lighting control 53...univ: 1-16 (16) supernode add: 1 risk of electric shock. disconnect power...

1
1. All consoles, NPU’s, 3d Computers MUST have the same software loaded!. 2. Connected consoles should be used to program to mitigate the risk of the Master console failing during output. 3. Add 1 millisecond to both the Artnet and sACN output ‘delay' fields in "setup/networking/network protocols" 4. sACN protocol field should be set to “FINAL” in ”setup/networking/network protocols" 5. Ethernet Port 1(eth 0) is MA/sACN Net and Ethernet Port 2 (eth 1) is Artnet Only! 6. Spare NPU's are NOT spare if they are plugged in. The MA shares the processor load across all NPU's on the network. Ensure system can operate without spare first, then add spare to network which will take the load if any NPU fails. 7. NPUs generate a high level of network traffic. Use the lowest number of NPUs required for parameter count. 8. Only the Master Console in a session will listen/send sACN/Artnet. 9. DISABLE “Network DMX if Alone” within Network Protocols menu. 10. Priority levels must be set in order to retain station configuration. 11. Artnet data corruption can occur if a previous master and new master are both connected to the Artnet network. 12. Do NOT use RDM in show conditions. DMX data is not reliable while RDM is discovering and may not be compatible with S400. 13. Any MA 3D, onPC, or other MA device that is powered down MUST be physically unplugged from network!! 14. Rob Base Lesson #2...It takes two to make it outta sight! MA2 Special Notes 1. All Fiber Optic runs, regardless of overall length, MUST NOT be made up of more then five lengths of cable 2. NO ETHERCON or CAT5E COUPLERS!! 3. S400 Supernodes should be set to “Merge2” to avoid any conflicts during a system failure. 4. Do NOT use RDM in show conditions. DMX data is not reliable while RDM is discovering If RDM must be used, leave “incremental” unchecked. 5. All VIA 12 switches MUST have the same software loaded and have unique IP addresses 6. All switches should be defaulted inc Network Settings prior to configuration. 7. All VIA 12 Port Speeds should be set to “Auto Negotiate” 8. VLAN = Virtual Local Area Network (VLANS are like groups they only talk to other ports configured as the same VLAN 9. Managment VLAN = 1. 10. When using VLAN’s Ports 11-12 (Cat5e on rear) and Ports 13-14 (Fiber Ports) must be set to TAGGED/UPLINK so as to pass ALL VLAN traffic 10. Rob Base Lesson #1...It takes two to make a thing go right. Important System Notes! Pete V676 PreVis Supernode Add: 5 Supernode Add: 4 Supernode Add: 3 Supernode Add: 2 Supernode Add: 1 7-Port Switch V676 7-Port Switch Artnet LiteConverse Cat 5e (Artnet) PETE’S PREVIS OF PLEASURE LIGHTING CONTROL LAYOUT COUNTS Cat 5e (Artnet) OptiCon Duo Fiber Cat 5e (MA Artnet) KEY Cat5e (V676) SUPERBOWL Halftime LX NETWORK DATE: 1/23/19 0922 SCALE: VISUAL ONLY DRAWN BY: CONTI ©2019 PRG REV E 350’ Limo Fiber x8 Active & Spare VIA12 Switch x22 Active & Spare U506K S400 Rack x7 Active 3838T- VIA MANAGED GIGABIT ETHERNET SWITCH Node Plus x14 Active & Spare 37999- Super Node x22 3799C- 10-Port Switch x11 Active & Spare 3132K- 350’ OptiCon Duo Fiber x4 Active & Spare 600’ OptiCon Duo Fiber x10 Active & Spare Spare OptiCon Duo Fiber 250’ OptiCon Duo Fiber x10 Active & Spare OptiCon Duo Couplers x8 Active & Spare Limo Fiber Cat 5e (MA/ sACN Net) Cat 5e (UPLINK) Spare Limo Fiber FOH Moves Like Jagger Pete V676 