l-04 analysis and design of two-way slab with beams (b&w)
TRANSCRIPT
1
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Lecture-04
Analysis and Design of Two-way
Slab System(Part-I: Two Way Slabs Supported on Stiff
Beams Or Walls)
By: Prof Dr. Qaisar Ali
Civil Engineering Department
UET Peshawarwww.drqaisarali.com
1
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Topics
� Behavior
� Moment Coefficient Method
� Steps in Moment Coefficient Method
� Design Example 1 (Typical House with 2 Rooms and Verandah)
� Design Example 2 (100′ × 60′, 3-Storey Commercial Building)
� Practice Examples
� References
2
2
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab System (Long span/short span < 2)
3
25′ 25′ 25′ 25′
20′
20′
20′
Behavior
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
4
One-Way Behavior Two-Way Behavior
Behavior
� Two-Way Bending of Two-Way Slabs
3
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
5
Behavior
� Two-Way Bending of Two-Way Slabs
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
6
Short Direction
Behavior
� Short Direction Moments in Two-Way Slab
4
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
7
Long Direction
Behavior
� Long Direction Moments in Two-Way Slab
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� More Demand (Moment) in short direction due to size
of slab
� Δcentral Strip = (5/384)wl4/EI
� As these imaginary strips are part of monolithic slab, the deflection at
any point, of the two orthogonal slab strips must be same:
� Δa = Δb
(5/384)wala4/EI = (5/384)wblb4/EI
� wa/wb = lb4/la4 wa = wb (lb4/la4)
� Thus, larger share of load (Demand) is taken by the shorter direction.
8
Behavior
5
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� The Moment Coefficient Method included for the first time in
1963 ACI Code is applicable to two-way slabs supported on
four sides of each slab panel by walls, steel beams relatively
deep, stiff, edge beams (h = 3hf).
� Although, not included in 1977 and later versions of ACI code,
its continued use is permissible under the ACI 318-11 code
provision (13.5.1). Visit ACI 13.5.1.
9
Moment Coefficient Method
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moments:
Ma, neg = Ca, negwula2
Mb, neg = Cb, negwulb2
Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la2
Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb2
� Where Ca, Cb = Tabulated moment coefficients
wu = Ultimate uniform load, psf
la, lb = length of clear spans in short and long directions respectively.
10
Ma,neglb
laMa,neg
Ma,posMb,neg Mb,negMb,pos
Moment Coefficient Method
6
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Cases
� Depending on the support conditions, several cases are possible:
11
Moment Coefficient Method
4 spans @ 25′-0″
3 spans @ 20′-0″
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
12
Moment Coefficient Method
� Cases
� Depending on the support conditions, several cases are possible:
4 spans @ 25′-0″
3 spans @ 20′-0″
7
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
13
Moment Coefficient Method
� Cases
� Depending on the support conditions, several cases are possible:
4 spans @ 25′-0″
3 spans @ 20′-0″
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
14
Moment Coefficient Method
� Cases
� Depending on the support conditions, several cases are possible:
4 spans @ 25′-0″
3 spans @ 20′-0″
8
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
15
Moment Coefficient Method
Note: Horizontal sides of the figure represents longer side while vertical side
represents shorter side.
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
16
Moment Coefficient Method
Note: Horizontal sides of the figure represents longer side while vertical side
represents shorter side.
9
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
17
Moment Coefficient Method
Note: Horizontal sides of the figure represents longer side while vertical side
represents shorter side.
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
18
Moment Coefficient Method
Note: Horizontal sides of the figure represents longer side while vertical side
represents shorter side.
10
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
19
Moment Coefficient Method
Note: Horizontal sides of the figure represents longer side while vertical side
represents shorter side.
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
20
Moment Coefficient Method
Note: Horizontal sides of the figure represents longer side while vertical side
represents shorter side.
11
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
21
Moment Coefficient Method
Note: Horizontal sides of the figure represents longer side while vertical side
represents shorter side.
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� hmin = perimeter/ 180 = 2(la + lb)/180
� Calculate loads on slab
� Calculate m = la/ lb
� Decide about case of slab
� Use table to pick moment coefficients
� Calculate Moments and then design
� Apply reinforcement requirements (smax = 2hf, ACI 13.3.2)
22
Steps in Moment Coefficient Method
12
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� 3D Model of the House
� In this building we will design a two-way slab (for rooms), a one-way
slab, beam and column (for verandah)
23
Design Example 1(Typical House with 2 Rooms and Verandah)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Given Data:
� Service Dead Load
� 4″ thick mud
� 2″ thick brick tile
� Live Load = 40 psf
� f′c = 3 ksi
� fy = 40 ksi
24
Design Example 1(Typical House with 2 Rooms and Verandah)
13
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Sizes
� For two way slab system
� hmin = perimeter / 180 = 2(la + lb)/180
� hmin = 2 (12 +16) /180 = 0.311 ft = 3.73 inch
� Assume 5 inch slab
� For one way slab system
� For 5″ slab, span length l is min. of:
� l = ln+ hf = 8 + (5/12) = 8.42′
� c/c distance between supports = 8.875′
� Slab thickness (hf) = (8.42/24) × (0.4+��/100000)
= 3.367″ (min. by ACI)
� Taking 5 in. slab
25
Design Example 1(Typical House with 2 Rooms and Verandah)
9′ Wide Verandah
ln = 8′
lc/c = (8 + (9/12) / 2 + 0.5) = 8.875′
9″ Brick Wall
Slab
h
A
A
Section AA
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Loads
� 5 inch Slab = 5/12 x 0.15 = 0.0625 ksf
� 4 inch mud = 4/12 x 0.12 = 0.04 ksf
� 2 inch tile = 2/12 x 0.12 = 0.02 ksf
� Total DL = 0.1225 ksf
� Factored DL = 1.2 x 0.1225 = 0.147 ksf
� Factored LL = 1.6 x 0.04 = 0.064 ksf
� Total Factored Load = 0.211 ksf
26
Design Example 1(Typical House with 2 Rooms and Verandah)
14
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis
� This system consist of both one way and two way slabs. Rooms
(two way slabs) are continuous with verandah (one way slab).
