CEAG Sicherheitstechnik GmbH 256
■
■
■
■
■
■
■■■■
■
DescriptionLB Remote I/O modules are used as signalconditioning units between field devicesand control systems. They plug into abackplane system which is mounted ona standard DIN rail.The modules may be plugged in orremoved from a live circuit.LB Remote I/O modules offer advantagesin that they are galvanically isolated, theycan boost and amplify signals, and areeasily mounted as plug-in units. Sincethey are galvanically isolated they do notrequire equipotential earth connectionsnormally encountered with safety barriers.Changes in the power supply voltage donot affect the excellent device performancedue to the properties of the built-inamplifier circuits. Furthermore they rendersystem I/O cards superflous. Wiringbetween them and the system is reducedto a single bus.Light emitting diodes (LEDs) indicate thedevice status. A green LED shows theoperating condition, a yellow LED depictsthe switch status as in switch amplifiers,and a red LED signals alarm conditionse.g. line faults and interruptions. Thisinformation can be accessed from theDCS and PLC via a standard bus.
LB Remote I/O
1 to 3 channels just16 mm wideConsiderable savings inhardware and wiringMounts on abackplane fittedto a DIN rail(horizontally or vertically)Plug-in modulesfor analogue ordigital I/OScrew plug-in fieldconnectorsSafe galvanicisolationStatus LEDsLow power consumptionEEx ia/ib approvedSuitable for PLCand DCSInternational approvals
-
777
CEAG Sicherheitstechnik GmbH 257
2
1
43
Designed to beUser-Friendly
Substations 1Substations can be connected to processcontrol systems (DCS) and programmablecontrolers (PLC) via standard busses. They openthe gate to all major system manufacturers.MountingMounted on a simple DIN rail, the LB Remote I/Oseries backplane is a compact and rugged baseon which the various IS modules are housed.The backplane 2The modular assembly concept allows thebackplanes to be simply slotted together to formthe most desirable panel layout. At each endthere are separate end pieces for supplyingpower and all communication 4.The modules 3The compact size allows high signal packingdensity and all this without the heatingproblems associated with traditional designs.Snap in mounting, utilising the most advancedplastics technology allows the LB Remote I/Oseries modules to be located firmly without theneed for fixing screws. The field connection ismade by a coded Phoenix mini combiconconnector on the top of the module. The systemis so designed that any of the modules can beslotted into any position on the backplane so thatIS terminations are made to suite the wiring andnot the other way around.Up to eight I/O modules 3 plus a power supplymodule can be connected to each backplanesegment and depending upon the moduleTypee, either one, two, or three channels can beutilised.A large range of interface modules are availablefor all applications including SMART/HARTcompatible devices.Power supply moduleTo meet and exceed the EMC regulations aseparate PSU module supplies up to eightLB Remote I/O series interface modules. Foreach backplane segment, one power supplymodule is required to guarantee a smoothregulated power supply.Communications module 4The communications module is the linkbetween the intrinsically safe I/O modulesand the control system. The unit can handleup to 48 I/O modules and is available in variousbus formats. The unit is located on the lefthand side of the first backplane segment.
-
CEAG Sicherheitstechnik GmbH 258
LB Remote I/O series softwareThe LB Remote I/O interface modules have nointernal or external switches or adjustments.The configuration can be done either by thecontrol system or by an easy to use WINDOWSprogram via the local RS 485 port on theLocal Bus backplane. The setup data for everymodule is stored in a non volatile memorylocated within the communications module.Self generating documentationThe free of charge LB Remote I/O seriessoftware uses the configuration data togenerate a full system documentation package.Considerable time and cost savings can berealised by utilising this feature.Plug and play serviceBecause the I/O setup data for every moduleis already stored, should a fault developwithin a module, it can easily be removedand replaced by a standard unprogrammedI/O module.As soon as the new unit is inserted, thecommunication module instantly updates thenew I/O module and within a fraction of asecond the device is back in operation. Thisscenario also applies to the communicationsmodule. However, a download of configurationdata is required either from the control system
Fast- andUser-FriendlySetup
or from a PC using the LB Remote I/O back-plane’s RS 485 port.Layered redundancyAs every control system has its own individualrequirements, the LB Remote I/O series has amodular approach to redundancy.Due to the LB Remote I/O series hardwaredesign, the power supply and the LB Remote I/Oare not regarded as being susceptible to majorsystem failure. The critical areas of concern arethe control system fieldbus and the commun-ications module.The LB Remote I/O series can overcome theseconcerns by offering a ”layered” solution.Redundant fieldbusAn option for ensuring fieldbus communi-cations is to have one communications modulewith two fieldbus connections, thus ensuringan effective redundant link to the controlsystem.Redundant communication moduleThe LB Remote I/O series communicationsmodules can, if required, be placed in parallelto give a higher level of system redundancy.Signal processingThe LB Remote I/O series interface units have aunique way of handling signals to and from thefield.
