GENERAL CONTRACTORS 835 GIL HARBIN INDUSTRIAL BLVD. VALDOSTA, GA 31601 (229) 244-6709 Fax (229) 244-7778 TO: BES Incorporated 2712 Bull Street Beaufort, SC 29902 P 843.522.2094 SUBMITTAL TRANSMITTAL DATE June 1, 2010 JOB NO. 09-019 ATTENTION Mr. Robert Beach RE Enclave Force Protection Access Control Point Contract W9128F-09-C-0051 Ft. Gillem, Georgia Submittal Number 13 34 20 SD-02 Description Prefabricated Guard booths See Form 4025 Attached COPY TO File SIGNED If enclosures are not as noted, kindly notify us at once.

Upload: trandat

Post on 28-Mar-2018

217 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

GENERAL CONTRACTORS 835 GIL HARBIN INDUSTRIAL BLVD. VALDOSTA, GA 31601 (229) 244-6709 ● Fax (229) 244-7778

TO: BES Incorporated

2712 Bull Street

Beaufort, SC 29902

P 843.522.2094

SUBMITTAL TRANSMITTAL

DATE June 1, 2010 JOB NO. 09-019

ATTENTION Mr. Robert Beach

RE Enclave Force Protection Access Control Point

Contract W9128F-09-C-0051

Ft. Gillem, Georgia

Submittal Number 13 34 20 SD-02

Description Prefabricated Guard booths

See Form 4025 Attached

COPY TO File

SIGNED

If enclosures are not as noted, kindly notify us at once.

Page 2: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 3: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 4: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 5: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Porta-King Building Systems Standard Finished Floor Covering

Aluminum Diamond Tread Plate

CHARACTERISTICS - Excellent at resisting moisture and strong for its light-weight. Diamond Tread pattern is slip-resistant and cosmetically appealing for hundreds of decorative applications. Raised lugs are on approximate 1” centers. 1/8” x 48” x 96” Sheets Approximate Weight Per Square Foot: 1.920 lbs.

Page 6: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

CR20 -- Commercial Series Duplex Receptacle

2P3W, 20A 125V, 5-20R, Smooth Nylon Face, Brown

Product Specifications

Product Type

Receptacle Style Duplex Face Shape Standard

Standard NEMA Amperage 20A Voltage 125V

Poles and Wires 2 Pole, 3 Wire Grounding Wiring Method Side Wire Only

Hospital Grade ? No Receptacle Grade Commercial Series Specification Grade Face Style Smooth Face

Color

NEMA No. 5-20R

Page 7: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Horsepower 1 Description Heavy Duty Straight Blade Duplex Receptacle

Type 2 Pole, 3 Wire, Grounding Rating 20A, 125V

Certification UL Listed, File E2186, Meets NEMA WD-6 requirements Listed to UL Standard 498, Certified to CSA, C22.2, No. 42

Terminal Screw Material

#8-32 Brass, Multiple Drive

Ground Screw Material

#8-32 Brass, Multiple Drive (Green)

Top Material Nylon Base Material Nylon

Power Contacts Material .031" (.8) Phosphor Bronze

Mounting Strap Material .040" (1) Steel (Galvanized)

Center Assembly Rivet Material

.040" (1) Steel (Galvanized) Staple

Auto Ground Clip Material

.032" (.8) Steel Wire

Mounting Screw Material Steel-Zinc Plated

Dielectric Voltage Withstands 2,000V minimum. Current Interrupting Certified for current interrupting at full rated current.

Temperature Rise Max 30°C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of 75%..

Terminal Identification

Terminals identified in accordance with UL498 (Brass, White, Green).

Terminal Accommodation

#14-#10 AWG copper stranded or solid conductor only.

Product Identification Ratings are a permanent part of the device. Flammability UL 94 V2.

Operating Temperatures Maximum continuous 75°C, minimum -40°C (w/o impact).

Page 8: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

T&B Catalog Number L-80:UPC Number: 04226964400Description: Dry-tite® Silver Lampholder, materi-

al-Die Cast Zinc Zamak 3. Lamp maximum-150 watt, PAR 38 or R40. Inside gasketand ground screw included.

Status: Active

FeaturesClean lines and precision manufacturing; high-qual-

ity replaceable porcelain socket with high-tempera-

ture leads allows for easy field maintenance.

Positive locking mounting arm keeps fixture in

aimed position to reduce costly call-backs and

ground screw boss in arm.

GeneralMaterial Die Cast Zinc

Color Silver

PackagingPackage in Units 36

T&B Sold in UOM Each

T&B Weight Per UOM 0.39 lbs. Each

Application SupportProduct Overview Available on Website

Certifications

File Nbr:E 51152

For further technical assistance, please contact us...

Thomas & Betts - USA8155 T&B Blvd.Memphis, TN 38125www.tnb.com

T&B Technical SupportMS 3B-508155 T&B Blvd.Memphis, TN 38125

Hours: 7AM - 6PM CDTMonday-FridayPhone: (888) 862-3289Fax: (901) 252-1321Email:[email protected]

Page 9: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

13

Your Outdoor Needs are Covered

Often times, the simplest things in life make the biggest impact. Intermatic understands that simple measures can have a big effect in protecting the electrical systems and products within your home or business.

Intermatic has designed a line of hard wearing weatherproof products that provide an exact match to the application, are easy to install and provide reliability and longevity. Our full line of weatherproof products are the perfect combination of utility and innovation. From our patented Flexi-Guard covers to our heavy duty die-cast outlet boxes, lamp holders and fittings, Intermatic has you completely covered from start to finish.

Intermatic also makes it easy to stay current with the latest electrical codes and all models comply with 2002 NEC Article 250.146, which provides direct mounting of wiring devices to the switch box. We have the best coverage in the industry and are constantly updating our product categories to meet your ever-changing needs and requirements. As new codes and articles are being introduced and enforced, Intermatic will have the box, cover or accessory you need to remain compliant.

Page 10: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

These NEMA 3R receptacle covers ensure compliance with 2005 NEC Article 406.8 (B) (1) which requires that15 and 20 ampere, 125 and 250 volt receptacles installed in a wet location have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. They also meet the 1999 NEC Article 410-57(b) and are designed to meet the 1999 NEC Article 210-60(b), which requires that receptacles installedbehind beds in hotels and motels be protected with a suitable guard.

All covers are shipped with gasket, mounting screws, base and cover assembly and patented inserts. TheFlexi-Guard series provides inserts for a variety of applications; 16 for the WP1100 single gang series and 70for the WP1200 two gang series. The single gang Flexi-Guard models are all designed to mount horizontallyor vertically. The patented insert design ensures flexibility in the field by simply inserting the proper insert intothe base and cover assembly. The two gang Flexi-Guard models utilize six “split” inserts which create virtuallyany dual device combination, as well as providing additional flexibility because the inserts can be rotated 90,180 or 270 degrees. This provides coverage for horizontally or vertically mounted devices as well as “lefthand” or “right hand” applications without removing and switching the two installed devices.

The “jumbo covers” WP1150C, WP1250C, WP1050 and WP1050G provide protection for a single large cordset (up to 3/4" dia.) for portable spa heaters and other heavy duty applications. A lockable hasp is providedon selected models. The hasp accepts up to .315" (8 mm) diameter shank.

NEMA 3RMeets UL and CSA Cold Impact Testing at -60˚F (-51˚C)

Patented: U.S. Patent #5 280 135 U.S. Design Pat. #342233

Canadian Patent #2 073 932 Other Patents Pending

Waterproof Cover Applications • Vending Machines • Amusement Equipment • Ventilating Fans • Landscape Lighting • Outdoor Signs• RV Connectors • Seasonal Lighting • Remote Power Needs • Portable Spas • Portable Marquee• Sprinkling Controls • Drinking Fountains • Athletic Field Lighting • Score Board Controls • Bug Zappers• Car Lot Lighting • Gate Controls • Process Start Up • Equipment • Septic Lift Pumps• Car Washes • Low Voltage Lighting • Meat Processing • Engine Block Heaters • Holiday Lighting• Food Preparation • Plant Grow Lighting • Plant Watering • Remote Feeders • Irrigation Pumps• Hotel Applications • Scoreboard Controls

SpecificationsAll covers for flushmount, surface mount or FS junction box mounting.Cover – Clear (gray or white on selected models) UV stabilized polycarbonate with two cord outlets 1/2"(12.7 mm) Wide by 9/16" (14.2 mm) High. Models WP1150C, WP1250C and WP1050 one cord outlet 3/4"(19.1 mm) Wide by 1-5/16" (33.3 mm) High.Mounting Base and Inserts – Black UV stabilized polycarbonate.Gasket – Neoprene - 1/8" (4.8 mm) thick with slits for mounting screws.Shipping Weight – WP1100C / WP1000HC – .38 lbs. (0.17 kg)

WP1110C / WP1010HC – .41 lbs. (0.19 kg)WP1150C / WP1230C / WP1030C – .75 lbs. (0.34 kg)WP1220C / WP1020C – .72 lbs. (0.33 kg)WP1250C / WP1050 – .9 lbs. (0.41 kg)

MEETS 2005 NEC 406.8(B) (1) Receptacles installed ina wet location must have an enclosure that is weather-proof when you insert the attachment plug.

UL514DE142193

C22.2-42.1LR88576

Weatherproof Receptacle Covers with Patented Insert Design

WEATHERPROOF • ENERGY CONTROLS • PROFESSIONAL LIGHTING • POOL & SPA • SURGE PROTECTION • CONSUMER14

Page 11: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

15

WP1000RC - Vertical CoverWP1000HRC - Horizontal CoverRecessed While-In-Use Cover

Weatherproof While-In-Use Cover

Product Features• Complies with 2005 NEC® Article 406.8(B)(1)• Heavy duty, polycarbonate cover for long lasting durability

APPLICATIONSProvides an attractive, code compliant solution for protecting while-in-use outdoor receptacles.

SPECIFICATIONS• Device installs recessed in wall for a flush finish for Siding, Stucco or Brick finishes• Removable siding flange provides clear finish for all siding types• Patented single gang inserts for GFCI, duplex, single receptacles, toggle switch and blank• Heavy Duty Gasket ensures protection from the elements• Recessed Sleeve adjusts to ensure lowest profile installation in every application• Outlet box offers mounting options for stud, block, brick or cut-in• Cord exit easily handles two 12/3 cord sets• Handles romex or conduit installations• Wider access to device for easy cord set installation• Heavy duty, UV resistant, polycarbonate constructed cover

Warranty: Limited 1-year warranty

Weatherproof Receptacle Covers with Patented Insert Design

GFCI DEVICE SHOWN NOT INCLUDED

2.00 lbs0.91 kg

WEATHERPROOF • ENERGY CONTROLS • PROFESSIONAL LIGHTING • POOL & SPA • SURGE PROTECTION • CONSUMER

Page 12: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

WP2000 Flexi-Guard Outlet PostWhile-In-Use Cover

Weatherproof

PRODUCT FEATURES• Complies with 2005 NEC® Article 406.8(B)(1)• Heavy duty PVC construction for long lasting durability

APPLICATIONSProvides a new, code compliant solution for supplying power to gardens and other out-of-the-way areas

A remotely mounted energy saving photo control and/or timer also available to activate area lighting

SPECIFICATIONS• Patented single gang inserts for GFCI, duplex, single receptacles, toggle switch and blank• Provisions for installing mechanical or digital timers to control area lighting:

– PB912M10R: 24 hour, 120 Volt mechanical timer – allows for 2 ON/OFF daily cycles– PB313K: 24 hour, 120 Volt electronic timer – allows for 8 ON/OFF daily cycles (Timers sold separately)

• Provisions for fixed-position, stem-mounting and stem & swivel mounting photo controls to control area lighting• All ports accept 1/2”,3/4”, or 1” PVC conduit (adapters included)• Base includes mounting holes and template for optional concrete/pavement mounting• Cover includes lockable hasp

Warranty: Limited-1 year warranty

Weatherproof Receptacle Covers with Patented Insert Design

3.00 lbs1.36 kg

GFCI DEVICE SHOWN NOT INCLUDED

WEATHERPROOF • ENERGY CONTROLS • PROFESSIONAL LIGHTING • POOL & SPA • SURGE PROTECTION • CONSUMER16

Page 13: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Die CastThese heavy duty die cast receptacle covers ensure compliance with the National Electrical Code (NEC). Thesemodels offer the same features as the plastic models but are manufactured of heavy duty cast metal for severeapplications such as schools and commercial buildings. The two gang model WP1030MC includes insertsfor double gang duplex and GFCI requirements. This patented insert design uses the same inserts as allWP1000 series weatherproof covers and provides flexibility in the field by selecting and inserting the properinsert. For other applications see insert listing below.

All models are recommended for 14 gauge or lighter cord sets. A lockable hasp is provided (lock notincluded). The hasp accepts up to .315" (8 mm) diameter shank.

SpecificationsCover – Gray die cast metalMounting Base – Gray die cast metal with cord outlets 1" (25.4 mm) Wide by 5/8" (15.9 mm) High; onefor models WP1010MC and WP1010HMC and two for model WP1030MC.Inserts – Black UV stabilized polycarbonate.Gasket – Neoprene 1/8" (3.2 cm) thick with slits for mounting screws.Shipping Weight – WP1010MC – 0.8 lbs. (0.36 kg)

WP1010HMC – 0.9 lbs. (0.41 kg) WP1030MC – 1.1 lbs. (0.5 kg)

All models comply with 2005 NEC Article 250.146 which provides direct mounting of wiring devices to the switch box.

17

Weatherproof Receptacle Covers

UL514DE142193

C22.2-42.1LR88576

WEATHERPROOF • ENERGY CONTROLS • PROFESSIONAL LIGHTING • POOL & SPA • SURGE PROTECTION • CONSUMER

Page 14: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

WEATHERPROOF • ENERGY CONTROLS • PROFESSIONAL LIGHTING • POOL & SPA • SURGE PROTECTION • CONSUMER

Intermatic Flexi-Guard Weatherproof Receptacle Covers let you handle even more configurations with fewerunits. The unique patented inserts and covers allow you to keep even less inventory than before, and covermore jobs out in the field.

Our single gang models handle both vertical or horizontal applications, just by changing the hinge points. Ourtwo-gang models include snap-together, rotating inserts that create combinations for almost every application.

With these new Flexi-Guard models, now more than ever, Intermatic is the best NEC code solution under thesun.

New FeaturesSingle gang plastic models feature pre-adhered gaskets and all covers feature keyhole slots on insertsfor the quickest installation available

Clear & Opaque Gray Models

Clear & White Models

Heavy Duty Die Cast Models

Outlet Post Recessed

Inset Design US Patent #5 280 135Canadian Patent #2073932

Now you can handle even more with less.

3-1/4"2-1/2"

6-1/2"

WP1030MC

5-9/16"

3-1/4"2-1/2"

6-1/2"

WP1010MC

3-3/4"

3-1/4"2-1/2"

4-1/2"

WP1010HMC

5-3/4"

3-1/2"2-5/8"

5-1/2"

WP1020/1220CWP1030/WP1230C

5"

3-1/2"2-5/8"

5-1/2"

WP1000WP1010

3-13/16"

3-1/2"2-5/8"

4-1/4"

WP1000HWP1010H

5"

4-7/8"

6"

WP1050/WP1250C

5"

4-3/4"3-1/2"

5-3/8"

WP1150C

3-1/2"

2-7/8"WP1110CWP1100C

3-1/2"2-5/8"

5-1/2"

WP1020/1220CWP1030/WP1230C

5"

34-7/8"

6"

WP1050/WP1250C

5"

InsertsInserts fit single gang models and two gangmodels of clear, gray or die cast design. The 2-gang inserts for models WP1020, WP1030,WP1020GC, WP1030GC, WP1030MC and WP1050can be mounted at any angle 90, 180 or 270degrees from that shown. Additional hardware, ifrequired, and special 2-gang gasket is packagedwith 2-gang (WP200 series) inserts.

16 Configurations forSingle Gang WP1100C Series

70 Configurations for DoubleGang WP1200C Series

Additional inserts available forFlexi-Guard or Guardian Series

Two Two Two Two TwoGang Gang Gang Gang GangDuplex GFCI Toggle Round Round

WWPP110011 WWPP110022 WWPP110033 WWPP110077 WWPP221133

1-3/8” 2-5/32”1-5/8” 2-21/32”

1-3/4”

Single Gang Flexi-Guard Two Gang Flexi-Guard

WP17 WP217† Converts to toggle, ‡ Converts to toggle,1-3/8", 1-5/8", 1-3/8" or 1-5/8"1-3/4" or 2-1/8" diameter rounddiameter round

8.17”

SIDE VIEW

9.43”

6.64”

FRONT VIEW

1-13/32”

1-13/32”

6-5/8” DIA

1-13/32” 1-13/32”

1-5/8” 1-5/8”

BOTTOM VIEW

WP20006.81

5.47

7.70

8.62

WET LOCATIONS ONLY WHEN COVER CLOSED

5.88

1.1250.25

3.50

6.0

1.125 8.62

7.25

5.90

6.81

WET LOCATIONS ONLY WHEN COVER CLOSED

1.1250.25

6.0

1.125

3.50

WP1000RC WP1000HRC

18

Page 15: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

19

Now you can handle even more with less.

* With lockable hasp† Converts to toggle, 1-3/8”, 1-5/8”, 1-3/4” or 2-1/8” diameter round‡ Converts to toggle, 1-3/8” or 1-5/8” diameter round

Insert Design US Patent #5 280 135Canadian Patent #2073932

Patented Single GangVertical or Horizontal

Two Gang with PatentedSnap-Together Inserts Patented Die Cast Metal Patented Two Gang

FixedPatented Single Gang

Fixed

2-1/4”Standard

Depth

ClearWP1220C

ClearWP1020C

ClearWP1000C

VerticalWP1000HCHorizontal*

GrayWP1000GC

VerticalWP1000HGCHorizontal*

2-3/4”Standard

Depth

Clear*WP1100C

White*WP1100WC

3-1/8”Standard

Depth

ClearWP1230C

ClearWP101MC Vertical

Single GangWP1030MC Two Gang

ClearWP1030C

ClearWP1010C

VerticalWP1010HCHorizontal*

3-5/8”Standard

Depth

Clear*WP1110C

White*WP1110WC

4-3/4”Standard

Depth

Clear*WP1150C

Clear*WP1250C

Clear*WP1050

WP1100 SeriesIncludes 3 Patented

Inserts

WP1200 SeriesIncludes 6 Snap

Together PatentedInserts

WP1000MC SeriesIncludes these Patented

Inserts

WP1000 SeriesIncludes these Inserts

WP1000 SeriesIncludes these Inserts

‡Two Gang

Single Gang

Vertical or Horizontal

Vertical or Horizontal

Vertical or Horizontal

WEATHERPROOF • ENERGY CONTROLS • PROFESSIONAL LIGHTING • POOL & SPA • SURGE PROTECTION • CONSUMER

Page 16: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Com

mer

cial

GFC

I Rec

epta

cles

Gro

und

Faul

t Pro

duct

sGround Fault Products2 Pole 3 Wire Grounding15 and 20 Ampere, 120 Volt ACStraight Blade Commercial Specification Gradeand Commercial Hospital Grade GFCI Duplex Receptacles

H-4 Dimensions in Inches (mm)www.hubbell-wiring.com

3.28"(83.3)

1.13"(28.7)

1.64"(41.7)

2.61"(66.3)

3.28"(83.3)

1.13"(28.7)

1.64"(41.7)

2.61"(66.3)

1.66"(42.2)

1.06"(27.1)

2.62"(66.5)

3.28"(83.3)

2.75"(69.8)

Circuit Guard®

Commercial Specification GradeGFCI Duplex ReceptaclesDescription Color Catalog NumbersFlush, nylon face, Brown GFR5252Aback & side wired, Ivory GFR5252IAmultiple drive screws. Gray GFR5252GYA Matching nylon wallplate White GFR5252WAincluded. Black GFR5252BKA

Office White GFR5252OWA Red GFR5252RA

Bulk packed, 50 pieces. Brown GFR5252AM1 Ivory GFR5252IAM1 Gray GFR5252GYAM1 White GFR5252WAM1 Black GFR5252BKAM1

Circuit Guard Faceless GFCIDescription Color Catalog NumbersFaceless, back and side wired, Brown - GFR5350multiple drive screws. Ivory - GFR5350IMatching nylon wallplate White - GFR5350Wincluded. Black - GFR5350BK

Circuit GuardCommercial Hospital GradeGFCI Duplex ReceptaclesDescription Color Catalog NumbersFlush, nylon face, Brown GF8200H GF8300Hback and side wired, multiple drive Ivory GF8200HI GF8300HIscrews. Matching nylon wallplate Gray GF8200HGY GF8300HGYincluded. Red GF8200HR GF8300HR

White GF8200HW GF8300HWOffice White GF8200HOW GF8300HOW

Note: GFCI type receptacles should not be used in critical care patient areas or for electrical lifesupport equipment applications because of the possibility of power interruption.

