lateral earth pres

Upload: syed-muhammad-mohsin

Post on 02-Jun-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Lateral Earth Pres

    1/36

    - 1 -L iterature Review

    1

    CHAPTER- 2

    Lateral Earth Pressures1. Introduction

    Lateral earth pressure is the pressure that is exerted by a soil mass on a retaining

    structure or a wall. The problem associated with lateral earth pressures and retaining wall

    stability is one of the most common in the civil engineering field, and a segment of soil

    mechanics that has been receiving widespread attention from engineers for a long time.

    Design of structures such as retaining walls, sheet piling, and braced sheeting of pits and

    trenches, bulkheads, bridge abutments, basement or pit walls etc., requires a quantitative

    estimate of lateral earth pressure. In this chapter we will learn how to determine the

    magnitude and direction of lateral earth pressures for which a structure must be designed. In

    last part of the chapter the intro to design of a gravity retaining wall will be taken up. By

    definition a retaining wall is a structure used for maintaining ground surface at different

    elevations on its either side. The soil supported by the retaining wall is called backfill.

    In this chapter we will be concentrating on lateral earth pressures experienced by a retraining

    wall. To understand the concept behind these earth pressures lets examine the sequence of

    retaining wall construction for a road construction project in a hilly area. The sequence is

    shown below:

    Ideally a vertical cut should be provided to economize on the cost of excavation but soils are

    seldom stable at vertical slope and tend to slough down to attain equilibrium. Generally they tend to

    stabilize at a gentle slope. The stable slope angle depends on the soil properties and the height of

    slope. A gentle cut may not be feasible due to high cost of excavation or due to existence of some

    structures which may be pulled down. Under such circumstances soil is cut at a steep slope and is

    supported by constructing a retaining wall. A reasonable slope is cut during dry part of the year (step2)

    and retaining wall is constructed. The space behind the wall is later filled with soil and proper drainage

    is provided to protect it from storm water erosion. The retaining wall supports the backfill and its

    thickness at every horizon must be adequate to resist lateral earth pressure so that the wall neither tilts

    excessively nor is displaced horizontally away from the soil mass it is supporting. The approach to

    design of these walls is as under:-

    a. Determine different forces which contribute to wall stabilityb. Determine forces which are trying to destabilize the wall

  • 8/10/2019 Lateral Earth Pres

    2/36

    - 2 -L iterature Review

    2

    c. Compare these forces to ensure that the structure is safe.

    Two basic types of soil pressures are evaluated in this chapter, active and passive. If the

    soil mass pushes against a retaining wall such as to push it away, the soil becomes the

    actuating element and the pressure resulting thereby is known as active pressure. On the

    other hand, if the wall pushes against the soil, the resulting pressure is known as passive

    pressure. In this case the actuating element is the retaining wall itself.

    Analysis of a wide range of earth-retaining structures is primarily based on either ofthe two theories formulated by such persons as Coulomb in 1776 and Rankine in 1857.Furthermore, although some research data and experience indicate that assumptions relatedto pressure distributions on retaining walls, or on the failure surface of backfills, are not quitethose depicted by these early investigators, substantial evidence exists that the analysis anddesign efforts based on their theories give acceptable results for most cases of cohesion-lesstype backfills. The results are significantly less dependable for the more cohesive soils.2. Common Uses of Retaining Walls

  • 8/10/2019 Lateral Earth Pres

    3/36

    - 3 -L iterature Review

    3

    3. Factors Affecting Lateral Earth Pressure

    The main factors that affect lateral earth pressure include wall movement, wall friction,

    water in the backfill, compaction of the backfill, slope of backfill, seasonal variation and the

    nature of the backfill, the interaction between the soil and the retaining structure at the

    interface and the imposed loading (e.g., height of backfill, surcharge loads). These are

    discussed briefly in the following sections.

    a. Wall Moment.Under service conditions a rigid retaining wall possibly can rotate

    about its base, its top, its middle or another point: it can translate or there can be

    a combination of these modes. It is also possible that wall may not yield at all.

    Terzaghi (1934) is believed to be the first to conclude from his large scale earth

    pressure tests that the lateral earth pressure distribution behind retaining wall is

    associated, with the type and the magnitude of wall movement. Earth pressure

    distribution behind a wall rotating about its base is considered as linear (Terzaghi

    1934).

    b. Wall Friction

    A relative movement between a retaining wall and its back fill develops shear

    forces between the face of the wall and the backfill. These are termed wall

    friction (Lambe and Whitman 1969). The wall friction depends on roughness of

    the wall, amount and direction of the wall movements, soil properties of the

    backfill and inclination of ground surface behind the wall. The wall friction is also

    influenced by the settlement of the structure and the backfill soil (Grandil 1987).

    The maximum value of wall friction may not occur simultaneously with the

    maximum shearing resistance and the value of wall friction may vary across the

    wall (Bowles 1982). Wall friction angle () between 1/3 to 2/3 is a good

    approximation for computing lateral earth pressure using Coulombs theory. The

    wall friction affects the magnitude and the direction of earth pressure.

    c. Water in the Backfill

    The presence of water in the wall backfill without compensating water in front

    substantially increases total pressure because the coefficient K for water is unity.

    The distribution of pressure on a retaining wall due to water is hydrostatic and the

    resultant water force acts at one third the water height from wall base. The

    effective earth force acts above one third of wall height due to the presence of

    water in the backfill. The combined force due to soil and water acts below the

    one-third of wall height.

    d. Seasonal Variation

    Seasonal Variations affect the magnitude and the distribution of earth pressure

    mainly because of changes in temperature, freezing of backfill and heavy rainfall.

    Field test results show about 30% variation of earth pressure due to seasonal

    variations (Terzaghi and peck 1967). There is variation in earth pressure in

    summer and winter (Duncan et al, 1990).The warm front face of a wall in the

    summer expands relative to the back face and causes the wall to deflect back

    against the fill. The result is an increase in earth pressure. In the winter the

  • 8/10/2019 Lateral Earth Pres

    4/36

    - 4 -L iterature Review

    4

    pressure is reversed, the earth pressure also increases in winter due to

    expansion of water in the backfill voids due to freezing.

    e. Nature of Backfill Soil

    The engineering properties of the backfill soil such as(c, , )cohesion, internal

    friction angle and unit weight have substantial effect on the magnitude of lateral

    earth pressure on retaining structures. Higher the cohesion and internal

    friction angle, the lower will be the pressure. On the other hand, higher the

    Unit weights, higher will the pressure on the wall.

    f. Slope of Backfill

    The backfill slope changes the direction of lateral earth pressure. Thus, the

    magnitude of horizontal earth force acting on the wall changes with the increase

    or decrease in slope.

    4. Lateral Earth Pressures at Rest, Active and Passive States

    Let there be a mass of soil of density at

    depth z, vertical and horizontal stresses

    can be given as, v= *z ,

    h= k* *z = k* v ,where k= h/ v

    k = Coefficient of earth pressure.

    Statically value of k is indeterminate. The notation of kFor certain special cases are given below:-

    ko= Coefficient of earth pressure at rest which corresponds to zero strain.

    ka= Coefficient of active earth pressure which corresponds to shear

    failure by expansion of soil.

    Kp= Coefficient of passive earth pressure which corresponds to shear

    failure by compression of soil.

    Figure 13.2 above shows some of the forces acting on a typical gravity retaining wall.

