TOESTERS “PURR-FECT” DESIGN ** Innovation is an American Tradition ** [email protected] http://www.turbonicsinc.com 4001 Pearl Road, Cleveland, OH 44109 Phone (216) 741-8300 Fax (216) 741-7768 Notable Features & Options: Shaded 4-Pole 2-speed encased motor for rugged operation and long motor life. Ultra-Low Profile fan coil draws air from a 360 degree radius and operates at either 650 or 850 RPM using the Purr-Fect™ Air Wheel for optimum balance & performance. Fits beneath cabinets with a virtually invisible grille in the recessed kick-space area. An optional two-speed wall-mountable switch offers Hi/Off/Lo control. The unit can be used without the switch and be controlled by the heat-sensing aquastat. Dependable: Quiet: Compact: Controls: Model Numbers Toester 4/5 Toester 6/8 Toester 10/12 Toester 11/13 Toester 16/19 UNDERCOUNTER HYDRONIC FAN COILS MANUFACTURER of HYDRONIC FAN COILS INC. Units use L/ASTM B75 type copper and have been IAPMO tested and passed ANSI/NSF 61 section 4 and are suitable for use with residential potable water Toester Undercounter Fan Coils These small, but ultra responsive, heating units can deliver from 4,000 to 19,000 BTU/hour to heat any space to an even and comfortable temperature. The undercounter units are reliable and easy to install. The Toester is another in a long line of Turbonics Fan Coils that specialize in bringing warmth to possibly difficult to heat areas using Micro-Zonal™ Technology. Toesters are Designed to fit below cabinets in the unused kick-space area and are accessed from above with a strategic access cover that is typically cus- tom built on-site. The Toesters come with a bleed valve and standard 1/2" pipe connections. All Turbonics products use components that have been tried and tested for years of reliability in other combinations. Five-Year limited warranty on the core and electrical components is the standard others aspire to. ELECTRICAL CONNECTION HIGH EFFICIENCY COPPER/ALUMINUM HEAT EXCHANGER PURR-FECT™ AIR WHEEL PLUMBING CONNECTIONS MODEL TOESTER 11/13 & 16/19 MODEL TOESTER 4/5 & 6/78 NOTE: Each Toester features a heat sensing aquastat for fan control or low water temperature limit to shut off the fan if the water temperature drops too low.

Upload: lykiet

Post on 21-Oct-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

TOESTERS “PURR-FECT” DESIGN

* * Innovation is an American Tradit ion * * [email protected]://www.turbonicsinc.com

4001 Pearl Road, Cleveland, OH 44109 Phone (216) 741-8300 Fax (216) 741-7768

Notable Features & Options:Shaded 4-Pole 2-speed encased motor for rugged operation and long motor life.

Ultra-Low Profile fan coil draws air from a 360 degree radius and operates at either650 or 850 RPM using the Purr-Fect™ Air Wheel for optimum balance & performance.

Fits beneath cabinets with a virtually invisible grille in the recessed kick-space area.

An optional two-speed wall-mountable switch offers Hi/Off/Lo control. The unitcan be used without the switch and be controlled by the heat-sensing aquastat.

Dependable:Quiet:Compact:Controls:

Model NumbersToester 4/5Toester 6/8Toester 10/12Toester 11/13Toester 16/19UNDERCOUNTER HYDRONIC FAN COILS

MANUFACTURER of HYDRONIC FAN COILSINC.

Units use L/ASTM B75 type copper and have been IAPMO tested and passed ANSI/NSF 61 section 4and are suitable for use with residential potable water

To

esterU

nd

ercou

nter

Fan

Co

ils

These small, but ultra responsive, heating units can deliver from 4,000 to 19,000 BTU/hour to heat any

space to an even and comfortable temperature. The undercounter units are reliable and easy to install.

The Toester is another in a long line of Turbonics Fan Coils that specialize in bringing warmth to possibly

difficult to heat areas using Micro-Zonal™ Technology. Toesters are Designed to fit below cabinets in the

unused kick-space area and are accessed from above with a strategic access cover that is typically cus-

tom built on-site. The Toesters come with a bleed valve and standard 1/2" pipe connections. All Turbonics

products use components that have been tried and tested for years of reliability in other combinations.