SpecificationsTrip Level 4 to 6 mA.Trip Time .025 sec. nominal.Frequency 60 Hz.Voltage 120V AC +10% - 15%.Amperage 15A/20A, 20A Feed Thru.Maximum Interrupting Capacity 2000A.Operating Temperature -35°C to +66°C or

-30°F to +150°F.Maximum Humidity 95%.Listings & Standards Meets UL498 for receptacles, UL943 2003 Class A for GFCIs

UL File E41978.CSA Certified.

Codes Meets all NEC & CEC requirements.

G

NEMA 5-15R15A 125V

UL CSA

W

G

NEMA 5-20R20A 125V

UL CSA1 HP

W

GFR5352AGFR5352IAGFR5352GYAGFR5352WAGFR5352BKAGFR5352OWAGFR5352RAGFR5352AM1GFR5352IAM1GFR5352GYAM1GFR5352WAM1GFR5352BKAM1

GFR5252IA

GFR5350BK

GF8300HI

cschulte
GFR5352A
Page 17: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Phone: (800) 624-6315 www.insulgard.com

ARMOR-GARD® BALULN25 Ballistics Security Glass Clad

Polycarbonate Specification Sheet

PRODUCT DESCRIPTION Bullet Resistant Security Glazing

Nominal Thickness 1.05” (26mm) Weight 11.3 lbs per SF

Available sizes – Any size up to maximum 60” x 96” Dimensional Tolerance: +/-.250

PERFORMANCE • UL Listed Level 3 • 3 shots 44 magnum, 4 1/2 triangle.

GUIDE SPECIFICATION Ballistic resistant glass where shown shall be BALULN25 glass-clad polycarbonate as manufactured byLEXGARD Laminates LLC. Each unit for glass type _____ shall be BALULN25. BALULN Products are designed for applications where ballistics performance is primary and optical characteristics are secondary. Protected side of window is a mar resistant polycarbonate with threat side a glass surface.

Each unit shall have a nominal overall thickness of 1.05".

APPLICABLE STANDARDS • ASTM C 1036-06 • ASTM C 1349-04 • UL752

INSTALLATION geFollow recommended glazing installations as set forth in: • Glass Association of North America Glazing Manual • Glass Association of North America Sealant Manual

Opening Any size up to max. sheet size Rabbet Depth 1 1/4” Edge Engagement 1” Edge Clearance 1/4" Face Clearance 1/8” each face

WARRANTY (Short Version)

LEXGARD Laminates LLC warrants BALULN Series of glass clad polycarbonate against defects in material and workmanship resulting in edge separation or delamination for a period of five (5) year from date of manufacture. (See Warranty Sheet for complete warranty information and specifications).

*Trademark of SABIC Innovative Plastics IP BV

ARMOR-GARD is a registered trademark of LEXGARD Laminates LLC

DS115-0908

Page 18: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Total volume and shelf area are calculated by the Association of Home Appliance Manufacturers’ standards.

AJEQ12DCD GE® 230/208 Volt Built-In Heat and Cool UnitWall Case Dimensions and Installation Information (in inches)

Listed by Underwriters Laboratories

For answers to your Monogram,® GE Profile™ or GE® appliance questions, visit our website at ge.com or call GE Answer Center® service, 800.626.2000.

Specification Created 9/09 390166

Note: When installing slide-out chassis units in through-the-wall applications, keep louvers free. Do not restrict air flow areas.

Perpendicular

230/208V20 Amp

AJCQ12DCD

Premium, Deluxe and Value ModelWall Case Dimensions (in inches)

Note: When installing units in through-the-wall applications.Do not restrict air flow areas.

15-5/8

2616-7/8

Page 19: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Total volume and shelf area are calculated by the Association of Home Appliance Manufacturers’ standards.

Wall Case Dimensions and Installation Information (in inches)

Listed by Underwriters Laboratories

For answers to your Monogram,® GE Profile™ or GE® appliance questions, visit our website at ge.com or call GE Answer Center® service, 800.626.2000.

Specification Created 9/09 390166

AJEQ12DCD GE® 230/208 Volt Built-In Heat and Cool Unit

Installation Information: A finished opening of 26-1/8" x 15-3/4" clear of intrusions is required. Keep clearance of 4" from side walls. Brick veneer or frame walls should have wood studding surrounding case to provide firm anchoring with screws. Case can be fastened directly to brick or block walls with screws sunk in lead expansion shields.

Note: Units should be caulked on all four sides of case to the building exterior to assure building integrity.

Two Wall Cases for Tenant Option Installation When the air conditioner is offered as a tenant option, these wall cases provide protection against outside elements.

RAB47 – includes wall case, exterior grille and steel closure panels.

RAB48 – includes wall case, exterior grille, steel closure panel and two layers of insulation.

Standard Wall Case RAB46 Solid-sided wall case fabricated of galvanized steel with baked enamel finish. Welded areas are coated with a sealing compound to help resist rust and corrosion. Polymer gasket surrounds opening to assure tight weather seal. Aluminum grille (RAG13) is included. Panels on interior and between case and grille provide weather protection prior to installation of chassis.Provide firm anchoring with screws. Case can be fastened directly to brick or block walls with screws sunk in lead expansion shields.

Built-in RAC Installation(Pub. 1-G003 pg. 138) April 30.1993

Make frame if desired or caulkbetween case and siding

15-3/426-1/8

Frame Construction

Brick Block and BrickFrame Construction

Fill open cellswith mortaror insulation

15-3/426-1/8

Lintel

Lintel

OUTSIDE INSIDE16-7/8

Caulking

Drip Rail

Trim Molding(if desired)

Plaster Line

Built-In Room Air ConditionersWall Opening for RAB36/37/38 CaseA finished opening of 26-1/8" x 15-3/4", clear ofintrusions, is required. Keep clearance of 4" fromside walls. Brick veneer or frame walls should havewood studding surrounding case to provide firmanchoring with screws. Case can be fastened directlyto brick or block walls with screws sunk in leadexpansion shields.

Flexible Mounting Position

Built-in RAC Installation(Pub. 1-G003 pg. 138) April 30.1993

Make frame if desired or caulkbetween case and siding

15-3/426-1/8

Frame Construction

Brick Block and BrickFrame Construction

Fill open cellswith mortaror insulation

15-3/426-1/8

Lintel

Lintel

OUTSIDE INSIDE16-7/8

Caulking

Drip Rail

Trim Molding(if desired)

Plaster Line

Built-In Room Air ConditionersWall Opening for RAB36/37/38 CaseA finished opening of 26-1/8" x 15-3/4", clear ofintrusions, is required. Keep clearance of 4" fromside walls. Brick veneer or frame walls should havewood studding surrounding case to provide firmanchoring with screws. Case can be fastened directlyto brick or block walls with screws sunk in leadexpansion shields.

Flexible Mounting Position

Built-in RAC Installation(Pub. 1-G003 pg. 138) April 30.1993

Make frame if desired or caulkbetween case and siding

15-3/426-1/8

Frame Construction

Brick Block and BrickFrame Construction

Fill open cellswith mortaror insulation

15-3/426-1/8

Lintel

Lintel

OUTSIDE INSIDE16-7/8

Caulking

Drip Rail

Trim Molding(if desired)

Plaster Line

Built-In Room Air ConditionersWall Opening for RAB36/37/38 CaseA finished opening of 26-1/8" x 15-3/4", clear ofintrusions, is required. Keep clearance of 4" fromside walls. Brick veneer or frame walls should havewood studding surrounding case to provide firmanchoring with screws. Case can be fastened directlyto brick or block walls with screws sunk in leadexpansion shields.

Flexible Mounting Position

Page 20: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Total volume and shelf area are calculated by the Association of Home Appliance Manufacturers’ standards.

AJEQ12DCD GE® 230/208 Volt Built-In Heat and Cool Unit

Listed by Underwriters Laboratories

For answers to your Monogram,® GE Profile™ or GE® appliance questions, visit our website at ge.com or call GE Answer Center® service, 800.626.2000.

Specification Created 9/09 390166

AJEQ12DCD

Features and Benefits• R-410ARefrigerant• 11,600/11,400CoolingBTU

• 11,600/9,500HeatingBTU

•9.4/9.4EER

• 230/208Volts

•Electroniccontrolswithremote

•Electronicdigitalthermostat

•Four-wayairdirection

•Up-front,washableairfilter

•2cool/2heat/2fanonlyspeeds

•Remotethermostatcapable

• Unitdimensions:14-7/8"Wx24-3/4"Hx19-7/8"D

• ModelAJEQ12DCD–SoftGray

AJEQ12DCD

Page 21: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Acrylic Modified Alkyd Enamel

ALK-200

CPCPB006

Product Information Effective 4/09

Physical Constants: All values are theoretical, depend on color and are Ready-to-Spray. Actual values could vary slightly due to manufacturing variability.

With ALK-201 Without ALK-201

Weight per gallon (US) 7.97 – 10.22 lbs/gal 7.88 – 10.28 lbs/galPercent solids (by weight) 38.29 – 58.32% 34.84 – 56.79%Percent solids (by volume) 31.75 – 42.15% 28.55 – 39.65%Flashpoint (ALK-200R only) 50° F (Pensky Martin) 50° F (Pensky Martin)VOC 4.21 – 5.06 lbs/gal 4.39 – 5.30 lbs/galHAPs Maximum - 3.00 lbs/gal Maximum - 3.2 lbs/galPhoto-chemically reactive Yes Yes

ALK-200 is a fast drying interior/exterior enamel intended for industrial use on properly prepared and/or primed metal surfaces. This topcoat provides a smooth film with excellent hardness in a range of intermediate gloss levels.

Example applications include metal fabrication, castings, cabinets, machinery, and heavy equipment.

Features and benefits:

· Cost-effective performance product · Fast drying for quick production turnaround

· Available in a wide range of colors and gloss

· Apply direct-to-metal or over a compatible primer

· Lead and chrome free

Associated Products:

· ALK-201 Polyurethane Enhancer (optional)

· DX-10-FLT Flattening Paste (optional)

Directions for Use:

Substrate Preparation:

The surface to be coated must be free of all contamination (including dust, dirt, oil, grease, and oxidation). A chemical treatment (or conversion coating) will improve adhesion and performance properties of the finished coat. Variability can occur with substrates, preparation, application method or environment. We recommend that adhesion and system compatibility be checked prior to full application.

Substrate Direct to properly treated substrate

Cold Rolled Steel Very good when proper conversion coatings are appliedHot Rolled Steel Very good when proper conversion coatings are appliedGalvaneal Not Recommended over Zinc SubstratesGalvanized Not Recommended over Zinc SubstratesAluminum Fair when scuff-sandedPlastic / Fiberglass Surface should be free of all contamination. Because of the variability of plastic/fiberglass substrates, coating performance should be confirmed on the actual plastic/fiberglass substrate being used.Note: For improved performance between this topcoat and CPC primers please see the CPC Primer/Topcoat compatibility chart (CPCTB01).

Page 22: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Page 2 CPCPB006

Directions for Use (continued)

Mix Directions:

Blend Ratio: With ALK-201 Without ALK-201 15 : 1 Ready-to-Spray

Pot Life @ 77°F: 10 hours N/A

Spray Viscosity Range: #2 EZ Zahn - 25 – 35 seconds

Reducers: 10% or less of Xylene (Q80), Aromatic 100 (Q50), or MAK (Q70)

Unopened Shelf Life: (each component) 2 years

Application Equipment:Conventional: 1.3 – 1.6 mm needle/nozzle with 45-60 psi at the gunConventional on Pressure Pot: 1.0 – 1.2 mm needle/nozzle with 45-60 psi at the gunHVLP: 1.3 – 1.5 mm needle/nozzle with 10 psi output at the gunHVLP on Pressure Pot: 1.0 – 1.2 mm needle/nozzle with 10 psi output at the gunAirless: Not recommendedAir-Assistd Airless: Not recommendedBrush or Roll: Not recommendedElectrostatic: Addition of 5% MAK (Q70) will help pattern, atomization, and wrap.

Application:Apply: 2 full wet coats Flash 5 – 10 minutes between coats (if needed) Recommended Wet Film Build: 2.8 – 3.3 mils (range)Recommended Dry Film Build: 1.5 – 2.0 mils (range)Coverage (varies by color): 526 – 677 sq. ft. at 1.0 mil dry film per U.S. gallon

Dry Times: Air Dry @ 77°F 50% RH: With ALK-201 Without ALK-201 Dry to Touch 2 hours 15 – 30 minutes Dry to Handle 3 hours* 1 hour* Recoat 3 hours to 4 days Before 6 hours or after 30 hours to 4 days**

Force Dry: Allow 10 minutes air dry before baking to prevent solvent popping 30 minutes @ 180°F / 82°C

* Paint film is not fully cured for 7 days. Drying time listed may vary, depending upon film build, color selection, temperature, humidity and degree of air movement. ** IMPORTANT! If this product is recoated between 6 and 30 hours, lifting of the previous finish will occur. Before 6 hours, the coating is adequately solubilized to prevent lifting, while after 30 hours to 4 days, the cure has progressed to a point where solvent resistance is achieved.

ALK-200

Page 23: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Page 3 CPCPB006

Technical Data*Performance Properties:

Test ASTM Method With ALK-201 Without ALK-201

Pencil Hardness D3363 F – H HB – H

Mandrel D522 PASS PASS

Chip Resistance D3170 5 5 – 6

Gloss - 60°** D523 89 – 91 85 – 89

Adhesion D3359 4B 3B – 4B

In Service Temperature Limit† 240°F 200°F

**Gloss levels can be adjusted using DX-10-FLT to achieve intermediate gloss levels.† As you approach the In Service Temperature Limit, depending on the pigmentation, the color may change, but the film integrity will be maintained until the limit is reached.

Chemical Resistance:

Chemical ASTM D1308 With ALK-201 Without ALK-201

Toluene Slight Stain and Wrinkle Extreme Wrinkle

10% NaOH (Sodium Hydroxide) Pass Stain, Wrinkle, Color Change

10% HCl (Hydrochloric acid) Pass Pass

10% H2SO4 (Sulphuric acid) Pass Pass

Gasoline Slight Stain and Color Change Slight Stain and Wrinkle

Isopropanol Slight Stain Slight Stain

Water Pass Pass

Weather Resistance:

ASTM Method With ALK-201 Without ALK-201

Salt Spray – 100 hours B117

Corrosion Creep D1654 None None

Scribe Blisters D714 8D None

Face Blisters D714 None None

Adhesion D3359 Method A 4A – 5A 5A

Humidity – 100 hours D2247

5 Minute Recovery Adhesion D3359 Method B 4B – 5B 3B – 4B

1 Hour Recovery Adhesion D3359 Method B 4B 3B

24 Hour Recovery Adhesion D3359 Method B 5B 3B – 4B

QUV-UVA: 60° angle D4587

200 hour retention D523 100% 91 – 100%

500 hour retention D523 98 – 100% 86 – 100%

QUV-UVB: 60° angle D4587

200 hour retention D523 95 – 100% 91 – 99%

All tests results assume proper cure and preparation of test substrates. Unless otherwise stated, all results were obtained spraying product direct to metal on Bonderite 1000.* The application and performance property data above are believed to be reliable based on laboratory findings. It is for the buyer to satisfy itself on the suitability of the product for its particular use. Variation in environment, procedures of use, or extrapolation of data may cause unsatisfactory results.

Miscellaneous: Gloss Level ALK-200 - % by Volume DX-10-FLT - % by Volume

Flattening ALK-200 using DX-10-FLT

Full Gloss 100 0Semi-gloss 83 17Satin 81 19Eggshell 78 22Flat 74 26

This product should not be applied directly to Zinc surfaces

ALK-200

Page 24: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

ALK-200 Acrylic Modified Alkyd Enamel

PPG Industries PPG Canada Inc. 19699 Progress Drive 2301 Royal Windsor Drive Strongsville, OH 44149 Mississauga, Ontario L5J 1K5 1-800-647-6050 1-888-310-4762

© 2009 PPG Industries www.ppgcommercialcoatings.com Part No. CPCPB006 4/09

Safety: These materials are designed for application only by professional, trained personnel, using proper equipment under controlled conditions and are not intended for sale to the general public. Safe application of paints and coatings requires knowledge of equipment, materials and individual training. Directions and precautionary information on both equipment and products should be carefully read and strictly observed for personal safety and property protection. Consideration must be given to eliminate conditions, which may generate hazardous atmospheres during spray application or subject operators or bystanders to injury or illness. Special precautions must be taken when utilizing spray equipment, particularly airless equipment. High-pressure injection of coatings into the skin by airless equipment may cause serious injury requiring immediate medical attention at a hospital. Treatment advice may also be obtained from Poison Centers. Air quality should be maintained with adequate ventilation; applicators can achieve additional protection by wearing respirators and other protective garments such as gloves and overalls. In all cases, wear protective eye equipment. During the application of all coatings materials, all flames, welding and smoking must be prohibited. Explosion proof equipment must be used when coating these materials in confined areas.

PRECAUTIONARY INFORMATIONBefore using the products listed herein, carefully read each product label and follow directions for its use. Please read and observe all warnings and precautionary information on all product labels. Prevent all contact with skin and eyes and breathing of vapors and spray mist. Repeated inhalation of high vapor concentrations may cause a series of progressive effects including irritation of the respiratory system, permanent brain and nervous system damage and possible unconsciousness and death in poorly ventilated areas. Eye watering, headaches, nausea, dizziness and loss of coordination are indications that solvent levels are too high. Intentional misuse by deliberately concentrating and inhaling the contents can be harmful or fatal.

KEEP OUT OF THE REACH OF CHILDREN

MEDICAL RESPONSEEmergency Medical or Spill Control Information (412) 434-4515; CANADA (514) 645-1320 Have label information available.

Material Safety Data Sheets for the PPG products mentioned in this publication are available through your PPG Distributor. For additional information regarding this product, see the MSDS AND LABEL information.

Page 25: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

MATERIAL SAFETY DATA SHEET

SECTION 1 - PRODUCT AND COMPANY INFORMATION

PPG Industries, Inc. One PPG Place

Pittsburgh, PA 15272

TECHNICAL INFORMATION:

(440) 572-2800 (STRONGSVILLE OHIO) 8:00 a.m. - 5:00 p.m. EST

PRODUCT SAFETY/MSDS INFORMATION: (412) 492-5555 7:00 a.m. - 4:30 p.m. ESTProduct ID: Q1275-144 (0808-F1)PRODUCT NAME: ALK-200 SEMI-GLOSS BLACKSYNONYMS: None ISSUE DATE: 06/14/2005EDITION NO.: 1 CHEMICAL FAMILY:

Alkyd

EMERGENCY OVERVIEW: Combustible. Keep away from heat, sparks, flames, and other sources of

ignition. Do not smoke.CAUSES SEVERE EYE IRRITATION. MAY CAUSE MODERATE SKIN IRRITATION. MAY BE HARMFUL IF

ABSORBED THROUGH THE SKIN.VAPOR AND/OR SPRAY MIST HARMFUL IF INHALED. VAPOR IRRITATES EYES, NOSE, AND

THROAT.HARMFUL OR FATAL IF SWALLOWED.