    Frictional forces that may be developed on the front and back faces of the retaining wall are

    not shown. The lateral force induced by the backfill pushes against the wall with a resultant

    pressure Pa. In turn, the retaining wall resists the lateral force of the backfill, thereby

    preventing its movement. In this case, it is apparent that the soil becomes the actuating force.

    The thrust Pa is the resultant of the active pressure, or simply the active thrust. The

    resistance to the active thrust is provided by the frictional force at the bottom of the

    wall and by the soil in front of the wall . For the sake of illustration, assume that the wall was

    pushed to the left by the active thrust Pa.In this case the soil in front of the wall at its toe

    provides a passive resistance to movement. This resistance is known as the passive earth

    pressure, with the resultant of this pressure denoted by Pp. The magnitude of the lateral

    force varies considerably as the wall undergoes lateral movement resulting in either tilting or

    lateral translation, or both. Terzaghi focused on this phenomenon during his classic

    experiments in 1929 -1934.

    The concept of active and passive earth pressure can be best illustrated by reviewing the

    experiments conducted at MIT. In these experiments a glass box was used. A retaining wall

    was placed as shown below and steel bars, 6 inch long and inch diameter, were placed on

    1

    3 244

    1z

  • 8/10/2019 Lateral Earth Pres

    5/36

    - 5 -L iterature Review

    5

    either side of the wall up to its top.

    Since the top level of bars was the same initially the wall stood vertically i.e., every thing was in

    equilibrium, forces from left side of wall were balancing forces from right hand side. Later

    some bars from the left side were removed. Since there was no force to balance out forces

    from the right hand side, the wall tilted slightly to the left resulting in a decrease in pressure on

    the wall. As more rods were removed from the left the pressure on the wall reduced further

    and it swayed away from the rods on the right side. Finally as the depth of rod removal on left

    side reached a certain magnitude the bars on the right moved one past the other and a zone of

    shear failure was formed. A clear cut surface of shear failure could be seen. The wall

    experienced the minimum horizontal pressure at this instance. As more rods were removed,

    there was no further reduction in pressure on the wall. A similar phenomenon occurs in soils.

    Letsconsider soil strata under geostatic state of stress. Initially on any element the horizontal

    stresses on left and right side of the element are the same to keep it in equilibrium. Letspass

    an imaginary retaining wall of zero volume through this soil. Now we start removing soil from

    left of this imaginary wall just like the example above. As above the pressure on the wall will

    decrease as the wall tilts to the left due to removal of support. As more soil is removed the tilt

    increases and finally the soil behind the wall fails in shear and a zone of shear failure is formed

    right behind the wall. There is no further reduction in the lateral pressure experienced by the

    wall. This minimum lateral earth pressure experienced by the wall as it moves away from the

    soil mass it is supporting is called ACTIVE earth pressure. By definition active earth

    pressure is the minimum lateral earth pressure experienced by the wall as

    it moves away from the soil mass to which it is supporting.

  • 8/10/2019 Lateral Earth Pres

    6/36

    - 6 -L iterature Review

    6

    Figure 12.2 above depicts the relationship betweenthe earth pressure and the walI movement.

    Porepresents the magnitude of pressure when no movement of the retaining wall takes

    place; it is commonly referred to as earth pressure at rest.As the wall moves toward the

    backfill, the pressure increases, reaching a maximum value of Ppat point C. On the other

    hand, if the wall moves away from the backfill, the force on the wall decreases, reaching a

    minimum value of Paat point B.

    Figures 12.3a and 12.3b show the active case, where the wall moves away from the backfill,

    together with the corresponding force polygon. Similarly, the case of passive resistance,

    together with its force polygon, is shown in Figs. 12.3c and 12.3d.

  • 8/10/2019 Lateral Earth Pres

    7/36

    - 7 -L iterature Review

    7

    5. Active and Passive Earth Pressures for (c- ) Soils with Horizontal Backfill

    a. Active Earth Pressure(c- , soils). Letsconsider a case for wall with horizontal

    backfill of c- , soilsas above. Here we assume that backfill is pushing the wall

    away from fill. So as we start excavation, the wall yields and lateral stresses 3

    will keep decreasing (shown in dotted). Finally the lateral pressure reduce to a

    level that the Mohrs circle touches strength envelope. This is limiting conditionsat which pressure can not reduce any further or its Mohrs circle cross strength

    envelope, which is impossible. The stresses so induced are plotted on Mohrs

    Circle and followed the well known Mohrs/Coulumbs shear strength equation

    (=C+ ntan )

  • 8/10/2019 Lateral Earth Pres

    8/36

    - 8 -L iterature Review

    8

    From small triangle, A = C/tan , B = (1+A)/2 and R = (1- A)/2 ------------ (i)

    But from fig R = (A+B) sin --------------------------------------------------------------(ii)

    Comparing eqn (i) & (ii) we get (1- A)/2 = (A+B) sin --------------------------(iii)By putting values of A & B in eqn (iii) we get,

    (1- A)/2 = ((C/tan + (1+A)/2)* sin(1- A)/2 = C/tan *sin+1sin/2+ Asin/2(1- A) = 2C cos + 1sin+ AsinA(1+ sin) = 1(1- sin) - 2C cos A= 1(1- sin)/ (1+ sin) - 2C cos /(1+ sin)PA = 1*ka- 2C kawhere, 1= *z and ka= (1- sin)/ (1+ sin)or Ka= tan

    2(45-/2)b. Passive Earth Pressure(c- , soils). Letsconsider a case for wall with horizontal

    backfill of c- , soils. Here we assume that backfill is being pushed by the walltowards fill. Therefore lateral earth pressure 3 will keep increasing due topushing of backfill by wall with passive pressure p and thus failure occur due tocompression of soil. The stresses so induced are plotted on Mohrs Circle andfollowed the well known Mohrs/Coulumbs shear strength equation

    ( =C+ ntan )

    From small triangle, A = C/tan , B = (1+p)/2 and R = (p- 1)/2 ------------ (i)But from fig R = (A+B) sin --------------------------------------------------------------(ii)Comparing eqn (i) & (ii) we get (p- 1)/2 = (A+B) sin --------------------------(iii)By putting values of A & B in eqn (iii) we get,(p- 1)/2 = ((C/tan + (1+p)/2)* sin(p- 1)/2 = C/tan * sin+ 1sin/2+ psin/2(p- 1)= 2C cos + 1sin+ psinp(1- sin) = 1(1+ sin) + 2C cos p= 1(1+ sin)/ (1- sin) +2C cos /(1- sin)Pp = 1*kp+ 2C kpwhere, 1= *z and kp= (1+ sin)/ (1- sin)or Kp= tan

    2(45+/2)

    Alternately

    CA

    (1+

    A)/2

    R=(1- A)/2

    =c+ ntan

    v

    h

    h

    BA

    n1

    CA

    (1+p)/2C/tan

    R=(p- 1)/2

    =c+ ntan

    3 p

    BA

  • 8/10/2019 Lateral Earth Pres

    9/36

    - 9 -L iterature Review

    9

    Lets starts with simple case of horizontal ground level and zero wall friction.

    Consider an element located at depth Z initially as wall moves awaydecreases and finally the soil fails. The state of stress for soil mass as it moves away from thebackfill from static equilibrium to plastic equilibrium is shown below:

    For the circle touching the strength envelope, h is minimum and is equal to Pa.

    From ABC

    Here

    Therefore

    1, (Active earth pressure)

    & -------2, (Passive earth pressure)

    Equation no one is called Bells Equation for active earth pressure for

    cohesive soils.