The LB Remote I/O series I/O modules convertincoming field signals to an internal LB RemoteI/O format. This also works in reverse foroutgoing signals.One function of the communications moduleis to supervise a rapid data exchange betweenall of the I/O modules and itself. At any time,an internal memory within the communicationsmodule, holds all the field signal data.The second function of the memory within thecommunications module, is to allow the controlsystem’s fieldbus to access and exchangeinformation.As the memory is the only interface between theLB Remote I/O and the control system fieldbus,future fieldbus developments in this area can beaccommodated easily.HART communicationThe LB Remote I/O series supports HARTcommunication. If the control system supportsHART communication it is then possible tocommunicate directly with the field devices.In addition to this, a RS 485 connection isavailable on the LB Remote I/O series back-plane which allows the user to access theHART field devices via a PC using standardsoftware.Local intelligenceThe LB Remote I/O series is capable ofconducting certain functions locally, withoutinvolving the external fieldbus connection to thecontrol system. This allows the system to reactquickly to time critical operations. The functionsare limited to redistributing data from an input toone or more outputs and in addition, withanalogue signals it is possible to perform tripfunctions.Line fault detectionAll LB Remote I/O series I/O modules have asophisticated Line Fault Detection System.This feature can be enabled or disabled foreach channel individually.On detecting a line fault on a channel, thefollowing events occur:• Red LED indication on I/O module• The input or output signal is taken to a
pre-determined level• A flag is set within the memory of the
communication module• A relay output within the communications
module is deenergised, allowing the controlsystem to perform an interrupt routine
PROFIBUS PAPower supplies for PROFIBUS PA, H1devices are envisaged for future expansions.
PROFIBUSDP, FMSMODBUS
Memory
Bus
I/OI/O I/O
Bus
LB Remote I/O
Bus Bus Bus
871 24 V DCPowerSupply
IS field equipment
Memory MemoryI/OI/O I/O
LB Remote I/O
Bus Bus
9-1624 V DCPowerSupply
IS field equipmentPROFIBUSDP, FMSMODBUS
Bus Bus Bus
1 8
Bus
24 V DCPowerSupply
Bus
Substation with1-48 I/O modulesand redundant bus
Substation with1-46 I/O modulesand redundantcomm. unit
-
777
CEAG Sicherheitstechnik GmbH 259
LB Remote I/O
Selection chart
Application Type Preferred version Page
2 channels LB 1101 GHG 127 0000 A1101 262fullyisolated
3 channels LB 1102 GHG 127 0000 A1102 263commonpositive
1 channel LB 1103 GHG 127 0000 A1103 2640-15 kHzfrequency, directionof rotation,dosing counter
Non SMART LB 3101 GHG 127 0000 A3101 26615 V supply
SMART/HART LB 3102 GHG 127 0000 A3102 267supply 16.5 V
SMART/HART LB 3103 GHG 127 0000 A3103 268supply 15 V
1 channel LB 210X GHG 127 0000 A210X 265with 2 positionfeedbacks
for valvesof most commonlyused suppliers
1 channel LB 4101 GHG 127 0000 A4101 269800 Ω
SMART/HART1 channel LB 4102 GHG 127 0000 A4102 270800 Ω
1 channel LB 4103 GHG 127 0000 A4103 271400 Ω
Accessories see page 276-279
Switch
Procimity switch
Electronic switch
Dig
ital
inp
ut
4-20 mATransmitter
Ana
log
inp
ut
0/4-20 mACurrent source
Solenoid valve
LED
4-20 mAI/P converter
positioner
Ana
log
out
put
Display
Sounders
Dig
ital
out
put
-
CEAG Sicherheitstechnik GmbH 260
LB Remote I/O
Selection chart
Application Type Preferred version Page
2-/3-/4-wire RTD LB 5101 GHG 127 0000 A5101 272
Thermocouples LB 5102 GHG 127 0000 A5102 273
2 Non IS LB 6101 GHG 127 0000 A6101 274relays fortrip pointsor Ex-d valves
Analog output LB 4101 GHG 127 0000 A4101 269bridge supply
plus
millivolt amplifier LB 5102 GHG 127 0000 A5102 273
set to LB 8101 GHG 127 0000 A8101 275PROFIBUS
␣ PROFIBUS DP, set to LB 8102 GHG 127 0000 A8102 275 ␣ FMS, MODBUS ␣ MODBUS RTU
Accessories see page 276-279
Tem
per
atur
e in
put
sTr
ip p
oin
ts
Relay contact
Communicationunit
Co
mm
unic
atio
n
Strain gauge
Sp
ecia
l tas
ks
-
777
CEAG Sicherheitstechnik GmbH 261
16.5 ±0,1±0,1
55 55165
119
LB 1101 - 9111Technical data
16
99.5
32
96
Modules
Backplane-Segments
Dimensions in mm
Dimensions in mm
General dataMax. number of I/O modules per backplane 48
defined by theMax. number of backplanes per system fieldbus spec.Power supply 24 V DC (20... 30 V)Start-up condition for each LB 9104 15 x nominal current for 20 ms
Conversion and transfer timeBetween field connector and communication interface memory:For analog signals < 20 msecFor digital signals < 5 msecFor temperature < 100 ms
Ambient condtionsOperating temperature - 20 0C ... 60 0CStorage temperature - 40 0C ... 80 0CRelative humidity < 75 % average, no condensation
HART communicationIf the external fieldbus to the DCS supports HART communication, the LB Remote I/O productstransfer the HART signals properly to the field units.
