KYN28-12 Series

H.V Metal Clad Switchgear

Product Specification

10/08/2015

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 2

KYN28-12 Series With Prevent Wrong Operation Of

Metal Clad Switchgear

No Maintenance Medium Voltage Switchgear

1. Summarize What is electrical switchgear? KYN28-12 Metal Clad Switchgear,

rated medium voltage 3.6 kV ~ 12 kV three phase AC 50 (60)Hz,

with high breaking capacity and low values of intercepting the

VS1 type (or ABB VD4 type ) vacuum circuit breaker. electrical

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 3

switch definition, vacuum circuit breaker as the main

switchgear.

KYN28-12 Series Metal Clad Switchgear, the power generation,

transmission, distribution, conversion and energy consumption

of On /Off, control & protection of the important high voltage

switchgear.

Widely Used: What is a switchgear? KYN28-12 Metal Clad

Switchgear, receiving and distribution of electrical energy and

the circuit for control, protection and detection, suitable for

single busbar, single bus section system or double busbar

system, metal enclosed switchgear widely used in electric

power system of electrical substation, power plants, Industrial

building and construction projects for high voltage electric

distribution & switchgear solutions.

Advanced Structure: KYN28-12 Metal Clad Switchgear,

medium voltage switchgear components of Cabinet Body and

handcart. Cabinet Body by metal clapboard separates into 4

separate partition room: bus room, circuit breaker handcart

room, cable room and relay control &instrument room. Metal

Clad Switchgear of Vacuum circuit breaker for the Middle

Position Type (circuit breaker, which is situated in the middle of

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 4

the switchgear cabinet before), the expansion of the lower

space savings can be used for other options or cable room.

High Security: KYN28-12 Metal Clad Switchgear, used

electrical switchgear easy, safe and reliable interlocking device:

to prevent wrong operation circuit breaker, prevent loading and

isolating switch, prevent charged hang ground wire, which

prevent electric grounding switch, prevent with ground wire

transmission. in switchgear medium voltage, includes high

voltage circuit breaker, grounding switch, mutual inductor,

microcomputer protection device, etc. KYN28-12 Metal Clad

Switchgear meet IEC298, IEC694 standards.

2. Types Of Meaning

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 5

3. Regular Service Condition

Surrounding Air Temperature The Highest Temperature + 40 ℃,

The Lowest Temperature -15 ℃

Low Humidity Conditions

Daily Average Relative Humidity ≤95% The Average Daily Water Vapor Pressure is Less Than 2.2 kPa

Monthly Average Relative Humidity ≤90% On Average Water Vapor Pressure is Not More Than 1.8 kPa

Low Altitude 3000 m and Below; 3000 m Low Seismic Intensity No More Than 8 degrees;

Low Ambient Air Shall Be Subjected To Corrosive or Flammable Gas, Water Vapor and Other Obvious Pollution Low Without Frequent Severe Vibration Place Low Beyond The Normal Environment Conditions In The Regulations When Used By Users and Manufacturers To Negotiate

4. Main Technical Parameters Item Description Unit Data

Rated Voltage KV 3.6、6,7.2,10,11,12

Rated Power Hz 50(60)

Circuit Breaker Rated Current

A

630、1250、1600、2000、2500、3150

Rated Current Switch Devices

A

630、1250、1600、2000、2500、3150

Rated Short-Time Resistance Current (4 s)

kA 16、20、25、31.5、40

Rated Short Circuit

Breaking Current kA 40、50、63、80、100

Rated Short Circuit Close Current (Peak Value)

1 min Frequency Withstand Voltage

kA 16、20、25、31.5、40

Rated Insulation Level

Lightning Impulse Withstand

Voltage (Peak Value)

Electrode Spacing,Phase

Grounding Spacing kA 24、32、42

Between The Fracture kV 24、32、48

Electrode Spacing,Phase

Grounding Spacing kV 40、60、75

Between The Fracture kV

Protection Grade Cabinet Body IP4X

Isolation, Circuit Breaker Room Door is Opened IP2X

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 6

5. Structural Features Fully metal armor, modular structure, combination scheme is

extensive.

