O
N
N
O
R
T
H
Scale: 1:100
FIRST FLOOR PLAN - POWER & SYSTEMS NEW LAYOUT2
E203
1
3
0.50
10 2
32
4 5 10
54
15
6 7 8m
20 25'
BARSCALE 1=100
Scale: 1:100
SECOND FLOOR PLAN - POWER & SYSTEMS NEW LAYOUT1
E203
Scale: 1:100
GROUND FLOOR PLAN - POWER & SYSTEMS NEW LAYOUT3
E203
3
4
5
5
3
10
8
7
9
6
5
17
1 2
18
1 2
1 2 1 2
5
5
5
19
19 19
Scale: 1:200
ROOF PLAN - POWER & SYSTEMS NEW LAYOUT4
E203
MODULAR SURFACE MOUNTED CONTROL PANEL TO BE INTERSPEC SYSTEMS AND CLASSMATE
CLASSROOM CONTROL PANEL TYPE. REFER TO 1/E302 FOR FURTHER INFORMATION ON INSTALLATION
LAYOUT.
MODULAR CONTROL PANEL RECEPTACLE TO BE CIRCUITED WITH THE CONVENIENCE RECEPTACLES
(NON-IWB CIRCUIT).
SUPPLY AND INSTALL HEAT DETECTOR AND 5-20R GFI RECEPTACLE IN PIT OF ELEVATOR. GFI
RECEPTACLE SHALL BE MOUNTED 100mm (4") BELOW ELEVATOR GROUND FLOOR LANDING OR AS
OTHERWISE DIRECTED BY ELEVATOR INSTALLER. TIE HEAT DETECTOR AND SMOKE DETECTOR AT THE
TOP OF SHAFT INTO NEW FIRE ALARM PANEL.
SMOKE DETECTOR MOUNTED AT THE TOP OF THE ELEVATOR SHAFT. TIE INTO ELEVATOR RECALL AS
PER CSA B44.
FOR ELEVATOR RECALL AS PER CSA B44.
SUPPLY AND INSTALL SUITABLE (3) SLEEVES POSITIONED AS PER ELEVATOR MANUFACTURER
REQUIREMENTS. SLEEVES SHALL BE AT LEAST MIN. 5". THEY SHALL BE PROVIDED BELOW THE
MACHINE ROOM FLOOR FOR ELECTRICAL WIRING. COORDINATE WITH ELEVATOR MANUFACTURER FOR
FINAL SLEEVE SIZING.
SUPPLY AND INSTALL A 1P-30A SN 125V EEMAC 1 LOCKABLE SAFETY DISCONNECT SWITCH WITH ONE
(1) 15A PLUG FUSE. TIE INTO NEW CIRCUIT NOTED. FINAL LOCATION TO BE COORDINATED ON SITE.
SUPPLY AND INSTALL LOCKABLE 208V/30A FUSED DISCONNECT SWITCH FED FROM PANEL 13A-19/21/23
WITH AUXILIARY CONTACT TO ELEVATOR CONTROL PANEL. COORDINATE WITH SUPPLIER FOR TYPE OF
FUSE. POSITION DISCONNECT AS PER ELEVATOR. MANUFACTURER RECOMMENDATIONS. FINAL
LOCATION TO BE COORDINATED ON SITE.
PROVIDE NEW 20A GFI RECEPTACLE IN ELEVATOR MACHINE ROOM COMPLETE WITH NEW DEDICATED
FEED FROM CIRCUIT NOTED.
PROVIDE NEW CAT 6 PHONE LINE FROM ELEVATOR TO MACHINE ROOM, AND ELEVATOR CONTROL
PANEL , MACHINE ROOM TO MAIN PHONE PANEL IN ELECTRICAL ROOM. COORDINATE WITH ELEVATOR
MANUFACTURER AND OWNER'S APPROVED SECURITY MONITORING COMPANY. PROVIDE 21mm
CONDUIT FROM ELECTRICAL ROOM TO MACHINE ROOM WITH PULL STRING.
PROVIDE SMOKE DETECTORS IN EACH ELEVATOR LOBBY/LANDING OUTSIDE ELEVATOR PER ULC 524,
OBC AND CSA B44.
PROVIDE NORMALLY CLOSED CONTACTS REPRESENTING SMOKE DETECTORS FOR PIT, LANDINGS,
MACHINE ROOM, AND WIRE IT AS REQUIRED AS PER CSA B44 AND ULC 524.
THE SMOKE DETECTOR LOCATED IN THE ELEVATOR MACHINE ROOM SHALL BE WIRED TO ACTIVATE
SAME NORMALLY CLOSED CONTACT AS THE SMOKE DETECTOR AT THE DESIGNATED LANDINGS.
COORDINATE ALL REQUIREMENTS WITH ELEVATOR CONTRACTOR.
CONTRACTOR IS RESPONSIBLE FOR CONFIRMING ALL ELEVATOR POWER AND FIRE ALARM
REQUIREMENTS WITH ELEVATOR SHOP DRAWINGS AND ELEVATOR MANUFACTURER.
REFER TO FIRE ALARM SCOPE OF WORK FOR ADDITIONAL REQUIREMENTS.
PROVIDE POWER AND DATA OUTLETS AT HIGH LEVEL FOR INTERACTIVE WHITEBOARD. COORDINATE
WITH ARCHITECTURAL ELEVATIONS AND GENERAL CONTRACTOR TO SUIT LOCATION OF INTERACTIVE
WHITEBOARD. REFER TO 2/E302 FOR DETAIL.
CONTRACTOR TO TIE IN CAMERA CALL-IN BUTTON AND ELECTRIC STRIKE TO EXISTING ACCESS
CONTROL PANEL. PROVIDE ROUGH-INS AND CONDUIT FROM SECURITY PANEL TO DOOR FOR
SECURITY CONTROL.
DEDICATED 20A CIRCUIT FOR PHOTOCOPIER AND LAPTOP CHARGING STATIONS. RECEPTACLE SHALL
BE CSA 5-20R TYPE.
ALL DEVICES ARE NEW EXCEPT WHERE NOTED.
CONTRACTOR TO AVOID ANY SURFACE MOUNT ON TO EXTERIOR WALL OF THE BUILDING.
INSTALL RECEPTACLES IN CLASSROOMS ON THE CHAIR RAIL RUNNING ABOVE THE WALL FINS.
TIE IN THE RECEPTACLE TO THE NEAREST EXISTING RECEPTACLE CIRCUIT IN THE SAME ROOM.
REFER TO ELECTRICAL GENERAL NOTE 12 ON DRAWING E100 FOR WIRING RUNS.
