lateral earth pres
TRANSCRIPT
-
8/10/2019 Lateral Earth Pres
1/36
- 1 -L iterature Review
1
CHAPTER- 2
Lateral Earth Pressures1. Introduction
Lateral earth pressure is the pressure that is exerted by a soil mass on a retaining
structure or a wall. The problem associated with lateral earth pressures and retaining wall
stability is one of the most common in the civil engineering field, and a segment of soil
mechanics that has been receiving widespread attention from engineers for a long time.
Design of structures such as retaining walls, sheet piling, and braced sheeting of pits and
trenches, bulkheads, bridge abutments, basement or pit walls etc., requires a quantitative
estimate of lateral earth pressure. In this chapter we will learn how to determine the
magnitude and direction of lateral earth pressures for which a structure must be designed. In
last part of the chapter the intro to design of a gravity retaining wall will be taken up. By
definition a retaining wall is a structure used for maintaining ground surface at different
elevations on its either side. The soil supported by the retaining wall is called backfill.
In this chapter we will be concentrating on lateral earth pressures experienced by a retraining
wall. To understand the concept behind these earth pressures lets examine the sequence of
retaining wall construction for a road construction project in a hilly area. The sequence is
shown below:
Ideally a vertical cut should be provided to economize on the cost of excavation but soils are
seldom stable at vertical slope and tend to slough down to attain equilibrium. Generally they tend to
stabilize at a gentle slope. The stable slope angle depends on the soil properties and the height of
slope. A gentle cut may not be feasible due to high cost of excavation or due to existence of some
structures which may be pulled down. Under such circumstances soil is cut at a steep slope and is
supported by constructing a retaining wall. A reasonable slope is cut during dry part of the year (step2)
and retaining wall is constructed. The space behind the wall is later filled with soil and proper drainage
is provided to protect it from storm water erosion. The retaining wall supports the backfill and its
thickness at every horizon must be adequate to resist lateral earth pressure so that the wall neither tilts
excessively nor is displaced horizontally away from the soil mass it is supporting. The approach to
design of these walls is as under:-
a. Determine different forces which contribute to wall stabilityb. Determine forces which are trying to destabilize the wall
-
8/10/2019 Lateral Earth Pres
2/36
- 2 -L iterature Review
2
c. Compare these forces to ensure that the structure is safe.
Two basic types of soil pressures are evaluated in this chapter, active and passive. If the
soil mass pushes against a retaining wall such as to push it away, the soil becomes the
actuating element and the pressure resulting thereby is known as active pressure. On the
other hand, if the wall pushes against the soil, the resulting pressure is known as passive
pressure. In this case the actuating element is the retaining wall itself.
Analysis of a wide range of earth-retaining structures is primarily based on either ofthe two theories formulated by such persons as Coulomb in 1776 and Rankine in 1857.Furthermore, although some research data and experience indicate that assumptions relatedto pressure distributions on retaining walls, or on the failure surface of backfills, are not quitethose depicted by these early investigators, substantial evidence exists that the analysis anddesign efforts based on their theories give acceptable results for most cases of cohesion-lesstype backfills. The results are significantly less dependable for the more cohesive soils.2. Common Uses of Retaining Walls
-
8/10/2019 Lateral Earth Pres
3/36
- 3 -L iterature Review
3
3. Factors Affecting Lateral Earth Pressure
The main factors that affect lateral earth pressure include wall movement, wall friction,
water in the backfill, compaction of the backfill, slope of backfill, seasonal variation and the
nature of the backfill, the interaction between the soil and the retaining structure at the
interface and the imposed loading (e.g., height of backfill, surcharge loads). These are
discussed briefly in the following sections.
a. Wall Moment.Under service conditions a rigid retaining wall possibly can rotate
about its base, its top, its middle or another point: it can translate or there can be
a combination of these modes. It is also possible that wall may not yield at all.
Terzaghi (1934) is believed to be the first to conclude from his large scale earth
pressure tests that the lateral earth pressure distribution behind retaining wall is
associated, with the type and the magnitude of wall movement. Earth pressure
distribution behind a wall rotating about its base is considered as linear (Terzaghi
1934).
b. Wall Friction
A relative movement between a retaining wall and its back fill develops shear
forces between the face of the wall and the backfill. These are termed wall
friction (Lambe and Whitman 1969). The wall friction depends on roughness of
the wall, amount and direction of the wall movements, soil properties of the
backfill and inclination of ground surface behind the wall. The wall friction is also
influenced by the settlement of the structure and the backfill soil (Grandil 1987).
The maximum value of wall friction may not occur simultaneously with the
maximum shearing resistance and the value of wall friction may vary across the
wall (Bowles 1982). Wall friction angle () between 1/3 to 2/3 is a good
approximation for computing lateral earth pressure using Coulombs theory. The
wall friction affects the magnitude and the direction of earth pressure.
c. Water in the Backfill
The presence of water in the wall backfill without compensating water in front
substantially increases total pressure because the coefficient K for water is unity.
The distribution of pressure on a retaining wall due to water is hydrostatic and the
resultant water force acts at one third the water height from wall base. The
effective earth force acts above one third of wall height due to the presence of
water in the backfill. The combined force due to soil and water acts below the
one-third of wall height.
d. Seasonal Variation
Seasonal Variations affect the magnitude and the distribution of earth pressure
mainly because of changes in temperature, freezing of backfill and heavy rainfall.
Field test results show about 30% variation of earth pressure due to seasonal
variations (Terzaghi and peck 1967). There is variation in earth pressure in
summer and winter (Duncan et al, 1990).The warm front face of a wall in the
summer expands relative to the back face and causes the wall to deflect back
against the fill. The result is an increase in earth pressure. In the winter the
-
8/10/2019 Lateral Earth Pres
4/36
- 4 -L iterature Review
4
pressure is reversed, the earth pressure also increases in winter due to
expansion of water in the backfill voids due to freezing.
e. Nature of Backfill Soil
The engineering properties of the backfill soil such as(c, , )cohesion, internal
friction angle and unit weight have substantial effect on the magnitude of lateral
earth pressure on retaining structures. Higher the cohesion and internal
friction angle, the lower will be the pressure. On the other hand, higher the
Unit weights, higher will the pressure on the wall.
f. Slope of Backfill
The backfill slope changes the direction of lateral earth pressure. Thus, the
magnitude of horizontal earth force acting on the wall changes with the increase
or decrease in slope.
4. Lateral Earth Pressures at Rest, Active and Passive States
Let there be a mass of soil of density at
depth z, vertical and horizontal stresses
can be given as, v= *z ,
h= k* *z = k* v ,where k= h/ v
k = Coefficient of earth pressure.
Statically value of k is indeterminate. The notation of kFor certain special cases are given below:-
ko= Coefficient of earth pressure at rest which corresponds to zero strain.
ka= Coefficient of active earth pressure which corresponds to shear
failure by expansion of soil.
Kp= Coefficient of passive earth pressure which corresponds to shear
failure by compression of soil.
Figure 13.2 above shows some of the forces acting on a typical gravity retaining wall.
