CEAG Sicherheitstechnik GmbH 256 Description LB Remote I/O modules are used as signal conditioning units between field devices and control systems. They plug into a backplane system which is mounted on a standard DIN rail. The modules may be plugged in or removed from a live circuit. LB Remote I/O modules offer advantages in that they are galvanically isolated, they can boost and amplify signals, and are easily mounted as plug-in units. Since they are galvanically isolated they do not require equipotential earth connections normally encountered with safety barriers. Changes in the power supply voltage do not affect the excellent device performance due to the properties of the built-in amplifier circuits. Furthermore they render system I/O cards superflous. Wiring between them and the system is reduced to a single bus. Light emitting diodes (LEDs) indicate the device status. A green LED shows the operating condition, a yellow LED depicts the switch status as in switch amplifiers, and a red LED signals alarm conditions e.g. line faults and interruptions. This information can be accessed from the DCS and PLC via a standard bus. LB Remote I/O 1 to 3 channels just 16 mm wide Considerable savings in hardware and wiring Mounts on a backplane fitted to a DIN rail (horizontally or vertically) Plug-in modules for analogue or digital I/O Screw plug-in field connectors Safe galvanic isolation Status LEDs Low power consumption EEx ia/ib approved Suitable for PLC and DCS International approvals

Upload: others

Post on 05-Feb-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • CEAG Sicherheitstechnik GmbH 256

    ■■■■

    DescriptionLB Remote I/O modules are used as signalconditioning units between field devicesand control systems. They plug into abackplane system which is mounted ona standard DIN rail.The modules may be plugged in orremoved from a live circuit.LB Remote I/O modules offer advantagesin that they are galvanically isolated, theycan boost and amplify signals, and areeasily mounted as plug-in units. Sincethey are galvanically isolated they do notrequire equipotential earth connectionsnormally encountered with safety barriers.Changes in the power supply voltage donot affect the excellent device performancedue to the properties of the built-inamplifier circuits. Furthermore they rendersystem I/O cards superflous. Wiringbetween them and the system is reducedto a single bus.Light emitting diodes (LEDs) indicate thedevice status. A green LED shows theoperating condition, a yellow LED depictsthe switch status as in switch amplifiers,and a red LED signals alarm conditionse.g. line faults and interruptions. Thisinformation can be accessed from theDCS and PLC via a standard bus.

    LB Remote I/O

    1 to 3 channels just16 mm wideConsiderable savings inhardware and wiringMounts on abackplane fittedto a DIN rail(horizontally or vertically)Plug-in modulesfor analogue ordigital I/OScrew plug-in fieldconnectorsSafe galvanicisolationStatus LEDsLow power consumptionEEx ia/ib approvedSuitable for PLCand DCSInternational approvals

  • 777

    CEAG Sicherheitstechnik GmbH 257

    2

    1

    43

    Designed to beUser-Friendly

    Substations 1Substations can be connected to processcontrol systems (DCS) and programmablecontrolers (PLC) via standard busses. They openthe gate to all major system manufacturers.MountingMounted on a simple DIN rail, the LB Remote I/Oseries backplane is a compact and rugged baseon which the various IS modules are housed.The backplane 2The modular assembly concept allows thebackplanes to be simply slotted together to formthe most desirable panel layout. At each endthere are separate end pieces for supplyingpower and all communication 4.The modules 3The compact size allows high signal packingdensity and all this without the heatingproblems associated with traditional designs.Snap in mounting, utilising the most advancedplastics technology allows the LB Remote I/Oseries modules to be located firmly without theneed for fixing screws. The field connection ismade by a coded Phoenix mini combiconconnector on the top of the module. The systemis so designed that any of the modules can beslotted into any position on the backplane so thatIS terminations are made to suite the wiring andnot the other way around.Up to eight I/O modules 3 plus a power supplymodule can be connected to each backplanesegment and depending upon the moduleTypee, either one, two, or three channels can beutilised.A large range of interface modules are availablefor all applications including SMART/HARTcompatible devices.Power supply moduleTo meet and exceed the EMC regulations aseparate PSU module supplies up to eightLB Remote I/O series interface modules. Foreach backplane segment, one power supplymodule is required to guarantee a smoothregulated power supply.Communications module 4The communications module is the linkbetween the intrinsically safe I/O modulesand the control system. The unit can handleup to 48 I/O modules and is available in variousbus formats. The unit is located on the lefthand side of the first backplane segment.

  • CEAG Sicherheitstechnik GmbH 258

    LB Remote I/O series softwareThe LB Remote I/O interface modules have nointernal or external switches or adjustments.The configuration can be done either by thecontrol system or by an easy to use WINDOWSprogram via the local RS 485 port on theLocal Bus backplane. The setup data for everymodule is stored in a non volatile memorylocated within the communications module.Self generating documentationThe free of charge LB Remote I/O seriessoftware uses the configuration data togenerate a full system documentation package.Considerable time and cost savings can berealised by utilising this feature.Plug and play serviceBecause the I/O setup data for every moduleis already stored, should a fault developwithin a module, it can easily be removedand replaced by a standard unprogrammedI/O module.As soon as the new unit is inserted, thecommunication module instantly updates thenew I/O module and within a fraction of asecond the device is back in operation. Thisscenario also applies to the communicationsmodule. However, a download of configurationdata is required either from the control system

    Fast- andUser-FriendlySetup

    or from a PC using the LB Remote I/O back-plane’s RS 485 port.Layered redundancyAs every control system has its own individualrequirements, the LB Remote I/O series has amodular approach to redundancy.Due to the LB Remote I/O series hardwaredesign, the power supply and the LB Remote I/Oare not regarded as being susceptible to majorsystem failure. The critical areas of concern arethe control system fieldbus and the commun-ications module.The LB Remote I/O series can overcome theseconcerns by offering a ”layered” solution.Redundant fieldbusAn option for ensuring fieldbus communi-cations is to have one communications modulewith two fieldbus connections, thus ensuringan effective redundant link to the controlsystem.Redundant communication moduleThe LB Remote I/O series communicationsmodules can, if required, be placed in parallelto give a higher level of system redundancy.Signal processingThe LB Remote I/O series interface units have aunique way of handling signals to and from thefield.

