le models: shipping, rigging, lifting, assembly manual
TRANSCRIPT
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 1
4510 Helgesen Drive, Madison, WI 53718(608) 221-4499, (800) 627-4499, Fax: (608) [email protected] www.renewaire.com
LE MODELS: SHIPPING, RIGGING, LIFTING, ASSEMBLY MANUAL
Table of ContentsSHIPPING.................................................................2 RIGGING..................................................................2 LIFTING ..................................................................2 ASSEMBLY (UNITS SHIPPED IN 2 MODULES).........................4 Indoor Units....................................................4 Rooftop Units..................................................7 ADDITIONAL INSTALLATION............................................7
MODULE WEIGHTS AND DIMENSIONS. ..............................8
www.renewaire.com (800) 627- 4499 [email protected]
This manual provides an overview of shipping, rigging, lifting and assembly information of the LE Series energy recovery ventilators.
Carefully read all instructions before proceeding with any work.
These instructions outline the suggested method of placing a RenewAire LE ERV in position. See also the Installation and Operation Manual supplied with the unit.
Following these instructions does not necessarily assure compliance with local codes and standards, which must always be observed. All local codes and regulations must be adhered by the Installing Contractor.
Any additional holes made by the installing Contractor must be well sealed to prevent air or water infiltration.
Any questions please contact your RenewAire representative.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. INSTALLATION AND SERVICE MUST BE PERFORMED BY A TRAINED, QUALIFIED INSTALLER. A COPY OF THIS MANUAL SHOULD BE KEPT WITH THE UNIT.
1. This shipping, rigging, joining and installation manual shows the suggested installation method. Additional measures may be required by local codes and standards.
2. Installation work and electrical wiring must be done by qualified professional(s) in accordance with all applicable codes, standards and licensing requirements.
3. Any structural alterations necessary for installation must comply with all applicable building, health, and safety code requirements.
4. This unit must be grounded.5. Danger of severe injury to bystanders and damage to
unit or property if high winds move this unit. Secure this unit to the building!
6. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment that might be installed in the area affected by this equipment. If this unit is exhausting air from a space in which chimney-vented fuel burning equipment is located, take steps to assure that combustion air supply is not affected. Follow the heating equipment manufacturer’s requirements and the combustion air supply requirements of applicable codes and standards.
7. Use the unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
8. This unit is intended for general ventilating only. Do not use to exhaust hazardous or explosive materials and vapors. Do not connect this unit to range hoods, fume hoods or collection systems for toxics.
9. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
www.renewaire.com (800) 627- 4499 [email protected]
LE8X SHOWN
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 2
SHIPPINGINDOOR/ROOFTOP
LE models can be delivered in two modules for on-site assembly or as a complete unit (additional charges apply).
In all cases, units or individual modules are shipped on pallets.
In all cases, extra protective pallet materials may have been added; this material was added at the factory to protect the unit or modules during shipping.
In all cases, when shipped in modules, assembly materials ship loose and can be found inside the modules. Note: Assembly materials must be removed and installed prior to unit operation.
For rooftop models, the outdoor air weather hoods ship loose and can be found inside the modules. Note: Weather hoods and assembly materials must be removed and installed prior to unit operation.
STORAGE
If installation will not occur immediately following delivery, store equipment in a dry protected area away from construction traffic and in the proper orientation as marked on the packaging with all internal packaging in place.
RIGGINGEQUIPMENT AND TOOLSAll rigging equipment is to be provided by the installing Contractor.
Rigging procedures may differ depending on the physical dimensions of the unit or modules, it’s location, the job site, or Installing Contractor preferences.
Tools needed (Suggested):• Crane to lift proper capacity• Adjustable spreader bars• Cables• 1.5” Dia. steel pipe schedule 40.• Tools requited to pull modules together, chains, bar
clamps, come alongs etc.
UNIT WEIGHTS AND MEASURESSee LE6X/8X/10X corner weights for individual modules and completed units starting on page 16.
LIFTING
The unit comes equipped with base rail lifting lugs at the lower 4 corners and in the middle of the unit.
Each lifting lugs come equipped with a 2” diameter hole which will accommodate a 1.5” dia. schedule 40 steel pipe (not provided).
Unit or module sections shall be lifted by cables attached to all of the lifting lugs.
If cables or chains are used to lift the unit they must be the same length. Care should be taken not to damage the cabinet, dampers, or electrical box.
Adjustable spreader bars should be used to properly support the unit in order to properly distribute the load thus applying an even vertical lifting force to all of the lifting lugs. This will prevent structural damage to the unit.
Also adjustable spreader bars should be used to maintain the required 10” clearance between the cables and the cabinet or any of the equipment attached to the unit or modules.
Provide additional blocking or covering as required.
Secure hooks and cables at all lifting points.
Take up slack in cables gradually as to avoid sudden movements as this may cause the unit or modules to shift.
Suspending the unit or modules for an extended period of time is not recommended and it is advised to place the unit as soon as possible after lifting.
Do not lift in high winds.
RenewAire will not be responsible for any damage during the rigging, lifting or installing of the unit or modules.
Refer to Corner Weight Charts for exact center of gravity.
All lifting lugs provided must be used. Never lift the unit or modules from the top of the unit.
Do not lift joined unit by the 4 corner lifting lugs only. Secure lifting cables to the center lifting lugs also.
Incorrect lifting can cause damage to the unit.
The units are designed to be lifted from lifting lugs attached to the unit base structure. Spreader bars must be used to hoist sections to avoid damaging the enclosure.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 3
www.renewaire.com (800) 627- 4499 [email protected]
www.renewaire.com (800) 627- 4499 [email protected]
www.renewaire.com (800) 627- 4499 [email protected]
Assembled modules should never be lifted using a forklift.
FORKLIFT REQUIREMENTS
When lifting individual modules, forklift extensions must be used and a minimum length of 72” (96” preferred).
When lifting modules off the pallets:
If entering from the door side or the open side of the module insure forks extend in far enough as to catch the furthest away stringer with fork extensions.
If entering from the side of the module, insure forks extend all the way through the module.
Do not attempt to lift a rooftop module off the pallet from the door side or open side as there are no stringers under the unit to carry the load.
