DATE: August 11, 2016
SOLICITATION NO.: ITB 160450LC
SUBJECT: ADDENDUM NUMBER 1
REFERENCE: Justice Center Switchgear Change Out
The following changes shall become a part of the Bid Documents and shall be as binding as if contained therein:
1. Proposal Form:1.1 A new Proposal Form (Form 1a) has been provided herein to
replace that provided on page 23 of the bid package.
You MUST use the new Proposal Form when submitting your bid. The new Proposal Form is attached and made part of this addendum.
Failure to utilize the new Proposal Form will result in your firm being deemed Non-Responsive and therefore ineligible for award.
2. Bill of Materials:2.1. A bill of materials/quotation is attached and made part of this
addendum to provide more detailed information on what Square D services is providing and what is included in their scope. Contractor must provide all items and services as listed within this bill of materials and may not modify list in any way. Equipment listed on bill of materials provides for gear only and is not inclusive of all materials required to completed full removal and replacement. Contractor is required to furnish and install any additional materials required to completed scope of work (IE: conduits, wiring, etc…).
2.2 Square D contact is Mr. Al Cason, Project Order Manager for Square D services at 239-936-5627.
2.3 REMINDER: All equipment shall be Square D. No substitutions, equals, or remanufactured/reconditioned products are permitted for this project.
3. Questions:
3.1 Is new Switchgear sales tax exempt, See Invitation to Bid item 9 on
page 7?
Answer As the Contractor is expected to furnish and install materials,
Contractor is responsible for any applicable sales tax.
BOARD OF COUNTY COMMISSIONERS
John E. Manning District One
Cecil L Pendergrass District Two
Larry Kiker District Three
Brian Hamman District Four
Frank Mann District Five
Roger Desjarlais County Manager
Richard Wm. Wesch County Attorney
Donna Marie Collins Hearing Examiner
![Page 2: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/2.jpg)
P.O. Box 398, Fort Myers, Florida 33902-0398 (239) 533-2111 Internet address http://www.lee-county.com
AN EQUAL OPPORTUNITY AFFIRMATIVE ACTION EMPLOYER
3.2 Is detailed information available, such as the original equipment
drawings to obtain the required lay-out & measurements?
Answer
The original gear has been modified many times, so no, there
are no accurate drawings. We would suggest that the pre-bid
walk-through after the pre-bid meeting be used to gather
information.
3.3
Per the requirements in Bid Item 2 on page 4, Bidder Examination/
Investigation of Site, will the existing gear be opened for us to
review the conditions?
Answer A site visit will be held following the pre-bid meeting; however
the switchgear itself will not be opened.
3.4
Drawing E3, existing single line, indicates circuit 3E is a 400amp
3pole space. Drawing E1 & E4, Proposed switchgear, indicate a
600amp 3pole. Which is correct?
Answer
The existing single line on E3 shows what exists now, E2 and E4
show what is desired of the new gear by the owner. To be more
specific, both are correct. E3 shows what they have and E2 and
E4 show what is desired.
3.5 Will the Switchgear be purchased from a State Contract Vendor,
Invitation to Bid page 9 Item 17a?
Answer
Purchase of switchgear is not anticipated to be completed
through a State Contract Vendor. This is a boilerplate clause
that reserves the County’s right to purchase off the State
Contract if parameters are met as listed within this provision.
3.6 Please confirm no Permits are required per the N/A as stated in the
Invitation to Bid page 14 Item 36.
Answer
Permits are required to complete this work; however the
Contractor is not expected to pay for any permits associated
with this project. This clause is only to list any permits the
Contractor is required to pay for.
3.7
Please provide the name & phone number of the FPL contact to
obtain the required Utility Company Charges, Invitation to Bid page
14 Item 36.
Answer The FP&L contact TLC worked with during design was
Shameed Hamid. Ph: 239-332-9187
3.8 Will factory start-up, testing and inspection be required prior to FPL
re-energizing their transformer?
Answer
Inspection will be required by the City of Fort Myers and Lee
County D+C before re-energizing the transformer. As noted on
the documents all bus duct modifications will be by the
manufacturer (Square D). Testing and infrared scanning is by
the contractor. Any work performed by Square D, would be
tested and checked by them.
![Page 3: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/3.jpg)
P.O. Box 398, Fort Myers, Florida 33902-0398 (239) 533-2111 Internet address http://www.lee-county.com
AN EQUAL OPPORTUNITY AFFIRMATIVE ACTION EMPLOYER
3.9
Will the facility operate under its own emergency power for this
shutdown or is the Contractor to provide and maintain emergency
power for the entire facility including the existing 1600amp bus to
the courthouse & chiller feeders?