    The LB Remote I/O series I/O modules convertincoming field signals to an internal LB RemoteI/O format. This also works in reverse foroutgoing signals.One function of the communications moduleis to supervise a rapid data exchange betweenall of the I/O modules and itself. At any time,an internal memory within the communicationsmodule, holds all the field signal data.The second function of the memory within thecommunications module, is to allow the controlsystem’s fieldbus to access and exchangeinformation.As the memory is the only interface between theLB Remote I/O and the control system fieldbus,future fieldbus developments in this area can beaccommodated easily.HART communicationThe LB Remote I/O series supports HARTcommunication. If the control system supportsHART communication it is then possible tocommunicate directly with the field devices.In addition to this, a RS 485 connection isavailable on the LB Remote I/O series back-plane which allows the user to access theHART field devices via a PC using standardsoftware.Local intelligenceThe LB Remote I/O series is capable ofconducting certain functions locally, withoutinvolving the external fieldbus connection to thecontrol system. This allows the system to reactquickly to time critical operations. The functionsare limited to redistributing data from an input toone or more outputs and in addition, withanalogue signals it is possible to perform tripfunctions.Line fault detectionAll LB Remote I/O series I/O modules have asophisticated Line Fault Detection System.This feature can be enabled or disabled foreach channel individually.On detecting a line fault on a channel, thefollowing events occur:• Red LED indication on I/O module• The input or output signal is taken to a

    pre-determined level• A flag is set within the memory of the

    communication module• A relay output within the communications

    module is deenergised, allowing the controlsystem to perform an interrupt routine

    PROFIBUS PAPower supplies for PROFIBUS PA, H1devices are envisaged for future expansions.

    PROFIBUSDP, FMSMODBUS

    Memory

    Bus

    I/OI/O I/O

    Bus

    LB Remote I/O

    Bus Bus Bus

    871 24 V DCPowerSupply

    IS field equipment

    Memory MemoryI/OI/O I/O

    LB Remote I/O

    Bus Bus

    9-1624 V DCPowerSupply

    IS field equipmentPROFIBUSDP, FMSMODBUS

    Bus Bus Bus

    1 8

    Bus

    24 V DCPowerSupply

    Bus

    Substation with1-48 I/O modulesand redundant bus

    Substation with1-46 I/O modulesand redundantcomm. unit

  • 777

    CEAG Sicherheitstechnik GmbH 259

    LB Remote I/O

    Selection chart

    Application Type Preferred version Page

    2 channels LB 1101 GHG 127 0000 A1101 262fullyisolated

    3 channels LB 1102 GHG 127 0000 A1102 263commonpositive

    1 channel LB 1103 GHG 127 0000 A1103 2640-15 kHzfrequency, directionof rotation,dosing counter

    Non SMART LB 3101 GHG 127 0000 A3101 26615 V supply

    SMART/HART LB 3102 GHG 127 0000 A3102 267supply 16.5 V

    SMART/HART LB 3103 GHG 127 0000 A3103 268supply 15 V

    1 channel LB 210X GHG 127 0000 A210X 265with 2 positionfeedbacks

    for valvesof most commonlyused suppliers

    1 channel LB 4101 GHG 127 0000 A4101 269800 Ω

    SMART/HART1 channel LB 4102 GHG 127 0000 A4102 270800 Ω

    1 channel LB 4103 GHG 127 0000 A4103 271400 Ω

    Accessories see page 276-279

    Switch

    Procimity switch

    Electronic switch

    Dig

    ital

    inp

    ut

    4-20 mATransmitter

    Ana

    log

    inp

    ut

    0/4-20 mACurrent source

    Solenoid valve

    LED

    4-20 mAI/P converter

    positioner

    Ana

    log

    out

    put

    Display

    Sounders

    Dig

    ital

    out

    put

  • CEAG Sicherheitstechnik GmbH 260

    LB Remote I/O

    Selection chart

    Application Type Preferred version Page

    2-/3-/4-wire RTD LB 5101 GHG 127 0000 A5101 272

    Thermocouples LB 5102 GHG 127 0000 A5102 273

    2 Non IS LB 6101 GHG 127 0000 A6101 274relays fortrip pointsor Ex-d valves

    Analog output LB 4101 GHG 127 0000 A4101 269bridge supply

    plus

    millivolt amplifier LB 5102 GHG 127 0000 A5102 273

    set to LB 8101 GHG 127 0000 A8101 275PROFIBUS

    ␣ PROFIBUS DP, set to LB 8102 GHG 127 0000 A8102 275 ␣ FMS, MODBUS ␣ MODBUS RTU

    Accessories see page 276-279

    Tem

    per

    atur

    e in

    put

    sTr

    ip p

    oin

    ts

    Relay contact

    Communicationunit

    Co

    mm

    unic

    atio

    n

    Strain gauge

    Sp

    ecia

    l tas

    ks

  • 777

    CEAG Sicherheitstechnik GmbH 261

    16.5 ±0,1±0,1

    55 55165

    119

    LB 1101 - 9111Technical data

    16

    99.5

    32

    96

    Modules

    Backplane-Segments

    Dimensions in mm

    Dimensions in mm

    General dataMax. number of I/O modules per backplane 48

    defined by theMax. number of backplanes per system fieldbus spec.Power supply 24 V DC (20... 30 V)Start-up condition for each LB 9104 15 x nominal current for 20 ms