SECTION 2 - COMPOSITION INFORMATIONThe following ingredient(s) marked with an "x" are considered hazardous under applicable U.S. OSHA and/or Canadian WHMIS regulations. If no ingredients are listed, then there are no U.S. OSHA and/or Canadian WHMIS hazardous ingredients in this product.

Material/ CAS Number

Percent Hazardous

XYLENES 1330-20-7

15 - 40 X

METHYL ETHYL KETONE 78-93-3

7 - 13 X

ETHYL BENZENE 100-41-4

3 - 7 X

2-BUTOXY ETHANOL 111-76-2

3 - 7 X

1-METHOXY-2-PROPYL ACETATE 108-65-6

1 - 5 X

N-BUTYL ACETATE 123-86-4

1 - 5 X

CARBON BLACK 1333-86-4

0.1-1.0 X

(As Glycol ethers) 111-76-2

* X See Sections 8 and 15 for

information.

SECTION 3 - HAZARDS IDENTIFICATION

ACUTE OVEREXPOSURE EFFECTS EYE CONTACT:Causes severe eye irritation. Redness, itching, burning sensation and visual disturbances may indicate excessive eye contact. SKIN CONTACT:May cause moderate skin irritation. Dryness, itching, cracking, burning, redness, and swelling are conditions associated with excessive skin contact.SKIN ABSORPTION:May be harmful if absorbed through the skin.

INHALATION:Vapor and/or spray mist harmful if inhaled. Vapor irritates eyes, nose, and throat. INGESTION:Harmful or fatal if swallowed. SIGNS & SYMPTOMS OF OVEREXPOSURE:Repeated exposure to high vapor concentrations may cause irritation of the respiratory system and permanent brain and nervous system damage. Eye watering, headaches, nausea, dizziness and loss of coordination are indications that solvent levels are too high. Intentional misuse by deliberately concentrating and inhaling the contents can be harmful or fatal. Dryness, itching, cracking, burning, redness, and swelling are conditions associated with excessive skin contact. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Not applicable. CHRONIC OVEREXPOSURE EFFECTS Avoid long-term and repeated contact.Repeated exposure to vapors above recommended exposure limits (see Section 8) may cause irritation of the respiratory system and permanent brain and nervous system damage. Intentional misuse by deliberately concentrating and inhaling the contents can be harmful or fatal. High exposures to xylenes in some animal studies have been reported to cause health effects on the developing embryo and fetus. These effects were often at levels toxic to the mother. The effects of long-term, low level exposures to this product have not been determined. Safe handling of this material on a long-term basis should emphasize the prevention of all contact with this material to avoid any effects from repetitive acute exposures. See Section 11, of this MSDS for a detailed list of chronic health effects information available on individual ingredients in this product.

SECTION 4 - FIRST AID MEASURESIf ingestion, irritation, any type of overexposure or symptoms of overexposure occur during or persists after use of this product, contact a POISON CONTROL CENTER, EMERGENCY ROOM OR PHYSICIAN immediately; have Material Safety Data Sheet information available.EYE CONTACT: Remove contact lens and pour a gentle stream of warm water through the affected eye for at least 15 minutes. If irritation persists, contact a poison control center, emergency room, or physician as further treatment may be necessary. SKIN CONTACT: Run a gentle stream of water over the affected area for 15 minutes. A mild soap may be used if available. If any symptoms persist, contact a poison control center, emergency room, or physician as further treatment may be necessary. INHALATION:Remove from area to fresh air. If symptomatic, contact a poison control center, emergency room or physician for treatment information. INGESTION:Gently wipe or rinse the inside of the mouth with water. Sips of water may be given. Never give anything by mouth to an unconscious person. Contact a poison control center, emergency room or physician right away as further treatment may be necessary.

SECTION 5 - FIRE FIGHTING MEASURES FLAMMABLE PROPERTIES FLASHPOINT: 101 Degrees F ( 38 Degrees C) FLASHPOINT TEST METHOD:Pensky-Martens Closed Cup UEL: Not Available. LEL: 1.6 AUTOIGNITION TEMPERATURE:Not Available.

__________________________________________________________________Page 1 of 4

01-800-00-21-400 (Mexico)

0532-3889090 (China)

EMERGENCY PHONE NUMBERS (24 hours/day):

(514) 645-1320 (Canada)

(412) 434-4515 (U.S.)

Page 26: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

_______________________________________________________________________________________________________________PPG Industries, Inc.

One PPG Place Pittsburgh, PA 15272

Product ID: Q1275-144 (0808-F1)PRODUCT NAME: ALK-200 SEMI-GLOSS BLACK

EXTINGUISHING MEDIA:Use National Fire Protection Association (NFPA) Class B extinguishers (carbon dioxide, dry chemical, or universal aqueous film forming foam) designed to extinguish NFPA Class II combustible liquid fires. Water spray may be ineffective. Water spray may be used to cool closed containers to prevent pressure build-up and possible autoignition or explosion when exposed to extreme heat. PROTECTION OF FIREFIGHTERS:Fire-fighters should wear self-contained breathing apparatus and full protective clothing. UNUSUAL FIRE AND EXPLOSION HAZARDS:When this product is used, the overspray and other combustible materials such as paint booth filters, rags, masking materials, etc., contaminated by coating material are subject to spontaneous combustion. Wetting the contaminated materials and not packing them tightly together in refuse containers will minimize the potential for this to occur. Keep this product away from heat, sparks, flame, and other sources of ignition (i.e., pilot lights, electric motors, static electricity). Invisible vapors can travel to a source of ignition and flash back. Do not smoke while using this product. Keep containers tightly closed when not in use. Closed containers may explode when overheated. Do not apply to hot surfaces. Toxic gases may form when this product comes in contact with extreme heat. May produce hazardous decomposition products when exposed to extreme heat. Extreme heat includes, but is not limited to, flame cutting, brazing, and welding.

SECTION 6 - ACCIDENTAL RELEASE MEASURE STEPS TO BE TAKEN IF MATERIAL IS RELEASED OR SPILLED:Provide maximum ventilation. Only personnel equipped with proper respiratory, skin, and eye protection should be permitted in the area. Remove all sources of ignition. Take up spilled material with sand, vermiculite, or other noncombustible absorbent material and place in clean, empty containers for disposal. Only the spilled material and the absorbant should be placed in this container.

SECTION 7 - HANDLING AND STORAGEPRECAUTIONS TO BE TAKEN DURING HANDLING AND STORAGE:Vapors may collect in low areas. If this material is part of a multiple component system, read the Material Safety Data Sheet(s) for the other component or components before blending as the resulting mixture may have the hazards of all of its parts. Containers should be grounded when pouring. Avoid free fall of liquids in excess of a few inches. STORAGE:Do not store above 120 degrees F.(48 degrees C.). Store large quantities in buildings designed and protected for storage of NFPA Class II combustible liquids.

SECTION 8 - EXPOSURE CONTROLS & PERSONAL PROTECTIONENGINEERING CONTROLS: Provide general dilution or local exhaust ventilation in volume and pattern to keep the concentration of ingredients listed in Section 8 below the lowest suggested exposure limits, the LEL below the stated limit, and to remove decomposition products during welding or flame cutting.

PERSONAL PROTECTIVE EQUIPMENT EYES:Wear chemical-type splash goggles and full face shield when possibility exists for eye contact due to splashing or spraying liquid, airborne particles, or vapors.

SKIN/GLOVES: Wear protective clothing to prevent skin contact. Apron and gloves should be constructed of: butyl rubber. No specific permeation/degradation testing have been done on protective clothing for this product. Recommendations for skin protection are based on infrequent contact with this product. For frequent contact or total immersion, contact a manufacturer of protective clothing for appropriate chemical impervious equipment. Clean contaminated clothing and shoes. RESPIRATOR:Overexposure to vapors may be prevented by ensuring proper ventilation controls, vapor exhaust or fresh air entry. A NIOSH- approved air purifying respirator with the appropriate chemical cartridges or a positive-pressure, air-supplied respirator may also reduce exposure. Read the respirator manufacturer's instructions and literature carefully to determine the type of airborne contaminants against which the respirator is effective, its limitations, and how it is to be properly fitted and used. Provide general dilution or local exhaust ventilation in volume and pattern to keep the concentration of ingredients listed in Section 2 below the lowest suggested exposure limits, the LEL below the stated limit, and to remove decomposition products during welding or flame cutting.GENERAL HYGIENE - ESTABLISHED EXPOSURE LIMITS If Threshold Limit Values (TLVs) have been established by ACGIH, OSHA, Ontario or PPG, they will be listed below. These limits are intended for use in the practice of industrial hygiene as guidelines or recommendations in the control of potential workplace health hazards. These limits are not a relative index of toxicity and should not be used by anyone without industrial hygiene training.

Material/ CAS Number

Percent ACGIH TLV ACGIH STEL

OSHA PEL OSHA STEL

XYLENES 1330-20-7

15 - 40 100 ppm 150 ppm 100 ppm 150 ppm

METHYL ETHYL KETONE 78-93-3

7 - 13 200 ppm 300 ppm 200 ppm 300 ppm

ETHYL BENZENE 100-41-4

3 - 7 100 ppm 125 ppm 100 ppm 125 ppm

2-BUTOXY ETHANOL 111-76-2

3 - 7 20 PPM Not established

S- 25 ppm Not established

N-BUTYL ACETATE 123-86-4

1 - 5 150 PPM 200 ppm 150 ppm 200 ppm

CARBON BLACK 1333-86-4

0.1-1.0 3.5 mg/m3 Not established

3.5 mg/m3 Not established

(As Glycol ethers) 111-76-2

* Not Listed Not Listed Not Listed Not Listed

Key: OSHA=Occupational Safety and Health Administration; PEL=Permissable Exposure Limit; Ceiling=PEL Ceiling Limit; STEL=PEL Short-Term Exposure Limit; Skin=OSHA Skin Designation.

__________________________________________________________________Page 2 of 4

Page 27: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

_______________________________________________________________________________________________________________PPG Industries, Inc.

One PPG Place Pittsburgh, PA 15272

Product ID: Q1275-144 (0808-F1)PRODUCT NAME: ALK-200 SEMI-GLOSS BLACK

Material/

CAS NumberPercent Ontario

TWAOntario STEL

PPG IPEL PPG STEL

XYLENES 1330-20-7

15 - 40 100 ppm 150 ppm Not established

Not established

METHYL ETHYL KETONE 78-93-3

7 - 13 200 ppm 300 ppm Not established

250 PPM

ETHYL BENZENE 100-41-4

3 - 7 100 ppm 125 ppm Not established

Not established

2-BUTOXY ETHANOL 111-76-2

3 - 7 S- 20 PPM Not established

Not established

Not established

1-METHOXY-2-PROPYL ACETATE

108-65-6

1 - 5 50 PPM Not established

100 ppm Not established

N-BUTYL ACETATE 123-86-4

1 - 5 150 ppm 200 ppm Not established

Not established

CARBON BLACK 1333-86-4

0.1-1.0 3.5 mg/m3 Not established

Not established

Not established

(As Glycol ethers) 111-76-2

* Not Listed Not Listed Not established

Not established

Key: ACGIH=American Conference of Governmental Industrial Hygienists; OSHA=Occupational Safety and Health Administration; TLV=Threshold Limit Value; TWA=Time Weighted Average; PEL=Permissible Exposure Limit; IPEL=Internal Permissible Exposure Limit; Ceiling=TLV or PEL Ceiling Limit; STEL=TLV or PEL Short-Term Exposure Limit; Skin= Skin Absorption Designation. [C- Ceiling Limit; S-Potential Skin Aborption; R-Respirable Dust]Additional Information Not applicable.

SECTION 9 - PHYSICAL & CHEMICAL PROPERTIES (FORMULA VALUES, NOT SALES SPECIFICATIONS)

SPECIFIC GRAVITY: .949 PHYSICAL STATE: LiquidPercent Solids: 39.89Percent Volatile by Volume: 66.000pH: Not available.ODOR THRESHOLD: Not available. Vapour Pressure: 20.4 mmHgODOR/APPEARANCE: Viscous liquid with an odor

characteristic of the solvents listed in Section 2.

VAPOR DENSITY: HEAVIER THAN AIREvaporation Rate: 174 BOILING POINT OR RANGE: 172 - 401Degrees FFreezing Point or Range: Not Applicable. Melting Point or Range(°C): Not Applicable. Partition coefficient (n-octanol/water)

Not Applicable.

WEIGHT PER GALLON: 7.91 (U.S.) / 9.4 (IMPERIAL)

SECTION 10 - STABILITY AND REACTIVITY STABILITY:This product is normally stable and will not undergo hazardous reactions. CONDITIONS TO AVOID:None Known. INCOMPATIBLE MATERIALS:Avoid contact with strong alkalies, strong mineral acids, or strong oxidizing agents. HAZARDOUS POLYMERIZATION:None Known.HAZARDOUS DECOMPOSITION PRODUCTS:- Carbon monoxide - Carbon dioxide - Lower molecular weight polymer fractions

SECTION 11 - TOXICOLOGICAL INFORMATIONACUTE TOXICITY

Material/ CAS Number

Percent ORAL LD50 (g/kg)

DERMAL LD50 (g/kg)

INHALATION LC50 (mg/l)

XYLENES 1330-20-7

15 - 40 4.30 g/kg 1.70 g/kg 21.88 mg/L. 4 h

METHYL ETHYL KETONE 78-93-3

7 - 13 2.74 g/kg 13.00 g/kg Not Available

ETHYL BENZENE 100-41-4

3 - 7 3.50 g/kg 17.80 g/kg Not Available

2-BUTOXY ETHANOL 111-76-2

3 - 7 .47 g/kg .22 g/kg 2.18 mg/L. 4 h

1-METHOXY-2-PROPYL ACETATE

108-65-6

1 - 5 8.53 g/kg Not Available Not Available

N-BUTYL ACETATE 123-86-4

1 - 5 10.77 g/kg 17.60 g/kg Not Available

CARBON BLACK 1333-86-4

0.1-1.0 15.40 g/kg 3.00 g/kg Not Available

CHRONIC TOXICITY Target Organs:- Bone marrow and blood tissues - Blood - Carcinogen - Kidney - Liver - Embryotoxin - Teratogen - Brain - Central nervous system - Lung

Mutagenicity Toxicity:This has not been tested for this product.Reproductive Toxicity:This has not been tested for this product.

SUPPLEMENTAL HEALTH INFORMATION: Material/

CAS Number

PercentIngredient Specific Animal Data:

METHYL ETHYL

KETONE 78-93-3

7 - 13 This product contains methyl ethyl ketone (MEK). MEK has been shown to cause minor embryotoxic/fetotoxic effects in laboratory animals exposed for prolonged periods at high concentrations via inhalation. The potential for human exposure to high concentrations is expected to be low due to the irritating effects of MEK at low concentrations.

ETHYL BENZENE 100-41-4

3 - 7 Ethylbenzene has been reported by NTP to cause cancer in laboratory animals following a chronic (2 year) inhalation exposure. Dose levels of 75, 250 and 750 ppm were used, with evidence of carcinogenicity found in the kidneys of rats and the lung and liver of mice at 750 ppm. The No Observed Effect Level (NOEL) was 75 ppm. The relevance of these findings to humans is uncertain, but appropriate safeguards should be employed to reduce or eliminate inhalation exposure to ethylbenzene.

2-BUTOXY ETHANOL 111-76-2

3 - 7 This product contains an ethylene series glycol ether and/or acetate which has been shown to cause adverse effects on the kidneys, liver, blood and/or blood-forming tissue. In a two-year NTP inhalation study, there was no significant increase in the incidence of any type of tumor in rats exposed to 2-butoxy ethanol at concentrations up to 125 ppm except a questionable trend in the incidence of adrenal gland tumors in female rats. When mice were exposed to concentrations of 62.5, 125, and 250 ppm, there was some evidence of carcinogenicity found in the liver of male mice and the forestomach of female mice at 250 ppm.

CARBON BLACK

1333-86-4

0.1-1.0 This product contains carbon black which has been rated an IARC 2B carcinogen due to animal data.

SECTION 12 - ECOLOGICAL INFORMATION

POTENTIAL ENVIRONMENTAL EFFECTS

__________________________________________________________________Page 3 of 4

Page 28: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

_______________________________________________________________________________________________________________PPG Industries, Inc.

One PPG Place Pittsburgh, PA 15272

Product ID: Q1275-144 (0808-F1)PRODUCT NAME: ALK-200 SEMI-GLOSS BLACK

Ecotoxicity: No Information Available.

ENVIRONMENTAL FATE Mobility: No Information Available.Biodegradation: No Information Available.Bioaccumulation: No Information Available.

PHYSICAL/CHEMICAL

Hydrolysis: No information availablePhotolysis: No information available

SECTION 13 - DISPOSAL CONSIDERATIONSProvide maximum ventilation, only personnel equipped with proper respiratory and skin and eye protection should be permitted in the area. Take up spilled material with sawdust, vermiculite, or other absorbent material and place in containers for disposal. Waste material must be disposed of in accordance with federal, state, provincial and local environmental control regulations. Empty containers should be recycled by an appropriately licensed reconditioner/salvager or disposed of through a permitted waste management facility. Additional disposal information is contained on the Environmental Data Sheet for this product, which can be obtained from your PPG representative.

SECTION 14 - TRANSPORTATION INFORMATIONProper Shipping Name: NOT AVAILABLENOS Technical Name: NOT AVAILABLEHazard Class: N.A. Subsidiary Class(es): N.A.UN Number: N.A.Packing Group: N.A.

USA - RQ Hazardous Substances: NOT AVAILABLE USA-RQ Hazardous Substance Threshold Ship Weight:

NOT AVAILABLE

Marine Pollutant Name: NOT AVAILABLE

SECTION 15 - REGULATORY INFORMATION INVENTORY STATUS U.S. TSCA: This product and/or all of its components are listed on the U.S. TSCA Inventory or is otherwise exempt from TSCA Inventory reporting requirements.FEDERAL REGULATIONS US Regulations

Material/ CAS Number

PercentCERCLA HS -

RQ (LBS)SARA EHS-TPQ (LBS)

SARA 313

XYLENES 1330-20-7

15 - 40 100 lbs Not Listed Listed

METHYL ETHYL KETONE 78-93-3

7 - 13 5000 lbs Not Listed Listed

ETHYL BENZENE 100-41-4

3 - 7 1000 lbs Not Listed Listed

2-BUTOXY ETHANOL 111-76-2

3 - 7 Not Listed Not Listed Not Listed

1-METHOXY-2-PROPYL ACETATE

108-65-6

1 - 5 Not Listed Not Listed Not Listed

N-BUTYL ACETATE 123-86-4

1 - 5 5000 lbs Not Listed Not Listed

CARBON BLACK 1333-86-4

0.1-1.0 Not Listed Not Listed Not Listed

(As Glycol ethers) 111-76-2

* Not Listed Not Listed Listed

SARA 311/312 Health (acute): YesHealth (chronic): YesFire (flammable): YesPressure: NoReactivity: NoWHMIS HAZARD CLASS: - Class B, Division 6 - Class D, Division 2, Subdivision A - Class D, Division 2, Subdivision B - Class D, Division 1, Subdivision B

STATE/PROVINCIAL REGULATIONS CALIFORNIA PROP. 65: WARNING: This product contains a chemical known to the State of California to cause cancer.Additional Information

Material/ CAS Number

PercentIARC

Group 1(Kno

wn Human Carc.)

IARC Group

2A (Proba

ble Carc.)