Each communication interface has an RS 485 HART interface. Suitable for software issued withfield devices including CORNERSTONE, AMS, SMARTVISION, KSMART etc.
-
CEAG Sicherheitstechnik GmbH 262
LB 1101Digital input
1 2
Local Bus
3 4 5 6+ + --
CH 1 CH 2
Product features• Inputs for contacts, NAMUR - proximity
switches and optocouplers• Galvanic isolation between both
inputs and the LB Remote I/O• 2 channel device• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
Input:contacts and 2 wireSignal Type NAMUR proximity switcheson > 2.1 mASwitching points off < 1.2 mA
Hysteresis 0.2 mAFrequency 0 - 100 HzPower dissipation 0.6 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 12.6 VSafety values Isc ≤ 12.7 mA
Ordering detailsType Order No.
Digital input IS LB 1101 GHG 127 0000 A1101Digital input LB 1001 GHG 127 0000 A1001
Status table, configuration parameters
Name Format (bit) DescriptionC1_STAT@TagNr 1 Input status, channel 1C2_STAT@TagNr 1 Input status, channel 2LFD_C1_G@TagNr 1 LFD status, channel 1 (1=fault)LFD_C2_G@TagNr 1 LFD status, channel 2 (1=fault)LFD_C1_S@TagNr 1 LFD on, channel 1 (1=active)LFD_C2S@TagNr 1 LFD on, channel 2 (1=active)
LB Remote I/O
-
777
CEAG Sicherheitstechnik GmbH 263
LB 1102Digital Input
• Inputs for contacts, NAMUR - proximityswitches and optocouplers
• Galvanic isolation between inputsand the LB Remote I/O
• 3 channel device• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
Input:contacts or 2 wireSignal Type NAMUR proximity switcheson > 2.1 mASwitching points off < 1.2 mA
Hysteresis 0.2 mAFrequency 0 - 100 HzPower dissipation 0.5 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 10.5 VSafety values Isc ≤ 32.6 mA
Ordering detailsType Order No.
Digital input IS LB 1102 GHG 127 0000 A1102Digital input LB 1002 GHG 127 0000 A1002
Status table, configuration parameters
Name Format (bit) DescriptionC1_STAT@TagNr 1 Input status, channel 1C2_STAT@TagNr 1 Input status, channel 2C3_STAT@TagNr 1 Input status, channel 3LFD_C1_G@TagNr 1 LFD status, channel 1 (1=fault)LFD_C2_G@TagNr 1 LFD status, channel 2 (1=fault)LFD_C3_G@TagNr 1 LFD status, channel 3 (1=fault)LFD_C1_S@TagNr 1 LFD on, channel 1 (1=active)LFD_C2_S@TagNr 1 LFD on, channel 2 (1=active)LFD_C3_S@TagNr 1 LFD on, channel 3 (1=active)
5 6-
1 2 3 4+ + + - -
CH 2CH 1 CH 3
Local Bus
Product features
LB Remote I/O
-
CEAG Sicherheitstechnik GmbH 264
LB 1103Digital input
• Frequency in, counter, direction of rotation• Inputs for contacts,
NAMUR - proximity switchesand optocouplers
• Galvanic isolation• Counter or frequency input• Overflow indication• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line monitor
Input:contacts and 2 wireSignal type NAMUR proximity switcheson > 2.1 mASwitching points off < 1.2 mA
Hysteresis 0.2 mAFrequency 0-15 KHzPower dissipation 0.6 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 12.6 VSafety values Isc ≤ 23.3 mA
Ordering detailsType Order No.
Digital input IS LB 1103 GHG 127 0000 A1103Digital input LB 1003 GHG 127 0000 A1003
Status table, configuration parameters
Name Format (bit) DescriptionC1_STAT@TagNr 1 Input status, channel 1CNT_VAL@TagNr 16 Counter/frequency outputLFD_C1_G@TagNr 1 LFD status, channel 1 (1=fault)LFD_C1_S@TagNr 1 LFD on, channel 1 (1=active)MOD_S@TagNr 1 Mode (0=counter)CNT_UD_S@TagNr 1 Counting direction (0=up)CNT_S@TagNr 1 Stop bit counterCNT_DIV@TagNr 8 2n divider (1-64)CNT_OVL@TagNr 1 OverflowCNT_SD_S@TagNr 1 Static/dynamic (0=static)CNT_FIX@TagNr 6 Set counter
Product features
direction ofrotation only
1 2
Local Bus
3 4 5 6+ - + -
CH 1
0000
LB Remote I/O
-
777
CEAG Sicherheitstechnik GmbH 265
ValveLEDAlarm
1 2
Local Bus
3 4 5 6+ + + - - -
CH 1 CH 2
LB 2101 - 2113Digital Output
U0R
a
Product features
Input:Sensor loops as per LB 1101
Output:LFD 100 Ω ..... 1000 ΩPower dissipation 0.52 W
Explosion protection:Approval PTB-No. Ex-95.D.2163Output loops Category [EEx ia] IICSensor loops Voc ≤ 10.5 V, Isc ≤ 12 mA
Ordering detailsVoutmin Routmin Current lim. VOC ISC Type Order No.