    Conversion and transfer timeBetween field connector and communication interface memory:For analog signals < 20 msecFor digital signals < 5 msecFor temperature < 100 ms

    Ambient condtionsOperating temperature - 20 0C ... 60 0CStorage temperature - 40 0C ... 80 0CRelative humidity < 75 % average, no condensation

    HART communicationIf the external fieldbus to the DCS supports HART communication, the LB Remote I/O productstransfer the HART signals properly to the field units.

    Each communication interface has an RS 485 HART interface. Suitable for software issued withfield devices including CORNERSTONE, AMS, SMARTVISION, KSMART etc.

  • CEAG Sicherheitstechnik GmbH 262

    LB 1101Digital input

    1 2

    Local Bus

    3 4 5 6+ + --

    CH 1 CH 2

    Product features• Inputs for contacts, NAMUR - proximity

    switches and optocouplers• Galvanic isolation between both

    inputs and the LB Remote I/O• 2 channel device• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

    Input:contacts and 2 wireSignal Type NAMUR proximity switcheson > 2.1 mASwitching points off < 1.2 mA

    Hysteresis 0.2 mAFrequency 0 - 100 HzPower dissipation 0.6 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 12.6 VSafety values Isc ≤ 12.7 mA

    Ordering detailsType Order No.

    Digital input IS LB 1101 GHG 127 0000 A1101Digital input LB 1001 GHG 127 0000 A1001

    Status table, configuration parameters

    Name Format (bit) DescriptionC1_STAT@TagNr 1 Input status, channel 1C2_STAT@TagNr 1 Input status, channel 2LFD_C1_G@TagNr 1 LFD status, channel 1 (1=fault)LFD_C2_G@TagNr 1 LFD status, channel 2 (1=fault)LFD_C1_S@TagNr 1 LFD on, channel 1 (1=active)LFD_C2S@TagNr 1 LFD on, channel 2 (1=active)

    LB Remote I/O

  • 777

    CEAG Sicherheitstechnik GmbH 263

    LB 1102Digital Input

    • Inputs for contacts, NAMUR - proximityswitches and optocouplers

    • Galvanic isolation between inputsand the LB Remote I/O

    • 3 channel device• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

    Input:contacts or 2 wireSignal Type NAMUR proximity switcheson > 2.1 mASwitching points off < 1.2 mA

    Hysteresis 0.2 mAFrequency 0 - 100 HzPower dissipation 0.5 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 10.5 VSafety values Isc ≤ 32.6 mA

    Ordering detailsType Order No.

    Digital input IS LB 1102 GHG 127 0000 A1102Digital input LB 1002 GHG 127 0000 A1002

    Status table, configuration parameters

    Name Format (bit) DescriptionC1_STAT@TagNr 1 Input status, channel 1C2_STAT@TagNr 1 Input status, channel 2C3_STAT@TagNr 1 Input status, channel 3LFD_C1_G@TagNr 1 LFD status, channel 1 (1=fault)LFD_C2_G@TagNr 1 LFD status, channel 2 (1=fault)LFD_C3_G@TagNr 1 LFD status, channel 3 (1=fault)LFD_C1_S@TagNr 1 LFD on, channel 1 (1=active)LFD_C2_S@TagNr 1 LFD on, channel 2 (1=active)LFD_C3_S@TagNr 1 LFD on, channel 3 (1=active)

    5 6-

    1 2 3 4+ + + - -

    CH 2CH 1 CH 3

    Local Bus

    Product features

    LB Remote I/O

  • CEAG Sicherheitstechnik GmbH 264

    LB 1103Digital input

    • Frequency in, counter, direction of rotation• Inputs for contacts,

    NAMUR - proximity switchesand optocouplers

    • Galvanic isolation• Counter or frequency input• Overflow indication• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line monitor

    Input:contacts and 2 wireSignal type NAMUR proximity switcheson > 2.1 mASwitching points off < 1.2 mA

    Hysteresis 0.2 mAFrequency 0-15 KHzPower dissipation 0.6 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 12.6 VSafety values Isc ≤ 23.3 mA

    Ordering detailsType Order No.