EXISTING DEVICE RELOCATED TO NEW LOCATION. EXTEND/CUT BACK WIRING AS REQUIRED.
REFER TO DRAWING 2/E301 FOR DISCONNECT SWITCH REQUIREMENT.
ALL THE RECEPTACLE AND DATA OUTLET TO BE FED FROM CEILING SPACE FOR FIRST FLOOR AND
GROUND FLOOR, AND ATTIC SPACE FOR THIRD FLOOR.
EXISTING 1-DOOR VIDEO INTERCOM SYSTEM TO BE REPLACED. CONTRACTOR SHALL COORDINATE
REMOVALS WITH TRENT SECURITY INCLUDING BUT NOT LIMITED TO WIRING, ACCESSORIES, ETC.
CONDUIT MAY BE REUSED IF IN GOOD CONDITION. PROVIDE AND INSTALL NEW 2-DOOR VIDEO
INTERCOM SYSTEM TO MATCH AIPHONE JO SERIES COMPLETE WITH DOOR ADAPTER, ELECTRIC
STRIKE (BY OTHERS), MASTER STATION, POWER SUPPLIES AND TWO DESKTOP
MONITOR/WORKSTATIONS. WORK TO BE DONE BY TRENT SECURITY (705.748.2001) UNDER DIV. 26.
CONFIRM DOOR LOCATIONS WITH ARCHITECTURAL DRAWINGS. PROPOSED LOCATIONS AT MAIN
ENTRANCE LOBBY AND HALL B06C. GENERAL CONTRACTOR TO CARRY SERVICES OF TRENT SECURITY
AND ALL ASSOCIATED COSTS TO PROVIDE THESE SERVICES INCLUDING BUT NOT LIMITED TO WIRING,
CONDUIT, ACCESSORIES TO FACILITATE A COMPLETE VIDEO INTERCOM SYSTEM INSTALLATION.
CONFIRM FINAL LOCATION OF EQUIPMENT ON SITE WITH OWNER AND TRENT.
NOTES:
1
2
3
4
5
6
7
8
9
10
11.
12.
13.
14.
15.
16.
17
18
17 17 17
20.
21
21
22
23
22(TYP.)
23
19
24.
17
25
25(TYP.)
25(TYP.)
26.
27.
25
25(TYP.)
22
2
2
2
2
22
22
2
2
28.
2
2
I/R DATE DESCRIPTION
ISSUE/REVISION
1 MAR/04/2020 TENDER AND PERMIT
2 MAR/23/2020 AECOM ADDENDUM NO1
SHEET TITLE
ELECTRICAL
SPECIFICATIONS
1 OF 2
SHEET NUMBER
E304
La
st sa
ve
d b
y: S
HA
RO
N.L
IN
(2
02
0-0
3-2
4) L
ast P
lo
tte
d: 2
02
0-0
3-2
4
Pro
je
ct M
an
ag
em
en
t In
itia
ls:
De
sig
ne
r:
Ch
ecke
d:
Ap
pro
ve
d:
__
__
__
__
__
__
__
_
File
na
me
: \\C
AW
BY
1F
P0
01
\D
AT
A\P
RO
JE
CT
S\6
06
24
14
0\9
00
-C
AD
_G
IS
\9
10
-C
AD
\2
0-S
HE
ET
S\E
\6
06
24
14
0-S
HT
-E
30
4-E
30
5.D
WG
ELECTRICAL SPECIFICATIONS
1. PART A - GENERAL
1.1. CODES AND STANDARDS
1.1.1. COMPLETE THE INSTALLATION OF THE WORK IN ACCORDANCE WITH
THE LATEST EDITIONS OF THE ONTARIO BUILDING CODE, ONTARIO ELECTRICAL
SAFETY CODE (O.E.S.C.), U.L.C., C.S.A., I.E.E.E., N.E.M.A., N.F.P.A., O.H.S.A. AND
OTHER CODES AS REQUIRED. COMPLY WITH ELECTRICAL AND BUILDING CODE
BULLETINS IN FORCE AT TIME OF BID SUBMISSION. WHILE NOT IDENTIFIED AND
SPECIFIED BY NUMBER IN THIS DIVISION, THEY ARE TO BE CONSIDERED AS
FORMING PART OF RELATED STANDARDS. ALL ELECTRICAL WORK SHALL
COMPLY WITH OWNER'S REQUIREMENTS AND BASE BUILDING STANDARDS.
1.2. EXISTING CONDITIONS
1.2.1. VISIT THE SITE AND EXAMINE THE EXISTING CONDITIONS AFFECTING
THE WORK OF THIS DIVISION. NO CLAIM FOR EXTRA PAYMENT SHALL BE MADE
FOR EXTRA WORK MADE NECESSARY BY CIRCUMSTANCES ENCOUNTERED DUE
TO CONDITIONS WHICH WERE VISIBLE UPON, OR REASONABLY INFERABLE
FROM AN EXAMINATION OF THE SITE PRIOR TO SUBMISSION OF THE CONTRACT
PRICE.
1.3. DEFINITIONS
1.3.1. WHEREVER THE WORDS "PROVIDE" OR "SUPPLY AND INSTALL" ARE
USED, IT SHALL BE UNDERSTOOD TO MEAN "SUPPLY AND INSTALL, INCLUSIVE
OF ALL LABOUR, MATERIALS, INSTALLATION, TESTING, AND CONNECTIONS"
FOR THE ITEM(S) TO WHICH IT REFERENCES.
1.3.2. WHEREVER THE WORDS "EQUAL", "APPROVED", OR "APPROVED
EQUAL" ARE USED, IT SHALL BE UNDERSTOOD TO MEAN "EQUAL", "APPROVED",
OR "APPROVED EQUAL" IN THE OPINION OF THE CONSULTANT ONLY.
1.4. SCOPE OF WORK
1.4.1. REFER TO SECTION 01 11 00 - SUMMARY OF WORK FOR OVERALL
PROJECT REQUIREMENTS.
1.4.2. PROVIDE ALL MATERIALS, EQUIPMENT AND LABOUR FOR A
COMPLETE OPERATIONAL INSTALLATION AS DESIGNATED IN THIS
SPECIFICATION AND AS INDICATED ON THE DRAWINGS EXCEPT WHERE
OTHERWISE NOTED.
