key changes to the 2015 ibc - sfpe-asa.org handouts/2014-09 ibc-ifc 2015... · key changes to the...

42
9/3/2014 2015 IBC/IFC Key Changes 1 2015 IBC Key Changes 1 Presented by Key Changes to the 2015 IBC Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction Introduction § Instructor § Kevin Scott § KH Scott & Associates § [email protected] § (661) 431-5897

Upload: hoangtuong

Post on 06-Mar-2018

217 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 1

2015 IBC Key Changes 1

Presented by

Key Changes to the 2015 IBCKey Changes to the 2015 IBC

2015 IBC Key Changes 2

IntroductionIntroduction

§ Instructor§ Kevin Scott§ KH Scott & Associates§ [email protected]§ (661) 431-5897

Page 2: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 2

2015 IBC Key Changes 3

ObjectivesObjectives

§ Major changes§ 2015 IBC§ 2015 IFC

§ Many other changes not covered

2015 IBC Key Changes 4

Food Processing Facilities & Commercial Kitchens§304.1

Food Processing Facilities & Commercial Kitchens§304.1

§ Group B – not associated with restaurants, cafeterias and similar dining facilities ≤2500 ft2

§ Group F-1 – not associated with restaurants, cafeterias and similar dining facilities >2500 ft2

Page 3: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 3

2015 IBC Key Changes 5

Group I-1§308.3

Group I-1§308.3§ Condition 1 – all persons receiving

custodial care are capable of responding to an emergency situation to complete building evacuation without any assistance

§ Condition 2 – any persons receiving custodial care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation

Residential Board and Care

Assisted Living

2015 IBC Key Changes 6

Group I-2§308.4

Group I-2§308.4§ Condition 1 – nursing and

medical care, but not emergency care, surgery, psychiatric care

§ Condition 2 – nursing and medical care and emergency care, surgery, or in-patient psychiatric care

Nursing Home

Hospital

Page 4: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 4

2015 IBC Key Changes 7

Group R-4§310.6

Group R-4§310.6§ Condition 1 – all persons receiving

custodial care are capable of responding to an emergency situation to complete building evacuation without any assistance

§ Condition 2 – any persons receiving custodial care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation

Halfway House

Congregate Care

2015 IBC Key Changes 8

Applicability of High-Rise Provisions§403.1

Applicability of High-Rise Provisions§403.1

Exceptions:1. Airport traffic control towers – §412.32. Open parking garages – §406.53. Group A-5 – §303.64. Special industrial – §503.1.15.1. Group H-1 buildings5.2. Buildings with Group H-2 –

§415.8,415.9.2, 415.9.3 or 426.15.3. Buildings with Group H-3 – §415.8

Page 5: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 5

2015 IBC Key Changes 9

Atrium – Smoke Control§404.5

Atrium – Smoke Control§404.5§ Atriums connecting only 2 stories do not require

smoke control, unless atrium is in a Group I-2, Condition 2 facility

2015 IBC Key Changes 10

Atrium – Egress Travel§404.9, §404.10

Atrium – Egress Travel§404.9, §404.10§ Egress travel not through an

atrium = §1017 § Egress travel through an

atrium on LED = §1017§ Egress travel through an

atrium not on LED = 200’§ ≤50% of interior exit stairways

are permitted to egress through an atrium on LED

Page 6: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 6

2015 IBC Key Changes 11

Size of Group I-2 Smoke Compartments§407.5

Size of Group I-2 Smoke Compartments§407.5§ Smoke compartments required on every story used by ≥50

persons, or persons receiving care, treatment or sleeping § Group I-2, Condition 1 – smoke compartments ≤22,500 ft2

§ Group I-2, Condition 2 – smoke compartments ≤40,000 ft2

§ Travel distance in a smoke compartment to a smoke barrier door ≤200’

X

X

X

X

1-HRSmokeBarrier

2015 IBC Key Changes 12

Travel Distance in Aircraft Manufacturing Facilities§412.7

Travel Distance in Aircraft Manufacturing Facilities§412.7

§ Exit access travel distance can be increased in buildings used for the manufacturing of aircraft if:§ Type I or II construction§ Distance cannot exceed

HEIGHT (feet) b

MANUFACTURING AREA (square feet) a

≥150,000 ≥200,000 ≥250,000 ≥500,000 ≥750,000 ≥1,000,000≥25 400 450 500 500 500 500≥50 400 500 600 700 700 700≥75 400 500 700 1,000 1,000 1,000≥100 400 500 750 1,000 1,250 1,500

Table 412.7Aircraft Manufacturing Exit Access Travel Distance

Contiguous floor area AT

indicated height

Page 7: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 7

2015 IBC Key Changes 13

Building Height and Number of StoriesTables 504.3 & 504.4

Building Height and Number of StoriesTables 504.3 & 504.4§ Table 504.3 – Allowable Building Height in Feet§ Table 504.4 – Allowable Number of Stories