22.0 V 315 Ohm 50 mA 24.9 V 93 mA LB 2101 GHG 127 0000 A210124.0 V 210 Ohm 75 mA 27.8 V 185 mA LB 2102*) GHG 127 0000 A210224.0 V 360 Ohm 50 mA 27.8 V 93 mA LB 2103 GHG 127 0000 A210322.0 V 220 Ohm 50 mA 24.2 V 146 mA LB 2104 GHG 127 0000 A210422.8 V 290 Ohm 50 mA 25.2 V 110 mA LB 2105 GHG 127 0000 A210516.5 V 115 Ohm - 18.7 V 282 mA LB 2106 GHG 127 0000 A210616.5 V 170 Ohm - 18.7 V 143 mA LB 2107 GHG 127 0000 A210714.0 V 122 Ohm - 15.8 V 172 mA LB 2108 GHG 127 0000 A210811.4 V 115 Ohm - 12.6 V 147 mA LB 2109 GHG 127 0000 A2109 6.8 V 78 Ohm - 7.9 V 145 mA LB 2110 GHG 127 0000 A2110 4.0 V 50 Ohm - 4.9 V 200 mA LB 2111 GHG 127 0000 A211125.3 V 329 Ohm - 28.0 V 110 mA LB 2112 GHG 127 0000 A211226.7 V 509 Ohm - 28.7 V 70 mA LB 2113 GHG 127 0000 A211324.0 V 210 Ohm 75 mA - - LB 2002 GHG 127 0000 A2002(*only group II B)
Status table, configuration parameters
Name Format (bit) DescriptionOUT_@TagNr 1 OutputC1_STAT@TagNr 1 Input status 1C2_STAT@TagNr 1 Input status 2CON_S@TagNr 1 Enable local connection (1=active)CONTYPE_S@TagNr 3 Type of local connection (2=analog; 3= digital)CONOUT_S@TagNr 1 Output (0=normal; 1=inverted)CONCHA_S@TagNr 3 Local connection channelCONDEV_S@TagNr 6 Local connection address,, 0.. 47CONHYS_S@TagNr 16 Local connection hysteresisCONVAL_S@TagNr 16 Local connection limit valueLFD_V_G@TagNr 1 LFD status, output (1=fault)LFD_C1_G@TagNr 1 LFD status, input 1 (1=fault)LFD_C2_G@TagNr 1 LFD status, input 2 (1=fault)
LB Remote I/O
• Solenoid valve driver withvalve position feedback
• Galvanic isolation• Drives LEDs and sounders
• 1 Digital output to solenoid2 digital inputs valve position
• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
-
CEAG Sicherheitstechnik GmbH 266
LB 3101Analog InputTransmitter Power Supply
1 2
Local Bus
3 4 5 6
+-
4- 20 mA
+-
4- 20 mA
+
-
Product features
• Power supply for 2 and 3 wire4-20 mA transmitters
• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
Input:Field device power supply 15 V (20 mA)Input range 4-20 mAInput impedance 50 ΩLinearity < 0.1 %Temperature drift < 0.1 % / 10 K
min. 1 mALine monitor max. 25 mA programmablePower dissipation 1 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 23.8 VSafety values Isc ≤ 90 mA
Ordering detailsType Order No.
Transmitter supply IS LB 3101 GHG 127 0000 A3101
Status table, configuration parameters
Name Format (bit) DescriptionIN_G@TagNr 12 InputLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)
LB Remote I/O
-
777
CEAG Sicherheitstechnik GmbH 267
LB 3102SMART/HARTAnalog InputTransmitter Power Supply
Product features• Power supply for 2- and 3-wire
4-20 mA transmitters• HART compatible• SMART communication via fieldbus,
local RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval
Line fault detection
Input:Field device power supply 16.5 V (20 mA)Input range 4-20 mAInput impedance 50 ΩLinearity < 0.1 %Temperature drift < 0.1 % / 10 K
min. 1 mALFD max. 25 mA programmablePower dissipation 1 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 23.8 VSafety values Isc ≤ 90 mA
Ordering detailsType Order No.
HART/SMART analog input IS LB 3102 GHG 127 0000 A3102HART/SMART analog input LB 3002 GHG 127 0000 A3002
Status table, configuration parameters
Name Format (bit) DescriptionIN_G@TagNr 12 InputLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)
LB Remote I/O
-
CEAG Sicherheitstechnik GmbH 268
LB 3103SMART/HARTAnalog InputTransmitter Power Supply
Input:Field device power supply 15 V (20 mA)Input range 4-20 mAInput impedance 50 ΩLinearity < 0.1 %Temperature drift < 0.1 % / 10 K
min. 1 mALFD max. 25 mA programmablePower dissipation 1 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 24 VSafety values Isc ≤ 76 mA
Ordering detailsType Order No.