Answer
As it states in the documents, all shutdowns are to be
coordinated through the owner/Jail and FP&L. The Jail and
the LCJC Proper have sufficient emergency power. However, if
scheduled properly during a long weekend to minimize the
outage for the legal community, only the jail may require
emergency power. No shutdown of the system, will be
considered without full knowledge and consent of the
stakeholders and a coordinated plan for the shutdown shall be
documented for all to approve
3.10
Existing One Line drawing E3 shows 5 Buss termination points.
The new proposed switchgear on Drawing E4 shows 3 Buss
connections. Please clarify.
Answer
The project is to replace existing switchgear which does not
have a main disconnect. The proposed switchgear has a main
disconnect and consolidates all breakers and accessories into a
consolidated, manageable footprint. It really doesn’t matter
that the existing gear has five (5) terminations, the new
proposed gear only requires three (3) bus terminations, so three
(3) are shown.
3.11 What is the spec for the switchgear for this project?
Answer The plans and specifications provided within the solicitation
package are complete and sufficient to provide a proposal for
the requested scope of work. All equipment shall be Square D
and as such plans have been based on use of Square D
equipment.
3.12 Is the existing gear is Westing House?
Answer Yes, the existing gear is Westing House with Square D housing.
3.13 Have we received FP&L specific startup criteria?
Answer See question 3.8. More detailed information can be determined
when Contractor meets with FP&L. Sufficient information has
been provided for bidding purposes.
3.14 Will the connection be a bolted or cable connection?
Answer Connections are to be bolted. Connections to equipment and
interface with or modification of existing Bus Duct must be and
will be completed by the manufacturer. Contractor is
responsible for coordination and scheduling with manufacturer
in addition to payment of any fees associated with services
provided manufacturer.
![Page 4: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/4.jpg)
P.O. Box 398, Fort Myers, Florida 33902-0398 (239) 533-2111 Internet address http://www.lee-county.com
AN EQUAL OPPORTUNITY AFFIRMATIVE ACTION EMPLOYER
3.15 What if equipment cannot fit pad?
Answer The gear selected is a custom design and made to fit the existing
pad. Due to size restrictions and underground pipes coming in
the design of the gear was made to fit the existing pad and to
accommodate the existing conduits and wire.
3.16 What is the location of the door to be removed?
Answer Contractor is responsible for removal and replacement of the
exterior entry door. Interior door to storage area will be
replaced by Lee County prior to work commencing.
3.17 What is to be done with the existing gear that is removed?
Answer Gear removed becomes property of the Contractor.
3.18 Is a GC (General Contractor) required to complete this work or pull
the permit?
Answer No, a GC is not required to complete this work and the permits
have been pulled already. A change of contractor will be
needed.
3.19 Bus duct is aluminum and plans call for reuse of existing. Has
existing been checked thoroughly? We cannot guarantee reuse or
quality of connection if condition is not known or bus is in poor
condition.
Answer Contractors shall work from plans as stated and plan to reuse
existing bus duct. Replacement is not expected to be necessary.
See question 3.20 for continuation to response.
3.20 Who is completing the bus duct connection? Is item 2.4 page 17
correct?
Answer As noted in the provided Bill of Materials and through item 2.4
on page 17 of the bid package, the work related to the bus duct
shall be performed by Square D services, so that the warranty is
retained on the new switchgear. Since all work is custom, the
field changes must be performed by the manufacturer.
3.21 There is not an area to store materials, correct?
Answer Correct. There is no area for storing of materials for this job.
3.22 Are there any security measures we need to be processed through?
Answer No security measures as we are at the exterior of the building.
Access through exterior door is via key only.
3.23 Can we use a Polaris connection?
Answer Plans clearly state, that the extension of the cabling shall be
performed by using double crimp, hy-press fittings with heat
shrink covering. See sheet E4.
![Page 5: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/5.jpg)
P.O. Box 398, Fort Myers, Florida 33902-0398 (239) 533-2111 Internet address http://www.lee-county.com
AN EQUAL OPPORTUNITY AFFIRMATIVE ACTION EMPLOYER
3.24 Could you please provide a contact for Facilities and the Inspection
Dept. so we can initiate conversations regarding their respective
involvement on the project?
We are primarily concerned with the requirements for temporary
when the System is down and the associated fees for the inspections
and permits.