� A system where a two way slab is continuous with a one way slab
or vice versa is called a mixed slab system.
27
Design Example 1(Typical House with 2 Rooms and Verandah)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis
� The ACI approximate methods of analysis are not applicable to
such systems because:
� In case of two way slabs, the moment coefficient tables are applicable
to two way slab system where a two way slab is continuous with a two
way slab.
� In case of one ways slabs, the ACI approximate analysis is applicable
to one way slab system where a one way slab is continuous with a one
way slab.
28
Design Example 1(Typical House with 2 Rooms and Verandah)
15
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis
� The best approach to analyze a mixed system is to use FE
software.
� However, such a system can also be analyzed manually by making
certain approximations.
� In the next slides, We will analyze this system using both of the
above mentioned methods.
29
Design Example 1(Typical House with 2 Rooms and Verandah)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis using FE Software (SAFE)
30
Design Example 1(Typical House with 2 Rooms and Verandah)
Moments in Longer Direction in Two Way Slabs
Moments in Shorter Direction in Two Way Slabs & Moment in Verandah One Way Slab
Two Way Slab Moments (ft-kip/ft)(Rooms)
One Way Slab Moment (ft-kip/ft)(Verandah)
Ma,pos Mb,pos Ma,neg Mb,neg Mver (+ve)
1.58 1.17 2.10 1.67 1.10
Mb,pos Mb,posMb,neg Ma,
pos
Ma,
pos
Ma,
neg
Ma,
neg
Mve
r(+
ve)
Mb,pos
Ma,
pos
Ma,
neg
Mb,negMb,pos
Ma,
neg
Ma,
pos
Mve
r(+
ve)
16
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis using Manual Approach
� For approximate manual analysis of two way slab of rooms, we
know that two way slabs of rooms are not only continuous along the
long direction but also continuous along the short direction with the
verandah slab. We assume that the verandah slab is a two way slab
instead of one way slab in order to calculate Mb,neg
� Now, using Moment Coefficient Method for analysis.
31
Design Example 1(Typical House with 2 Rooms and Verandah)
Mb,pos
Ma,
pos
Ma,
neg
Mb,negMb,pos
Ma,
neg
Ma,
pos
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis
Case = 4
m = la/lb = 12/16 = 0.75
Ca,neg = 0.076
Cb,neg = 0.024
Ca,posDL = 0.043
Cb,posDL = 0.013
Ca,posLL = 0.052
Cb,posLL = 0.016
Design Example 1(Typical House with 2 Rooms and Verandah)
32
16′
12′
Mb,negMb,pos
Ma,
pos
Case 4
Ma,
neg
17
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis
Case = 4
m = la/lb = 12/16 = 0.75
Ca,neg = 0.076
Cb,neg = 0.024
Ca,posDL = 0.043
Cb,posDL = 0.013
Ca,posLL = 0.052
Cb,posLL = 0.016
Design Example 1(Typical House with 2 Rooms and Verandah)
33
16′
12′
Mb,negMb,pos
Ma,
pos
Case 4
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Case = 4
m = la/lb = 12/16 = 0.75
Ca,neg = 0.076
Cb,neg = 0.024
Ca,posDL = 0.043
Cb,posDL = 0.013
Ca,posLL = 0.052
Cb,posLL = 0.016
� Two-Way Slab Analysis
Design Example 1(Typical House with 2 Rooms and Verandah)
34
16′
12′
Mb,negMb,pos
Ma,
pos
Case 4
Ma,
neg
18
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Case = 4
m = la/lb = 12/16 = 0.75
Ca,neg = 0.076
Cb,neg = 0.024
Ca,posDL = 0.043
Cb,posDL = 0.013
Ca,posLL = 0.052
Cb,posLL = 0.016
� Two-Way Slab Analysis
Design Example 1(Typical House with 2 Rooms and Verandah)
35
16′
12′
Mb,negMb,pos
Ma,
pos
Case 4
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Case = 4
m = la/lb = 12/16 = 0.75
Ca,neg = 0.076
Cb,neg = 0.024
Ca,posDL = 0.043
Cb,posDL = 0.013
Ca,posLL = 0.052
Cb,posLL = 0.016
� Two-Way Slab Analysis
Design Example 1(Typical House with 2 Rooms and Verandah)
36
16′
12′
Mb,negMb,pos
Ma,
pos
Case 4
Ma,
neg
19
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Case = 4
m = la/lb = 12/16 = 0.75
Ca,neg = 0.076
Cb,neg = 0.024
Ca,posDL = 0.043
Cb,posDL = 0.013
Ca,posLL = 0.055
Cb,posLL = 0.016
� Two-Way Slab Analysis
Design Example 1(Typical House with 2 Rooms and Verandah)
37
16′
12′
Mb,negMb,pos
Ma,
pos
Case 4
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
38
Design Example 1(Typical House with 2 Rooms and Verandah)
� Two-Way Slab Analysis
� Calculating moments using ACI Coefficients:
Ma, neg = Ca, negwula2
Mb, neg = Cb, negwulb2
Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la2
Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb2
� Using above relations the moments calculated are:
Ca,neg = 0.076 Cb,neg = 0.024
Ca,posLL = 0.052 Cb,posLL = 0.016
Ca,posDL = 0.043 Cb,posDL = 0.013
wu, d l = 0.147 ksf, wu, ll = 0.064 ksf, wu = 0.211 ksf
� Ma,neg = 2.31 ft-kip
� Mb,neg = 1.29 ft-kip
� Ma,pos = 1.39 ft-kip
� Mb,pos = 0.76 ft-kip
16′
12′
Mb,negMb,pos
Ma,
pos
Case 4
Ma,
neg
20
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� One Way Slab Analysis
� For calculation of Mver (+ve) along the short direction in the verandah
slab, we will pick the coefficients of continuous one way slabs having
two spans.
� Now, using ACI Approximate analysis procedure (ACI 8.33) for analysis.