SMART/HART analog input IS LB 3103 GHG 127 0000 A3103
Status table, configuration parameters
Name Format (bit) DescriptionIN_G@TagNr 12 InputLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)
Product features• Power supply for 2- and 3-wire
4-20 mA transmitters• HART compatible• SMART communication via fieldbus,
local RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
LB Remote I/O
-
777
CEAG Sicherheitstechnik GmbH 269
1 2
Local Bus
3 4 5 6
I
4- 20 mA
LB 4101Analog Output
Product features• Output isolator for 4-20 mA I/P converters,
indicators, positioners• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
Output:Max. load 750 ΩI 4-20 mAImin./max. 1/25 mALinearity < 0.1 %Temperature drift < 0.1 % / 10 KLFD > 850 Ω ... 4 kΩPower dissipation 0.6 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 27.3 VSafety values Isc ≤ 87 mA
Ordering detailsType Order No.
Analog output IS LB 4101 GHG 127 0000 A4101
Status table, configuration parameters
Name Format (bit) DescriptionOUT@TagNr 12 OutputCON_DEV@TagNr 6 Local connection addressCON_AKT@TagNr 1 Enable local connectionLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)
LB Remote I/O
-
CEAG Sicherheitstechnik GmbH 270
LB 4102SMART/HARTAnalog Output
Product features• Output isolator for 4-20 mA I/P converters,
indicators, positioners• HART compatible• SMART communication via fieldbus, local
RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
Output:Max. load 750 ΩI 4-20 mAImin./max. 1/25 mALinearity < 0.1 %Temperature drift < 0.1 % / 10 KLFD > 850 Ω ... 4 kΩPower dissipation 0.60 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 27.3 VSafety values Isc ≤ 87 mA
Ordering detailsType Order No.
SMART/HART analog output IS LB 4102 GHG 127 0000 A4102SMART/HART analog output LB 4002 GHG 127 0000 A4002
Status table, configuration parameters
Name Format (bit) DescriptionOUT@TagNr 12 OutputCON_DEV@TagNr 6 Local connection addressCON_AKT@TagNr 1 Enable local connectionLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)
1 2
Local Bus
3 4 5 6
HCC
I
4- 20 mA
LB Remote I/O
-
777
CEAG Sicherheitstechnik GmbH 271
LB 4103Analog Output
Product features• Output isolator for 4-20 mA I/P converters,
indicators, positioners• Especially designed for conventional actuators
or displays with special requirements to theintrinsically safe circuits
• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
Output:Max. load 400 ΩI 4-20 mAImin./max. 1/25 mALinearty < 0.1 %Temperature drift < 0.1 % / 10 KPower dissipation 0.6 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 12 VSafety values Isc ≤ 93 mA
Ordering detailsType Order No.
Analog output IS LB 4103 GHG 127 0000 A4103
Status table, configuration parameters
Name Format (bit) DescriptionOUT@TagNr 12 OutputCON_DEV@TagNr 6 Local connection addressCON_AKT@TagNr 1 Enable local connectionLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)
LB Remote I/O
1 2 3 4 5 6
I
4- 20 mA
-
CEAG Sicherheitstechnik GmbH 272
LB 5101RTD Transmitter
Product features• 2-, 3-, 4-wire RTD (temperature)• Configuration via fieldbus, local
RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection
Input:Range 10 - 400 ΩSmallest span 20 ΩWire resistance 50 ΩNon linearity < 0.1 %Temperature drift < 0.1 % / 10 KSensor current 200 µAPower dissipation 0.52 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 2.7 VSafety values Isc ≤ 10.6 mA
Ordering detailsType Order No.
RTD transmitter IS LB 5101 GHG 127 0000 A5101RTD transmitter LB 5001 GHG 127 0000 A5001
Status table, configuration parameters
Name Format (bit) DescriptionIN_@TAGNr 12 InputTA_S@TagNr 1 Temperature (0=°C; 1=°F)NF_S@TagNr 1 Filter (0=50 Hz; 1= 60 Hz)M_MOD_S@TagNr 8 Mode (0=2 wire; 1=3 wire; 2=4 wire)M_SEN_S@TagNr 8 Sensor (1=PT 100)M_STRT_S@TagNr 16 Beginning of range in °CM_END_S@TagNr 16 End of range in °C
LFD filter timeM_DLY_S@TagNr 8 static (1=0; 2=250; 3=500; 4=1000; 5=2000 ms)
dynamic (1=0; 2=40; 3=80; 4=160; 5=320 ms)M_WIRE_S@TagNr 16 LFD at 2 wire (0..100)LFD_S@TagNr 1 LFD on (1=active)LFD_G@TagNr 1 LFD status (1=fault)
Burn out drive (0=20 %; 1=100 %; 2=1 %;LFD_BA_S@TagNr 2 3=frozen)
1 2 3 4 5 6
mV
Local Bus
2 Ltr.
3 Ltr.
4 Ltr.
LB Remote I/O
2-wire
3-wire
4-wire
-
777
CEAG Sicherheitstechnik GmbH 273
LB 5102ThermocoupleTransmitter, mV
Product features• Transmitter for all thermocouples• mV Input• Configuration via fieldbus, local RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval
Input:Range all thermocouples -75 mV .... + 75 mVCompensation internal (at connector) or externalNon linearty < 0.1 % (at 5 mV span)Temperature drift < 0.1 % / 10 KLFD > 1 kΩPower dissipation 0.52 W
Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163
Voc ≤ 1.8 VSafety value Isc ≤ 21.6 mA
Ordering detailsType Order No.