LIFTING
LE8X SHOWN
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 4
ASSEMBLYCONFIGURATION LABEL
RenewAire LE series Energy Recovery Ventilators can either be built and shipped factory assembled or be ordered unassembled for applications where modules must be manipulated separately. If the unit was ordered unassembled, then you will need to assemble the modules in the field.
Each module is labeled with a configuration and serial number label. Locate these labels and insure each module assembled together have the same configuration and serial number.
If for any reason you are unable to identify a module or it’s position in the final assembly, then consult the Installation Contractor or RenewAire Customer Service.
INDOOR MODULES
Extra protective pallet material has to be removed prior to assembly. This additional pallet material was added at the factory to protect the unit during shipping.
Also, plywood protective packaging material has to be removed from modules before assembly.
It is desirable to situate all required modules in the installation location as near as possible to the order in which they will be connected. Be sure to leave enough space to work between modules before connection. Gasket tape will be applied before assembling the modules.
All materials for assembling the modules are supplied by RenewAire.
Remove shipping straps
Remove shipping straps from opening/mating ends before joining modules and operating the unit. Shipping straps are attached to the modules at the factory. These straps insure proper rigidity when shipping and lifting. Once the straps are removed they may be disposed of along with the screws that held them in place.
Shipping straps on open end.
Apply gasket tape
Apply 1/4" X 1" gasket tape (provided), as shown on next page. Gasket tape creates an airtight seal between modules. The adhesive backing on the gasket tape is easily repositioned during assembly if needed. However, if gasket tape is allowed to set more than 48 hours, it will be difficult to reposition.www.renewaire.com (800) 627- 4499 [email protected]
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 5
Failure to apply gasket tape in these locations will compromise water and airtight seal of the unit.
www.renewaire.com (800) 627- 4499 [email protected]
Assemble
Align modules and push together using forklift or other means compressing the gasket tape. The lower lifting lugs are equipped with 2" diameter holes that 1.5" dia. (2" OD) steel pipe could be used to assist in alignment. Joining lift lugs also have a spacing bolt at the tip of one lug that will fit into the empty lug hole of the other module for alignment and lug tip spacing.
Clamping Together at Lifting Lugs
After positioning the modules together, compressing the gasket tape, insert four 3/8” - 16 x 1-1/4 plated hex head bolts through the holes on the base rail lifting lugs of the two adjacent modules. Secure the nuts to secure the bases of the two modules together tightly.
www.renewaire.com (800) 627- 4499 [email protected]
www.renewaire.com (800) 627- 4499 [email protected]
www.renewaire.com (800) 627- 4499 [email protected]
Failure to install bolts in these locations will compromise the structural integrity of the unit and damage will occur during lifting. Also a water and airtight seal of the unit will be compromised.
Bolt Together Mating Roof Beams
Use bar clamps, or other non-destructive winching device to pull the top of the modules together tightly compressing the gasket. After aligning the 4 roof bolt locations, insert 1/4” - 20 x 1.00” Grade 5 zinc plated hex head bolts through the holes in the roof beam. Secure the nuts to secure the roof section.
www.renewaire.com (800) 627- 4499 [email protected]
ASSEMBLYAdditionally, for added unit strength and gasket clamping force, insert four 3/8" - 16 x 1-1/4 plated hex head bolts through holes in base rails of joining ends in LE indoor units or through holes in base centering angles of joining ends in LE rooftop units as shown below. Hand holes are provided in base rails to reach these locations when joined.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 6
ASSEMBLYCaulk the Seams
Attention should be taken to assure the modules are forming an air and water tight seal.
Apply a continuous ½” bead of Tremsil 600 Silicone Sealant caulk (provided) at the seam along the entire roof and sides of the unit.
Failure to apply caulk in these locations will compromise the water and airtight seal of the unit.
www.renewaire.com (800) 627- 4499 [email protected]
Install Joining Roof Cap
A galvanized cap roof flange is provided to seal the roof seam and to maintain an water and airtight seal. The cap roof flange is provided with pre-drilled holes. #12 X .75 hex head tek screw w/washers are provided to attach the cap roof flange.
For best results, use a lower torque setting on the power drill. Be careful not to over tighten the screw.
Failure to install the roof cap will compromise the water and airtight integrity of the unit.
www.renewaire.com (800) 627- 4499 [email protected]
Install Assembly Strap
Two (2) galvanized metal assembly straps are used to secure the module seams to assist in maintaining a water and airtight seal and provide structural rigidity during lifting. One (1) used on each side of the unit. These straps are provided with pre-drilled holes. #12 X .75 hex head tek screw w/washers are provided to attach the joining straps to the unit. For additional protection, caulk sides of straps after attachment.
For best results, use a lower torque setting on the power drill. Be careful not to over tighten the screw.
www.renewaire.com (800) 627- 4499 [email protected]
Failure to install the assembly straps will compromise the structural integrity of the unit and cause unit damage during lifting. Also compromise the water and airtight integrity of the unit.
Install Joining Roof End Caps
Two (2) galvanized roof cap ends are provided to seal the top end of each module and maintain a water and airtight seal. The roof cap joining ends are provided with pre-drilled holes. #12 X .75 hex head tek screw w/washers are provided to attach these roof cap joining ends to the unit.
www.renewaire.com (800) 627- 4499 [email protected]
Failure to install roof cap ends will compromise the structural integrity of the unit and cause unit damage during lifting. Also compromise the water and airtight integrity of the unit.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 7
ROOFTOP MODULES
Cross members must be positioned per the drawing in order for properly support the unit.
The building structure must provide adequate structural support under vertical roofcurb members.
Assembly Before Lifting (See Indoor Module Assembly)
FOLLOW STEPS FOR INDOOR UNIT. LEAVE HOODS INSIDE.
The RenewAire roofcurb is shipped knocked-down with assembly hardware and instructions provided.
The roof curb must then be assembled on the job site and set in place. Curb must be installed first. In all cases curb must be properly installed on roof before placing the unit on it.
Dimensions accompany the curb but can also be found in this manual. See below.
Ensure that the roofcurb is square and level before installing the ERV.
The installing contractor is responsible for proper connection to the roof along with insuring the curb to be watertight by caulking all curb joints.
UNITS ASSEMBLED ON THE GROUND
Apply curb clips as per RenewAire Curb Clip Manual 138241.
Insure ducts are in place.
Insure the curb is properly gasketed and the orientation of the unit is correct to line up with the curb openings.