Answer Specific questions regarding this project should be directed to
the Procurement Management office only. See bid package
cover page for contact information.
For general permitting and inspection questions please see Lee
County websites for details and contact information.
https://www.leegov.com/dcd/BldPermitServ
3.25 Please provide specific requirements regarding which loads need to
be keep operational during the shutdown by providing a one line
diagram of the Emergency System or Systems that will be affected /
utilized by this shutdown. Who specifically, and a contact number,
should this be addressed with at this time for preparation of our
proposal?
Answer The specific requirements will be determined, when the
shutdown date has been coordinated and set with the downtown
Jail, Lee County D+C and the owner. As all critical systems in
the jail and the LCJC Proper are on Emergency and can be
isolated from the switchgear being removed, a one-line is not
required. The names of the County personnel that need to be
contacted will be provided after the project has been awarded.
As noted on the documents, the work is to occur over a long or
holiday weekend. Which weekend will be determined by when
all parties can agree on a date and when the gear can be on-site.
Please refer to shutdown scheduling notes on Drawings E1 – E4
and Addendum #1 responses 3.9 – 3.24. Pay specific attention to
response 3.24 which instructs the bidders to only communicate
with procurement unless specifically directed otherwise.
3.26 Will there be fuel requirements to run the emergency system?
Answer Lee County and the Jail will take care of the fueling
requirements over a long weekend.
![Page 6: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/6.jpg)
P.O. Box 398, Fort Myers, Florida 33902-0398 (239) 533-2111 Internet address http://www.lee-county.com
AN EQUAL OPPORTUNITY AFFIRMATIVE ACTION EMPLOYER
3.27 We are not able to see inside the switchgear until the shutdown.
Please provide a single line riser diagrams of the existing loads /
connections for the Existing Switchboard. We need to have wire
sizes and quantities to have the proper material available to
spice existing cables. Is THHN acceptable for splicing?
Answer You will have to estimate wire sizes and quantities based upon
NEC tables for the purpose of bidding. If you read the Square
D bill of material, you will see that it calls for a shutdown ahead
of the gear replacement to verify connections and modifications
to the bus for the purpose of being prepared for the shutdown
and gear replacement. At the point when the shutdown for
Square D is done, the contactor could then open the gear and
confirm cable quantity and sizes within the switchgear and also
confirm cable lengths and insulation types.
3.28 Are there any control circuits that are connected to this switchgear
that will be affected by this replacement? Please detail.
Answer There is a shunt trip circuit that goes to the exterior shown on
Drawing E4.
3.29 Drawing E1 – Existing Switchgear Elevation shows 3 buss
connections. Drawing E3 - Existing One Line appears to indicates 5
buss connections. What is correct?
Answer See question 3.10.
3.30 Drawing E3 - Existing One Line indicates (14) 4” conduits entering
the top of the Switchboard. We only were able to see 8. Where are
the other conduits and what are they for?
Answer As stated previously, There have been many changes overtime,
the conduits as shown on the one line, indicate that the (6) 4”
feed the JC Proper and the (8) 4” feed the CEP. There has been
some work that converts some of the conduits to busduct, and J-
boxes which should have been observed during the pre-bid
walkthrough.
3.31 Is new or additional grounding required or just a reconnection of the
existing system?
Answer That will depend on what the ground connection measures, once
the new gear is in place and everything is re-connected. If the
re-connected grounding meets the requirements of Specification
Section 260526 then no additional grounding is required.
3.32 Does the exterior door need to be replaced by the end of the
shutdown or can it be replaced the next day during normal working
hours?
Answer The room cannot be left unsecured. Once the shutdown is
completed and the equipment is re-energized, the room must be
secured.
![Page 7: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/7.jpg)
P.O. Box 398, Fort Myers, Florida 33902-0398 (239) 533-2111 Internet address http://www.lee-county.com
AN EQUAL OPPORTUNITY AFFIRMATIVE ACTION EMPLOYER
3.33 Please provide a contact, and contact number, for the Inspection
Dept. to initiate conversations regarding their respective
involvement on the project. This is needed for the permitting and
inspection requirements and the associated fees and scheduling a
Sunday or Holiday for the inspection.
Answer See question 3.24.
3.34 When will we be able to schedule a shutdown prior to the
replacement?
Answer Please refer to shutdown scheduling notes on Drawings E1 – E4
and Addendum #1 responses 3.9 – 3.24. Pay specific attention to
response 3.24 which instructs the bidders to only communicate
with procurement unless specifically directed otherwise. Also
see response to 3.27.