Main Univ: 46-55 (10) Supernode Add: 5 Univ: 36-45(10) Supernode Add: 4 Univ: 25-35 (11) Supernode Add: 3 Univ: 17-24 (8) Supernode Add: 2 Univ: 1-16 (16) Supernode Add: 1 VIA VIA12 Gigabit Switch IP Add: 10.66.201.001 VIA Session ID: 1 SBLII SPARE grandMA 2 Lite: Jason MAIN (High) eth0 Add: 192.168.0.1 eth1 Add: 10.66.0.1 Pete V676 Backup Cat 5e (v676) Node Plus FILTER (S400 Mode) Add:11 Univ: 98,99,x,x,x,x grandMA 2 Lite: PYRO MAIN (High) eth0 Add: 192.168.0.201 eth1 Add: 10.66.0.201 grandMA 2 Lite: Jason SPARE (Normal) eth0 Add: 192.168.0.2 eth1 Add: 10.66.0.2 VIA12 Gigabit Switch IP Add: 10.66.201.002 VIA S400 Tools IP Add:10.66.200.1 Cat 5e (Artnet) 10-Port Switch VIA12 Gigabit Switch IP Add: 10.66.248.001 VIA12 Gigabit Switch IP Add: 10.66.248.002 VIA SPARE Cat 5e (MA Artnet) VIA12 Gigabit Switch IP Add: 10.66.201.003 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 VIA12 Gigabit Switch IP Add: 10.66.248.003 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA Artnet Ports 6-10 UPLINK: All Data Ports 11-14 SPARE CATWALK SWITCHES SUITES & 200 LEVEL SWITCHES FIELD SWITCHES West Truss Cat 5e (Artnet) Univ: 56-64 (9) Supernode Add: 6 Cat 5e (v676) Cat 5e (v676) Cat 5e (v676) Cat 5e (Artnet) Cat 5e (Artnet) 10-Port Switch Cat 5e (Artnet) VIA VIA Hippo 1: 192.168.0.31 Artnet IP: 10.66.0.31 IP Add: 192.168.0.11 NPU #1 IP Add: 192.168.0.12 NPU #2 IP Add: 192.168.0.13 NPU #3 NW-DSL Field Rack Univ: 47,48,53,x,x,x,98,99 Addr: 711 Supernode (S400 Mode) Cat 5e (Artnet) VIA12 Gigabit Switch IP Add: 10.66.207.011 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 VIA Supernode (S400 Mode) VIA12 Gigabit Switch IP Add: 10.66.247.011 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 VIA Cat 5e (Artnet) NE-DSR Field Rack Univ: 52,x,x,x,x,x,98,99 Addr: 721 Supernode (S400 Mode) Cat 5e (Artnet) Univ: 52,x,x,x,x,x,x,98,99 VIA12 Gigabit Switch IP Add: 10.66.207.021 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 VIA Addr: 722 Supernode (S400 Mode) VIA12 Gigabit Switch IP Add: 10.66.247.021 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 VIA Cat 5e (Artnet) Pathfinder IP Add: 192.168.0.51 SE-USR Field Rack Univ: 40,41,46,47,48,52,x,x Addr: 735 Supernode (S400 Mode) Univ: 56,57,58,59,36,37,38,39 VIA12 Gigabit Switch IP Add: 10.66.207.031 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 Addr: 734 Supernode (S400 Mode) VIA12 Gigabit Switch IP Add: 10.66.247.031 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 VIA Univ: 40,41,46,47,48,52,x,x Addr: 732 Supernode (S400 Mode) Supernode (S400 Mode) VIA Univ: 56,57,58,59,36,37,38,39 Addr: 731 SW-USL Field Rack Univ: 49,50,51,53,x,x,98,99 Addr: 744 Supernode (S400 Mode) VIA12 Gigabit Switch IP Add: 10.66.207.041 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 Addr: 743 Supernode (S400 Mode) VIA12 Gigabit Switch IP Add: 10.66.247.041 VLAN 1: V676 Artnet Ports 1-5 VLAN 2: MA/sACN ports 6-10 UPLINK: All Data Ports 11-14 VIA Cat 5e (Artnet) Addr: 742 Supernode (S400 Mode) Supernode (S400 Mode) VIA Cat 5e (Artnet) Univ: 60,61,62,63,42,43,44,45 Addr: 741 CART #25 S400 Rack 111 S400 Rack 121 VIA12 Gigabit Switch IP Add: 10.66.207.111 VLAN 1: V676 Artnet Ports 1-10 UPLINK: All Data Ports 11-14 VIA12 Gigabit Switch IP Add: 10.66.247.111 VLAN 1: V676 Artnet Ports 1-10 UPLINK: All Data Ports 11-14 SPARE VIA VIA S400 Rack 211 North Truss VIA VIA12 Gigabit Switch IP Add: 10.66.201.021 VIA VIA12 Gigabit Switch IP Add: 10.66.248.021 SPARE