    Digital input IS LB 1103 GHG 127 0000 A1103Digital input LB 1003 GHG 127 0000 A1003

    Status table, configuration parameters

    Name Format (bit) DescriptionC1_STAT@TagNr 1 Input status, channel 1CNT_VAL@TagNr 16 Counter/frequency outputLFD_C1_G@TagNr 1 LFD status, channel 1 (1=fault)LFD_C1_S@TagNr 1 LFD on, channel 1 (1=active)MOD_S@TagNr 1 Mode (0=counter)CNT_UD_S@TagNr 1 Counting direction (0=up)CNT_S@TagNr 1 Stop bit counterCNT_DIV@TagNr 8 2n divider (1-64)CNT_OVL@TagNr 1 OverflowCNT_SD_S@TagNr 1 Static/dynamic (0=static)CNT_FIX@TagNr 6 Set counter

    Product features

    direction ofrotation only

    1 2

    Local Bus

    3 4 5 6+ - + -

    CH 1

    0000

    LB Remote I/O

  • 777

    CEAG Sicherheitstechnik GmbH 265

    ValveLEDAlarm

    1 2

    Local Bus

    3 4 5 6+ + + - - -

    CH 1 CH 2

    LB 2101 - 2113Digital Output

    U0R

    a

    Product features

    Input:Sensor loops as per LB 1101

    Output:LFD 100 Ω ..... 1000 ΩPower dissipation 0.52 W

    Explosion protection:Approval PTB-No. Ex-95.D.2163Output loops Category [EEx ia] IICSensor loops Voc ≤ 10.5 V, Isc ≤ 12 mA

    Ordering detailsVoutmin Routmin Current lim. VOC ISC Type Order No.

    22.0 V 315 Ohm 50 mA 24.9 V 93 mA LB 2101 GHG 127 0000 A210124.0 V 210 Ohm 75 mA 27.8 V 185 mA LB 2102*) GHG 127 0000 A210224.0 V 360 Ohm 50 mA 27.8 V 93 mA LB 2103 GHG 127 0000 A210322.0 V 220 Ohm 50 mA 24.2 V 146 mA LB 2104 GHG 127 0000 A210422.8 V 290 Ohm 50 mA 25.2 V 110 mA LB 2105 GHG 127 0000 A210516.5 V 115 Ohm - 18.7 V 282 mA LB 2106 GHG 127 0000 A210616.5 V 170 Ohm - 18.7 V 143 mA LB 2107 GHG 127 0000 A210714.0 V 122 Ohm - 15.8 V 172 mA LB 2108 GHG 127 0000 A210811.4 V 115 Ohm - 12.6 V 147 mA LB 2109 GHG 127 0000 A2109 6.8 V 78 Ohm - 7.9 V 145 mA LB 2110 GHG 127 0000 A2110 4.0 V 50 Ohm - 4.9 V 200 mA LB 2111 GHG 127 0000 A211125.3 V 329 Ohm - 28.0 V 110 mA LB 2112 GHG 127 0000 A211226.7 V 509 Ohm - 28.7 V 70 mA LB 2113 GHG 127 0000 A211324.0 V 210 Ohm 75 mA - - LB 2002 GHG 127 0000 A2002(*only group II B)

    Status table, configuration parameters

    Name Format (bit) DescriptionOUT_@TagNr 1 OutputC1_STAT@TagNr 1 Input status 1C2_STAT@TagNr 1 Input status 2CON_S@TagNr 1 Enable local connection (1=active)CONTYPE_S@TagNr 3 Type of local connection (2=analog; 3= digital)CONOUT_S@TagNr 1 Output (0=normal; 1=inverted)CONCHA_S@TagNr 3 Local connection channelCONDEV_S@TagNr 6 Local connection address,, 0.. 47CONHYS_S@TagNr 16 Local connection hysteresisCONVAL_S@TagNr 16 Local connection limit valueLFD_V_G@TagNr 1 LFD status, output (1=fault)LFD_C1_G@TagNr 1 LFD status, input 1 (1=fault)LFD_C2_G@TagNr 1 LFD status, input 2 (1=fault)

    LB Remote I/O

    • Solenoid valve driver withvalve position feedback

    • Galvanic isolation• Drives LEDs and sounders

    • 1 Digital output to solenoid2 digital inputs valve position

    • EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

  • CEAG Sicherheitstechnik GmbH 266

    LB 3101Analog InputTransmitter Power Supply

    1 2

    Local Bus

    3 4 5 6

    +-

    4- 20 mA

    +-

    4- 20 mA

    +

    -

    Product features

    • Power supply for 2 and 3 wire4-20 mA transmitters

    • Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

    Input:Field device power supply 15 V (20 mA)Input range 4-20 mAInput impedance 50 ΩLinearity < 0.1 %Temperature drift < 0.1 % / 10 K

    min. 1 mALine monitor max. 25 mA programmablePower dissipation 1 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 23.8 VSafety values Isc ≤ 90 mA

    Ordering detailsType Order No.

    Transmitter supply IS LB 3101 GHG 127 0000 A3101

    Status table, configuration parameters

    Name Format (bit) DescriptionIN_G@TagNr 12 InputLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)

    LB Remote I/O

  • 777

    CEAG Sicherheitstechnik GmbH 267

    LB 3102SMART/HARTAnalog InputTransmitter Power Supply

    Product features• Power supply for 2- and 3-wire

    4-20 mA transmitters• HART compatible• SMART communication via fieldbus,

    local RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval

    Line fault detection

    Input:Field device power supply 16.5 V (20 mA)Input range 4-20 mAInput impedance 50 ΩLinearity < 0.1 %Temperature drift < 0.1 % / 10 K

    min. 1 mALFD max. 25 mA programmablePower dissipation 1 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 23.8 VSafety values Isc ≤ 90 mA

    Ordering detailsType Order No.