Thermocouple transmitter IS LB 5102 GHG 127 0000 A5102Thermocouple transmitter LB 5002 GHG 127 0000 A5002
Status table, configuration parameters
Name Format (bit) DescriptionIN_@TAGNr 12 InputTA_S@TagNr 1 Temperature (0=°C; 1=°F)NF_S@TagNr 1 Filter (0=50 Hz; 1= 60 Hz)M_MOD_S@TagNr 8 Mode (0=2 Leit.; 1=3 Leit.; 2=4 Leit.)M_SEN_S@TagNr 8 Sensor (1=PT 100)M_STRT_S@TagNr 16 Beginning of range in °CM_END_S@TagNr 16 End of range in °C
LFD filter timeM_DLY_S@TagNr 8 static (1=0; 2=250; 3=500; 4=1000; 5=2000 ms)
dynamic (1=0; 2=40; 3=80; 4=160; 5=320 ms)M_EXT_S@TagNr 16 CJC extern 0.00 ... 500.00, 1.00CLFD_S@TagNr 1 LFD on (1=active)LFD_G@TagNr 1 LFD status (1=fault)
Burn-out drive (0=20 %; 1=100 %; 2=1 %;LFD_BA_S@TagNr 2 3=frozen)
1 2 3 4 5 6
mV
FB Remote I/O
CJC
+ -
RTDVST
LB Remote I/O
-
CEAG Sicherheitstechnik GmbH 274
Product features• Relay output• 2 channel• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Self monitoring• System output or local connection for
Ex-d valves, trip points, and generalswitching functions
Output:Relay ratingUmax. 250 V AC / 150 V DCImax.. 1 A AC / DCSwitch power Pmax. 60 VA / 30 WResponse time < 10 msPower dissipation 0.65 W
Ordering detailsType Order No.
Relay output LB 6101 GHG 127 0000 A6101
Status table, configuration parameters
Name Format (bit) DescriptionCON_R1_S@TagNr 1 Enable local connection relay 1CONTYP_1S@TagNr 3 Type of local connection (2=analog; 3=digital) rel. 1CONOUT_1S@TagNr 1 Output (0=normal; 1=inverted) relay 1CONCHA_1S@TagNr 3 Local connection channel relay 1CONDEV_1S@TagNr 6 Local connection address 0..47 relay 1CONHYS_1S@TagNr 8 Local connection hysteresis relay 1CONVAL_1S@TagNr 16 Local connection limit value relay 1CON_R2_S@TagNr 1 Enable local connection relay 2CONTYP_2S@TagNr 1 Type of local connection (2=analog; 3=digital) rel. 2CONOUT_2S@TagNr 1 Output (0=normal; 1=inverted) relay 2CONCHA_2S@TagNr 3 Local connection channel relay 2CONDEV_2S@TagNr 6 Local connection address 0..47 relay 2CONHYS_2S@TagNr 8 Local connection hysteresis relay 2CONVAL_2S@TagNr 16 Local connection limit value relay 2
5 61 2 3 4
LB Remote I/O
CH 1
LB 6101Relay Output
CH 2
-
777
CEAG Sicherheitstechnik GmbH 275
Ordering detailsType Order No.
PROFIBUS communication interface (standard) LB 8101 GHG 127 0000 A8101MODBUS communication interface (standard) LB 8102 GHG 127 0000 A8102PROFIBUS communication interface redundancy LB 8103 GHG 127 0000 A8103MODBUS communication interface redundancy LB 8104 GHG 127 0000 A8104Other communication interfaces
LB 8101 - LB 8104CommunicationInterface
Product features• Non volatile configuration and parameter
memory• HART compatible• Integrated redundancy features
using 2 busses
Technical dataPROFIBUS: DP, FMS
Fieldbus connection MODBUS: ASCII, RTUother upon enquiryMODBUS: 9.6 Kbaud, 19.2 KbaudTransfer rate PROFIBUS: 9.6 Kbaud...1.5 Mbaud
Power dissipation 2 W
Bus length/transmission rateDepending on the standard employed for the bus, 31-127 substations can be connected to onebus line. Fibre optic links allow you to extend the cable length beyond the figures in the table. Thisalso applies for systems using repeaters.