39
Design Example 1(Typical House with 2 Rooms and Verandah)
Mve
r(+v
e)Mve
r(-v
e)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
40
Design Example 1(Typical House with 2 Rooms and Verandah)
� One-Way Slab Analysis
� For two span one way slab system, positive moment at midspan is given as
follows:
� Mver (+ve) = wuln2/14
� Mver (+ve) = 0.211 × (8)2/14
= 0.96 ft-k/ft
� Mver (-ve) = wuln2/9 = 1.5 ft-k/ft
9′ Wide Verandah
ln = 8′
9″ Brick Wall
Wu = 0.211 ksf
h
1/14
1/9 1/9SpandrelSupport
Simply Supported
For negative moment above the long wall commonto rooms and veranda, maximum moment will bepicked from both analyses.
Moment of 2.3 from two way slab analysis is morethan 1.5, therefore we will design for 2.31.
1/24
21
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
41
Design Example 1(Typical House with 2 Rooms and Verandah)
� Design of Two-Way Slab
� Comparison of Analysis Results from FE Analysis and Manual Analysis
� Analysis results from both approaches are almost similar.
� Hence the intelligent use of manual analysis yields fairly reasonable results in most cases.
Analysis Type
Ma,neg Mb,neg Ma,pos Mb,pos Mver (+ve)
SAFE 2.10 1.67 1.58 1.17 1.10
Manual 2.31 1.3 1.39 0.76 0.96
NOTE: All values are in ft-kip units
Mb,pos
Ma,
pos
Ma,
neg
Mb,negMb,pos
Ma,
neg
Ma,
pos
Mve
r(+
ve)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
42
Design Example 1(Typical House with 2 Rooms and Verandah)
� Design of Two-Way Slab
� First determining capacity of min. reinforcement:
� As,min = 0.002bhf = 0.12 in2
� Using #3 bars: Spacing for As,min = 0.12 in2 = (0.11/0.12) × 12 = 11″ c/c
� However ACI max spacing for two way slab = 2h = 2(5) = 10″ or 18″ = 10″ c/c
� Hence using #3 bars @ 10″ c/c
� For #3 bars @ 10″ c/c: As,min = (0.11/10) × 12 = 0.132 in2
� Capacity for As,min: a = (0.132 × 40)/(0.85 × 3 × 12) = 0.17″
� ΦMn = ΦAsminfy(d – a/2) = 0.9 × 0.132 × 40(4 – (0.17/2)) = 18.60 in-kip
� Therefore, for Mu values ≤ 18.60 in-k/ft, use As,min (#3 @ 10″ c/c) & for Mu
values > 18.6 in-kip/ft, calculate steel area using trial & error procedure.
22
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
43
Design Example 1(Typical House with 2 Rooms and Verandah)
� Design of Two-Way Slab
� For Ma,neg = 2.31 ft-kip = 27.71 in-kip > 18.60 in-kip: As = 0.20 in2 (#3 @ 6.6″ c/c)
� Using #3 @ 6″ c/c
� For Mb,neg = 1.29 ft-kip = 15.56 in-kip < 18.60 in-kip: Using #3 @ 10″ c/c
� For Ma,pos = 1.39 ft-kip = 16.67 in-kip < 18.60 in-kip: Using #3 @ 10″ c/c
� For Mb,pos = 0.76 ft-kip = 9.02 in-kip < 18.60 in-kip: Using #3 @ 10″ c/c
16′
12′
Mb,negMb,pos
Ma,
pos
Case 4M
a,ne
g
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
44
Design Example 1(Typical House with 2 Rooms and Verandah)
� Design of Two-Way Slab
� Reinforcement at Discontinuous Ends
� Reinforcement at discontinuous ends in a two way slab is 1/3 of the positive
reinforcement.
� Positive reinforcement at midspan in this case is #3 @ 10″ c/c. Therefore
reinforcement at discontinuous end may be provided @ 30″ c/c.
� However, in field practice, the spacing of reinforcement at discontinuous ends
seldom exceeds 18″ c/c. The same is provided here as well.
� Supporting Bars
� Supporting bars are provided to support negative reinforcement.
� They are provided perpendicular to negative reinforcement, generally at spacing
of 18″ c/c.
23
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
45
Design Example 1(Typical House with 2 Rooms and Verandah)
� Design of One-Way Slab
� Main Reinforcement:
� Mver (+ve) = 14.73 in-kip
� As,min = 0.002bhf = 0.002(12)(5) = 0.12 in2
� Using #3 bars, spacing = (0.11/0.12) × 12 = 11″ c/c
� For one-way slabs, max spacing by ACI = 3h = 3(5) = 15″ or 18″ = 15″ c/c
� For #3 bars @ 15″ c/c, As = (0.11/15) × 12 = 0.09 in2. Hence using As,min = 0.12 in2
� a = (0.12 × 40)/(0.85 × 3 × 12) = 0.16″
� ΦMn = ΦAsminfy(d – a/2) = 0.9 × 0.12 × 40(4 – (0.16/2)) = 16.94 in-kip > Mver (+ve)
� Therefore, using #3 @ 11″ c/c
� However, for facilitating field work, we will use #3 @ 10″ c/c
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
46
Design Example 1(Typical House with 2 Rooms and Verandah)
� Design of One-Way Slab
� Shrinkage Reinforcement:
� Ast = 0.002bhf = 0.12 in2 (#3 @ 11″ c/c)
� However, for facilitating field work, we will use #3 @ 10″ c/c
24
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
47
� Verandah Beam Design
� Step 01: Sizes
� Let depth of beam = 18″
� ln + depth of beam = 15.875′ + (18/12) = 17.375′
� c/c distance between beam supports
= 16.375 + (4.5/12) = 16.75′
� Therefore l = 16.75′
� Depth (h) = (16.75/18.5) × (0.4 + 40000/100000) × 12
= 8.69″ (Minimum requirement of ACI 9.5.2.2).