Cabinet put oneself in another's position chooses import apply

aluminium zinc steel plate, the CNC machine tool processing.

USES the advanced multiple flanging process, with the pull rivet

nut, high strength bolt connection, and the precision is high,

corrosion resistance, light weight, high strength, strong parts

universal.

Can be equipped with VS1 series or VD4 vacuum circuit

breaker, wide applicability, high reliability, realize years free

maintenance.

Handcart, experimental position, the position has the positioning

and display device, safe and reliable.

All kinds of hand press modulus modular change, guarantee the

handcart free swap with specifications, different specifications

handcart absolutely cannot enter.

Comprise by special delivery of handcart, lightweight, flexible

operation.

Cable room can be installed up to 9 single core cable;

Highly reliable interlock, fully meet the requirements of "five

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 7

prevention".

The high pressure chamber are relief channel, ensure the

personal safety.

The front door is equipped with observation window, can

observe indoor components working condition.

6. External Dimension

Height B 2300(2200)(mm)

Width A Small Branch Busbar Rated Current Of 1250 A The Thermal

Stability Of Current 40 KA 800(mm)

More Than 1600 A Small Branch Busbar Current Rating 1000(mm)

Depth C Outlet and Inlet Line Of Cable 1500(mm)

Outlet and Inlet Line Of Overhead 1660(mm) Weight Including Vacuum Circuit Breaker Switchgear 600-900(kg)

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 8

7. Main Technical Data 7.1 (VS1 Type) Vacuum Circuit Breaker Technology Parameters

No. Items Unit Data

1 Rated Voltage KV 12

2 Maximum Working Voltage KV 12

3 Rated Current A 630 1250 630 1250 630 1250

4 Rated Short Open Circuit Current KA 20 25 31.5

5 Rated Short circuit Close Current KA 50 63 80

6 Rated Front Value Tolerance Current KA 50 63 80

7 4 s Rated Short Circuit Resistance Current KA 20 25 31.5

8 Rated

Insulation Level

Power Frequency Withstand

Voltage (Rated Before and

After Breaking) KV

42(Fracture18)

Impact Pressure (Rated Before

and After Breaking) 75(Fracture84)

9 Rated Operating Sequence open-0.3S-close/open-180S-close/open 10 Mechanical Life time 10000

11 Rated Short Open Circuit Current

Switching Frequency Hz 50(60)

12 Operation Mechanism Rated

Switching Voltage (dc) V 110,220

13 Operation Mechanism Rated Points

Gate Voltage (DC) V 110,220

14 Contact Open Distance mm 11±1

15 Super Stroke (Contact Spring

Compression Length) mm 3.5±0.5

16 Three-Phase Points Switching ms ≤2

17 Contact Switching Bounce Time ms ≤2

18 Average Brake Speed m/s 0.9~1.2

19 Average Closing Speed m/s 0.5~0.8

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 9

20

Points Brake

Highest Operating Voltage s

≤0.05

Time Minimum Operating Voltage ≤0.08

21 Closing Time s 0.1

22 Each Phase Main Loop Resistance u Ω 60 50

23 Action Contact Allowed To Wear Cumulative Thickness

mm 3

7.2 Voltage Transformer Technical Parameters

Type Rated Voltage (kV) Rated Capacity At Each Level(VA)

0.5 Level 1 Level 3 Level

JDZ-3 3/0.1

50 80 200

JDZJ-3 31.0

31.0

33

JDZ-6 6/0.1

JDZJ-6 31.0

31.0

36

JDZ-10 10/0.1

JDZJ-10 31.0

31.0

310

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 10

7.3 (LZZBJ9-10 Type)Current Transformer Parameters

Rated Primary Current

Accurate Level Combination

Rated Secondary Output Thermal Stability

Current Dynamic

Stability Current 0.2S 0.5S 10P10

5-15

0.5s/10P10 0.2s/10P10 10 10 15

2 5 20 3 7.5 25 4 10 30 5 12.5 40 6.3 15 50 8.1 20 75 16.2 40.5 100 21.3 54 150 36 81