Occupancy Classification

Type Of Construction (PARTIAL)See

FootnotesType I Type II Type III Type IV Type V

A B A B A B HT A B

A-1 NS UL 5 3 2 3 2 3 2 1S UL 6 4 3 4 3 4 3 2

A-2 NS UL 11 3 2 3 2 3 2 1S UL 12 4 3 4 3 4 3 2

A-3 NS UL 11 3 2 3 2 3 2 1S UL 12 4 3 4 3 4 3 2

A-4 NS UL 11 3 2 3 2 3 2 1S UL 12 4 3 4 3 4 3 2

A-5 NS UL UL UL UL UL UL UL UL ULS UL UL UL UL UL UL UL UL UL

B NS UL 11 5 3 5 3 5 3 2S UL 12 6 4 6 4 6 4 3

E NS UL 5 3 2 3 2 3 1 1S UL 6 4 3 4 3 4 2 2

F-1 NS UL 11 4 2 3 2 4 2 1S UL 12 5 3 4 3 5 3 2

Occupancy Classification

Type Of ConstructionSee

FootnotesType I Type II Type III Type IV Type V

A B A B A B HT A B

A, B, E, F, M, S, U NS b UL 160 65 55 65 55 65 50 40S UL 180 85 75 85 75 85 70 60

H-1, H-2, H-3, H-5 NS c,dUL 160 65 55 65 55 65 50 40S

H-4 NS c,d UL 160 65 55 65 55 65 50 40S UL 180 85 75 85 75 85 70 60

I-1 Condition 1, I-3 NS d,e UL 160 65 55 65 55 65 50 40S UL 180 85 75 85 75 85 70 60

I-1 Condition 2, I-2 NS d,f,e UL 160 65 55 65 55 65 50 40S UL 180 85

I-4 NS d,g UL 160 65 55 65 55 65 50 40S UL 180 85 75 85 75 85 70 60

RNS d,h UL 160 65 55 65 55 65 50 40S13R 60 60 60 60 60 60 60 60 60

S UL 180 85 75 85 75 85 70 60

NS = buildings not sprinkleredS = NFPA 13 sprinklered buildingsS13R = NFPA 13R sprinklered buildings

2015 IBC Key Changes 14

Building Area§506.2

Building Area§506.2

Table 506.2Allowable Area Factor (At = NS, S1, S13R, or SM, as applicable) in square feet

Occupancy Classification

Type Of Construction (PARTIAL)

See Footnotes Type I Type II Type III Type IV Type VA B A B A B HT A B

A-1NS UL UL 15,500 8,500 14,000 8,500 15,000 11,500 5,500S1 UL UL 62,000 34,000 56,000 34,000 60,000 46,000 22,000SM UL UL 46,500 25,500 42,000 25,500 45,000 34,500 16,500

A-2NS UL UL 15,500 9,500 14,000 9,500 15,000 11,500 6,000S1 UL UL 62,000 38,000 56,000 38,000 60,000 46,000 24,000SM UL UL 46,500 28,500 42,000 28,500 45,000 34,500 18,000

A-3NS UL UL 15,500 9,500 14,000 9,500 15,000 11,500 6,000S1 UL UL 62,000 38,000 56,000 38,000 60,000 46,000 24,000SM UL UL 46,500 28,500 42,000 28,500 45,000 34,500 18,000

A-4NS UL UL 15,500 9,500 14,000 9,500 15,000 11,500 6,000S1 UL UL 62,000 38,000 56,000 38,000 60,000 46,000 24,000SM UL UL 46,500 28,500 42,000 28,500 45,000 34,500 18,000

A-5NS

UL UL UL UL UL UL UL UL ULS1SM

BNS UL UL 37,500 23,000 28,500 19,000 36,000 18,000 9,000S1 UL UL 150,000 92,000 114,000 76,000 144,000 72,000 36,000SM UL UL 112,500 69,000 85,800 57,000 108,000 54,000 27,000

ENS UL UL 26,500 14,500 23,500 14,500 25,500 18,500 9,500S1 UL UL 106,000 58,000 94,000 58,000 102,000 74,000 38,000SM UL UL 79,500 43,500 70,500 43,500 76,500 55,500 28,500

NS = buildings not sprinkleredS1 = sprinklered 1-story buildingsSM = sprinklered multiple-story buildings

Page 8: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 8

2015 IBC Key Changes 15

Building Area – Example §506.2

Building Area – Example §506.2

Table 506.2Allowable Area Factor (At = NS, S1, S13R, or SM, as applicable) in square feet

§ Single story, sprinklered A-3 – Type IIB; no frontage increase

§ Aa = At + (NS x If)§ Aa =

Occupancy Classification

Type Of Construction (PARTIAL)

See Footnotes Type I Type II Type III Type IV Type VA B A B A B HT A B

A-1NS UL UL 15,500 8,500 14,000 8,500 15,000 11,500 5,500S1 UL UL 62,000 34,000 56,000 34,000 60,000 46,000 22,000SM UL UL 46,500 25,500 42,000 25,500 45,000 34,500 16,500

A-2NS UL UL 15,500 9,500 14,000 9,500 15,000 11,500 6,000S1 UL UL 62,000 38,000 56,000 38,000 60,000 46,000 24,000SM UL UL 46,500 28,500 42,000 28,500 45,000 34,500 18,000

A-3NS UL UL 15,500 9,500 14,000 9,500 15,000 11,500 6,000S1 UL UL 62,000 38,000 56,000 38,000 60,000 46,000 24,000SM UL UL 46,500 28,500 42,000 28,500 45,000 34,500 18,000

38,000 + (9,500 = 38,000 ft2x 0)

2015 IBC Key Changes 16

Mezzanines§505.2.3

Mezzanines§505.2.3§ Not considered a story§ ≤33.3% of floor area in the room where they are

located§ Floor area of mezzanine added to floor below§ Mezzanine open to floor below§ ≤42” high wall§ Can be enclosed if:§ OL ≤10, or§ ≥2 exits or exit access stairways, or§ Floor area ≤10%