3.35 Please provide the Lee County Holiday Schedule, or the days
available over the next 9 months to schedule the shutdown.
Answer Lee County holiday scheduled is attached and made part of this
addendum.
ATTACHMENTS:
1. Proposal Form - Revised
2. Bill of Materials / Quotation
3. Pre-Bid Sign-in Sheets
4. Lee County Holiday Schedule
BIDDER IS ADVISED, YOU ARE REQUIRED TO ACKNOWLEDGE RECEIPT OF THIS ADDENDUM WHEN SUBMITTING A BID. FAILURE TO COMPLY WITH THIS REQUIREMENT MAY RESULT IN THE BIDDER BEING CONSIDERED NON-RESPONSIVE. ALL OTHER TERMS AND CONDITIONS OF THE BIDDING DOCUMENTS ARE AND SHALL REMAIN THE SAME.
Lindsay Cepero ___________
Procurement Analyst Lee County Procurement Management
![Page 8: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/8.jpg)
Ver 6/2/2016
23 ADDENDUM 1 – Issued 8/11/2016
Form 1a – Proposal Form (Revised)
Lee County Procurement Management
PROPOSAL FORM
Company Name:
Solicitation # ITB 160450LC Solicitation Name Justice Center Switchgear Change Out
Having carefully examined the “Terms and Conditions”, and the “Detailed Specifications”, all of which are contained herein, propose to furnish
the following which meet these specifications.
Term
From Notice to Proceed or Purchase Order date, whichever applies: 180 calendar days to substantial completion, 210 calendar days to final
completion. Installation of equipment must be completed over the course of one (1) weekend which may include holidays. The County’s
performance and obligation to pay under this contract and any applicable renewal options is contingent upon appropriation of funds.
Pricing
Pricing shall be inclusive of all labor, equipment, supplies, overhead, profit, material, and any other incidental costs required to perform and
complete all work as specified herein.
Price quoted shall provide for a full “Turn Key” service inclusive of all parts, delivery, installation, testing, haul away, disposal, site restoration,
etc…encompassing all terms and conditions as specified herein. There will be NO Change Orders allowed or approved under this award. All
pricing to be F.O.B destination.
Warranty
All materials and equipment furnished and work performed is guaranteed for a period of one (1) year from the date of installation and shall
follow all terms as defined herein.
Delivery Lead Time
Delivery lead time is expected to be approx. ___________ calendar days after receipt of Notice to Proceed / Purchase Order. (Insert Days)
JUSTICE CENTER SWITCHGEAR CHANGE OUT
ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SWITCHGEAR CHANGE OUT
1
Removal and replacement of the existing switchgear located at the Lee
County Justice Center. Scope of work includes, but is not limited to: all
required manpower to take delivery of existing gear such as disconnect all
conduits, cables, grounding and bus duct from existing gear and installation
of a new 4000 Amp main disconnect and switchgear with reconnection of all
conduits, cables, grounding, and bus ducts. Scope additionally includes:
removal of the existing door(s) and frame(s) where applicable along with re-
installation of existing door(s) with furnish and supply of new panic bar
style hardware. Work shall be a complete “Turn Key” package inclusive of
all: switchgear, miscellaneous material, and labor (including nights,
weekends, and holidays as project requires) necessary to complete scope of
work and all project requirements contained in ITB 160450LC, Justice
Center Switchgear Change Out.
LS 1 $
BID SUMMARY
PROJECT GRAND TOTAL: $
GRAND TOTAL:
(Use Words to Write Total) Square D Materials:
With signature below, Contractor affirms that all items as presented in bill of materials provided within Addendum 1 are included within
pricing proposed without modification.
Authorized Bidder Signature Date:
Authorized Bidder Name (Print or Type)
![Page 9: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/9.jpg)
PAGE 1 OF 5
QUOTATION
Quotation
Quote Number: 1
Project Name: LEE COUNTY JUSTICE CENTER
Project Sub-Name:
Project Location: Fort Myers, FL
Quote Name: REPLACEMENT SERVICE ENTRANCE
Through Addenda Number: 0
Bid Date: 8/4/2016
Consultant / Specifier: TILDEN LOBNITZ COOPER
Contractor / Installer:
Sales Representative: ADY HARDY
Conditions of Sale
This Quotation is subject to Coordinated Project Terms.