1.4.3. THE SCOPE OF WORK FOR THIS DIVISION INCLUDES, BUT IS NOT
LIMITED TO, SUPPLY AND INSTALLATION OF THE FOLLOWING ITEMS:
1.4.3.1. POWER DISTRIBUTION
1.4.3.2. LIGHTING
1.4.3.3. EMERGENCY LIGHTING AND EXIT SIGNAGE
1.4.3.4. FEEDERS AND OVERCURRENT PROTECTION FOR MECHANICAL
EQUIPMENT
1.4.3.5. MOTOR STARTERS FOR MECHANICAL EQUIPMENT
1.4.3.6. FIRE ALARM SYSTEM
1.4.3.7. CABLING PATHWAYS FOR TELECOMMUNICATIONS (VOICE/DATA,
WIRELESS, PA, INTERCOM)
1.5. MATERIALS AND EQUIPMENT
1.5.1. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, C.S.A. CERTIFIED
AND MANUFACTURED TO THE STANDARDS SPECIFIED.
1.5.2. WHERE THERE IS NO ALTERNATIVE TO SUPPLYING EQUIPMENT
WHICH IS NOT C.S.A. CERTIFIED, OBTAIN SPECIAL APPROVAL FROM THE
ELECTRICAL SAFETY AUTHORITY AND CONSULTANT.
1.6. DEMOLITION
1.6.1. REFER TO SECTION 02 41 19 - SELECTIVE DEMOLITION FOR OVERALL
SCOPE RELATED TO THIS ITEM.
1.7. PERMITS AND FEES
1.7.1. THE ELECTRICAL CONTRACTOR SHALL ACT AS THE OWNER'S AGENT
IN ACCORDANCE WITH SECTION 2 OF THE O.E.S.C. AND SHALL IMMEDIATELY
UPON AWARD OF CONTRACT, SUBMIT TO THE LOCAL ELECTRICAL INSPECTION
DEPARTMENT, THE NECESSARY NUMBER OF DOCUMENTS FOR EXAMINATION,
SPECIAL INSPECTION AND APPROVAL, PRIOR TO THE COMMENCEMENT OF THE
WORK, AND PAY ALL COSTS AND ASSOCIATED FEES. IF REQUIRED, PREPARE
ANY ADDITIONAL DRAWINGS/DOCUMENTS REQUIRED BY THE AUTHORITY.
1.7.2. THE CONSULTANT WILL PROVIDE UPON REQUEST, AT THE
CONTRACTOR'S COST, THE REQUIRED QUANTITY OF DRAWINGS.
1.7.3. PROVIDE CERTIFICATES(S) OF ACCEPTANCE FROM THE
AUTHORITIES INSPECTION DEPARTMENT, UPON COMPLETION OF WORK.
1.8. INSURANCE
1.8.1. PROVIDE AND MAINTAIN INSURANCE TO PROTECT THE OWNER AND
TRADES FROM ALL POSSIBLE CLAIMS. SUBMIT WITH BID FOR AN AMOUNT
ACCEPTABLE TO OWNER. ALSO ALL INSURANCE AS NOTED WITHIN
ARCHITECTURAL REQUIREMENTS.
1.9. CONTRACT DOCUMENTS
1.9.1. THE DRAWINGS FOR THE ELECTRICAL WORK ARE DIAGRAMMATIC
ONLY, INTENDED TO CONVEY THE SCOPE OF WORK AND INDICATE THE
GENERAL ARRANGEMENT AND APPROXIMATE SIZE AND LOCATION OF
ELECTRICAL EQUIPMENT. THE DRAWINGS DO NOT INTEND TO SHOW
ARCHITECTURAL, INTERIOR DESIGN, MECHANICAL, STRUCTURAL OR BASE
BUILDING DETAILS. BE RESPONSIBLE FOR A THOROUGH KNOWLEDGE OF SAME
BEFORE PROCEEDING WITH THE WORK.
1.9.2. DO NOT SCALE OR MEASURE ELECTRICAL DRAWINGS, BUT OBTAIN
INFORMATION REGARDING ACCURATE DIMENSIONS FROM THE DIMENSIONS
SHOWN ON THE DRAWINGS, OR BY SITE REQUIREMENTS/CONDITIONS.
1.9.3. ANY DISCREPANCIES BETWEEN DRAWINGS AND/OR SPECIFICATIONS
AND EXISTING CONDITIONS, MUST BE REFERRED TO THE CONSULTANT BEFORE
ANY WORK AFFECTED IS BEGUN.
1.9.4. MAKE, AT NO ADDITIONAL COST, ANY CHANGES OR ADDITIONS TO
MATERIALS AND EQUIPMENT NECESSARY TO ACCOMMODATE STRUCTURAL
CONDITIONS (OFFSETS AROUND BEAMS, COLUMN, ETC.)
1.10. INTENT
IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS THAT THE
CONTRACTOR PROVIDES COMPLETE AND OPERATIONAL SYSTEMS AS
REQUIRED, WHERE DIFFERENCES OCCUR, CONTRACTOR SHALL CONTACT
ENGINEER OF RECORD FOR FURTHER CLARIFICATION.
1.10.1. ANY MISCELLANEOUS ITEMS, HARDWARE, DEVICES, WIRING, ETC.,
NOT SPECIFICALLY DESCRIBED, BUT REQUIRED FOR THE OPERATION OF THE
SYSTEM, MUST BE PROVIDED AND INCLUDED AS PART OF THE CONTRACT
PRICE.
1.11. SHOP DRAWINGS
1.11.1. "SHOP DRAWINGS" SHALL INCLUDE DRAWINGS, DIAGRAMS,
ILLUSTRATIONS, SCHEDULES, PERFORMANCE, CHARTS, BROCHURES, AND
OTHER DATA WHICH ARE TO BE PROVIDED BY CONTRACTOR TO ILLUSTRATE
DETAILS OF WORK UNDER CONTRACT. INDICATE ALL REQUIRED ACCESSORIES
AND ANCHORAGES FOR COMPLETION OF WORK.
1.11.2. SUBMIT SHOP DRAWINGS IN ELECTRONIC FORMAT TO CONSULTANT
FOR REVIEW WITHIN TWO (2) WEEKS OF PROJECT AWARD. CLEARLY IDENTIFY
ANY LONG LEAD ITEMS OR CRITICAL PATH ITEMS. SHOP DRAWINGS SHALL BE
REVIEWED, STAMPED, AND SIGNED BY THE ELECTRICAL CONTRACTOR PRIOR
TO SUBMISSION TO THE CONSULTANT. SHOP DRAWINGS NOT REVIEWED SHALL
BE REJECTED. REVIEW SHALL INCLUDE AT MINIMUM EQUIPMENT
PERFORMANCE, DIMENSIONS, CLEARANCES, COLOURS/FINISHES, ELECTRICAL
REQUIREMENTS INCLUDING VOLTAGES AND RATINGS, AND COORDINATION WITH
EXISTING SITE CONDITIONS.