Hoist unit directly over duct openings.
Carefully lower and align the unit with duct openings. Make sure the unit is properly seated and level.
NOTEFor modular units, make certain to always install the module with bottom duct connection/s first.
These shims also act to hold the first module in place as the second module is slid along the curb to be joined to the first.
Set the second module on the curb as close as possible to the first module to minimize curb gasket tape damage when modules are slid together.
ADDITIONAL INSTALLATIONROOFTOP MODELS
Weather hoods are located inside the unit and must be installed after the unit is in place (See IOM Manual accompanying the unit)
Before operating the unit, insure all materials have been removed from the unit.
UNITS ASSEMBLED ON THE CURB
When placing the unit on the curb in two modules, ensure the first module that is lifted and set in place has equal amount of gap between the frame rail of the unit and the curb approx. ½” all around. A shim should be used to properly align the module to the curb. This insures proper alignment of the second module to the first when pulling the modules together.
Align modules and push together compressing the gasket tape. The lower lifting lugs are equipped with 2” diameter holes that 1.5” dia. Schedule 40 steel pipe could be used to assist in alignment. Joining lift lugs also have a spacing bolt at the tip of one lug that will fit into the empty lug hole of hte other module for unit alignment and lug tip spacing.
Follow assembly instructions above per indoor models to insure structural, water and airtight integrity.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 8
LE6XRT Curb
LE8XRT Curb
ROOFTOP CURB DIMENSIONS
111 1/2" I.D.
25"
2
0" 33" 17 1/4"
115 1/4" O.D.
9 1
/2"
3"
60
1/2"
I.D
.
64
1/4"
O.D
. AARA
FA
TOP VIEW
LE6XRTCURB 6X
1 7/8"
14"
3"
SECTION A-ASCALE 1 : 30
1 1/2" X 1/4"Neoprene Gasket
3/4" X 3 1/2"Wooden Nailer
CURB CROSS-SECTION A-A (TYP.)
DUCT SUPPORT DIMENSIONSWIDTH: 3" DEPTH: 1 1/2"
Model: LE6XRT CURBDrawing Type: Curb DimensionVersion: OCT15
RA: Room Air to be exhaustedFA: Fresh Air to inside
151 1/2" I.D.
25"
2
0"
9 1
/2"
49" 21 1/8"
155 1/4" O.D.
4 7
/8"
60
1/2"
I.D
.
64
1/4"
O.D
. AA RA
FA
TOP VIEW
LE8XRTCURB 8X
1 7/8"
14"
3"
SECTION A-ASCALE 1 : 30
1 1/2" X 1/4"Neoprene Gasket
3/4" X 3 1/2"Wooden Nailer
CURB CROSS-SECTION A-A (TYP.)
DUCT SUPPORT DIMENSIONSWIDTH: 3" DEPTH: 1 1/2"
Model: LE8XRT CURBDrawing Type: Curb DimensionVersion: OCT15
RA: Room Air to be exhaustedFA: Fresh Air to inside
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 9
LE10XRT CurbROOFTOP CURB DIMENSIONS
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 10
69 1/4" Case 111 1/8" Overall
22 1/4" 19 5/8"Typ.
2"Typ. 73 3/8"
Lifting Lugs 2" Typ.
RTH, RTFONLYRAFARTH, RTR
ONLY
FARTV, RTF
ONLYRA
RTV, RTRONLY
FRONT VIEW
Pressure Ports(4) Typ.
125 3/8" Overall 122 5/8" Case
8 3
/4"
25 3/8" Duct Flange24" X 32" Typ.OA Inlets,
OA DamperLocations(Optional)
RIGHT VIEW
25 1/4"
9" 6
5 5/
8" C
ase
7
1 1/
8" O
vera
ll
4"
53
1/2"
44 5/8"
CL 5 1/4"(2) 7/8" KnockoutsCL 11 3/8"
(5) 7/8"Knockouts
DisconnectSwitch
EA Outlet
EA DamperLocation (Optional)
E-Box
15 1/2" X 13 3/8"ElectricalConnectionCover
18 3/8"
38
7/8"
49 5/8"
44"
60 1
/4"
Min
imum
Blow
er S
ervi
ceA
rea
Typ.
111" MinimumService Area
36" E-BoxMinimum
Service Area
69 3/4" MinimumService Area
OA
OA
EARA (RTV, RTR)Opening33 1/2" X 24"
FA (RTV, RTF)Opening
19 1/2" X 16 1/8"
DoorSwing
DoorSwing
DoorSwing
DoorSwing
TOP VIEW
115
1/4
" O.D
. 64 1/4" O.D.
3" 60 1/2" I.D.
17
1/4"
3
3"
20" 25" 9 1/2"
AA
TOP VIEW
CURB LE6X
FA RA
1 7/8"
3"
14"
SECTION A-A
CURB CROSS-SECTION A-A (TYP.)1 1/2" X 1/4"Neoprene Gasket
3/4" X 3 1/2"Wooden Nailer
LEFT VIEW
Model: LE6XRTDrawing Type: Unit DimensionVersion: NOV15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to insideRTV: Rooftop Vertical RA & FARTF: Rooftop Vertical FA OnlyRTR: Rooftop Vertical RA OnlyRTH: Rooftop Horizontal RA & FA
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE:1. UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
69 1/8" Case
111 1/4" Overall
22 1/2" 19 3/4"
73 3/8"Lifting Lugs 2" Typ.
RTH, RTFONLYRAFARTH, RTR
ONLY
FARTV, RTF
ONLYRA
RTV, RTRONLY
FRONT VIEW
27 3/8"
8 3
/4"
162 5/8" Case 165 3/8" Overall
RA Opening24" X 48"
OA Inlets,OA Damper
Locations(Optional)
RIGHT VIEW
28 1/2"
58 5/8"
4"
65 5
/8"
Cas
e
71
1/8"
Ove
rall
9"
64 5/8"
53
1/2"
CL 5 1/4"(2) 7/8"Knockouts
CL 11 3/8"(5) 7/8"
Knockouts
DisconnectSwitch
EA Outlet
EA DamperLocation (Optional)
E-Box
15 1/2" X 13 3/8"ElectricalConnectionCover
16 1/8" X 16 3/8"Typ.
LEFT VIEW
78 1
/2"
Min
imum
Blow
er S
ervi
ceA
rea
Typ.