    HART/SMART analog input IS LB 3102 GHG 127 0000 A3102HART/SMART analog input LB 3002 GHG 127 0000 A3002

    Status table, configuration parameters

    Name Format (bit) DescriptionIN_G@TagNr 12 InputLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)

    LB Remote I/O

  • CEAG Sicherheitstechnik GmbH 268

    LB 3103SMART/HARTAnalog InputTransmitter Power Supply

    Input:Field device power supply 15 V (20 mA)Input range 4-20 mAInput impedance 50 ΩLinearity < 0.1 %Temperature drift < 0.1 % / 10 K

    min. 1 mALFD max. 25 mA programmablePower dissipation 1 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 24 VSafety values Isc ≤ 76 mA

    Ordering detailsType Order No.

    SMART/HART analog input IS LB 3103 GHG 127 0000 A3103

    Status table, configuration parameters

    Name Format (bit) DescriptionIN_G@TagNr 12 InputLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)

    Product features• Power supply for 2- and 3-wire

    4-20 mA transmitters• HART compatible• SMART communication via fieldbus,

    local RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

    LB Remote I/O

  • 777

    CEAG Sicherheitstechnik GmbH 269

    1 2

    Local Bus

    3 4 5 6

    I

    4- 20 mA

    LB 4101Analog Output

    Product features• Output isolator for 4-20 mA I/P converters,

    indicators, positioners• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

    Output:Max. load 750 ΩI 4-20 mAImin./max. 1/25 mALinearity < 0.1 %Temperature drift < 0.1 % / 10 KLFD > 850 Ω ... 4 kΩPower dissipation 0.6 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 27.3 VSafety values Isc ≤ 87 mA

    Ordering detailsType Order No.

    Analog output IS LB 4101 GHG 127 0000 A4101

    Status table, configuration parameters

    Name Format (bit) DescriptionOUT@TagNr 12 OutputCON_DEV@TagNr 6 Local connection addressCON_AKT@TagNr 1 Enable local connectionLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)

    LB Remote I/O

  • CEAG Sicherheitstechnik GmbH 270

    LB 4102SMART/HARTAnalog Output

    Product features• Output isolator for 4-20 mA I/P converters,

    indicators, positioners• HART compatible• SMART communication via fieldbus, local

    RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

    Output:Max. load 750 ΩI 4-20 mAImin./max. 1/25 mALinearity < 0.1 %Temperature drift < 0.1 % / 10 KLFD > 850 Ω ... 4 kΩPower dissipation 0.60 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 27.3 VSafety values Isc ≤ 87 mA

    Ordering detailsType Order No.

    SMART/HART analog output IS LB 4102 GHG 127 0000 A4102SMART/HART analog output LB 4002 GHG 127 0000 A4002

    Status table, configuration parameters

    Name Format (bit) DescriptionOUT@TagNr 12 OutputCON_DEV@TagNr 6 Local connection addressCON_AKT@TagNr 1 Enable local connectionLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)

    1 2

    Local Bus

    3 4 5 6

    HCC

    I

    4- 20 mA

    LB Remote I/O

  • 777

    CEAG Sicherheitstechnik GmbH 271

    LB 4103Analog Output

    Product features• Output isolator for 4-20 mA I/P converters,

    indicators, positioners• Especially designed for conventional actuators

    or displays with special requirements to theintrinsically safe circuits

    • Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

    Output:Max. load 400 ΩI 4-20 mAImin./max. 1/25 mALinearty < 0.1 %Temperature drift < 0.1 % / 10 KPower dissipation 0.6 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 12 VSafety values Isc ≤ 93 mA

    Ordering detailsType Order No.

    Analog output IS LB 4103 GHG 127 0000 A4103

    Status table, configuration parameters

    Name Format (bit) DescriptionOUT@TagNr 12 OutputCON_DEV@TagNr 6 Local connection addressCON_AKT@TagNr 1 Enable local connectionLFD_G@TagNr 1 LFD status (1=fault)LFD_S@TagNr 1 LFD on (1=active)

    LB Remote I/O

    1 2 3 4 5 6

    I

    4- 20 mA

  • CEAG Sicherheitstechnik GmbH 272

    LB 5101RTD Transmitter

    Product features• 2-, 3-, 4-wire RTD (temperature)• Configuration via fieldbus, local

    RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval• Line fault detection

    Input:Range 10 - 400 ΩSmallest span 20 ΩWire resistance 50 ΩNon linearity < 0.1 %Temperature drift < 0.1 % / 10 KSensor current 200 µAPower dissipation 0.52 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 2.7 VSafety values Isc ≤ 10.6 mA

    Ordering detailsType Order No.

    RTD transmitter IS LB 5101 GHG 127 0000 A5101RTD transmitter LB 5001 GHG 127 0000 A5001

    Status table, configuration parameters

    Name Format (bit) DescriptionIN_@TAGNr 12 InputTA_S@TagNr 1 Temperature (0=°C; 1=°F)NF_S@TagNr 1 Filter (0=50 Hz; 1= 60 Hz)M_MOD_S@TagNr 8 Mode (0=2 wire; 1=3 wire; 2=4 wire)M_SEN_S@TagNr 8 Sensor (1=PT 100)M_STRT_S@TagNr 16 Beginning of range in °CM_END_S@TagNr 16 End of range in °C

    LFD filter timeM_DLY_S@TagNr 8 static (1=0; 2=250; 3=500; 4=1000; 5=2000 ms)

    dynamic (1=0; 2=40; 3=80; 4=160; 5=320 ms)M_WIRE_S@TagNr 16 LFD at 2 wire (0..100)LFD_S@TagNr 1 LFD on (1=active)LFD_G@TagNr 1 LFD status (1=fault)

