kr-rm-li ups brochure - power inspired ltd · kr-rm-li ups brochure author: power inspired subject:...
TRANSCRIPT
Lithium Ion Online UPS Systems
Reduced Whole Life Costs over lead acid (VRLA)
Longer Life. Typical VRLA is 200-300 cycles and 3-5 year life. Li-Ion is 1000+ cycles and 10 year life, removing the need to factor in battery changes for the useful life of the system.
Lower Operating Costs. Li Ion charges quicker and more efficiently than VRLA coupled with a high efficiency UPS System operating costs are reduced.
Smaller & Lightweight. The high power density of Li Ion provides much longer runtimes. Occupying only 2U in height the KR-RM-LI gives 11 minutes runtime at full load. No need for extra battery cabs.
5 Year Warranty. The long life claims are backed up by a 5 year warranty which includes the Li-Ion battery. Standard UPS warranties are 3 years maximum and this doesn’t include the battery.
Greener. Li Ion batteries have been shown to have less of an environmental impact than VRLA. No heavy metals and longevity makes Li Ion a greener alternative.
Online Double Conversion
Rack / Tower Convertible
International Options
SNMP & Dry Relay Contact Options
Provides the highest levels of power
protection
Versatile mounting options, with only 2U of
rack space required.
Available in both 120V and 230V versions, with each unit being 50/60Hz
auto-sensing
As well as USB interface the unit can be fitted with SNMP or Relay
card options.
Higher Operating Temperature VRLA degrade rapidly above 30
oC. The KR-RM-LI will operate up to 60
oC without any negative
battery performance. Protects battery investment and reduces cooling demands.
KR-RM-LI
Voltage Frequency Independent (VFI) technology— for the
highest levels of power protection.
The improved runtime over lead acid means the UPS occupies less space. The increased operating temperature allows the
unit to be installed without the necessary cooling requirements for lead
acids.
Blackouts Sags Spikes Under Volts Over Volts Noise Frequency Transients Harmonics
Provides Protection Against
Telecom
Server Room
Laboratory
High Temperature Environments
Typical Applications
REAR PANEL CONFIGURATIONS
KR1000RM-LI 1KVA 230V
KR2000RM-LI KR3000RM-LI 2/3KVA 230V
KR1000A-RM-LI 1KVA 120V
KR2000A-RM-LI 2KVA 120V
KR3000A-RM-LI 3KVA 120V
Power Inspired Ltd. Unit 122 Churchill Road, Bicester, Oxfordshire, OX26 4XD, UK. T: +44 1869 814055; W: www.powerinspired.com; E: [email protected]
Although every effort is made to ensure accuracy of this document, it is provided for guidance only and does not form part of any contract. Specifications are subject to change without notice.
DOC: BR-UPS-KR-RM-LI Rev 2.1
SPECIFICATIONS
MODEL KR1000-
RM-LI
KR2000-
RM-LI
KR3000-
RM-LI
KR1000A-
RM-LI
KR2000A-
RM-LI
KR3000A-
RM-LI
INPUT
Voltage Range (Full Load) 120-295 60-148
Frequency Range 50/60Hz±10% (50/60Hz Auto sense)
Power Factor >0.99
THDi <5%
OUTPUT
Capacity (VA/Watts) 1000/900 2000/1800 3000/2700 1000/900 2000/1800 3000/2700
AC/AC Efficiency 91.0% 91.5% 93.0% 91.7% 92.5% 92.5%
Power Factor 0.9 to 45°C, 0.8 to 50°C, 0.7 to 55°C, 0.6 to 60°C
Voltage (Vac) 208/220/230/240 ±1% (Settable via
LCD) 110 / 120 ±1% (Settable via LCD)
Frequency (Hz) 50/60 ±0.1 Battery Mode
THDv <3% (Linear Load), <5% (Non-Linear Load)
Transfer Time 0
ECO mode Yes
Overload 101% - 115% for 1 min, 116% - 133% for 1 sec, >134% 200ms max
BATTERY
Type & Quantity Lithium Ion
Charge Current 4.0A max
Nominal Battery String 24V 48V 72V 24V 48V 72V
Backup Time (mins) 11 11 11 11 11 11
PHYSICAL
Environment 0-60°C 0-90% RH (Non Condensing). Altitude 1500m max
Note output capacity is derated to 0.7pf > 45°C
Noise <55dB
Input Connector IEC C14 IEC C20 IEC C14 5-20P L5-30P
Output Connector 6x IEC C13 6x IEC C13 + 1x IEC C19 (8)5-15R (6)5-20R (4)5-20R
+ (1)L5-30R
Dimensions WxDxH
(mm) 438x420x87 438x570x87 438x420x87 438x570x87
Net Weight kg 9 13.6 16.1 8.9 13.6 17.1
Other
Communication Interface USB. SNMP/Dry Contact Options
Protection Battery under voltage, overload, short circuit, over temperature, over voltage
Alarm Battery low, mains abnormal, UPS fault, overload