lessons learned solving pilot valve instability issues on lng storage tanks

28
1 Lessons learned solving pilot valve instability issues on LNG storage tanks LNG Summit Houston 23/24 Feb 2017 Thorsten Schaper (Speaker) Braunschweiger Flammenfilter GmbH (PROTEGO)

Upload: protego-braunschweiger-flammenfilter-gmbh

Post on 12-Apr-2017

55 views

Category:

Technology


0 download

TRANSCRIPT

Page 1: Lessons learned solving pilot valve instability issues on LNG storage tanks

1

Lessons learned solving pilot

valve instability issues on LNG

storage tanks

LNG Summit Houston 23/24 Feb 2017

Thorsten Schaper (Speaker)

Braunschweiger Flammenfilter GmbH (PROTEGO)

Page 2: Lessons learned solving pilot valve instability issues on LNG storage tanks

2

Applications for Cryogenic Tanks

LNG Terminal Bulk Storage Tank with a set of P/V valves

Page 3: Lessons learned solving pilot valve instability issues on LNG storage tanks

3

Pilot-operated Valves on LNG-Tanks

Page 4: Lessons learned solving pilot valve instability issues on LNG storage tanks

4

Where are the problems?

• Pilot operated pressure relief valves installed on cryogenic

storage tanks may become unstable as a result of inaccurate

plant design or sudden construction changes on site.

• Pilot operated valves which are forced to become unstable may

not provide sufficient relief capacity resulting in overpressure

and imposing safety risks to the facility.

• It is known that relief valve instability is a dynamic problem

which requires an understanding and coupling of the pressure

source (e.g. LNG storage tank), the inlet line, the pilot operated

pressure relief valve and the discharge line.

Page 5: Lessons learned solving pilot valve instability issues on LNG storage tanks

5

Some reasons for instability and lessons learned

• It is quite obvious that the 3 % rule – known from

pressure safety valves - is not sufficient to guarantee

POV stability.

• POV instability is a dynamics problem which requires

an understanding and coupling of the dynamics of the

following components:

1- Inlet Line

2- Discharge Line

3- Pressure Source or Vessel/Equipment

4- Pilot-Operated Valve - POV

Page 6: Lessons learned solving pilot valve instability issues on LNG storage tanks

6

Since the 80th PROTEGO® delivered a lot of Pilot valves around the world

Lessons learned for 1 and 2

Page 7: Lessons learned solving pilot valve instability issues on LNG storage tanks

7

Since the 80th PROTEGO® delivered a lot of Pilot valves around the world

Lessons learned for 1 and 2

Results:

• Common guidance on

how to design the

piping seems to be

missing or is not

applied in all cases

• Inlet pressure loss

seem to be neglected in

some cases

• Built up pressure in the

discharge line is not

allways considered

Page 8: Lessons learned solving pilot valve instability issues on LNG storage tanks

8

˙

To high inlet pressure loss:

Chattering, hammering, results in flow

reduction and can destroy the valve

To high built up pressure in the vent line:

Pumping, Flow reduction but lower risk of

destroying the valve

Lessons learned for 1 and 2

1- Inlet Line 2- Discharge Line

Page 9: Lessons learned solving pilot valve instability issues on LNG storage tanks

9

Example LNG Plant:

The installed 12“ PROTEGO-devices PM/S 300/350

experienced extrem instabilities.

The valve pallet was hammering on the seat and

destroyed the Aluminum valve pallet.

When opening the discharge line we could see that

the valve pallet did no reach full lift, which can

result in a reduced relief capacity

˙

Page 10: Lessons learned solving pilot valve instability issues on LNG storage tanks

10

Problem-analysis (chattering)

Chattering resulted from to high inlet pressure losses.

For safety relief valve everyone is familiar with the 3%

rule.

When calculating the inlet pressure losses we received

results up 20%-30% of the set pressure

This high inlet pressure loss exceeded the blow down

by far.

In addition the customer used a sensing line directly at

the valve body and not an installation at the tank. In that

case higher flow reduces the static pressure and the

valve acts extremly unstable. The static pressure fell

below the crack pressure of the magnetic valve.