Frictional forces that may be developed on the front and back faces of the retaining wall are
not shown. The lateral force induced by the backfill pushes against the wall with a resultant
pressure Pa. In turn, the retaining wall resists the lateral force of the backfill, thereby
preventing its movement. In this case, it is apparent that the soil becomes the actuating force.
The thrust Pa is the resultant of the active pressure, or simply the active thrust. The
resistance to the active thrust is provided by the frictional force at the bottom of the
wall and by the soil in front of the wall . For the sake of illustration, assume that the wall was
pushed to the left by the active thrust Pa.In this case the soil in front of the wall at its toe
provides a passive resistance to movement. This resistance is known as the passive earth
pressure, with the resultant of this pressure denoted by Pp. The magnitude of the lateral
force varies considerably as the wall undergoes lateral movement resulting in either tilting or
lateral translation, or both. Terzaghi focused on this phenomenon during his classic
experiments in 1929 -1934.
The concept of active and passive earth pressure can be best illustrated by reviewing the
experiments conducted at MIT. In these experiments a glass box was used. A retaining wall
was placed as shown below and steel bars, 6 inch long and inch diameter, were placed on
1
3 244
1z
-
8/10/2019 Lateral Earth Pres
5/36
- 5 -L iterature Review
5
either side of the wall up to its top.
Since the top level of bars was the same initially the wall stood vertically i.e., every thing was in
equilibrium, forces from left side of wall were balancing forces from right hand side. Later
some bars from the left side were removed. Since there was no force to balance out forces
from the right hand side, the wall tilted slightly to the left resulting in a decrease in pressure on
the wall. As more rods were removed from the left the pressure on the wall reduced further
and it swayed away from the rods on the right side. Finally as the depth of rod removal on left
side reached a certain magnitude the bars on the right moved one past the other and a zone of
shear failure was formed. A clear cut surface of shear failure could be seen. The wall
experienced the minimum horizontal pressure at this instance. As more rods were removed,
there was no further reduction in pressure on the wall. A similar phenomenon occurs in soils.
Letsconsider soil strata under geostatic state of stress. Initially on any element the horizontal
stresses on left and right side of the element are the same to keep it in equilibrium. Letspass
an imaginary retaining wall of zero volume through this soil. Now we start removing soil from
left of this imaginary wall just like the example above. As above the pressure on the wall will
decrease as the wall tilts to the left due to removal of support. As more soil is removed the tilt
increases and finally the soil behind the wall fails in shear and a zone of shear failure is formed
right behind the wall. There is no further reduction in the lateral pressure experienced by the
wall. This minimum lateral earth pressure experienced by the wall as it moves away from the
soil mass it is supporting is called ACTIVE earth pressure. By definition active earth
pressure is the minimum lateral earth pressure experienced by the wall as
it moves away from the soil mass to which it is supporting.
-
8/10/2019 Lateral Earth Pres
6/36
- 6 -L iterature Review
6
Figure 12.2 above depicts the relationship betweenthe earth pressure and the walI movement.
Porepresents the magnitude of pressure when no movement of the retaining wall takes
place; it is commonly referred to as earth pressure at rest.As the wall moves toward the
backfill, the pressure increases, reaching a maximum value of Ppat point C. On the other
hand, if the wall moves away from the backfill, the force on the wall decreases, reaching a
minimum value of Paat point B.
Figures 12.3a and 12.3b show the active case, where the wall moves away from the backfill,
together with the corresponding force polygon. Similarly, the case of passive resistance,
together with its force polygon, is shown in Figs. 12.3c and 12.3d.
-
8/10/2019 Lateral Earth Pres
7/36
- 7 -L iterature Review
7
5. Active and Passive Earth Pressures for (c- ) Soils with Horizontal Backfill
a. Active Earth Pressure(c- , soils). Letsconsider a case for wall with horizontal
backfill of c- , soilsas above. Here we assume that backfill is pushing the wall
away from fill. So as we start excavation, the wall yields and lateral stresses 3
will keep decreasing (shown in dotted). Finally the lateral pressure reduce to a
level that the Mohrs circle touches strength envelope. This is limiting conditionsat which pressure can not reduce any further or its Mohrs circle cross strength
envelope, which is impossible. The stresses so induced are plotted on Mohrs
Circle and followed the well known Mohrs/Coulumbs shear strength equation
(=C+ ntan )
-
8/10/2019 Lateral Earth Pres
8/36
- 8 -L iterature Review
8
From small triangle, A = C/tan , B = (1+A)/2 and R = (1- A)/2 ------------ (i)
But from fig R = (A+B) sin --------------------------------------------------------------(ii)
Comparing eqn (i) & (ii) we get (1- A)/2 = (A+B) sin --------------------------(iii)By putting values of A & B in eqn (iii) we get,
(1- A)/2 = ((C/tan + (1+A)/2)* sin(1- A)/2 = C/tan *sin+1sin/2+ Asin/2(1- A) = 2C cos + 1sin+ AsinA(1+ sin) = 1(1- sin) - 2C cos A= 1(1- sin)/ (1+ sin) - 2C cos /(1+ sin)PA = 1*ka- 2C kawhere, 1= *z and ka= (1- sin)/ (1+ sin)or Ka= tan
2(45-/2)b. Passive Earth Pressure(c- , soils). Letsconsider a case for wall with horizontal
backfill of c- , soils. Here we assume that backfill is being pushed by the walltowards fill. Therefore lateral earth pressure 3 will keep increasing due topushing of backfill by wall with passive pressure p and thus failure occur due tocompression of soil. The stresses so induced are plotted on Mohrs Circle andfollowed the well known Mohrs/Coulumbs shear strength equation
( =C+ ntan )
From small triangle, A = C/tan , B = (1+p)/2 and R = (p- 1)/2 ------------ (i)But from fig R = (A+B) sin --------------------------------------------------------------(ii)Comparing eqn (i) & (ii) we get (p- 1)/2 = (A+B) sin --------------------------(iii)By putting values of A & B in eqn (iii) we get,(p- 1)/2 = ((C/tan + (1+p)/2)* sin(p- 1)/2 = C/tan * sin+ 1sin/2+ psin/2(p- 1)= 2C cos + 1sin+ psinp(1- sin) = 1(1+ sin) + 2C cos p= 1(1+ sin)/ (1- sin) +2C cos /(1- sin)Pp = 1*kp+ 2C kpwhere, 1= *z and kp= (1+ sin)/ (1- sin)or Kp= tan
2(45+/2)
Alternately
CA
(1+
A)/2
R=(1- A)/2
=c+ ntan
v
h
h
BA
n1
CA
(1+p)/2C/tan
R=(p- 1)/2
=c+ ntan
3 p
BA
-
8/10/2019 Lateral Earth Pres
9/36
- 9 -L iterature Review
9
Lets starts with simple case of horizontal ground level and zero wall friction.
Consider an element located at depth Z initially as wall moves awaydecreases and finally the soil fails. The state of stress for soil mass as it moves away from thebackfill from static equilibrium to plastic equilibrium is shown below:
For the circle touching the strength envelope, h is minimum and is equal to Pa.