East Truss S400 Rack 421 South Truss S400 Rack 411 Cat 5e (Artnet) 214 Rackland SPARE Univ: 31,33,35,x,x,x VIA12 Gigabit Switch IP Add: 10.66.202.011 VIA Node Plus (S400 Mode) Add:222 Univ: 31,33,35,x,x,x Node Plus (S400 Mode) Add:221 Univ: 28,29,x,x,x,x Cat 5e (Artnet) VIA12 Gigabit Switch IP Add: 10.66.248.211 VIA Node Plus (S400 Mode) Add:224 Node Plus (S400 Mode) Add:223 Cat 5e (Artnet) SPARE Univ: 28,29,x,x,x,x, SPARE SPARE SPARE SPARE SPARE 208 Rackland SPARE Univ: 30,31,32,x,x,x VIA12 Gigabit Switch IP Add: 10.66.202.012 VIA Node Plus (S400 Mode) Add:232 Univ: 30,31,32,x,x,x Node Plus (S400 Mode) Add:231 Univ: 25,26,27,x,x,x Cat 5e (Artnet) VIA12 Gigabit Switch IP Add: 10.66.248.212 VIA Node Plus (S400 Mode) Add:234 Node Plus (S400 Mode) Add:233 Cat 5e (Artnet) SPARE Univ: 25,26,27,x,x,x SPARE Cat 5e (UPLINK) Cat 5e (UPLINK) Cat 5e (UPLINK) TO FIELD TO SUITES & 200 Level TO CATWALK CATWALK FIBER 1200’ OptiCON Duo Fiber x 2 (4 x 600’ + 2 x Coupler) FIELD FIBER 950’ OptiCON Duo Fiber x 3 (3 x 600’ + 3 x 350’ + 3 x Coupler) 600’ OptiCON Duo Fiber x 2 (2 x 600’ ) 250’ OptiCON Duo Fiber x 2 (2 x 250’ ) 250’ OptiCON Duo Fiber x 2 (2 x 250’ ) 250’ OptiCON Duo Fiber x 2 (2 x 250’ ) 350’ OptiCON Duo Fiber x 2 (2 x 350’ ) 550’ Limo Fiber x 2 (2 x 350’+ 2 x 200’ ) Univ: 47,48,53,x,x,x,98,99 Addr: 712 Univ: 98,99,x,x,x,x Node Plus Add: 733 Univ: 98,99,x,x,x,x Node Plus Add: 736 Cat 5e (Artnet) Cat 5e (Artnet) SPARE SPARE SPARE Univ: 49,50,51,53,x,x,98,99 Univ: 60,61,62,63,42,43,44,45 SPARE SPARE SPARE SPARE Univ: 103,106,109,112,145,124,136 Univ:103,106,109,112,145,124,136 Node Plus Add: 803 Univ: 98,99,x,x,x,x Node Plus Add: 806 SPARE Univ: 98,99,x,x,x,x Addr: 804 Supernode (S400 Mode) 114/134 113/135 110/111 107/108 104/105 101/102 115/139 116/140 116/141 117/141 120/134 121/135 122/125 125/126 128/129 131/132 119/138 119/142 118/144 117/147 Supernode (S400 Mode) Addr: 801 S400 Tools IP Add:10.66.200.2 SUITES & 200 LEVEL FIBER 1250’ OptiCON Duo Fiber x 2 2 x 1000’ + 2 x 250’+ 2 x Coupler) PROGRAMING FIBER 350’ Limo Fiber x 2 (2 x 350’) 1000’ OptiCon Duo Fiber x2 Active & Spare Pete’s Programing Position of Sugar Supernode Add: 6 Cat 5e (v676) Cat 5e (Artnet) IP Add: 10.66.0.41 grandMA 3D IP Add: 192.168.0.3 Univ 12/x 12/x 13/x 13/x 14/x 14/x 20/x 21/x x/x x/x Univ 1/x 1/x 2/x 2/x 3/x 3/x 4/x 4/x x/x x/x Univ 6/x 6/x 7/x 8/x x/x x/x x/x x/x x/x x/x S400 Rack 511 Univ 9/x 9/x 10/x 11/x 11/x 18/x 19/x x/x x/x x/x 10-Port Switch 10-Port Switch Cat 5e (Artnet) Cat 5e (Artnet) SPARE 10-Port Switch S400 Rack 311 Cat 5e (Artnet) Univ 15/x 15/x 16/x 17/x x/x x/x x/x x/x x/x x/x 10-Port Switch 10-Port Switch SPARE 10-Port Switch 10-Port Switch SPARE 10-Port Switch 550’ Limo Fiber x 2 (2 x 350’+ 2 x 200’ ) 550’ Limo Fiber x 2 (2 x 350’+ 2 x 200’ ) CISCO SG112 Gigabit Switch IP Add: 192.168.101.2 Hippo 2: 192.168.0.32 Artnet IP: 10.66.0.32 IP Add: 192.168.0.21 NPU #4 IP Add: 192.168.0.22 NPU #5 IP Add: 192.168.0.23 NPU #6 CISCO SG112 Gigabit Switch IP Add: 192.168.101.1 Cat 5e (MA/sACN Net) Pathfinder IP Add: 192.168.0.42 Pathfinder IP Add: 192.168.0.41 Cat 5e (MA/sACN Net) Cat 5e (MA/sACN Net) Pathfinder IP Add: 192.168.0.52 200’ Limo Fiber x8 Active & Spare Univ: 127,130,133,145,146, Addr: 802 Supernode (S400 Mode) Cat 5e (MA/sACN Net) Addr: 805 Supernode (S400 Mode) Univ:127,130,133,145,146 Cat 5e (Artnet) Cat 5e (MA/sACN Net) Cat 5e (Artnet) Cat 5e (MA/sACN Net) Glow Motion IP Add: 192.168.0.53