� Take h = 1.5′ = 18″
� d = h – 3 = 15″
� b = 12″
Design Example 1(Typical House with 2 Rooms and Verandah)
Verandah Beam
16.375′ 16.375′
ln = 16.375 – 0.5(12/12) = 15.875′ ln = 16.375 – 0.5(12/12) = 15.875′
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
48
� Verandah Beam Design
� Step 02: Loads
� Load on beam will be equal to
� Factored load on beam from slab + factored
self weight of beam web
� Factored load on slab = 0. 211 ksf
� Load on beam from slab = 0. 211 ksf x 5 =
1.055 k/ft
� Factored Self load of beam web =
� = 1.2 x (13 × 12/144) × 0.15 = 0.195 k/ft
� Total load on beam = 1.055 + 0.195
= 1.25 k/ft
5′
Design Example 1(Typical House with 2 Rooms and Verandah)
ln = 8′
9″ Brick Wall
8/2 = 4′
12″ Column
4′ + 1′ = 5′
25
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
49
� Verandah Beam
Design
� Step 03: Analysis
� Using ACI Moment
Coefficients for analysis
of verandah beam
Design Example 1(Typical House with 2 Rooms and Verandah)
16.375′ln = 16.375 – 0.5(12/12) = 15.875′ ln = 16.375 – 0.5(12/12) = 15.875′16.375′
16.375′
ln = 15.875′ ln = 15.875′
9.92 k
11.41 k
Vu(ext) = 8.34 k
Vu(int) = 9.61 k
343.66 in-kip 343.66 in-kip
420.03 in-kip
Verenda beam is l beam,be
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Beam Design
� Flexure Design:
� Shear Design:
� Smax is min. of: (1) Avfy/(50bw) = 14.67″ (2) d/2 =7.5″ (3) 24″ c/c (4) Avfy/ 0.75√(fc′)bw = 17.85″
50
Design Example 1(Typical House with 2 Rooms and Verandah)
Mu(in-kip)
d (in.)
b (in.)
As(in2)
Asmin(in2)
Asmax(in2)
As(governing)
Bar used
# of bars
343.66 (+) 15 28.75 (beff) 0.64 0.90 3.654 0.90 #4 5
#5 3
420.03 (-) 15 12 0.81 0.90 3.654 0.90 #4 5
#4 + #5 2 + 2
Location V u (@ d)(kip)
ΦVc = Φ2 �′�bwd (kips) ΦVc > Vu, Hence
providing minimum reinforcement.
smax, ACI
S taken(#3 2-legged)
Exterior 8.34 14.78 7.5″ 7.5″
Interior 9.61 14.78 7.5″ 7.5″
26
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
51
Design Example 1(Typical House with 2 Rooms and Verandah)
� Column Design
� Sizes:
� Column size = 12″ × 12″
� Loads:
� Pu = 11.41 × 2 = 22.82 kip
Verandah Column
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
52
Design Example 1(Typical House with 2 Rooms and Verandah)
� Column Design
� Main Reinforcement Design:
� Nominal strength (ΦPn) of axially loaded column is:
ΦPn = 0.80Φ {0.85fc′ (Ag – Ast) + Astfy} {for tied column, ACI 10.3.6}
� Let Ast = 1% of Ag (Ast is the main steel reinforcement area)
� ΦPn = 0.80 × 0.65 × {0.85 × 3 × (144 – 0.01 × 144) + 0.01 × 144 × 40}
= 218.98 kip > Pu = 22.82 kip, O.K.
� Ast =0.01 × 144 =1.44 in2
� Using 3/4″ Φ (#6) with bar area Ab = 0.44 in2
� No. of bars = 1.44/0.44 = 3.27 ≈ 4 bars
� Use 4 #6 bars (or 8 #4 bars) and #3 ties @ 9″ c/c
27
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
53
Design Example 1(Typical House with 2 Rooms and Verandah)
� Drafting Details for
Slabs
Panel Depth (in) Mark Bottom Reinforcement Mark Top rei nforcement
S1 5"M1 #3 @ 10" c/c
MT1 #3 @ 10" c/c Continuous EndMT1 #3 @ 18" c/c Non Continuous End
M2 #3 @ 10" c/cMT2 #3 @ 6" c/c Continuous EndMT2 #3 @ 18" c/c Non Continuous End
S2 5"M1 #3 @ 10" c/c MT2 #3 @ 6" c/c Continuous EndM2 #3 @ 10" c/c MT2 #3 @ 18" c/c Non Continuous End
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
54
Design Example 1(Typical House with 2 Rooms and Verandah)
� Drafting Details for Slabs
28
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
55
Design Example 1(Typical House with 2 Rooms and Verandah)
� Drafting Details for Verandah Beam
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
56
Design Example 1(Typical House with 2 Rooms and Verandah)
� Drafting Details for Verandah Column
OR
29
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� A 100′ × 60′, 3-storey commercial building is to be designed. The grids of
column plan are fixed by the architect.
� In this example, the slab of one of the floors of this 3-storey building will
be designed.