200-400 45 100 500-1000 63 130 1200-3000 80 160

7.4 (VS1 Type) Electric Operating Mechanism Parameters Rated Voltage

& Type(V) Rated Input Power

(W) Rated Time For Emerge

Storage (S) Service Voltage

Range

-48≌110≌220 80 ≤11 85%-110%Ue

Switch-On Electromagnet

Voltage & Current Alternating Current Direct Current Service Voltage Range

Rated Voltage(V) 110 220 48 110 220 85%~110%Ue

Rated Current(A) 2 1 3.53 1.55 0.77

Switch-Off Electromagnet

Voltage & Current Alternating Current Direct Current Service Voltage Range

Rated Voltage(V) 110 220 48 110 220 65%~120%Ue

Rated Current(A) 2 1 3.53 1.55 0.77

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 11

7.5 (RN1 Type) Fuse Technical Parameters

Type RN1-6 RN1-10

Rated Voltage (kV) 6 10

Max Breaking Current Effective (Ka) 20 12

Rated Current (A) 20

Rated Current For Fuse(A) 2,3,5,7.5,10,15,20

Current Limiting Peak For Breaking Limiting Short Scirait Current 5.2 4.5

RN2 Type Fuse Technical Parameters

Type Rated Voltage (kV)

Rated Current(A) Rated Breaking Capacity MVA

Fuse Pipe Resistance(Ω)

RN2-6 6 0.5 1000 5.6

RN2-10 10

7.6 Zinc-Oxide Arrester (Silicone Rubber Gapless) Parameters

Type (HY5WS) 10/30 17/50 10/30 17/45 10/27 10/45

System Rated Voltage(Kv)

6 10 6 10 6 10

Arrester Rated Voltage(kV) 10 17 10 17 10 17

Continual Service Voltage(kv) 7 12.7 7 12.7 7 12.7

Reference Voltage DC 1mA (kv) 15.0 25.0 14.4 24.0 13.8 23.0

Rating Discharge Current(Ka) 5 5 5 5 5 5

Residual Voltage Under Lighting Impulse Current (≤Kv) 30.0 50.0 27.0 45.0 27.0 45.0

Residual Voltage Under Steep Current Impulse (≤Kv) 34.5 57.5 31.0 51.8 / /

Residual Voltage Under Operating Impulse Current (≤Kv) 25.5 42.5 23.0 38.3 21.0 35

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 12

Discharge Capacity For ZMS Square Impulse (A) 100 100 150 150 400 400

Note Discharge Station

8. Interpretive Structural Switch equipment designed standard armoured metal-enclosed

switchgear.

KYN28-12 Series H.V Metal Clad Switchgear by fixed cabinet

body and handcart,

composed of two parts.

cabinet body shell and the

separator adopts bolt

coupling of each function unit.

Switchgear enclosure

protection grade is IP4X,

circuit breaker room door is opened, the protective class is

IP2X.

Can with the vacuum circuit breaker handcart Switchgear, can

also be used with fixed load switch.

With overhead into (out of) line, cable wire and other functions.

Switchgear can be installed into a double tank arrangement,

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 13

that is, installation into a back to back or face to face double row

arrangement (see figure 6, 7)

FIG 6 Double Bus (back to back) Solution &Switchgear Schematic

FIG 7 Double Bus (Face-to-Face) Solution &Switchgear Schematic

8.1 Shell and Partition

KYN28-12 Series H.V Metal Clad Switchgear shell and baffle

plate is made by aluminium zinc steel plate, the CNC machine

tool processing, and adopts the multiple folding process, the

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 14

whole cabinet body not only has high precision, strong

resistance to corrosion and oxidation resistance.