    Burn out drive (0=20 %; 1=100 %; 2=1 %;LFD_BA_S@TagNr 2 3=frozen)

    1 2 3 4 5 6

    mV

    Local Bus

    2 Ltr.

    3 Ltr.

    4 Ltr.

    LB Remote I/O

    2-wire

    3-wire

    4-wire

  • 777

    CEAG Sicherheitstechnik GmbH 273

    LB 5102ThermocoupleTransmitter, mV

    Product features• Transmitter for all thermocouples• mV Input• Configuration via fieldbus, local RS 485 interface• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Intrinsically safe approval

    Input:Range all thermocouples -75 mV .... + 75 mVCompensation internal (at connector) or externalNon linearty < 0.1 % (at 5 mV span)Temperature drift < 0.1 % / 10 KLFD > 1 kΩPower dissipation 0.52 W

    Explosion protection:Category [EEx ia] IICApproval PTB-No. Ex-95.D.2163

    Voc ≤ 1.8 VSafety value Isc ≤ 21.6 mA

    Ordering detailsType Order No.

    Thermocouple transmitter IS LB 5102 GHG 127 0000 A5102Thermocouple transmitter LB 5002 GHG 127 0000 A5002

    Status table, configuration parameters

    Name Format (bit) DescriptionIN_@TAGNr 12 InputTA_S@TagNr 1 Temperature (0=°C; 1=°F)NF_S@TagNr 1 Filter (0=50 Hz; 1= 60 Hz)M_MOD_S@TagNr 8 Mode (0=2 Leit.; 1=3 Leit.; 2=4 Leit.)M_SEN_S@TagNr 8 Sensor (1=PT 100)M_STRT_S@TagNr 16 Beginning of range in °CM_END_S@TagNr 16 End of range in °C

    LFD filter timeM_DLY_S@TagNr 8 static (1=0; 2=250; 3=500; 4=1000; 5=2000 ms)

    dynamic (1=0; 2=40; 3=80; 4=160; 5=320 ms)M_EXT_S@TagNr 16 CJC extern 0.00 ... 500.00, 1.00CLFD_S@TagNr 1 LFD on (1=active)LFD_G@TagNr 1 LFD status (1=fault)

    Burn-out drive (0=20 %; 1=100 %; 2=1 %;LFD_BA_S@TagNr 2 3=frozen)

    1 2 3 4 5 6

    mV

    FB Remote I/O

    CJC

    + -

    RTDVST

    LB Remote I/O

  • CEAG Sicherheitstechnik GmbH 274

    Product features• Relay output• 2 channel• Galvanic isolation• EMC to IEC 1000 and EN 50081-50082• Self monitoring• System output or local connection for

    Ex-d valves, trip points, and generalswitching functions

    Output:Relay ratingUmax. 250 V AC / 150 V DCImax.. 1 A AC / DCSwitch power Pmax. 60 VA / 30 WResponse time < 10 msPower dissipation 0.65 W

    Ordering detailsType Order No.

    Relay output LB 6101 GHG 127 0000 A6101

    Status table, configuration parameters

    Name Format (bit) DescriptionCON_R1_S@TagNr 1 Enable local connection relay 1CONTYP_1S@TagNr 3 Type of local connection (2=analog; 3=digital) rel. 1CONOUT_1S@TagNr 1 Output (0=normal; 1=inverted) relay 1CONCHA_1S@TagNr 3 Local connection channel relay 1CONDEV_1S@TagNr 6 Local connection address 0..47 relay 1CONHYS_1S@TagNr 8 Local connection hysteresis relay 1CONVAL_1S@TagNr 16 Local connection limit value relay 1CON_R2_S@TagNr 1 Enable local connection relay 2CONTYP_2S@TagNr 1 Type of local connection (2=analog; 3=digital) rel. 2CONOUT_2S@TagNr 1 Output (0=normal; 1=inverted) relay 2CONCHA_2S@TagNr 3 Local connection channel relay 2CONDEV_2S@TagNr 6 Local connection address 0..47 relay 2CONHYS_2S@TagNr 8 Local connection hysteresis relay 2CONVAL_2S@TagNr 16 Local connection limit value relay 2

    5 61 2 3 4

    LB Remote I/O

    CH 1

    LB 6101Relay Output

    CH 2

  • 777

    CEAG Sicherheitstechnik GmbH 275

    Ordering detailsType Order No.

    PROFIBUS communication interface (standard) LB 8101 GHG 127 0000 A8101MODBUS communication interface (standard) LB 8102 GHG 127 0000 A8102PROFIBUS communication interface redundancy LB 8103 GHG 127 0000 A8103MODBUS communication interface redundancy LB 8104 GHG 127 0000 A8104Other communication interfaces

    LB 8101 - LB 8104CommunicationInterface

    Product features• Non volatile configuration and parameter

    memory• HART compatible• Integrated redundancy features

    using 2 busses

    Technical dataPROFIBUS: DP, FMS

    Fieldbus connection MODBUS: ASCII, RTUother upon enquiryMODBUS: 9.6 Kbaud, 19.2 KbaudTransfer rate PROFIBUS: 9.6 Kbaud...1.5 Mbaud

    Power dissipation 2 W

    Bus length/transmission rateDepending on the standard employed for the bus, 31-127 substations can be connected to onebus line. Fibre optic links allow you to extend the cable length beyond the figures in the table. Thisalso applies for systems using repeaters.