1.11.3. SUBMIT FOUR (4) COPIES OF SHOP DRAWINGS OF ALL SPECIFIED
EQUIPMENT FOR REVIEW AND RECORDS BEFORE COMMENCEMENT OF WORK.
1.11.4. MAKE CHANGES IN SHOP DRAWINGS AS OWNER OR CONSULTANT
MAY REQUIRE. CHANGES MADE TO THE SHOP DRAWINGS BY THE CONSULTANT
SHALL NOT AFFECT THE CONTRACT PRICE.
1.10 RECORD DRAWINGS
1.11.1. KEEP A RECORD SET OF DRAWINGS ON THE SITE ON WHICH SHALL
BE CLEARLY INDICATED THE EXACT LOCATION OF PANELS, CONDUITS,
JUNCTION BOXES, ETC.. INFORMATION ON THESE DRAWINGS SHALL BE
INCORPORATED IN THE AS-BUILT DRAWINGS UPON COMPLETION OF THE
CONTRACT AND BEFORE APPLYING FOR FINAL PAYMENT.
1.11 INTERRUPTION OF SERVICES
1.11.1. INTERRUPTION OF ELECTRICAL SERVICE TO ANY PART OF THE
BUILDING SHALL OCCUR ONLY BY PER-ARRANGEMENT WITH AND AT TIMES
SUITABLE TO THE OWNER.
1.12 IDENTIFICATION
1.12.1. PROVIDE LAMACOID NAMEPLATES ON ALL EQUIPMENT TO MATCH
EXISTING NAMEPLATES. NAMEPLATES SHALL BE MECHANICALLY ATTACHED
TO EQUIPMENT BY MEANS OF RIVETS OR SELF TAPPING SCREWS.
1.12.2. CLEARLY MARK ALL EXPOSED CONDUIT, PULLBOXES, JUNCTION
BOXES, ETC., TO INDICATE THE NATURE OF THE SERVICE TO MATCH EXISTING
BUILDING STANDARDS.
1.13 ENGINEERS INSPECTIONS
1.13.1. CONTRACTOR SHALL ARRANGE FOR INSPECTIONS BY THE
CONSULTANT PRIOR TO CEILINGS AND/OR WALLS BEING CLOSED IN. PROVIDE
MINIMUM THREE (3) BUSINESS DAYS' NOTICE. WHERE PROPER NOTICE OR
ARRANGEMENTS HAVE NOT BEEN MADE, CONTRACTOR SHALL OPEN UP ANY
WALLS, CHASES, OR CEILINGS AS REQUIRED FOR FULL AND ADEQUATE
INSPECTION BY THE CONSULTANT.
1.13.2. FINAL INSPECTION IS IMPERATIVE. CONTRACTOR SHALL CONTACT
CONSULTANT AND THE OWNER'S EXISTING REPRESENTATIVE TO PERFORM A
FINAL INSPECTION. ENSURE THAT ALL NEW INSTALLATION PERFORMED IS NOT
OBSTRUCTED FOR INSPECTION. AND ALL NOTED DEFICIENCIES ARE
CORRECTED TO OWNERS/CONSULTANT SATISFACTION.
1.14 PROGRESS PAYMENTS
1.14.1 PROVIDE DETAILED PROGRESS DRAW BREAKDOWN INCLUDING
MATERIALS AND LABOURS FOR ALL DIVISIONS AND SUB-TRADES. SUBMIT
DRAFT TO CONSULTANT FOR REVIEW PRIOR TO FIRST INVOICE. INCLUDE
MINIMUM $2,000.00 FOR CLOSEOUTS INCLUDING O&M MANUALS AND AS-BUILT
DRAWINGS. CLOSEOUTS LINE ITEM SHALL REMAIN UNBILLED UNTIL O&M
MANUALS AND AS-BUILT DRAWINGS HAVE BEEN SUBMITTED AND APPROVED BY
THE CONSULTANT.
1.15 OPERATION AND MAINTENANCE DOCUMENTATION
1.15.1. PROVIDE ELECTRONIC COPY OF O&M MANUAL ON USB DRIVE. O&M
MANUAL SHALL INCLUDE, BUT NOT BE LIMITED TO, TABLE OF CONTENTS,
CONTRACTOR AND SUB-TRADE LIST AND CONTACT INFORMATION, WARRANTY
LETTER, SHOP DRAWINGS INCLUDING CONSULTANT'S REVIEW STAMP, STARTUP
AND TEST REPORTS, ESA CERTIFICATE, FIRE ALARM VERIFICATION REPORT,
EMERGENCY LIGHTING TEST REPORT, O&M MANUALS FOR ALL EQUIPMENT, AND
AS-BUILT DRAWINGS. AS-BUILT DRAWINGS SHALL BE SUBMITTED IN
HARD-COPY AND STAMPED BY THE ELECTRICAL CONTRACTOR. AS-BUILT
DRAWINGS SHALL INCLUDE THE ENTIRE ELECTRICAL DRAWING SET WITH ALL
CHANGES OR EXISTING CONDITIONS MARKED NEATLY IN RED INK. AS-BUILT
DRAWINGS WILL BE REJECTED IF AN INCOMPLETE SET OR MARKUPS ARE
SUBMITTED.
2. PART B - PRODUCTS
2.1. GENERAL
2.1.1. ALL ELECTRICAL EQUIPMENT SHALL BE C.S.A. APPROVED AND BEAR
THE C.S.A. STAMP. ALL EQUIPMENT SHALL BE NEW UNLESS OTHERWISE NOTED.
2.1.2. COMPLETE THE INSTALLATION IN ACCORDANCE WITH CSA C22.1
EXCEPT WHERE SPECIFIED OTHERWISE.
2.2. BUILDING WIRES
2.2.1. CONDUCTORS: COPPER, STRANDED FOR 10 AWG AND LARGER.
MINIMUM SIZE: 12 AWG OR AS INDICATED, WITH 1000 V INSULATION OF
CHEMICALLY CROSS-LINKED THERMOSETTING POLYETHYLENE MATERIAL
RATED RW90.
2.2.2. CONNECTORS: PRESSURE TYPE, FIXTURE TYPE, ETC. TO CSA C22.2
NO. 65 WITH CURRENT CARRYING PARTS OF COPPER SIZED TO FIT COPPER
CONDUCTORS AS REQUIRED. BUSHING STUD TYPE TO EEMAC 1Y-2.
2.3. CONDUIT
2.3.1. LIQUID TIGHT FLEXIBLE METAL CONDUIT TO CSA C22.2 NO. 56 FOR
FINAL CONNECTIONS TO MOTORS/ROOFTOP UNITS IN DAMP OR WET LOCATIONS
AND FLEXIBLE METAL CONDUIT FOR CONNECTION TO SURFACE/RECESSED
LUMINAIRES AND MOTORS IN DRY AREAS. MAXIMUM 1M (3') LENGTH.