Bus- max. cableprotocol transmission length
MODBUS 38.4 kbit/s 1200 m19.2 kbit/s 9.6 kbit/s
PROFIBUS 1500 kbit/s 200 mFMS, DP 500 kbit/s 400 m
187.5 kbit/s 1000 m 93.75 kbit/s 1200 m 19.2 kbit/s 9.6 kbit/s
Bus structure
1488 sensors/actors or 4464 digital loops or any combination of the two can operate on a singlebus line
Status table, configuration parameters
Name Format (bit) DescriptionBA@ 8 BusaddressND@ 8 Data
• phase 2 redundancyusing 2 comm. units
Bus- max. cable protocol transmission length
PROFIBUS 31.75 kbit/s 1900 m PA, H1
Servicebus 9.6 kbit/s 1200 m MODBUS
LB Remote I/O
Substation 1
LB Remote I/O
Substation n
LB Remote I/O
Substation 31
PLCDCS
•••
Memory
µP µP
LB Remote I/O
FieldbusConfig.HART Redundancy
LB Remote I/O
Memory
Bus 2
Comm. Unit 1 Comm. Unit 2
-
CEAG Sicherheitstechnik GmbH 276
1
2
3
4
5
67
8
4
Product features• Backplane segments for up to 8
I/O modules
LB 9101 - 9199Backplane Segments,Accessories
Configuration table1 Fieldbus connection 12 Fieldbus connection 23 HART/configuration/service bus4 Supply terminals5 LFD relay contacts6 LB 9102 left end segment7 LB 9101 backplane segment8 LB 9103 right end segment
Ordering detailsType Ex-i Order number
LB 9007 Front connector (screw fixing/green) GHG 127 0000 A 9007LB 9008 Cover for front connector (green) GHG 127 0000 A 9008LB 9011 Front connector (screw fixing for TC/green) GHG 127 0000 A 9011LB 9012 Voltage divider for 10 V inputs GHG 127 0000 A 9012LB 9099 Dummy I/O with terminals GHG 127 0000 A 9099LB 9101 Backplane Segment GHG 127 0000 A 9101LB 9102 Left End Segment GHG 127 0000 A 9102LB 9103 Right End Segment GHG 127 0000 A 9103LB 9104 Power Supply Module (1 unit per LB 9101 required) GHG 127 0000 A 9104LB 9107 Front Connector (fixed with screw) X GHG 127 0000 A 9107LB 9108 Cover for front connector (blue) X GHG 127 0000 A 9108LB 9109 DIN A4 sheet for TAG-numbers GHG 127 0000 A 9109LB 9110 SUB D Connector (for bus cable) GHG 127 0000 A 9110LB 9111 Front Connector (fixed with screw for TC) X GHG 127 0000 A 9111LB 9114 Configuration cable GHG 127 0000 A 9114LB 9121 Redundancy backplane with 6 I/O slots GHG 127 0000 A 9121LB 9151 Extension cable for 2 rows, 450 mm GHG 127 0000 A 9151LB 9152 Extension cable for 2 rows, 600 mm GHG 127 0000 A 9152LB 9153 Extension cable for 2 rows, 770 mm GHG 127 0000 A 9153LB 9198 Dummy (double width) GHG 127 0000 A 9198LB 9199 Dummy I/O with terminals X GHG 127 0000 A 9199
products in bold print are available from stock
• Expandable up to6 backplane segments
LB 9104Power Supply Module
LB 8101/8102Interface
-
777
CEAG Sicherheitstechnik GmbH 277
Engineering Aids
SubstationsSubstations are fitted with 1-48 I/Omodules which can be arranged in anydesired order. This will lead to the spacerequirements shown adjacent. Power isconnected on the left and right hand endsegments.
max. configuration mounted vertically or horizontally using 6 backplane segments for 48 I/O modules
1100 mm + 2 x 6 m m
24 V
24 V
LB 9101LB 9102
LB 810X LB 9104 LB 9104LB 9104LB 9104LB 9104LB 9104
LB 9103
Com
.
Pow
er
Pow
er
Pow
er
Pow
er
Pow
er
Pow
er
LB 9101LB 9101LB 9101LB 9101LB 9101
5 backplane segments mounted vertically or horizontally for 40 I/O modules
935 mm + 2 x 6 m m
24 V
24 V
LB 9101LB 9102
LB 810X LB 9104 LB 9104LB 9104LB 9104LB 9104
LB 9103
Com
.
Pow
er
Pow
er
Pow
er
Pow
er
Pow
er
LB 9101LB 9101LB 9101LB 9101
4 backplane segments mounted vertically or horizontally for 32 I/O modules
770 mm + 2 x 6 m m
24 V
24 V
LB 9101LB 9102
LB 810X LB 9104 LB 9104LB 9104LB 9104
LB 9103
Com
.
Pow
er
Pow
er
Pow
er
Pow
er
LB 9101LB 9101LB 9101
3 backplane segments for 24 I/O modules
605 mm + 2 x 6 m m
24 V
24 V
LB 9101LB 9102
LB 810X LB 9104 LB 9104LB 9104
LB 9103
Com
.
Pow
er
Pow
er
Pow
er
LB 9101LB 9101
2 backplane segments for 16 I/O modules
440 mm + 2 x 6 m m
24 V
24 V
LB 9101LB 9102
LB 810X LB 9104 LB 9104
LB 9103
Pow
er
Pow
er
LB 9101
Com
.