    Bus- max. cableprotocol transmission length

    MODBUS 38.4 kbit/s 1200 m19.2 kbit/s 9.6 kbit/s

    PROFIBUS 1500 kbit/s 200 mFMS, DP 500 kbit/s 400 m

    187.5 kbit/s 1000 m 93.75 kbit/s 1200 m 19.2 kbit/s 9.6 kbit/s

    Bus structure

    1488 sensors/actors or 4464 digital loops or any combination of the two can operate on a singlebus line

    Status table, configuration parameters

    Name Format (bit) DescriptionBA@ 8 BusaddressND@ 8 Data

    • phase 2 redundancyusing 2 comm. units

    Bus- max. cable protocol transmission length

    PROFIBUS 31.75 kbit/s 1900 m PA, H1

    Servicebus 9.6 kbit/s 1200 m MODBUS

    LB Remote I/O

    Substation 1

    LB Remote I/O

    Substation n

    LB Remote I/O

    Substation 31

    PLCDCS

    •••

    Memory

    µP µP

    LB Remote I/O

    FieldbusConfig.HART Redundancy

    LB Remote I/O

    Memory

    Bus 2

    Comm. Unit 1 Comm. Unit 2

  • CEAG Sicherheitstechnik GmbH 276

    1

    2

    3

    4

    5

    67

    8

    4

    Product features• Backplane segments for up to 8

    I/O modules

    LB 9101 - 9199Backplane Segments,Accessories

    Configuration table1 Fieldbus connection 12 Fieldbus connection 23 HART/configuration/service bus4 Supply terminals5 LFD relay contacts6 LB 9102 left end segment7 LB 9101 backplane segment8 LB 9103 right end segment

    Ordering detailsType Ex-i Order number

    LB 9007 Front connector (screw fixing/green) GHG 127 0000 A 9007LB 9008 Cover for front connector (green) GHG 127 0000 A 9008LB 9011 Front connector (screw fixing for TC/green) GHG 127 0000 A 9011LB 9012 Voltage divider for 10 V inputs GHG 127 0000 A 9012LB 9099 Dummy I/O with terminals GHG 127 0000 A 9099LB 9101 Backplane Segment GHG 127 0000 A 9101LB 9102 Left End Segment GHG 127 0000 A 9102LB 9103 Right End Segment GHG 127 0000 A 9103LB 9104 Power Supply Module (1 unit per LB 9101 required) GHG 127 0000 A 9104LB 9107 Front Connector (fixed with screw) X GHG 127 0000 A 9107LB 9108 Cover for front connector (blue) X GHG 127 0000 A 9108LB 9109 DIN A4 sheet for TAG-numbers GHG 127 0000 A 9109LB 9110 SUB D Connector (for bus cable) GHG 127 0000 A 9110LB 9111 Front Connector (fixed with screw for TC) X GHG 127 0000 A 9111LB 9114 Configuration cable GHG 127 0000 A 9114LB 9121 Redundancy backplane with 6 I/O slots GHG 127 0000 A 9121LB 9151 Extension cable for 2 rows, 450 mm GHG 127 0000 A 9151LB 9152 Extension cable for 2 rows, 600 mm GHG 127 0000 A 9152LB 9153 Extension cable for 2 rows, 770 mm GHG 127 0000 A 9153LB 9198 Dummy (double width) GHG 127 0000 A 9198LB 9199 Dummy I/O with terminals X GHG 127 0000 A 9199

    products in bold print are available from stock

    • Expandable up to6 backplane segments

    LB 9104Power Supply Module

    LB 8101/8102Interface

  • 777

    CEAG Sicherheitstechnik GmbH 277

    Engineering Aids

    SubstationsSubstations are fitted with 1-48 I/Omodules which can be arranged in anydesired order. This will lead to the spacerequirements shown adjacent. Power isconnected on the left and right hand endsegments.

    max. configuration mounted vertically or horizontally using 6 backplane segments for 48 I/O modules

    1100 mm + 2 x 6 m m

    24 V

    24 V

    LB 9101LB 9102

    LB 810X LB 9104 LB 9104LB 9104LB 9104LB 9104LB 9104

    LB 9103

    Com

    .

    Pow

    er

    Pow

    er

    Pow

    er

    Pow

    er

    Pow

    er

    Pow

    er

    LB 9101LB 9101LB 9101LB 9101LB 9101

    5 backplane segments mounted vertically or horizontally for 40 I/O modules

    935 mm + 2 x 6 m m

    24 V

    24 V

    LB 9101LB 9102

    LB 810X LB 9104 LB 9104LB 9104LB 9104LB 9104

    LB 9103

    Com

    .

    Pow

    er

    Pow

    er

    Pow

    er

    Pow

    er

    Pow

    er

    LB 9101LB 9101LB 9101LB 9101

    4 backplane segments mounted vertically or horizontally for 32 I/O modules

    770 mm + 2 x 6 m m

    24 V

    24 V

    LB 9101LB 9102

    LB 810X LB 9104 LB 9104LB 9104LB 9104

    LB 9103

    Com

    .

    Pow

    er

    Pow

    er

    Pow

    er

    Pow

    er

    LB 9101LB 9101LB 9101

    3 backplane segments for 24 I/O modules

    605 mm + 2 x 6 m m

    24 V

    24 V

    LB 9101LB 9102

    LB 810X LB 9104 LB 9104LB 9104

    LB 9103

    Com

    .