Page 9: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 9

2015 IBC Key Changes 17

Group H-5 in Unlimited Area Buildings§507.9

Group H-5 in Unlimited Area Buildings§507.9§ Unlimited area of mixed occupancy of Group B,

F, H-5, M or S buildings provided:§ ≤2 stories above grade plane § Automatic sprinkler system throughout § Surrounded by public ways or yards ≥60’§ Type I or II construction§ Group H-5 separated per §415.11 and §508.4§ Group H-5 is less than allowable area, OR

subdivided into areas by 2-HR fire barriers

2015 IBC Key Changes 18

Sprinklers for 1-HR SubstitutionTable 601, Footnote d

Sprinklers for 1-HR SubstitutionTable 601, Footnote d§ 2012 allowed fire sprinklers as substitute for 1-HR

construction, but prohibited any modifications based on sprinklers

§ Footnote deleted which allowed 1-HR substitution§ Sprinkler system is no longer allowed as a substitution

for 1-HR constructionOccupancy

Classification

Type Of Construction (PARTIAL)

See Footnotes Type I Type II Type III Type IV Type VA B A B A B HT A B

A-2NS UL UL 15,500 9,500 14,000 9,500 15,000 11,500 6,000S1 UL UL 62,000 38,000 56,000 38,000 60,000 46,000 24,000SM UL UL 46,500 28,500 42,000 28,500 45,000 34,500 18,000

Page 10: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 10

2015 IBC Key Changes 19

Vertical Separation of Openings§705.8.5

Vertical Separation of Openings§705.8.5§ Generally, fire-resistance-rated exterior walls are only

required to be protected on the interior side when the wall is >10’ from property line

§ When building is >3 stories protection required on both sides of exterior wall

Not required if building is sprinklered

2015 IBC Key Changes 20

Fire Walls – Structural Stability§706.2

Fire Walls – Structural Stability§706.2§ Designed to allow collapse on either side without

collapse of the fire wall§ Single fire wall§ Double fire wall – NFPA 221§ Tied fire wall – NFPA 221§ Cantilevered fire wall – NFPA 221

§ Now allowed to utilize any design in NFPA 221

Page 11: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 11

2015 IBC Key Changes 21

Ducts Transitioning between Shafts§717.1.1

Ducts Transitioning between Shafts§717.1.1§ Shafts enclosing vertical openings are fire-

resistance-rated

Fire-resistance-rated shaft Duct

Dampers at each shaft penetration

2015 IBC Key Changes 22

Corridor Dampers§717.3, §717.5.4.1

Corridor Dampers§717.3, §717.5.4.1§ Corridor dampers required at penetration of

corridor ceiling constructed as a corridor wall§ Ceiling radiation dampers required at penetration

of floor/ceiling or roof/ceiling assembly§ Ratings§ 1-HR fire-resistance rating§ Class I or II leakage rating

§ If fans are designed to operate during a fire, damper must be specifically listed for such operation

Page 12: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 12

2015 IBC Key Changes 23

Occupant Load FactorsTable 1004.1.2

Occupant Load FactorsTable 1004.1.2§ Mercantile occupant load factor revised to a

single factor of 60§ Applicable regardless of the story

2012 Table 1004.1.2Maximum Floor Area Allowances per Occupant

Function of Space Occupant Load Factor a

MercantileAreas on other floorsBasement and grade floor areasStorage, stock, shipping areas

60 gross30 gross300 gross

Table 1004.1.2Maximum Floor Area Allowances per Occupant

Function of Space Occupant Load Factor a

Mercantile

Storage, stock, shipping areas

60 gross

300 gross

2015 IBC Key Changes 24

Exits – Number and Configuration§1006

Exits – Number and Configuration§1006

§ ReformattedTable 1006.2.1 – Spaces with One Exit or Exit Access Doorway

OCCUPANCYMAXIMUM

OCCUPANT LOAD OF SPACE

MAXIMUM COMMON PATH OF TRAVEL DISTANCE (feet)

Without Sprinkler System (feet) With Sprinkler System(feet)

Occupant Load

≤30 >30A c, E, M 49 75 75 75 a

B 49 100 75 100 a

F 49 75 75 100 a

H-1, H-2, H-3 3 NP NP 25 b

H-4, H-5 10 NP NP 75 b

I-1, I-2 d, I-4 10 NP NP 75 a

I-3 10 NP NP 100 a

R-1 10 NP NP 75 a

R-2 10 NP NP 125 a

R-3 e 10 NP NP 125 a

R-4 e 10 75 75 125 a

S f 29 100 75 100 a

U 49 100 75 75 a

Page 13: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 13

2015 IBC Key Changes 25

Measurement of Exit Separation§1007.1.1.1, Item 1

Measurement of Exit Separation§1007.1.1.1, Item 1

§ Distance between doorways measured to anypoint in doorway width

2015 IBC Key Changes 26

Measurement of Exit Separation§1007.1.1.1, Item 2

Measurement of Exit Separation§1007.1.1.1, Item 2

§ Distance between exit access stairways measured to closest riser

Separation distance measured to closest risers at floor level

Separation distance must be maintained

Page 14: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 14

2015 IBC Key Changes 27

Two-Way Communication Systems§1009.8

Two-Way Communication Systems§1009.8

§ 2-way communication at all elevators except at LED§ Exceptions:§ Not required on floors with exit

ramps§ Service elevators§ Freight elevators§ Private residence elevator

§ Written directions and visual character sign required

2015 IBC Key Changes 28

Door Locking Systems§1010.1.9

Door Locking Systems§1010.1.9

§ Egress doors must be readily openable, EXCEPT:

New Locking Method Old Locking Method 2015 Section

Controlled Egress Doors in Groups I-1 and I-2

Special Locking Arrangements in Group I-2

§1010.1.9.6

Delayed Egress Delayed Egress Locks §1010.9.7

Sensor Release of Electrically Locked Egress Doors

Access-Controlled Egress Doors §1010.1.9.8

Electromagnetically Locked Egress Doors

Electromagnetically Locked Egress Doors

§1010.1.9.9

Locking Arrangements in Correctional Facilities

Locking Arrangements in Correctional Facilities

§1010.1.9.10

Stairway Doors Stairway Doors §1010.1.9.11

Page 15: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 15

2015 IBC Key Changes 29

Travel Distance in Groups F-1 and S-1§1017.2.2

Travel Distance in Groups F-1 and S-1§1017.2.2

§ Exit access travel distance in F-1 and S-1 is:§ 200’ – not sprinklered§ 250’ – sprinklered§ 400’ if:§ Sprinklered§ Building is limited to 1 story§ Minimum of 24’ from floor to

underneath side of roof or ceiling above

≥24’

2015 IBC Key Changes 30

Corridor Width and Capacity§1020.2

Corridor Width and Capacity§1020.2

§ Corridor width is based on use and OL

Table 1020.2 – Minimum Corridor WidthOCCUPANCY WIDTH (minimum)

Any facilities not listed below 44 inchesAccess to and utilization of mechanical, plumbing or electrical systems or equipment 24 inches

With an OL <50 36 inchesWithin a dwelling unit 36 inchesIn Group E with a corridor having an OL ≥100 more 72 inchesIn corridors and areas serving stretcher traffic in ambulatory care facilities 72 inches

Group I-2 in areas where required for bed movement 96 inches

Page 16: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 16

2015 IBC Key Changes 31

§1023.3.1Stairway Extension§1023.3.1Stairway Extension§ Interior exit stairway can connect to an exit

passageway without a fire-rated door, if NOother openings into the exit passageway

No other openings in exit

passageway

Fire rated door not required

Door not required

Wall not required

2015 IBC Key Changes 32

Structural Glued Cross-Laminated Timber§2303.1.4

Structural Glued Cross-Laminated Timber§2303.1.4§ “A prefabricated engineered

wood product consisting of at least three layers of solid-sawn lumber or structural composite lumber where the adjacent layers are cross-oriented and bonded with structural adhesive to form a solid wood element.”

§ Referred to as CLT§ ANSI/APA PRG 320-2011 Photo courtesy of FP Innovations

Page 17: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 17

2015 IBC Key Changes 33

Engineered Wood Rim Board§2303.1.13

Engineered Wood Rim Board§2303.1.13

Photo courtesy of APA –The Engineered Wood Association

§ “A full-depth structural composite lumber, wood structural panel, structural glued laminated timber, or prefabricated wood I-joist member designed to transfer horizontal (shear) and vertical (compression) loads, provide attachment for diaphragm sheathing, siding and exterior deck ledgers, and provide lateral support at the ends of floor or roof joists or rafters.”

§ ANSI/APA PRR 410 § ASTM D 7672

2015 IBC Key Changes 34

Gypsum Panel ProductsChapter 25

Gypsum Panel ProductsChapter 25§ “The general name for a family

of sheet products consisting essentially of gypsum.”

§ Essentially gypsum sheet products that are manufactured unfaced or with a facing other than paper§ Glass mat-faced§ Unfaced gypsum sheet materials

Photo courtesy of Gypsum Association

Page 18: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 18

2015 IBC Key Changes 35

Plastic Composites§2612

Plastic Composites§2612§ Plastic Composite – A generic

designation that refers to wood/plastic composites and plastic lumber.

§ Plastic Lumber – A manufactured product made primarily of plastic materials (filled or unfilled) which is generally rectangular in cross-section.

§ Wood/Plastic Composite – A composite material made primarily from wood or cellulose-based materials and plastic.

§ Flame spread index ≤200

Photo courtesy of Peter Kulczyk

Allowed for exterior deck boards, stair treads, handrails and guards

in Type VB buildings

2015 IBC Key Changes 36

Elevator Hoistway Venting§3004

Elevator Hoistway Venting§3004§ Requirement for elevator hoistway venting in §3004 has

been deleted§ Elevator hoistways are no longer required to be vented

to the exterior2012 required venting in

elevator shafts penetrating >3 stories

2015 – venting is not required

Page 19: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 19

2015 IBC Key Changes 37

Elevator Lobbies§3006

Elevator Lobbies§3006

§ Design of elevator lobbies§ High-rise – elevator door protection only for elevators

traveling >75’§ Area of refuge – lobby separated by smoke barriers

or horizontal exit§ Fire service access elevator§ Occupant evacuation elevator

2015 IBC Key Changes 38

Existing BuildingsChapter 34

Existing BuildingsChapter 34

§ Ch 34 deleted§ §101.4.7 – provisions of the

IEBC shall apply§ Repairs, alterations, change

of occupancy, additions, relocations

Page 20: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 20

2015 IBC Key Changes 39

Key Changes to the 2015 IFCKey Changes to the 2015 IFC

2015 IBC Key Changes 40

Emergency Preparedness§403

Emergency Preparedness§403

§ Fire Safety and Evacuation Plans§ Required for§ Group A, other than church with OL <2,000§ Buildings with both Group A and atrium§ Group B, F, M with OL >500, or >100 on floor other

than LED§ Groups R-1, R-4, R-2 college/univ dormitories§ High-rise§ Mall buildings >50,000 ft2