IARC 2B (

Suspected

Carc.)

ACGIH Carc.

NTP Known Carc.

OSHA Carc.

ETHYL BENZENE 100-41-4

3 - 7 N N Y N N Y

CARBON BLACK 1333-86-4

0.1-1.0 N N Y N N Y

Key: IARC- International Agency on the Research of Cancer; ACGIH- American Conference of Governmental Industrial Hygienists; NTP- National Toxicology Program *Denotes chemical as NTP Known Carcinogen; + Denotes NTP Possible Carcinogen; OSHA-Occupational Safety and Health Administration.

SECTION 16 - OTHER INFORMATION

Hazard Rating Systems NFPA Rating: 2 20HMIS Rating: 2*20 Rating System: 0=Minimal, 1=Slight, 2=Moderate, 3=Serious, 4=Severe, *=Chronic Effects.

HMIS=Hazardous Materials Identification System; NFPA=National Fire Protection Association;

Safe handling of this product requires that all of the information on the MSDS be evaluated for specific work environments and conditions of use.

PREPARED BY: Product Safety DepartmentREASON FOR REVISION: Date. Edition.Updated MSDS format. This Material Safety Data Sheet has been prepared in accordance with Canada's Workplace Hazardous Materials Information System (WHMIS) and the OSHA Hazard Communication Standard (29 CFR 1910.1200), the supplier notification requirements of SARA Title III, Section 313 and other applicable right-to-know regulations. Additional environmental information is contained on the Environmental Data Sheet for this product, which can be obtained from your PPG representative. Q1275-144 001002 (00348496.001)(06/13/05)040615, 001, 0808

*** END OF MSDS ***

__________________________________________________________________Page 4 of 4

Page 29: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

FILE: Distribution Products Catalog

QO

®

Circuit Breaker Load Centers

Class 1130

October 1995

CONTENTSDescription Class Pages

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1130 . . . . . . . . . . . . . . . . . . . . .2-11Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1130 . . . . . . . . . . . . . . . . . . . .12-17Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1130 . . . . . . . . . . . . . . . . . . . .18-19Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1130 . . . . . . . . . . . . . . . . . . . .20-22

cschulte
Porta King Building Systems Standard Load Center Submittal Package Model QO112M100
Page 30: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO

®

Circuit Breaker Load Centers

2

Type

Circuit breaker load centers for use on ac systems. Underwrit-ers Laboratories Inc. Listed under File E-6294 (Panelboards).Federal Specifications W-P-115c, Type 1, Class 2. QO, QOT,QO-PL, QO-GFI, (UL Class A Ground Fault Protection) andQO-EPD (30 mA Equipment Ground Fault Protection) branchcircuit breakers.

Services

120Vac 1Ø2W120/240Vac 1Ø3W240Vac Delta 3Ø3W208Y/120Vac 3Ø4W240/120Vac Delta 3Ø4W240Vac Corner Grounded Delta 3Ø3W

Ratings

Main Lugs 1Ø 30-400A3Ø 60-400A

Main Circuit Breaker 1Ø 100-400A3Ø 100-400A

Branch Circuit Breakers

c

For use with 150-225A load centers only.

q

For use with 300A and 400A load centers only. Requires PK3CA mounting kit. Order separately.

j

Breaker takes 8 pole spaces – 4 on each side of interior.

10,000 AIR

QO1-Pole 10-70A2-Pole 10-125A3-Pole 10-100A

QOT 1-Pole 15-20A

QO-EPD 1-Pole 15-30A2-Pole 15-30A

QO-GFI 1-Pole 15-30A2-Pole 15-60A

QO-HID1-Pole 15-50A2-Pole 15-50A3-Pole 15-30A

QO-PL1-Pole 10-20A, 30A2-Pole 10-60A3-Pole 15-60A

QO-SWN 2-Wire 10-50A3-Wire 10-50A

QOK 1-Pole 10-30A

Q1 2-Pole 150A

cj

Application Data

QO QO QO1-Pole 2-Pole 3-Pole

QOK QO-GF1 QO-GF11-Pole 1-Pole 2-Pole

QO-PL QO-EPD2-Pole 1-Pole

22,000 AIR

QO-VHGFI 1-Pole 15-30A

QO-VH1-Pole 15-30A2-Pole 15-125A3-Pole 15-100A

QOB-VH 2-Pole 150A

q

3-Pole 110-150A

q

42,000 AIR

QOH 2-Pole 40-125A

65,000 AIR

QH1-Pole 15-30A2-Pole 15-30A3-Pole 15-30A

Page 31: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO

®

Circuit Breaker Load Centers

3

Indoor Enclosures NEMA Type 1

Welded sheet steel with knockouts at top, bottom, back andsides.

Finish: Gray baked enamel, electrodeposited over cleanedphosphatized steel.

Most 100A-225A indoor enclosures are 14.25" wide. (SeeDimension Page 18.)

300A and 400A indoor enclosures are 20" wide.

Indoor Covers

Doors to cover circuit breaker handles, except on 2–4, 6–12, and 8–16 circuit models.

Shutter type twistouts.

Flush and service covers available, merchandised sepa-rately.

Flush covers have automatic flush adjustment.

Field installed door lock provisions available on most covers.

QOFP filler plates available for all covers.

Triple lead cover screws for fast cover installation.

Rainproof Enclosures, NEMA Type 3R

Complete enclosure includes interior trim and door.

Welded, galvannealed steel.

Finish: Gray baked enamel, electrodeposited over cleaned,phosphatized, galvannealed steel.

RB devices have provisions for interchangeable bolt-on hub.

Bolt-on Hubs

Hubs available from

3

4

" to 4" conduit size.

No gasket required with hubs from

3

4

" to 2

1

2

" when used on“RB’’ type load centers.

3" to 4" hubs for field cut openings.

Application Data

Page 32: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO

®

Circuit Breaker Load Centers

4

Class CTL

UL Listed Class CTL load centers.

Interior breaker mounting rails have slots to accept tandemcircuit breakers.

Meets paragraph 384-15 of the NEC.

Phasing

Load centers have distributed phase bussing.

Most branch breakers can be mounted in any position.

Line Lugs

All lugs suitable for 75

°

C copper or aluminum wires. (SeeTechnical Information Pages 12-17).

Main lugs and main circuit breaker load centers have wirebinding screw tightening values on wiring diagrams andbreaker labels.

Neutral Assemblies

All lugs suitable for copper or aluminum wire. (See Techni-cal Information Pages 12-17).

Branch neutral terminals suitable for #14 to #4 AWG cop-per and #12 to #4 AWG aluminum wire.

Three #14 to 1/0 AWG copper and #14 to #6 AWG alumi-num terminals provided on 12-42 circuits, 100-225A loadcenters.

Suitable lug provided on neutrals for termination of ground-ing conductor.

All unused neutral terminals may be used to terminate bareor green equipment grounding conductors when load cen-ter is used as service equipment – as follows:

one or two #14 through #12 copper,one or two #12 through #10 aluminum.

Application Data

Page 33: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO

®

Circuit Breaker Load Centers

5

UL Listed

Suitable for use as service equipment.

75

°

C wire rating.(See Technical Information Pages 12-17)

Short Circuit Current Rating

Main lugs up to 10,000 Amperes. (See Technical Information Pages 12-17)

Interior

Tin plated aluminum bus.

Tin plated copper bus available option on 6-12 and 8-16 circuit load centers.

Mains

Factory installed main lugs.

Top mains positioning only.

Top or bottom feed.

Backfed main breaker can be field-installed in 6-12 and 8-16 load centers using PK2MB retaining kit.

Cover

Flush or surface cover included with load centers.

Cover with door available option on 6-12 and 8-16 circuitload centers.

2 Through 16 Circuit, 30 Through 100 Amperes, Fixed MainsApplication Data

Page 34: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO

®

Circuit Breaker Load Centers

6

UL Listed

Suitable for use as service equipment.

75

°

C wire rating.(See Technical Information Pages 12-17).

Short Circuit Current Rating

Main lugs up to 65,000 Amperes. (Depends on lowestinterrupting rating of branch breakers installed.)

Main breaker 22,000 AIR standard.

22,000 AIR main breaker kits (Refer to Page 7 MainBreaker Kits).(See Technical Information Pages 12-17).

Interior

Shielded, one-piece tin plated copper bus.

Removable interior with single, captive mounting screw.

Split branch neutral with up to 50% more terminations thanrequired.

Multiple mounting locations for equipment ground bar kits –left, right, and bottom.

Main lugs load centers have equipment ground bar kitsincluded (not factory installed.)

Mains

Main Breaker Main Lug

Factory installed main lugs convertible to main breaker

Factory installed main breaker convertible to main lugs

Top or bottom mains positioning. Rotate entire load center 180degrees. (See Technical Information Pages 12-17).

Load CenterAmperage

Main BreakerKit Amperage

125 50–125150 150200 150-200225 150-225

Main BreakerAmperage

Main LugKit Amperage

Load CenterAmperage

100 125 100125 125 125150 225 150200 225 200225 225 225

Single Phase, 12 Through 42 Circuit, 100 Through 225 Amperes, Convertible MainsApplication Data

Page 35: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO

®

Circuit Breaker Load Centers

7

Covers

Flush and surface covers merchandised separately.

Flush covers have spring loaded interior trim for automaticflush adjustment.

Positive action, easy open door latch.

QO120M100

Main Lugs Kits:

Field installable in main breaker or main lugs load centers.

QOL125 QOL225

QOL125 kit for use in 100 through 125 Ampere load centers.

QOL225 kit for use in 150 through 225 Ampere load centers.

Main Breaker Kits:

Field installable in main lugs or main breaker load centers.

22,000 AIR main breaker kit 50 thorugh 225 Amperesseries rated with 10,000 AIR branch circuit breakers.

Field Installable Main Circuit Breaker (Convertible Load Centers Only)

k

Do not exceed the load center mains rating.

j

Wire range listed for QOM circuit breaker kits is the wire range of that circuit breaker. To find out maximum wire size permitted in a particular load center per UL, see Main Wire Size on Pages 12-16.

f

Add suffix 1021 for shunt trip.

Main

k

Circuit Breaker Amp Rating

Use With Convertible Load

Center Mains Rating

22,000 AIR Lug Wire Size

j

AWG/kcmilAl or Cu

Main Circuit Breaker

QOM1 Frame Size

50 100-125 QOM50VH

#4-2/0

60 100-125 QOM60VH70 100-125 QOM70VH80 100-125 QOM80VH90 100-125 QOM90VH

100 100-125 QOM100VH110 125 QOM110VH125 125 QOM125VH

QOM2 Frame Size

f

100 150-225 QOM2100VH

#4-300

125 150-225 QOM2125VH150 150-225 QOM2150VH175 200-225 QOM2175VH200 200-225 QOM2200VH225 225 QOM2225VH

QOM1 Main Frame Size50-125 Amperes

QOM2 Main Frame Size150-225 Amperes

Single Phase, 12 Through 42 Circuit, 100 Through 225 Amperes, Convertible MainsApplication Data

Page 36: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO

®

Circuit Breaker Load Centers

8

Main Lugs Recreational Vehicle Load Centers

QO2L30TTS

• UL Listed and CSA Certified.• Available single phase, 2 and 3 wire.• Factory installed equipment ground bar.• Covers included with load centers.

Main Breaker Mobile Home Load Centers

• Combination flush/surface cover included with load centers.

• Factory installed equipment gorund bar.• Top or bottom feed on incoming service by rotating com-

plete load center 180 degrees.

Main Circuit Breaker with Feed-thru Lugs

QO1816M200FTRB

• Available rainproof enclosure only.• 125, 150 and 200 Ampere mains rating.• 125, 150 and 200 Ampere sub-feed lugs.• Space for up to 8 single pole circuit breakers.

Generator Panel

• Connects utility and standby power to installed branch circuits.

• Includes two factory-installed 2-pole main circuit breakerstied together with mechanical interlock.

• 30A and 60A main breaker versions.• Supply up to 8 branch circuits using tandem circuit

breakers.• Available indoor enclosure only.• Cover with door included.

Special PurposeApplication Data

Page 37: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

9

UL Listed• Suitable for use as service equipment. • 75°C wire rating.

(See Technical Information Page 15).Short Circuit Current Rating

• Main lugs up to 65,000 Amperes. (Depends on lowestinterrupting rating of branch breakers installed).

• Main circuit breaker up to 225A 22,000 Amperes standard– optional up to 65,000 Amperes for 100A to 225A mainbreakers.

• Main circuit breaker 300A and 400A up to 42,000 Amperes.(See Technical Information Page 15).

Mains• Factory installed main lugs or main circuit breaker. • Main neutral terminal located next to phase terminals on

125 through 225 Ampere main circuit breaker devices. • Top or bottom feed. (See Technical Information Page 15).• Fully convertible from main circuit breaker to fixed main

lugs. (100 through 225 Amp).• 100 Ampere maximum back fed main QO circuit breaker.

Requires use of retaining kit PK3MB.

Cover • Flush and surface covers merchandised separately.• Flush covers have spring loaded interior trim for automatic

flush adjustment.• Positive action, easy open door latch.

Interior • Shielded one piece plated copper bus. 100 through 225

Ampere.• Removable interior with single, captive mounting screw,

100 through 225 Ampere. (Indoor only).• Main lugs load centers have equipment ground bar kits

included (not factory installed).

Branch Neutral Termination• Suitable for copper or aluminum wire.• Terminals suitable for #14 to #4 AWG copper and #12 to #4

AWG aluminum wire.• Positioned on both sides of mains compartment.• Slot/square drive wire binding screws.• Three (3) #14 to 1/0 AWG neutral terminations standard.

QO330M150

Main Lugs Kits • Field installable in main circuit

breaker or main lugs load centers.

• QOL125 kit for use in 100 through 125 Ampere load centers.

• QOL225 kit for use in 150 through 225 Ampere load centers.

Main Circuit Breakers• Field installable in main circuit

breaker load centers.• 22,000 AIR main circuit breakers

series rated with 10,000 AIR branchcircuit breakers.

• Series rated up to 65,000 AIR maincircuit breakers 100A-225A serieswith 10,000 AIR branch circuitbreakers in 30 circuit or larger mainbreaker load centers.

• Back-fed QO-VH main circuitbreaker may be field-installed inmain lugs and main breaker loadcenters. Requires PK3MB retainingkit.

• 27 circuit, 100 Ampere main breaker load center includesfactory-installed back-fed QO-VH main breaker.

• 30 through 42 circuit main breaker load centers includeintegral KDL circuit breaker.

q When used as main breaker in load center, short circuit current rating is 22,000 Amperes.

Amperage 25,000 AIRq 65,000 AIR

100 KDL32100 KGL32100110 KDL32110 KGL32110125 KDL32125 KGL32125150 KDL32150 KGL32150175 KDL32175 KGL32175200 KDL32200 KGL32200225 KDL32225 KGL32225

Q0330L200G

Three Phase, 3 Through 42 Circuits, 60 Through 225 AmperesApplication Data

QOL3225

KDL Circuit Breaker100-225 Amperes

Page 38: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

10

UL Listed• Suitable for use as service equipment.• 75°C wire rating.

(See Technical Information).Short Circuit Current Rating:

• Main lugs up to 65,000 Amperes.• Main breaker 42,000 AIR.

(See Technical Information Pages 12-17).Mains

• Factory installed main lugs and main breaker.• Multiple wire terminals per phase and neutral.• Top or bottom mains positioning.

(See Technical Information Pages 12-17).Cover

• Flush and surface covers merchandised separately.

Interior• Available in single and three phase construction.• 12–42 circuit load centers have single row bus construction.• Interiors accept QO and 110–150 Ampere max. QOB-VH

circuit breakers. QOB-VH circuit breakers require connec-tor kit PK3CA.

• Tin plated aluminum bus.• Neutral assemblies positioned opposite mains compartment.

QON42LS400 and MH53

QON42MS400 and MH68

12 Through 42 Circuit, 300 Through 400 AmperesApplication Data

Page 39: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

11

Grounding Bar Kits

• Field installable in all load centers.• Wire size of terminals.

(See Technical Information, Page 17).• Suitable for copper or aluminum wire.• Available with #1-4/0 lug PK15GTA-L, PK18GTA-L and

PK23GTA-L. (See Technical Information Page 17).

Flush Lock Kits• Available for indoor load centers.• Two keys provided with each lock kit.

• PK6FL for convertible 12-42 circuitload centers.

• PK4FL for 300 and 400 Ampereload centers.

Auxiliary Neutral Lugs

• UL Listed for copper or aluminum wire.• Field installable on neutral assembly.

LK70AN #12-2Al or #14-4 CuLK100AN #6-#2/0 AWGLK150AN #2-3/0

Cover Filler Plates

• Fast to install – snap-in type.• QOFP branch circuit.• QOM1FP 70 through 125 Ampere single phase main

breaker.• QOM2FP 150 through 225 Ampere single phase main

breaker.• KFP 100 through 225 Ampere three phase main circuit

breaker.

SURGEBREAKER™ Secondary Surge Arrester

• QO2175SB UL Listed Secondary Surge Arrester.• Easy plug-on installation for QO load centers.• LED indicates operational status.• Plug-on design requires two pole spaces.

PK7GTA

LK150AN LK100AN

LK70AN

QOFP KFP

QO2175SB

AccessoriesApplication Data

PK6FL

PK4FL

Page 40: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

12

Single Phase Three Wire 120/240VacMain Lugs – Indoor

f Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.q 22,000 rms symmetrical Amperes maximum when supplied by integral Square D type QOMVH main breaker with 22,000 rms symmetrical Amperes minimum

interrupting rating and when all QO installed branch circuit breakers have 10,000 rms symmetrical amperes minimum interrupting rating.d UL Listed 5000 rms symmetrical Amps. short circuit current rating when used in 3Ø 240Vac grounded “B” phase systems when used as main lugs load center

only. Use 240Vac circuit breakers only.k UL Listed 5000 rms symmetrical Amps. short circuit current rating when used in 3Ø 240Vac grounded “B” phase systems. Use 240Vac circuit breakers only.B UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with field installed service disconnect.C UL Listed suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and

when not used as a lighting and appliance branch circuit panelboard.

Main Rating inAmperes

Load CenterCatalog Number

Load Center Cover

Catalog Number

UL Listed Service

Equipment

Max. UL Short Circuit

Rating f

Main Wire Size

AWG/kcmil

Wire Bending Space

Dimension (IN.)

Box No.