Due to adopting multiple flanging process, make the cabinet

body than other similar equipment cabinet body, light weight,

high mechanical strength as a whole.

Cabinet body adopts modular structure, with the pull rivet nuts

and high strength bolt connection and into.

Short production cycle, parts versatility, covers an area of less,

easy to organize production.

Switchgear is separated into handcart room, bus room, cable

room, relay instrument room (low voltage room), every outdoor

insulation shell are independent grounding.

Switchgear door use spraying plastics coating process, make its

surface impact resistant, corrosion resistant, guarantees the

appearance is beautiful

8.2 Handcart

Handcart skeleton, uses the steel plate, riveting after processed

by CNC machine tool.

Handcart and Cabinet body insulation coordination, mechanical

interlocking, safe, reliable and flexible.

According to the purpose, handcart can be divided into the

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 15

circuit breaker handcart, voltage

transformer handcart, metering

handcart, and so on.

All kinds of height and depth of the

handcart is unified, the same

specifications of the handcart can swap.

Handcart in the Cabinet body with isolation/test position and

work location, each place has positioning device, to ensure

reliable interlocking, should be performed according to

interlocks prevent wrong operation procedure.

All handcart adopt rock propulsion, exit the nut, screw, its

lightweight, flexible operation, suitable for the personnel on

duty operation.

Handcart when you need to remove the Cabinet body, with a

special transport vehicles, can be pulled out, for all kinds of

inspection, maintenance;

Use intermediate implantation, the handcart is small in size,

inspection, maintenance is extremely convenient.

8.3 Switchgear Inside the Compartment

KYN28-12 Series H.V Metal Clad Switchgear of the main

electrical components have their separate compartment, circuit

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 16

breaker room handcart room, bus room, cable room, relay

instrument room.

Each compartment protection grade achieved IP2X;

In addition to relay outside, other three compartment

respectively have its drain voltage channel.

Adopted the intermediate implantation, cable room position has

greatly increased, so the device can connect multiple cable.

8.3.1 Circuit Breaker Room

In the circuit breaker room installed for circuit breaker

handcart sliding guide rail.

Handcart can work in the location, test/isolation between

mobile.

Activity curtain plate made of metal plate installed after the

handcart room wall.

Handcart from isolation in mobile to work location/test

position, in a small busbar room and cable connection

chamber (cable room) in the static contact box on the static

contact of the activity curtain plate automatically open.

Reverse direction handcart, activity curtain plate automatic

closing, closed up and the static contact case, so as to

guarantee the operators do not touch the charged body.

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 17

Handcart in the switchgear door closed cases by operation,

through the observation window you can see the handcart

inside ark's position.

At the same time also can see the hand car On (to make the

circuit breaker closing)/OFF (to make the circuit breaker

break-brake) buttons and On/OFF mechanical position

indicator and energy storage/release status indicator

8.3.2 Draw Out Type Circuit Breaker Handcar

Frame is welded by steel plate, hand car equipped with

vacuum circuit breaker and other auxiliary equipment.

A dynamic contact with spring contacts subsystem, the arm

in a circuit breaker on the outlet terminals, circuit breaker

operating mechanism of the control button and on/off

instructions, etc., are in the handcart panel, with convenient

operation.

Handcart into the Switchgear arrived at isolation/test position,

the handcart shell and reliable

connected switchgear earthing

system, instrument protection

and control circuit are also

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 18

through secondary switchgear and plug for connection.

8.3.3 Bus Compartment Room

Bus bar from one switchgear to the other switchgear, through

the branch busbar and static contact box fixed.

Lady rounded copper platoon of contact line and bus bar with

rectangular cross section.

Used for high current load need to use two rectangle busbar.

All bus bar with heat shrinkable casing cover.

Flat branch line by bolt connection with static contact box of

mistress line connected.

Bus through the Switchgear supported by insulating sleeve

plate, if internal arc fault line inside ark, can prevent bus

through melting, guarantee the accident does not spread to

the adjacent tank, and avoid mistress line deformation due to

the effect of electric power.