From ABC
Here
Therefore
1, (Active earth pressure)
& -------2, (Passive earth pressure)
Equation no one is called Bells Equation for active earth pressure for
cohesive soils.
From equation- 1 at ground surface z = 0
at the base of wall
Stress diagram is shown below:
vh K 0 h
2
2
31
31
CotC
Sin
hav P 31 &
22
avav PPCotCSin
Sin
CosC
Sin
SinP
CosCSinSinP
PSinPSinCosC
PSinPSinSin
CosSinC
a
va
avav
avav
1
2
1
1
211
2
2
aava KCKP 2
pvpp KCKP 2
a
aaa
KC
KCZKP
2
02
aaa KCHKP 2
Zv
h = K v (C - )
A C
O
B
C
= K0h v
2
av P
= Pa = Ka h v
v
C/tan
aKC2A
2Z0 Z0
+
H
60.6kn/m
-
-
8/10/2019 Lateral Earth Pres
10/36
- 10 -L iterature Review
10
At certain depth zo, Pa= 0
As indicated in the figure up to a depth the soil is under tension. Since soil
cannot sustain tension a tension crack is generally formed at top to a depth of . If the
crack is filled with water then the pressure of this water on wall must be given due
consideration.
From fig it is clear that up to a depth of 2Z0the net pressure on the wall is zero i.e. a cohesive
soil can stand without any lateral support up to a depth,
Therefore, the critical Hcan unsupported vertical cut in clay is given as: 2Z0= Hc
For computation of lateral stress in case of cohesive soils, theve pressure are neglected &
whole +ve pressure below depth z is taken into consideration.
6. Unsupported cuts in (c -) soil
Unsupported excavations would theoretically be possible in (c-) soils if the lateral
pressure (3for the active case) would not exceed the strength of the soil. The general
expression forthe horizontal stress for the active is given as:
(d)
At ground surface, h = 0. Thus,
3= -2cKa (Tension)
This implies the formation of a crack as depicted in Fig. 12.15a given below. The
corresponding pressure distribution based on Eq. (d) is shown in Fig. 12.15 b.
The theoretical depth of the crack htcan be determined by recognizing that, at the
bottom of the crack, 3 = 0 or Pa=0. Thus, from Eq. (d),
0 = htKa-2cka or ht = 2c /ka (12-17)
The theoretical maximum depth Hc of unsupported excavation may be calculated as the
02 aa KCZK
a
a
a
KCZ
K
KCZ
2
02
0
0
aK
CZ
20
aK
C
2
aK
CZ
42 0
a
cK
CH
4
aaa KCHKP 2
-
8/10/2019 Lateral Earth Pres
11/36
- 11 -L iterature Review
11
point where the tension forces equal the cohesive strength. Hence, from
Figure 12.15 b, Hc= 2 ht.
Though the above equation provides a theoretical depth to which an excavation may be
made without lateral support, it should be used cautiously. Surface moisture that may enter the
crack may induce hydrostatic stresses or may decrease the shear strength of the soil. Hence,
the unsupported excavation to such depths should be for short duration at best. Even then,judgment reflecting on the potential consequences from unsupported excavation is indeed
warranted.
In general it is advisable to minimize the use of cohesive backfill when ever possible.
With changes in moisture content the pressure induced by highly cohesive soils may change
significantly. If the clay dries out and shrinks then the pressure on the wall will reduce. On the
other hand a dry soil may take up moisture and swell thus exerting tremendous pressure on
the wall.
a. At Rest Earth Pressure. Let us consider the mass of soil shown in Figure 2.1. The
mass of soil bounded by a frictionless wall AB that extends to infinite depth. An element
located at a depth z will be subjected to a vertical pressure vand horizontal pressure h. For
the case considered here, vand hare effective and total pressures and there are no shear
stresses on the vertical and horizontal planes.
If the wallAB is static-that is, if it does not move either to the right to or the left of its initialposition-the soil mass will be in a state of elastic equilibrium. The ratio of the horizontal stressto the vertical stress is the coefficient of earth pressure at rest, Ko, or Ko= h/v-------------(2.1)Since v= *z, so, h= Ko(*z) -----------------------------------------(2.2)
For granular soils, the coefficient of earth pressure at rest can be represented by the
empirical relation (Jaky, 1944), Ko= 1- Sin ------ (2.3)Brooker and Ireland (1965) recommended the following equation for Ko in normallyconsolidated clays, Ko= 0.95- Sin -------------- (2.4)
Also(1) For -soils
(a) For horizontal backfill, ko= (1- sin )(b) For sloping backfill, ko= (1- sin )(1+ sin)=ko(1+ sin)
(2) For c-soils (Brooker & Ireland)(a) For 0
-
8/10/2019 Lateral Earth Pres
12/36
- 12 -L iterature Review
12
b. Earth Pressure at Rest for Partially Submerged Soil
Figure 2.3a shows a wall of height H. The ground water table is located at a depth H1below the ground surface. For z H1 the lateral earth pressure at rest can be given ash= Ko (*z). The variation of h with depth is shown by the triangle ACE in Figure-2.3 a.However, for z H1 (Below GWT)
The pressure on the wall is found from the effective stress and pore water pressurecomponents in the following manner:
Effective vertical pressure = /v= H1+ '(z - H1) ------------------- (2.9)
where ' = sat- w= the effective unit weight of soilSo, the effective lateral pressure at rest is/h= Ko
/h= Ko {(H1+ '(z - H1)} -------------------------------------(2.10)
The variation of /hwith depth is shown by CEGB in Figure 2.3 a.Again, the lateral pressure due to pore water is, u = w(z-H1)--- (2.11)
The variation of u with depth is shown in fig 2.3 bHence, the total lateral earth pressure at any depth z H1is equal toh=
/h+u = Ko {(H1+ '(z - H1)}+ w(z - H1) -----------------------(2.12)
The force per unit width of the wall can be found from the sum of areas of the pressure
diagrams in Figures 9.3a and b and is equal to
Po= {(1/2*KoH21)+( KoH1H2)+ ( Ko
/ + w)H22} ----------------(2.13)
(Area ACE) (Area CEFB) (Area EFG&IJK)c. General Comments on Earth Pressure Coefficient at Rest
While designing a wall that may be subjected to lateral earth pressure at rest, care must
be taken in evaluating the value of Ko. Sherif, Fang, Sherif (1984), based on their laboratory
tests, have shown that Jaky's eqn for Ko eqn (2.3), gives good results when the backfill is
H2
KoH1
(a)
GWT
GF
E
B
A
z
Unit weight of soil =
H
Fig-2.3
C
Ko(H1+ /H2)
KoH1
H1
Saturated Unit
weight of soil = sat
KJ
I
wH2
(b)
Ko(H1+/H2)+wH2
H2
H1
=
60.
-
8/10/2019 Lateral Earth Pres
13/36
- 13 -L iterature Review
13
loose. However, for a dense sand backfill, eqn. (2.3) grossly underestimates lateral earth
pressure at rest. This is due to the process of compacting backfill. For that reason, they have
recommended the following design relationship.