Top or Bottom Mains

Position

UL Listed for

Grounded "B" Phase

SystemAl Cu

Fixed Mains - Factory Installed Main Lugs

30 QO2L30S INCLUDED NO 10,000 #12-10 #14-10 1.6 1 TOP NO

70 QO2-4L70F/S INCLUDED B 10,000 #12-3 #14-4 3.0 2 TOP NO

100QO6-12L100F/S INCLUDED B,C 10,000 #8-1 4.5 3 TOP

NOQO6-12L100DF/S INCLUDED B,C 10,000 #8-1 4.5 3 TOPQO6-12L100DFCU/SC INCLUDED B,C 10,000 #8-1 4.5 3 TOP

100QO8-16L100F/S INCLUDED B,C 10,000 #8-1 4.5 3 TOP

NOQO8-16L100DF/S INCLUDED B,C 10,000 #8-1 4.5 3 TOPQO8-16L100DFCU/SC INCLUDED B,C 10,000 #8-1 4.5 3 TOP

Convertible Mains - Factory Installed Main LugsQOM1 Main Frame Size - Convertible to Main Breaker - Copper Bus

125

QO112L125G QOC16UF/S B,C 65,000dq #4-2/0 6.0 5A BOTH

YES

QO112-24L125G QOC16UF/S B,C 65,000dq #4-2/0 6.0 5A BOTHQO116L125G QOC24UF/S B,C 65,000dq #4-2/0 6.0 6 BOTHQO116-24L125G QOC24UF/S B,C 65,000dq #4-2/0 6.0 6 BOTHQO120L125G QOC24UF/S B 65,000dq #4-2/0 6.0 6 BOTHQO120-24L125G QOC24UF/S B 65,000dq #4-2/0 6.0 6 BOTHQO124L125G QOC24UF/S B 65,000dq #4-2/0 6.0 6 BOTH

Convertible Mains - Factory Installed Main LugsQOM2 Main Frame Size - Convertible to Main Breaker - Copper Bus

150QO120-30L150G QOC30UF/S B,C 65,000dq #4-250 8.5 8 BOTH

YESQO124L150G QOC30UF/S B,C 65,000dq #4-250 8.5 8 BOTHQO130L150G QOC30UF/S B,C 65,000dq #4-250 8.5 8 BOTH

200QO112L200G QOC30UF/S B,C 65,000dq #4-250 8.5 8 BOTH

YESQO130L200G QOC30UF/S B,C 65,000dq #4-250 8.5 8 BOTHQO130-40L200G QOC30UF/S B,C 65,000dq #4-250 8.5 8 BOTH

225 QO142L225G QOC42UF/S B 65,000dq #4-300 10.3 10 BOTH YES

Fixed Mains - Factory Installed Main Lugs

400

QON12LS400 (Interior) MHC50VF/S C 65,000k (1)1/0-750 15.1 19 BOTH YESMH50 (2)1/0-300

QON30LS400 (Interior) MHC50VF/S NO 65,000k (1)1/0-750 15.1 19 BOTH YESMH50 (Box) (2)1/0-300

QON42LS400 (Interior) MHC53VF/S NO 65,000k (1)1/0-750 14.4 21 BOTH YESMH53 (Box) (2)1/0-300

Single PhaseTechnical Information

Page 41: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

13

Single Phase Three Wire 120/240VacMain Breaker – Indoor

f Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.c 22,000 rms symmetrical Amperes maximum when supplied by integral Square D type QOM-VH main breaker with 22,000 rms symmetrical Amperes minimum

interrupting rating and when all QO installed branch circuit breakers have 10,0000 rms symmetrical Amperes minimum interrupting rating. 65,000 rms symmetrical Amperes maximum when main lugs kits are installed.

k UL Listed 5000 rms symmetrical Amps. short circuit current rating when used in 3Ø 240Vac grounded “B” phase systems. Use 240Vac circuit breakers only.A UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with factory installed service disconnect.B UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with field installed main lugs when not more than six disconnecting

means are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Section 384-14.

Main Rating in Amperes

Load CenterCatalog Number

Load Center Cover

Catalog Number

UL Listed Service

Equipment

Max. ULShort Circuit

Rating f

Main Wire Size

AWG/kcmil

Wire Bending Space

Dimension (IN.)

Box No.

Top or Bottom

Mains Posi-tion

UL Listed for Grounded "B" Phase SystemsAl Cu

Convertible Mains - Factory Installed Main Circuit BreakerQOM1 Main Frame Size - Convertible to Main Lugs or Lower Amperage Main Breaker- Copper Bus

100

QO112M100 QOC12UF/S A,B 22,000c #4-1 4.5 4 BOTH

NOQO116M100 QOC20U100F/S A,B 22,000c #4-1 6.0 5 BOTHQO120M100 QOC20U100F/S A 22,000c #4-1 4.5 5 BOTHQO124M100 QOC24UF/S A 22,000c #4-1 6.0 6 BOTH

125 QO124M125 QOC24UF/S A 22,000c #4-2/0 6.0 6 BOTH NO

Convertible Mains - Factory Installed Main Circuit BreakerQOM2 Main Frame Size - Convertible to Main Lugs or Lower Amperage Main Breaker - Copper Bus

150QO120-30M150 QOC30UF/S A,B 22,000c #4-250 8.5 8 BOTH

NOQO124M150 QOC30UF/S A,B 22,000c #4-250 8.5 8 BOTHQO130M150 QOC30UF/S A,B 22,000c #4-250 8.5 8 BOTH

200

QO120-40M200 QOC30UF/S A,B 22,000c #4-250 8.5 8 BOTH

NOQO124M200 QOC30UF/S A,B 22,000c #4-250 8.5 8 BOTHQO130M200 QOC30UF/S A,B 22,000c #4-250 8.5 8 BOTHQO130-40M200 QOC30UF/S A,B 22,000c #4-250 8.5 8 BOTHQO140M200 QOC40UF/S A,B 22,000c #4-250 8.5 9 BOTH

225 QO140M225 QOC42UF/S A,B 22,000c #4-300 10.3 10 BOTH NO

Fixed Mains - Factory Installed Main Circuit Breaker

300 QON42MS300 (Interior) MHC68VF/S A 42,000k (1)#4-500 14.5 20 BOTH YESMH68 (Box) (2)#4-3/0

400 QON42MS400 (Interior) MHC68VF/S A 42,000k (1)#4-600 14.5 20 BOTH YESMH68 (Box) (2)#4-250

Single PhaseTechnical Information

cschulte
Highlight
cschulte
Highlight
cschulte
Polygon
Page 42: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

14

Single Phase Three Wire 120/240VacMain Lugs – Rainproof

f Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.q 22,000 rms symmetrical Amperes maximum when supplied by integral Square D type QOMVH main breaker with 22,000 rms symmetrical Amperes minimum

interrupting rating and when all QO installed branch circuit breakers have 10,000 rms symmetrical Amperes minimum interrupting rating.d UL Listed 5000 rms symmetrical Amps. short circuit current rating when used in 3Ø 240Vac grounded “B” phase systems when used as main lugs load center

only. Use 240Vac circuit breakers only.c 22,000 rms symmetrical Amperes maximum when supplied by integral Square D type QOM-VH main breaker with 22,000 rms symmetrical Amperes minimum

interrupting rating and when all QO installed branch circuit breakers have 10,000 rms symmetrical Amperes minimum interrupting rating. 65,000 rms symmetrical Amperes maximum when main lug kits installed.

A UL Listed suitable for use as service equipment (neutral bonded at time of installation) with factory installed service disconnect.B UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with field installed service disconnect.C UL Listed suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and

when not used as a lighting and appliance branch circuit panelboard. See NEC Sec. 384-14.D UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with field installed main lugs when not more than six service disconnect-

ing means are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Sec. 384-14.

Main Rating in Amperes

Load CenterCatalog Number

Load Center Cover

Catalog Number

UL Listed Service

Equipment

Max. UL Short Circuit

Rating f

Main Wire Size

AWG/kcmilWire

Bending Space Dimension (IN.)

Box No.

Top or Bottom Mains

Position

UL Listed for Grounded "B"

Phase SystemsAl Cu

Fixed Mains - Factory Installed Main Lugs

30 QO2L40RB INCLUDED B 10,000 #12-6 #14-6 3.0 1R TOP NO

70 QO2-4L70RB INCLUDED B 10,000 #12-3 #14-4 3.0 1R TOP NO

100QO6-12L100RB INCLUDED B,C 10,000 #8-1 4.5 2R TOP

NOQO6-12L100TRB INCLUDED B,C 10,000 #8-1 4.5 2R TOPQO6-12L100RBCU INCLUDED B,C 10,000 #8-1 4.5 2R TOP

100 QO8-16L100RB INCLUDED B,C 10,000 #8-1 4.5 2R TOP NOQO8-16L100RBCU INCLUDED B,C 10,000 #8-1 4.5 2R TOP

Convertible Mains - Factory Installed Main LugsQOM1 Main Frame Size - Convertible to Main Breaker - Copper Bus

125

QO112L125GRB INCLUDED B,C 65,000dq #4-2/0 6.0 3R TOP

YESQO112-24L125GRB INCLUDED B,C 65,000dq #4-2/0 6.0 3R TOPQO116-24L125GRB INCLUDED B,C 65,000dq #4-2/0 6.0 4R TOPQO124L125GRB INCLUDED B 65,000dq #4-2/0 6.0 4R TOP

Convertible Mains - Factory Installed Main LugsQOM2 Main Frame Size - Convertible to Main Breaker - Copper Bus

150 QO130L150GRB INCLUDED B,C 65,000dq #4-250 8.6 6R TOP YES

200QO112L200GRB INCLUDED B,C 65,000dq #4-250 8.6 5R TOP

YESQO130L200GRB INCLUDED B,C 65,000dq #4-250 8.6 6R TOPQO130-40L200GRB INCLUDED B,C 65,000dq #4-250 8.6 6R TOP

225 QO142L225GRB INCLUDED B 65,000dq #4-300 12.9 8R TOP YES

Single Phase Three Wire 120/240VacMain Breaker - Rainproof

Main Rating in Amperes

Load CenterCatalog Number

Load Center Cover

Catalog Number

UL Listed Service

Equipment

Max. UL Short Circuit Rating

Main Wire Size AWG/kcmil Wire

Bending Space Dimension (IN.)

Box No.

Top or Bottom Mains

Position

UL Listed for Grounded “B”

Phase SystemsAl Cu

Convertible Mains - Factory Installed Main Circuit BreakerQOM1 Main Frame Size - Convertible to Main Lugs or Lower Amperage Main Breaker- Copper Bus

100QO112M100RB INCLUDED A,D 22,000c #4-1 4.5 3R TOP

NOQO116M100RB INCLUDED A,D 22,000c #4-1 4.5 4R TOPQO120M100RB INCLUDED A 22,000c #4-1 6.0 4R TOP

125 QO124M125RB INCLUDED A 22,000c #4-2/0 6.0 4R TOP NO

Convertible Mains - Factory Installed Main Circuit BreakerQOM2 Main Frame Size - Convertible to Main Lugs or Lower Amperage Main Breaker - Copper Bus

150 QO120-30M150RB INCLUDED A,D 22,000c #4-250 8.6 5R TOP NOQO130M150RB INCLUDED A,D 22,000c #4-250 8.6 6R TOP

200QO120-40M200RB INCLUDED A,D 22,000c #4-250 8.6 5R TOP

NOQO130M200RB INCLUDED A,D 22,000c #4-250 8.6 6R TOPQO140M200RB INCLUDED A,D 22,000c #4-250 8.5 7R TOP

Main Breaker with Feed Thru Lugs

125 QO16-12M125FTRB INCLUDED A 22,000c #4-2/0 6.0 3R TOP NO

150 QO18-16M150FTRB INCLUDED A 22,000c #4-4/0 8.5 6R TOP NO

200 QO18-16M200FTRB INCLUDED A 22,000c #4-4/0 8.5 6R TOP NO

Single PhaseTechnical Information

Page 43: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

15

3 Phase 4 Wire 208Y/120Vac, 3 Phase 4 Wire 240/120Vac Delta, 3 Phase 3 Wire 240Vac DeltaMain Lugs, Main Breaker – Indoor

f Short circuit current rating depends on lowest AIR rating of branch circuit breaker installed.q 22,000 rms symmetrical Amperes maximum when supplied by integral Square D type KDL main circuit breaker with 22,000 rms Amperes minimum interrupting rat-

ing and when all QO and Q1 installed branch circuit breakers have 10,000 rms symmetrical Amperes minimum interrupting rating.j 65,000 rms symmetrical Amperes maximum when Square D type KGL main breaker with 65,000 rms Amperes minimum interrupting rating is installed and when

all QO and Q1 installed branch circuit breakers have 10,000 RMS symmetrical Amperes minimum interrupting rating.A UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with factory installed service disconnect.B UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with field installed service disconnect.C UL Listed suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and

when not used as a lighting and appliance branch circuit panelboard. See NEC Section 384-14.D UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with field installed main lugs, when not more than six service disconnect-

ing means are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Section 384-14.X Mains positioning for top or bottom feed, first rotate main circuit breaker 180° then rotate complete load center 180°.

Main Rating in Amperes

Load Center Catalog Number

Load Center Cover Catalog Number

UL Listed Service

Equipment

Max. UL Short Circuit

Rating f

Main Wire Size

AWG/kcmilWire

Bending Space Dimension (IN.)

Box No.

Top or Bottom Mains

Position

UL Listed for Grounded "B"

Phase SystemsAl Cu

Fixed Mains - Factory Installed Main Lugs

60 QO403L60NF/S INCLUDED B 22,000f -- #10-6 2.8 17 TOP NO

125QO312L125G QOC16UF/S B,C 65,000f #4-4/0 #4-2/0 6.0 5A BOTH

NOQO320L125G QOC24UF/S B,C 65,000f #4-4/0 #4-2/0 6.0 6 BOTHQO324L125G QOC24UF/S B,C 65,000f #4-4/0 #4-2/0 6.0 6 BOTH

200 QO318L200G QOC30UF/S B,C 65,000f #4-250 #4-250 10.3 8 BOTH NOQO330L200G QOC30UF/S B,C 65,000f #4-250 #4-250 10.3 8 BOTH

225 QO342L225G QOC42UF/S B 65,000f #4-300 #4-300 12.1 10 BOTH NO

400 QON442LS400 MHC53VF/S NO 65,000f (1)-1/0-750 14.4 21 BOTH NOMH53 (Box) (2)1/0-300

Convertible Mains - Factory Installed Main Breaker

100 QO327M100 QOC30UF/S A 22,000 #4-1/0 #4-1 10.3 8 BOTH NO

125 QO330M125 QOC342MF/S A 65,000 jq #4-250 #4-250 8.5 15 X NO

150 QO330M150 QOC342MF/S A,D 65,000 jq #4-250 #4-250 8.5 15 X NOQO342M150 QOC342MF/S A 65,000 jq #4-250 #4-250 8.5 15 X

200 QO330M200 QOC342MF/S A,D 65,000 jq #4-250 #4-250 8.5 15 X NOQO342M200 QOC342MF/S A 65,000 jq #4-250 #4-250 8.5 15 X

225 QO342M225 QOC342MF/S A 65,000 jq #4-250 #4-250 8.5 15 X NO

Fixed Mains - Factory Installed Main Circuit Breaker

300 QON442MS300 MHC68VF/S A 42,000f (1)#4-500 14.5 20 X NOMH68 (2)#4-3/0

400 QON442MS400 MHC68VF/S A 42,000f (1)#4-600 14.5 20 X NOMH68 (2)#4-250

Main Lugs, Main Breaker - Rainproof

Main Rating in Amperes

Load Center Catalog Number

Load Center Cover Catalog Number

UL Listed Service

Equipment

Max. UL Short Circuit Rating

Main Wire Size AWG/kcmil Wire Bending

Space Dimension (IN.)

Box No.

Top or Bottom Mains

Position

UL Listed for Grounded "B"

Phase SystemsAl Cu

Fixed Mains - Factory Installed Main Lugs

60 QO403L60NRB INCLUDED B 22,000f #10-6 3.6 12R TOP NO

125 QO312L125GRB INCLUDED B,C 65,000f #4-4/0 #4-2/0 6.0 3R TOP NOQO320L125GRB INCLUDED B,C 65,000f #4-4/0 #4-2/0 6.0 4R TOP

200 QO318L200GRB INCLUDED B,C 65,000f #4-250 #4-250 11.1 6R TOP NOQO330L200GRB INCLUDED B,C 65,000f #4-250 #4-250 11.1 6R TOP

225 QO342L225GRB INCLUDED B 65,000f #4-300 #4-300 12.9 8R TOP NO

Convertible Mains - Factory Installed Main Breaker

100 QO327M100RB INCLUDED A 22,000 #4-1/0 #4-1 7.5 6R TOP NO

125 QO330M125RB INCLUDED A 65,000 jq #4-250 #4-250 8.5 16R TOP NO

150 QO330M150RB INCLUDED A,D 65,000jq #4-250 #4-250 8.5 16R TOP NO

200 QO330M200RB INCLUDED A,D 65,000 jq #4-250 #4-250 8.5 16R TOP NOQO342M200RB INCLUDED A 65,000 jq #4-250 #4-250 8.5 16R TOP

225 QO342M225RB INCLUDED A 65,000 jq #4-250 #4-250 8.5 16R TOP NO

Three PhaseTechnical Information

Page 44: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

16

Modular Housing, Mobile Home and Trailer

f Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.q 22,000 rms symmetrical Amperes maximum when supplied by integral Square D type QOM-VH main breaker with 22,000 rms symmetrical Amperes minimum

interrupting rating and when all QO installed branch circuit breakers have 10,000 rms symmetrical Amperes minimum interrupting rating.a Main circuit breaker is field installed – standard QO 1-pole circuit breaker.c Short gutter side limited to #3 AWG wire maximum.p CSA certified.u Will not accept Quick Guard QO-GFI circuit breaker.v Use #10 AWG maximum size wire for QO-GFI circuit breaker.k 70A maximim branch circuit breaker and 70A maximum back fed main circuit breaker.A UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with factory installed service disconnect.B UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with field installed service disconnect.C UL Listed suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and

when not used as a lighting and appliance branch circuit panelboard. See NEC Section 384-14.D UL Listed suitable for use as service equipment (neutral bonded at the time of installation) with field installed main lugs and not more than six service disconnecting

means are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Section 384-14.

Main Rating in Amperes

Load Center Catalog Number

Load Center Cover

Catalog Number

UL Listed Service

Equipment

Max. UL Short Circuit

Ratingf

Main Wire Size

AWG/kcmil

Wire Bending Space

Dimension (IN.)

Box No.

Top or Bottom Mains

Position

UL Listed for Grounded "B"

Phase SystemsAl Cu

1 Phase 2 Wire 120Vac - Main Lugs Only

30 QO2L30TTSpu INCLUDED NO 10,000 #12-10 #14-10 1.5 1 TOP NO

50 QO2-4L50TTSpv INCLUDED NO 10,000 #14-6 2.9 2 TOP NO

1 Phase 2 Wire 120Vac - Main Circuit Breaker

70 QO4-7FM70TTSap INCLUDED NO 10,000 See Breaker Info 4.5 16 TOP NO

1 Phase 3 Wire 120/240Vac - Main Lugs Only

70 QO2-4L70TSp INCLUDED B 10,000 #12-3 #14-4 3.0 2 TOP NO

100 QO6-12L100TF/Spk INCLUDED B,C 10,000 #4-1 #4-10 4.5 3 TOP YESQO6-12L100DTF/Spk INCLUDED B,C 10,000 #4-1 #4-1 4.5 3 TOP

100 QO8-16L100TF/Sk INCLUDED B,C 10,000 #4-1 #4-1 4.5 3 TOP NOQO8-16L100DTF/Sk INCLUDED B,C 10,000 #4-1 #4-1 4.5 3 TOP

1 Phase 3 Wire 120/240Vac - Main Circuit Breaker

200 QO120-40M200TC INCLUDED A,D 22,000q #4-250 8.5 8 BOTH NO

RISER

Main Rating in Amperes

Load Center Catalog Number

Load Center Cover Catalog

Number

UL Listed Service

Equipment

Max. UL Short Circuit Rating

Main Wire Size

AWG/kcmil

Wire Bending

Space Dimen-sion (IN.)

BoxNo.

Top or Bottom Mains

Position

UL Listed for Grounded "B"

Phase SystemsAl Cu

1 Phase 3 Wire 120/240Vac - Factory Installed Main Lugs - Offset Interior Wide GutterQOM1 Main Frame Size - Convertible to Main Breaker - Copper Busc

125 QO112-24L125GWGC INCLUDED B,C 65,000q #4-2/0 6.0 18 BOTH YESQO120-24L125GWGC INCLUDED B 65,000q #4-2/0 6.0 18 BOTH

Generator Panel

Main Rating in Amperes

Load Center Catalog Number

Load Center Cover Catalog

Number

UL Listed Service

Equipment

Max. UL Short Circuit Rating

Main Wire Size

AWG/kcmil

Wire Bending

Space Dimen-sion (IN.)

BoxNo.