˙

Page 11: Lessons learned solving pilot valve instability issues on LNG storage tanks

11

Solution: Increase blow down of the pilot valve

0

50

100

150

200

250

Magnetplatte Nr 1 pe=+10 … 20 mbar

Magnetplatte Nr 2pe=+21… 120 mbar

Magnetplatte Nr 2pe=+21… 120 mbar

Magnetplatte Nr 3pe=+120… 300 mbar

Magnetplatte Nr 3pe=+120… 300 mbar

pre

ss

ure

in m

ab

rg

Ventileinstelldruck mbar

Schließdruck mbar

Valve set pressure mbarg

Valve reseating pressure mbarg

Page 12: Lessons learned solving pilot valve instability issues on LNG storage tanks

12

Important remarks for sizing

• The tank is insulated but your

discharge pipeline may not be

• In the discharge line the cryogenic

gas warms up due to heat input from

environment

• Consider the density changes along

the line when calculating the pressure

losses and the tank relief loads

• Build up your own or use a

commercial package with a reliable

thermo-fluid dynamic model

• Consider the internal piping within

the tank

Tank

HEAT

Page 13: Lessons learned solving pilot valve instability issues on LNG storage tanks

13

Lessons learned during start up/valve testing (3- Pressure Source or Vessel/Equipment and 4- PRV)

The pressure relief system is designed for (e.g.):

• Liquid LNG input

• Thermal outbreathing

• Liquid Displacement and Flashing by filling

• Roll over

• Recirculation from a submerged pump

This design results in very high relief loads and that

means large valves with very high capacities

But what is your testing procedure before start up?

Page 14: Lessons learned solving pilot valve instability issues on LNG storage tanks

14

Example: Nitrogen evaporation procedure

• The tank is just filled with a small amount of liquid

nitrogen, which then evaporates

• Relative to the design case the evaporation rate is very

small

• This results in chattering of the valve due to massive

oversizing

• If this start up/test procedure is used the valve

potentially runs into instability issues through rapidly

relieving and closing

But how can we solve this during start up and assure

that the valves works even though the valve is operated

within a zone that causes instability?

Page 15: Lessons learned solving pilot valve instability issues on LNG storage tanks

15

Testing to extreme condition

and forcing the valve to

operate instable is a must for

understanding the valve

behavior

Solving the instability challenge during start up

Page 16: Lessons learned solving pilot valve instability issues on LNG storage tanks

16

Instabilty Problem: Valve chattering heavily

Page 17: Lessons learned solving pilot valve instability issues on LNG storage tanks

17

Instabilty Solution: Valve with dampening system

Page 18: Lessons learned solving pilot valve instability issues on LNG storage tanks

18

Lesson learned

Challenge:

• Start up with small vaporizing quantities can result in

valve instability

Solution:

• Dampening systems which prevent valve instabilty

Page 19: Lessons learned solving pilot valve instability issues on LNG storage tanks

19

Cryogenic Test showing chattering effect and the

performance of the damping system

Page 20: Lessons learned solving pilot valve instability issues on LNG storage tanks

24

Cryogenic test

Tests according to ISO 21013-4

„Cryogenic vessels – Pilot operated pressure relief devices –

Part 4: Pressure-relief accessories for cryogenic service“.

Page 21: Lessons learned solving pilot valve instability issues on LNG storage tanks

25

PROTEGO PM/HF with Fiel-Test-Connection and Test-Kit

Page 22: Lessons learned solving pilot valve instability issues on LNG storage tanks

26

Oxygen-Cleanliness-Workshop

Washing machines

Oil-free test bench

UV-light Tent for Visual Inspection

Ultra-sonic bath for small pieces

Page 23: Lessons learned solving pilot valve instability issues on LNG storage tanks

27

Vacuum-Breaker for Cryogenic Application

Propylene Storage Tank

Page 24: Lessons learned solving pilot valve instability issues on LNG storage tanks

28

Vacuum-Breaker for Cryogenic Application

Vacuum Breaker installed on Cryogenic Storage Tanks

need to be very tight against leaking!

• Vacuum breaker are exposed to relativley high

over-pressure due to the operating pressure of the

storage tank which works as a closing force to the

valve pallet

Page 25: Lessons learned solving pilot valve instability issues on LNG storage tanks

29

Competitors soft sealing with FEP-foil

Page 26: Lessons learned solving pilot valve instability issues on LNG storage tanks

30

Competitors valve leaks due to exposure to sun

radiation – Visible through IR-camera

Page 27: Lessons learned solving pilot valve instability issues on LNG storage tanks

31

Vacuum-Breaker for Cryogenic Application

PROTEGO has inproved vacuum breakers with setting

at -2,5 mbar / - 1“ WC, metallic sealing and highest possible capacity

Page 28: Lessons learned solving pilot valve instability issues on LNG storage tanks

32

Thank you for your attention

Excellence in Safety and Environment