2.3.2. ELECTRICAL METALLIC TUBING (BUILDING INTERIOR, WHERE NOT
SUBJECT TO PHYSICAL DAMAGE) TO CSA C22.2 NO. 83 WITH COUPLINGS OR
RIGID METAL CONDUIT - HOT DIPPED GALVANIZED STEEL THREADED (BUILDING
INTERIOR WHERE SUBJECT TO PHYSICAL DAMAGE, ALL BUILDING EXTERIOR
AND EPOXY COATED EXCEPT 2.3.1 ABOVE) TO CSA C22.2 NO. 45 C/W LIQUID
TIGHT COMPRESSION FITTINGS.
2.3.3. CONDUIT TO BE 21MM (3/4") MINIMUM TRADE SIZE.
2.3.4. FOLLOW MANUFACTURER'S RECOMMENDATIONS AND C22.1 FOR
EXPANSION FITTINGS (RMC), FASTENINGS, FITTINGS, ACCESSORIES TO PROVIDE
A COMPLETE INSTALLATION. U SHAPED CHANNELS, HANGARS, CLAMPS SHALL
BE GALVANIZED STEEL TYPE, WITH FREE RUNNING THREADS WHERE FIT.
2.4. OUTLET BOXES, CONDUIT BOXES:
2.4.1. SIZED TO CSA C22.1.
2.4.2. 102MM SQUARE OR LARGER BOXES AS REQUIRED. GANG BOXES
WHERE WIRING DEVICES ARE GROUPED. BLANK COVER PLATES FOR BOXES
WITHOUT WIRING DEVICES. COMBINATION BOXES WITH BARRIERS FOR
DIFFERENT SYSTEMS WHERE GROUPED.
2.4.3. CONDUIT OUTLET BODIES FOR CONDUIT UP TO 35MM AND PULL
BOXES FOR CONDUITS LARGER THAN 35MM. CAST ALUMINUM BOXES WITH
FACTORY THREADED HUBS AND MOUNTING FEET FOR SURFACE WIRING OF
DEVICES.
2.4.4. KNOCKOUT FILLERS TO PREVENT ENTRY OF DEBRIS.
2.5. SERVICE EQUIPMENT
2.5.1. ALL NEW DISCONNECT SWITCHES, ETC. TO BE OF THE SAME
MANUFACTURER. PROVIDE LOCKABLE NEMA 4X DISCONNECTS FOR OUTDOOR
MOUNTING AND NEMA 2 FOR INDOOR.
2.5.2. ENCLOSURE: BOXES SHALL BE GALVANIZED STEEL CONSTRUCTED,
FRONT SHALL HAVE ANSI 49 GRAY ENAMEL ELECTRODE DEPOSITED OVER
CLEANED PHOSPHATIZED STEEL.
2.5.3. MANUFACTURER: - EATON, SIEMENS, SCHNEIDER ELECTRIC
2.6. FUSES
2.6.1. FUSES SHALL BE BUSSMAN 'FUSETRON' DUAL ELEMENT SLOW
BLOW TYPE, SIZED AS NOTED.
2.7. CIRCUIT BREAKERS
2.7.1. BREAKERS TYPE AND KAIC RATING TO MATCH EXISTING BREAKERS.
MOULDED CASE CIRCUIT BREAKERS TO CSA C22.2 NO. 5.
2.7.2. BOLT ON, QUICK MAKE, QUICK BREAK TYPE FOR MANUAL AND
AUTOMATIC OPERATION.
2.7.3. COMMON-TRIP BREAKERS: WITH SINGLE HANDLE FOR MULTI-POLE
APPLICATIONS.
2.7.4. MAGNETIC INSTANTANEOUS TRIP ELEMENTS IN CIRCUIT BREAKERS
TO OPERATE ONLY WHEN VALUE OF CURRENT REACHES SETTING. TRIP
SETTINGS ON BREAKERS WITH ADJUSTABLE TRIPS TO RANGE FROM 3-8 TIMES
CURRENT RATING.
2.7.5. MOULDED CASE CIRCUIT BREAKER TO OPERATE AUTOMATICALLY
BY MEANS OF THERMAL AND MAGNETIC TRIPPING DEVICES TO PROVIDE
INVERSE TIME CURRENT TRIPPING AND INSTANTANEOUS TRIPPING FOR SHORT
CIRCUIT PROTECTION.
2.8. RECEPTACLES
2.8.1. CSA TYPE 5-15R OR 5-20 R (T-SLOT), 125 V, 15A OR 20 A, U GROUND,
TO: CSA C22.2 No.42 WITH FOLLOWING FEATURES: (1) WHITE UREA MOULDED
HOUSING (2) SUITABLE FOR NO. 10 AWG FOR BACK AND SIDE WIRING (3) BREAK
OFF LINKS FOR USE AS SPLIT RECEPTACLES (4) EIGHT BACK WIRED
ENTRANCES , FOUR SIDE WIRING SCREWS (5) TRIPLE WIRE CONTACTS AND
RIVETTED GROUNDING CONTACTS (6) WEATHERPROOF, GFCI CLASS A RATED
FOR OUTDOOR INSTALLATION.
2.8.2. USB: HUBBELL USB ISX2 WHITE
2.8.3. DO NOT INSTALL OUTLETS BACK TO BACK.
2.8.4. RECEPTACLES WITHIN 1500MM (5FT) OF A WET OR DAMP LOCATIONS
SHALL BE GROUND FAULT CIRCUIT INTERRUPTER TYPE. RECEPTACLE COVER
PLATES SHALL BE STAINLESS STEEL UNLESS OTHERWISE NOTED.
2.9. SWITCHES
2.9.1. 15A/20A, 120V, SINGLE POLE SWITCHES, IVORY TOGGLE AND
MATCHING COVER PLATES. USE CAST BOX IF SURFACE MOUNTED.
2.10. GROUNDING
2.10.1. ALL GROUNDING SHALL CONFORM TO THE ONTARIO ELECTRICAL
SAFETY CODE AND LOCAL AUTHORITY REQUIREMENTS.
2.10.2. PROVIDE SEPARATE GREEN INSULATED GROUND CONDUCTOR IN
EVERY POWER CONDUIT TO ALL DEVICES, EQUIPMENT, AND WITH ALL FEEDERS.