52 1
/8"
Typ.
17 3/8"
49 3/8"
36" E-BoxMinimum
Service Area
111" MinimumService Area
69 3/4" MinimumService Area
OA
OA
EARA (RTV, RTR)Opening24" X 48"
FA (RTV, RTF)Opening19" X 48"
DoorSwing
DoorSwing
DoorSwing
DoorSwing
TOP VIEW
21
1/4"
4
9"
155
1/4
" O.D
.
60 1/2" I.D.
20" 25" 9 1/2"
151
1/2
" I.D
.
3"
64 1/4" O.D.
AA
TOP VIEW
CURB LE8X
FA RA
1 7/8"
3"
14"
SECTION A-A
CURB CROSS-SECTION A-A (TYP.)
1 1/2" X 1/4"Neoprene Gasket
3/4" X 3 1/2"Wooden Nailer
Model: LE8XRTDrawing Type: Unit DimensionVersion: NOV15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to insideRTV: Rooftop Vertical RA & FARTF: Rooftop Vertical FA OnlyRTR: Rooftop Vertical RA OnlyRTH: Rooftop Horizontal RA & FA
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE:1. UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
ROOFTOP UNIT DIMENSIONSLE6XRT
LE8XRT
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 11
73 3/8"Lift Lugs
111 1/8" Overall
69 1/8" Case
2" 2" Typ.
4"
CL 2 1/4"Wiring
PressurePorts(4) Typ.
4 1/2" 93 5/8"
8 3
/4"
47 1/4"
202 5/8" Case 205 3/8" Overall
24" X 48"RA Inlet(RTH, RTF)
OA InletsOA Damper
Locations(Optional) 2
9 5/
8"
53
1/2"
84 5/8"
37
7/8"
44 5/8"
69
5/8"
Cas
e
71
1/8"
Ove
rall
9"
47 1/4"
CL 5 1/4"(2) 7/8"Knockouts
CL 11 3/8"(5) 1 1/8"Knockouts
E-BoxDisconnect
Switch
EA OutletEA Damper
Location(Optional)
15 1/2" X 13 3/8"Electrical
ConnectionCover
24" X 48"FA Outlet
RTH, RTR
79 7
/8"
Min
imum
Blow
erSe
rvic
eA
rea
Typ.
36" E-BoxMinimum
Service Area
111" MinimumService Area
72 1
/8"
Typ.
17 3/8"
49 3/8"
69 3/4" MinimumService Area
RA (RTV, RTR)24" X 48"
FA (RTV, RTF)19" X 48"
DoorSwing
DoorSwing
DoorSwing
DoorSwing
EA
OA
OA
64 1/4" O.D.
41
1/8"
4
9"
195
1/4
" O.D
.
20"
9 1/2"
25" 3"
60 1/2" I.D.
191
1/2
" I.D
.
AA
TOP VIEW
CURB LE10X
FA RA
1 7/8"
14"
3"
SECTION A-A
CURB CROSS-SECTION A-A (TYP.)
1 1/2" X 1/4"Neoprene Gasket
3/4" X 3 1/2"Wooden Nailer
TOP VIEW
FRONT VIEWLEFT VIEW RIGHT VIEW
RTH, RTRONLYFA
EA OA
RTH, RTFONLYRARTH, RTR
ONLYFA
RTV, RTFONLY
FA
RTV, RTRONLY
RA
Model: LE10XRTDrawing Type: Unit DimensionVersion: NOV15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to insideRTV: Rooftop Vertical RA & FARTF: Rooftop Vertical FA OnlyRTR: Rooftop Vertical RA OnlyRTH: Rooftop Horizontal RA & FA
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE:1. UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THENEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECTTO CHANGE WITHOUT NOTICE.
ROOFTOP UNIT DIMENSIONSLE10XRT
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 12
RA
EA
FA
CL 73 3/8"Lift Lugs
2" Typ. 69 1/8" Case
4 1/4" DamperFlanges
80 1/4" Overall
2"
4"
18 5/8"
CL 2 1/4"Wiring
EA
FA RA
OA
PressurePorts (4) Typ.
69
5/8"
Cas
e
71
1/8"
Ove
rall
44 5/8"
53
1/2"
2
9 5/
8"
33 5/8"
6 1
/4"
38
3/4"
27"
CL 5 1/4"(2) 7/8"Knockouts
CL 11 3/8"(5) 1 1/8"Knockouts
LEFT VIEW
OptionalMotorized
Damper
22" X 24"Duct Flange Typ.
OptionalMotorized
Damper
15 1/2" X 13 3/8"Electrical
ConnectionCover
E-Box
DisconnectSwitch
41
1/2"
25 1/4" 25 1/4"
8 3
/4"
125 3/8" Overall 122 5/8" Case
RIGHT VIEW
60 1
/4" M
inim
umBl
ower
Ser
vice
Are
a Ty
p.
69 3/4" MinimumService Area
111" MinimumService Area
36" E-BoxMinimum
Service Area
OA
FRONT VIEW
TOP VIEW
DoorSwing
DoorSwing
DoorSwing
DoorSwing
24" X 32"Duct Flange Typ.
Model: LE6XINHDrawing Type: Unit DimensionVersion: OCT15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE1.UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THENEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECTTO CHANGE WITHOUT NOTICE.
OA
RA
EA
FA
2" Typ. 69 1/8" Case
CL 73 3/8"Lift Lugs
2"
80 1/4" Overall
4"
18 5/8"
4 1/4" DamperFlanges
CL 2 1/4"Wiring
PressurePorts (4) Typ.Disconnect
Switch
165 3/8" Overall 162 5/8" Case
41
1/2"
27 3/8"
8 3
/4"
27 3/8" 24" X 32"Duct Flange Typ.
64 5/8"
53
1/2"
29
5/8"
69
5/8"
Cas
e
71
1/8"
Ove
rall
38
1/4"
6"
27 1/4"
27 1/4" CL 5 1/4"(2) 7/8"Knockouts
CL 11 3/8"(5) 1 1/8"
Knockouts
15 1/2" X 13 3/8"ElectricalConnectionCover
22" X 24"Duct Flange Typ.Optional
MotorizedDamper
OptionalMotorized Damper
E-Box
78 1
/2"
Min
imum
Blow
erSe
rvic
eA
rea
Typ.