§ Occupant evacuation elevators

IBC §1001.4 requires that the FS&E Plan is

submitted as part of MoEreview

Page 21: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 21

2015 IBC Key Changes 41

Combustible Materials in Plenums§315.6, §605.12

Combustible Materials in Plenums§315.6, §605.12

§ Storage is prohibited§ It must be removed

§ Abandoned wiring is deemed to be storage§ It must be removed in the accessible areas§ Unless the wiring is tagged for future use

2015 IBC Key Changes 42

Protection of Elevators§607.6

Protection of Elevators§607.6

§ Design must keep water from fire sprinklers outside of lobby from reaching § Fire service access

elevators, and§ Occupant evacuation

elevators

ElevatorLobby

ElevatorHoistway

ElevatorHoistway

F.S.AccessElevator

F.S.AccessElevator

ElevatorHoistway

ElevatorHoistway

Requirement does not apply to water from fire sprinklers inside lobby

Page 22: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 22

2015 IBC Key Changes 43

Type I Hood – Commercial Cooking Appliances§609.2

Type I Hood – Commercial Cooking Appliances§609.2

§ New exception eliminates Type I hood over electric cooking appliances based on a test in UL 710B§ Emissions Test§ Effluent from cooking

contains <5mg/m3 or less § Does NOT need to be listed

to UL 710B; only must meet this particular test

Photo courtesy of Target Corporation

If Type I hood is not required, neither is fire-extinguishing

system in that hood

2015 IBC Key Changes 44

Fire Sprinklers in Group A§903.2.1

Fire Sprinklers in Group A§903.2.1

§ Fire sprinklers installed on entire floor and all floor levels to all LEDs

Group A-2

Fire sprinkler system installed on all stories

to all levels of exit discharge

Fire sprinkler system installed on story with Group A

Page 23: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 23

2015 IBC Key Changes 45

Assembly Occupancies on Roofs§903.2.1.6

Assembly Occupancies on Roofs§903.2.1.6

§ WHEN:§ Rooftop is used for assembly, AND § Assembly OL >100 for Group A-2 uses, OR § OL >300 for other Group A uses

§ THEN:§ Sprinklers required in all

floors below the roof,down to and including thelevel of exit discharge

2015 IBC Key Changes 46

Multiple Group A Fire Areas§903.2.1.7

Multiple Group A Fire Areas§903.2.1.7§ Sprinklers required where

multiple fire areas contain Group A-1, A-2, A-3 or A-4 occupancies that share egress components and OL ≥300

Group A-2Restaurant

OL = 93

Group A-3Art GalleryOL = 123

Group MBook StoreOL = 110

Group A-2Restaurant

OL = 93

All occupancies separated by 2-HR fire barriers

Aggregate occupant load = 309 Therefore, sprinklers are required

Page 24: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 24

2015 IBC Key Changes 47

Buildings ≥55’ in Height§903.2.11.3

Buildings ≥55’ in Height§903.2.11.3

§ Height measured to “finished floor” with occupant load of 30 or more§ Now includes a mezzanine

If mezzanine has OL ≥30; measure to that floor level

If ≥55’ from LLFDVA; then sprinklers are required

2015 IBC Key Changes 48

Buildings ≥55’ in Height§903.2.11.3

Buildings ≥55’ in Height§903.2.11.3

§ Airport traffic control towers are no longer including in the exceptions§ IBC §412.3.6 contains sprinkler criteria for

airport control towers§ Sprinklers required where an occupied floor is >35’

above the LLFDVA

Page 25: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 25

2015 IBC Key Changes 49

Sprinklers in Elevator Machine Rooms§903.3.1.1.1

Sprinklers in Elevator Machine Rooms§903.3.1.1.1

§ Elevator shunt trip is specifically prohibited in both fire service access elevators and occupant evacuation elevators§ New exempt sprinkler locations

have been added to protectthe elevator hoistway§ Machinery rooms§ Machinery spaces§ Control rooms§ Control spaces

2015 IBC Key Changes 50

Sprinklers in Elevator Machine Rooms§903.3.1.1.1

Sprinklers in Elevator Machine Rooms§903.3.1.1.1

§ Sprinklers not required in:

§ Machine rooms

§ Machinery spaces

§ Control rooms

§ Control spaces

A room outside the hoistwaywith an elevator machine

A space where a machine and motor controller are located inside the hoistway

A room outside the hoistway with a motor controller and not a machine

A space outside the hoistway with a motor controller and not a machine

Page 26: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 26

2015 IBC Key Changes 51

Exempt Locations for NFPA 13 Sprinklers§903.3.1.1.2

Exempt Locations for NFPA 13 Sprinklers§903.3.1.1.2

§ Sprinklers not required in Group R-1, R-2, R-3 bathrooms ≤55 ft2 provided they are located within individual dwelling units or sleeping units

§ Walls and ceilings must be of noncombustible or limited-combustible materials with a 15-minute thermal barrier rating