Payment Terms: STANDARD
Billing Type(s):
Currency: US DOLLARS
Quote Markings
PRINTED 8/8/2016 8:32:00 AM
ADDENDUM 1 – Issued 8/11/2016
![Page 10: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/10.jpg)
PAGE 2 OF 5
Quote Number: 1
Project Name: LEE COUNTY JUSTICE CENTER Quote Name: REPLACEMENT SERVICE ENTRANCE
Item No. Qty. Catalog Number / Details
QUOTATION
001-00 1 Designation: MDP Square D Custom Swbd QED Switchboard --------------------------------- Square D Custom Swbd Designed and Tested in accordance with: UL 891/NATIONAL ELECTRIC CODE/NEMA PB-2 System Voltage - 480Y/277V 3Ph 4W 60Hz Source Description - Single Main System Ampacity - 4000A Bussing - Silver Plated Copper Neutral Bus - 100% Max Available Fault Current (RMS) - 100kA Enclosure - Type 1 Accessibility: Front and Rear Breaker Lifting and Transport Truck (Flr Crane) Exterior Paint Color - ANSI 49 Ground Lug provided for each device Copper Ground Bus
Dimensions --------------------------------- 1 - 24" Wide Section(s) 2 - 36" Wide Section(s) 3 - 48" Wide Section(s) 6 - 48" Deep Enclosure(s) Dimensions: 240.00" W X 48" Max D X 91.5" H Approximate Weight: 8180.00 lbs / 3710.45 kgs
Incoming Requirements --------------------------------- Suitable for Use As Service Entrance Entry Point: Center of Lineup, Through the Top Aluminum Busway, Bus Duct Dummy Front to Rear NCBA Surge Arrestor SPD with Surge Rating 240kA SPD Dry Contacts Includes Surge Counter Power Meter - PM5563RD 3 CTs PM5563 w/ Display - 3 phase 4 wire wye 4000A
Mains --------------------------------- 1 - 4000AF/4000AT 100% 3 Pole Stored Energy,
Drawout Mounted Circuit Breaker, UL: Type NW Ammeter Trip Unit, Long Time, Short Time, Instantaneous, Ground Fault
Overcurrent Trip Switch 1A/1B Form C Contact (SDE) Auxiliary Switches 4A-4B Padlock Attachment Shunt Trip - 120Vac Drawout Crank Contact Wear Indication - Visual Padlock Provisions on Cradle Cradle Cell Keying Specials: Flanged End 21" from Right Special Flanged End 21" from Right #:
PRINTED 8/8/2016 8:32:00 AM
ADDENDUM 1 – Issued 8/11/2016
![Page 11: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/11.jpg)
PAGE 3 OF 5
Quote Number: 1
Project Name: LEE COUNTY JUSTICE CENTER Quote Name: REPLACEMENT SERVICE ENTRANCE
Item No. Qty. Catalog Number / Details
QUOTATION
6026789
Feeders --------------------------------- 4 - 400AS/400AT 480V 100% Rated 100 kA 3 Pole
UL, Group Mounted Electronic Trip Circuit Breaker: Type LL
Standard Trip Unit, Long Time, Instantaneous
Shunt Trip - 120Vac Padlock Attachment 2 - 600AS/600AT 480V 100% Rated 100 kA 3 Pole
UL, Group Mounted Electronic Trip Circuit Breaker: Type PL
Standard Trip Unit, Long Time, Instantaneous
Padlock Attachment Shunt Trip without Communications - 120Vac 1 - 2000AF/1600AT 100% 3 Pole Stored Energy,
Drawout Mounted Circuit Breaker, UL: Type NW Standard Trip Unit, Long Time, Short Time, Instantaneous
Copper Busway, Qwik-Flange Overcurrent Trip Switch 1A/1B Form C Contact (SDE)
Auxiliary Switches 4A-4B Left to Right NABC Drawout Crank Contact Wear Indication - Visual Cradle Cell Keying Power Meter - PM5563RD 3 CTs PM5563 w/ Display - 3 phase 4 wire
wye 2000A 1 - 3000AF/3000AT 100% 3 Pole Stored Energy,
Drawout Mounted Circuit Breaker, UL: Type NW Standard Trip Unit, Long Time, Short Time, Instantaneous
Copper Busway, Qwik-Flange Overcurrent Trip Switch 1A/1B Form C Contact (SDE) Auxiliary Switches 4A-4B Front to Rear NCBA Drawout Crank Contact Wear Indication - Visual Cradle Cell Keying Power Meter - PM5563RD 3 CTs PM5563 w/ Display - 3 phase 4 wire wye 3000A
PRINTED 8/8/2016 8:32:00 AM
ADDENDUM 1 – Issued 8/11/2016
![Page 12: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/12.jpg)
PAGE 4 OF 5