57
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Given Data:
� Material Properties:
� f′c = 3 ksi, fy = 40 ksi
� Sizes:
� Slab thickness = 7″
� Columns = 14″ × 14″
� Beams = 14″ × 20″
� Loads:
� S.D.L = Nil
� Self Weight = 0.15 x (7/12) = 0.0875 ksf
� L.L = 144 psf = 0.144 ksf ; wu = 0.336 ksf
58
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
30
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Complete analysis of the slab is done by analyzing four panels
59
Panel I Panel I
Panel I Panel I
Panel II Panel II
Panel III Panel III
Panel III Panel III
Panel IV Panel IV
4 spans @ 25′-0″
3 spans @ 20′-0″
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-I)
Case = 4
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.071
Cb,neg = 0.029
Ca,posDL = 0.039
Cb,posDL = 0.016
Ca,posLL = 0.048
Cb,posLL = 0.020
Case 4 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,neg
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
60
31
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-I)
Case = 4
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.071
Cb,neg = 0.029
Ca,posDL = 0.039
Cb,posDL = 0.016
Ca,posLL = 0.048
Cb,posLL = 0.020
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
61
Case 4 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-I)
Case = 4
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.071
Cb,neg = 0.029
Ca,posDL = 0.039
Cb,posDL = 0.016
Ca,posLL = 0.048
Cb,posLL = 0.020
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
62
Case 4 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,neg
32
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-I)
Case = 4
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.071
Cb,neg = 0.029
Ca,posDL = 0.039
Cb,posDL = 0.016
Ca,posLL = 0.048
Cb,posLL = 0.020
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
63
Case 4 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-I)
Case = 4
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.071
Cb,neg = 0.029
Ca,posDL = 0.039
Cb,posDL = 0.016
Ca,posLL = 0.048
Cb,posLL = 0.020
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
64
Case 4 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,neg
33
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-I)
Case = 4
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.071
Cb,neg = 0.029
Ca,posDL = 0.039
Cb,posDL = 0.016
Ca,posLL = 0.048
Cb,posLL = 0.020
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
65
Case 4 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
66
� Two-Way Slab Analysis (Panel-I)
� Calculating moments using ACI Coefficients:
Ma, neg = Ca, negwula2
Mb, neg = Cb, negwulb2
Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la2
Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb2
� Using above relations the moments calculated are:
Ca,neg = 0.071 Cb,neg = 0.029
Ca,posLL = 0.048 Cb,posLL = 0.020
Ca,posDL = 0.039 Cb,posDL = 0.016
wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf
� Ma,neg = 8.44 ft-k (101.2 in-k)
� Mb,neg = 5.52 ft-k (66.2 in-k)
� Ma,pos = 5.37 ft-k (64.4 in-k)
� Mb,pos = 3.57 ft-k (42.8 in-k)
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Case 4 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,neg
34
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-II)
Case = 9
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.075
Cb,neg = 0.017
Ca,posDL = 0.029
Cb,posDL = 0.010
Ca,posLL = 0.042
Cb,posLL = 0.017
Case 9 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
67
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-II)
Case = 9
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.075
Cb,neg = 0.017
Ca,posDL = 0.029
Cb,posDL = 0.010
Ca,posLL = 0.042
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
68
Case 9 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
35
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-II)
Case = 9
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.075
Cb,neg = 0.017
Ca,posDL = 0.029
Cb,posDL = 0.010
Ca,posLL = 0.042
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
69
Case 9 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-II)
Case = 9
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.075
Cb,neg = 0.017
Ca,posDL = 0.029
Cb,posDL = 0.010
Ca,posLL = 0.042
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
70
Case 9 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
36
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-II)
Case = 9
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.075
Cb,neg = 0.017
Ca,posDL = 0.029
Cb,posDL = 0.010
Ca,posLL = 0.042
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
71
Case 9 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-II)
Case = 9
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.075
Cb,neg = 0.017
Ca,posDL = 0.029
Cb,posDL = 0.010
Ca,posLL = 0.042
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
72
Case 9 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
37
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
73
� Two-Way Slab Analysis (Panel-II)
� Calculating moments using ACI Coefficients:
Ma, neg = Ca, negwula2
Mb, neg = Cb, negwulb2
Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la2
Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb2
� Using above relations the moments calculated are:
Ca,neg = 0.075 Cb,neg = 0.017
Ca,posLL = 0.042 Cb,posLL = 0.017
Ca,posDL = 0.029 Cb,posDL = 0.010
wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf
� Ma,neg = 8.91 ft-k (106.9 in-k)
� Mb,neg = 3.24 ft-k (38.8 in-k)
� Ma,pos = 4.51 ft-k (54.1 in-k)
� Mb,pos = 2.82 ft-k (33.8 in-k)
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Case 9 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-III)
Case = 8
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.055
Cb,neg = 0.041
Ca,posDL = 0.032
Cb,posDL = 0.015
Ca,posLL = 0.044
Cb,posLL = 0.019
Case 8 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
74
38
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-III)
Case = 8
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.055
Cb,neg = 0.041
Ca,posDL = 0.032
Cb,posDL = 0.015
Ca,posLL = 0.044
Cb,posLL = 0.019
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
75
Case 8 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-III)
Case = 8
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.055
Cb,neg = 0.041
Ca,posDL = 0.032
Cb,posDL = 0.015
Ca,posLL = 0.044
Cb,posLL = 0.019
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
76
Case 8 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
39
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-III)
Case = 8
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.055
Cb,neg = 0.041
Ca,posDL = 0.032
Cb,posDL = 0.015
Ca,posLL = 0.044
Cb,posLL = 0.019
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
77
Case 8 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-III)
Case = 8
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.055
Cb,neg = 0.041
Ca,posDL = 0.032
Cb,posDL = 0.015
Ca,posLL = 0.044
Cb,posLL = 0.019
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
78
Case 8 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
40
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-III)
Case = 8
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.055
Cb,neg = 0.041
Ca,posDL = 0.032
Cb,posDL = 0.015