Five-Year limited warranty on the core and electrical components is the standard others aspire to.

ELECTRICALCONNECTION

HIGH EFFICIENCYCOPPER/ALUMINUMHEAT EXCHANGER

PURR-FECT™AIR WHEEL

PLUMBINGCONNECTIONS

MODEL TOESTER 11/13 & 16/19

MODELTOESTER4/5 & 6/78

NOTE: Each Toester features

a heat sensing aquastat for fan

control or low water temperature

limit to shut off the fan if the water

temperature drops too low.

16"12 3/4"3-1/2" 2"

17-1/2"

4"

AIR VENTELECTRICALCONNECTION

1/2" SUPPLY

1/2" RETURN

17" MIN

Toester 4/5Toester 6/8

CONTROL BOX

TWO-SPEEDMOTORGND

WHITE

BLACK

AQUASTAT

RED (LO)

BLACK

BLUE

BLUE

BLACK (HI)GND

FUSED FIELD115 VAC 60 Hz(From Fan Control)

A

FACTORY WIRED ON LO SPEED

A To direct wire on HI speed replace RED (LO) wire connection to BLUE AQUASTAT wirewith BLACK (HI) wire. Cap the disconnected RED (LO) wire before powering unit.

CONTROL BOX

TWO-SPEEDMOTORGND

WHITE

BLACK

AQUASTAT

RED (LO)

BLACK

BLUE

BLUE

BLACK (HI)GND

FUSED FIELD115 VAC 60 Hz(From Fan Control)

OPTIONAL 2-SPEED SWITCH INSTALLATION

All Electrics Must Comply With Local & National Codes

FIELD BLACKTO SWITCHCOMMON

BLACK (HI)FROM SWITCH

RED (LO)FROM SWITCH

WHITE WHITE

* * Innovation is an American Tradit ion * * [email protected]://www.turbonicsinc.com

4001 Pearl Road, Cleveland, OH 44109 Phone (216) 741-8300 Fax (216) 741-7768

I. INSTALLATION: GeneralA. Toester fan coil space heaters are suitable for connection to hot water supply at any pressure

up to 125 P.S.I. Maximum water temperature should not exceed 200˚F.B. Building codes and plumbing regulations may vary. Check local codes and regulations

before determining proper application and installation. (See KWM & HDX Application Manuals)C. Cut an access panel under the bottom shelf. Starting at the right edge of the selected loca-

tion, cut an opening in the the toe-space riser at least 4" x 17-1/2" (SEE FIG. 1) for additional dimen-sions required for each particular model. Cabinet Details may vary for each installation.

D. Lift the Toester out through the access door and sweat on fittings.

II. PIPING: GeneralA. The piping to the unit will usually be copper or any other locally approved piping. Accessible

1/2" sweat fittings are provided on the unit itself. An optional Flexible Stainless Steel Connector Kitwith shut-off valves is available for connecting the unit to any type of piping system.

B. All piping systems should be designed by a technician with experience in the various pipingarrangements that work with this type of unit.

C. As with any system employing circulated water, the pipes passing through unheated spacesshould be insulated.

D. When using mono-flo or “venturi” fittings, we suggest placement of a ball valve just after thesupply take-off and before the return is connected.

III. PIPING - HOT WATER BOILERA. The unit supply line should be taken from the boiler side beyond any flo-control valve. If the

system being used is a gravity-flow or cast-iron hot water system, a separate circuit must beinstalled.

IV. PIPING - WATER HEATER:A. To install correctly, a technician with knowledge of piping arrangements and back-flo valves

must design the piping system.

V. WIRING THE UNIT:A. A field wiring connection is provided on the unit. Connect wires at this point only.B. The unit is manufactured with a built-in factory wired aquastat with a set point of 140˚F on

and 110˚F off. The aquastat may be disabled in the field if not required.C. Unit is pre-wired from the factory on Hi speed. Unit may be optionally installed with a remote

mounted 2-speed switch (included) and/or a line voltage thermostat. (SEE FIG. 2)D. All wiring should be done to all local and national codes.