8.3.4 Cable Compartment Room

Cable compartment room back wall, can be installed current

transformer, voltage transformer, grounding switch, cable room

also can install lightning arrester.

After handcart and horizontal clapboard move, construction

personnel could enter a Switchgear installed cable from the

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 19

front.

Has specific cable connection in indoor cable conductor, and

1-6 single core cable, at the same time in the lower part of the

preparation of removable metal plate, to ensure that the site

construction convenience.

8.3.5 Instrument Compartment

Instrument interior insulation can be installed relay protection

equipment, instruments, electrical monitoring indicator and

special requirements of secondary equipment.

Control circuit laying within the enough space of the trough, and

the metal plate.

On the left side of the trough is reserved for the control of small

bus introduction and raises, secondary line Switchgear

equipped on the right.

There were small instrument compartment on the side panel of

bus bar through the hole to construction.

8.4 Prevent Wrong Operation Interlock

Switchgear has reliable interlocking device for operating and

maintenance personnel to provide reliable safety protection, its

action is as follows:

Handcart from work position to the isolation/test position,

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 20

activity curtain board to separate the static contact box, prevent

into charged across the room. Overhaul, the available padlock

lock activity curtain plate.

The circuit breaker is in a state ON, handcart cannot be pulled

out from the work position or push isolation/test position to work

location. Circuit breaker handcart has fully lock test position or

work position can be operation

Grounding switch only in handcart in isolation/test position and

to be operating outside the tank, when the earthing switch is in a

state ON, handcart can't work from isolation/test location to

location.

Handcart in the work position, the second plug is locked can not

pull to open

8.5 Pressure Relief Devices

In the handcart room, busbar room and cable room above, are

equipped with pressure relief devices.

When a circuit breaker or bus internal arc fault occurs, along

with the emergence of the arc, higher air

pressure inside the Switchgear, the top

pressure relief plate assembly will be

automatically open.

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 21

Release pressure and discharge gas, to ensure the safety of

operators and switchgear.

8.6 Second Plug and The Location Of Handcart Interlock

Second line in the Switchgear and the handcart secondary line

of contact is done by a second plug.

Secondary dynamic contact plug through a nylon corrugated

pipe is connected to a handcart, secondary static contactor seat

installed in the top right switchgear breaker compartment.

Handcart only in the test/isolation position, can plug in and

remove the second plug, handcart in working position in

mechanical interlock function, quadratic plug is locked, can't

remove.

Circuit breaker handcart in secondary can only before the plug

is not connected to brake, as a result of the circuit breaker

handcart switch mechanism by electromagnetic lock, so I can't

make its closing.

8.7 Charged Display Device

Switchgear with charged display device.

The device is composed of high voltage sensors and portable

display of two parts.

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 22

Sensors installed in bus or feeder side, the monitor interface is

installed on the low voltage switchgear isolation room, need to

be detected when A, B, C three-phase is charged, can insert the

plug of the portable display L1, L2, L3 interfaces, if the display

action, says bus or feeder side charged, on the other hand,

shows no charge.

At the same time also can be used as phase sequence detector

or lightning indicator, its effect also is testing whether charged

on the high side

8.8 Prevent Condensation and Corrosion

In order to prevent the high humidity or temperature change the

larger environment, climate produce condensation of danger.

In the circuit breaker room and cable room installed heater

respectively, in order to use in the environment and prevent the

corrosion.

8.9 Grounding Device

In the cable room separate 5 x 40mm ² was grounding copper

platoon, by the adjacent Switchgear, and with the cabinet body

good contact.

Grounding for the use of direct grounding of the components.

Cabinet body with aluminized zinc plate split, so that the whole

Electrical Treasure ▏One-Stop Supplier Of Electrical Equipment 23

cabinet body was in good grounding, ensuring the safety of

operating personnel and cabinet body..