Ca,posLL = 0.044
Cb,posLL = 0.019
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
79
Case 8 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
80
� Two-Way Slab Analysis (Panel-III)
� Calculating moments using ACI Coefficients:
Ma, neg = Ca, negwula2
Mb, neg = Cb, negwulb2
Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la2
Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb2
� Using above relations the moments calculated are:
Ca,neg = 0.055 Cb,neg = 0.041
Ca,posLL = 0.044 Cb,posLL = 0.019
Ca,posDL = 0.032 Cb,posDL = 0.015
wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf
� Ma,neg = 6.54 ft-k (78.4 in-k)
� Mb,neg = 7.80 ft-k (93.6 in-k)
� Ma,pos = 4.78 ft-k (57.4 in-k)
� Mb,pos = 3.38 ft-k (40.5 in-k)
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Case 8 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
41
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-IV)
Case = 2
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.065
Cb,neg = 0.027
Ca,posDL = 0.026
Cb,posDL = 0.011
Ca,posLL = 0.041
Cb,posLL = 0.017
Case 2 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
81
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-IV)
Case = 2
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.065
Cb,neg = 0.027
Ca,posDL = 0.026
Cb,posDL = 0.011
Ca,posLL = 0.041
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
82
Case 2 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
42
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-IV)
Case = 2
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.065
Cb,neg = 0.027
Ca,posDL = 0.026
Cb,posDL = 0.011
Ca,posLL = 0.041
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
83
Case 2 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-IV)
Case = 2
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.065
Cb,neg = 0.027
Ca,posDL = 0.026
Cb,posDL = 0.011
Ca,posLL = 0.041
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
84
Case 2 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
43
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-IV)
Case = 2
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.065
Cb,neg = 0.027
Ca,posDL = 0.026
Cb,posDL = 0.011
Ca,posLL = 0.041
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
85
Case 2 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Two-Way Slab Analysis (Panel-IV)
Case = 2
m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80
Ca,neg = 0.065
Cb,neg = 0.027
Ca,posDL = 0.026
Cb,posDL = 0.011
Ca,posLL = 0.041
Cb,posLL = 0.017
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
86
Case 2 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
44
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
87
� Two-Way Slab Analysis (Panel-IV)
� Calculating moments using ACI Coefficients:
Ma, neg = Ca, negwula2
Mb, neg = Cb, negwulb2
Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la2
Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb2
� Using above relations the moments calculated are:
Ca,neg = 0.065 Cb,neg = 0.027
Ca,posLL = 0.041 Cb,posLL = 0.017
Ca,posDL = 0.026 Cb,posDL = 0.011
wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf
� Ma,neg = 7.72 ft-k (92.7 in-k)
� Mb,neg = 5.14 ft-k (61.6 in-k)
� Ma,pos = 4.31 ft-k (51.8 in-k)
� Mb,pos = 2.88 ft-k (34.5 in-k)
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Case 2 la = 18.83′
lb = 23.83′
Ma,
neg
Ma,
pos
Mb,posMb,negMb,neg
Ma,
neg
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
88
� Analysis Results (All values are in ft-kip)
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
8.42
4 spans @ 25′-0″
3 spans @ 20′-0″
5.375.523.57
8.91
8.91
3.244.51
2.82
6.54
7.80 7.804.783.38
7.72
7.72
5.145.144.31
2.880.94
1.19
1.79 1.60 Mneg at Non-
Continuous End =
1/3 of Mpos
NOTE: White: Longer Direction Moments, Yellow: Short er Direction Moments
45
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
89
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
� Slab Design
� First determining the capacity of min. reinforcement:
� As,min = 0.002bhf = 0.002 × 12 × 7 = 0.17 in2
� For #4 bars, spacing = (0.20/0.17) × 12 = 14.2″ c/c.
� ACI max spacing for two-ways slabs = 2h = 2(7) = 14″ or 18″
� Using #4 @ 12″ c/c
� For the 12″ spacing: As = (0.20/12) × 12 = 0.20 in2. Hence As,min = 0.20 in2
� Capacity for As,min: a = (0.20 × 40)/(0.85 × 3 × 12) = 0.26″
� ΦMn = ΦAsminfy(d – a/2) = {0.9 × 0.20 × 40(6 – (0.26/2))}/12 = 3.52 ft-kip
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
90
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
� Slab Design
� Positive Moments in Long Direction:
� 3.57 ft-kip/ft
� 3.38 ft-kip/ft
� 2.82 ft-kip/ft
� 2.88 ft-kip/ft
� Since all the above moments values are almost equal to or less than
3.52 ft-kip/ft. Therefore using #4 @ 12″ c/c for all positive moments in
Longer direction.
46
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
91
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
� Slab Design
� Positive Moments in Short Direction:
� 5.37 ft-kip/ft
� 4.51 ft-kip/ft
� 4.78 ft-kip/ft
� 4.31 ft-kip/ft
� Using trial and success method for determining As for 5.37 ft-kip/ft:
� Assume a = 0.2d= 0.2(6) = 1.2″, As = (5.37 × 12)/{0.9 × 40(6 – (1.2/2))} = 0.33 in2
� Now, a = (0.33 × 40)/(0.85 × 3 × 12) = 0.43″, As = 0.31 in2
� For #4 bars, spacing = (0.20/0.31) × 12 = 7.7″
� As all the above moments are almost same, we will use #4 @ 7″ c/c for all above
moments.
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
92
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
� Slab Design
� Negative Moments at Non-Continuous Ends in Short & Long Directions:
� 1.19 ft-kip/ft
� 1.79 ft-kip/ft
� 1.60 ft-kip/ft
� 0.94 ft-kip/ft
� Since, all the above moments are
less than 3.52 ft-kip/ft, therefore using
#4 @ 12″ c/c
47
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
93
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
� Slab Design
� Negative Moments at Continuous Ends in Short Direction:
� 8.42 ft-kip/ft
� 8.91 ft-kip/ft
� 7.72 ft-kip/ft
� 6.54 ft-kip/ft
� Using trial and success method:
� For 8.91 ft-kip/ft: As = 0.52 in2
� Using #4 bars, spacing = 4.5″ c/c
� As all above moments are almost same, we will use #4 @ 4.5″ c/c
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
94
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
� Slab Design
� Negative Moments at Continuous Ends in Long Direction:
� 5.52 ft-kip/ft
� 7.80 ft-kip/ft
� 3.24 ft-kip/ft
� 5.14 ft-kip/ft
� Reinforcement:
� 7. 80 ft-kip/ft is almost equal to 8.91 ft-kip/ft:
Therefore using #4 bars @ 4.5″ c/c
� 5.14 ft-kip/ft is almost equal to 5.37 ft-kip/ft:
Therefore using #4 bars @ 7″ c/c
Designing for 7.80 ft-kip/ft
Designing for 5.14 ft-kip/ft
48
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Slab Reinforcement Details
95
A
BBB
C
C
A
C CB
A
A
BA
C
C
A
A B
A
A= #4 @ 12″B = #4 @ 7″C = #4 @ 4.5″
4 spans @ 25′-0″
3 spans @ 20′-0″
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
NOTE: White: Longer Direction Moments, Yellow: Short er Direction Moments
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
96
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
� Load Transfer from Slab to the Beam
� Review of Load transfer to Beam from One-Way Slabs
• In case of one-way slab system the entire slab load is transferred in short direction.