VI. COMPLETION:

A. Secure unit to floor through holes on perimeter of the bottom plate (screws provided).

B. Bleed the unit, secure the access panel and install front grille cover.

5 YEAR LIMITED WARRANTYTurbonics, Inc. warrants to the original user each new product manufactured by it or sold under its trade names to be free from defects in workmanship and material under normal use and service for a period of five years from date of shipment from the fac-

tory warehouse excluding the pump on the Chill Chaser whose warranty is one year. The sole liability of Turbonics, Inc. under this warranty is limited to repairing, or at it‘s option, replacing free of cost, any defective part or parts f.o.b. it’s factory, provided

that (1) the defective part is returned prepaid to Turbonics, Inc. upon it‘s written authorization, and (2) Turbonics, Inc. determines the defective part has not been subjected to misuse, abuse, negligence, accident, or improper installation, operation, service

or repair. This warranty does not include any field labor charge involved in removal of the defective part or installation of the repaired or replacement part. During the first year, with prior factory approval , a labor charge of $15.00 per hour may be applied

for on warranty repairs. This warranty is made only to the original user of the product and cannot be transferred or assigned, and it is effective only while the product is in use at the place of original installation. Such warranty shall not apply to any product

on which the serial number or date of manufacture has been altered, effaced or removed. This warranty applies only to products installed within the continental boundaries of North America. This warranty constitutes the only warranty, or representation of

Turbonics, Inc. and no other warranty, or representation, statutory or otherwise, is expressed or may be implied. In no event will Turbonics, Inc. be responsible for special or consequential damages of any kind whatsoever.

* Heat Ratings based on 2 GPM and 65˚F Entering Air. For 1 GPM multiply by .95 factor.

INC.

TOESTER 4/5 RATINGS*Fluid Temperature 120˚ 140˚ 160˚ 180˚ 200˚

High SpeedLow Speed

3000 3900 4800 5700 65002200 3100 4000 4800 5600

Pressure Drop (Feet of Head).33' @ 1 GPM 1.0' @ 2 GPM 3.0' @ 4 GPM

TOESTER 6/8 RATINGS*Fluid Temperature 120˚ 140˚ 160˚ 180˚ 200˚

High SpeedLow Speed

3800 5150 6600 7700 91002900 4050 5200 6100 7200

Pressure Drop (Feet of Head).5' @ 1 GPM 1.5' @ 2 GPM 4.0' @ 4 GPM

TOESTER 10/12 RATINGS*Fluid Temperature 120˚ 140˚ 160˚ 180˚ 200˚

High SpeedLow Speed

4100 6200 8100 10000 120003200 4800 6500 7800 9500

Pressure Drop (Feet of Head).6' @ 1 GPM 1.8' @ 2 GPM 4.5' @ 4 GPM

TOESTER 11/13 RATINGS*Fluid Temperature 120˚ 140˚ 160˚ 180˚ 200˚

High SpeedLow Speed

5800 8200 10900 13200 162004000 6200 8800 10900 13800

Pressure Drop (Feet of Head).6' @ 1 GPM 1.8' @ 2 GPM 4.5' @ 4 GPM

TOESTER 16/19 RATINGS*Fluid Temperature 120˚ 140˚ 160˚ 180˚ 200˚

High SpeedLow Speed

6900 9900 13250 16200 191004900 7500 10600 14000 16900

Pressure Drop (Feet of Head).33' @ 1 GPM 1.0' @ 2 GPM 3.0' @ 4 GPM

22"17-1/4"3-1/4" 1-1/2"

17-1/2"

4"

AIR VENTELECTRICALCONNECTION

1/2" SUPPLY

1/2" RETURN

23" MIN

Toester 10/12

30"24-1/2"3-1/2" 2"

17-1/2"

4"

Toester 11/13Toester 16/19

AIR VENTELECTRICALCONNECTION

1/2" SUPPLY

1/2" RETURN

31" MIN.

FIG. 1 DIMENSIONAL DATA

FIG. 2 WIRING DIAGRAM