2.11. OCCUPANCY SENSORS
2.11.1. ALL SENSORS SHALL BE 24V. PROVIDE POWER PACKS FOR ALL
SENSORS. SENSOR SHALL BE DUAL TECHNOLOGY USING BOTH PASSIVE
INFRARED AND ULTRASOUND.
2.11.2. SENSORS SHALL HAVE A RE-TRIGGER FUNCTION TO CALL ON THE
LIGHTING SYSTEM WITHIN 5 SECONDS OF TURNING OFF, AND HIGH IMMUNITY TO
FALSE TRIGGERING FROM RFI, EMI. SENSORS THAT INTERFERE WITH
OCCUPANTS USING COCHLEAR IMPLANTS OR HEARING AIDS WILL NOT BE
ACCEPTABLE AND SHALL BE REPLACED WITH A SUITABLE PRODUCT DURING
THIS PROJECT.
2.11.3. PIR SHALL HAVE MULTIPLE SEGMENTED FRESNEL LENS, IN A
MULTIPLE TIER CONFIGURATION, WITH GROOVES-IN TO ELIMINATE DUST AND
RESIDUE BUILD UP. ULTRASONIC SENSORS SHALL UTILIZE ADVANCED SIGNAL
PROCESSING TO ADJUST THE DETECTION THRESHOLD DYNAMICALLY TO
COMPENSATE FOR CONSTANTLY CHANGING LEVELS OF ACTIVITY AND AIR
FLOW THROUGHOUT CONTROLLED SPACE. ULTRASONIC OPERATING
FREQUENCY SHALL BE CRYSTAL CONTROLLED AT NOMINALLY 32 KHZ WITHIN ±
0.002% TOLERANCE TO ASSURE RELIABLE PERFORMANCE AND ELIMINATE
SENSOR CROSS-TALK. SENSORS USING MULTIPLE FREQUENCIES ARE NOT
ACCEPTABLE.
2.11.4. ALL SENSORS SHALL BE CAPABLE OF OPERATING WITH
ELECTRONIC BALLASTS AND MOTOR LOADS. SENSORS SHALL UTILIZE
TECHNOLOGY FOR AUTOMATICALLY ADJUSTABLE TIME DELAY AND SENSITIVITY
SETTINGS.. ALL SENSORS SHALL HAVE UL RATED, 94V-0 PLASTIC ENCLOSURES,
WHITE FINISH. LL SENSORS SHALL PROVIDE AN LED AS A VISUAL MEANS OF
INDICATION AT ALL TIMES TO VERIFY THAT MOTION IS BEING DETECTED DURING
BOTH TESTING AND NORMAL OPERATION. INE VOLTAGE SWITCH WITH BUILT IN
PHOTOCELL, CAPABLE OF BEING MOUNTED IN A 1 GANG SWITCH BOX AND
MADE OF HIGH IMPACT INJECTION MOULDED PLASTIC.
2.11.5. WALL SENSOR SHALL BE HUBBELL INC. LIGHTHAWK2 SERIES,
SIGNIFY PHILIPS OCCUSWITCH SERIES OR APPROVED EQUAL WITH AUTO-ON
AND MANUAL-ON OPERATING MODES. CEILING SENSOR SHALL BE HUBBELL INC.
OMNI SERIES, SIGNIFY PHILIPS OCCUSWITCH LLA SERIES OR APPROVED EQUAL.
2.11.6. HUBBELL UNIVERSAL VOLTAGE POWER PACKS TYPE UVPPM,
SIGNIFY PHILIPS OCCUSWITCH SERIES OR APPROVED EQUAL FOR USE WITH
BOTH MANUAL AND AUTOMATIC ON/OFF CONTROL TO BE INSTALLED AT
LOCATIONS WITH UP TO 4 SENSORS, MOUNTED IN A JUNCTION BOX. OPERATING
VOLTAGE 120V, 60 HZ WITH ELECTRICAL LOAD SWITCHING CAPABILITY OF 20A.
REGULATED 24VDC CURRENT; 150MA OUTPUT. AUTOMATIC VOLTAGE
DETECTION. ZERO ARC POINT SWITCHING TO MINIMIZE RELAY-CONTACT WEAR
FROM HIGH INRUSH LOADS.
2.11.7. ALTERNATES SHALL BE LEVITON, LUTRON, PASS & SEYMOUR.
ENSURE COMPATIBILITY WITH SELECTED LUMINAIRE PRIOR TO INSTALLATION.
2.12. LIGHTING
2.12.1. ALL NEW LIGHTING SHALL BE LED. REFER TO LUMINAIRE SCHEDULE
FOR DETAILS OF FIXTURES. LED'S AND DRIVERS ARE TO BE 100% COMPATIBLE
WITH EACH OTHER. NEMA 410 COMPLIANT DRIVERS. LUMINAIRE WITH LED AND
DRIVER TO BE CSA APPROVED OR ULC LISTED, AND CERTIFIED AND TESTED AS
A COMPLETE ASSEMBLY.
2.12.2. SPECIFICATION STANDARDS TO MEET REQUIREMENTS OF IES LM 79
AND WHERE CONNECTED TO DIMMERS, BE 100% COMPATIBLE WITH CONNECTED
DIMMER CONTROLS TO PROVIDE DIMMING DOWN TO 1%. COORDINATE WITH
DIMMING CONTROLS VENDORS TO ENSURE THAT TECHNICAL OPERATIONS OF
DIMMERS (I.E. FORWARD PHASE, REVERSE PHASE, ETC.) MATCH LED/ DRIVER
TECHNOLOGY. CLEARLY IDENTIFY THIS INFORMATION IN SHOP DRAWING
SUBMISSIONS.
2.12.3. LEDS TO BE SELECTED FROM SAME COLOUR BIN SIZE FOR
CONSISTENCY IN CHROMATICITY AND MEET ANSI C78 377A AS A MINIMUM;
GENERALLY, COLOUR TEMPERATURE RANGE TO BE FROM 2700 K TO 6500 K;
SPECIFIC TEMPERATURE REQUIREMENTS TO BE IDENTIFIED ON SCHEDULE OF
LUMINAIRES AND REVIEWED WITH CONSULTANT PRIOR TO ORDERING; MINIMUM
CRI OF 85. MINIMUM RATED LIFE (BASED ON LM-80 AND TM-21) FROM 50,000 TO
70,000 HOURS.
2.12.4. DRIVERS SHALL OPERATE FROM 60 HZ INPUT SOURCE OF 120
VAC/347VAC (AS APPLICABLE) WITH SUSTAINED VARIATIONS OF ± 10%
(VOLTAGE AND FREQUENCY) WITH NO DAMAGE TO DRIVER; OUTPUT
REGULATED TO ±5% ACROSS LOAD RANGE; POWER FACTOR GREATER THAN
0.90; TOTAL HARMONIC DISTORTION LESS THAN 20%; CLASS A SOUND RATING;
COMPLY WITH ANSI C62.41 CATEGORY A FOR TRANSIENT PROTECTION.