2015 IBC Key Changes 52

NFPA 13R Sprinkler Systems§903.3.1.2

NFPA 13R Sprinkler Systems§903.3.1.2

§ NFPA 13R applicable to:§ Group R buildings ≤4 stories§ Group R buildings ≤60’ in height

Parking3-HR horizontalseparation

Number of stories measured from

horizontal separation Height for Group

R measured from grade plane

Page 27: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 27

2015 IBC Key Changes 53

Water Mist Systems§904.2, §904.11

Water Mist Systems§904.2, §904.11

§ Must comply with NFPA 750

§ When used as alternative to fire sprinkler system, building is considered “NOT sprinklered throughout”

§ When 2nd water is required for building, water mist must have 2nd water supply

Photo courtesy of Tyco Fire Protection Products

2015 IBC Key Changes 54

Fire Alarm Shop Drawings§907.1.2

Fire Alarm Shop Drawings§907.1.2§ Minimum audibility level for

occupant notification§ New item to be included with fire

alarm drawings

§ Public Operating Mode§ ≥15dB above the average ambient

sound or 5 dB above the maximum sound

§ Private Operating Mode§ ≥10dB above the average ambient

sound or 5 dB above the maximum sound

Maximum of 110 dBA

Page 28: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 28

2015 IBC Key Changes 55

Manual Fire Alarm System in Group E§907.2.3

Manual Fire Alarm System in Group E§907.2.3

§ Group E requires a manual fire alarm system with emergency voice/alarm communications§ Exceptions:

1. Alarm not required when OL ≤50 2. EVAC system not be required when OL ≤ 1003. Manual fire alarm boxes not required when corridors,

shops, labs, auditoriums, gymnasiums have heat or smoke detection

4. Manual fire alarm boxes not required when building is sprinklered

2015 IBC Key Changes 56

Fire Detection in Atriums§907.2.14

Fire Detection in Atriums§907.2.14

§ Atriums with >2 stories§ Smoke detection design in

accordance with:§ Rational analysis in §909.4§ System operation requirements

in §909.17

Page 29: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 29

2015 IBC Key Changes 57

Elevator Hoistway Pressurization§909.21

Elevator Hoistway Pressurization§909.21

§ Elevator hoistway pressurization in lieu of elevator lobby§ Lobby for fire service access elevators and

occupant evacuation elevators is still required§ Pressure differential of 0.1 to 0.25 inches of

water column

2015 IBC Key Changes 58

Smoke and Heat Removal§910

Smoke and Heat Removal§910

§ Smoke & heat removal required:§ Groups F-1 & S-1 with more than 50,000 ft2 of

undivided area§ High-piled storage areas where required by Table

3206.2§ Smoke & heat vents OR mechanical smoke

removal systemNot required in

areas with ESFR sprinkler system

Not required in frozen food

warehouses with Class I or II

commodities

Not required in areas with CMSA

sprinkler system, if RTI is 50 or less

Page 30: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 30

2015 IBC Key Changes 59

Smoke and Heat Removal§910

Smoke and Heat Removal§910

§ Selection of smoke & heat removal method

Method of Smoke & Heat

Removal

Sprinklered Building

NonsprinkleredBuilding

1st Story with Stories Above

Smoke/Heat Vents Option 1 Required Not allowed

Mechanical Smoke Removal Option 2 Not allowed Required

2015 IBC Key Changes 60

Smoke and Heat Removal§910

Smoke and Heat Removal§910

§ Smoke/heat vents§ Calculation for sprinklered building§ AVR = V/9000

§ Calculation for unsprinklered building§ AVR = V/50

Page 31: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 31

2015 IBC Key Changes 61

Smoke and Heat Removal§910

Smoke and Heat Removal§910

§ Mechanical smoke removal§ 2 air changes per hour§ Based on empty building§ Makeup air openings ≤6’ of floor§ Automatic shutdown upon sprinkler

operation§ Manual controls in room accessible

from the exterior with 1-HR separation

2015 IBC Key Changes 62

Electric Circuits Supplying Fire Pumps§913.2.2

Electric Circuits Supplying Fire Pumps§913.2.2

§ Circuits for electric fire pumps must be designed and listed for survivability§ UL 2196§ 2” concrete covering§ 2-HR rated assembly§ Cable with a fire-resistance

rating of 2-HR§ Cable and installation

method tested

Seamless Copper Sheath

Magnesium Oxide Insulation

Solid Copper Conductors

Graphic courtesy of Pentair Thermal Management

Page 32: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 32

2015 IBC Key Changes 63

Carbon Monoxide Detection§915.1.1

Carbon Monoxide Detection§915.1.1

§ CO detection required in Groups I-1, I-2, I-4 and R occupancies, and Group E classrooms§ CO detection is only required when the following

potential sources of CO exist:§ Fuel-burning appliances in the space or building§ Fuel-burning fireplace in the space or building§ Fuel-burning, forced air furnace § Attached private garage