• Load transfer in short direction = (Wu × l / 2 × 1) + (Wu × l / 2 × 1)
• Load transfer in long direction = Wu × l / 2 × 0
l/2
l/2
l/2 l/2
49
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
97
� Load transfer from Slab to Beam
� Load Transfer to Beam from Two-Way Slab
• In case of two way slab system, entire slab load is NOT transferred in shorter direction.
• Load transfer in shorter direction = (Wu × l / 2 × Wa ) + (Wu × l / 2 × Wa )
Longer Direction
4 spans @ 25′-0″
3 spans @ 20′-0″
Shorter D
irection
Panel I Panel I
Panel I Panel I
Panel II Panel II
Panel III Panel III
Panel III Panel III
Panel IV Panel IV
This value will NOT be 1 in this case, It is specified by ACI Table• Load transfer in longer direction = (Wu × l / 2 × Wb ) + (Wu × l / 2 × Wb )
Wb = 1 - Wa
ACI Table for W a values
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
98
� Load transfer from Slab to Beam
� Load Transfer to Beam from Two-Way Slab
4 spans @ 25′-0″
3 spans @ 20′-0″
Panel I Panel I
Panel I Panel I
Panel II Panel II
Panel III Panel III
Panel III Panel III
Panel IV Panel IV
Load Transfer from Slab to Beam B1
• Load is transferred to B1 from Panel-I and Panel-II in
short direction
= Wu × l / 2 × Wa,Panel-I + Wu × l / 2 × Wa,Panel-I I
= 0.336 × 20/2 × 0.71 + 0.336 × 20/2 × 0.83
= 5.17 k/ft
Shorter D
irection
20′
Wu = 0.336 ksfShorter D
irection
20′
Wu = 0.336 ksf
• Wu = 0.336 ksf
• Wa,Panel-I = 0.71
• Wa,Panel-II = 0.83
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
50
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
99
� Load transfer from Slab to Beam
� Load Transfer to Beam from Two-Way Slab
4 spans @ 25′-0″
3 spans @ 20′-0″
Panel I Panel I
Panel I Panel I
Panel II Panel II
Panel III Panel III
Panel III Panel III
Panel IV Panel IV
Load Transfer from Slab to Beam B2
• Load is transferred to B2 from Panel-I and Panel-III in
long direction
= Wu × l / 2 × Wb,Panel-I + Wu × l / 2 × Wb,Panel-I II
= 0.336 × 25/2 × (1 - 0.71) + 0.336 × 25/2 ×
(1 - 0.55)
= 3.11 k/ft
Shorter D
irection
20′
Wu = 0.336 ksf
Shorter D
irection
20′
Wu = 0.336 ksf
• Wu = 0.336 ksf
• Wb,Panel-I = (1 – Wa,Panel-I) = 1 - 0.71 = 0.29
• Wb,Panel-III = (1 – Wa,Panel-III) = 1 - 0.55 = 0.45
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Example 2
� Load On Beams from coefficient tables
100
Table: Load on beam in Panel I, usingCoefficients
(wu = 0.336 ksf)
BeamLength
(ft)
Width (bs) of slab panel
supported by beam
Wa Wb
Load due to slab, Wwubs
(k/ft)
B1 25 10 0.71 - 2.39B2 25 10 0.71 - 2.39B3 20 12.5 - 0.29 1.22B4 20 12.5 - 0.29 1.22
Panel I
4 spans @ 25′-0″
3 spans @ 20′-0″
B1
B1
B2
B2
B3 B3 B3 B4B4
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
51
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Table: Load on beam in Panel I, usingCoefficients
(wu = 0.336 ksf)
BeamLength
(ft)
Width (bs) of slab panel
supported by beam
Wa Wb
Load due to slab, Wwubs
(k/ft)
B1 25 10 0.71 - 2.39B2 25 10 0.71 - 2.39B3 20 12.5 - 0.29 1.22B4 20 12.5 - 0.29 1.22
� Moment Coefficient Method: Example 2
� Load On Beams from coefficient tables
B1
B1
B2
B2
B3 B3 B3 B4B4
4 spans @ 25′-0″
3 spans @ 20′-0″
Panel I
101
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Panel I
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Example 2
� Load On Beams from coefficient tables
102
4 spans @ 25′-0″
3 spans @ 20′-0″
B1
B1
B2
B2
B3 B3 B3 B4B4
Table: Load on beam in Panel II, usingCoefficients
(wu = 0.336 ksf)
BeamLength
(ft)
Width (bs) of slab panel
supported by beam
Wa Wb
Load due to slab, Wwubs
(k/ft)
B1 25 10 0.83 - 2.78B3 20 12.5 - 0.17 0.714B4 20 12.5 - 0.17 0.714
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Panel II
52
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Table: Load on beam in Panel II, usingCoefficients
(wu = 0.336 ksf)
BeamLength
(ft)
Width (bs) of slab panel
supported by beam
Wa Wb
Load due to slab, Wwubs
(k/ft)
B1 25 10 0.83 - 2.78B3 20 12.5 - 0.17 0.714B4 20 12.5 - 0.17 0.714
� Moment Coefficient Method: Example 2
� Load On Beams from coefficient tables
B1
B1
B2
B2
B3 B3 B3 B4B4
Panel II
4 spans @ 25′-0″
3 spans @ 20′-0″
103
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Panel II
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Example 2
� Load On Beams from coefficient tables
104
4 spans @ 25′-0″
3 spans @ 20′-0″
B1
B1
B2
B2
B3 B3 B3 B4B4
Table: Load on beam in Panel III, usingCoefficients
(wu = 0.336 ksf)
BeamLength
(ft)
Width (bs) of slab panel
supported by beam
Wa Wb
Load due to slab, Wwubs
(k/ft)
B1 25 10 0.55 - 1.84B2 25 10 0.55 - 1.84B3 20 12.5 - 0.45 1.89
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Panel III
53
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Table: Load on beam in Panel III, usingCoefficients
(wu = 0.336 ksf)
BeamLength
(ft)
Width (bs) of slab panel
supported by beam
Wa Wb
Load due to slab, Wwubs
(k/ft)
B1 25 10 0.55 - 1.84B2 25 10 0.55 - 1.84B3 20 12.5 - 0.45 1.89
� Moment Coefficient Method: Example 2
� Load On Beams from coefficient tables
B1
B1
B2
B2
B3 B3 B3 B4B4
Panel III
4 spans @ 25′-0″
3 spans @ 20′-0″
105
