kerbside mtfi map

4
MTFI KERBSIDE FUEL POINT North Yorkshire O7/02/11 CREATED BYDAVID MURRAY 1 of 4 CONTROL ROOM AND EMERGENCY PHONE KEY FIRE POINT SPILL KIT PUMP 2 KEY READER TANK 1 MT DIESO TANK 2 ULGAS UK DIES O PATH TO SQN BARRIER Way in EXIT AIR LINE PUMP 1 Zone 2 Zone 1 Zone 0 VENTS PUMP 4 INTERCEPTED AREA IN RED (ARCO DRAINS) BECOMES Zone 2 AROUND SPILLAGE 3 M INTERCEPTOR Vent pipe for ULGAS and INTERCEPTOR opening (Zone 1) at 5m above working level and a Zone 2 radius of 2m around it. Vent dia 50mm at 250hr rate. (h=5m ,R1 = 2m.

Upload: david-murray

Post on 20-Jul-2015

47 views

Category:

Documents


0 download

TRANSCRIPT

MTFI KERBSIDE FUEL POINT North Yorkshire O7/02/11 CREATED BYDAVID MURRAY

1 of 4

CONTROL ROOM AND EMERGENCY PHONE

KEY

FIRE POINT

SPILL KIT

PUMP 2KEY READER

TANK 1MT

DIESO

TANK 2ULGAS

UK DIES

O

PATH TO SQN

BARRIER

Way in

EXIT

AIR LINE

PUMP 1

Zone 2Zone 1Zone 0

VENTS

PUMP 4

INTERCEPTED AREA IN RED (ARCO DRAINS)BECOMES Zone 2 AROUND SPILLAGE 3 M

INTERCEPTOR

Vent pipe for ULGAS and INTERCEPTOR opening (Zone 1) at 5m above working level and a Zone 2 radius of 2m around it. Vent dia 50mm at 250hr rate. (h=5m ,R1 = 2m.

MTFI KERBSIDE FUEL POINT North Yorkshire O7/02/11 CREATED BYDAVID MURRAYTANKER DELIVERY AREA

2 of 4

MTFI KERBSIDE FUEL POINT North Yorkshire O7/02/11 CREATED BYDAVID MURRAYZONE AS SEEN ON PICTURE

3 of 4

MTFI KERBSIDE FUEL POINT North Yorkshire O7/02/11 CREATED BYDAVID MURRAYZONE TO INCLUDE POSSIBLE SPILLAGE AREA FROM USRP

ZONE 2 IN THIS AREA IF A SPILLAGE HAPPENS, MAX SIZE DEPENDS ON SPILL, USUAL IS 3 M

4 of 4