2015 IBC Key Changes 64

LP-gas Dispensing§2307.4

LP-gas Dispensing§2307.4

§ Point of transfer§ 25’ from wall <1-HR§ 25’ from combustible eave§ 25’ from property line§ 25’ from centerline of RR§ 10’ from public street,

driveways, sidewalks§ Self-service into vehicles

allowed§ Special nozzle required

Page 33: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 33

2015 IBC Key Changes 65

Class I Commodities§3203.2

Class I Commodities§3203.2

§ Class I commodities stored on plastic pallets are no longer classified as Class I§ NFPA 13 §5.6.2.2 § 1 classification level increase

for unreinforced PE or PP pallets§ 2 classification level increase

for reinforced PE or PP pallets§ Listed plastic pallets are

equivalent to wood palletsUL 2335 or FM 4996

2015 IBC Key Changes 66

Group S-1 Occupancy

Dead-end Aisles in High-piled Storage§3206.9.3

Dead-end Aisles in High-piled Storage§3206.9.3

§ Limitations for dead-end aisle lengths are now specifically addressed in high-piled storage areas§ Maximum length of dead-

ends§ Group S = 50’§ Group M = 20’

Page 34: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 34

2015 IBC Key Changes 67

Group M Occupancy

Dead-end Aisles in High-piled Storage§3206.9.3, Exception

Dead-end Aisles in High-piled Storage§3206.9.3, Exception

§ If length of aisle <2.5 time the wide, then not considered dead-end aisle

Dead-end aislemaximum 20’

79’

98’

2015 IBC Key Changes 68

Cleaning Piping Systems with Flammable Gas§3306.2

Cleaning Piping Systems with Flammable Gas§3306.2

§ Significant gas explosions have occurred when cleaning/purging gas piping§ 6/9/2009 – ConAgra Foods Slim

Jim™ meat processing facility in Garner, NC: 4 workers killed and 67 others injured

§ 2/7/2010 – Kleen Energy power plant in Middletown, CT: 6 workers killed and 50 others injured

Page 35: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 35

2015 IBC Key Changes 69

Cleaning Piping Systems with Flammable Gas§3306.2

Cleaning Piping Systems with Flammable Gas§3306.2

§ New piping and systems need to be cleaned and purged prior to operation§ Using the gas product is a handy and

convenient cleaning media

2015 IBC Key Changes 70

Cleaning Piping Systems with Flammable Gas§3306.2

Cleaning Piping Systems with Flammable Gas§3306.2

§ Flammable gas shall not be used as the cleaning media§ Cleaning and purging of flammable gas piping

systems must comply with NFPA 56§ Fuel gas piping in accordance with IFGC©§ Compressed gas piping in accordance with IFC Ch 53§ LP-gas piping in accordance with IFC Ch 61

Page 36: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 36

2015 IBC Key Changes 71

MAQsTable 5003.1.1(1)

MAQsTable 5003.1.1(1)

Maximum Allowable Quantity Per Control Area Of Hazardous MaterialsPosing A Physical Hazard a,j,m,n,p

MATERIAL CLASS

GROUP WHEN THE MAXIMUM

ALLOWABLE QUANTITY IS EXCEEDED

STORAGE b USE-CLOSED SYSTEMS b USE-OPEN SYSTEMS b

Solid pounds

(cubic feet)

Liquid gallons

(pounds)

Gas(cubic feet

at NTP)

Solid pounds (cubic feet)

Liquid gallons

(pounds)

Gas(cubic feet

at NTP)

Solid pounds (cubic feet)

Liquid gallons

(pounds)

Combustible fiber q

Loose Baled c H-3 (100)

(1,000) NA NA (100) (1,000) NA NA (20)

(200) NA

Consumer fireworks 1.4G H-3 125 d, e, l NA NA NA NA NA NA NA

Cryogenic Inert

NA NA NA NA NL NA NA NL NA NA

Inert gas

Cryogenic inert

Gaseous Liquefied

NA

NA NA NA

NA NA NA

NA NA NA

NL NL NL

NA NA NA

NA NA NA

NL NL NL

NA NA NA

NA NA NA

Unstable (reactive)

43 2 1

H-1 H-1 or H-2

H-3 NA

1 e, g

5 d, e

50 d, e

NL

(1) e, g

(5) d, e

(50) d, e

NL

10 g

50 d, e

250 750 d, e

NL

0.25 g

1 d50 d

NL

(0.25) g(1) d

(50) dNL

2 e, g

10 d, e

250 750 d, e

NL

0.25 g

1 d10 d

NL

(0.25) g(1) d

(10) dNL

2015 IBC Key Changes 72

MAQsTable 5003.1.1(1) – Footnotes

MAQsTable 5003.1.1(1) – Footnotes

c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers ≤1.3 gal. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, or consumer or industrial products, and cosmetics containing ≤50% by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not be limited, provided that such materials are packaged in individual containers ≤1.3 gallons. e. MAQ shall be increased 100% when stored in approved storage cabinets, day boxes, gas cabinets, gas rooms, exhausted enclosures, or listed safety cans. Listed safety cans shall be in accordance with §5003.9.10. Where Note d also applies, the increase for both notes shall be applied accumulatively.p. The following shall not be included in determining the maximum allowable quantities:

1 - 5. Vehicle fuel tanks on vehicles; motorized equipment; regulated by IFGC or IMC5. Alcohol based hand rubs classified as Class I or II liquids in dispensers that are installed in accordance with §5705.5 and §5705.5.1. The location of the alcohol based hand rub (ABHR) dispensers shall be provided in the construction documents.