Upload: others

Post on 28-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LIGHTING CONTROL 53...Univ: 1-16 (16) Supernode Add: 1 Risk of electric shock. Disconnect power before opening. Risque de decharge electrique Debrancher le pouvoir avant d'ouvrier

1. All consoles, NPU’s, 3d Computers MUST have the same software loaded!. 2. Connected consoles should be used to program to mitigate the risk of the Master console failing during output. 3. Add 1 millisecond to both the Artnet and sACN output ‘delay' fields in "setup/networking/network protocols"4. sACN protocol field should be set to “FINAL” in ”setup/networking/network protocols"5. Ethernet Port 1(eth 0) is MA/sACN Net and Ethernet Port 2 (eth 1) is Artnet Only!6. Spare NPU's are NOT spare if they are plugged in. The MA shares the processor load across all NPU's on the network. Ensure system can operate without spare first, then add spare to network which will take the load if any NPU fails.7. NPUs generate a high level of network traffic. Use the lowest number of NPUs required for parameter count. 8. Only the Master Console in a session will listen/send sACN/Artnet. 9. DISABLE “Network DMX if Alone” within Network Protocols menu. 10. Priority levels must be set in order to retain station configuration. 11. Artnet data corruption can occur if a previous master and new master are both connected to the Artnet network.12. Do NOT use RDM in show conditions. DMX data is not reliable while RDM is discovering and may not be compatible with S400.13. Any MA 3D, onPC, or other MA device that is powered down MUST be physically unplugged from network!!14. Rob Base Lesson #2...It takes two to make it outta sight!

MA2 Special Notes

1. All Fiber Optic runs, regardless of overall length, MUST NOT be made up of more then five lengths of cable2. NO ETHERCON or CAT5E COUPLERS!!3. S400 Supernodes should be set to “Merge2” to avoid any conflicts during a system failure. 4. Do NOT use RDM in show conditions. DMX data is not reliable while RDM is discovering If RDM must be used, leave “incremental” unchecked. 5. All VIA 12 switches MUST have the same software loaded and have unique IP addresses6. All switches should be defaulted inc Network Settings prior to configuration. 7. All VIA 12 Port Speeds should be set to “Auto Negotiate” 8. VLAN = Virtual Local Area Network (VLANS are like groups they only talk to other ports configured as the same VLAN9. Managment VLAN = 1.10. When using VLAN’s Ports 11-12 (Cat5e on rear) and Ports 13-14 (Fiber Ports) must be set to TAGGED/UPLINK so as to pass ALL VLAN traffic10. Rob Base Lesson #1...It takes two to make a thing go right.