2.12.5. EMERGENCY LIGHTING: REMOTE HEADS TO MATCH EXISTING.
CONNECT NEW HEADS TO EXISTING BATTERY UNITS AND AIM HEADS TO SUIT
SITE CONDITIONS. TEST OPERATION OF HEADS AND CONFIRM.
2.12.6. FOLLOW MANUFACTURER RECOMMENDATIONS FOR MOUNTING IN
SUSPENDED OR T-BAR CEILING. USE AIRCRAFT CABLE FOR MOUNTING
REQUIREMENTS.
2.13. SYSTEMS
2.13.1. GENERAL
2.13.1.1. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING
SERVICES OF QUALIFIED SYSTEMS SUB-CONTRACTORS FOR THE SYSTEMS
NOTED BELOW, AND CARRY OUT ALL THE WORK INCLUDING, BUT NOT LIMITED
TO, CONDUIT, WIRING, DEVICES, EQUIPMENT, TESTING AND VERIFICATION.
2.13.1.2. CONFIRM ROOM NUMBERING WITH ARCHITECT AND OWNER PRIOR
TO PROGRAMMING THE SYSTEMS.
2.13.2. FIRE ALARM
2.13.2.1. NEW FIRE ALARM PANEL TO BE SIMPLEX 4100 ES.
2.13.2.2. PROVIDE ALL MATERIAL AND LABOUR REQUIRED FOR A COMPLETE
AND ADEQUATE INSTALLATION OF THE FIRE ALARM SYSTEM AS SHOWN ON THE
DRAWINGS. PANEL TO BE SINGLE STAGE NON-CODED ADDRESSABLE/HYBRID.
WIRE EXISTING CIRCUITS TO NEW PANEL ZONES.
2.13.2.3. ALL NEW DEVICES TO MATCH NEW PANEL.
2.13.2.4. ALL NEW CONDUIT AND WIRING TO EXISTING DETECTION DEVICES
AND CONTROL EQUIPMENT, WHERE REQUIRED DUE TO ARCHITECTURAL AND
MECHANICAL UPGRADES, SHALL MEET LOCAL AND NATIONAL BUILDING, FIRE
AND ELECTRICAL CODES AND STANDARDS, AND MANUFACTURER
REQUIREMENTS.
2.13.2.5. PAINT ALL FIRE ALARM JUNCTION BOXES RED. PROVIDE LABELING
FOR INDICATING IDC OR NAC FUNCTION.
2.13.2.6. PROVIDE VERIFICATION REPORT ON COMPLETION OF WORK TO
CAN/ULC S537-M "STANDARD FOR THE VERIFICATION OF FIRE ALARM SYSTEMS".
2.13.2.7. PERFORM AUDIBILITY TESTS AS PER ONTARIO BUILDING CODE (MIN.
65dBA, MAX. 100dBA THROUGHOUT) AND PROVIDE REPORT TO CONSULTANT.
ALL SPACES WITHIN PROJECT AREA SHALL BE TESTED. DOORS SHALL BE
CLOSED DURING TESTING.
2.13.2.8. GRAPHIC PANEL TO BE FRAMED UNDER 3.15MM CLEAR PLASTIC
COVER. CLEARLY OUTLINE DETECTION ZONE BOUNDARIES WITH BLACK INK ON
VINYL, NAMES AND NUMBERS WITH RED INK (MIN. HEIGHT 3MM) AND MARK WITH
HIGH VISIBILITY RED LETTERS WITH ARROW SHOWING "YOU ARE HERE".
GRAPHIC PANEL (508MMX508MM) TO BE FIXED PERMANENTLY TO THE WALL.
SHOW LOCATIONS OF ANNUNCIATOR PANEL AND CONTROL PANEL. ORIENT
BUILDING FLOOR PLAN ON GRAPHIC TO LOCATION OF PERSON VIEWING
GRAPHIC I.E. DIRECTION VIEWER IS FACING IS TOWARD TOP OF GRAPHIC
DISPLAY. PROVIDE NORTH ARROW. LOCATIONS - IN VESTIBULE AT THE
LOCATION OF ANNUNCIATOR PANEL, AND ELECTRICAL ROOM B12.
2.13.2.9. NEW FIRE ALARM ZONING SHALL FOLLOW EXISTING (11 ZONES) AND
ADDITIONALLY INCLUDE 1 NEW ZONE FOR ELEVATOR AND 50% SPARE ZONES
FOR FUTURE. ZONING SHALL FOLLOW THE LATEST OBC REQUIREMENTS
2.13.3. PUBLIC ADDRESS, COMMUNICATIONS & SECURITY:
2.13.3.1. INSTALL P.A. DEVICES, COMMUNICATION SYSTEM AND SECURITY
SYSTEM AS PER EACH MANUFACTURERS REQUIREMENTS.ALL NEW DEVICES TO
MATCH EXISTING.
2.13.3.2. PROVIDE INFRASTRUCTURE AS REQUIRED INCLUDING BUT NOT
LIMITED TO BACK BOXES, CONDUIT COMPLETE WITH POLYPROPYLENE PULL
STRING, INSULATING BUSHINGS, STUBS, JUNCTION BOXES, ETC. TO CONSTITUTE
A COMPLETE PATHWAY IN ORDER TO FACILITATE SYSTEM CABLING/WIRING
INSTALLATION.
2.13.3.3. P.A. SYSTEM: EXISTING BY DUKANE
2.13.3.4. P.A. SPEAKERS: EXISTING BY TORTECH/MCBRIDE WHITE SQUARE
GRILL WITH 25V TRANSFORMERS. SPEAKERS TO BE TAPPED 2-4W FOR GYM AND
BOILER ROOMS, 0.25W FOR OFFICES AND 1W FOR ALL OTHER APPLICATIONS.
2.13.3.5. P.A. WIRING: PROVIDE HOME RUNS FROM P.A. DEVICES TO MAIN P.A.
RACK. CABLING SHALL BE CAT6 FT6 WHITE RATED WHEN IN CONDUIT OR FT6
WHERE CONDUIT INSTALLATION IS NOT POSSIBLE. USE EXISTING
COMMUNICATIONS CONDUIT WHERE POSSIBLE OR USE J-HOOKS FOR RUNNING
NEW WIRING WHEN NOT IN CONDUIT. USE PROPER TOOLS FOR PUNCH DOWN ON
EXISTING BIX PANEL FOR ALL WIRING.