Ko= (1-sin )+( d/ d(min)-1)*5.5 ------------------------------------(2.14)
where d= actual compacted dry unit weight of the sand behind the wall
d(min)= dry unit weight of the sand in the loosest stateExample:
Data: As shown on fig
Req: Calculate fol:
ko, ka, kp
PO,Pa, Pp
location of pressures.
Solution:
a. Values of k
ko= 1- sin = 1- sin 35o= 0.43
ka= tan2(45-/2) = tan2(45-35o/2) = 0.27
kp= tan2(45+/2)= tan2(45+35o/2)= 3.69
b. Po= * Ko H2= *0.43*125*30
2= 24187 lb/ft
2
Loc of Po= H/3=30/3= 10 ft from base of wall.
c. Pa= * Ka H2= *0.27*125*30
2= 15187 lb/ft
2
Loc of Pa= H/3=30/3= 10 ft from base of wall.
d. Pp= * Kp (H1)2= *3.69*120*10
2= 22140 lb/ft
2
Loc of Pp= H1/3=10/3= 3.33 ft from base of wall.
Example:
Data: As shown on fig
Req: Calculate active force per unit of wall
for Rankins state. Also find location of resultant.
Solution
1. Calculation of Ka
a. For top layer Ka1
Ka1= 1-sin30o/1+sin30o= 0.33
b. For Bottom layer Ka2
Ka2= 1-sin35o/1+sin35
o= 0.27
H
PO
KoH
H
Pa
KaH
Pp
H1
KpH1
= 120 pcf= 35o
H1=10 ft
= 125 pcf= 35o
H = 30 ft
3m
3m= 16kn/m= 30oc=0
= 18kn/m= 35oc=0
3
-
8/10/2019 Lateral Earth Pres
14/36
- 14 -L iterature Review
14
2. Calculation of Pa
a. For top layer Pa1
at z=0, v=0 but at z=3m, v1= 16*3=48kn/m2
So a1=Ka1*v1= 16*3* 0.33= 16 kn/m2
and Pa1= *3*16= 24 kn/m2
b. For Bottom layer Pa2
at z=3, v=3*16 =48kn/m2 (just below top layer)
and a2=Ka2* = 0.27*48= 13 kn/m2
at z=6m, /v2= v1+ /v2= 48+3*(18-9.81)=72.6kn/m
2
/a2= Ka2* /v2= 0.27*72.6= 19.7 kn/m
2
c. Pressure due to water-uAt z=0, u=0
At z=3m, u=0At z=6m, u= 3*9.81=29.43kn/m2
d. Total active pressure,
Pa=(*16*3)+13*3+ 19.7-13(3*1/2)+*29.43*3
= 24+39+10+44.14 =117.15 kn/m2
e. Location of pressure By taking moment at the base of wall.
117.15*z= 24(3+3/3)+39*3/2+10*3/3+44.15*3/3=208.15
z= 208.15/117.15= 1.78 m
Example:
An unsupported cut as shown in fig with the given
soil properties, find
a. Stress at top and bottom of cutb. Max depth of potential tension crackc. Max un-sported excavation.
Solution As we know that major & minor principal stresses are decided on the basis of their
magnitudes. Here, a is greater in magnitude, so considering it as major principal stress,hence, stresses would be calculated basing ona.
a. Stresses at Top and BottomStresses at point A (Top)- As h = 0, so a= h Ka- 2ckaa= -2cka= (2*25) tan (45-5
0) = -41.95 kn/m
2
Stresses at point B (Bottom)- As h = 4.2 m,
a= h Ka- 2cka= 18.2*4.2 tan2(45-50)2*25 tan (45-50) = 11.87 kn/m2
b. Max depth of Potential Tension Crack
ht= 2c /ka = (2*25) /18.2tan2(45-50)= 3.27 mc. Max Un sported ExcavationAs we know that Hc= 2 ht,
so Hc= 2 *3.27 = 6.54 m7. Rankines Theory
Coulombs and Rankine are the best-known theories which are used to compute the
magnitude and direction of forces which act on the retaining wall due to the backfill behind it.
These theories are frequently referred to as the classical earth pressure theories. The theory
proposed by Rankine in 1857 is based on the following assumptions:
Frictional forces between backfill and retaining wall are zero. ( the implication of this
assumption is that shear stresses on the vertical and horizontal planes are zero i.e.,
these planes are principal planes)
The back of the wall is vertical,
The surface of the backfill is horizontal.
19.7kn/m2
3
13kn/m
3
16kn/m
29.43kn/m
3
A
B
= 18.2
kn/m3= 10o
H = 4.2 m
-
8/10/2019 Lateral Earth Pres
15/36
- 15 -L iterature Review
15
The backfill is a homogeneous, isotropic, dry and cohesion-less material.
The failure surface is plane.
The wall yields about the base and satisfies conditions of plastic equilibrium.
The basic concept behind Rankines theory can be depicted by Mohrs circle. Consider the
element shown in Fig.12.3, subjected to the geostatic stresses shown. The value for 1/could
be approximated as the product of the average unit weight times depth, namely, 1/= h. If
the wall were to move to the left, thereby creating a case of active stress, the value for 1/
would become the major principal stress and at failure the minor principal stress h/ is equal
to the active earth pressure. The corresponding Mohr circle for this case is depicted by circle-I
in Fig. 5. On the other hand, if the wall were to push against the backfill i.e., move towards the
backfill, a case of passive pressure would be developed. The vertical stress would then
become the minor principal stress
3/ and the lateral stress would thus become the major
principal stress which at failure is the passive earth pressure. The Mohr circle for this condition
is depicted by circle- 2 in Fig. 5.
The pressures on retaining wall vary linearly with depth, as indicated by Fig. 12.7.
The corresponding resultant pressures, active and passive, can be calculated for a unit length
of retaining wall as
Pa = 0.5 H ka= 0.5 * H2tan
2(45 - /2)
Pp = 0.5 H kp= 0.5 * H2tan 2(45 + /2)
The corresponding slip planes for the active and passive cases are shown in Figure
12.5c and 12.5d. The or ientat ion of these planes can be best being und erstood u sing
the conc ept of po le. For active case point 3represents pole. A line drawn from this point
to the point representing state of stress on failure plane yields the orientation of failure planes
for the active state. It is to be pointed out that once the lateral stresses in this case drop to the
active value, shear failure along an infinite number of planes behind the wall is imminent and at
the instant the soil is said to be in a state of limit equilibrium. Since the state of stress in backfill
is known for either at rest condition or the active condition, retaining walls are designed for the
limit equilibrium conditions and such design is called limit design.