Important System Notes!

Pete V676 PreVis

Supernode Add: 5

Supernode Add: 4

Supernode Add: 3

Supernode Add: 2

Supernode Add: 1

7-Port Switch V676

7-Port Switch Artnet

LiteConverse

Cat 5e (Artnet)

PETE’S PREVISOF PLEASURE

LIGHTING CONTROL LAYOUT

COUNTS

Cat 5e (Artnet)

OptiCon DuoFiber

Cat 5e(MA Artnet)

KEY

Cat5e(V676)

SUPERBOWL Halftime

LX NETWORK

DATE: 1/23/19 0922 SCALE: VISUAL ONLY

DRAWN BY: CONTI ©2019 PRG

REV E

350’ Limo Fiberx8 Active & Spare

VIA12 Switchx22 Active & SpareU506K

S400 Rackx7 Active 3838T-

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

NodePlusx14 Active & Spare37999-

SuperNodex223799C-

10-PortSwitchx11 Active & Spare3132K-

350’ OptiCon Duo Fiberx4 Active & Spare

600’ OptiCon Duo Fiberx10 Active & Spare

Spare OptiCon DuoFiber

250’ OptiCon Duo Fiberx10 Active & Spare

OptiCon Duo Couplersx8 Active & Spare

Limo Fiber

Cat 5e(MA/ sACN Net)

Cat 5e (UPLINK)

SpareLimo Fiber

FOH MovesLike Jagger

Pete V676 Main

Univ: 46-55 (10)

Supernode Add: 5

Univ: 36-45(10)

Supernode Add: 4

Univ: 25-35 (11)

Supernode Add: 3

Univ: 17-24 (8)

Supernode Add: 2

Univ: 1-16 (16)

Supernode Add: 1

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

VIA12 Gigabit SwitchIP Add: 10.66.201.001

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

SessionID: 1 SBLII

SPARE

grandMA 2 Lite: JasonMAIN (High)eth0 Add: 192.168.0.1eth1 Add: 10.66.0.1

Pete V676 Backup

Cat 5e (v676)

Node Plus FILTER

(S400 Mode)Add:11

Univ: 98,99,x,x,x,x

grandMA 2 Lite: PYRO MAIN (High)eth0 Add: 192.168.0.201eth1 Add: 10.66.0.201

grandMA 2 Lite: JasonSPARE (Normal)eth0 Add: 192.168.0.2eth1 Add: 10.66.0.2

VIA12 Gigabit SwitchIP Add: 10.66.201.002

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

S400 ToolsIP Add:10.66.200.1

Cat 5e (Artnet)

10-Port Switch

VIA12 Gigabit SwitchIP Add: 10.66.248.001

VIA12 Gigabit SwitchIP Add: 10.66.248.002

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

SPARE

Cat 5e (MA Artnet)

VIA12 Gigabit SwitchIP Add: 10.66.201.003VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14 VIA12 Gigabit Switch

IP Add: 10.66.248.003VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA Artnet Ports 6-10UPLINK: All Data Ports 11-14

SPARE

CATWALK SWITCHES

SUITES & 200 LEVEL SWITCHES

FIELD SWITCHES

West Truss

Cat 5e (Artnet)

Univ: 56-64 (9)

Supernode Add: 6

Cat 5e (v676)

Cat 5e (v676)

Cat 5e (v676)

Cat 5e (Artnet)

Cat 5e (Artnet)

10-Port Switch

Cat 5e (Artnet)

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Hippo 1: 192.168.0.31Artnet IP: 10.66.0.31

IP Add: 192.168.0.11NPU #1

IP Add: 192.168.0.12NPU #2

IP Add: 192.168.0.13

NPU #3

NW-DSL Field Rack

Univ: 47,48,53,x,x,x,98,99

Addr: 711Supernode (S400 Mode)

Cat 5e (Artnet)

VIA12 Gigabit SwitchIP Add: 10.66.207.011VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Supernode (S400 Mode)

VIA12 Gigabit SwitchIP Add: 10.66.247.011VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Cat 5e (Artnet)

NE-DSR Field Rack

Univ: 52,x,x,x,x,x,98,99

Addr: 721Supernode (S400 Mode)

Cat 5e (Artnet)