    From equation- 1 at ground surface z = 0

    at the base of wall

    Stress diagram is shown below:

    vh K 0 h

    2

    2

    31

    31

    CotC

    Sin

    hav P 31 &

    22

    avav PPCotCSin

    Sin

    CosC

    Sin

    SinP

    CosCSinSinP

    PSinPSinCosC

    PSinPSinSin

    CosSinC

    a

    va

    avav

    avav

    1

    2

    1

    1

    211

    2

    2

    aava KCKP 2

    pvpp KCKP 2

    a

    aaa

    KC

    KCZKP

    2

    02

    aaa KCHKP 2

    Zv

    h = K v (C - )

    A C

    O

    B

    C

    = K0h v

    2

    av P

    = Pa = Ka h v

    v

    C/tan

    aKC2A

    2Z0 Z0

    +

    H

    60.6kn/m

    -

  • 8/10/2019 Lateral Earth Pres

    10/36

    - 10 -L iterature Review

    10

    At certain depth zo, Pa= 0

    As indicated in the figure up to a depth the soil is under tension. Since soil

    cannot sustain tension a tension crack is generally formed at top to a depth of . If the

    crack is filled with water then the pressure of this water on wall must be given due

    consideration.

    From fig it is clear that up to a depth of 2Z0the net pressure on the wall is zero i.e. a cohesive

    soil can stand without any lateral support up to a depth,

    Therefore, the critical Hcan unsupported vertical cut in clay is given as: 2Z0= Hc

    For computation of lateral stress in case of cohesive soils, theve pressure are neglected &

    whole +ve pressure below depth z is taken into consideration.

    6. Unsupported cuts in (c -) soil

    Unsupported excavations would theoretically be possible in (c-) soils if the lateral

    pressure (3for the active case) would not exceed the strength of the soil. The general

    expression forthe horizontal stress for the active is given as:

    (d)

    At ground surface, h = 0. Thus,

    3= -2cKa (Tension)

    This implies the formation of a crack as depicted in Fig. 12.15a given below. The

    corresponding pressure distribution based on Eq. (d) is shown in Fig. 12.15 b.

    The theoretical depth of the crack htcan be determined by recognizing that, at the

    bottom of the crack, 3 = 0 or Pa=0. Thus, from Eq. (d),

    0 = htKa-2cka or ht = 2c /ka (12-17)

    The theoretical maximum depth Hc of unsupported excavation may be calculated as the

    02 aa KCZK

    a

    a

    a

    KCZ

    K

    KCZ

    2

    02

    0

    0

    aK

    CZ

    20

    aK

    C

    2

    aK

    CZ

    42 0

    a

    cK

    CH

    4

    aaa KCHKP 2

  • 8/10/2019 Lateral Earth Pres

    11/36

    - 11 -L iterature Review

    11

    point where the tension forces equal the cohesive strength. Hence, from

    Figure 12.15 b, Hc= 2 ht.

    Though the above equation provides a theoretical depth to which an excavation may be

    made without lateral support, it should be used cautiously. Surface moisture that may enter the

    crack may induce hydrostatic stresses or may decrease the shear strength of the soil. Hence,

    the unsupported excavation to such depths should be for short duration at best. Even then,judgment reflecting on the potential consequences from unsupported excavation is indeed

    warranted.

    In general it is advisable to minimize the use of cohesive backfill when ever possible.

    With changes in moisture content the pressure induced by highly cohesive soils may change

    significantly. If the clay dries out and shrinks then the pressure on the wall will reduce. On the

    other hand a dry soil may take up moisture and swell thus exerting tremendous pressure on

    the wall.

    a. At Rest Earth Pressure. Let us consider the mass of soil shown in Figure 2.1. The

    mass of soil bounded by a frictionless wall AB that extends to infinite depth. An element

    located at a depth z will be subjected to a vertical pressure vand horizontal pressure h. For

    the case considered here, vand hare effective and total pressures and there are no shear

    stresses on the vertical and horizontal planes.

    If the wallAB is static-that is, if it does not move either to the right to or the left of its initialposition-the soil mass will be in a state of elastic equilibrium. The ratio of the horizontal stressto the vertical stress is the coefficient of earth pressure at rest, Ko, or Ko= h/v-------------(2.1)Since v= *z, so, h= Ko(*z) -----------------------------------------(2.2)

    For granular soils, the coefficient of earth pressure at rest can be represented by the

    empirical relation (Jaky, 1944), Ko= 1- Sin ------ (2.3)Brooker and Ireland (1965) recommended the following equation for Ko in normallyconsolidated clays, Ko= 0.95- Sin -------------- (2.4)

    Also(1) For -soils

    (a) For horizontal backfill, ko= (1- sin )(b) For sloping backfill, ko= (1- sin )(1+ sin)=ko(1+ sin)

    (2) For c-soils (Brooker & Ireland)(a) For 0

  • 8/10/2019 Lateral Earth Pres

    12/36

    - 12 -L iterature Review

    12

    b. Earth Pressure at Rest for Partially Submerged Soil

    Figure 2.3a shows a wall of height H. The ground water table is located at a depth H1below the ground surface. For z H1 the lateral earth pressure at rest can be given ash= Ko (*z). The variation of h with depth is shown by the triangle ACE in Figure-2.3 a.However, for z H1 (Below GWT)

    The pressure on the wall is found from the effective stress and pore water pressurecomponents in the following manner:

    Effective vertical pressure = /v= H1+ '(z - H1) ------------------- (2.9)

    where ' = sat- w= the effective unit weight of soilSo, the effective lateral pressure at rest is/h= Ko

    /h= Ko {(H1+ '(z - H1)} -------------------------------------(2.10)

    The variation of /hwith depth is shown by CEGB in Figure 2.3 a.Again, the lateral pressure due to pore water is, u = w(z-H1)--- (2.11)

    The variation of u with depth is shown in fig 2.3 bHence, the total lateral earth pressure at any depth z H1is equal toh=

    /h+u = Ko {(H1+ '(z - H1)}+ w(z - H1) -----------------------(2.12)

    The force per unit width of the wall can be found from the sum of areas of the pressure

    diagrams in Figures 9.3a and b and is equal to

    Po= {(1/2*KoH21)+( KoH1H2)+ ( Ko

    / + w)H22} ----------------(2.13)

    (Area ACE) (Area CEFB) (Area EFG&IJK)c. General Comments on Earth Pressure Coefficient at Rest

    While designing a wall that may be subjected to lateral earth pressure at rest, care must

    be taken in evaluating the value of Ko. Sherif, Fang, Sherif (1984), based on their laboratory

    tests, have shown that Jaky's eqn for Ko eqn (2.3), gives good results when the backfill is

    H2

    KoH1

    (a)

    GWT

    GF

    E

    B

    A

    z

    Unit weight of soil =

    H

    Fig-2.3

    C

    Ko(H1+ /H2)

    KoH1

    H1

    Saturated Unit

    weight of soil = sat

    KJ

    I

    wH2

    (b)

    Ko(H1+/H2)+wH2

    H2

    H1

    =

    60.

  • 8/10/2019 Lateral Earth Pres

    13/36

    - 13 -L iterature Review

    13

    loose. However, for a dense sand backfill, eqn. (2.3) grossly underestimates lateral earth

    pressure at rest. This is due to the process of compacting backfill. For that reason, they have

    recommended the following design relationship.

    Ko= (1-sin )+( d/ d(min)-1)*5.5 ------------------------------------(2.14)

    where d= actual compacted dry unit weight of the sand behind the wall

    d(min)= dry unit weight of the sand in the loosest stateExample:

    Data: As shown on fig

    Req: Calculate fol:

    ko, ka, kp

    PO,Pa, Pp

    location of pressures.