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Panel III
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Example 2
� Load On Beams from coefficient tables
106
4 spans @ 25′-0″
3 spans @ 20′-0″
B1
B1
B2
B2
B3 B3 B3 B4B4
Table: Load on beam in Panel IV, usingCoefficients
(wu = 0.336 ksf)
BeamLength
(ft)
Width (bs) of slab panel
supported by beam
Wa Wb
Load due to slab, Wwubs
(k/ft)
B1 25 10 0.71 - 2.39B3 20 12.5 - 0.29 1.22
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Panel IV
54
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Table: Load on beam in Panel IV, usingCoefficients
(wu = 0.336 ksf)
BeamLength
(ft)
Width (bs) of slab panel
supported by beam
Wa Wb
Load due to slab, Wwubs
(k/ft)
B1 25 10 0.71 - 2.39B3 20 12.5 - 0.29 1.22
� Moment Coefficient Method: Example 2
� Load On Beams from coefficient tables
B1
B1
B2
B2
B3 B3 B3 B4B4
Panel IV
4 spans @ 25′-0″
3 spans @ 20′-0″
107
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Panel IV
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Example 2
� Load On Beams
108
2.39 k/ft
1.22 k/ft
2.39 k/ft
1.22 k/ft
2.77 k/ft
2.77 k/ft
0.71 k/ft 0.71 k/ft
1.84 k/ft
1.89 k/ft
1.84 k/ft
1.89 k/ft
2.39 k/ft
1.22 k/ft
2.39 k/ft
1.22 k/ft
4 spans @ 25′-0″
3 spans @ 20′-0″
B1
B1
B2
B2
B3 B3 B3 B4B4
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
55
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Example 2
� Load On Beams
109
5.16 k/ft
1.22 k/ft
2.39 k/ft
3.11 k/ft
5.16 k/ft
0.71 k/ft 1.93 k/ft
4.23 k/ft
1.84 k/ft
3.11 k/ft
4.23 k/ft
1.93 k/ft
4 spans @ 25′-0″
3 spans @ 20′-0″
B1
B1
B2
B2
B3 B3 B3 B4B4
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Example 2
� Load On Beams
110
Self weight of beam
= 1.2 × (14 ×
13/144) × 0.15
= 0.23 kip/ft
Adding this with the
calculated loads on
beams:
14″
20″
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
5.16 k/ft
1.22 k/ft
2.39 k/ft
3.11 k/ft
5.16 k/ft
0.71 k/ft 1.93 k/ft
4.23 k/ft
1.84 k/ft
3.11 k/ft
4.23 k/ft
1.93 k/ft
4 spans @ 25′-0″
3 spans @ 20′-0″
B1
B1
B2
B2
B3 B3 B3 B4B4
56
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Example 2
� Load On Beams (including self-weight)
111
1.45 k/ft
2.62 k/ft
5.39 k/ft
0.94 k/ft
3.34 k/ft
2.07 k/ft
2.16 k/ft
4.46 k/ft
4 spans @ 25′-0″
3 spans @ 20′-0″
B1
B1
B2
B2
B3 B3 B3 B4B4
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
112
lnln ln
Simplesupport
Integral withsupport
wu
Spandrelsupport Negative
Moment
x wuln2
1/24 1/10* 1/11 1/11 1/10* 0
*1/9 (2 spans)
* 1/11(on both faces of other interior supports)
Columnsupport 1/16
PositiveMomentx
1/14 1/16 1/11
wuln2
Note: For simply supported slab, M = wul2/8, where l = span length (ACI 8.9).
* 1/12 (for all spans with ln < 10 ft)
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
57
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis of Beams
� Interior Beam B1
113
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis of Beams
� Exterior Beam B2
114
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
58
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis of Beams
� Interior Beam B3
115
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Analysis of Beams
� Exterior Beam B4
116
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
1.45 k/ft
59
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
117
Pictures of a Multi-Storey
Commercial Building
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
118
Pictures of a Multi-Storey
Commercial Building
60
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Different Stages of Building Construction
119
Phases of Construction
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Home Work
� Design the given slab system
120
Panel I Panel I
Panel I Panel I
Panel II Panel II
Panel III Panel III
Panel III Panel III
Panel IV Panel IV
4 spans @ 25′-0″
3 spans @ 20′-0″
Slab thickness = 6″
SDL = 40 psf
LL = 60 psf
fc′ =3 ksi
fy = 40 ksi
Practice Examples
61
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� Moment Coefficient Method: Home Work
� Design the given slab system
121
Panel I Panel I
Panel I Panel I
Panel II Panel II
Panel III Panel III
Panel III Panel III
Panel IV Panel IV
4 spans @ 20′-0″3 spans @
15′-0″
Slab thickness = 6″
SDL = 40 psf
LL = 60 psf
fc′ =3 ksi
fy = 40 ksi
Practice Examples
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
� CRSI Design Handbook
� ACI 318
� Design of Concrete Structures 13th Ed. by Nilson, Darwin and
Dolan.
122
References
62
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
The End
123
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
124
63
Prof. Dr. Qaisar Ali Reinforced Concrete Design – II
Department of Civil Engineering, University of Engineering and Technology Peshawar
125
� Analysis Results (All values are in ft-kip)
Design Example 2(100′ × 60′, 3-Storey Commercial Building)
8.42
4 spans @ 25′-0″3 spans @
20′-0″
5.375.523.57
8.91
8.91
3.244.51
2.82
6.54
7.80 7.804.783.38
7.72
7.72
5.145.144.31
2.880.94
1.19
1.79 1.60 Mneg at Non-
Continuous End =
1/3 of Mpos
NOTE: White: Longer Direction Moments, Yellow: Short er Direction Moments