8. Effects of Surcharge loads
Concentrated or uniformly distributed loads, commonly referred to as surcharge loads, acting
on the surface of the backfill, will:
o Increase the lateral pressure against the, retaining wall.
o Move the point of application of the resultant pressure upward.
a. Effect of UDL Surcharge
Figure 12.17 shows uniformly distributed surcharge q (kN/m2) acting on the surface of the
-
8/10/2019 Lateral Earth Pres
16/36
- 16 -L iterature Review
16
backfill. The vertical stress 1on an element within the soil backfill at a depth h is equal to
h + q. Correspondingly, the lateral stress 3for a (c-)soil, is
99.. RRaannkkiinnAAnnaallyyssiissBBaacckkffiillllwwiitthhUUnniiffoorrmmSSuurrcchhaarrggee
If the backfill is horizontal & carries a uniform surcharge q-kn/m2, the vertical stress at
any depth will increase by q. The increase in lateral pressure for active case therefore will be
kaq as shown below:
Example
Find the passive resistance (Pp) of given frictionless
Retaining wall as shown in fig. Also calc the location
of passive resultant.Solution
a. Calculation of K
Kp= 1+sin250/1-sin250= 2.45
2. Calculation of Stresses
a. Passive Resistance/Stresses
at top of layer, z=0, v=q= 12 kn/m2(surcharge)
p= 2.45*12+2*102.45= 60.6 kn/m2
at bottom of layer, z=5m, v=q+h = 12+15*5 =87kn/m2
p= 2.45*87+2*102.45= 244.35 kn/m2
b. Passive Resistance
Pp= 60.6*5+244.3*5*1/2= 303+610.9 = 914 kn/m
c. Location of Resultant. Taking moment of pressure diagram about wall base.
914*z = 303*5/2 + 611*5/3= 757.5+1018.3 = 1775.83 = z=1775.83/914 =1.94m
b. Effect of Point load Surcharge (by Boussinesqs equation)
To determine lateral pressure on wall due to point load
aaa KCHKP 2
z=nH
x=mH
Q
H
q kN/m2
aa KCHK 2
244.3kn/m2
60.6kn/m2
5 m
= 15 kn/m
= 25oc=10 kn/m2
q=12kn/m2
914kn/m
-
8/10/2019 Lateral Earth Pres
17/36
- 17 -L iterature Review
17
Q placed at surface of the backfill as shown in fig.
If the load Q is placed on the plane of section as shown;
We can substitute y=0 and =0.5 in vertical stress distr
equation developed by Boussinesq. This is modified as
x =Q/2(3x2*z/R
5) -------------(A)
where R= (x2+z2)1/2
Substituting x=mH & z=nH in eqn (A), we get
x =3Q/2H2{m
2n/(m
2+n
2)5/2
}-------------- (B)
The horizontal stresses expressed by eqn (B), does not include restraining effect of wall.
Therefore the eqn has been modified as per real time situation as under:-
x =1.77Q/H2{m
2n
2/(m
2+n
2)3} for m> 0.4-------------- (C)
x =0.28Q/H2{n
2/(0.16+n
2)3} for m 0.4-------------- (D)
For concentrated surcharge loads Q such as may be induced by a continuous footing,
railroad tracks, and the like, running parallel to the wall, it is possible, although rather
laborious, to estimate the increased stresses on the wall based on Boussinesqs equation,
consistent with the theory of elasticity for a semi-infinite homogeneous soil mass. However,
graphical methods given below are more expedient for this purpose.
Experimental data indicate that Boussinesqs formula for lateral stress gives acceptable
results where the wall movement is compatible to soil deformations within the backfill. On the
other hand, if the retaining wall is totally rigid such that the soil deformation is greatly restricted
by the rigid boundary, the horizontal stress approaches a value twice that given by
Boussinesqs equation.This effect becomes less noticeable as the distance of Q relative to
the wall increases.
c. Effect of Point load Surcharge (by graphical method)
The line of action of the active thrust induced by the concentrated surcharge loads Qis
commonly based on empirical procedures. Such a procedure gives acceptable results for
cohesion less backfill; it may be illustrated with the aid of Fig 12.19. When the concentrated
surcharge load is located to the left of point C, the active thrust Pa may be determined by
drawing lines EDand FDparallel to lines AGand AC,respectively. The point of application
of Pais one-third the distance FEfrom point F, as indicated in Fig. 12.19a. But when load Q
is located to the right of the failure plane, as indicated in Fig. 12.19b, line EDis parallel to line
AC. The point of application of Pais one-third the distance EAfrom point F, as shown in
Fig. 12.19b. We noted that the line of action of the resultant thrust moves up the wall as the
load Qapproaches the wall. Furthermore, the lateral thrust as well as the overturning effect
decreases as the load Qmoves away from the wall.
-
8/10/2019 Lateral Earth Pres
18/36
- 18 -L iterature Review
18
ExampleFind the lateral force Pa due to backfilland
point load 1.5m away from back face of wall as shown in fig.
Solution (for point load)
Here x=1.5m, H= 5m, z= 0-5m (for n= 0.2,0.4,0.6,0.8,1.0)
Divide H in five equal parts for calc pressure per unit of wall.
m= x/H = 1.5/5=0.3 i.e less than 0.4
Therefore we will use
x =0.28Q/H2{n
2/(0.16+n
2)3} for m 0.4
x =0.28*150/52{0.2
2/(0.16+0.2
2)
3} = 1.68*5= 8.4kn (for n= 0.2)
x =0.28*150/52{0.4
2/(0.16+0.4
2)
3} = 1.68*4.88= 8.2kn (for n= 0.4)
x =0.28*150/52{0.6
2/(0.16+0.6
2)
3} = 1.68*2.56= 4.3kn (for n= 0.6)
x =0.28*150/52{0.8
2/(0.16+0.8
2)
3} = 1.68*1.25= 2.1kn (for n= 0.8)
x =0.28*150/52{1
2/(0.16+1
2)3} = 1.68*0.41= 0.69kn (for n= 1.0)
Now lateral force P due to point load will be
P= (0+8.4)*1+ (8.4+8.2)*1+ (8.2+4.3)*1+ (4.3+2.1)*1 + (2.1+0.69)*1= 23.35kn/m of wall ht2 2 2 2 2
For geostatic stresses ka= tan2(45-/2)= 0.626
At top lateral stresses, h= 2*12.50.626=2*12.5*0.7= 19.75kn/m2
At bottom of wall, h= 18*5*0.626-2*12.5*0.79= 36.6 kn/m2
Pressure on wall= 19.75*5+16.85*52/2= 98.75+210.6= 309.35kn/m of wall ht
For resultant Pressure location taking moments at base of wall
Z= (98.75*5/2)+(210.6*1.67)/309.6=246.87+351.7=598.57/309.6=1.93m from base.
d. Effect of line load Surcharge (by Boussinesqs equation)
To determine lateral pressure on wall due to line load
q placed at surface of the backfill as shown in fig.
If the load q is placed on the plane of section as shown;
Eqn (D) is modified as
x =4q/H {m2n/(m
2+n
2)
2} for m> 0.4-------------- (E)
x =0.203q/H {n/(0.16+n2)2} for m 0.4-------------- (F)
ExampleA line load of 50kn/m is located at a distance of 3m from back
face of retaining wall 4.5m high. Determine lateral force P on wall due to line load.