    Solution:

    a. Values of k

    ko= 1- sin = 1- sin 35o= 0.43

    ka= tan2(45-/2) = tan2(45-35o/2) = 0.27

    kp= tan2(45+/2)= tan2(45+35o/2)= 3.69

    b. Po= * Ko H2= *0.43*125*30

    2= 24187 lb/ft

    2

    Loc of Po= H/3=30/3= 10 ft from base of wall.

    c. Pa= * Ka H2= *0.27*125*30

    2= 15187 lb/ft

    2

    Loc of Pa= H/3=30/3= 10 ft from base of wall.

    d. Pp= * Kp (H1)2= *3.69*120*10

    2= 22140 lb/ft

    2

    Loc of Pp= H1/3=10/3= 3.33 ft from base of wall.

    Example:

    Data: As shown on fig

    Req: Calculate active force per unit of wall

    for Rankins state. Also find location of resultant.

    Solution

    1. Calculation of Ka

    a. For top layer Ka1

    Ka1= 1-sin30o/1+sin30o= 0.33

    b. For Bottom layer Ka2

    Ka2= 1-sin35o/1+sin35

    o= 0.27

    H

    PO

    KoH

    H

    Pa

    KaH

    Pp

    H1

    KpH1

    = 120 pcf= 35o

    H1=10 ft

    = 125 pcf= 35o

    H = 30 ft

    3m

    3m= 16kn/m= 30oc=0

    = 18kn/m= 35oc=0

    3

  • 8/10/2019 Lateral Earth Pres

    14/36

    - 14 -L iterature Review

    14

    2. Calculation of Pa

    a. For top layer Pa1

    at z=0, v=0 but at z=3m, v1= 16*3=48kn/m2

    So a1=Ka1*v1= 16*3* 0.33= 16 kn/m2

    and Pa1= *3*16= 24 kn/m2

    b. For Bottom layer Pa2

    at z=3, v=3*16 =48kn/m2 (just below top layer)

    and a2=Ka2* = 0.27*48= 13 kn/m2

    at z=6m, /v2= v1+ /v2= 48+3*(18-9.81)=72.6kn/m

    2

    /a2= Ka2* /v2= 0.27*72.6= 19.7 kn/m

    2

    c. Pressure due to water-uAt z=0, u=0

    At z=3m, u=0At z=6m, u= 3*9.81=29.43kn/m2

    d. Total active pressure,

    Pa=(*16*3)+13*3+ 19.7-13(3*1/2)+*29.43*3

    = 24+39+10+44.14 =117.15 kn/m2

    e. Location of pressure By taking moment at the base of wall.

    117.15*z= 24(3+3/3)+39*3/2+10*3/3+44.15*3/3=208.15

    z= 208.15/117.15= 1.78 m

    Example:

    An unsupported cut as shown in fig with the given

    soil properties, find

    a. Stress at top and bottom of cutb. Max depth of potential tension crackc. Max un-sported excavation.

    Solution As we know that major & minor principal stresses are decided on the basis of their

    magnitudes. Here, a is greater in magnitude, so considering it as major principal stress,hence, stresses would be calculated basing ona.

    a. Stresses at Top and BottomStresses at point A (Top)- As h = 0, so a= h Ka- 2ckaa= -2cka= (2*25) tan (45-5

    0) = -41.95 kn/m

    2

    Stresses at point B (Bottom)- As h = 4.2 m,

    a= h Ka- 2cka= 18.2*4.2 tan2(45-50)2*25 tan (45-50) = 11.87 kn/m2

    b. Max depth of Potential Tension Crack

    ht= 2c /ka = (2*25) /18.2tan2(45-50)= 3.27 mc. Max Un sported ExcavationAs we know that Hc= 2 ht,

    so Hc= 2 *3.27 = 6.54 m7. Rankines Theory

    Coulombs and Rankine are the best-known theories which are used to compute the

    magnitude and direction of forces which act on the retaining wall due to the backfill behind it.

    These theories are frequently referred to as the classical earth pressure theories. The theory

    proposed by Rankine in 1857 is based on the following assumptions:

    Frictional forces between backfill and retaining wall are zero. ( the implication of this

    assumption is that shear stresses on the vertical and horizontal planes are zero i.e.,

    these planes are principal planes)

    The back of the wall is vertical,

    The surface of the backfill is horizontal.

    19.7kn/m2

    3

    13kn/m

    3

    16kn/m

    29.43kn/m

    3

    A

    B

    = 18.2

    kn/m3= 10o

    H = 4.2 m

  • 8/10/2019 Lateral Earth Pres

    15/36

    - 15 -L iterature Review

    15

    The backfill is a homogeneous, isotropic, dry and cohesion-less material.

    The failure surface is plane.

    The wall yields about the base and satisfies conditions of plastic equilibrium.

    The basic concept behind Rankines theory can be depicted by Mohrs circle. Consider the

    element shown in Fig.12.3, subjected to the geostatic stresses shown. The value for 1/could

    be approximated as the product of the average unit weight times depth, namely, 1/= h. If

    the wall were to move to the left, thereby creating a case of active stress, the value for 1/

    would become the major principal stress and at failure the minor principal stress h/ is equal

    to the active earth pressure. The corresponding Mohr circle for this case is depicted by circle-I

    in Fig. 5. On the other hand, if the wall were to push against the backfill i.e., move towards the

    backfill, a case of passive pressure would be developed. The vertical stress would then

    become the minor principal stress

    3/ and the lateral stress would thus become the major

    principal stress which at failure is the passive earth pressure. The Mohr circle for this condition

    is depicted by circle- 2 in Fig. 5.

    The pressures on retaining wall vary linearly with depth, as indicated by Fig. 12.7.

    The corresponding resultant pressures, active and passive, can be calculated for a unit length

    of retaining wall as

    Pa = 0.5 H ka= 0.5 * H2tan

    2(45 - /2)

    Pp = 0.5 H kp= 0.5 * H2tan 2(45 + /2)

    The corresponding slip planes for the active and passive cases are shown in Figure

    12.5c and 12.5d. The or ientat ion of these planes can be best being und erstood u sing

    the conc ept of po le. For active case point 3represents pole. A line drawn from this point

    to the point representing state of stress on failure plane yields the orientation of failure planes

    for the active state. It is to be pointed out that once the lateral stresses in this case drop to the

    active value, shear failure along an infinite number of planes behind the wall is imminent and at

    the instant the soil is said to be in a state of limit equilibrium. Since the state of stress in backfill

    is known for either at rest condition or the active condition, retaining walls are designed for the

    limit equilibrium conditions and such design is called limit design.