69 3/4"Minimum
Service Area
111" MinimumService Area
36" E-BoxMinimum
Service Area
OA
RA
EA
FA
FRONT VIEW RIGHT VIEWLEFT VIEW
TOP VIEW
DoorSwing
DoorSwing
DoorSwing
DoorSwing
Model: LE8XINHDrawing Type: Unit DimensionVersion: OCT15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE1.UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THENEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECTTO CHANGE WITHOUT NOTICE.
INDOOR UNIT DIMENSIONSLE6XINH
LE8XINH
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 13
OA
RA
EA
FA
69 1/8" Case 73 3/8"Lift Lugs
2"
4"
80 1/4"Overall4 1/4"
DamperFlanges
18 5/8"
2"Typ.
CL 2 1/4"Wiring
FRONT VIEW
Pressure Ports (4) Typ. 202 5/8" Case
205 3/8" Overall
41
1/2"
47 1/4"
8 3
/4" 47 1/4" 24" X 48"
Duct Flange Typ.
53
1/2"
47 1/8"
84 5/8"
69
5/8"
Cas
e
71
1/8"
Ove
rall
47 1/4"
38
1/4"
6"
29
5/8"
CL 5 1/4"(2) 7/8"Knockouts
CL 11 3/8"(5) 1 1/8"Knockouts
LEFT VIEW
E-BoxDisconnect
Switch
15 1/2" X 13 3/8"Electrical
ConnectionCover
22" X 50"Duct Flange Typ.
OptionalMotorizedDamper
OptionalMotorized
Damper
69 3/4"Minimum
Service Area
36" E-BoxMinimum
Service Area
79 7
/8"
Min
imum
Blow
erSe
rvic
eA
rea
Typ.
111" MinimumService Area
OA
RAFA
EA
DoorSwing
DoorSwing
DoorSwing
DoorSwing
TOP VIEW
RIGHT VIEW
Model: LE10XINHDrawing Type: Unit DimensionVersion: NOV15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE:1. UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
INDOOR UNIT DIMENSIONSLE10XINH
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 14
60 1
/4"
Min
imum
Bl
ower
Serv
ice
Are
a
34"Minimum
Service Area
111" MinimumService Area
36" E-BoxMinimum
Service Area
69 3/4" MinimumService Area
TOP VIEW
CL 73 3/8"Lift Lugs
69 1/8" Case 2" Typ. 4"
2"
80 1/4" Overall 4 1/4" Damper
Flanges
18 5/8" Typ. CL 2 1/4"
Wiring
FRONT VIEW
PressurePorts (4) Typ.
44 5/8"
53
1/2"
29
5/8"
33 5/8"
25 1/4"
69
5/8"
Cas
e
71
1/8"
Ove
rall
CL 5 1/4"(2) 7/8"Knockouts
CL 11 3/8"(5) 1 1/8"Knockouts
LEFT VIEW
24" X 32"Duct Flange Typ.
22" X 24"Duct Flange Typ.
15 1/2" X 13 3/8"Electrical
ConnectionCover
E-BoxDisconnectSwitch
OptionalMotorized
Damper
125 3/8" Overall
41 1
/2"
Typ.
25 1/4"
122 5/8" Case
33 5/8"
6 1/
4"Ty
p.
EA
OARA
FA
OARA
EAFA
RIGHT VIEW
OptionalMotorizedDamper
DoorSwing
DoorSwing
DoorSwing
DoorSwing
Model: LE6XINVDrawing Type: Unit DimensionVersion: OCT15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE1.UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECTTO CHANGE WITHOUT NOTICE.
2" Typ.
2"
18 5/8"Typ.
69 1/8" Case
80 1/4" Overall 4 1/4" Damper
Flanges
4"
CL 73 3/8"Lift Lugs
CL 2 1/4"Wiring
TOP VIEW
FRONT VIEWLEFT VIEW
PressurePorts (4) Typ.
DisconnectSwitch
165 3/8" Overall 162 5/8" Case
41 1
/2"
Typ.
27 3/8"
6" Typ.
27 1/4"
RIGHT VIEW
OptionalMotorized
Damper
64 5/8"
53
1/2"
29
5/8"
27 1/4"
69
5/8"
Cas
e
71
1/8"
Ove
rall
27 3/8"
CL 5 1/4"(2) 7/8"Knockouts
CL 11 3/8"(5) 1 1/8"Knockouts
15 1/2" X 13 3/8"ElectricalConnectionCover
OptionalMotorized
Damper24" X 48"
Duct Flange Typ.
22" X 50"Duct FlangeTyp.
E-Box
78 1
/2"
Min
imum
Blo
wer
Serv
ice
Are
a
111" MinimumService Area
36" E-BoxMinimum
Service Area
34"
Min
imum
Serv
ice
Are
a
69 3/4" MinimumService Area
DoorSwing
DoorSwing
DoorSwing
DoorSwing
RA
FA
OA
EA
RA
FA
OA
EA
Model: LE8XINVDrawing Type: Unit DimensionVersion: OCT15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE1.UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECTTO CHANGE WITHOUT NOTICE.
INDOOR UNIT DIMENSIONSLE6XINV
LE8XINV
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 15
69 1/8" Case 73 3/8"Lift Lugs
2"
80 1/4"Overall
4" 2" Typ.
4 1/4"DamperFlanges
18 5/8"
CL 2 1/4"Wiring
FRONT VIEW
PressurePorts (4) Typ.
41
1/2"
47 1/4" 47 1/4"
6"
202 5/8" Case 205 3/8" Overall
24" X 48" Duct Flange Typ.
22" X 50"Duct Flange Typ.
OptionalMotorized
Damper
29
5/8"
5
3 1/
2" 47 1/8"
84 5/8"
71
1/8"
Ove
rall
69
5/8"
Cas
e
6"
47 1/4"
41
1/2"
CL 11 3/8"(5) 1 1/8"Knockouts CL 5 1/4"
(2) 7/8"Knockouts
E-BoxDisconnect
Switch
15 1/2" X 13 3/8"Electrical
ConnectionCoverOptional
MotorizedDamper
34" M
inim
umSe
rvic
e A
rea
69 3/4"Minimum
Service Area
79 7
/8"
Min
imum
Blow
erSe
rvic
e A
rea
111" MinimumService Area
36" E-BoxMinimum
Service Area
DoorSwing
DoorSwing
DoorSwing
DoorSwing
RA
FA EA
OA
TOP VIEW
LEFT VIEW RIGHT VIEW
RA
FA
OA
EA
Model: LE10XINVDrawing Type: Unit DimensionVersion: NOV15
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
INSTALLATION ORIENTATIONUnit must be installed in orientationshown.