Solution
Here x=3m, H= 6m, z= 0-6m (for n= 0.25,0.5,0.75,1.0)
Divide H in four equal parts of 1.5 m for calc pressure on wall.
m= x/H = 3/6=0.5 i.e more than 0.4
Therefore we will use
x =4q/ H {m2n/(m
2+n
2)2} for m> 0.4
x =4*50/*6 {0.520.25/(0.52+0.252)2} = 10.61*0.64= 6.8kn (for n= 0.25)
x =4*50/*6 {0.520.5/(0.5
2+0.5
2)2} = 10.61*0.5= 5.3kn (for n= 0.5)
x =4*50/*6 {0.520.75/(0.5
2+0.75
2)2} = 10.61*0.28= 3.0kn (for n= 0.75)
z=nH
x=3m
q= 50kn/m
H=6m
z=nH
x=mH
Q=150Kn
H
=18kn/mc=12.5kn/m2
=150
z=nH
x=mH
q= kn/m
H
-
8/10/2019 Lateral Earth Pres
19/36
- 19 -L iterature Review
19
x =4*50/*6 {0.521.0/(0.5
2+1
2)2} = 10.61*0.16= 1.7kn (for n= 1.0)
Now lateral force P due to point load will be
P= (0+6.8)*1.5+ (6.8+5.3)*1.5+ (5.3+3)*1.5+ (3+1.7)*1.5 = 24kn/m of wall width
2 2 2 2
e. Effect of strip load Surcharge (by Boussinesqs equation)
To determine lateral pressure on wall due to strip load
q/area placed at surface of the backfill as shown in fig.
If the load q is placed at distance m1 from wall back of
of height H with width as m2.The horizontal stress
at depth z on wall due to strip loading is given as
x =q/H(-sin*cos 2), angles & as defined on fig-------------- (G)
for actual soil behavior conditions eqn (G) can be modified as
x =2q/H*{(-sin*cos 2)}, -------------- (H)
The force P per unit width of wall can be obtained by integ eqn (H)For z & H this is given as
P= q/90{H(21)}, where is in deg and given as
1 = tan-1
(m1/H) & 2 = tan-1
((m1+m2)/H)
ExampleA strip loading as shown in fig; m1= 10ft, m2= 5ft
Calculate xat 2/interval of H.
Also determine lateral force P on wall due to strip load.
Solution
Calculation of xby using eqn (H)
x =2q/H*{(-sin*cos 2)}
Calculation of x
z m1 m2 = tan-
(m1+ m2/2)/z = {tan-
(m1+ m2)/z}-{ tan-
(m1)/z} x=2q/z*{(-sin*cos 2)}2 10 5 80.91
3.71
5657lb/ft
4 10 5 72.25
6.9
5225lb/ft
6 10 5 64.36
9.2
4629 lb/ft
8 10 5 57.38
10.60 4000 lb/ft
10 10 5 51.34
11.31
3402lb/ft12 10 5 46.17
11.5
2877 lb/ft
Calculation of PUsing eqn given above as, P= q/90(21) and1 = tan
-1(m1/H) & 2 = tan
-1(m1+m2/H)
1 = tan-1
(m1/H)= tan-1
(10/12)= 39.80
2 = tan-1
((m1+m2)/H))= tan-1
((10+5)/12)= 51.340
Now, P= q/90{H(21)}= 1500/90{12(51.34-39.8)}= 2308 lb/ft of wall width
10. Cohesion less Backfill and Inclined Surface
Let us now consider cohesion less mass with a sloping surface behind a smooth vertical
retaining wall. Assume this condition to be depicted by Fig. 12.8a. The lateral stresses acting
on the vertical faces of the element (i.e., the faces parallel to the wall) are parallel to the
inclined surface. Thus, any such planes experience not only normal but also shear stresses.
These planes, therefore, are no longer principal planes as was the case for horizontal ground
surface.
For the following analysis Rankine made an additional assumption i.e., the vertical stress
acting on any plane and the lateral stress acting on the element are conjugate stresses .
This assumption implies that the lateral earth pressure is parallel to the surface of the backfill
slope. The corresponding resultant pressure on the wall could be determined with the aid of
q= 1500psf
H = 12ft
x
m2m1
q/area
HP
-
8/10/2019 Lateral Earth Pres
20/36
- 20 -L iterature Review
20
Mohrs circle. Figure l2.8c symbolizes an active state of stress. The magnitude of the vertical
stress is depicted by the distance OC; the lateral stress, acting parallel to the sloped surface, is
represented by the distance OA. Hence, from Fig. 12.8c we have:
-
8/10/2019 Lateral Earth Pres
21/36
- 21 -L iterature Review
21
-
8/10/2019 Lateral Earth Pres
22/36
- 22 -L iterature Review
22
Equation 12-9 is Rankines expression for the active lateral pressure at depth H.
Equation 12-10 is Rankines expression for the passive case.
For a given sloped surface and uniform soil properties Kabecomes a constant. Thus,
the intensity of load, or stress, varies linearly with depth. Hence, as before, the total resultant
active force may be given by Eq. 12-9. Again, we noted that the direction of the resultant is
parallel to the sloped surface. For the case of level surface, Eqs. 12-9 and 12-10 reduce to
Eqs. 12-5 and 12-6, respectively.
11. Rankine State for Sloping Backfill (In short)
The coefficient of active earth pressure will be:
Ka= Cos{(Cos- Cos2- Cos2)/ (Cos+ Cos2- Cos2)}
Kp= Cos{(Cos+ Cos2- Cos2)/ (Cos- Cos2- Cos2)}
H
-
8/10/2019 Lateral Earth Pres
23/36
- 23 -L iterature Review
23
12. Rankin Analysis, R/W with submerged Backfill
At A
At B
13. Active Earth Pressure Partially submerged Backfill
0v
Hsatv
HHKK
HH
wsata
van
wsatv
.baseatHHK
HHKP
wa
wsataHa
A
B
C
Dry
Sat
H1
H2
A
B
H
-
8/10/2019 Lateral Earth Pres
24/36
- 24 -L iterature Review
24
Assuming that '' is same for dry & saturated granular fill:
Lets assume that Moist > Saturated
Therefore Ka sat> Kamoist.
The shape of pressure diagram for such a case will be
14. Active Earth Pressure against Inclined Back Retaining Wall
Consider a retaining wall with inclined back as above. Rankines analysis can be extended to
solve such problem by computing active earth pressure against a vertical plane C D. Let F 1
be the force due to active earth pressure. The weight & its location of wedge BCD, W can be
determined.
The resultant of F1&W gives the required force R. Similarly if the backfill is inclined
then the active force against plane 'CD' is lot and let it be F1. The resultant of F1& weight W is
R which is required force againstthe wall as shown below.
F1 = Ka H12
15. Coulombs Analysis of lateral Earth Pressures (inclined back & inclined fill)
.
''
''
0''
221
21
21
221
21
1
1
baseatHHKHKP
HKHK
HH
HHH
HHCAt
HKP
HBAt
AAt
wadaha
adah
dv
wsatdv
satdv
daa
dv
v
awamaH
amah
m
wsatmv
satmv
maa
maamv
av
PHHKHKHKHK
HH
HHH
HHCAt
HKPerfaceAt
HKPHBAt
PAAt
22212
2212
21
221
21
12
111
''
int
00
A
B
C
Ka1 mH1 H1
Ka2 mH1
H2
F1
CBA
D
H
W H/3
F1
H/3
R
CBA
D
H
-
8/10/2019 Lateral Earth Pres
25/36
- 25 -L iterature Review
25
In 1776 Coulomb introduced an expression for determining the active thrust on retaining walls.