1 segment for 8 I/O
275 mm + 2 x 6 m m
24 V
24 V
LB 9101LB 9102
LB 810X LB 9104
LB 9103
Pow
er
Com
.
777
277
-
CEAG Sicherheitstechnik GmbH 278
Engineering AidsAccessories
Mounting accessoriesExtensions LB 915X are used for mounting2 rows of a substation horizontally aboveone another.
770 mm bus extension for 6 segments in 2 rows withleft and right end segments
600 mm bus extension LB 9152 for4 segments in 2 rows with left and rightend segments.
RedundancyCommunication units feature 3 galvan. isolateddata links. Two of these can be used asredundant buses. Maximum redundancy isachieved using 2 communication units.
Cabinets 800 x 400 x 2000Horizontal mounting of8 rows with 3 backplanes 192 I/OVertical mounting of3 rows with 9 backplanes 192 I/O
PlugsSensors and actuators are adapted via front endscrew plug-in connectors.
Bus connection/power supplyThe bus is wired to the left end segment. Powerline terminals are to be connected at the left andright end segments.
Cold junction compensation/codingA connector with built-in cjc is available forthermocouple measurements. Connectors canbe coded mechanically to avoid mix-ups.
Cabinets 800 x 600 x 2000Front and rear accessHorizontal mounting of2 x 8 rows with 3 backplanes 384 I/OVertical mounting2 x 3 rows with 9 backplanes 384 I/O
CabinetsLB Remote I/O products can be mounted instandard cabinets. 384 I/O modules can befitted depending on cabinet size. A combinationwith PLC components in the samecabinet is also possible.
left end segmentLB 9102
right end segmentLB 9103
COMBICON plug
covered screwplug-inconnector screw plug-in
connector
cover
screw plug-inconnector
multicore
b
a
LB 1101
Kodierfahne
TAG #
RTD cold junctioncompensation forthermocouples LB 9111
24 V
24 V
24 V
24 V
LB 9101 LB 9101
LB 9102
LB 9103
LB 9101 LB 9101
LB 9152
24 V
24 V
24 V
24 V
LB 9101 LB 9101LB 9101
LB 9102
LB 9103
LB 9101LB 9101 LB 9101
LB 9153
LB 9153
LB 9153
LB 9152
LB 9152
24 V
LB 9121 LB 9101LB 9102
2 x LB 810X LB 9104
NE
TZ
KO
PP
LE
R
KO
PP
LE
R
278
codingstrip
Co
m.
Co
m.
Po
wer
-
777
CEAG Sicherheitstechnik GmbH 279
Bus
ZONE 1
Accessories
Type Cable entry Terminals/type Order No.
GHG 721 1 Screw terminals1xM40 for Ø 16-28 mm 48 x 2.5 mm2 + 25 PA6xM32 for 4 x Ø 4.5-7 mm Ex-i type GHG 721 1001 R0013
Screwless terminals1xM40 for Ø 16-28 mm 48 x 2.5 mm2 + 25 PA6xM32 for 4 x Ø 4.5-7 mm Ex-i type GHG 721 1001 R0017
GHG 745 Screw terminals1 x M50 for Ø 21-35 mm 60 x 2.5 mm2 + 31 PA8 x M32 for 4 x Ø 4.5-7 mm Ex-i type GHG 745 0201 R0012
Screwless terminals1 x M50 for Ø 21-35 mm 60 x 2.5 mm2 + 31 PA8 x M32 for 4 x Ø 4.5-7 mm Ex-i type GHG 745 0201 R0016
Junction box:
Type Cable entry Terminals/type Order No.
GHG 791 01 Screw terminals1 x M25 for Ø 8-17 mm 6 x 2.5 mm2 + 3 PA1 x M25 for 2 x Ø 4.5-7 mm Ex-i type GHG 791 0101 R0004
Screwless terminals1 x M25 for Ø 8-17 mm 6 x 2.5 mm2 + 3 PA1 x M25 for 2 x Ø 4.5-7 mm Ex-i type GHG 791 0101 R0008
Screw terminalsGHG 791 02 1 x M25 for Ø 8-17 mm 12 x 2.5 mm2 + 4 PA
1 x M32 for 4 x Ø 4.5-7 mm Ex-i type GHG 791 0201 R0009
Screwless terminals1 x M25 for Ø 8-17 mm 12 x 2.5 mm2 + 4 PA1 x M32 for 4 x Ø 4.5-7 mm Ex-i type GHG 791 0201 R0013
LB Remote I/OAnalog and digital inputs and outputsare wired to junction boxes. From theremulticore cables take the loops todistribution boxes.The signals then reach the intrinsically safesignal conditioning equipment individually.The interface consists of galvanicallyisolated bus modules mounted on aDIN rail.A serial data link ensures communicationbetween the substation and the DCS orPLC via a standard bus.You can expect considerable savings inengineering, I/O modules, marshalling andwiring.
Distribution box:
I/O