    8. Effects of Surcharge loads

    Concentrated or uniformly distributed loads, commonly referred to as surcharge loads, acting

    on the surface of the backfill, will:

    o Increase the lateral pressure against the, retaining wall.

    o Move the point of application of the resultant pressure upward.

    a. Effect of UDL Surcharge

    Figure 12.17 shows uniformly distributed surcharge q (kN/m2) acting on the surface of the

  • 8/10/2019 Lateral Earth Pres

    16/36

    - 16 -L iterature Review

    16

    backfill. The vertical stress 1on an element within the soil backfill at a depth h is equal to

    h + q. Correspondingly, the lateral stress 3for a (c-)soil, is

    99.. RRaannkkiinnAAnnaallyyssiissBBaacckkffiillllwwiitthhUUnniiffoorrmmSSuurrcchhaarrggee

    If the backfill is horizontal & carries a uniform surcharge q-kn/m2, the vertical stress at

    any depth will increase by q. The increase in lateral pressure for active case therefore will be

    kaq as shown below:

    Example

    Find the passive resistance (Pp) of given frictionless

    Retaining wall as shown in fig. Also calc the location

    of passive resultant.Solution

    a. Calculation of K

    Kp= 1+sin250/1-sin250= 2.45

    2. Calculation of Stresses

    a. Passive Resistance/Stresses

    at top of layer, z=0, v=q= 12 kn/m2(surcharge)

    p= 2.45*12+2*102.45= 60.6 kn/m2

    at bottom of layer, z=5m, v=q+h = 12+15*5 =87kn/m2

    p= 2.45*87+2*102.45= 244.35 kn/m2

    b. Passive Resistance

    Pp= 60.6*5+244.3*5*1/2= 303+610.9 = 914 kn/m

    c. Location of Resultant. Taking moment of pressure diagram about wall base.

    914*z = 303*5/2 + 611*5/3= 757.5+1018.3 = 1775.83 = z=1775.83/914 =1.94m

    b. Effect of Point load Surcharge (by Boussinesqs equation)

    To determine lateral pressure on wall due to point load

    aaa KCHKP 2

    z=nH

    x=mH

    Q

    H

    q kN/m2

    aa KCHK 2

    244.3kn/m2

    60.6kn/m2

    5 m

    = 15 kn/m

    = 25oc=10 kn/m2

    q=12kn/m2

    914kn/m

  • 8/10/2019 Lateral Earth Pres

    17/36

    - 17 -L iterature Review

    17

    Q placed at surface of the backfill as shown in fig.

    If the load Q is placed on the plane of section as shown;

    We can substitute y=0 and =0.5 in vertical stress distr

    equation developed by Boussinesq. This is modified as

    x =Q/2(3x2*z/R

    5) -------------(A)

    where R= (x2+z2)1/2

    Substituting x=mH & z=nH in eqn (A), we get

    x =3Q/2H2{m

    2n/(m

    2+n

    2)5/2

    }-------------- (B)

    The horizontal stresses expressed by eqn (B), does not include restraining effect of wall.

    Therefore the eqn has been modified as per real time situation as under:-

    x =1.77Q/H2{m

    2n

    2/(m

    2+n

    2)3} for m> 0.4-------------- (C)

    x =0.28Q/H2{n

    2/(0.16+n

    2)3} for m 0.4-------------- (D)

    For concentrated surcharge loads Q such as may be induced by a continuous footing,

    railroad tracks, and the like, running parallel to the wall, it is possible, although rather

    laborious, to estimate the increased stresses on the wall based on Boussinesqs equation,

    consistent with the theory of elasticity for a semi-infinite homogeneous soil mass. However,

    graphical methods given below are more expedient for this purpose.

    Experimental data indicate that Boussinesqs formula for lateral stress gives acceptable

    results where the wall movement is compatible to soil deformations within the backfill. On the

    other hand, if the retaining wall is totally rigid such that the soil deformation is greatly restricted

    by the rigid boundary, the horizontal stress approaches a value twice that given by

    Boussinesqs equation.This effect becomes less noticeable as the distance of Q relative to

    the wall increases.

    c. Effect of Point load Surcharge (by graphical method)

    The line of action of the active thrust induced by the concentrated surcharge loads Qis

    commonly based on empirical procedures. Such a procedure gives acceptable results for

    cohesion less backfill; it may be illustrated with the aid of Fig 12.19. When the concentrated

    surcharge load is located to the left of point C, the active thrust Pa may be determined by

    drawing lines EDand FDparallel to lines AGand AC,respectively. The point of application

    of Pais one-third the distance FEfrom point F, as indicated in Fig. 12.19a. But when load Q

    is located to the right of the failure plane, as indicated in Fig. 12.19b, line EDis parallel to line

    AC. The point of application of Pais one-third the distance EAfrom point F, as shown in

    Fig. 12.19b. We noted that the line of action of the resultant thrust moves up the wall as the

    load Qapproaches the wall. Furthermore, the lateral thrust as well as the overturning effect

    decreases as the load Qmoves away from the wall.

  • 8/10/2019 Lateral Earth Pres

    18/36

    - 18 -L iterature Review

    18

    ExampleFind the lateral force Pa due to backfilland

    point load 1.5m away from back face of wall as shown in fig.

    Solution (for point load)

    Here x=1.5m, H= 5m, z= 0-5m (for n= 0.2,0.4,0.6,0.8,1.0)

    Divide H in five equal parts for calc pressure per unit of wall.

    m= x/H = 1.5/5=0.3 i.e less than 0.4

    Therefore we will use

    x =0.28Q/H2{n

    2/(0.16+n

    2)3} for m 0.4

    x =0.28*150/52{0.2

    2/(0.16+0.2

    2)

    3} = 1.68*5= 8.4kn (for n= 0.2)

    x =0.28*150/52{0.4

    2/(0.16+0.4

    2)

    3} = 1.68*4.88= 8.2kn (for n= 0.4)

    x =0.28*150/52{0.6

    2/(0.16+0.6

    2)

    3} = 1.68*2.56= 4.3kn (for n= 0.6)

    x =0.28*150/52{0.8

    2/(0.16+0.8

    2)

    3} = 1.68*1.25= 2.1kn (for n= 0.8)

    x =0.28*150/52{1

    2/(0.16+1

    2)3} = 1.68*0.41= 0.69kn (for n= 1.0)

    Now lateral force P due to point load will be

    P= (0+8.4)*1+ (8.4+8.2)*1+ (8.2+4.3)*1+ (4.3+2.1)*1 + (2.1+0.69)*1= 23.35kn/m of wall ht2 2 2 2 2

    For geostatic stresses ka= tan2(45-/2)= 0.626

    At top lateral stresses, h= 2*12.50.626=2*12.5*0.7= 19.75kn/m2

    At bottom of wall, h= 18*5*0.626-2*12.5*0.79= 36.6 kn/m2

    Pressure on wall= 19.75*5+16.85*52/2= 98.75+210.6= 309.35kn/m of wall ht

    For resultant Pressure location taking moments at base of wall

    Z= (98.75*5/2)+(210.6*1.67)/309.6=246.87+351.7=598.57/309.6=1.93m from base.

    d. Effect of line load Surcharge (by Boussinesqs equation)

    To determine lateral pressure on wall due to line load

    q placed at surface of the backfill as shown in fig.

    If the load q is placed on the plane of section as shown;

    Eqn (D) is modified as

    x =4q/H {m2n/(m

    2+n

    2)

    2} for m> 0.4-------------- (E)

    x =0.203q/H {n/(0.16+n2)2} for m 0.4-------------- (F)

    ExampleA line load of 50kn/m is located at a distance of 3m from back

    face of retaining wall 4.5m high. Determine lateral force P on wall due to line load.