Coulomb knew about effect of both cohesion and friction on shear strength of soil. He
observed a number of retaining wall failures and he concluded that when ever a retaining wall
fails a certain mass of soil breaks off in the form a wedge and exerts pressure on wall thus
concluding that the retaining wall shall be designed for the MAXIMUM pressure exerted by this
mass of soil. Although he observed that the failure surface is not plane but for simplicity ofanalysis he assumed that the failure surface is plane and the soil is cohesion less. He did this
in order to simplify somewhat the mathematically complex problem introduced when cohesion
and non-planer sliding surfaces are considered. He did, however, account for the effects of
frictional interaction between the soil backfill and the face of the retaining wall. Due to relative
motion between soil and the wall shear forces develop at interface. In active zone the soil
tends to move down along wall face as the wall moves away from the backfill. This downward
motion imparts a downward drag force on the wall. The magnitude of this shear force depends
on the friction angle between the wall & the soil wand is called angle of wall friction.
Typically for concrete. w = 2/3
In case of passive earth pressure the soil moves up as it is pushed by the wall & in the process
it exerts an upward shear force on the wall. The direction of this frictional force depends on the
direction of motion of soil mass and shall be evaluated carefully.
16. Coulombs Assumptions
a. Backfill is dry, cohesion less isotropic, homogeneous and elastically un-
deformable but breakable.
b. The slip surface is plane which passes through the heel of the wall.
c. The sliding wedge itself acts as a rigid body and the value of earth pressure is
obtained by considering the limiting equilibrium of sliding wedge as a whole.
d. The position and direction of resultant earth pressure are known. The resultant
force acts on the back of the wall at 1/3 rdthe height of the wall form the base and
is inclined at (angle of wall friction) to the normal to the back)
e. Back of the wall is rough and relative movement of the wall and soil takes place
which develops frictional forces that influence the direction of resultant pressure.
According to Coulombs theory, the thrust is induced by the sliding wedge, as shown in Fig.
12.l0a. For this reason, it is sometimes referred to as the sliding wedge analysis. The
corresponding force polygon is shown in Fig. 12.l0b. The development of Coulombs equation
follows from this basic relationship. From Fig. 12.l0b, using the Law of Sines, we have
-
8/10/2019 Lateral Earth Pres
26/36
- 26 -L iterature Review
26
Explanation of Force Polygon Angles
W = Wt of wedge
F = Resultant of Normal and Shear forces on the plane.
Pa= Active Pressure.
H = Ht of wall.
= Inclination of back face of wall
= Angle of force Pa with normal, friction angle between soil and wall.
= Internal friction angle, or angle of friction with normal.
= Angle of failure plan with horizontal.
i = Slope of backfill with horizontal
-
8/10/2019 Lateral Earth Pres
27/36
- 27 -L iterature Review
27
-
8/10/2019 Lateral Earth Pres
28/36
- 28 -L iterature Review
28
-
8/10/2019 Lateral Earth Pres
29/36
- 29 -L iterature Review
29
Example: A retaining wall as shown in Fig, below with soil properties. Find Paand Pp.
Note: Solve examples 9.1-9.8 Braja M. Das (Principles of Geotechnical Engineering)
17. Coloumbs Solution for R/W with Inclined Back and Inclined Back fill
Consider a RW as shown below the geometry of problem has changed but will we have
two unknown R& Fa, and one known quantity W the weight of wedge as shown.
The vector diagram is shown above.
By applying sine lawto force diagram.
Fa
CBA
D
H
i
W
w
Normal to
inclined surface
R
- i
-
- w
180-( - ) ( - w)
W
R
Fa
-
8/10/2019 Lateral Earth Pres
30/36
- 30 -L iterature Review
30
Also from sine law:
Putting values of eqn- B in eqn- A, we get
To determine maximum value of Fawe differentiate above equation with respect to and
equate it to zero. The resulting equation for maximum Fais,
18. Culmanns Method
The following graphical procedure was devised by Karl Culmann in (1875). It is used to
determine the magnitude and the location of the resultant earth pressures, both active and
passive, on retaining walls. This method is applicable with acceptable accuracy to cases where
the backfill surface is level or sloped, regular or irregular and where the backfill material is
uniform or stratified. Also, it considers such variables as wall friction, cohesion less soils, and
with some procedural modifications, cohesive soils and surcharge loads, both concentrated
and uniformly distributed. It however, requires that the angle of internal friction of the soil be a
constant for the total backfill. The procedure presented here is limited to cohesion-less soils.
)(180
180
180
&
12
1
180
180
iSinSin
HAD
SinABAD
AB
ADSinAlso
Sin
HAB
AB
HSin
BCADW
ABCFrom
ASin
SinWF
F
Sin
W
Sin
w
a
a
w
)(
)(
)(
2
1
)()(
)(
)(
)(
)()(
2
2 BiSinSin
iSinSinHW
iiiSin
iSin
Sin
HBC
iSin
iSinABBC
iSin
BC
iSin
AB
w
aSin
Sin
iSinSin
iSinSinHF
180)(
)(
2
12
2
2
12
22
)(2
1
iSinSin
iSinSinSinSin
SinHF
w
ww
Maxa
-
8/10/2019 Lateral Earth Pres
31/36
- 31 -L iterature Review
31
Reference is made to Fig. 12.20 in describing the procedure for determining the active
pressure for a case of cohesion less soil by Cullmans method:-
a. Select a convenient scale to show a representative configuration of retaining wall
and backfill. This should include height and slope of the retaining wall, surface
configuration of the backfill, location and magnitude of concentrated (line)
surcharge loads, uniformly distributed surcharge, and so on.
b. From pointA draw lineAC, which makes an angle of with the horizontal.
c. Draw lineAD at an angle of from lineAC. Figure 12.20 shows the angle to
be the angle between the vertical and the resultant active pressure.
d. Draw raysAB1, AB2, AB3, and so on, that is, assumed failure surfaces.
e. Determine the weight of each wedge, accounting for variations, if the backfill is a
layered system, for variable moisture content, and so on.
f. Select a convenient scale and plot these weights along lineAC. For the distance
fromA to W1 along lineAC equals W1 similarly, from theW1 to W2 along lineAC
equals W2, and so on.
g. From each of the points located on lineAC, draw lines parallel to line AD, to
intersect the corresponding assumed failure surfaces; that is, from W1 will
intersect lineAB1, then from W2 will intersect line AB2and so on.
h. Connect these points of intersection with a smooth line, Culmanns curve.
i. Parallel to lineAC; draw a tangent to Culmanns curve. In Fig. 12.20 point Erepresents a tangent point. More than one tangent is possible if Culmann line isirregular.
j. From the point of tangency, draw line EF parallel to lineAD. The magnitude of
EF, based on the selected scale, represents the active pressure Pa. Severaltangents to the curve are possible; the largest of such values becomes the value
of Pa. The failure surface passes through E andA, as Fig. 12.20.