Univ: 52,x,x,x,x,x,x,98,99

VIA12 Gigabit SwitchIP Add: 10.66.207.021VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Addr: 722Supernode (S400 Mode)

VIA12 Gigabit SwitchIP Add: 10.66.247.021VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Cat 5e (Artnet)

PathfinderIP Add: 192.168.0.51

SE-USR Field Rack

Univ: 40,41,46,47,48,52,x,x

Addr: 735Supernode (S400 Mode)

Univ: 56,57,58,59,36,37,38,39

VIA12 Gigabit SwitchIP Add: 10.66.207.031VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14

Addr: 734Supernode (S400 Mode)

VIA12 Gigabit SwitchIP Add: 10.66.247.031VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Univ: 40,41,46,47,48,52,x,x

Addr: 732Supernode (S400 Mode)Supernode (S400 Mode)

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Univ: 56,57,58,59,36,37,38,39

Addr: 731

SW-USL Field Rack

Univ: 49,50,51,53,x,x,98,99

Addr: 744Supernode (S400 Mode)

VIA12 Gigabit SwitchIP Add: 10.66.207.041VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14

Addr: 743Supernode (S400 Mode)

VIA12 Gigabit SwitchIP Add: 10.66.247.041VLAN 1: V676 Artnet Ports 1-5VLAN 2: MA/sACN ports 6-10UPLINK: All Data Ports 11-14

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Cat 5e (Artnet)

Addr: 742Supernode (S400 Mode)Supernode (S400 Mode)

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Cat 5e (Artnet)

Univ: 60,61,62,63,42,43,44,45

Addr: 741

CART #25

S400 Rack 111 S400 Rack 121

VIA12 Gigabit SwitchIP Add: 10.66.207.111VLAN 1: V676 Artnet Ports 1-10UPLINK: All Data Ports 11-14

VIA12 Gigabit SwitchIP Add: 10.66.247.111VLAN 1: V676 Artnet Ports 1-10UPLINK: All Data Ports 11-14

SPARERisk of electric shock.

Disconnect powerbefore opening.

Risque de dechargeelectrique. Debrancher

le pouvoir avantd'ouvrier.

90-260VAC.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

S400 Rack 211

North Truss

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

VIA12 Gigabit SwitchIP Add: 10.66.201.021

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

VIA12 Gigabit SwitchIP Add: 10.66.248.021

SPARE

East Truss

S400 Rack 421

South Truss

S400 Rack 411

Cat 5e (Artnet)

214 Rackland

SPARE Univ: 31,33,35,x,x,x

VIA12 Gigabit SwitchIP Add: 10.66.202.011

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Node Plus (S400 Mode)

Add:222

Univ: 31,33,35,x,x,x

Node Plus (S400 Mode)

Add:221

Univ: 28,29,x,x,x,x

Cat 5e (Artnet)

VIA12 Gigabit SwitchIP Add: 10.66.248.211

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Node Plus (S400 Mode)

Add:224

Node Plus (S400 Mode)

Add:223

Cat 5e (Artnet)

SPARE Univ: 28,29,x,x,x,x,

SPARE

SPARESPARE

SPARE SPARE

208 Rackland

SPARE Univ: 30,31,32,x,x,x

VIA12 Gigabit SwitchIP Add: 10.66.202.012

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Node Plus (S400 Mode)

Add:232

Univ: 30,31,32,x,x,x

Node Plus (S400 Mode)

Add:231

Univ: 25,26,27,x,x,x

Cat 5e (Artnet)

VIA12 Gigabit SwitchIP Add: 10.66.248.212

Risk of electric shock.Disconnect power

before opening.Risque de decharge

electrique. Debrancherle pouvoir avant

d'ouvrier.90-260VAC

.75A 50/60 Hz

ATTENTION

48VDC PoE INPUT200W MAX

AC THRUMAX 10A

VIAMANAGED GIGABIT

POELINK/ACT

ETHERNET SWITCH

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10

Node Plus (S400 Mode)

Add:234

Node Plus (S400 Mode)

Add:233

Cat 5e (Artnet)

SPARE Univ: 25,26,27,x,x,x

SPARE

Cat 5e (UPLINK)

Cat 5e (UPLINK)

Cat 5e (UPLINK)