NOTE:1. UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
INDOOR UNIT DIMENSIONSLE10XINV
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 16
LE6X CORNER WEIGHTS
73.5"Lifting Lug
LR RR
LF RF
119.
5" L
iftin
g Lu
g
CORNER WEIGHTS AT LIFTING LUGS
BASIC UNIT WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP 1984 569 433 442 558
1997 575 434 425 563
2116 626 442 434 614
5 HP
7.5 HP
Motors UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 418 105 104 104 105
15 13 1 0 1
18
18
VFDs
EA Damper
FA Damper
Total Selected Weights
Add the additional weights for options to the Basic Unit weights determined bymotor size to determine Unit and Corner weights for a specific unit.
12 6 0 0
0 0 6 12
"B"
"A"
1/30/2014 MFSPECIFICATIONS SUBJECTTO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawing
LE-6X-INV_CORNER_WEIGHTS_JAN14.2.dwg
LE6XRT Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 2086 575 566 469 476
5 2100 579 570 472 479
7.5 2218 621 615 489 493
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 418 105 104 104 105
(2) VFDs 15 13 1 0 1
EA Damper 17 5 12 0 0
OA Damper 39 0 0 19 20
TOTAL SELECTED WEIGHTS
Center of Gravity A = 33” B = 59-1/2” (+/- 2”)
73.5"Lifting Lug
LF RF
59.3
" Lift
ing
Lug
FRONT MODULE WEIGHTS AT LIFTING LUGS
BASIC MODULE WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP 1269 341 304 294 330
1283 345 306 297 335
1400 387 323 314 376
5 HP
7.5 HP
Options UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 208 64 40 40 64
15 11 3 0 1
18 0 0 12 6
18 6 12 0 0
VFDs
EA Damper
FA Damper
Total Selected Weights
Add the additional weights for options to the Basic Unit weights determined bymotor size to determine Unit and Corner weights for a specific unit.
Front Module
Door End
"B"
"A"
1/30/2014 MFSPECIFICATIONS SUBJECTTO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawing
LE-6X-INV_CORNER_WEIGHTS_JAN14.2.dwg
LE6XRT Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1068 281 243 252 292
5 1075 284 245 253 293
7.5 1135 309 259 259 308
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 208 64 40 40 64
(2) VFDs 15 11 3 0 1
EA Damper 0 0 0 0 0
OA Damper 17 0 0 7 10
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 37-1/4” B = 27” (+/- 2”)
73.5"Lifting Lug
LR RR
59.3
" Lift
ing
Lug
REAR MODULE WEIGHTS AT LIFTING LUGS
BASIC MODULE WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP
714 207 158 151 1985 HP
7.5 HP
Options UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 208 64 40 40 64
0 0 0 0 0
0 0
VFDs
EA Damper
FA Damper
Total Selected Weights
Add the additional weights for options to the Basic Unit weights determined bymotor size to determine Unit and Corner weights for a specific unit.
0 0 0
0 00 0 0
Back Module
Door End
"A"
"B"
1/30/2014 MFSPECIFICATIONS SUBJECTTO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawing
LE-6X-INV_CORNER_WEIGHTS_JAN14.2.dwg
LE6XRT Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 1018 256 206 248 308
5 1024 257 205 250 312
7.5 1084 272 206 261 345
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 208 64 40 40 64
(2) VFDs 0 0 0 0 0
EA Damper 17 0 0 10 7
OA Damper 19 8 11 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 42” B = 25” (+/- 2”)
Use all lifting lugs provided when lifting, including central lugs on assembled units.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 17
LE6X CORNER WEIGHTS
LE6XINH Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 1975 565 550 424 436
5 1989 570 555 426 438
7.5 2106 611 600 443 452
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall #VALUE! 105 104 104 105
(2) VFDs 14 12 1 0 1
EA Damper 17 5 12 0 0
FA Damper 18 12 6 0 0
TOTAL SELECTED WEIGHTS
LE6XINV Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 1984 569 433 424 558
5 1997 575 434 425 563
7.5 2116 626 442 434 614
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 418 105 104 104 105
(2) VFDs 15 13 1 0 1
EA Damper 18 0 0 6 12
FA Damper 18 12 6 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity A = 36” B = 51” (+/- 2”) Center of Gravity A = 31-3/4” B = 59-1/2” (+/- 2”)
LE6XINH Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1031 307 261 213 250
5 1039 310 263 214 252
7.5 1099 338 277 218 266
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 208 64 40 40 64
(2) VFDs 15 11 3 0 1
EA Damper 0 0 0 0 0
FA Damper 18 6 12 0 0
TOTAL SELECTED WEIGHTS
LE6XINV Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1269 341 304 294 330
5 1283 345 306 297 335
7.5 1400 387 323 314 376
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 208 64 40 40 64
(2) VFDs 15 11 3 0 1
EA Damper 18 0 0 12 6
FA Damper 18 6 12 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 36” B = 27” (+/- 2”) Center of Gravity: A = 32-3/4” B = 27” (+/- 2”)
LE6XINH Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 942 229 174 233 306
5 949 230 174 235 310
7.5 1009 245 175 246 343
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 208 64 40 40 64
(2) VFDs 0 0 0 0 0
EA Damper 17 0 0 10 7
FA Damper 0 0 0 0 0
TOTAL SELECTED WEIGHTS
LE6XINV Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 714 207 158 151 198
5 714 207 158 151 198
7.5 714 207 158 151 198
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 208 64 40 40 64
(2) VFDs 0 0 0 0 0
EA Damper 0 0 0 0 0
FA Damper 0 0 0 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 36” B = 23” (+/- 2”) Center of Gravity: A = 42” B = 25” (+/- 2”)
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 18
LE8X CORNER WEIGHTS
73.5"Lifting Lug
LR RR
LF RF
159.