Surcharge loads and their respective effects on the location of the resultant are accounted
for as described in the previous section. Examples 12.5 and 12.6 further enhance this
explanation.
-
8/10/2019 Lateral Earth Pres
32/36
- 32 -L iterature Review
32
Figure 12.21 illustrates the procedure for determining the passive resistancevia culmanns
method.
The approach is similar to that for the active pressure, with some notable differences:
(1) LineAC makesan angle of ' ' degrees below rather than above the horizontal;
(2) The reference line makes an angle of with line AC, with measured magnitude as
indicated in Fig. 12.21.
For the assumed sliding wedges, the weights W1, W2, and so on, are plotted along line
AC. From these points, lines are drawn parallel to the reference line to intersect the
corresponding rays, as shown in Fig. 12.21. The Culmann line represents a smooth curve
connecting such points of intersection. A tangent to the Culmann curve parallel to line AC is
drawn, with the resultant earth pressure being the scaled value of line FE, as shown in fig.
Example: A retaining wall with backfill as shown in fig-12-22, with the given data as:-
Ht of wall= 7 m, =30o, line load = 100 kn/m, =18.2 kn/m3, =900
Find the active thrust by Culmans method.
For convenient calculation of wedge weight; the bases for all the wedges are taken same.
Hence, the weight of all the wedges equals 127.4 kN, as shown in Fig. 12.23. The
corresponding points alongAC are shown in Fig. 12.22 for an arbitrary scale of 1 cm = 100 kN.
-
8/10/2019 Lateral Earth Pres
33/36
- 33 -L iterature Review
33
From these points lines are drawn parallel to lineAD so as to intersect raysAB1, AB2, AB3, and
so on. Note that a similar line is drawn for the line load by connecting these points of
intersection with a smooth curve (Culman curve) and drawing a tangent to this curve parallel to
lineAC, we obtain the Pa, which is equal to the corresponding scaled value FE. The scale for
FE = 1.85 cm for 185 kN. The point where 'Pa' acts is determined as described in the
preceding section and as shown in Fig. 12.24. Line EG is parallel to lineAC, and line GE isparallel to the failure plane. Patherefore acts at one-third distance FE from point E, a total of
4.25 m above pointA.
19. Design of Gravity Retaining Walls
Retaining walls are structures used to provide stability for earth or other material whereconditions disallow the mass to assume its natural slope, and are commonly used to hold back
or support soil banks, coal or ore piles and water.
Retaining walls are classified, based on the method of achieving stability, into six
principal types.
-
8/10/2019 Lateral Earth Pres
34/36
- 34 -L iterature Review
34
a. Gravity Retaining Walls. The gravity wall depends upon its weight, as the name
implies, for stability. The tensile stresses are avoided by proper proportioning of
the wall.
b. Cantilever Walls. The cantilever wall is a reinforced-concrete wall that utilizescantilever action to retain the mass behind the wall from assuming a natural slope.
Stability of this wall is partially achieved from the weight of soil on the portion of the
base slab.
c. Counter fort Retaining Walls. A counter fort retaining wall is similar to a
cantilever retaining wall, except that it is used where the cantilever is long or for
very high pressure behind the wall and has counter forts, which tie the wall and
breast together, built at intervals along the wall to reduce the bending moments
and shears. As indicated in Fig, the counter fort is behind the wall and subjectedto tensile forces.
d. Buttressed Wall. A buttressed retaining wall is in compression instead of tension
as shown in figure.
e. Crib Walls. These are built-up members of pieces of pre-cast concrete, metal or
timber and are supported by anchor pieces embedded in the soil for stability.
f. Bridge Abutments. These are retaining with wing wall extensions to retain the
approach fill and provide protection against erosion.
Keys
A roach Slabs
-
8/10/2019 Lateral Earth Pres
35/36
- 35 -L iterature Review
35
20. Gravity Retaining Walls
a. Common Proportions
Retaining wall design proceeds with the selection of tentative dimension, which
are then analyzed for stability and structural requirements and are revised as
required. Since this is trial process, several solutions to the problem may be
obtained all of which are satisfactory. A computer solution greatly simplifies the
work in retaining wall design and provides the only practical means to optimize
the design.
Gravity-wall dimensions may be taken as shown in figure below. Gravity walls,
generally, are trapezoidal-shaped but also may be built with broken backs. The
base and other dimensions should be such that the resultant falls within the
middle one-third of the base. The top width of the stem should be on the order of
0.30 m. If the heel projection is only 100 to 150 mm, the Coulmb equation may
be used for evaluating the lateral earth pressure, with the surface of sliding taken
along the back face of the wall. The Rankine solution may also be used on or
along the back face of the wall. The Rankine solution may also be used on a
section taken through the heel. Because of the massive proportions and resulting
low concrete stresses, low-strength concrete can generally be used for the wall
construction.
A critical section for analysis of tensile flexure stress will occur through the junction ofthe toe portion at the front face of the wall.
b. Stability of Wall. Gravity retaining walls must provide adequate stability againstsliding. The soil in front of the wall provides a passive-earth pressure resistanceas the wall tends to slide into it. If the soil is excavated or eroded after the wall isbuilt, the passive-pressure component is not available and sliding instability mayoccur. If there is certainty of no loss of toe soil, the designer may use the passivepressure in this zone as part of the sliding resistance. Additional sliding stabilitymay be derived from the use of a key beneath the base.
c. Design of Gravity Retaining Wall. A gravity retaining wall is a structure whichresists lateral earth pressure by its weight.
A retaining wall is considered safe, if it is safe against:
(1) Overturning (2) Sliding (3) Bearing failure
The proportioning should be such that no tension should develop anywhere in wall.
0.5 to 0.7 H
H
Minimum
batter
1:48
D to D
D to D
H/B to H/b
0.30 m to H/12
Slope change to
reduce concrete
(b)(a)
Approach Fill
PaPv
a
d
w
-
8/10/2019 Lateral Earth Pres
36/36
36
Consider a retaining wall as shown in the figure. Let R be the reaction from base actingat distance x from toe of the wall O. The total active force can be split into its horizontal andvertical components Ph and Pv respectively. The passive earth pressure Pp is ignored since it issupporting and less. The wall will be safe against overturning if the resultant passes thoughmiddle third of the base. Taking moment of all forces about O
Rv * x = W*a + Pv*d- Ph*b
x = (W*a + Pv * d - Ph * b) / Rv
Where Rv = W + Pv
The eccentricity of R from the centre of base is given as:
e = B/2 - xWe must ensure that e < B/6 so that there is no overturning.
a. FOS against overturning.
b. FOS against sliding, where = friction angle between wall
base and soil.
c. FOS against bearing capacity
The maximum stress should not exceed bearing capacity of soil.
5.1
Re
bP
dPW
gMomentOverturnin
entsistingMomFOS
h
va
5.1tan
h
v
P
RFOS
B
e
B
Rf
B
e
B
Rf
v
v
61
61
min
max