TO FIELD TO SUITES & 200 Level

TO CATWALK

CATWALK FIBER1200’ OptiCON Duo Fiber x 2

(4 x 600’ + 2 x Coupler)

FIELD FIBER950’ OptiCON Duo Fiber x 3

(3 x 600’ + 3 x 350’ + 3 x Coupler)

600’

Opt

iCO

N D

uo F

iber

x 2

(2 x

600

’ )

250’ OptiCON Duo Fiber x 2(2 x 250’ )

250’ OptiCON Duo Fiber x 2(2 x 250’ )

250’ OptiCON Duo Fiber x 2(2 x 250’ )

350’ OptiCON Duo Fiber x 2(2 x 350’ )

550’ Limo Fiber x 2(2 x 350’+ 2 x 200’ )

Univ: 47,48,53,x,x,x,98,99

Addr: 712

Univ: 98,99,x,x,x,x

Node Plus Add: 733

Univ: 98,99,x,x,x,x

Node Plus Add: 736

Cat 5e (Artnet)Cat 5e (Artnet)

SPARESPARE

SPARE

Univ: 49,50,51,53,x,x,98,99Univ: 60,61,62,63,42,43,44,45SPARE SPARE

SPARESPARE

Univ: 103,106,109,112,145,124,136Univ:103,106,109,112,145,124,136

Node Plus Add: 803

Univ: 98,99,x,x,x,x

Node Plus Add: 806

SPARE Univ: 98,99,x,x,x,x

Addr: 804Supernode (S400 Mode) 114/134

113/135110/111107/108104/105101/102115/139116/140116/141117/141

120/134121/135122/125125/126128/129131/132119/138119/142118/144117/147

Supernode (S400 Mode)Addr: 801

S400 ToolsIP Add:10.66.200.2

SUITES & 200 LEVEL FIBER1250’ OptiCON Duo Fiber x 2

2 x 1000’ + 2 x 250’+ 2 x Coupler)

PROGRAMING FIBER350’ Limo Fiber x 2

(2 x 350’)

1000’ OptiCon Duo Fiberx2 Active & Spare

Pete’s ProgramingPosition of Sugar

Supernode Add: 6

Cat 5e (v676)

Cat 5e (Artnet)

IP Add: 10.66.0.41

grandMA 3D IP Add: 192.168.0.3

Univ12/x12/x13/x13/x14/x14/x20/x21/xx/xx/x

Univ1/x1/x2/x2/x3/x3/x4/x4/xx/xx/x

Univ6/x6/x7/x8/xx/xx/xx/xx/xx/xx/x

S400 Rack 511Univ9/x9/x

10/x11/x11/x18/x19/xx/xx/xx/x

10-Port Switch

10-Port Switch

Cat 5e (Artnet)Cat 5e (Artnet)

SPARE

10-Port Switch

S400 Rack 311

Cat 5e (Artnet)

Univ15/x15/x16/x17/xx/xx/xx/xx/xx/xx/x

10-Port Switch

10-Port SwitchSPARE

10-Port Switch

10-Port Switch

SPARE

10-Port Switch

550’ Limo Fiber x 2(2 x 350’+ 2 x 200’ )

550’ Limo Fiber x 2(2 x 350’+ 2 x 200’ )

CISCO SG112 Gigabit SwitchIP Add: 192.168.101.2

Hippo 2: 192.168.0.32Artnet IP: 10.66.0.32

IP Add: 192.168.0.21NPU #4

IP Add: 192.168.0.22NPU #5

IP Add: 192.168.0.23

NPU #6

CISCO SG112 Gigabit SwitchIP Add: 192.168.101.1

Cat 5e

(MA/sAC

N N

et)

PathfinderIP Add: 192.168.0.42

PathfinderIP Add: 192.168.0.41

Cat 5e (MA/sACN Net)Cat 5e (MA/sACN Net)

PathfinderIP Add: 192.168.0.52

200’ Limo Fiberx8 Active & Spare

Univ: 127,130,133,145,146,

Addr: 802Supernode (S400 Mode)

Cat 5e(MA/sACN Net)

Addr: 805Supernode (S400 Mode)

Univ:127,130,133,145,146

Cat 5e(Artnet)

Cat 5e(MA/sACN Net)

Cat 5e(Artnet)

Cat 5e(MA/sACN Net)

Glow MotionIP Add: 192.168.0.53