    Solution

    Here x=3m, H= 6m, z= 0-6m (for n= 0.25,0.5,0.75,1.0)

    Divide H in four equal parts of 1.5 m for calc pressure on wall.

    m= x/H = 3/6=0.5 i.e more than 0.4

    Therefore we will use

    x =4q/ H {m2n/(m

    2+n

    2)2} for m> 0.4

    x =4*50/*6 {0.520.25/(0.52+0.252)2} = 10.61*0.64= 6.8kn (for n= 0.25)

    x =4*50/*6 {0.520.5/(0.5

    2+0.5

    2)2} = 10.61*0.5= 5.3kn (for n= 0.5)

    x =4*50/*6 {0.520.75/(0.5

    2+0.75

    2)2} = 10.61*0.28= 3.0kn (for n= 0.75)

    z=nH

    x=3m

    q= 50kn/m

    H=6m

    z=nH

    x=mH

    Q=150Kn

    H

    =18kn/mc=12.5kn/m2

    =150

    z=nH

    x=mH

    q= kn/m

    H

  • 8/10/2019 Lateral Earth Pres

    19/36

    - 19 -L iterature Review

    19

    x =4*50/*6 {0.521.0/(0.5

    2+1

    2)2} = 10.61*0.16= 1.7kn (for n= 1.0)

    Now lateral force P due to point load will be

    P= (0+6.8)*1.5+ (6.8+5.3)*1.5+ (5.3+3)*1.5+ (3+1.7)*1.5 = 24kn/m of wall width

    2 2 2 2

    e. Effect of strip load Surcharge (by Boussinesqs equation)

    To determine lateral pressure on wall due to strip load

    q/area placed at surface of the backfill as shown in fig.

    If the load q is placed at distance m1 from wall back of

    of height H with width as m2.The horizontal stress

    at depth z on wall due to strip loading is given as

    x =q/H(-sin*cos 2), angles & as defined on fig-------------- (G)

    for actual soil behavior conditions eqn (G) can be modified as

    x =2q/H*{(-sin*cos 2)}, -------------- (H)

    The force P per unit width of wall can be obtained by integ eqn (H)For z & H this is given as

    P= q/90{H(21)}, where is in deg and given as

    1 = tan-1

    (m1/H) & 2 = tan-1

    ((m1+m2)/H)

    ExampleA strip loading as shown in fig; m1= 10ft, m2= 5ft

    Calculate xat 2/interval of H.

    Also determine lateral force P on wall due to strip load.

    Solution

    Calculation of xby using eqn (H)

    x =2q/H*{(-sin*cos 2)}

    Calculation of x

    z m1 m2 = tan-

    (m1+ m2/2)/z = {tan-

    (m1+ m2)/z}-{ tan-

    (m1)/z} x=2q/z*{(-sin*cos 2)}2 10 5 80.91

    3.71

    5657lb/ft

    4 10 5 72.25

    6.9

    5225lb/ft

    6 10 5 64.36

    9.2

    4629 lb/ft

    8 10 5 57.38

    10.60 4000 lb/ft

    10 10 5 51.34

    11.31

    3402lb/ft12 10 5 46.17

    11.5

    2877 lb/ft

    Calculation of PUsing eqn given above as, P= q/90(21) and1 = tan

    -1(m1/H) & 2 = tan

    -1(m1+m2/H)

    1 = tan-1

    (m1/H)= tan-1

    (10/12)= 39.80

    2 = tan-1

    ((m1+m2)/H))= tan-1

    ((10+5)/12)= 51.340

    Now, P= q/90{H(21)}= 1500/90{12(51.34-39.8)}= 2308 lb/ft of wall width

    10. Cohesion less Backfill and Inclined Surface

    Let us now consider cohesion less mass with a sloping surface behind a smooth vertical

    retaining wall. Assume this condition to be depicted by Fig. 12.8a. The lateral stresses acting

    on the vertical faces of the element (i.e., the faces parallel to the wall) are parallel to the

    inclined surface. Thus, any such planes experience not only normal but also shear stresses.

    These planes, therefore, are no longer principal planes as was the case for horizontal ground

    surface.

    For the following analysis Rankine made an additional assumption i.e., the vertical stress

    acting on any plane and the lateral stress acting on the element are conjugate stresses .

    This assumption implies that the lateral earth pressure is parallel to the surface of the backfill

    slope. The corresponding resultant pressure on the wall could be determined with the aid of

    q= 1500psf

    H = 12ft

    x

    m2m1

    q/area

    HP

  • 8/10/2019 Lateral Earth Pres

    20/36

    - 20 -L iterature Review

    20

    Mohrs circle. Figure l2.8c symbolizes an active state of stress. The magnitude of the vertical

    stress is depicted by the distance OC; the lateral stress, acting parallel to the sloped surface, is

    represented by the distance OA. Hence, from Fig. 12.8c we have:

  • 8/10/2019 Lateral Earth Pres

    21/36

    - 21 -L iterature Review

    21

  • 8/10/2019 Lateral Earth Pres

    22/36

    - 22 -L iterature Review

    22

    Equation 12-9 is Rankines expression for the active lateral pressure at depth H.

    Equation 12-10 is Rankines expression for the passive case.

    For a given sloped surface and uniform soil properties Kabecomes a constant. Thus,

    the intensity of load, or stress, varies linearly with depth. Hence, as before, the total resultant

    active force may be given by Eq. 12-9. Again, we noted that the direction of the resultant is

    parallel to the sloped surface. For the case of level surface, Eqs. 12-9 and 12-10 reduce to

    Eqs. 12-5 and 12-6, respectively.

    11. Rankine State for Sloping Backfill (In short)

    The coefficient of active earth pressure will be:

    Ka= Cos{(Cos- Cos2- Cos2)/ (Cos+ Cos2- Cos2)}

    Kp= Cos{(Cos+ Cos2- Cos2)/ (Cos- Cos2- Cos2)}

    H

  • 8/10/2019 Lateral Earth Pres

    23/36

    - 23 -L iterature Review

    23

    12. Rankin Analysis, R/W with submerged Backfill

    At A

    At B

    13. Active Earth Pressure Partially submerged Backfill

    0v

    Hsatv

    HHKK

    HH

    wsata

    van

    wsatv

    .baseatHHK

    HHKP

    wa

    wsataHa

    A

    B

    C

    Dry

    Sat

    H1

    H2

    A

    B

    H

  • 8/10/2019 Lateral Earth Pres

    24/36

    - 24 -L iterature Review

    24

    Assuming that '' is same for dry & saturated granular fill:

    Lets assume that Moist > Saturated

    Therefore Ka sat> Kamoist.

    The shape of pressure diagram for such a case will be

    14. Active Earth Pressure against Inclined Back Retaining Wall

    Consider a retaining wall with inclined back as above. Rankines analysis can be extended to

    solve such problem by computing active earth pressure against a vertical plane C D. Let F 1

    be the force due to active earth pressure. The weight & its location of wedge BCD, W can be

    determined.

    The resultant of F1&W gives the required force R. Similarly if the backfill is inclined

    then the active force against plane 'CD' is lot and let it be F1. The resultant of F1& weight W is

    R which is required force againstthe wall as shown below.

    F1 = Ka H12

    15. Coulombs Analysis of lateral Earth Pressures (inclined back & inclined fill)

    .

    ''

    ''

    0''

    221

    21

    21

    221

    21

    1

    1

    baseatHHKHKP

    HKHK

    HH

    HHH

    HHCAt

    HKP

    HBAt

    AAt

    wadaha

    adah

    dv

    wsatdv

    satdv

    daa

    dv

    v

    awamaH

    amah

    m

    wsatmv

    satmv

    maa

    maamv

    av

    PHHKHKHKHK

    HH

    HHH

    HHCAt

    HKPerfaceAt

    HKPHBAt

    PAAt

    22212

    2212

    21

    221

    21

    12

    111

    ''

    int

    00

    A

    B

    C

    Ka1 mH1 H1

    Ka2 mH1

    H2

    F1

    CBA

    D

    H

    W H/3

    F1

    H/3

    R

    CBA

    D

    H

  • 8/10/2019 Lateral Earth Pres

    25/36

    - 25 -L iterature Review

    25

    In 1776 Coulomb introduced an expression for determining the active thrust on retaining walls.