Page 37: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 37

2015 IBC Key Changes 73

CO2 Systems in Beverage Dispensing§5307

CO2 Systems in Beverage Dispensing§5307

§ Multiple small gaseous CO2 cylinders are being replaced with single larger vessels which contain liquefied CO2

§ Accidental release can fill an enclosed space§ Odorless and colorless gas§ Heavier than air

§ Systems >100 pounds (≈9.5 gallons) are regulated

2015 IBC Key Changes 74

CO2 Systems in Beverage Dispensing§5307

CO2 Systems in Beverage Dispensing§5307

§ Operational permit required >100 pounds§ Protection required§ Continuous gas detection system, or§ Mechanical ventilation

§ External fill connections

Page 38: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 38

2015 IBC Key Changes 75

NOSMOKING

Hydrogen Fuel Gas Rooms§5808

Hydrogen Fuel Gas Rooms§5808

§ H2 shall not exceed the MAQ

H2 gas detectors at high points in

the roomExterior wall

Ventilation outlets –in roof/ceiling, or

high in exterior wall

Standby power provided for:• Mechanical ventilation system• H2 gas detection system

Audible/visual device connected to gas detection system:• Activates when 25% LFL of H2 gas is detected• Alarm inside and outside hydrogen fuel gas room

Fire-resistance-rating of walls and ceiling:• Comply with IBC Table 509.1, and • 1-HR minimum

No Smoking signsSupply air inlets – low

in exterior wallsMechanical ventilation system:• Maintains a negative pressure compared to adjacent rooms• Minimum ventilation rate of 1 cfm/12 ft3 of room volume• Failure of ventilation system results in shutdown of H2 fueling operation

2015 IBC Key Changes 76

Fire-flowAppendix B

Fire-flowAppendix B

§ Revision of fire-flow tablesTable B105.2

Required Fire-flow for Buildings Other Than 1- and 2-family Dwellings, Group R-3 and R-4 Buildings and Townhouses

§ Required water supply for sprinklered buildings shall meet the greater of:§ Sprinkler demand with hose§ Required fire-flow

AUTOMATIC SPRINKLER SYSTEM(Design Standard)

MINIMUM FIRE-FLOW(gallons per minute)

FLOW DURATION(hours)

No automatic sprinkler system Value in Table B105.1(2) Duration in Table B105.1(2)Section 903.3.1.1 25% of the value in Table B105.1(2)a Duration in Table B105.1(2) at reduced flow rateSection 903.3.1.2 25% of the value in Table B105.1(2)b Duration in Table B105.1(2) at reduced flow rate

860 GPM @ 45 PSI

2,250 GPM @ 20 PSI

Page 39: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 39

2015 IBC Key Changes 77

Existing Ambulatory Care FacilitiesAppendix K

Existing Ambulatory Care FacilitiesAppendix K

§ When ≥4 patients, separated from remainder of building with 1-HR fire partitions§ When >10,000 ft2 must be separated into 2

smoke compartments§ Sprinklers in IIB, IIIB or VB construction with:§ ≥4 patients incapable of self-preservation, OR§ 1 patient incapable of self-preservation on floor other

than LED§ Smoke detection system§ Detectors can be eliminated if building is sprinklered

2015 IBC Key Changes 78

§ Appendix L does not require a FF Air Replenishment System, but it provides design criteria when FARS is installed

§ SCBA bottle refilling stations§ 5th floor above or below grade§ Every 3rd floor thereafter

§ Refilling stations consist of either:§ Bottle refill with secondary containment§ RIC/UAC quick fill connections

Fire-fighter Air Replenishment SystemsAppendix L

Fire-fighter Air Replenishment SystemsAppendix L

FARS fill station (typical)

Photo courtesy of Rescue Air Systems, Inc.

Page 40: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 40

2015 IBC Key Changes 79

Fire-fighter Air Replenishment SystemsAppendix L

Fire-fighter Air Replenishment SystemsAppendix L

§ Source of air§ On-site air storage system§ External mobile air connection

§ Quality of air§ NFPA 1989§ Constantly monitored on-site§ Air sample tested quarterly

Graphics courtesy of Rescue Air Systems, Inc.

2015 IBC Key Changes 80

Sprinklers in Existing High-rise BuildingsAppendix M

Sprinklers in Existing High-rise BuildingsAppendix M

§ Fires in high-rise buildings are difficult to fight§ Longer evacuation times§ Often cannot fight the fire from the

ground§ Delayed access time for FFs to

reach the fire§ Time required for FFs moving

equipment to upper floors

Page 41: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 41

2015 IBC Key Changes 81

Sprinklers in Existing High-rise BuildingsAppendix M

Sprinklers in Existing High-rise BuildingsAppendix M

§ Automatic sprinkler system is required in existing high-rise buildings§ High-rise is a building with an occupied floor level

>75’ above LLFDVA§ Exceptions for:§ Airport traffic control towers§ Open parking garages§ Group U§ Group F-2

2015 IBC Key Changes 82

Sprinklers in Existing High-rise BuildingsAppendix M

Sprinklers in Existing High-rise BuildingsAppendix M

§ Automatic sprinkler system must meet current requirements§ 2015 IFC § 2013 NFPA 13

§ Compliance schedule§ Develop schedule within 365 days§ Design§ Plan review & permit

§ Installation completed within 12 years

Page 42: Key Changes to the 2015 IBC - sfpe-asa.org Handouts/2014-09 IBC-IFC 2015... · Key Changes to the 2015 IBC 2015 IBC Key Changes 2 Introduction §Instructor §Kevin Scott §KH Scott

9/3/2014

2015 IBC/IFC Key Changes 42

2015 IBC Key Changes 83

Thank you for participatingThank you for participating

Kevin ScottKH Scott & Associates LLC

at(661) 431-5897

orE-mail: [email protected]