Top or Bottom Mains

Position

UL Listed for Grounded "B"

Phase SystemsAl Cu

1 Phase 3 Wire 120/240Vac - Factory Installed Main Circuit Breakers with Mechanical Interlock

30 QO4-8M30DS-GP INCLUDED NO 10,000 #14-8 4.5 3 BOTTOMNO

60 QO4-8M60DS-GP INCLUDED A 10,000 #8-2 4.5 3 BOTTOM

Technical Information

Page 45: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

17

Grounding Bar KitsAll PK Equipment Grounding Kits are supplied with mounting screws, necessary installation instructions and an “Equipment Ground-ing Terminal” self-adhesive label.

k PK27GTA includes one main grounding lug which mounts by utilizing two terminal screws, requires three terminals for mounting.q 3.13" on small terminals; 5.25" on large terminals.

Catalog Number Total Quantity

Terminals

Approximate Overall Length

C To C L LDistance Between Mounting Holes

MountingQuantity Each SizeSee Table “B” For Wire Range

I II III IV V VI

PK0GTA-2 2 2 1.75" One Hole Top

PK0GTA-6 6 6 4.61" 1.69" Top

PK3GTA-1 3 3 1.38" One Hole Top

PK4GTA 4 4 1.63" One Hole Top

PK5GTA 5 5 2.25" 1.25" Top

PK7GTA 7 7 2.88" 1.25" Top or Side

PK9GTA-1 9 9 3.25" One Hole Top

PK9GTA 9 9 3.78" 3.13" Top

PK12GTA 12 12 4.70" 3.13" Top

PK15GTA 15 15 5.63" 3.13" Top

PK15GTA-L 16 15 1 8.13" 3.13" Top

PK15GTA-6 21 15 6 5.88" q Top

PK18GTA 18 18 6.56" 3.13" Top

PK18GTA-L 19 18 1 8.81" 3.13" Top

PK23GTA 23 23 8.11" 3.13" Top

PK23GTA-L 24 23 1 9.44" 3.13" Top

PK27GTA 27 or k 26 2726 1 9.36" 3.13" Top

Table BSize Cu (Awg) Al (Awg)

I (1) #14 to #4 or (2) #14 or #12 (1) #12 to #4 or (2) #12 or #10

II (1) #1 to 4/0 (1) #1 to 4/0

III (1) #6 to 2/0 (1) #6 to 2/0

IV (1) #6 to 3/0 (1) #6 to 3/0

V (1) #14 to 1/0 (1) #14 to 1/0

VI (1) #10 to 2/0 (1) #6 to 2/0

Slot/Robertson Screw

.5013

.31258

Dual Dimensions: INCHESMillimeters

Technical Information

Standard Ground Bar Profile Dimensions

Page 46: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

18

A,B,C,D

A,B,CAA,B,C

A

BOX 2BOX 1

A,B,C

A

A

A,B,C

A

BOX 4

AA,B,CC,D,E,F,G

A,B

B,C,D,E

A,B,C,D

A,B

A

A,B,C,D

A,B,C,DAA,B

A

BOX 3

BOX 16

B,C,D,E

B,C,D,EA,B

A

A

A

BOX 17

A,B,C,D

C,D,E,F

A,B

C,D,E,F

C,D,E,F

D,E,F,G,H,ID,E,F,G,H

BOX 19, 20, 21

A,B,C,D

A,B,C,DA,B,C,D

A,B,C,D

C,D,E,F

A,B

A

C,D,E,F

BOX 5

B,C,D,E

A,B,C,D

C,D,E,F

D,E,F,G

BOX 23

A,B,C,D

C,D,E,F

BOX 24

D,E,F,G

BOX 25

C,D,E,F

D,E,F,G

E,F,G,H

AA,B,CC,D,E,F,G

A,B

A,B

A

C,D,E,F

BOX 5A

B,C,D,E

A,B,C,D

AA,B,CC,D,E,F,G

A,B

A,B

A

A,B

B,C

A

C,D,E,F

BOX 6

B,C,D,E

C,D,E,F C,D,E,F C,D,E,F

B,C,D,ED,E,F,G

B,C,D,E D,E,F,G

B,C,D,E

A,B,C,D

A,B,C,DB,C,D,E

A,B,C,DB,C,D,E

A,B,C,DB,C,D,E

AA,B,CC,D,E,F,G

A,B AA,B,CC,D,E,F,G

A,B

D,E,F,G

C,D,E,F

D,E,F,G

C,D,E,F

B,C,D,E

A,B,C,DB,C,D,E

D,E,F,G

C,D,E,FD,E,F,G

C,D,E,FD,E,F,G

A,B

B,C

A

AA,B,CC,D,E,F,G

A,B

BOX 10BOX 9BOX 8

A,B

B,C

A

AA,B,CC,D,E,F,G

A,B

BOX 18

A,B

A

B,C,D,E

B,C,D,E

A,B,C,D

AA,B,CC,D,E,F,G

A,B

BOX 15

A,B

B,C

A

AA,B,CC,D,E,F,G

A,B

Knockout Information and Enclosure DimensionsIndoor

Dimensions

Box No.W H D

IN mm IN mm IN mm

1 3.81 97 6.72 171 3.00 76

2 4.81 122 9.30 236 3.19 81

3 8.88 226 12.57 319 3.80 97

4 14.25 362 14.92 379 3.75 95

5, 5A 14.25 362 17.92 455 3.75 95

6 14.25 362 20.92 531 3.75 95

8 14.25 362 29.86 758 3.75 95

9 14.25 362 33.78 858 3.75 95

10 14.25 362 37.98 965 3.75 95

15 14.25 362 39.50 1003 3.75 95

Dimensions

Box No.

W H D

IN mm IN mm IN mm

16 7.38 187 9.89 251 3.30 84

17 5.88 149 13.12 333 3.38 86

18 14.25 362 20.92 531 3.75 95

19 20.00 508 50.00 1270 5.75 146

20 20.00 508 68.00 1727 5.75 146

21 20.00 508 53.00 1346 5.75 146

23 5.88 149 16.12 409 3.38 86

24 7.56 192 23.12 587 4.25 108

25 9.62 244 26.12 663 4.75 121

Knockouts

Symbol A B C D E F G H I

ConduitSize

1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2

Knockouts, Dimensions

cschulte
Polygon
Page 47: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

19

Knockout Information and Enclosure DimensionsRainproof

Knockouts

Symbol A B C D E F G H

Conduit Size

1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3

Dimensions

Box No.W H D

IN mm IN mm IN mm

1R 4.88 124 9.38 238 4.00 102

2R 8.88 226 12.65 321 4.27 108

3R 14.25 362 18.92 481 4.52 115

4R 14.25 362 22.06 560 4.52 115

5R 14.25 362 26.04 661 4.52 115

6R 14.25 362 29.86 758 4.52 115

7R 14.25 362 33.78 858 4.52 115

8R 14.25 362 37.98 965 4.52 115

11R 4.56 116 6.50 165 3.88 99

12R 6.92 176 13.18 335 4.12 105

13R 7.56 192 23.24 590 4.75 121

14R 9.62 244 26.24 666 5.50 140

15R 6.92 176 16.18 411 4.12 105

16R 14.25 362 39.37 1000 4.52 115

A,B,C,D

A,B,C,DA

BOX 2R

A,B

A,B,C,DA

BOX 1R

A,B

BOX 3R, 4R

A A,B C,D,E,F A,B,C

C,D,E,F

BOX 5R

AD,E,F,G

A,B,CC,D,E,F

BOX 6R, 7R, 8R

AA,B D,E,F,G A,B,C

D,E,F,G

BOX 11R

A,B,C

A,B,C,D

C,D,E,F

BOX 12R, 15R

B,C,D,E

2 1/2" Hub Maximum 2 1/2" Hub Maximum

A,B,C,D

2 1/2" Hub Maximum

C,D,E,F

2 1/2" Hub Maximum

A,B

C,D,E,F

2 1/2" Hub Maximum

D,E,F,G

D,E,F,GA,B

A,B,C

A

BOX 16R

B,C,D,E

2 1/2" Hub Maximum

2 1/2" Hub Maximum

D,E,F,G

D,E,F,G

BOX 13R

2 1/2" Hub Maximum

D,E,F,G

BOX 14R

2 1/2" Hub Maximum

E,F,G,H E,F

Knockouts, Dimensions, Bolt-On Hubs

Page 48: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

20

7

13

6

145 9

12

114

15 16

8

10

1

3

2

Represents a typical label. Information may not be applicable or may change without notice. See actual label in the load center for lat-est information.

Wiring Diagram

1. Number of circuits maximum.2. Amperage rating.3. Box catalog number.4. See panelboard interior for catalog number.5. Service equipment marking.6. Short circuit ratings.7. Wire range and lug torque data table.

8. Use of unused neutral branch terminals forequipment grounding, service equipment appli-cation only.

9. Catalog number for secondary surge arrestor.10. Catalog number of covers.11. U.L. Listing.12. Neutral lug for wire larger than 1/0.

13. Alternate wiring diagram for main circuit breakeror main lug.

14. Square D circuit breakers that may be used inthis panelboard.

15. Voltage ratings.16. Short Circuit ratings and replacement or addi-

tional circuit breakers.

Page 49: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

21

QO2L30SQO2L40RB

SN

QO2L30TTS

SN

G/B

QO112L125GQO112L125GRBQO112L200GQO112L200GRB

SN

SN

SN

SN

QO112-24L125GQO112-24L125GRBQO112-24L125GWGC

QO2-4L70F/SQO2-4L70RB

SN

QO2-4L50TTS

SN

GB

QO4-7FM70TTS

GB

Line

S/N

QO6-12L100F/SQO6-12L100DF/SQO6-12L100DFCU/SCUQO6-12L100RBQO6-12L100RBCU

S/N

QO4-8M30DSGPQO4-8M60DSGP

S/N

QO6-12L100TF/SQO6-12L100DTF/SQO6-12L100TRB

S/N

GB

QO8-16L100F/SQO8-16L100DF/SQO8-16L100DFCU/SCUQO8-16L100RBQO8-16L100RBCU

S/N

QO8-16L100TF/SQO8-16L100DTF/S

S/N

GB

QO116L125G

SN

SN

QO116-24L125GQO116-24L125GRB

SN

SN

SN

SN

QO120L125G

SN

SN

QO120-30L150G

SN

SN

QO120-24L125GQO120-24L125GWGC

SN

SN

QO124L125GQO124L150GQO124L125GRB

QON12LS400

SN

SN

QO130L150GQO130L200GQO130L150GRBQO130L200GRB

SN

SN

QO130-40L200GQO130-40L200GRB

SN

SN

QO142L225GQO142L225GRB

QON30LS400

S/N

QON42LS400

S/N

S/N

MAINSN

QO16-12M125FTRB

SF

SN MAIN

SN

QO18-16M150FTRBQO18-16M200FTRB

MAINSN

SN

QO112M100QO112M100RB

MAINSN

SN

QO116M100QO116M100RB

MAINSN

SN

QO120M100QO120M100RB

MAINSN

SN

QO120-30M150QO120-30M150RB

MAINSN

SN

QO120-40M200QO120-40M200RB

MAINSN

SN

QO124M125QO124M125RBQO124M150QO124M200

MAINSN

SN

QO130M150QO130M200QO130M150RB

QON42MS300QON42MS400

MAIN

S/N

MAINSN

SN

QO140M200QO140M225QO140M200RB

1 Phase 3 Wire Main Lugs

1 Phase 3 Wire Main Breaker

QO2-4L70TS

SN

G/B

MAINSN

SN

QO130-40M200

MAINSN

SN

QO120-40M200TC

GB

Main Main

Wiring Diagrams

Page 50: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

QO® Circuit Breaker Load Centers

22

QO403L60NF/SQO403L60NRB

SN

QO312L125GQO312L125GRB

SN

SN

QO324L125G

SN

SN

QO320L125GQO320L125GRB

SN

SN

QO342M150QO342M200QO342M225QO342M200RBQO342M225RB

SN

SN

MAIN

QO342L225GQO342L225GRB

SN

SN

QON442MS300QON442MS400

S/N

MAIN

QON442LS400

S/N

QO327M100QO327M100RB

SN

SN

QO318L200GQO318L200GRB

SN

SN

QO330L200GQO330L200GRB

SN

SN

MAIN

QO330M125QO330M150QO330M200QO330M125RBQO330M150RBQO330M200RB

SN

SN

MAIN

3 Phase 4 Wire Main Lugs

3 Phase 4 Wire Main Circuit Breaker

Wiring Diagrams

Page 51: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Order No. 1130CT9501 Oct 95 Printed in U.S.A.(Replaces 1130CT9101 and 1130CT9401) © 1995 Square D Company

SURGEBREAKER is a Trademark of Square D Company.

QO, s and SQUARE D are Registered Trademarks of Square D Company.

Page 52: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

5821

Leviton Catalog #:       5821 Description: 20 Amp, 250 Volt, NEMA 6-20R, 2P, 3W, Narrow Body Single Receptacle, Straight Blade, Commercial Grade, Grounding, , Side Wired, Steel Strap, - Brown

Product Features:     Ground: 

    Amperage:      Voltage: 

    NEMA:      Pole:      Wire: 

    Termination:      Face Material:      Body Material:      Strap Material: 

    Color:      Standards and Certifications: 

    Warranty: 

 Grounding   20 Amp   250 Volt   6-20R   2   3   Side   Nylon   Nylon   Steel   Brown   UL/CSA   10 Year Limited 

Electrical Specifications

Dielectric Voltage Withstands 2000V per UL498

Current Limiting Full Rated Current

Material Specifications

Face Material Nylon

Body Material Nylon

Line Contacts Brass Double Wipe .031 Thick

Terminal Screws Brass 8-32

Grounding Screw Brass 8-32

Yoke Zinc-Plated Steel

AC Horsepower Ratings

At Rated Voltage 2 HP

   

Mechanical Specifications

Terminal ID Brass-Hot, Green-Ground, White-Neutral

Terminal Accom. 14-10 AWG

Product ID Ratings are permanently marked on device

Environmental Specifications

Flammability Rated V-2 per UL94

Operating Temp. -40C to 60C

Standards and Certifications

NEMA WD-2 WD-6

ANSI C-73

UL498 File E13399

UL Fed Spec WC-596 File E13399

CSA C22.2 No. 42 File 152105

NOM 057

   

Page 1 of 2Leviton EZ-Find

5/9/2006http://www.levitonhelpdesk.com/catalog/default.asp?server_name=www.levitonhelpdesk.co...

Page 53: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

For answers to technical questions call our Techline at 1-800-824-3005 (8:30AM-6:00PM EST M-F).

For Other products go to www.leviton.com and select Leviton EZ-Find.

Leviton Manufacturing Co., Inc. 59-25 Little Neck Parkway, Little Neck, NY 11362-2591

Telephone: 1-800-323-8920 FAX: 1/800-832-9538

Leviton Manufacturing of Canada, Ltd. 165 Hymus Boulevard, Pointe Claire, Quebec H9R 1E9

Outside Canada: 1-514-954-1840 FAX: 1-514-954-1853/1854 Inside Canada: 1-800-469-7890 Techline: 1-800-405-5320 FAX 1-800-563-1853

Note: Because Leviton engages in a continuous program of product improvement, data is subject to change without notice. Copyright 2004 Leviton Manufacturing Co., Inc. All right reserved.

Page 2 of 2Leviton EZ-Find

5/9/2006http://www.levitonhelpdesk.com/catalog/default.asp?server_name=www.levitonhelpdesk.co...

Page 54: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

• Powder coated 18 ga. steel front • In-Built single pole thermostat with 50°-90°F temperature range • Automatic reset thermal limit • Steel block fin element • Vane axial fan blade - 600 RPM / 175 CFM • Weight 22 lbs. • Rough in dimensions - 14 3/16" wide x 19 15/16" high x 4" deep • Grill dimensions - 15 3/8” wide x 20 9/64” high

FAN FORCED WALL HEATERS

UPC IVORY UPC WHITE 686334 MODEL 686334 MODEL 381987 E3311TSRP 382588 E3311TSRPW 750 2560 6.25

382571 E3312TSRP 382595 E3312TSRPW 1000 3413 8.3

379618 E3313TSRP 384018 E3313TSRPW 1500 5120 12.5

377713 F3316TSRP 384025 F3316TSRPW 4000 13648 19.2

377782 F3317TSRP 384032 F3317TSRPW 4800 16380 23

377898 HF3313TSRP 384056 HF3313TSRPW 1500 / 1125 5120 6.2 / 5.4

377515 HF3314TSRP 384063 HF3314TSRPW 2000 / 1500 6826 8.3 / 7.2

377607 HF3315TSRP 384070 HF3315TSRPW 3000 / 2250 10240 12.5 / 10.8

377690 HF3316TSRP 384087 HF3316TSRPW 4000 / 3000 13648 16.8 / 14.4

377768 H3317TSRP 384094 H3317TSRPW 4800 16380 240 20.0

377553 G3314TSRP 384117 G3314TSRPW 2000 6826 7.2

377645 G3315TSRP 384124 G3315TSRPW 3000 10240 10.8

377737 G3316TSRP 384131 G3316TSRPW 4000 13648 14.4

377805 G3317TSRP 384148 G3317TSRPW 4800 16380 17.3

240 / 208

277

IVORY WHITE

120

208

MODELS WITH SUMMER FAN SWITCH

WATTS MAX BTU'S

VOLTS AMPS

UPC UPC

686334 686334

377850 BOX3310 377850 BOX3310 ADDITIONAL BACK CAN

377843 3310EX33 384155 3310EX33W SURFACE MOUNTING FRAME

DISCONNECT SWITCH Factory Installed

IVORY WHITE

MODEL MODEL

Field Installed

SUFFIX D

DESCRIPTION ACCESSORY TYPE

ACCESSORY TYPE

UPC IVORY UPC WHITE

686334 MODEL 686334 MODEL

380652 E3313TRP 384162 E3313TRPW 1500 5120 120 12.5

380706 H3313TRP 384209 H3313TRPW 1500 5120 240 6.25

379960 HF3314TRP 384216 HF3314TRPW 2000 / 1500 6826 240 / 208 8.3 / 7.2

380560 HF3315TRP 382229 HF3315TRPW 3000 / 2250 10240 240 / 208 12.5 / 10.8

379984 HF3316TRP 382236 HF3316TRPW 4000 / 3000 13648 240 / 208 16.6 / 14.4

380317 HF3317TRP 382243 HF3317TRPW 4800 16380 240 20.0

AMPS VOLTS MAX BTU'S

IVORY WHITE WATTS

MODELS WITHOUT SUMMER FAN SWITCH

cschulte
380560 HF3315TRP 382229 HF3315TRPW 3000 / 2250 10240 240 / 208 12.5 / 10.8
cschulte
379984 HF3316TRP 382236 HF3316TRPW 4000 / 3000 13648 240 / 208 16.6 / 14.4
Page 55: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

PERFORMANCE ADVANTAGES• Cost-effective – ease of handling

and fabrication plus light weight make for easy, fast installation and low total applied cost.

• Thermally Efficient – provides effective resistance to heat transfer with R-values up to R-17.4 (RSI-3.06).

• Acoustically Efficient – reduces transmission of sound through roofs and walls.

• Fire-resistant and Noncombustible – (see Specification Compliance).

• Moisture-resistant – vapor-retarder facings resist water vapor transmission (see Specification Compliance).

• Noncorrosive – does not accelerate corrosion of pipes, wiring or metal studs.

• Durable – unaffected by moisture, oil, grease and most acids. It will not rot, mildew or otherwise deteriorate, preventing slumping and uninsulated voids.

• Easy to Handle – unlike some products that are friable, fiber glass maintains its physical integrity during handling.

• Self-supporting – because of its rigidity, Insul-SHIELD 300 and 600 can often be attached without framing.

Insul-SHIELD®

Thermal and Acoustical Semi-rigid and Rigid Board Products

PRODUCT DESCRIPTION

Insul-SHIELD is a series of semi-rigid or rigid thermal and acoustical fiber glass insulating boards for custom curtain wall applications. They are made from inorganic glass fibers bonded with a thermosetting binder. The insulating boards are typically used where framing is not present.