    Coulomb knew about effect of both cohesion and friction on shear strength of soil. He

    observed a number of retaining wall failures and he concluded that when ever a retaining wall

    fails a certain mass of soil breaks off in the form a wedge and exerts pressure on wall thus

    concluding that the retaining wall shall be designed for the MAXIMUM pressure exerted by this

    mass of soil. Although he observed that the failure surface is not plane but for simplicity ofanalysis he assumed that the failure surface is plane and the soil is cohesion less. He did this

    in order to simplify somewhat the mathematically complex problem introduced when cohesion

    and non-planer sliding surfaces are considered. He did, however, account for the effects of

    frictional interaction between the soil backfill and the face of the retaining wall. Due to relative

    motion between soil and the wall shear forces develop at interface. In active zone the soil

    tends to move down along wall face as the wall moves away from the backfill. This downward

    motion imparts a downward drag force on the wall. The magnitude of this shear force depends

    on the friction angle between the wall & the soil wand is called angle of wall friction.

    Typically for concrete. w = 2/3

    In case of passive earth pressure the soil moves up as it is pushed by the wall & in the process

    it exerts an upward shear force on the wall. The direction of this frictional force depends on the

    direction of motion of soil mass and shall be evaluated carefully.

    16. Coulombs Assumptions

    a. Backfill is dry, cohesion less isotropic, homogeneous and elastically un-

    deformable but breakable.

    b. The slip surface is plane which passes through the heel of the wall.

    c. The sliding wedge itself acts as a rigid body and the value of earth pressure is

    obtained by considering the limiting equilibrium of sliding wedge as a whole.

    d. The position and direction of resultant earth pressure are known. The resultant

    force acts on the back of the wall at 1/3 rdthe height of the wall form the base and

    is inclined at (angle of wall friction) to the normal to the back)

    e. Back of the wall is rough and relative movement of the wall and soil takes place

    which develops frictional forces that influence the direction of resultant pressure.

    According to Coulombs theory, the thrust is induced by the sliding wedge, as shown in Fig.

    12.l0a. For this reason, it is sometimes referred to as the sliding wedge analysis. The

    corresponding force polygon is shown in Fig. 12.l0b. The development of Coulombs equation

    follows from this basic relationship. From Fig. 12.l0b, using the Law of Sines, we have

  • 8/10/2019 Lateral Earth Pres

    26/36

    - 26 -L iterature Review

    26

    Explanation of Force Polygon Angles

    W = Wt of wedge

    F = Resultant of Normal and Shear forces on the plane.

    Pa= Active Pressure.

    H = Ht of wall.

    = Inclination of back face of wall

    = Angle of force Pa with normal, friction angle between soil and wall.

    = Internal friction angle, or angle of friction with normal.

    = Angle of failure plan with horizontal.

    i = Slope of backfill with horizontal

  • 8/10/2019 Lateral Earth Pres

    27/36

    - 27 -L iterature Review

    27

  • 8/10/2019 Lateral Earth Pres

    28/36

    - 28 -L iterature Review

    28

  • 8/10/2019 Lateral Earth Pres

    29/36

    - 29 -L iterature Review

    29

    Example: A retaining wall as shown in Fig, below with soil properties. Find Paand Pp.

    Note: Solve examples 9.1-9.8 Braja M. Das (Principles of Geotechnical Engineering)

    17. Coloumbs Solution for R/W with Inclined Back and Inclined Back fill

    Consider a RW as shown below the geometry of problem has changed but will we have

    two unknown R& Fa, and one known quantity W the weight of wedge as shown.

    The vector diagram is shown above.

    By applying sine lawto force diagram.

    Fa

    CBA

    D

    H

    i

    W

    w

    Normal to

    inclined surface

    R

    - i

    -

    - w

    180-( - ) ( - w)

    W

    R

    Fa

  • 8/10/2019 Lateral Earth Pres

    30/36

    - 30 -L iterature Review

    30

    Also from sine law:

    Putting values of eqn- B in eqn- A, we get

    To determine maximum value of Fawe differentiate above equation with respect to and

    equate it to zero. The resulting equation for maximum Fais,

    18. Culmanns Method

    The following graphical procedure was devised by Karl Culmann in (1875). It is used to

    determine the magnitude and the location of the resultant earth pressures, both active and

    passive, on retaining walls. This method is applicable with acceptable accuracy to cases where

    the backfill surface is level or sloped, regular or irregular and where the backfill material is

    uniform or stratified. Also, it considers such variables as wall friction, cohesion less soils, and

    with some procedural modifications, cohesive soils and surcharge loads, both concentrated

    and uniformly distributed. It however, requires that the angle of internal friction of the soil be a

    constant for the total backfill. The procedure presented here is limited to cohesion-less soils.

    )(180

    180

    180

    &

    12

    1

    180

    180

    iSinSin

    HAD

    SinABAD

    AB

    ADSinAlso

    Sin

    HAB

    AB

    HSin

    BCADW

    ABCFrom

    ASin

    SinWF

    F

    Sin

    W

    Sin

    w

    a

    a

    w

    )(

    )(

    )(

    2

    1

    )()(

    )(

    )(

    )(

    )()(

    2

    2 BiSinSin

    iSinSinHW

    iiiSin

    iSin

    Sin

    HBC

    iSin

    iSinABBC

    iSin

    BC

    iSin

    AB

    w

    aSin

    Sin

    iSinSin

    iSinSinHF

    180)(

    )(

    2

    12

    2

    2

    12

    22

    )(2

    1

    iSinSin

    iSinSinSinSin

    SinHF

    w

    ww

    Maxa

  • 8/10/2019 Lateral Earth Pres

    31/36

    - 31 -L iterature Review

    31

    Reference is made to Fig. 12.20 in describing the procedure for determining the active

    pressure for a case of cohesion less soil by Cullmans method:-

    a. Select a convenient scale to show a representative configuration of retaining wall

    and backfill. This should include height and slope of the retaining wall, surface

    configuration of the backfill, location and magnitude of concentrated (line)

    surcharge loads, uniformly distributed surcharge, and so on.

    b. From pointA draw lineAC, which makes an angle of with the horizontal.

    c. Draw lineAD at an angle of from lineAC. Figure 12.20 shows the angle to

    be the angle between the vertical and the resultant active pressure.

    d. Draw raysAB1, AB2, AB3, and so on, that is, assumed failure surfaces.

    e. Determine the weight of each wedge, accounting for variations, if the backfill is a

    layered system, for variable moisture content, and so on.

    f. Select a convenient scale and plot these weights along lineAC. For the distance

    fromA to W1 along lineAC equals W1 similarly, from theW1 to W2 along lineAC

    equals W2, and so on.

    g. From each of the points located on lineAC, draw lines parallel to line AD, to

    intersect the corresponding assumed failure surfaces; that is, from W1 will

    intersect lineAB1, then from W2 will intersect line AB2and so on.

    h. Connect these points of intersection with a smooth line, Culmanns curve.

    i. Parallel to lineAC; draw a tangent to Culmanns curve. In Fig. 12.20 point Erepresents a tangent point. More than one tangent is possible if Culmann line isirregular.

    j. From the point of tangency, draw line EF parallel to lineAD. The magnitude of

    EF, based on the selected scale, represents the active pressure Pa. Severaltangents to the curve are possible; the largest of such values becomes the value

    of Pa. The failure surface passes through E andA, as Fig. 12.20.