Quote Number: 1
Project Name: LEE COUNTY JUSTICE CENTER Quote Name: REPLACEMENT SERVICE ENTRANCE
Item No. Qty. Catalog Number / Details
QUOTATION
002-00 1 Designation: 3000A for CEP I-LINE BUSWAY I-LINE BUSWAY CONSISTING OF ----------------------------------------------
3000A Copper/Silver Busway 480Y/277V 3Ph 4W 60Hz Ground Bus Reqmt: Copper Integral Ground 100kA Feeder / 125kA Plug-in RMS Symmetrical Short Circuit Rating Date Configured: 8/4/2016 8:52:17 AM
Indoor Segment Run Consisting of: ----------------------------------------------
3 Feet of Feeder Busway 1 90 Degree Elbows 1 Assembly Tools
003-00 1 Designation: 2000A for Justice Cntr I-LINE BUSWAY I-LINE BUSWAY CONSISTING OF ----------------------------------------------
2000A Copper/Silver Busway 480Y/277V 3Ph 4W 60Hz Ground Bus Reqmt: Copper Integral Ground 100kA RMS Symmetrical Short Circuit Rating Date Configured: 8/4/2016 8:52:17 AM
Indoor Segment Run Consisting of: ----------------------------------------------
20 Feet of Feeder Busway 4 90 Degree Elbows 1 Assembly Tools
004-00 1 ACF27EC. BUSWAY END CLOSURE
PRINTED 8/8/2016 8:32:00 AM
ADDENDUM 1 – Issued 8/11/2016
![Page 13: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/13.jpg)
PAGE 5 OF 5
Quote Number: 1
Project Name: LEE COUNTY JUSTICE CENTER Quote Name: REPLACEMENT SERVICE ENTRANCE
Item No. Qty. Catalog Number / Details
QUOTATION
005-00 1 SRVINCLVTEST
Square D Services
Evaluation site visit (power outage required) - busway run revisions - confirm internal switchboard connections
006-00 1 SRVINCLV
Square D Services
On site technical supervision: -removal and re-installaion of existing 4000A service entrance busway (contractor responsible for labor and meggering) -remova1 and re-installation of existing 3000A busway plus new 3000A busway (contractor responsible for labor and meggering) -removal and re-installation of existing 2000A busawy plus new 2000A busway (contractor responsible for labor and meggering) -removal of existing switchboard, installation of new equipment (labor by contractor)
007-00 1 SRVLVMADTTKY
Square D Services to provide:
Switchboard spare circuit breakers:
3000/3 2000/3 600/3 400/3
PRINTED 8/8/2016 8:32:00 AM
ADDENDUM 1 – Issued 8/11/2016
![Page 14: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/14.jpg)
ADDENDUM 1 – Issued 8/11/2016
![Page 15: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/15.jpg)
ADDENDUM 1 – Issued 8/11/2016
![Page 16: Lee County Procurement Management 1500 Monroe Street …...the switchgear itself will not be opened. 3.4 Drawing E3, existing single line, indicates circuit 3E is a 400amp 3pole space](https://reader036.vdocument.in/reader036/viewer/2022071403/60f6fd2d2e876c061148b747/html5/thumbnails/16.jpg)
8/11/2016 Lee County Holidays
https://www.leegov.com/hr/holidays 1
Lee County Holidays
HOLIDAYS DATES OBSERVED
2016
New Year's Day Dec. 31, 2015 & Jan. 1, 2016
Martin Luther King, Jr. Day Jan. 18, 2016
Memorial Day May 30, 2016
Independence Day July 4, 2016
Labor Day Sept. 5, 2016
Veterans' Day Nov. 11, 2016
Thanksgiving Nov. 24‐25, 2016
Christmas Dec. 23 & 26, 2016
2017
New Year's Day Dec. 30, 2016 & Jan. 2, 2017
Martin Luther King, Jr. Day Jan. 16, 2017
Memorial Day May 29, 2017
Independence Day July 4, 2017
Labor Day Sept. 4, 2017
Veterans' Day Nov. 10, 2017
Thanksgiving Nov. 23‐24, 2017
Christmas Dec. 22 & 25, 2017
Based upon Lee County Policy 403‐Holidays, Human Resources will update the designated New Year's Holidaydates for the 2017 Holiday Schedule by Oct. 1, 2016.
NOTE: Some Lee County departments remain open and/or provide services on these observed holidays.
Please contact specific departments directly to determine their individual schedules.