    Pow

    er

    Pow

    er

    Pow

    er

    LB 9101LB 9101

    2 backplane segments for 16 I/O modules

    440 mm + 2 x 6 m m

    24 V

    24 V

    LB 9101LB 9102

    LB 810X LB 9104 LB 9104

    LB 9103

    Pow

    er

    Pow

    er

    LB 9101

    Com

    .

    1 segment for 8 I/O

    275 mm + 2 x 6 m m

    24 V

    24 V

    LB 9101LB 9102

    LB 810X LB 9104

    LB 9103

    Pow

    er

    Com

    .

    777

    277

  • CEAG Sicherheitstechnik GmbH 278

    Engineering AidsAccessories

    Mounting accessoriesExtensions LB 915X are used for mounting2 rows of a substation horizontally aboveone another.

    770 mm bus extension for 6 segments in 2 rows withleft and right end segments

    600 mm bus extension LB 9152 for4 segments in 2 rows with left and rightend segments.

    RedundancyCommunication units feature 3 galvan. isolateddata links. Two of these can be used asredundant buses. Maximum redundancy isachieved using 2 communication units.

    Cabinets 800 x 400 x 2000Horizontal mounting of8 rows with 3 backplanes 192 I/OVertical mounting of3 rows with 9 backplanes 192 I/O

    PlugsSensors and actuators are adapted via front endscrew plug-in connectors.

    Bus connection/power supplyThe bus is wired to the left end segment. Powerline terminals are to be connected at the left andright end segments.

    Cold junction compensation/codingA connector with built-in cjc is available forthermocouple measurements. Connectors canbe coded mechanically to avoid mix-ups.

    Cabinets 800 x 600 x 2000Front and rear accessHorizontal mounting of2 x 8 rows with 3 backplanes 384 I/OVertical mounting2 x 3 rows with 9 backplanes 384 I/O

    CabinetsLB Remote I/O products can be mounted instandard cabinets. 384 I/O modules can befitted depending on cabinet size. A combinationwith PLC components in the samecabinet is also possible.

    left end segmentLB 9102

    right end segmentLB 9103

    COMBICON plug

    covered screwplug-inconnector screw plug-in

    connector

    cover

    screw plug-inconnector

    multicore

    b

    a

    LB 1101

    Kodierfahne

    TAG #

    RTD cold junctioncompensation forthermocouples LB 9111

    24 V

    24 V

    24 V

    24 V

    LB 9101 LB 9101

    LB 9102

    LB 9103

    LB 9101 LB 9101

    LB 9152

    24 V

    24 V

    24 V

    24 V

    LB 9101 LB 9101LB 9101

    LB 9102

    LB 9103

    LB 9101LB 9101 LB 9101

    LB 9153

    LB 9153

    LB 9153

    LB 9152

    LB 9152

    24 V

    LB 9121 LB 9101LB 9102

    2 x LB 810X LB 9104

    NE

    TZ

    KO

    PP

    LE

    R

    KO

    PP

    LE

    R

    278

    codingstrip

    Co

    m.

    Co

    m.

    Po

    wer

  • 777

    CEAG Sicherheitstechnik GmbH 279

    Bus

    ZONE 1

    Accessories

    Type Cable entry Terminals/type Order No.

    GHG 721 1 Screw terminals1xM40 for Ø 16-28 mm 48 x 2.5 mm2 + 25 PA6xM32 for 4 x Ø 4.5-7 mm Ex-i type GHG 721 1001 R0013

    Screwless terminals1xM40 for Ø 16-28 mm 48 x 2.5 mm2 + 25 PA6xM32 for 4 x Ø 4.5-7 mm Ex-i type GHG 721 1001 R0017

    GHG 745 Screw terminals1 x M50 for Ø 21-35 mm 60 x 2.5 mm2 + 31 PA8 x M32 for 4 x Ø 4.5-7 mm Ex-i type GHG 745 0201 R0012

    Screwless terminals1 x M50 for Ø 21-35 mm 60 x 2.5 mm2 + 31 PA8 x M32 for 4 x Ø 4.5-7 mm Ex-i type GHG 745 0201 R0016

    Junction box:

    Type Cable entry Terminals/type Order No.

    GHG 791 01 Screw terminals1 x M25 for Ø 8-17 mm 6 x 2.5 mm2 + 3 PA1 x M25 for 2 x Ø 4.5-7 mm Ex-i type GHG 791 0101 R0004

    Screwless terminals1 x M25 for Ø 8-17 mm 6 x 2.5 mm2 + 3 PA1 x M25 for 2 x Ø 4.5-7 mm Ex-i type GHG 791 0101 R0008

    Screw terminalsGHG 791 02 1 x M25 for Ø 8-17 mm 12 x 2.5 mm2 + 4 PA

    1 x M32 for 4 x Ø 4.5-7 mm Ex-i type GHG 791 0201 R0009

    Screwless terminals1 x M25 for Ø 8-17 mm 12 x 2.5 mm2 + 4 PA1 x M32 for 4 x Ø 4.5-7 mm Ex-i type GHG 791 0201 R0013

    LB Remote I/OAnalog and digital inputs and outputsare wired to junction boxes. From theremulticore cables take the loops todistribution boxes.The signals then reach the intrinsically safesignal conditioning equipment individually.The interface consists of galvanicallyisolated bus modules mounted on aDIN rail.A serial data link ensures communicationbetween the substation and the DCS orPLC via a standard bus.You can expect considerable savings inengineering, I/O modules, marshalling andwiring.

    Distribution box:

    I/O