    Surcharge loads and their respective effects on the location of the resultant are accounted

    for as described in the previous section. Examples 12.5 and 12.6 further enhance this

    explanation.

  • 8/10/2019 Lateral Earth Pres

    32/36

    - 32 -L iterature Review

    32

    Figure 12.21 illustrates the procedure for determining the passive resistancevia culmanns

    method.

    The approach is similar to that for the active pressure, with some notable differences:

    (1) LineAC makesan angle of ' ' degrees below rather than above the horizontal;

    (2) The reference line makes an angle of with line AC, with measured magnitude as

    indicated in Fig. 12.21.

    For the assumed sliding wedges, the weights W1, W2, and so on, are plotted along line

    AC. From these points, lines are drawn parallel to the reference line to intersect the

    corresponding rays, as shown in Fig. 12.21. The Culmann line represents a smooth curve

    connecting such points of intersection. A tangent to the Culmann curve parallel to line AC is

    drawn, with the resultant earth pressure being the scaled value of line FE, as shown in fig.

    Example: A retaining wall with backfill as shown in fig-12-22, with the given data as:-

    Ht of wall= 7 m, =30o, line load = 100 kn/m, =18.2 kn/m3, =900

    Find the active thrust by Culmans method.

    For convenient calculation of wedge weight; the bases for all the wedges are taken same.

    Hence, the weight of all the wedges equals 127.4 kN, as shown in Fig. 12.23. The

    corresponding points alongAC are shown in Fig. 12.22 for an arbitrary scale of 1 cm = 100 kN.

  • 8/10/2019 Lateral Earth Pres

    33/36

    - 33 -L iterature Review

    33

    From these points lines are drawn parallel to lineAD so as to intersect raysAB1, AB2, AB3, and

    so on. Note that a similar line is drawn for the line load by connecting these points of

    intersection with a smooth curve (Culman curve) and drawing a tangent to this curve parallel to

    lineAC, we obtain the Pa, which is equal to the corresponding scaled value FE. The scale for

    FE = 1.85 cm for 185 kN. The point where 'Pa' acts is determined as described in the

    preceding section and as shown in Fig. 12.24. Line EG is parallel to lineAC, and line GE isparallel to the failure plane. Patherefore acts at one-third distance FE from point E, a total of

    4.25 m above pointA.

    19. Design of Gravity Retaining Walls

    Retaining walls are structures used to provide stability for earth or other material whereconditions disallow the mass to assume its natural slope, and are commonly used to hold back

    or support soil banks, coal or ore piles and water.

    Retaining walls are classified, based on the method of achieving stability, into six

    principal types.

  • 8/10/2019 Lateral Earth Pres

    34/36

    - 34 -L iterature Review

    34

    a. Gravity Retaining Walls. The gravity wall depends upon its weight, as the name

    implies, for stability. The tensile stresses are avoided by proper proportioning of

    the wall.

    b. Cantilever Walls. The cantilever wall is a reinforced-concrete wall that utilizescantilever action to retain the mass behind the wall from assuming a natural slope.

    Stability of this wall is partially achieved from the weight of soil on the portion of the

    base slab.

    c. Counter fort Retaining Walls. A counter fort retaining wall is similar to a

    cantilever retaining wall, except that it is used where the cantilever is long or for

    very high pressure behind the wall and has counter forts, which tie the wall and

    breast together, built at intervals along the wall to reduce the bending moments

    and shears. As indicated in Fig, the counter fort is behind the wall and subjectedto tensile forces.

    d. Buttressed Wall. A buttressed retaining wall is in compression instead of tension

    as shown in figure.

    e. Crib Walls. These are built-up members of pieces of pre-cast concrete, metal or

    timber and are supported by anchor pieces embedded in the soil for stability.

    f. Bridge Abutments. These are retaining with wing wall extensions to retain the

    approach fill and provide protection against erosion.

    Keys

    A roach Slabs

  • 8/10/2019 Lateral Earth Pres

    35/36

    - 35 -L iterature Review

    35

    20. Gravity Retaining Walls

    a. Common Proportions

    Retaining wall design proceeds with the selection of tentative dimension, which

    are then analyzed for stability and structural requirements and are revised as

    required. Since this is trial process, several solutions to the problem may be

    obtained all of which are satisfactory. A computer solution greatly simplifies the

    work in retaining wall design and provides the only practical means to optimize

    the design.

    Gravity-wall dimensions may be taken as shown in figure below. Gravity walls,

    generally, are trapezoidal-shaped but also may be built with broken backs. The

    base and other dimensions should be such that the resultant falls within the

    middle one-third of the base. The top width of the stem should be on the order of

    0.30 m. If the heel projection is only 100 to 150 mm, the Coulmb equation may

    be used for evaluating the lateral earth pressure, with the surface of sliding taken

    along the back face of the wall. The Rankine solution may also be used on or

    along the back face of the wall. The Rankine solution may also be used on a

    section taken through the heel. Because of the massive proportions and resulting

    low concrete stresses, low-strength concrete can generally be used for the wall

    construction.

    A critical section for analysis of tensile flexure stress will occur through the junction ofthe toe portion at the front face of the wall.

    b. Stability of Wall. Gravity retaining walls must provide adequate stability againstsliding. The soil in front of the wall provides a passive-earth pressure resistanceas the wall tends to slide into it. If the soil is excavated or eroded after the wall isbuilt, the passive-pressure component is not available and sliding instability mayoccur. If there is certainty of no loss of toe soil, the designer may use the passivepressure in this zone as part of the sliding resistance. Additional sliding stabilitymay be derived from the use of a key beneath the base.

    c. Design of Gravity Retaining Wall. A gravity retaining wall is a structure whichresists lateral earth pressure by its weight.

    A retaining wall is considered safe, if it is safe against:

    (1) Overturning (2) Sliding (3) Bearing failure

    The proportioning should be such that no tension should develop anywhere in wall.

    0.5 to 0.7 H

    H

    Minimum

    batter

    1:48

    D to D

    D to D

    H/B to H/b

    0.30 m to H/12

    Slope change to

    reduce concrete

    (b)(a)

    Approach Fill

    PaPv

    a

    d

    w

  • 8/10/2019 Lateral Earth Pres

    36/36

    36

    Consider a retaining wall as shown in the figure. Let R be the reaction from base actingat distance x from toe of the wall O. The total active force can be split into its horizontal andvertical components Ph and Pv respectively. The passive earth pressure Pp is ignored since it issupporting and less. The wall will be safe against overturning if the resultant passes thoughmiddle third of the base. Taking moment of all forces about O

    Rv * x = W*a + Pv*d- Ph*b

    x = (W*a + Pv * d - Ph * b) / Rv

    Where Rv = W + Pv

    The eccentricity of R from the centre of base is given as:

    e = B/2 - xWe must ensure that e < B/6 so that there is no overturning.

    a. FOS against overturning.

    b. FOS against sliding, where = friction angle between wall

    base and soil.

    c. FOS against bearing capacity

    The maximum stress should not exceed bearing capacity of soil.

    5.1

    Re

    bP

    dPW

    gMomentOverturnin

    entsistingMomFOS

    h

    va

    5.1tan

    h

    v

    P

    RFOS

    B

    e

    B

    Rf

    B

    e

    B

    Rf

    v

    v

    61

    61

    min

    max