5" L
iftin
g Lu
g
BASIC UNIT WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP 2495 727 524 521 723
2509 733 524 522 730
2627 787 530 527 783
5 HP
7.5 HP
Options UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 524 131 131 131 131
15 13 1 0 1
29 0 0 8 21
29 21 8 0 0
VFDs
EA Damper
FA Damper
Total Selected Weights
Add the additional weights for options to the Basic Unit weights determined bymotor size to determine Unit and Corner weights for a specific unit.
CORNER WEIGHTS AT LIFTING LUGS
"B"
"A"
1/24/2014 MFSPECIFICATIONS SUBJECTTO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawing
LE-8X-INV_CORNER_WEIGHTS_JAN14.1.dwg
LE8XRT Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 2631 740 660 581 651
5 2645 734 714 591 605
7.5 2763 778 759 605 620
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 524 131 131 131 131
(2) VFDs 15 13 1 0 1
EA Damper 21 6 15 0 0
OA Damper 42 0 0 17 25
TOTAL SELECTED WEIGHTS
Center of Gravity A = 32-1/2” B = 76-1/2” (+/- 2”)
73.5"Lifting Lug
RF LF
RR LR
79.5
" Lift
ing
Lug
BASIC UNIT WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP
918 255 204 204 2555 HP
7.5 HP
Options UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 262 78 53 53 78
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
VFDs
EA Damper
FA Damper
Total Selected Weights
Add the additional weights for options to the Basic Module weights determinedby motor size to determine Module and Corner weights for a specific unit.
BACK MODULE CORNER WEIGHTS AT LIFTING LUGS
Door End
Back Module
"A"
"B"
1/1242014 MFSPECIFICATIONS SUBJECTTO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawing
LE-8X-INV_CORNER_WEIGHTS_JAN14.1.dwg
LE8XRT Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 1320 332 266 321 401
5 1327 333 266 323 404
7.5 1386 341 270 343 433
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 262 78 53 53 78
(2) VFDs 0 0 0 0 0
EA Damper 21 0 0 12 9
OA Damper 21 7 14 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 42” B = 35” (+/- 2”)
73.5"Lifting Lug
LF RF
79.5
" Lift
ing
Lug
BASIC MODULE WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP 1577 461 329 328 459
1591 468 329 328 466
1709 516 341 339 513
5 HP
7.5 HP
Options UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 262 78 53 53 78
15 12 2 0 1
29 0 0 17 12
29 12 17 0 0
VFDs
EA Damper
FA Damper
Total Selected Weights
Add the additional weights for options to the Basic Module weights determinedby motor size to determine Module and Corner weights for a specific unit.
FRONT MODULE CORNER WEIGHTS AT LIFTING LUGS
LR RR
Door End
Front Module
"B"
"A"
1/1242014 MFSPECIFICATIONS SUBJECTTO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawing
LE-8X-INV_CORNER_WEIGHTS_JAN14.1.dwg
LE8XRT Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1311 413 302 251 345
5 1318 417 303 252 346
7.5 1377 449 313 253 362
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 262 78 53 53 78
(2) VFDs 15 12 2 0 1
EA Damper 0 0 0 0 0
OA Damper 21 0 0 9 12
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 33” B = 32-3/4” (+/- 2”)
Use all lifting lugs provided when lifting, including central lugs on assembled units.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 19
LE8X CORNER WEIGHTS
LE8XINH Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 2479 730 636 518 595
5 2493 724 693 526 550
7.5 2611 767 736 542 566
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 524 131 131 131 131
(2) VFDs 15 13 1 0 1
EA Damper 29 8 21 0 0
FA Damper 29 21 8 0 0
TOTAL SELECTED WEIGHTS
LE8XINV Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 2495 727 524 521 723
5 2509 733 524 522 730
7.5 2627 787 530 527 783
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 524 131 131 131 131
(2) VFDs 15 13 1 0 1
EA Damper 29 0 0 8 21
FA Damper 29 21 8 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity A = 36-1/2” B = 66-1/2” (+/- 2”) Center of Gravity A = 32-1/2” B = 76-1/2” (+/- 2”)
LE8XINH Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 1214 286 229 311 388
5 1221 288 229 312 392
7.5 1280 301 228 324 427
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 262 78 53 53 78
(2) VFDs 0 0 0 0 0
EA Damper 29 0 0 17 12
FA Damper 0 0 0 0 0
TOTAL SELECTED WEIGHTS
LE8XINV Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 918 255 204 204 255
5 918 255 204 204 255
7.5 918 255 204 204 255
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 262 78 53 53 78
(2) VFDs 0 0 0 0 0
EA Damper 0 0 0 0 0
FA Damper 0 0 0 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 36-3/4” B = 35” (+/- 2”) Center of Gravity: A = 42” B = 35” (+/- 2”)
LE8XINH Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1265 409 295 235 326
5 1272 413 296 235 328
7.5 1331 445 307 236 343
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 262 78 53 53 78
(2) VFDs 15 12 2 0 1
EA Damper 0 0 0 0 0
FA Damper 29 12 17 0 0
TOTAL SELECTED WEIGHTS
LE8XINV Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1577 461 329 328 459
5 1591 468 329 328 466
7.5 1709 516 341 339 513
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 262 78 53 53 78
(2) VFDs 15 12 2 0 1
EA Damper 29 0 0 17 12
FA Damper 29 12 17 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 36-1/2” B = 32-3/4” (+/- 2”) Center of Gravity: A = 33” B = 32-3/4” (+/- 2”)
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 20
LE10X CORNER WEIGHTS
73.5" Lifting Lug
LR RR
LF RF
194.
5" L
iftin
g Lu
g
BASIC UNIT WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP 3032 842 841 674 674
3046 847 846 676 676
3164 892 890 690 691
5 HP
7.5 HP
Options UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 627 155 158 158 155
15 13 1 0 1
21 7 14 0 0
70 0 0 36 35
VFDs
EA Damper
OA Damper
Total Selected Weights
Add the additional weights for options to the Basic Unit weights determined by motor size to determine Unit and Corner weights for a specific unit.