Note: Insul-SHIELD may be manufactured either with or without a formaldehyde-based binder. Check with your sales representative for availability of Formaldehyde-free™ Insul-SHIELD in your area.

APPLICATIONS

• New and Retrofit Construction – Insul-SHIELD insulation provides thermal and acoustical insulating values for exterior curtain wall cavities, parking structures, mechanical rooms, theaters, casinos and other commercial construction applications. The insulating boards are typically used where framing is not present. (I/S 100 is often used in shaft wall applications.)

• Custom Curtain Wall Construction – Exterior curtain wall cavities – Insul-SHIELD is exceptionally well suited to curtain wall construction in terms of both installation and performance. When used in the exterior envelope of steel-framed buildings, it helps reduce heat loss in the winter and heat gain in the summer. The result is an attractive, efficient thermal enclosure that significantly reduces the cost of air treatment, cuts long-term energy expenses and improves life-cycle costs.

The insulation, in sizes up to 56" x 84" (1.42 m x 2.14 m), is easily installed by one person. Insul-SHIELD is available in a variety of densities, thicknesses and facings for custom curtain wall applications. It can be custom-manufactured to precise dimensions to fit specific spandrel panel designs.

• Standard Metal Panel Construction – Insul-SHIELD offers a variety of sizes, densities and facings for on-the-job or in-the-shop insulation of metal panel buildings such as power plants, assembly buildings, sports arenas and other commercial facilities.

In these applications, Insul-SHIELD is field-installed between an interior liner and the outer metal panel using semi-rigid boards (I/S 150, 225) that are plain or faced with a factory-applied vapor retarder. Insul-SHIELD is also available custom-cut to fit pre-insulated metal sandwich panels.

• General Construction – A versatile insulation, Insul-SHIELD is also an ideal thermal barrier for masonry or concrete structures such as shopping centers, banks and many other types of low-rise commercial or institutional buildings. It is also ideal for use in parking garage ceilings.

In masonry applications, semi-rigid and rigid Insul-SHIELD boards faced with an FSK vapor retarder are installed between “Z” or hat channels applied directly to the masonry surface. Normally, gypsum board and/or architectural panels are then used as interior surfaces.

• Theaters – With a state-of-the-art acrylic-coated surface, Insul-SHIELD Coated Black is an ideal backdrop for theater screens. The opaque surface absorbs both sound and light, eliminating concern about back-scatter into the viewing arena.

Page 56: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Insul-SHIELD® Thermal and Acoustical Semi-rigid and Rigid Board Products

Visit us at JM.com Or call: 1-800-654-3103

AVAILABLE FORMSInsul-SHIELD is available unfaced or with FSK-25, PSK, black mat or coated black facing.

Unfaced Boards FSK-25 or PSK-Faced Boards Black Mat Boards Coated Black Rolls

• Standard board size – 24" x 48" (610 mm x 1219 mm) available for all densities.

• Nonstandard sizes – furnished upon request in many nonstandard lengths and widths pre-cut to meet specific dimensions.

• Standard board size – 24" x 48" (610 mm x 1219 mm) available for all densities.

• Nonstandard sizes – furnished upon request in many nonstandard lengths and widths pre-cut to meet specific dimensions.

• Standard board size – 24" x 48" (610 mm x 1219 mm) available for all densities.

• Nonstandard sizes – furnished upon request in many nonstandard lengths and widths pre-cut to meet specific dimensions.

• Roll form – I/S 100 and 150 available in 16," 24" and 48" (406 mm, 610 mm, and 1219 mm) widths.

• Available in 1" (25 mm) and 2" (51 mm) thicknesses.

• Available with face and edge coating where black color is specified.

Insul-SHIELD boards are designed for custom curtain wall applications.

Faced Insul-SHIELD boards can be used where a vapor barrier is needed. FSK facing has the best fire performance characteristics and helps maximize lighting efficiency.

Insul-SHIELD Black provides a semi-rigid substrate beneath the fabric treatment used on theater side walls. The black, mat-faced insulation provides adequate shadowing behind any surface treatment.

Insul-SHIELD Coated Black is ideal for theater applications. Product shown was specified with both face and edge coating.

Walls and ceilings up to 24" x 48" (0.61 m x 1.22 m)

Ceilings up to 48" x 96" (1.22 m x 2.44 m)

Walls up to 48" x 96" (1.22 m x 2.44 m)

X X X

XX

X

X

X

X X

X

XX

X

X

X

X X

Insul-SHIELD

Concrete Floor

Safing

Aluminum Spandrel

INSTALLATION

Insul-SHIELD can be easily cut and friction-fit between vertical or Z-shaped framing or hat channels applied directly to a masonry surface. The insulation can also be installed with impaling pins or with suitable adhesives.

In standard metal panel construction applications, Insul-SHIELD is field-installed between an interior liner and the outer metal panel. Normally, gypsum board and/or architectural panels are then used as interior surfaces. Some trimming may be necessary if used in ceiling grids, as this product is a commercial-use board.Note: In colder climate areas, vapor retarders (whether attached to the insulation or applied separately) are often placed toward the heated or conditioned side of the wall. This is done to reduce water vapor penetration into the wall from the building interior. Conversely, in predominantly hot, humid climates local practices often call for placing the vapor retarder toward the outside of the wall cavity. Check your local building codes for vapor retarder requirements.

Recommended Pin Patterns I/S 100, 150, 225, 300 and 600: pins should be placed approximately 3"–5" (76 mm–127 mm) from the edges of the product.

Page 57: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

SOUND ABSORPTION DATA*

Insul-SHIELD® Thermal and Acoustical Semi-rigid and Rigid Board Products

STANDARD DIMENSIONAL DATA AND FACINGS* “k”- Values Thickness ThicknessType Btu · in/ (hr· f t² ·˚F) (w/m·˚K) (in) (mm) Facing**

I/S 100 0.27 0.039 1½ 38 UnfacedI/S 150 0.24 0.035 1, 1½, 2, 2½, 3, 3½, 4 25, 38, 51, 64, 76, 89, 102 Unfaced, FSK-25, PSK I/S 225 0.23 0.033 1, 1½, 2, 2½, 3, 3½, 4 25, 38, 51, 64, 76, 89, 102 Unfaced, FSK-25, PSK I/S 300 0.23 0.033 1, 1½, 2, 2½, 3, 3½, 4 25, 38, 51, 64, 76, 89, 102 Unfaced, FSK-25, PSK I/S 600 0.22 0.032 1, 1½, 2, 2½, 3 25, 38, 51, 64, 76 Unfaced, FSK-25, PSK I/S Coated Black 0.25 0.036 1, 2 25, 51 Durable black-coated surface

* Product sizes vary by plant locations; consult your Johns Manville sales representative for other available sizes.** Meets HH-B-100 B, Type I and II specifications.

1" (25 mm) Thickness Unfaced (Type “A” Mounting)** Thermal Data

Density Typical Coefficients by Frequency (Hz) “R” “RSI”Type pcf kg/m³ 125 250 500 1000 2000 4000 NRC*** (hr· ft² ·˚F) /Btu m2·˚K/w

I/S 150 1.5 24.0 0.07 0.24 0.63 0.87 1.00 1.02 0.70 4.2 0.74

I/S 225 2.25 36.1 0.08 0.27 0.69 0.95 1.05 1.02 0.75 4.3 0.76

I/S 300 3.0 48.1 0.06 0.29 0.75 0.99 1.04 1.02 0.75 4.3 0.76

I/S 600 6.0 96.1 0.10 0.35 0.85 1.04 1.05 1.03 0.80 4.5 0.79

1½" (38 mm) Thickness Unfaced (Type “A” Mounting)** Thermal Data

Density Typical Coefficients by Frequency (Hz) “R” “RSI”Type pcf kg/m³ 125 250 500 1000 2000 4000 NRC*** (hr· ft² ·˚F) /Btu m2·˚K/w

I/S 100 1.0 16.0 0.15 0.37 0.81 0.96 1.04 1.01 0.80 5.6 0.99

I/S 300 3.0 48.1 0.13 0.62 1.07 1.08 1.06 1.04 0.95 6.5 1.14

I/S 600 6.0 96.1 0.14 0.60 1.01 1.08 1.06 1.05 0.95 6.8 1.20

2" (51 mm) Thickness Unfaced (Type “A” Mounting)** Thermal Data

Density Typical Coefficients by Frequency (Hz) “R” “RSI”Type pcf kg/m³ 125 250 500 1000 2000 4000 NRC*** (hr· ft² ·˚F) /Btu m2·˚K/w

I/S 150 1.5 24.0 0.24 0.68 1.10 1.13 1.10 1.07 1.00 8.3 1.46

I/S 225 2.25 36.1 0.19 0.88 1.15 1.14 1.10 1.07 1.05 8.7 1.53

I/S 300 3.0 48.1 0.24 1.00 1.11 1.08 1.06 1.05 1.05 8.7 1.53

I/S 600 6.0 96.1 0.38 0.93 1.10 1.07 1.07 1.07 1.05 9.1 1.60

2" (51 mm) Thickness FSK-25/PSK Faced (Type “A” Mounting)** Thermal Data

Density Typical Coefficients by Frequency (Hz) “R” “RSI”Type pcf kg/m³ 125 250 500 1000 2000 4000 NRC*** (hr· ft² ·˚F) /Btu m2·˚K/w

I/S 150 1.5 24.0 0.25 1.09 1.11 0.58 0.26 0.12 0.75 8.3 1.46

I/S 225 2.25 36.1 0.32 1.17 1.00 0.75 0.42 0.20 0.85 8.7 1.53

I/S 300 3.0 48.1 0.41 1.13 0.85 0.73 0.38 0.16 0.75 8.7 1.53

I/S 600 6.0 96.1 0.49 0.26 0.68 0.47 0.33 0.22 0.45 9.1 1.60

I/S Coated Black; 1.5 pcf (24.0 kg/m³) Density (Type “A” Mounting)** Thermal Data

Thickness Typical Coefficients by Frequency (Hz) “R” “RSI”pcf kg/m³ 125 250 500 1000 2000 4000 NRC*** (hr· ft² ·˚F) /Btu m2·˚K/w

1 25 0.09 0.29 0.67 0.89 1.03 0.99 0.70 4.0 0.702 51 0.23 0.73 1.05 1.13 1.06 1.07 1.00 8.0 1.41

* Per ASTM C 423. ** Type “A” Mounting per ASTM E 795. *** Noise Reduction Coefficient.

Visit us at JM.com Or call: 1-800-654-3103

Page 58: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Distributed by: Building Insulation Division717 17th Street (80202) P.O. Box 5108 Denver, CO 80217-5108 1-800-654-3103 JM.com

HIG-1214DK 2/06 © 2006 Johns Manville

Insul-SHIELD® Thermal and Acoustical Semi-rigid and Rigid Board Products

* When ordering material to comply with any government specification (or any other listed specification), a statement of that fact must appear on the purchase order.** Exceptions to ASTM standards: Not tested for compression resistance. Not tested for use at elevated temperatures. Corrosiveness is tested in galvanized steel instead of plain low-carbon steel. Type 100 has k value of 0.27 Btu-in./(hr.-sq. ft.-F) at 75˚ F

mean temperature.

TypeI/S 100

I/S 150

I/S 225

I/S 300

I/S 600

Coated I/S Black

ASTM C 612, Type IA, Category 1** X X X X X X

ASTM C 612, Type IB, Category 1** X X X X

ASTM C 612, Type IB, Category 2** X X

ASTM C 553, Type I and II** X X

ASTM C 665, Type I** X XASTM C 665, Type III,** Class A, Category 1 or 2 X

ASTM E 136 (Noncombustible) X X X XASTM E 84 (Flame/Smoke 25/50 or less) X X X X X X

RECOMMENDED STORAGE AND TRANSPORT

Store insulation indoors. Keep insulation clean and dry at all times. When transporting, cover completely with a waterproof tarpaulin as necessary.

SPECIFICATION COMPLIANCE*

Insul-SHIELD complies with applicable ASTM and federal specifications and the standards of ICBO, BOCA and SBCCI building codes. It meets air erosion standards up to 1,800 fpm (9.14 m/s) per UL 181.

SHORT FORM SPECIFICATION

All insulation shown on drawings or specified herein shall be “Johns Manville Insul-SHIELD Thermal and Acoustical Insulation.” Thermal resistance “R” (RSI) values of the insulation shall be R (RSI) in ceilings, R (RSI) in walls, and R (RSI) in floors over unheated spaces. The product shall have an FHC rating of 25/50 or less.

LIMITATIONS OF USE

Check applicable building codes.

Properly insulating a structure using Johns Manville building insulation helps preserve our environment by reducing energy consumption for heating and cooling, reducing the pollution resulting from fuel burning, reducing the emission of hazardous air pollutants during manufacturing and reducing waste through the utilization of recycled materials.

Technical specifications as shown in this literature are intended to be used as general guidelines only. The physical and chemical properties of Insul-SHIELD thermal and acoustical fiber glass insulation listed herein represent typical, average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. They are supplied as a technical service and are subject to change without notice. Any references to numerical flame spread or smoke developed ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with the sales office nearest you for current information. All Johns Manville products are sold subject to Johns Manville’s Limited Warranty and Limitation of Remedy. For a copy of the Johns Manville Limited Warranty and Limitation of Remedy or for information on other Johns Manville thermal and acoustical insulation and systems, call or write to the 800 number or address listed below.

Visit us at JM.com Or call: 1-800-654-3103

Page 59: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

M O U N T I N G D ATA

METALUX®T Y P E : C ATA L O G # :

COOPER LIGHTING

DESCRIPT ION

The W Series wraparound fea-tures economy and energy effi-cient performance. The lumi-naire’s characteristic clean, lowprofile design is both appealingand practically functional. The WSeries utilizes a clear, lowbrightness, extruded acrylicrefractor and a heavy gaugesteel end plate with embossedlight seal for dependable per-formance and good looks.

APPL ICAT ION

The efficient and economicalW Series is the perfect wrap-around for commercial spaces,schools, dormitories, offices andretail areas.

EB Ballast & STD Lamps

217 (36)

240 (72)

232 (61)

ES Ballast & STD Lamps

220 (58)

217 (45)

240 (86)

232 (71)

Luminaire Efficacy Rating

LER = FW-72

Catalog Number: W-232A

Yearly Cost of 1000 lumens,

3000 hrs at .08 KWH = $3.33

*Reference the lamp/ballast data in theTechnical Section for specific lamp/ballastrequirements.

W220217240232

2 ' S U R FA C E

2 L A M P S LT S O R H T S

4 ' O R 8 ' S U R FA C E

2 L A M P S

Commerc ia l Wrap

ADF020676(Supersedes ADF991800)

E N E R G Y D ATA

Input Watts:

SPEC IF ICAT ION FEATURES

A …C o n s t r u c t i o n

Housing die formed code gaugeprime cold rolled steel. Six fulllength ribs for strength. Ballastcover easily removed withouttools. Steel end plates with 7/8"KO and light-seal embossment.Couplers for continuous rowmounting.

B …E l e c t r i c a l *Ballasts are CBM/ETL Class “P”and are positively secured bymounting bolts. Pressure locklampholders. UL/CUL listed.Suitable for damp locations.

C …F i n i s h

Multistage, iron phosphate pre-treatment ensures maximumbonding and rust inhibitor.Lighting grade, baked whiteenamel finish.

D …F r a m e / S h i e l d i n g

100% clear virgin acrylic refrac-tor/lens. Sides have inside lin-ear prisms and bottom haspyramidal prisms for lowbrightness control. Lens can behinged from either side in a liftand shift manner.

L A M P C O N F I G U R AT I O N S

A B C D

8-1/2" [216mm]

2-5/8"[67mm]

8-1/4" [210mm]

7-1/4" [184mm]

7-1/4" [184mm]

1-1/4"[32mm]

7/8" [22mm] K.O. (7)Ceiling Stand-Off Embossments

96" [2438mm]

88-5/8" [2251mm]

90-7/8" [2308mm]

48" [1219mm]

7-1/4" [184mm]

1-1/4"[32mm]

7/8" [22mm] K.O. (5)Ceiling Stand-Off Embossments

Ground Screw Bump

48" [1219mm]

42-7/8" [1089mm]

40-5/8" [1032mm]

XX=3-1/4"[83mm]

2-5/8" [67mm]

8-1/2"[216mm]

7-1/4"[184mm]

X X=5-1/4" [133mm]

L I F T & S H I F T R E F R A C T O R

Easily Removed. Hinges Either Side(Not Recommended For Sloped Ceiling Applications.)

7-1/4"[184mm]

1-1/4"[32mm]

24" [610mm]

18-15/16" [481mm]21" [533mm]

16-11/16" [424mm]

14-11/16"[373mm]

7/8" [22mm] K.O. (4)9/32" [7mm] Hole (4)

1/4" [6mm] Hole For Grounding

cschulte
Porta King Building Systems Standard (4') Fluorescent Light Fixture Submittal Sheet 1 of 2
Page 60: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Visit our web site at www.cooperlighting.comCustomer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 ADF020676

Cande la

Angle Along II 45° Across⊥0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

1328 1328 1328

1307 1324 1336

1238 1296 1334

1122 1211 1249

950 1023 1034

667 749 738

364 451 441

200 277 310

108 189 325

10 155 374

11 241 389

12 232 344

13 166 253

13 106 164

14 59 92

14 35 51

15 25 32

15 17 19

13 13 13

O R D E R I N G I N F O R M AT I O N

W-217A 8 lbs.W-232A 17 lbs.8TW-232A 33 lbs.

S H I P P I N G I N F O R M AT I O N

Catalog No. Wt.

Coe f f i c i en ts o f Ut i l i za t ion

Effective floor cavity reflectance 20%

rc 80% 70% 50% 30% 10% 0%

rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0

RCR

0

1

2

3

4

5

6

7

8

9

10

Typ ica l VCP Percentages

Height Along Height Across

Room Size (Ft.) 8.5’ 10.0’ 8.5’ 10.0’

20 x 20

30 x 30

30 x 60

60 x 30

60 x 60

P H O T O M E T R I C S

Zona l Lumen Summary

Zone Lumens %Lamp %Fixture

0-30

0-40

0-60

0-90

90-180

0-180

||

W-232A

Energy SavingBallast

F32T8/35K Lamps2850 Lumens

Spacing criterion:(II) 1.3 x mountingheight, (⊥ ) 1.4 xmounting height

Efficiency 80.5%

Test Report#134P108

LER = FW-72

Yearly Cost of 1000lumens, 3000 hrs at.08 KWH = $3.33

1077 18.9 23.5

1775 31.1 38.7

2960 51.9 64.5

3739 65.6 81.4

852 14.9 18.6

4591 80.5 100.0

65 70 63 70

58 62 53 60

50 53 37 43

59 63 56 62

50 53 39 44

92 92 92 92 88 88 88 88 81 81 81 75 75 75 68 68 68 66

84 80 77 74 80 77 74 71 71 69 66 65 63 62 60 59 57 55

77 71 66 61 74 68 63 59 63 59 56 58 55 52 54 51 49 47

71 63 57 52 68 61 55 51 56 52 48 52 48 45 48 45 43 40

65 56 50 45 62 54 48 43 50 45 41 47 43 39 43 40 37 35

60 50 43 38 57 48 42 37 45 40 36 42 37 34 39 35 32 30

55 45 38 33 53 43 37 32 40 35 31 38 33 30 35 31 28 26

51 40 34 29 49 39 33 28 37 31 27 34 29 26 32 28 25 23

47 36 30 25 45 35 29 25 33 28 24 31 26 23 29 25 22 20

43 33 26 22 41 32 26 21 30 24 21 28 23 20 26 22 19 17

40 30 23 19 38 29 23 19 27 22 18 25 21 17 24 20 17 15

W

NOTE See option/accessories sections for additional detailed product data.Specifications and Dimensions subject to change without notice.1 Consult Pre Sales Technical Support.