2.13.3.6. P.A., TESTING: PERFORM TESTING AND COMMISSIONING,
ADJUSTMENTS TO EXISTING PROGRAMMING AS REQUIRED, VERIFICATION AND
CERTIFICATION OF THE SYSTEM. MAKE ANY CORRECTIONS AT NO COST TO THE
OWNER. PROVIDE FINAL REPORT TO CONSULTANT FOR REVIEW. REPORT TO
INCLUDE TEST DETAILS FOR ALL LINES INDICATING CONTINUITY, SHORTS AND
GROUND. INCLUDE RESULTS OF IMPEDANCE TESTING AT EACH SPEAKER.
2.13.3.7. SECURITY WIRING: USE EXISTING COMMUNICATIONS CONDUIT
WHERE POSSIBLE OR USE J-HOOKS FOR RUNNING NEW WIRING WHEN NOT IN
CONDUIT. PROVIDE HOME RUNS FROM DEVICES TO MAIN SECURITY CONTROL
PANEL. INSTALL DEVICES AND WIRING AS PER MANUFACTURER REQUIREMENT.
2.13.3.8. SECURITY TESTING: PERFORM TESTING AND COMMISSIONING,
ADJUSTMENTS AS REQUIRED, VERIFICATION AND CERTIFICATION OF THE
SYSTEM. MAKE ANY CORRECTIONS AT NO COST TO THE OWNER. PROVIDE FINAL
REPORT TO CONSULTANT FOR REVIEW.
2.13.3.9. COMMUNICATIONS CABLING PER TIA 568.0-D, 568.01-D, 568.02-D.
2.13.3.10. COMMUNICATIONS PATHWAYS PER TIA 569-E.
2.13.3.11. COMMUNICATIONS GROUNDING AND BONDING PER TIA 607-D.
2.13.3.12. COMMUNICATIONS CABLING: ALL COMMUNICATIONS CABLING
SHALL BE RUN WITHIN EXISTING COMMUNICATIONS CONDUIT/RACEWAYS
WHERE POSSIBLE. ALL CABLING SHALL BE RUN IN CONDUIT FROM
COMMUNICATION OUTLETS TO CORRIDOR CABLE MANAGEMENT SYSTEM.
EXISTING SYSTEM SHALL BE BASED ON PANDUIT STRUCTURED CABLING.
MAXIMUM HORIZONTAL RUN SHALL NOT EXCEED 100m FROM HORIZONTAL
CROSS CONNECT. ALL CABLING MUST BE 24AWG CAT6 100-OHM BALANCED
UNSHIELDED TWISTED PAIR, FT6 RATED, BLUE OUTER SHEATH FOR BOTH VOICE
AND DATA. FACEPLATES TO MOUNT UP TO SIX (6) JACKS IN A SINGLE GANG AND
UP TO NINE (9) JACKS IN A DOUBLE GANG. JACKS SHALL BE 8-POSITIONED
UNKEYED WITH 94 V0 RATING. ALL DROPS SHALL BE CLEARLY LABELED ON THE
PATCH PANEL AND CABLE BOX. PROVIDE YELLOW FOR VOICE AND GREEN FOR
DATA. PROVIDE HOME RUN CABLING TO MAIN SWITCH FROM EACH WIRELESS
ACCESS POINT. ALLOW ENOUGH LENGTH OF CABLE AT EACH END (PATCH
PANEL AND OUTLET) TO ALLOW RELOCATING CABLING IN THE FUTURE.
PROVIDE 4' AND 6' PATCH CABLES AT WORK WORK STATION END AS REQUIRED
TO SUIT THE INSTALLATION. COORDINATE WITH OWNER. FOR EACH ACCESS
POINT, CONTRACTOR TO ALLOW FOR NEW HOMERUN CABLE BACK TO THE MAIN
CONTROL PANEL FOR POSSIBLE RELOCATION.
2.13.3.13. COMMUNICATIONS TESTING: TEST ALL DROPS FOR DATA
TRANSMISSION REQUIREMENTS PER APPLICABLE STANDARDS AND PROVIDE
REPORT TO CONSULTANT.
2.13.3.14. COORDINATE WITH OWNER AND MANUFACTURER FOR ALL
REQUIRED DOCUMENTS, STANDARDS AND RECOMMENDATIONS PRIOR TO
COMMENCING WORK ON P.A., COMMUNICATIONS AND SECURITY.
2.13.3.15. CONTRACTOR SHALL RE-PROGRAM ON EACH SYSTEM (P.A.,
COMMUNICATIONS, SECURITY) AFTER COMPLETION OF INSTALLATION AND
PERFORM TESTING FOR OPERATIONAL READINESS. PROVIDE TEST REPORTS TO
CONSULTANT FOR REVIEW. COORDINATE SCOPE EXTENT OF PROGRAMMING
WITH THE OWNER
2.13.4. LIST OF APPROVED SUB-CONTRACTORS:
2.13.4.1. ACCESS CONTROL SYSTEMS & SECURITY SYSTEMS:
TRENT SECURITY, 705.748.2001
2.13.4.2. P.A., COMMUNICATION SYSTEMS:
ELECTRICAL CONTRACTOR TO BE RESPONSIBLE FOR OBTAINING
THE SERVICES OF A QUALIFIED PUBLIC ADDRESS SYSTEM CONTRACTOR.
2.13.4.3. FIRE ALARM
FIRE ALARM INSTALLER: CFAA CERTIFIED.
Printed on ___% Post-Consumer
Recycled Content Paper
This draw
ing has been prepared for the use of A
EC
OM
's client and m
ay not be used, reproduced or relied upon by third parties, except as agreed by A
EC
OM
and its client, as required by law
or for use by governm
ental review
ing agencies. A
EC
OM
accepts no responsibility, and denies any liability w
hatsoever, to any party that m
odifies this draw
ing w
ithout A
EC
OM
's express w
ritten consent. D
o not scale this docum
ent. A
ll m
easurem
ents m
ust be obtained from
stated dim
ensions.
KEY PLAN
REGISTRATION
CLIENT
Kawartha Pine Ridge
District School Board
1994 Fisher Drive, Peterborough, Ontario
705.742.9773 tel 705.742.7801 fax
www.kprdsb.ca
PROJECT
New Elevator & Renovation
Prince of Wales
Public School
1211 Monaghan Road. S. Peterborough, Ontario
PROJECT NUMBER
60624140
AR
CH
D
2
4" x 3
6"
CONSULTANT
AECOM Canada Ltd.
300 Water Street
Whitby, Ontario, Canada L1N 9J2
905.215.1400 tel 905.668.0221 fax
www.aecom.com
2
2
2