CORNER WEIGHTS AT LIFTING LUGS
"B"
"A"
10 HP 3202 906 904 695 696
Center of gravity: A=32" B= 99-1/2" (+/- 2")
11/24/2015 KMCSPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawing
LE10X-RT_CORNER_WEIGHTS_NOV15.dwg
LE10X-RT Corner WeightsSheet 1 of 4
73.5" Lifting Lug
LF RF
99.5
" Lift
ing
Lug
FRONT MODULE CORNER WEIGHTS AT LIFTING LUGS
LR RR
"B"
"A"
Front Module
Door End
BASIC UNIT WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP 1493 445 396 307 344
1500 448 398 308 346
1559 474 415 313 357
5 HP
7.5 HP
Options UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 313 77 79 79 77
15 12 2 0 1
0 0 0 0 0
21 0 0 10 11
VFDs
EA Damper
OA Damper
Total Selected Weights
Add the additional weights for options to the Basic Unit weights determined by motor size to determine Unit and Corner weights for a specific unit.
10 HP 1578 483 420 314 361
Center of gravity: A=31-1/2" B= 46-1/2" (+/- 2")
11/24/2015SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawingLE10X-RT Front Module Corner Weights Sheet 3 of 4LE10X-RT_CORNER_WEIGHTS_NOV15.dwg
73.5" Lifting Lug
RF LF
RR LR
99.5
" Lift
ing
Lug
BACK MODULE CORNER WEIGHTS AT LIFTING LUGS
"A"
"B"
Door End
Back Module
BASIC UNIT WEIGHTS (lbs.)
Motors UNIT LF LR RR RF
3 HP 1539 330 334 440 435
1546 354 346 419 427
1605 363 348 437 456
5 HP
7.5 HP
Options UNIT LF LR RR RF
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Double Wall 313 91 66 66 91
0 0 0 0 0
21 0 0 15 6
35 17 18 0 0
VFDs
EA Damper
OA Damper
Total Selected Weights
Add the additional weights for options to the Basic Unit weights determined by motor size to determine Unit and Corner weights for a specific unit.
10 HP 1624 367 349 443 466
Center of gravity: A=41" B= 48-1/2" (+/- 2")
11/24/2015SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
RenewAire LLC
Do not scale drawingLE10X-RT Back Module Corner Weights Sheet 4 of 4LE10X-RT_CORNER_WEIGHTS_NOV15.dwg
LE10XRT Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 3032 842 841 674 674
5 3046 847 846 676 676
7.5 3164 892 890 690 691
10 3202 906 904 695 696
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 627 155 158 158 155
VFDs 15 13 1 0 1
EA Damper 21 7 14 0 0
OA Damper 70 0 0 36 35
TOTAL SELECTED WEIGHTS
Center of Gravity A = 32" B = 99-1/2" (+/- 2")
LE10XRT Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 1539 330 334 440 435
5 1546 354 346 419 427
7.5 1605 363 348 437 456
10 1624 367 349 443 466
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 313 91 66 66 91
VFDs 0 0 0 0 0
EA Damper 21 0 0 15 6
OA Damper 35 17 18 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 41" B = 48-1/2" (+/- 2")
LE10XRT Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1493 445 396 307 344
5 1500 448 398 308 346
7.5 1559 474 415 313 357
10 1578 483 420 314 361
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 313 77 79 79 77
(2) VFDs 15 12 2 0 1
EA Damper 0 0 0 0 0
OA Damper 21 0 0 10 11
TOTAL SELECTED WEIGHTS
Center of Gravity: A = 31-1/2" B = 46-1/2" (+/- 2")
Use all lifting lugs provided when lifting, including central lugs on assembled units.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 21
LE10X CORNER WEIGHTS
LE10XINV Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 2858 819 665 616 759
5 2872 825 666 617 765
7.5 2990 874 676 628 812
10 3028 889 679 632 828
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 616 153 155 155 153
(2) VFDs 15 13 1 0 1
EA Damper 29 0 0 10 19
FA Damper 29 19 10 0 0
TOTAL SELECTED WEIGHTS
LE10XINH Models
Motor HPBasic Unit Weights (lbs.)
Unit LF LR RR RF
3 2858 828 817 603 611
5 2872 833 822 604 612
7.5 2990 878 866 619 627
10 3028 892 880 624 632
Adder Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 627 155 158 158 155
(2) VFDs 15 13 1 0 1
EA Damper 29 19 10 0 0
FA Damper 29 10 19 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity A = 35-1/2" B = 86-1/2" (+/- 2")
LE10XINV Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 1127 349 204 212 362
5 1127 349 204 212 362
7.5 1127 349 204 212 362
10 1127 349 204 212 362
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 313 91 66 66 91
(2) VFDs 0 0 0 0 0
EA Damper 0 0 0 0 0
FA Damper 0 0 0 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity A = 37-1/2" B = 37" (+/- 2")
LE10XINH Models
Motor HPBasic Back Module Weights (lbs.)
Unit LF LR RR RF
3 1423 340 267 359 456
5 1430 341 268 361 460
7.5 1489 350 271 378 490
10 1508 353 271 384 499
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 313 91 66 66 91
(2) VFDs 0 0 0 0 0
EA Damper 29 0 0 20 9
FA Damper 0 0 0 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity A = 30-1/2" B = 99" (+/- 2")
LE10XINV Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1732 468 442 399 423
5 1746 473 443 401 428
7.5 1864 511 464 423 466
10 1902 525 469 428 479
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 308 76 78 78 76
(2) VFDs 15 12 2 0 1
EA Damper 29 0 0 20 9
FA Damper 29 9 20 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity A = 43" B = 43" (+/- 2")
Center of Gravity A = 35" B = 47" (+/- 2")
LE10XINH Models
Motor HPBasic Front Module Weights (lbs.)
Unit LF LR RR RF
3 1436 384 389 286 322
5 1443 441 391 287 323
7.5 1502 467 408 292 334
10 1521 477 412 293 339
Adder Module Weights for Installed Options (lbs.)
Options Unit LF LR RR RF
Double Wall 313 78 79 79 78
(2) VFDs 15 12 2 0 1
EA Damper 0 0 0 0 0
FA Damper 29 10 19 0 0
TOTAL SELECTED WEIGHTS
Center of Gravity A = 30-1/2" B = 46-1/2" (+/- 2")
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 22
This page intentionally left blank.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 23
This page intentionally left blank.
LE Rigging Due to continuing product development, specifications are subject to change without notice. © 2015 RenewAire LLC138231_002 LERiggingMan_Dec15.indd Revised 12/2015 www.renewaire.com Page 24
See more specific Installation and Operation Manual for additional Assembly, Start-Up, Commissioning and Maintenance supplied
with the unit and Manuals at www.renewaire.com.