Number

of Lamps(Not included)

Wattage (Length)

20=20W (24")17=17W (24") 40=40W (48")32=32W T8 (48")

2

Voltage1

120=120V277=277V\347=347VUNV=UniversalVoltage120-277V

A

A=Acrylic Refractor/Lens

SAMPLE NUMBER: W-232A

Opt ions (add as suffix)

Options

GL=Internal SingleElement FusingGM=Dual ElementFusingEL4=Emergency Lightingself-contained1

RIF1=Radio InterferenceSuppressorRLS=Rotor-Lock Socket (T8 Lamps Only)(Additional options available.See Accessory Section)

Ballast Type

LE3= Energy SavingMagneticBallast

LEOC8= Energy SavingMagneticBallast (T-8 LampOnly)

EB_ _= Generic Electronic BallastNo. of Ballasts1 or 2Lamp Size2=T128=T8

(For Specific ElectronicBallast Specify Brand andCatalog Number)

Leave Blank for LTS andHTS Fixtures.

Tandem

8T=8' Length

W

Series

A C C E S S O R I E S

(Order Separately)

SCF=Fixed Stem Set (Specify Length)

SCS=Swivel Stem Set (Specify Length)

SCA=Adjustable 48” Stem Set

A1B/Spacer-U=Spacer 1-1/2" to 2-1/2"from ceiling (Use 2 per fixture)

Lengths Available: 6, 8, 12, 18, 24, 36, 48

(Additional Accessories Available. See Optionsand Accessories Section.

L A M P S PA C I N G ( 8 " )

(2 Lamp Housing with 8" lamp spac-

ing also available.)

Catalog Number

W-A-232A (120V or 277V)

2-5/8" [67mm]

14" [356mm]

8"[203mm]

12-3/4"[324mm]

Voltage

LTS=LowTrigger Start(20 Watt)HTS=HighTrigger Start(20 Watt)

Wide Body

A= 2 Lamps

cschulte
32 120 EB81
cschulte
Porta King Building Systems Standard (4') Fluorescent Light Fixture Submittal Sheet 2 of 2
cschulte
Page 61: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

Porta-King Building Systems 4133 Shoreline Drive Earth City, MO 63045 800-456-5464 www.portaking.com

INSTALLATION INSTRUCTIONS

and

MAINTENANCE MANUAL

Page 62: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

ANCHOR DETAILS PREASSEMBLED BUILDINGS

________________________________________________

Porta-King Building Systems 4133 Shoreline Drive Earth City, MO 63045 800-456-5464 www.portaking.com

Page 63: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

PREPARATORY WORKand INSTALLATION

________________________________________________

Porta-King Building Systems4133 Shoreline DriveEarth City, MO 63045800-456-5464 www.portaking.com

PREPARATORYWORK

It is the responsibility ofthe buyer to perform allpreparatory work (unlessotherwise specified in aPorta-King BuildingSystems contract).

IMPORTANT: Thesecuring of buildingpermits and compliancewith appropriate buildingcodes is not theresponsibility of Porta-King, but is theresponsibility of thepurchaser of the building.

It is NOT theresponsibility of Porta-King to verify that these“suggestions” complywith local and statecodes, rather, it is theresponsibility of thepurchaser of the building.

SUGGESTIONS

1. Pour concrete island (pad) minimum 4” deep. Theisland should be a minimum of 12” wider than theroofline dimensions to allow a 6” concrete border oneach side of the building roofline.

2. Level the concrete island and install ballards at eachcorner of the building to further protect the buildingfrom damage caused by passing vehicles.

3. Provide three-wire 240v/110v single-phase, 100amperage, service (standard) to the concrete island.Refer to your Porta-King approval drawing, whichillustrate the proper “stub up” location for yourelectrical source.

4. If your installation requires plumbing, provide a freshwater supply line and gray-matter waste line to theconcrete island. Refer to your Porta-King approvaldrawing, which illustrate the proper “stub up” locationfor your plumbing lines.

5. Receive and offload the building using either a forklifttruck or overhead crane. Position the building square onthe concrete island and anchor. Remove wooden skids.

6. Recommended concrete anchor is ½” x 4” galvanized orstainless steel, or comply with local codes – which everis MORE stringent.

7. Make the final electrical / plumbing / communicationconnections and clean the work area.

TYPICAL CONDUIT ACCESS CUTOUTLOCATION AND BREAKER BOXSPECIFICATION

1. The “typical” conduit access floor cutout measures 6” x12”. It is located 10” and 4” from the corner of thebuilding, as illustrated.

2. The “standard” breaker box is a single-phase, 12-circuit,100-amp main load center, positioned as illustrated.

Page 64: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

RECEIVING andOFFLOADING INSTRUCTIONS

________________________________________________

Porta-King Building Systems4133 Shoreline DriveEarth City, MO 63045800-456-5464 www.portaking.com

RECEIVING

Each Porta-Kingpreassembled building willarrive to the job site viaflatbed truck. Each buildingwill be individually wrappedby Porta-King; additionally,the trucker will have tampedeach building to furtherprotect it during transit.

Once the building arrives,INSPECT each buildingPRIOR TO SIGNING theCLEAR BILL. If thebuilding arrives damagednote the damage on theclear bill. If you are unableto inspect each buildingthoroughly prior to signingthe clear bill, note on theclear bill the phrase“SUBJECT TOINSPECTION.” This willreduce your liability shouldthe building have incurredany “hidden” damage notyet identified.

Offload the building usingeither a forklift truck oroverhead crane. Set thebuilding on a concrete pad.Refer to “InstallationInstructions” for additionalinformation.

IMPORTANT: Buildings withexterior roofs can beexposed to the outdoorelements. If your buildingdoes not feature an exteriorroof design then thebuilding must be protectedfrom the elements. Any wall/ roof penetration (climatecontrol units, etc…) must besealed PRIOR to exposure tothe outside elements

OFFLOADING (FORKLIFT TRUCK)

1. Prior to shipping, each buildingis positioned onto a flat bedtruck utilizing a forklift truck;therefore, the use of a forklifttruck is recommended foroffloading the building at thejob site. The building ships onskids to allow easy access t beneath the building.

2. Simply drive the forks of the forklift truck beneath theelevated base of the building. Be sure not to puncturethe sub-floor with the forks as the building is lifted;forklift extensions may be needed on buildings withwider spans.

3. Gently lift the building from beneath its base. Be sure toprotect the building during the offloading process tokeep from damaging the building walls, glazing, and/orgutter / fascia.

OFFLOADING (OVERHEAD CRANE)

1. The building ships on skidsto allow easy access tobeneath the building.

2. Cradle the building bypositioning slings(…appropriately designedto carry the weight of thebuilding…) beneath thebuilding base. Be sure to use spreader bars to preventdamage to the building top-frame and/or roof fasciaduring the offloading process.

3. Gently lift the building and set onto a concrete pad.

OFFLOADING (LIFTING RINGS)

1. Utilizing the “adderoptional” lifting rings, attachthe lifting straps(…appropriately designed tocarry the weight of thebuilding…) to the liftingrings, which are attachedthrough the roof material.

2. Gently lift the building and set onto a concrete pad.

Page 65: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

GENERAL BUILDING CAREand MAINTENANCE

________________________________________________

Porta-King Building Systems4133 Shoreline DriveEarth City, MO 63045800-456-5464 www.portaking.com

GENERALBUILDING CAREandMAINTENANCE

Periodic cleaning andmaintenance usingproper procedures andcompatible cleaners isrecommended to prolongservice life.

For general cleaning andmaintenance, it isrecommended that thefollowing instructions beused.

FOUNDATION

1. Inspect the concrete island (pad) on which the buildingsits. The island should be kept clean and free of debris.Sweep the concrete island on a regular basis.

2. Inspect the grout and / or caulk around the base of thebooth and foundation. Replace as needed.

BUILDING INTERIOR

1. Periodically, sweep the interior of the booth with abroom.

2. Clean the interior walls, doors, and glazing (refer toinstructions found herein) when dirty. Be sure not to useabrasive objects and cleaners, which may damage theinterior finish.

3. Inspect sliding windows and door tracks for dirt anddebris. Keep dirt and debris from these areas.

4. Inspect electrical and communication connectsperiodically to be sure that the connections are tight andnot frayed. Replace damaged / questionablecomponents / materials. Replace light fixtures asneeded.

5. Refer to your manufacturers warranty on climatecontrol components for periodic general care andmaintenance instructions.

BUILDING EXTERIOR

1. Periodically, clean the building exterior surfaces, asneeded (refer to instructions found herein).

2. Inspect window framing and doors for broken seals.Replace damaged components and repair broken seals,as needed.

3. Inspect roof, especially during the autumn months, forfallen debris (such as, leaves, sticks, paper, etc…) andremove such items from the roof. Keep the waterdrainage holes / scuppers free from debris to insureproper water drainage.

Page 66: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

CLEAR ANODIZED ALUMINUMSURFACES

________________________________________________

Porta-King Building Systems4133 Shoreline DriveEarth City, MO 63045800-456-5464 www.portaking.com

GENERAL CAREANDMAINTENANCEINSTRUCTIONS

Periodic cleaning andmaintenance usingproper procedures andcompatible cleaners isrecommended to prolongservice life.

For general cleaning andmaintenance, it isrecommended that thefollowing instructions andmaterials be used.

______________________________

Disclaimer: Although anyinformation, recommendations, oradvice contained herein is given ingood faith, Porta-King makes nowarranty or guarantee, express orimplied, as to the effectiveness orsafety of any procedure or materialsand it shall in no event beresponsible for any loss resultingfrom any use of these materials on itsproduct described herein.IMPORTANT: If a material isfound to be incompatible in a short-term test, it will usually be found tobe incompatible in the field. Theconverse, however, is not alwaystrue. Favorable performance is noguarantee that actual end-useconditions have been duplicated.Therefore, these results should beused as a guide only and it isrecommended that the user test theproducts under actual end-useconditions.______________________________

CLEANING PROCEDURES

1. Wash with a mild solution of soap or detergent andlukewarm water.

2. Using a soft cloth or sponge, gently wash the clearanodized aluminum surface to loosen dirt and grime andrinse well with clean water.

3. To prevent water spotting, thoroughly dry with chamoisor cellulose sponge.

4. Avoid the use of abrasive cleaners, squeegees and/orother cleaning implements that may mar or gouge theglazing material. Avoid cleaning in direct sunlight toprevent streaking. Avoid use of cleaners containingacid (…citrus or otherwise).

CLEANING AGENTS WHICH HAVE BEENFOUND TO BE COMPATIBLE WITH CLEARANODIZED ALUMINUM MATERIALS UNDERLABORATORY CONDITIONS

• Aqueous Solutions of Soaps and DetergentsWindex Top JobJoy Mr. CleanFantastik Formula 409

• Organic SolventsNaphtha (VM&P) grade (graffiti removal)

• Alcohol’sIsopropyl Alcohol (graffiti removal)

All residual solvents should be removed with a secondaryrinse.

COMPONENT LISTING OF CLEAR ANODIZEDALUMINUM MATERIALS

• Duraluminum: Building frame and exterior wall panels,standard-design window frames and door, gutter andfascia.

• Durasteel, Durasteel-PC, Durasteel-Shelters:Building standard-design window frames and doors.

Page 67: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

PAINTED SURFACES_________________________________________________

Porta-King Building Systems4133 Shoreline DriveEarth City, MO 63045800-456-5464 www.portaking.com

CLEANING ANDMAINTENANCEINSTRUCTIONS

Your Porta-Kingpreassembled building isfabricated from eithergalvanized steel or clearanodized aluminummaterial. The buildinghas been properlyprotected with a baseprimer and commercialquality paint. Periodiccleaning using properprocedures andcompatible cleaners isrecommended to prolongservice life.

In the event that thebuilding paint surface hasbeen removed it isimperative that thedamaged area beproperly touched up toprevent prematureoxidation.

For general cleaning andmaintenance, it isrecommended that thefollowing instructions andmaterials be used.

CLEANING PROCEDURES

1. Painted surfaces should be cleaned only with cool to warmwater and mild detergent, such as Meguiars #M-62 carwash shampoo.

2. Using a soft cloth or sponge, gently wash the paintedsurface to loosen dirt and grime and rinse well with cleanwater. Always hand-apply cleaners.

3. To prevent water spotting, thoroughly dry with chamois orcellulose sponge.

4. For blemishes not removed by normal cleaning such asscuffs, light stains and excessively dirty areas, clean with amild compound cleaner, such as Meguiars #M-9716 paintcleaner.

5. Avoid the use: (a) of abrasive cleaners, squeegees and/orother cleaning implements that may mar or gouge thecoating; (b) aggressive compound containing grit; (c)harsh acidic type or abrasive cleaners or solvents; (d)high-speed buffers or polishes; (e) high temperaturewater such as a steam cleaning pressure washer designedfor degreasing or industrial cleaning; (f) pressure washingis recommended ONLY with unheated water and a lowerpressure – between 800 and 1200 pounds.

DAMAGE REPAIR & TOUCH-UP

Scratches and gouges where painted surfaces have beenscored or removed will require paint touch-up.

For light scratches where no metal is exposed, clean the areaof any contaminates – such as dirt or grease. Allow to dry –brush or dab touch-up paint into area.

For deeper scratches where bare metal is exposed, filler maybe required to level the surface before painting. Sand theexposed metal with 320-grit sandpaper. To level the area,apply filler putty, such as 3M-#5966, with a razor blade orsmall spreader into damaged area. Allow to dry – sandsmooth with the 320-grit sandpaper. After area is level, puttymust be coated with any primer sealer type product either bybrush or aerosol spray. After area is sealed, apply paint torepaint area. Brush edges lightly into undamaged areasurrounding repair to help blend.

To repaint the entire area of a building, repair any exposed metaldamage as previously instructed. Scuff all surfaces to be paintedwith 3M-#7447 Scotch Brite pad until sheen is removed. Roll orspray one to two coats of exterior grade enamel paint over entirearea, as required.

Page 68: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

SLIDING DOOR and SLIDING WINDOW ADJUSTMENTS

________________________________________________

Porta-King Building Systems4133 Shoreline DriveEarth City, MO 63045800-456-5464 www.portaking.com

MAINTENANCEINSTRUCTIONS

Periodic door andwindow adjustments maybe required throughnormal use. Using properprocedures isrecommended to prolongservice life.

For general door andwindow maintenance, it isrecommended that thefollowing instructions beused.

DOOR LEVELING & REMOVALINSTRUCTIONS

Leveling1. Using a thin (flat)

wrench turn the Postto adjust verticallyfor height andplumb.

2. Do not unscrewPost from theHanger.

Removal1. To remove door, activate Tab (gray) forward with a Flat

back Screw Driver.

WINDOW LEVELING / ADJUSTMENTINSTRUCTIONS

Leveling1. Using a Phillips screw-

driver turn theadjustment screw eitherclockwise or counterclockwise to raise orlower the activewindow.

Removal1. To remove window,

position the window panel to the middle ofthe entire window-frame opening (the window willappear half-open / half-closed).

2. With your hands, grab each side of the window panelframe and gently lift upward then pull inward towardyourself.

Page 69: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

GLAZING________________________________________________

Porta-King Building Systems4133 Shoreline DriveEarth City, MO 63045800-456-5464 www.portaking.com

CLEANING ANDMAINTENANCEINSTRUCTIONS

Periodic cleaning usingproper procedures andcompatible cleaners isrecommended to prolongservice life.

For general cleaning andmaintenance, it isrecommended that thefollowing instructions andmaterials be used.

______________________________

Disclaimer: Although anyinformation, recommendations, oradvice contained herein is given ingood faith, Porta-King makes nowarranty or guarantee, express orimplied, as to the effectiveness orsafety of any procedure or materialsand it shall in no event beresponsible for any loss resultingfrom any use of these materials on itsproduct described herein.IMPORTANT: If a material isfound to be incompatible in a short-term test, it will usually be found tobe incompatible in the field. Theconverse, however, is not alwaystrue. Favorable performance is noguarantee that actual end-useconditions have been duplicated.Therefore, these results should beused as a guide only and it isrecommended that the user test theproducts under actual end-useconditions.______________________________

CLEANING PROCEDURES

1. Wash with a mild solution of soap or detergent andlukewarm water.

2. Using a soft cloth or sponge, gently wash the glazing toloosen dirt and grime and rinse well with clean water.

3. To prevent water spotting, thoroughly dry with chamoisor cellulose sponge.

4. Avoid the use of abrasive cleaners, squeegees and/orother cleaning implements that may mar or gouge theglazing material. Avoid cleaning in direct sunlight toprevent streaking.

CLEANING AGENTS WHICH HAVE BEENFOUND TO BE COMPATIBLE WITHTEMPERED GLASS, LAMINATED GLASS,POLYCARBONATE AND ACRYLIC GLAZINGMATERIALS UNDER LABORATORYCONDITIONS

• Aqueous Solutions of Soaps and DetergentsWindex Top JobJoy Mr. CleanFantastik Formula 409

• Organic SolventsNaphtha (VM&P) grade

• Alcohol’sIsopropyl Alcohol

All residual solvents should be removed with a secondaryrinse.

GRAFFITI REMOVAL

1. Be sure that the solvent will not attack the glazing.2. Isopropyl alcohol, VM&P naphtha or similar solvents

have been successfully used.3. Be sure to rinse with clear water after solvent

application.

Page 70: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous

WARRANTY DURALUMINUM and DURASTEEL PRODUCTS

________________________________________________

Porta-King Building Systems 4133 Shoreline Drive Earth City, MO 63045 800-456-5464 www.portaking.com

WARRANTY INFORMATION This warranty shall not cover items damaged due to acts of vandalism, misuse, abuse, damage caused by a third party, or natural phenomena. Warranty shall not cover damage caused during maintenance actions by untrained or unapproved personnel.

DURALUMINUM PRODUCTS General

The workmanship and material on all Porta-King Duraluminum products are guaranteed to be free from manufacturing defect for a period of one- (1) year from the date of shipment. All accessory items (i.e. storage drawers, climate control units, and/or other special “buy-out” items) shall be covered separately under the specific warranty of that manufacturer.

Extended 1. A five- (5) year warranty applies to all clear anodized

aluminum surfaces to be free from oxidation. 2. A five- (5) year warranty applies to all wall panels to be

free from swelling and delamination due to moisture absorption.

3. A ten- (10) year limited warranty applies to the exterior roof from leaks, in applications where the roof is lined with a rubber roofing membrane.

DURASTEEL PRODUCTS General

The workmanship and material on all Porta-King Durasteel products are guaranteed to be free from manufacturing defect for a period of one- (1) year from the date of shipment. All accessory items (i.e. storage drawers, climate control units, and/or other special “buy-out” items) shall be covered separately under the specific warranty of that manufacturer.

Extended 1. A five- (5) year warranty applies to all clear anodized

aluminum surfaces to be free from oxidation. 2. A ten- (10) year limited warranty applies to the exterior

roof from leaks, in applications where the roof is lined with a rubber roofing membrane.

Page 71: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
ahannon
Text Box
DESIGN DATA OF A SIMILAR STRUCTURE - RATED FOR 110 MPH WIND LOAD
Page 72: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 73: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 74: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 75: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 76: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 77: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 78: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 79: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 80: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 81: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 82: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 83: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 84: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 85: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 86: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 87: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 88: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 89: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 90: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 91: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 92: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 93: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 94: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 95: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 96: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 97: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 98: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 99: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 100: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 101: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 102: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 103: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 104: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 105: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 106: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous
Page 107: K:Darren RutmanisDurasteelCS03562 BR-105SL Model (1)login.sloneassoc.com/login/documents/13 34 20 Resubmittal Prefab... · Flammability UL 94 V2. Operating Temperatures Maximum continuous